This document provides details on a federal contract opportunity and related project drawings. The solicitation is for the construction of Vehicle Storage Building No. 4 at the Bismarck Operations and Maintenance Service Center in Bismarck, North Dakota. Solicitation number 89503420BWA000020 was issued by the Department of Energy's Western Area Power Administration to construct the storage building. Project drawings file 05. BSM Project Drawings.pdf is related to this federal contract opportunity to build the new vehicle storage facility. Interested parties should review the solicitation and drawings for full requirements and response details.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BUILDING NO. 4
NORTH DAKOTA
SECTION C
DESCRIPTION/SPECIFICATIONS
Solicitation No. 89503420BWA000020 Spec. No. 20WC136420-996
BISMARCK O&M SERVICE CENTER
VEHICLE STORAGE BUILDING NO. 4
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION DRAW INGS: Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale. Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: W here details shown on standard drawings included herein differ from construction or project drawings or text, the details of construction or project drawings or text shall govern. A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise Western Area Power Administration of any errors or omission.
B. LIST OF DRAWINGS:
General:
1. BSM G-001 – Cover Sheet
2. BSM G-002 – Sheet Index
Life Safety Sheet List:
3. BSM LS101 – Life Safety Code and Criteria
4. BSM LS102 – Overall Life Safety Plan
Civil Sheet List:
5. BSM C-001 – General Civil Notes
6. BSM C-002 – Legend & Abbreviations
7. BSM C-003 – Survey Control Plan
8. BSM C-004 – Access & Safety Plan
9. BSM CD-001 – Demolition Plan
10. BSM CS-001 – Civil Site Plan
11. BSM CS-002 – Civil Point Control Plan
12. BSM CS-003 – Civil Point Control Table
13. BSM CU-001 – Civil Utility Plan
14. BSM CG-001 – Civil Grading Plan
15. BSM CG-002 – Erosion & Sediment Control Plan
16. BSM C-500 – Civil Site Details I
17. BSM C-501 – Civil Site Details II
18. BSM C-502 – Civil Site Details III
19. BSM C-503 – Civil Site Details IV
Architecture Sheet List:
20. BSM AG001 – Architectural Legend & Abbreviations
21. BSM AG002 – Architectural General Notes
22. BSM A-101 – Ground Floor Plan
23. BSM A-120 – Overall Roof Plan
24. BSM A-121 – Roof Drainage System Sizing
25. BSM A-150 – Reflected Ceiling Plan
26. BSM A-201 – Exterior Building Excavations
27. BSM A-301 – Building Sections
28. BSM A-311 – Wall Sections
29. BSM A-551 – ADA and General Mounting Height Information
30. BSM A-581 – Roof & Wall Penetration Details
31. BSM A-582 – Roof & Wall Details
32. BSM A-600 – Door, Window & Louvre Details
33. BSM A-601 – Door Schedule, Frames, Types, Hardware Sets, Room Finish Schedule and Finish
Legend https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx http://www.wapa.gov/business/buys.htm
Structural Sheet List:
34. BSM S001 – General Notes Sheet I
35. BSM S002 – Special Inspections Sheet I
36. BSM S003 – Special Inspections Sheet II
37. BSM S004 – Standard Concrete Notes and Details I
38. BSM S005 – Standard Concrete Notes and Details II
39. BSM S006 – Standard Concrete Notes and Details III
40. BSM S050 – Foundation Plan
41. BSM S100 – Overall Slab Plan
42. BSM S101 – Slab Joint Plan
43. BSM S201 – Foundation Sections & Details
44. BSM S202 – Building Sections & Details I
45. BSM S203 – Building Sections & Details II
Mechanical Sheet List:
46. BSM M000 – Mechanical General Notes, Symbols, and Abbreviations
47. BSM M101- Mechanical Plan
48. BSM M500 – Mechanical Details I
49. BSM M501 – Mechanical Details II
50. BSM M502 – Mechanical Details III
51. BSM M600 – Mechanical Schedules I
52. BSM M601 – Mechanical Schedules II
53. BSM M700 – Mechanical Controls
54. BSM MP100 – Mechanical Underground Piping Plan
55. BSM MP101 – Mechanical Above Ground Piping Plan
Plumbing Sheet List:
56. BSM P000 – Plumbing General Notes, Symbols, and Abbreviations
57. BSM P100 – Plumbing Underground Plan
58. BSM P101 – Plumbing Aboveground Plan
59. BSM P500 – Plumbing Details
60. BSM P600 – Plumbing Schedule
61. BSM P700 – Plumbing Riser Diagram
Fire Alarm Sheet List:
62. BSM FA001 – Fire Alarm Notes, Legend, Abbreviations
63. BSM FA101 – Fire Alarm Floor Plan
64. BSM FA601 – Fire Alarm One Line Diagram and Matrix
Fire Suppression Sheet List:
65. BSM FX001 – Fire Suppression Notes, Legend and Abbreviations
66. BSM FX101 – Fire Suppression Floor Plan
Electrical Sheet List:
67. BSM E-001 – Electrical Legend
68. BSM E-501 – Electrical Details
69. BSM EG101 – Grounding Plan
70. BSM EL101 – Lighting Plan
71. BSM EP101 – Power Plan
72. BSM EP601 – One-Line Diagram
73. BSM EP701 – Panelboard Schedules
74. BSM ES101 – Electrical
PROJECT DESCRIPTION:
APPROXIMATELY 9,000 SF PRE-ENGINEERED METAL BUILDING (109' X 80') TO
HOUSE SIX (6) DRIVE-THRU VEHICLE BAYS. FACILITY IS TO BE UTILIZED AS
A VEHICLE STORAGE FACILITY WITH NO OCCUPIABLE SPACE SUCH AS
STORAGE OR OFFICE AND HAS NO RESTROOM.
THONG C.
KHO
57834
R E
G I
S
T E
R E D A R C H
I T
E C
T
A
R I Z O N A U . S
. A
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
R E
G I
S
T E
R E D A R C H
I T
E C
T
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
A
R I Z O N A U . S
. A
Expires 06/30/23
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
7/2/20
G-001JULY 2 2020
COVER SHEET
TCK PJV
WAPA - BISMARCK O & M SERVICE CENTER
BURLEIGH COUNTY
BISMARCK, NORTH DAKOTA
ARCHITECTURE, CIVIL, MECHANICAL, PLUMBING,
ELECTRICAL, FIRE, STRUCTURAL
Issued for Construction
DATE: 7/2/20 BURNS & McDONNELL
9785 MAROON CIRCLE, SUITE 400
CENTENNIAL, CO 80112
TEL: 720-592-3451
ARCHITECTURE, CIVIL, MECHANICAL, PLUMBING,
ELECTRICAL, FIRE, STRUCTURAL
PROJECT TEAM
VEHICLE STORAGE BLDG N0. 4
B 6/23/20 90% DESIGN SUBMITTAL
0 7/2/20 ISSUED FOR CONSTRUCTION
THONG C.
KHO
57834
R E
G I
S
T E
R E D A R C H
I T
E C
T
A
R I Z O N A U . S
. A
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
R E
G I
S
T E
R E D A R C H
I T
E C
T
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
A
R I Z O N A U . S
. A
Expires 06/30/23
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
7/2/20
G-002JULY 2 2020
SHEET INDEX
TCK PJV
ARCHITECTURE SHEET LIST
20 AG001 ARCHITECTURAL LEGEND & ABBREVIATIONS 0
21 AG002 ARCHITECTURAL GENERAL NOTES 0
22 A-101 GROUND FLOOR PLAN 0
23 A-120 OVERALL ROOF PLAN 1
24 A-121 ROOF DRAINAGE SYSTEM SIZING 1
25 A-150 REFLECTED CEILING PLAN 0
26 A-201 EXTERIOR BUILDING ELEVATIONS 1
27 A-301 BUILDING SECTIONS 1
28 A-311 WALL SECTIONS 1
29 A-551 ADA AND GENERAL MOUNTING HEIGHT INFORMATION 0
30 A-581 ROOF & WALL PENETRATION DETAILS 0
31 A-582 ROOF & WALL DETAILS 0
32 A-600 DOOR, WINDOW & LOUVRE DETAILS 0
33 A-601 DOOR SCHEDULE, FRAMES , TYPES , HARDWARE SETS,
ROOM FINISH SCHEDULE AND FINISH LEGEND
LIFE SAFETY SHEET LIST
3 LS101 LIFE SAFETY CODE AND CRITERIA 0
4 LS102 OVERALL LIFE SAFETY PLAN 0
GENERAL SHEET LIST
Sheet Order
Sheet Number Sheet Name
Current Revision
1 G-001 COVER SHEET 0
2 G-002 SHEET INDEX 1
ELECTRICAL SHEET LIST
67 E-001 ELECTRICAL LEGEND 0
68 E-501 ELECTRICAL DETAILS 0
69 EG101 GROUNDING PLAN 0
70 EL101 LIGHTING PLAN 0
71 EP101 POWER PLAN 0
72 EP601 ONE-LINE DIAGRAM 0
73 EP701 PANELBOARD SCHEDULES 0
74 ES101 ELECTRICAL SITE PLAN 0
PLUMBING SHEET LIST
56 P000 PLUMBING GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS 0
57 P100 PLUMBING UNDERGOUND PLAN 0
58 P101 PLUMBING ABOVEGROUND PLAN 0
59 P500 PLUMBING DETAILS 0
60 P600 PLUMBING SCHEDULES 0
61 P700 PLUMBING RISER DIAGRAM 0
MECHANICAL SHEET LIST
Sheet Order
Sheet Number Sheet Name
Current Revision
46 M000 MECHANICAL GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS
47 M101 MECHANICAL PLAN 0
48 M500 MECHANICAL DETAILS I 0
49 M501 MECHANICAL DETAILS II 0
50 M502 MECHANICAL DETAILS III 0
51 M600 MECHANCAL SCHEDULES I 0
52 M601 MECHANICAL SCHEDULES II 0
53 M700 MECHANICAL CONTROLS 0
54 MP100 MECHANICAL UNDERGROUND PIPING PLAN 0
55 MP101 MECHANICAL ABOVE GROUND PIPING PLAN 0
FIRE ALARM SHEET LIST
FA001 FIRE ALARM NOTES, LEGEND, AND ABBREVIATIONS 0
FA101 FIRE ALARM FLOOR PLAN 0
FA601 FIRE ALARM ONE-LINE DIAGRAM AND MATRIX 0
FIRE SUPPRESSION SHEET LIST
FX001 FIRE SUPPRESSION NOTES, LEGEND AND ABBREVIATIONS 0
FX101 FIRE SUPPRESSION FLOOR PLAN 0
STRUCTURAL SHEET LIST
S001 GENERAL NOTES SHEET I 0
S002 SPECIAL INSPECTIONS SHEET I 0
S003 SPECIAL INSPECTIONS SHEET II 0
S004 STANDARD CONCRETE NOTES AND DETAILS I 0
S005 STANDARD CONCRETE NOTES AND DETAILS II 0
S006 STANDARD CONCRETE NOTES AND DETAILS III 0
S050 FOUNDATION PLAN 0
S100 OVERALL SLAB PLAN 0
S101 SLAB JOINT PLAN 0
S201 FOUNDATION SECTIONS & DETAILS 0
S202 BUILDING SECTIONS & DETAILS I 0
S203 BUILDING SECTIONS & DETAILS II 0
CIVIL SHEET LIST
5 C-001 GENERAL CIVIL NOTES 0
6 C-002 LEGEND AND ABBREVIATIONS 0
7 C-003 SURVEY CONTROL PLAN 0
8 C-004 ACCESS & SAFETY PLAN 0
9 CD-001 DEMOLITION PLAN 0
10 CS-001 CIVIL SITE PLAN 0
11 CS-002 CIVIL POINT CONTROL PLAN 0
12 CS-003 CIVIL POINT CONTROL TABLE 0
13 CU-001 CIVIL UTILITY PLAN 0
14 CG-001 CIVIL GRADING PLAN 0
15 CG-002 EROSION & SEDIMENT CONTROL PLAN 0
16 C-500 CIVIL SITE DETAILS I 0
17 C-501 CIVIL SITE DETAILS II 0
18 C-502 CIVIL SITE DETAILS III 0
19 C-503 CIVIL SITE DETAILS III 0
B 6/23/20 90% DESIGN SUBMITTAL
0 7/2/20 ISSUED FOR CONSTRUCTION
1 7/9/20 REV 1
57834
R E
G I
S
T E
R E D A R C H
I T
E C
T
A
R I Z O N A U . S
. A
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
R E
G I
S
T E
R E D A R C H
I T
E C
T
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
A
R I Z O N A U . S
. A
Expires 06/30/23
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
7/2/20
LS1017/1/20
LIFE SAFETY CODE AND CRITERIA
TC KHO Approver
1. APPLICABLE CODES AND STANDARDS
ABBREVIATIONS TITLE EDITION
IBC INTERNATIONAL BUILDING CODE 2018
IMC INTERNATIONAL MECHANICAL CODE 2018
IECC INTERNATIONAL ENERGY CONSERVATION CODE 2018
IFC INTERNATIONAL FIRE CODE 2018
IFC INTERNATIONAL FUEL CODE 2018
NEC UNIFORM ELETRICAL CODE AND NORTH DAKOTA STATE WIRING STANDRADS ADOPTED
BY THE NORTH DAKOTA STATE OF ELECTRICAL BOARD
UPC UNIFORM PLUMBING CODE AND NORTH DAKOTA STATE PLUMBING STANDARDS ADOPTED
BY THE NORTH DAKOTA STATE PLUMBING BOARD
2. TYPE OF CONSTRUCTION (IBC TABLE 601)
BUILDING ELEMENT
TYPE OF
CONSTRUCTION
FIRE RESISTANCE
RATING
PRIMARY STRUCTURAL FRAME llB 0 HR ***
BEARING EXTERIOR WALL llB 0 HR **
BEARING INTERIOR WALL llB 0 HR *
NON-BEARING EXTERIOR WALL llB 0 HR **
NON-BEARING INTERIOR WALL llB 0 HR *
FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS llB 0 HR *
ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS llB 0 HR
3. CLASSIFICATION OF OCCUPANCY
AREAS OCCUPANCY IBC
PAKING AND LOW MAINTENANCE UTILITY AND MISCELLANEOUS 312
8. MODIFIED ALLOWABLE HEIGHT (IBC TABLE 504.3)
OCCUPANCY
*RESTRICTING ALLOWABLE
HEIGHT (FT / STORY)
SPRINKLER INCREASE
(FT / STORY)
MODIFIED ALLOWABLE
HEIGHT (FT / STORY)
U 55 / 2 20 / 1 75 / 3
11. OCCUPANT LOAD SUMMARY AND MINIMUM EXITS FROM FLOOR
FLOOR GROSS AREA (SF) OCCUPANTS REQUIRED EXITS (OSSC 1021.1)
REQUIRED EXIT
SEPARATION
(IBC 1015.2)
LEVEL 1 8,720 43 2 (SINGLE EXIT COMMON PATH
EXCEEDS 75')
1/3 DIAGONAL
12. COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS
OCCUPANCY
COMMON PATH LIMIT* (IBC
TABLE 1006.3.3(2)) (FT)
DEAD END LIMIT* (IBC TABLE
1020.4) (FT)
TRAVEL DISTANCE LIMIT* (IBC
TABLE 1017.2) (FT)
U 75 50 400
13. MINIMUM EGRESS WIDTHS
COMPONENT REQUIREMENT WIDTH (IN) OSSC
DOORS IN EGRESS ACCESS PER COMPONENT 32 1010.1.1
CORRIDOR SERVING 50 OR MORE OCCUPANTS PER COMPONENT 44 1020.2
CORRIDOR SERVING LESS THAN 50 OCCUPANTS PER COMPONENT 36 1020.2
CORRIDOR FOR ACCESS TO ELECTRICAL/MECHANICAL SYSTEMS PER COMPONENT 24 1020.2
OTHER EGRESS COMPONENTS PER PERSON 0.2 1005.3.2
STAIRWAYS PER PERSON 0.3 1005.3.1
14. MINIMUM INTERIOR FINISH RATINGS (IBC TABLE 803.13)
OCCUPANCY
EXIT ENCLOSURE AND EXIT
PASSAGEWAYS CORRIDORS ROOMS AND ENCLOSED SPACES
U NO RESTRICTIONS NO RESTRICTIONS NO RESTRICTIONS
15. FIRE SUPPRESSION REQUIREMENTS
SPRINKLERS (IBC 903) STANDPIPE (IBC 905) FIRE EXTINGUISHERS (IBC 906)
SPRINKLERS PROVIDED THROUGHOUT THE
BUILDING
NOT REQUIRED FIRE EXTINGUISHERS PROVIDED THROUGHOUT
THE BUILDING
16. FIRE ALARM REQUIREMENTS (IBC 907)
MANUAL INITIATION AUTOMATIC INITIATION OCCUPANT NOTIFICATION
MANUAL PULL STATION PROVIDED AT NW
EXIT FROM THE BUILDING
FLOW AND TAMPER SWITCHES, SPOT
SMOKE DETECTOR ABOVE FIRE ALARM
PANEL
NOT REQUIRED
17. FIRE EXTINGUISHER DISTRIBUTION (IBC TABLE 906.3(1))
OCCUPANCY
PRIMARY CLASSIFICATION OF FIRE
AND HAZARD MINIMUM RATING
MAXIMUM FLOOR AREA PER A
(SF)
MAX TRAVEL
DISTANCE (FT)
U CLASS A - ORDINARY 2-A 1,500 (MAX. BLDG. FLR AREA -
11,250)
* EXCEPT AS REQUIRED FOR OCCUPANCY SEPARATION, INCIDENTAL USE, AND OTHER PASSIVE FIRE PROTECTION.
** EXCEPT AS REQUIRED FOR BUILDING SEPARATION.
*** EXCEPT AS REQUIRED TO SUPPORT HORIZONTAL ASSEMBLY.
9. BUILDING SEPARATION (IBC. TABLE 602)
OCCUPANCY ELEVATION
RESTRICTIVE FIRE SEPARATION
DISTANCE (FT)*
FIRE RESISTIVE RATING OF
EXTERIOR WALL
U NORTH/SOUTH/WEST/EAST > 30 NO RATING
7. BUILDING ALLOWABLE AREA - NONSEPARATED (IBC TABLE 506.2 AND SECTION 508.3)
FLOOR FLOOR AREA (SF)
RESTRICTING
OCCUPANCY
RESTRICTING OCCUPANCY MODIFIED ALLOWABLE AREA (SF)
- SPRINKLER INCREASE
LEVEL 1 34,000 U 34,000
10. OCCUPANT LOAD CALCULATIONS (IBC TABLE 1004.5)
FLOOR AREA
FUNCTION OF
SPACE AREA (SF)
OCCUPANT
LOAD FACTOR
(SF/PERSON) OCCUPANTS
LEVEL 1 TRUCK BAY 1, 2, 3, 4, 5 & 6 PARKING 8,720 200 43
18. REQUIRED PLUMBING FIXTURES* (IBC 2902.1)
FLOOR / OCCUPANCY OCCUPANT LOAD WATER CLOSETS LAVATORIES
DRINKING
FOUNTAINS
LEVEL 1 / U (STORAGE) 43 1M 1 F 1M 1F 1
(NOT TO BE
CONSTRUCTED)
(NOT TO BE
CONSTRUCTED)
(NOT TO BE
CONSTRUCTED)
* THIS TRUCK PARKING STRUCTURE IS USED PREDOMINANTLY AS A STORAGE FACILITY WITH NO OCCUPIABLE SPACE.
EMPLOYEES HAVE ACCESS TO RESTROOM FACILITY AT ADJACENT MAINTENANCE BUILDING.
A 6/01/20 30% DESIGN SUBMITTAL
CP
DN
DN
TV
DN
DN
DN
DN
C P
NUMBER OF OCCUPANTS
ROOM NAME
AREA
COMMON PATH
OF TRAVEL
TRAVEL
DISTANCE
EGRESS
PATH
COMMON PATH
TERMINATION
POINT
EXIT DOOR
NAME
XX
111SF
GENERAL NOTES
1. REFER TO ARCHITECTURAL LEGEND FOR ADDITIONAL
INFORMATION REGARDING SYMBOLS AND
ABBREVIATIONS.
2. REFER TO AG003 FOR LIFE SAFETY NARRATIVE AND
BUILDING CODE ANALYSIS.
3. REFER TO THE ELECTRICAL LIGHTING PLANS FOR
LOCATION OF EXIT SIGNS AND EMERGENCY
LIGHTING.
4. REFER TO THE FIRE SUPPRESSION AND ALARM
PLANS FOR LOCATION OF FIRE PROTECTION
DEVICES.
5. FINAL LOCATIONS OF FIRE EXTINGUISHERS AND
HOSE REELS SHALL BE APPROVED BY THE AHJ PRIOR
TO INSTALLATION.
ROOM OCCUPANCY TAG
EGRESS PATH
TERMINATION OF
DEAD END
CORRIDOR
DEAD END DISTANCE
DEAD END CORRIDOR
100'
100'CP:666'
A:B:C: TYPE DRY CHEMICAL
2A-20B-C
B:C TYPE DRY CHEMICAL
40B:C
CLEAN AGENT
2a:10B:C
CO2 EXTINGUISHER
2A:10B:C
WATER EXTINGUISHER
2A:10B
PORTABLE FIRE EXTINGUISHERS AND HOSE REELS
FE:SR
EXTINGUISHER /HOSE
REEL TYPE
EXTINGUISHER/HOSE
REEL MOUNTING
-FE: FIRE EXTINGUISHER
-SR: SEMI-RECESSED CABINET
-BR: BRACKET MOUNTED
-HR: HOSE REEL
-SM: SURFACE MOUNT CABINET
-FR: FULLY RECESSED CABINET
HR:SM
WET-PIPE HOSE REEL
DRY-PIPE HOSE REEL
COMBINATION
EXTINGUISHER HOSE REEL
CLEAR WIDTH
EXIT CAPACITY
OCCUPANTS SERVED
REQUIRED WIDTH
36"
22"
44" 44"
DOOR EGRESS TAG STAIR EGRESS TAG
D
A
E
C
B
89'CP:0'
33.5" 32"
89'CP:0'
8470 SF
TRUCK BAY
R A
M P
S
LO
P E
1:
S
ID
E W
A
LK
R A
M P
S
LO
P E
1:
R A
M P
S
LO
P E
1:
S
ID
E W
A
LK
R A
M P
S
LO
P E
1:
MOUNT FIRE EXTINGUISHER
TO THE NEAREST STRUCTURAL
COLUMN
33.5" 32"
MOUNT FIRE EXTINGUISHER
TO THE NEAREST STRUCTURAL
COLUMN
MOUNT FIRE EXTINGUISHER
TO THE NEAREST STRUCTURAL
COLUMN
THONG C.
KHO
57834
R E
G I
S
T E
R E D A R C H
I T
E C
T
A
R I Z O N A U . S
. A
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
R E
G I
S
T E
R E D A R C H
I T
E C
T
C E
R
T I F I C A T E
N O
D a t e S i g n e d _ _ _ _ _ _ _
A
R I Z O N A U . S
. A
Expires 06/30/23
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
7/2/20
LS1027/1/20
OVERALL LIFE SAFETY PLAN
TC KHO Approver
LS102
GROUND FLOOR PLAN - LIFE
SAFETY
1 PERSON / 200 SF NETPARKING ('U' OCCUPANCY)NORTH
A 6/01/20 30% DESIGN SUBMITTAL
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
GENERAL NOTES:
1. ALL DIMENSIONS, ELEVATIONS, AND STATIONS ARE IN FEET, UNLESS INDICATED
OTHERWISE.
2. CALLOUTS, COORDINATES, AND DIMENSIONS ARE POINTED TO OR MEASURED TO
STRUCTURE CENTER, EDGE OF PAVEMENT, BACK OF CURB, OR OUTSIDE FACE
OF FOUNDATION WALL, UNLESS INDICATED OTHERWISE.
3. WHEN CONSTRUCTION WORK IS RESTRICTED TO BEING PERFORMED WITHIN
EASEMENTS, CONTRACTOR SHALL CONFINE WORK WITHIN THE PERMANENT AND
TEMPORARY EASEMENTS.
4. ALL WORK SHALL BE SUBJECT TO INSPECTION BY AUTHORIZED PERSONNEL OF
LOCAL AND GOVERNMENT REGULATORY AGENCIES.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMITS AND INSPECTIONS
REQUIRED BY ALL AGENCIES HAVING JURISDICTION.
6. ALL WORK SHALL BE CONDUCTED IN ACCORDANCE WITH THE PLANS AND
SPECIFICATIONS AND LOCAL AND GOVERNMENT CODES, ORDINANCES, AND
REGULATIONS. IN CASE OF CONTRADICTION OR DISCREPANCY BETWEEN
REQUIREMENTS, CONTRACTOR SHALL INCORPORATE WHICHEVER IS MOST
STRINGENT.
7. ALL WORK SHALL BE CONDUCTED IN A PROFESSIONAL WORKMANSHIP MANNER
USING QUALITY MATERIALS.
8. CONTRACTOR SHALL LOCATE ALL CONSTRUCTION TRAILERS AND STORE ALL
MATERIALS NOT BEING WORKED IN A DESIGNATED "LAY-DOWN" AREA; LOCATION
TO BE DETERMINED BY CONTRACTOR AND APPROVED BY OWNER. CONTRACTOR
SHALL BE FULLY RESPONSIBLE FOR SECURITY ON THE CONSTRUCTION SITE
DURING CONSTRUCTION.
9. ALL VARIATIONS IN PROJECT CONDITIONS, LOCATIONS, AND CONFIGURATIONS,
AND ANY OTHER CHANGES OR DEVIATIONS FROM THE INFORMATION
PRESENTED ON THE ORIGINAL, APPROVED CONSTRUCTION DRAWINGS SHALL BE
NOTED. THIS INCLUDES BURIED OR CONCEALED CONSTRUCTION AND UTILITY
FEATURES THAT WERE REVEALED DURING CONSTRUCTION.
10. THE LOCATION OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES
SHOWN HEREIN ARE THE BEST ESTIMATE AVAILABLE. THE ENGINEER DOES NOT
WARRANT THE COMPLETENESS OR CORRECTNESS OF THE LOCATIONS. IT SHALL
BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO PROTECT IN PLACE OR REPAIR
ALL UTILITIES IDENTIFIED ON THESE DRAWINGS. CONTRACTOR SHALL EXERCISE
REASONABLE DILIGENCE DURING EXCAVATION IN ALL AREAS. CONTRACTOR MAY
POT-HOLE TO LOCATE UNDERGROUND INSTALLATIONS AT HIS OWN EXPENSE
PRIOR TO COMMENCING EXCAVATION.
11. INSTALLATION OF GROUNDWATER DEWATERING SYSTEMS MAY BE REQUIRED TO
FACILITATE CONSTRUCTION OF PROPOSED FACILITIES. GROUNDWATER LEVELS
SHALL BE MAINTAINED BELOW THE BOTTOM OF THE TRENCH AND STRUCTURE
EXCAVATION DURING INSTALLATION. CONTRACTOR IS REQUIRED TO SECURE
DEWATERING DISPOSAL SITES AND REQUIRED AGENCY PERMITS.
12. CONTRACTOR SHALL MAINTAIN UPDATED RECORD DRAWINGS AT ALL TIMES
THROUGH THE DURATION OF THE PROJECT. CONSTRUCTION RECORD
DRAWINGS SHALL BE SUBMITTED TO THE OWNER.
13. DURING CONSTRUCTION OF THE PROJECT, CONTRACTOR SHALL BE
RESPONSIBLE FOR KEEPING TRACK OF ANY APPROVED FIELD CONSTRUCTION
REVISIONS TO THE DESIGN DEPICTED ON APPROVED CONSTRUCTION
DRAWINGS. THESE REVISIONS SHALL BE USED TO PREPARE RECORD DRAWINGS
OF COMPLETED CONSTRUCTION.
14. WHENEVER MATERIAL OR A PIECE OF EQUIPMENT IS REFERRED TO ON THE
PLANS BY THE MANUFACTURER'S BRAND NAME, SYMBOL OR CATALOG NUMBER,
IT SHALL BE UNDERSTOOD TO INDICATE ITS TYPE, STYLE AND QUALITY, AND NOT
NECESSARILY ITS MANUFACTURER. CONTRACTOR MAY REQUEST A
SUBSTITUTION OF MATERIAL OR EQUIPMENT. CONTRACTOR SHALL PROVIDE A
SUBMITTAL PER THE SPECIFICATIONS INCLUDING ALL INFORMATION REQUIRED
BY THE ENGINEER TO DETERMINE THE ACCEPTABILITY OF THE PROPOSED
SUBSTITUTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REVISIONS AND
ALTERATIONS NECESSARY TO INSTALL SUBSTITUTED MATERIAL OR EQUIPMENT
AT NO ADDITIONAL EXPENSE TO THE OWNER.
DEMOLITION NOTES:
1. ALL DEMOLITION, WASTE, DEBRIS, AND UNSATISFACTORY MATERIALS SHALL BE
DISPOSED OF OFF SITE.
2. PAVEMENT DESIGNATED FOR SAWCUT SHALL BE SAWCUT FULL DEPTH UNLESS
SPECIFIED OTHERWISE.
3. EXISTING PAVEMENT EDGES SHALL BE SAWCUT IN LOCATIONS SHOWN TO
PROVIDE CLEAN EDGE FOR CONSTRUCTION OF PROPOSED PAVEMENT.
4. ANY DAMAGE TO PAVEMENT AREAS DESIGNATED TO REMAIN SHALL BE
REPAIRED OR REMOVED AND REPLACED AT NO ADDITIONAL COST TO OWNER.
5. CONTRACTOR SHALL PRESERVE EXISTING TREES AND VEGETATION WHENEVER
PRACTICABLE. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS TO
PROTECT ROOT SYSTEMS OF SHRUBS, PLANTS AND TREES ALONG THE AREA OF
EXCAVATION.
6. EXISTING VEGETATION AND FACILITIES WHICH ARE NOT INDICATED TO BE
REMOVED SHALL BE PROTECTED FROM DEMOLITION OR OTHER CONSTRUCTION
ACTIVITIES.
7. SPECIAL HANDLING AND CONSIDERATION SHALL BE REQUIRED FOR EXCAVATED
SOILS THOUGHT TO CONTAIN PETROLEUM-BASED/CONTAMINATED/HAZARDOUS
SUBSTANCES. CONTRACTOR SHALL PERIODICALLY MONITOR EXCAVATED SOILS.
SOILS SHALL BE TREATED ON SITE OR DISPOSED OF PROPERLY IN ACCORDANCE
WITH ALL FEDERAL, STATE, AND LOCAL REQUIREMENTS AND THE PROJECT
SPECIFICATIONS. CONTRACTOR SHALL COORDINATE REMOVAL OF
PETROLEUM-BASED/CONTAMINATED/HAZARDOUS MATERIALS WITH OWNER.
8. CONTRACTOR SHALL COORDINATE WITH THE OWNER AND THE UTILITY PRIOR TO
REMOVAL OF EXISTING UTILITIES IN SERVICE.
9. RELOCATED UTILITIES SHALL BE CONSTRUCTED BEFORE REMOVAL OF EXISTING
UTILITIES TO MAINTAIN SERVICE TO THE FACILITIES SERVED BY THE UTILITY. ALL
RELOCATIONS SHALL BE COORDINATED WITH THE OWNER AND UTILITY.
10. UTILITY CAPPING METHODS SHALL BE IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS FOR SPECIFIC PIPE MATERIAL IN SERVICE. ALL CAPPING
SHALL BE INSPECTED AND APPROVED BY THE ENGINEER OR APPLICABLE UTILITY
INSPECTOR.
11. ALL STRUCTURES, VALVES, ETC. TO REMAIN SHALL BE PROTECTED AND ALL
BOXES/LIDS SHALL BE ADJUSTED TO FINISH GRADE.
12. IN AREAS OF UTILITY REMOVAL OF ABANDONED LINES, THE PORTION OF
EXISTING ABANDONED LINES TO REMAIN SHALL BE CAPPED OR PLUGGED AT
REMOVAL INTERFACE.
13. UTILITY STRUCTURES AND MANHOLES TO BE ABANDONED SHALL HAVE FRAME
AND COVER REMOVED, FILLED WITH SAND, AND BACKFILLED TO MEET
PROPOSED GRADE.
14. ALL UTILITIES EQUAL TO OR GREATER THAN 6 INCHES IN DIAMETER AND
INDICATED TO BE ABANDONED IN PLACE SHALL BE FILLED WITH A LOW
STRENGTH FLOWABLE FILL. END SECTIONS SHALL BE PLUGGED TO CONTAIN
FLOWABLE FILL. FLOWABLE FILL SHALL BE A CEMENT/SAND MIX WITH A
COMPRESSIVE STRENGTH OF 75-100 PSI.
15. ALL UTILITY SYSTEM STRUCTURES INDICATED TO BE ABANDONED IN PLACE
SHALL BE DISCONNECTED AND CAPPED.
16. CONTRACTOR SHALL MINIMIZE THE DISRUPTION OF DOMESTIC WATER AND
MAINTAIN WATER SUPPLY TO THE GREATEST EXTENT POSSIBLE. DEMOLITION OF
EXISTING MAINS SHALL NOT COMMENCE UNTIL NEW WATER MAINS ARE
COMPLETE AND OPERATIONAL.
EXCAVATION AND TRENCHES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL EXCAVATION,
TRENCHING, AND SHORING ARE PERFORMED IN A MANNER THAT COMPLIES WITH
LOCAL REGULATIONS AND OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA) REGULATIONS FOR CONSTRUCTION.
2. OPEN TRENCHES AND EXCAVATIONS AT THE CONSTRUCTION SITE SHALL BE
PROMINENTLY MARKED WITH ORANGE BARRICADES WITH FLASHING RED LIGHTS
ACCEPTABLE TO THE CONTRACTOR.
3. CONTRACTOR SHALL PROVIDE A MINIMUM NOTICE OF 48 HOURS TO THE
ASSOCIATED UTILITY COMPANIES AND AGENCIES BEFORE PROCEEDING WITH
ANY EXCAVATION.
4. OPEN ONLY THOSE TRENCHES FOR WHICH MATERIAL IS ON-HAND AND READY
FOR PLACING THEREIN. AS SOON AS POSSIBLE AFTER THE MATERIAL HAS BEEN
PLACED AND WORK APPROVED, BACKFILL AND COMPACT TRENCHES AS
SPECIFIED.
GRADING NOTES:
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL LOCAL, STATE,
AND FEDERAL PERMITS REQUIRED FOR STORM WATER POLLUTION PREVENTION
AS A RESULT OF CONSTRUCTION ACTIVITIES. THE CONTRACTOR SHALL PREPARE
A STORM WATER POLLUTION PREVENTION PLAN FOR REVIEW BY THE OWNER.
THE CONTRACTOR SHALL OBTAIN A COPY OF THE U.S. ENVIRONMENTAL
PROTECTION AGENCY'S NPDES GENERAL PERMIT FOR STORM WATER
DISCHARGE ASSOCIATED WITH CONSTRUCTION ACTIVITY (OTHERWISE KNOWN
AS THE CONSTRUCTION GENERAL PERMIT OF CGP) AND SUBMIT A "NOTICE OF
INTENT" (NOI) FOR PERMIT COVERAGE UNDER THE GENERAL PERMIT. THE CGP
DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH OTHER
REGULATIONS OR CONTRACT REQUIREMENTS REGARDING STORM WATER
POLLUTION PREVENTION INCLUDING BUT NOT LIMITED TO: PROTECTION OF
SURFACE WATERS, PREVENTION OF SOIL RUNOFF INTO DRAINS, DUST CONTROL,
PREVENTION OF TRACKING SOILS TO ADJACENT STREETS, FUEL CONTAINMENT,
SPILL CONTROL, ETC.
2. DESIGN ELEVATIONS INDICATED ARE FOR TOP OF FINAL GRADE, PAVEMENT, OR
STRUCTURE UNLESS INDICATED OTHERWISE.
3. ELEVATION DENOTED AS “MATCH” ARE INTENDED TO MEET EXISTING GRADE
ELEVATIONS. CONTRACTOR SHALL VERIFY ELEVATIONS AT TIE-INS AND MATCH
POINTS PRIOR TO BEGINNING CONSTRUCTION.
4. SURFACES AROUND THE FACILITY SHALL BE GRADED TO PROVIDE POSITIVE
DRAINAGE AWAY FROM BUILDINGS AND PAVEMENTS.
5. THE CONTRACTOR SHALL REMOVE STANDING WATER FROM THE PROJECT WORK
LIMITS AS NECESSARY TO PROTECT SUBGRADE, SUBBASE, AND/OR BASE
COURSE OF NEW PAVEMENT, SURROUNDING PAVEMENT-TO-REMAIN, OR OTHER
COMPLETED WORKS.
6. ACCESSIBLE PARKING SHALL NOT HAVE A CROSS-SLOPE THAT EXCEEDS 2.00
PERCENT.
7. FINISH GRADE OF CONCRETE STOOPS AT BUILDING DOORWAYS SHALL MATCH
FINISH FLOOR OF BUILDING AND SLOPE AWAY FROM THE BUILDING AT 2.00
PERCENT UNLESS NOTED OTHERWISE.
8. ELEVATIONS IMMEDIATELY OUTSIDE PERSONNEL DOOR ADJACENT TO
FOUNDATION SHALL BE 0.04 FEET LOWER THAN FINISH FLOOR ELEVATION AT
DOOR.
OTHER SAFETY REQUIREMENTS
1. CONTRACTOR SHALL MAINTAIN SAFETY PRACTICES THAT CONFORM TO
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) REGULATIONS.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN AND PAY FOR ALL
APPLICABLE PERMITS, FEES AND LICENSES FOR CONSTRUCTION AND
EQUIPMENT.
3. THE CONTRACTOR SHALL PERFORM ON-SITE INSPECTIONS DAILY THROUGHOUT
THE PROJECT AND REMEDY ANY SAFETY CONCERNS IMMEDIATELY.
4. ANY TEMPORARY WASTE AREA SHALL BE APPROVED BY THE OWNER AND SHALL
BE KEPT IN AN ORDERLY CONDITION. REMOVAL OF WASTE THAT IS NOT
PROPERLY MAINTAINED IS SUBJECT TO THE DIRECTION OF THE OWNER.
5. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL REQUIREMENTS WITH
STATE AND LOCAL AUTHORITIES AND SUBMITTING DOCUMENTS FOR PERMITTING
FOR EROSION, SEDIMENT CONTROL, AND STORMWATER POLLUTION
PREVENTION.
6. EROSION CONTROL DEVICES SHALL BE USED FOR THE ACCESS AND HAUL
ROUTES, STAGING AREA, AND ANY MATERIAL STOCKPILES WHEN NECESSARY TO
CONTROL EROSION AND STORM WATER RUNOFF.
7. STOCKPILED MATERIAL SHALL BE CONSTRAINED IN A MANNER TO PREVENT
MOVEMENT RESULTING FROM WIND CONDITIONS.
8. CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO LIMIT DUST CAUSED BY
CONSTRUCTION ACTIVITIES TO A LIMIT ACCEPTABLE TO PROJECT SITE
OPERATIONS. THE CONTRACTOR SHALL CONTROL BLOWING DUST ON THE
PROJECT SITE FROM ANY HAUL ROUTE OR WORK AREA REGARDLESS OF
SOURCE.
9. WILDLIFE ATTRACTANTS, SUCH AS TRASH AND FOOD SCRAPS, FROM
CONSTRUCTION PERSONNEL AND ACTIVITIES SHALL BE REMOVED FROM THE
PROJECT LIMITS.
10. GASOLINE, DIESEL FUEL, OIL, AND HAZARDOUS WASTE RESULTING FROM
CONTRACTOR'S OPERATIONS OR ACTIVITIES SHALL BE PROPERLY DISPOSED OF
IN ACCORDANCE WITH THE SPECIFICATIONS AND LOCAL REGULATORY
REQUIREMENTS AND PROPERLY REMOVED FROM THE PROJECT PROPERTY. IF
HAZARDOUS MATERIALS ARE ENCOUNTERED OR UNCOVERED DURING
CONSTRUCTION ACTIVITIES, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE
OWNER.
11. IF CONSTRUCTION REQUIRES THE DISRUPTION OR DISCONNECTION OF ANY
WATER LINES OR FIRE HYDRANTS ON PROJECT PROPERTY OR ADJOINING
PROPERTY, THE CONTRACTOR SHALL PROVIDE A MINIMUM NOTICE OF 48 HOURS
TO THE LOCAL FIRE AUTHORITY AND ALL OTHER EMERGENCY SERVICES.
UTILITY NOTES:
1. ALL EXISTING UTILITY LOCATIONS ARE APPROXIMATE AND SHALL BE
FIELD VERIFIED.
2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FULLY REVIEW ALL WORK.
ANY QUESTIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION
OF THE ENGINEER.
3. THE CONTRACTOR IS REQUIRED TO COMPLY WITH ALL APPLICABLE
FEDERAL, STATE, COUNTY AND LOCAL REQUIREMENTS, WHETHER
EXPLICITLY STATED OR NOT.
4. ALL VALVE CLOSURES AND OPENINGS SHALL BE COORDINATED WITH
BISMARCK PUBLIC WORKS DEPARTMENT (701-355-1700). THE
CONTRACTOR SHALL NOT OPERATE ANY EXISTING VALVES WITHOUT
PERMISSION FROM BISMARCK PUBLIC WORKS DEPARTMENT.
5. NOTIFICATION SHALL BE MADE TO THE FIRE DEPARTMENT PRIOR TO
SHUT-DOWNS. FIRE HYDRANTS TAKEN OUT OF SERVICE AS A RESULT OF
SHUT-DOWNS SHALL BE BAGGED AND THE FIRE DEPARTMENT NOTIFIED
DIRECTLY OF WHICH HYDRANTS ARE OUT OF SERVICE AND THE
EXPECTED DURATION OF THE OUTAGE.
6. THE CONTRACTOR SHALL BE AWARE OF UTILITY CROSSINGS IN THE
PROJECT AREA. CONTRACTOR SHALL CALL NORTH DAKOTA 811 PRIOR
TO ANY DIGGING TO LOCATE ANY UTILITIES IN PROJECT AREA.
CONTRACTOR SHALL POTHOLE ALL EXISTING UTILITIES WELL IN
ADVANCE TO ALLOW TIME FOR DESIGN MODIFICATIONS IF NECESSARY.
NO EXTRA PAYMENT WILL BE MADE TO LOCATE UTILITIES WHICH ARE
BLUE STAKED BUT NOT SHOWN ON THE PLANS.
7. WATER AND SANITARY SEWER SEPARATION SHALL BE ACCORDING TO
A.A.C. R18-1-1014.
8. ALL WATERLINES AND FITTINGS SHALL HAVE THE "NSF-PW" SEAL.
9. ALL MATERIALS AND PRODUCTS USED IN THE CONSTRUCTION OF THE
WATER SYSTEM SHALL CONFORM TO NSF STANDARD 61.
10. ALL MATERIALS AND PRODUCTS USED IN THE CONSTRUCTION OF THE
DOMESTIC WATER SYSTEM SHALL BE LEAD FREE AS DEFINED IN A.A.C.
R18-4-504 AND A.A.C. R18-1-101.
11. ALL WATER SYSTEMS SHALL BE PRESSURE TESTED ACCORDING TO
AWWA C600.
12. ALL WATER SYSTEMS SHALL BE DISINFECTED BY CHLORINATION
ACCORDING TO CONSTRUCTION SPECIFICATIONS FOR MUNICIPAL
PUBLICS WORKS IMPROVEMENTS BISMARCK, NORTH DAKOTA SECTION
901-3.6 DISINFECTION AND BACTERIOLOGICAL TESTING.
13. ALL PIPING AND CONDUIT INSTALLATION SHALL MAINTAIN A MINIMUM
COVER OF 4.5 FEET TO TOP OF PIPE.
14. ALL PIPING AND CONDUIT SHALL HAVE TRACER WIRE TAPED TO THE TOP
OF PIPE AND MARKING TAPE PLACED TWO FEET ABOVE THE PIPE ALONG
THE ENTIRE LENGTH.
15. THRUST BLOCKS SHALL BE INSTALLED PER CONSTRUCTION
SPECIFICATIONS FOR MUNICIPAL PUBLICS WORKS IMPROVEMENTS
BISMARCK, NORTH DAKOTA STANDARD DETAIL 900-1.
16. ALL AREAS DISTURBED DURING CONSTRUCTION WILL BE REPAIRED
AND REPLACED TO THE SAME CONDITION THEY WERE PRIOR TO
CONSTRUCTION. AREAS INCLUDE BUT NOT LIMITED TO SIDEWALK,
CURB & GUTTER, DRIVEWAYS, FENCES, LANDSCAPING, ETC.
17. CONTRACTOR SHALL PROVIDE AND INSTALL A NEW METER BOX.
18. CONTRACTOR SHALL PLACE BLOW-OFFS AS NECESSARY TO TEST AND
DRAIN THE NEW WATERLINE.
C001
NT
GENERAL CIVIL NOTES
ACG
07/02/2020
B 06/23/20 90% DESIGN REVIEW
0 07/02/20 ISSUED FOR CONSTRUCTION
7/2/2020
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
AB
AC
ASTM
BCF
BCHH
BM
BVCE
BVCS
C-C
CIP
CL/C
CMP
CONC
CONST
CP
CY
DIA
DTL
DWG
E
EA
EG
EL/ELEV
EP
ESMT
EVCE
EVCS
EX
FND
FG
FL
AGGREGATE BASE
ASPHALT CONCRETE
AMERICAN SOCIETY FOR TESTING
AND MATERIALS
BRASS CAP FLUSH
BRASS CAP IN A HAND HOLE
BENCH MARK
BEGIN VERTICAL CURVE ELEVATION
BEGIN VERTICAL CURVE STATION
CENTER TO CENTER
CAST IRON PIPE
CENTERLINE
CORRUGATED METAL PIPE
CONCRETE
CONSTRUCTION
CONTROL POINT
CUBIC YARD
DIAMETER
DETAIL
DRAWING
EASTING
EACH
EXISTING GRADE
ELEVATION
EDGE OF PAVEMENT
EASEMENT
END VERTICAL CURVE ELEVATION
END VERTICAL CURVE STATION
EXISTING
FOUND
FINISHED GRADE ELEVATION
FLOWLINE
ABBREVIATIONS:
FT
INV
JT
LF
LS
LT
MAX
MH
MIN
NIC
N
NAD
NG
NPI
NTS
OC
OD
OHE
OL
OSHA
PC
PCC
PI
PK
PL
PRC
PROP
PSI
FEET
INVERT ELEVATION
JOINT
LINEAR FEET
LUMP SUM
LEFT
MAXIMUM
MANHOLE
MINIMUM
NOT IN CONTRACT
NORTHING
NORTH AMERICAN DATUM
NATURAL GRADE ELEVATION
NO PAY ITEM
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OVERHEAD ELECTRIC
OVERLAY
OCCUPATIONAL SAFETY AND HEALTH ACT
POINT OF CURVATURE
PORTLAND CEMENT CONCRETE OR
POINT OF COMPOUND CURVE
POINT OF INTERSECTION
PARKER-KALON SURVEY NAIL
PROPERTY LINE
POINT OF REVERSE CURVE
PROPOSED
POUNDS PER SQUARE INCH
PT
RCP
PVMT
RGRCP
RP
RT
S
SD
SF
SG
SHT
SHLDR
SPEC
SY
STA
TOP
TOS
TYP
U.O.N.
VC
W
POINT OF TANGENCY
REINFORCED CONCRETE PIPE
PAVEMENT
RUBBER GASKET REINFORCED CONCRETE PIPE
RADIUS POINT
RIGHT
SOUTH
STORM DRAIN
SQUARE FEET
SUBGRADE
SHEET
SHOULDER
SPECIFICATIONS
SQUARE YARD
STATION
TOP OF PAVEMENT
TOP OF SLAB
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL CURVE
WEST
LEGEND
FENCE
STORM DRAIN
WATER LINE
FIRE LINE
SEWER LINE
GAS LINE
ELECTRICAL DUCT
TELEPHONE LINE
SEWER MANHOLE
WATER VALVE
FIRE HYDRANT
EXISTING PROPOSED
WATER METER
DRAIN INLET
ELECTRICAL METER
TELEPHONE PEDESTAL
AIR CONDITIONING UNIT
PROPERTY LINE
F.H.
W
E E
FOUND BRASS CAP IN HANDHOLE
FOUND BRASS CAP FLUSH
FOUND REBAR
FLAG POLE
BOLLARD
POWER POLE
TRANSFORMER PAD
MHT
COMMUNICATION DUCT
C002
NT
LEGEND & ABBREVIATIONS
ACG
07/02/2020
B 06/23/20 90% DESIGN REVIEW
U.S.B.R. BUILDING
F.F. ELEV.=1666.0
BUILDING NO. 1
BISMARCK
MAINTENANCE
BUILDING
F.F. ELEV.=1667.45
BUILDING NO. 2
GARAGE
F.F. ELEV.=1663.2
BU
IL
D
IN
G N
O . 3
ST
O
R
AG
E
BU
IL
D
IN
G
F.
F.
E
LE
V.
=1
3.
E.
B
IS
M
AR
C
K
EX
PY
EXIST TRENCH DRAIN
EXIST FENCE
EXIST
PROPERTY
BOUNDARY EXIST
ASPHALT
EXIST CONCRETE
EXIST CONCRETE
EXIST
CONCRETE
APRON
EXIST CONCRETE
CP100
CP101
CP102
CP103
CP104
EXIST
CONCRETE
APRON
EXIST
CONCRETE
APRON
EXIST RECESSED
TRUCK DOCK
40' UTILITY EASEMENT
SURVEY CONTROL POINT TABLE
POINT #
ELEVATION
1665.35
1662.74
1663.75
1665.07
1663.51
1667.37
NORTHING
418367.21
417789.34
418340.55
418531.86
417793.96
417869.62
EASTING
1910592.31
1910591.92
1909981.34
1909940.56
1909926.84
1909538.56
DESCRIPTION
CP100
CP101
CP102
CP103
CP104
CP105
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NORTH 0
SCALE IN FEET
50' 100'
SURVEY CONTROL PLAN
LEGEND
SURVEY CONTROL POINT
SURVEY CONTROL NOTES:
1. CONTROL REFERENCES NORTH DAKOTA STATE PLAN COORDINATE SYSTEM,
SOUTH ZONE NAD 83 (2011) AND NORTH AMERICAN VERTICAL DATUM NAVD88.
2. SURVEY LOCATED AT THE SOUTHEAST QUARTER OF SECTION 35, T 139 N, R 80 W
OF THE 5TH P.M. IN THE CITY OF BISMARCK, BURLEIGH COUNTY, NORTH DAKOTA
WAS COMPLETED BY WHITE SHIELD, INC LAND SURVEYING ENVIRONMENTAL
SERVICES ON MAY 12, 2017.
3. CONTROL REFERENCES WERE ACCOMPLISHED BY SETTING TWO PRIMARY SITE
CONTROL POINTS FOR USE AS A PROJECT BASELINE, USING THE MIDSTATES
VIRTUAL REFERENCE STATION (VRS). EACH POINT WAS OBSERVED WITH A 180
EPOCH SHOT. FROM THE PRIMARY CONTROL BASELINE, FOUR SECONDARY
CONTROL POINTS WERE SET THROUGHOUT THE SITE USING A TRIMBLE S6
ROBOTIC TOTAL STATION. THESE CONTROL POINTS WERE OCCUPIED BY
CYLINDER TARGETS FOR SCANNER ORIENTATION DURING THE SCANNING
PROCESS. A TOTAL OF 66 SCANS WERE PERFORMED IN THE FIELD.
C003
NT
SURVEY CONTROL PLAN
ACG
07/02/2020
B 06/23/20 90% DESIGN REVIEW
BUILDING NO. 1
BISMARCK
MAINTENANCE
BUILDING
F.F. ELEV.=1667.45
BUILDING NO. 2
GARAGE
F.F. ELEV.=1663.2
VEHICLE STORAGE
FACILITY
F.F. ELEV. =1667.5
E.
B
IS
M
AR
C
K
EX
PY
CONSTRUCTION FENCE
EXIST RECESSED
TRUCK DOCK
.75
40' UTILITY EASEMENT
SITE ENTRANCE GATE
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NORTH
ACCESS & SAFETY PLAN
LEGEND
SCALE IN FEET
20'10' 40'
C004
NT
ACCESS & SAFETY PLAN
ACG
07/02/2020
ACCESS AND STAGING
1. ACCESS AND HAUL ROUTES FOR ALL CONTRACTOR PERSONNEL, VEHICLES, EQUIPMENT, AND
DELIVERIES ARE ILLUSTRATED ON THIS DRAWING. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY
TO COORDINATE OFF-SITE HAUL ROUTES WITH THE OWNER. ACCESS ROUTES AND HAUL ROUTES
ARE SUBJECT TO CHANGE AT THE DIRECTION OF THE OWNER AND MAY CHANGE BASED ON
OPERATIONAL REQUIREMENTS OF THE PROJECT SITE.
2. CONTRACTOR SHALL COORDINATE ACTIVITIES AND MAINTAIN ALL ACCESS AND HAUL ROUTES IN A
MANNER THAT ALLOWS UNOBSTRUCTED EMERGENCY ACCESS TO ALL PROJECT AREAS, AND
EXISTING ROADWAYS AT ALL TIMES WITHOUT DELAY TO EMERGENCY AND SECURITY VEHICLE
RESPONSE TIME.
3. IF ANY EMERGENCY ROUTES REQUIRE CLOSURE DUE TO CONSTRUCTION ACTIVITIES, CONTRACTOR SHALL NOTIFY THE SECURITY, OWNER'S FIRE DEPARTMENT, AND ALL OTHER EMERGENCY SERVICES
OF THE CLOSURE.
4. CONTRACTOR SHALL MAINTAIN ACCESS AND HAUL ROUTES TO BE FREE FROM DEBRIS CAUSED FROM
CONSTRUCTION ACTIVITIES ON A DAILY BASIS.
5. CONTRACTOR SHALL RESTRICT ALL OPERATIONS TO AREAS WITHIN THE CONSTRUCTION LIMITS
UNLESS COORDINATED OTHERWISE WITH THE OWNER.
6. CONTRACTOR SHALL PROVIDE TEMPORARY CONSTRUCTION FENCING AROUND THE ENTIRE SITE
DURING CONSTRUCTION. FENCE SHALL BE LOCATED AS SHOWN FOR WORK TO BE COMPLETED
INSIDE OF TEMPORARY CONSTRUCTION FENCING.
7. WHEN NOT ENGAGED IN CONSTRUCTION ACTIVITIES, CONTRACTOR'S EQUIPMENT AND VEHICLES SHALL BE PARKED IN THE STAGING AREA AND/OR CONTRACTOR PARKING LOTS AS APPROVED BY THE
OWNER.
8. CONTRACTOR SHALL PROVIDE A MINIMUM NOTICE OF 24 HOURS TO THE OWNER REGARDING
CONSTRUCTION DELIVERIES PRIOR TO THOSE DELIVERIES.
9. ACCESS POINTS, HAUL ROUTES, STAGING AREA, AND ANY OTHER AREAS DISTURBED BY THE
CONTRACTOR SHALL BE RESTORED TO THEIR ORIGINAL CONDITION OR BETTER TO THE
SATISFACTION OF THE OWNER.
10. CONTRACTOR SHALL RESTRICT ALL OPERATIONS TO AREAS WITHIN THE CONSTRUCTION LIMITS
UNLESS COORDINATED OTHERWISE WITH THE OWNER.
TRAFFIC CONTROL
1. PRIOR TO CONSTRUCTION, CONTRACTOR SHALL CORDON OFF THE CONSTRUCTION WORK AREA AND
ASSOCIATED ROADWAYS BY USING BARRICADES APPROVED BY THE OWNER.
2. ALL CONSTRUCTION EQUIPMENT AND VEHICLES SHALL BE MARKED WITH COMPANY DESIGNS,
INSIGNIAS, OR OTHER MARKINGS, WHICH ARE CLEARLY VISIBLE.
3. CONSTRUCTION EQUIPMENT SHALL HAVE AUTOMATIC SIGNALING DEVICES TO SOUND AN ALARM
WHEN MOVING IN REVERSE.
4. ONLY RUBBER-TIRE VEHICLES WILL BE ALLOWED ON EXISTING PAVEMENT-TO-REMAIN.
5. NO PEDESTRIAN TRAFFIC SHALL BE ALLOWED INSIDE THE CONSTRUCTION LIMITS.
6. CONTRACTOR SHALL PROVIDE A MINIMUM NOTICE OF 1 WEEK TO WAPA, SECURITY, FIRE
DEPARTMENT AND THE CONTRACTOR FOR ROAD CLOSURE PRIOR TO THE ROAD REQUIRING
CLOSURE.
7. PRIOR TO THE REMOVAL OF BARRICADES AND TRAFFIC CONTROL DEVICES, THE CONTRACTOR SHALL
REQUEST THE OWNER TO SCHEDULE AN INSPECTION.
8. ANY DAMAGE TO ROADS AND PAVEMENTS-TO-REMAIN DUE TO CONSTRUCTION EQUIPMENT OR
TRAFFIC SHALL BE REPAIRED TO RESTORE THE ROADS AND PAVEMENTS TO THEIR ORIGINAL
CONDITION TO THE SATISFACTION OF THE OWNER.
ACCESS/HAUL ROUTE
CONSTRUCTION FENCE
MAINTENANCE
BUILDING
F.F. ELEV.=1667.45
BUILDING NO. 2
GARAGE
F.F. ELEV.=1663.2 E.
B
IS
M
AR
C
K
EX
PY
EXIST
ASPHALT
EXIST CONCRETE
EXIST ASPHALT
(TBR&R)
EXIST ABANDONED
WATER LINE (TBR)
EXIST COMMUNICATION
DUCT (TBA)
EXIST CONCRETE
(TBR&R)
EXIST ASPHALT
(TBR&R)
40' UTILITY EASEMENT
EXIST CONCRETE
(TBR&R)
EXIST COMMUNICATION
DUCT (DND)
EXIST WATER
LINE (DND)
EXIST ELECTRICAL
DUCT (DND)
EXIST STORM
PIPE (DND)
EXIST COMMUNICATION
DUCT (DND)
EXIST ELECTRICAL
DUCT (DND)
EXIST GAS LINE
(DND)
SAWCUT
LIMITS (TYP.)
N 418098.35 E 1910305.61
N 418098.25 E 1910297.61
N 418084.68 E 1910305.61
N 418077.02 E 1910297.61
N 418071.20 E 1910617.33
N 418063.19 E 1910617.33
N 418094.50 E 1910601.72
N 418094.51 E 1910437.57
N 418111.31 E 1910437.57
N 418112.15 E 1910371.29
N 418329.39 E 1910373.97 N 418329.10
E 1910380.10
N 418314.98 E 1910382.41
N 418305.90 E 1910525.80
N 418320.73 E 1910554.98
N 418320.73 E 1910593.89
N 418281.64 E 1910593.00
N 418166.44 E 1910658.95
N 418160.44 E 1910658.88
N 418166.68 E 1910645.44
N 418160.68 E 1910645.34
N 418177.96 E 1910644.87
N 418265.58 E 1910660.15
N 418265.82 E 1910647.16
N 418259.82 E 1910647.05
N 418259.59 E 1910660.08
N 418186.10 E 1910388.41
N 418182.98 E 1910354.47
N 418178.15 E 1910354.39
N 418177.86 E 1910372.33
N 418182.69 E 1910372.40
N 418249.70 E 1910373.46
N 418261.46 E 1910373.65
N 418261.51 E 1910355.71
N 418249.71 E 1910355.53
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NORTH
DEMOLITION PLAN
LEGEND
DEMOLITION AREA
TO BE REMOVED
TO BE REMOVED AND REPLACED
TBR
TBR&R
DEMOLITION NOTES:
1. EXISTING FENCES TO BE PROTECTED. REMOVE
AND REPLACE FENCE WHERE REQUIRED TO
INSTALL NEW UTILITIES.
2. REFER TO C001 FOR ADDITIONAL DEMOLITION
AND UTILITY NOTES.
SCALE IN FEET
30' 60'
CD001
NT
DEMOLTION PLAN
ACG
07/02/2020
TO BE ABANDONEDTBA
B 06/23/20 90% DESIGN REVIEW
0 07/02/20 ISSUED FOR CONSTRUCTION
DO NOT DISTURBDND
MAINTENANCE
BUILDING
F.F. ELEV.=1667.45
VEHICLE STORAGE
FACILITY
F.F. ELEV. =1667.5
ASPHALT LIMITS
BOLLARD (TYP. OF 26)
CONCRETE APRON
CONCRETE APRON
5.0' SIDEWALK
5.0' SIDEWALK
EXIST RECESSED
TRUCK DOCK
EXIST CONCRETE
APRON
EXIST ASPHALT
SLOPED
CONC
PAVEMENT
SLOPED
CONC
PAVEMENT
SLOPED
CONC
PAVEMENT
5.0' RAMP
5.0' RAMP
CONCRETE
DRAINAGE PAN
EXIST ASPHALT
REPLACE
CONCRETE
APRON
ROAD BASE LIMITS
ROAD BASE LIMITS
6" VERTICAL
CURB 6" VERTICAL
CURB
6" VERTICAL
CURB
40' UTILITY EASEMENT
REPLACE
CONCRETE
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NORTH
CIVIL SITE PLAN
LEGEND
6" ROAD BASE
CONCRETE PAVEMENT
BOLLARD
SCALE IN FEET
20'10' 40'
C501
C500
C500
C500
C500
NOTES:
1. ISOLATION JOINTS SHALL BE USED BETWEEN CONCRETE
APRONS AND SLOPED CONCRETE PAVEMENTS. SEE
DETAIL 5 ON SHEET C500.
2. 24 FOOT MAXIMUM CONTROL JOINT SPACING FOR
CONCRETE APRONS.
3. 15 FOOT MAXIMUM CONSTRUCTION JOINT SPACING FOR
CONCRETE APRONS.
4. ALL CURBS HAVE TAPERED ENDS AT THE END OF THE
RAMPS/SIDEWALKS. SEE DETAIL 7 ON SHEET C501 FOR
TAPERED END DETAIL.
5. MATCH EXISTING CONCRETE THICKNESS FOR CONCRETE
REPLACEMENTS.
CS001
NT
CIVIL SITE PLAN
ACG
07/02/2020
4" ASPHALT PAVEMENT
C501
B 06/23/20 90% DESIGN REVIEW
0 07/02/20 ISSUED FOR CONSTRUCTION
A 06/02/20 30% DESIGN REVIEW
C501
C501
C501
C500
MAINTENANCE
BUILDING
F.F. ELEV.=1667.45
VEHICLE STORAGE
FACILITY
F.F. ELEV. =1667.5
1 2
3 4
27 28 29 30 31 32
34 35 36 37 38 39
EXIST RECESSED
TRUCK DOCK
EXIST CONCRETE
APRON
EXIST ASPHALT
R62'
EXIST ASPHALT
65 66
73 74 75 76 77 78
7980818283
85 86
90 91
95 96
40' UTILITY EASEMENT
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NORTH
CIVIL POINT CONTROL PLAN
LEGEND
CONCRETE PAVEMENT
BOLLARD
SCALE IN FEET
20'10' 40'
ROAD BASE
NOTES:
1. SEE SHEET CS003 FOR POINT TABLE.
CS002
NT
CIVIL POINT CONTROL PLAN
ACG
07/02/2020
APHALT PAVEMENT
B 06/23/20 90% DESIGN REVIEW
CONTROL POINT TABLE
POINT #
ELEVATION
1667.02
1667.02
1667.50
1667.50
1667.50
1666.00
1667.50
1666.00
1667.10
1666.44
1665.01
1667.50
1667.35
1667.25
1667.50
1667.50
1667.50
1667.50
1667.50
1667.50
1666.50
1666.50
1667.50
1667.50
1667.50
1663.92
1667.48
1667.48
1667.48
1667.48
1667.48
1667.48
1667.43
1667.43
1667.42
1667.42
1667.42
1667.42
1667.42
1667.69
1664.64
1665.69
1663.87
1664.95
1665.16
1667.13
1667.51
1666.00
1667.50
1667.50
NORTHING
418286.83
418286.83
418256.83
418256.83
418176.41
418146.41
418176.41
418146.41
418253.42
418165.16
418112.00
418252.87
418227.37
418205.87
418180.37
418180.37
418252.87
418252.87
418252.87
418247.37
418227.37
418205.87
418185.87
418180.37
418180.37
418094.50
418258.33
418258.33
418258.33
418258.33
418258.33
418258.33
418174.91
418174.91
418174.91
418174.91
418174.91
418174.91
418174.91
418318.64
418378.30
418374.40
418094.50
418094.51
418111.31
418112.15
418281.87
418146.41
418185.87
418247.37
EASTING
1910443.13
1910552.55
1910443.13
1910552.55
1910443.13
1910443.13
1910552.55
1910552.55
1910403.16
1910403.16
1910456.32
1910438.13
1910438.13
1910438.13
1910438.13
1910443.13
1910443.12
1910552.55
1910557.55
1910557.55
1910557.55
1910557.55
1910557.55
1910557.55
1910552.55
1910593.60
1910462.67
1910481.67
1910497.67
1910514.67
1910530.67
1910545.67
1910448.00
1910462.67
1910481.67
1910497.67
1910514.67
1910530.67
1910545.67
1910198.21
1910241.47
1910603.62
1910601.72
1910437.50
1910437.57
1910371.29
1910373.97
1910441.13
1910438.13
1910438.13
DESCRIPTION
CONC APRON CORNER
CONC APRON CORNER
BLDG CORNER
BLDG CORNER
BLDG CORNER
CONC APRON CORNER
BLDG CORNER
CONC APRON CORNER
CONC DP BEGIN
CONC DP BEND
CONC DP END
CONC SW CORNER
CONC SW CORNER
CONC SW CORNER
CONC SW CORNER
CONC SW CORNER
CONC SW CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
CONC SW RAMP CORNER
ASPHALT CORNER
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
ROAD BASE CORNER
ROAD BASE CORNER
ROAD BASE CORNER
ROAD BASE CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
SLOPED CONC CORNER
CONC SW CORNER
CONC SW CORNER
CONTROL POINT TABLE
POINT #
ELEVATION
1666.81
1666.30
1666.38
1666.36
1666.41
1666.65
1667.03
1667.25
1666.00
1666.17
1666.50
1666.50
1667.02
1667.02
1667.03
1667.14
1667.14
1667.04
1667.48
1667.37
1667.52
1667.42
1667.48
1667.48
1667.48
1667.48
1667.48
1667.48
1667.42
1667.42
1667.42
1667.42
1667.42
1666.64
1667.01
1667.01
1666.63
1666.82
1663.26
1664.00
1663.01
1663.01
1667.25
1667.50
1667.50
1667.50
1667.50
1666.50
1666.50
1667.50
NORTHING
418320.73
418374.49
418374.71
418373.49
418329.39
418335.72
418180.37
418205.87
418146.41
418179.87
418205.87
418227.37
418253.37
418286.83
418178.15
418177.86
418182.69
418182.98
418249.71
418249.70
418261.51
418261.46
418258.33
418258.33
418258.33
418258.33
418258.33
418258.33
418174.91
418174.91
418174.91
418174.91
418174.91
418320.73
418098.25
418098.35
418077.02
418084.68
418071.81
418066.10
418066.32
418063.19
418205.87
418179.87
418179.87
418179.87
418179.87
418205.87
418227.37
418253.37
EASTING
1910593.89
1910595.13
1910574.83
1910575.02
1910373.97
1910241.71
1910436.13
1910436.13
1910554.55
1910562.05
1910562.05
1910562.05
1910562.05
1910554.55
1910354.39
1910372.33
1910372.40
1910354.47
1910355.53
1910373.46
1910355.71
1910373.65
1910448.00
1910467.00
1910483.00
1910500.00
1910516.00
1910533.00
1910533.00
1910516.00
1910500.00
1910483.00
1910467.00
1910554.98
1910297.61
1910305.61
1910297.61
1910305.61
1910603.18
1910603.45
1910617.33
1910617.33
1910437.63
1910437.63
1910443.13
1910552.55
1910558.05
1910558.05
1910558.05
1910558.05
DESCRIPTION
ASPHALT CORNER
ROAD BASE CORNER
ROAD BASE CORNER
ROAD BASE CORNER
ASPHALT CORNER
ROAD BASE CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
SLOPED CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
BOLLARD
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
ASPHALT CORNER
CONC SW CURB
CONC SW CURB
CONC SW CURB
CONC SW CURB
CONC SW CURB
CONC SW CURB
CONC SW CURB
CONC SW CURB
CONTROL POINT TABLE
POINT #
ELEVATION
1667.50
1664.36
1664.22
1663.57
1663.43
1663.00
1663.00
1663.00
1663.00
1667.45
1667.47
NORTHING
418253.37
418265.82
418259.82
418265.59
418259.59
418166.68
418160.68
418166.44
418160.44
418254.87
418247.37
EASTING
1910552.55
1910647.16
1910647.05
1910660.15
1910660.08
1910645.44
1910645.34
1910658.95
1910658.88
1910436.13
1910436.13
DESCRIPTION
CONC SW CURB
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
CONC CORNER
BOLLARD
BOLLARD
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NOTES:
1. SEE SHEET CS002 FOR POINT CONTROL PLAN.
2. ELEVATIONS SHOWN DEPICT THE TOP OF PAVEMENT, GRAVEL, OR
FINISH GRADE ONLY. FINISH FLOOR, EQUIPMENT PAD, AND OTHER
STRUCTURAL ITEMS REFER TO STRUCTURAL DRAWINGS FOR TOP OF
CONCRETE ELEVATIONS
CS003
NT
CIVIL POINT CONTROL TABLE
ACG
07/02/2020
B 06/23/20 90% DESIGN REVIEW
MAINTENANCE
BUILDING
F.F. ELEV.=1667.45
VEHICLE STORAGE
FACILITY
F.F. ELEV. =1667.5
6"x36" SADDLE TAP TEE N = 418233.04 E = 1910645.61
SANITARY
SEWER MANHOLE
N = 418213.27 E = 1910625.09
RIM ELEV = 1664.22
INV (W) = 1660.70
INV (N) = 1660.21 (APPROX.)
INV (S) = 1660.26 (APPROX.)500 GAL OIL/WATER
INTERCEPTOR
N = 418211.88
E = 1910559.90
6"x2"x6" TEE N = 418233.04
E = 1910637.16
ISOLATION VALVE
COMM VAULT (SEE ELEC)
N = 418176.46
E = 1910434.59
EXIST COMM VAULT
(FIELD VERIFY)
N = 418068.31 E = 1910619.93
ELEC POWER TIE INTO
BLDG (SEE ELEC)
N = 418258.38 E = 1910355.66
COMM TIE INTO
BLDG (SEE ELEC)
N = 418098.30 E = 1910301.61
ELEC POWER TIE INTO
BLDG (SEE ELEC)
N = 418231.35 E = 1910443.13
2" TYPE K HARD COPPER WATER
TIE INTO BLDG (SEE MECH)
N = 418202.89 E = 1910554.96
6" PVC FIRE WATER TIE INTO
BLDG (SEE FIRE PROTECTION)
N = 418233.04 E = 1910553.00
COMM BEND
N = 418080.85
E = 1910301.61
2" TYPE K HARD COPPER WATER
90° BEND
N = 418202.89 E = 1910637.16
4" CAST IRON SANITARY SEWER
TIE INTO BLDG (SEE MECH)
N = 418209.40 E = 1910556.52
INV = 1662.6875
8" PVC UNDERDRAIN
DAYLIGHT
N = 418163.81 E = 1910663.78
INV = 1662.45
8" PVC UNDERDRAIN
DAYLIGHT
N = 418262.43 E = 1910666.25
INV = 1662.47
8" PVC UNDERDRAIN
90° BEND
N = 418163.81 E = 1910465.84
INV = 1663.44
8" PVC UNDERDRAIN
90° BEND
N = 418163.81 E = 1910498.84
INV = 1663.27
8" PVC UNDERDRAIN
90° BEND
N = 418163.81 E = 1910531.84
INV = 1663.11
8" PVC UNDERDRAIN
90° BEND
N = 418262.43 E = 1910465.84
INV = 1663.47
8" PVC UNDERDRAIN
90° BEND
N = 418262.43 E = 1910498.84
INV = 1663.31
8" PVC UNDERDRAIN
90° BEND
N = 418262.43 E = 1910531.84
INV = 1663.14
EXIST 36" WATER MAIN
EXIST 8" SANITARY SEWER
EXIST 3" GAS LINE40' UTILITY EASEMENT
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
EAC
DESIGNED
WESTERN AREA POWER ADMINISTRATION
NORTH
CIVIL UTILITY PLAN
COMMUNICATIONS
LEGEND
ELEC POWER
SANITARY SEWER
WATER
SCALE IN FEET
20'10' 40'
FIRE PROTECTION
NOTES:
1. ALL WATER SERVICES MUST BE A MINIMUM DEPTH OF 7.5' BELOW
FINISHED GRADE WITH A STOP FITTED WITH A BOX SET AT A LOCATION
SPECIFIED BY THE CITY ENGINEER. CURB STOPS MUST BE THE STOP
AND WASTE TYPE UNLESS OTHERWISE SPECIFIED BY THE CITY
ENGINEER. CURB STOPS MUST BE EQUIPPED WITH EXTENSION BOXES
NOT LESS THAN TWO INCHES IN DIAMETER, WITH MUELLER BOXES, OR
THEIR APPROVED EQUAL ADJUSTED TO GRADE.
2. PRIVATE FIRE PROTECTION SERVICES MUST BE CONTROLLED BY A
GATE VALVE PLACED IN THE STREET AS NEAR THE UTILITY AS
PRACTICABLE. VALVES MUST BE A STANDARD TYPE AND HAVE A
SUBSTANTIAL VALVE BOX FITTED WITH A COVER WITH THE
DIRECTIONS FOR OPENING OR CLOSING PLAINLY MARKED UPON IT.
3. ANY WATER METER TWO INCHES IN SIZE OR OVER SHALL HAVE A
BYPASS AND SHALL HAVE A SUITABLE VALVE ON EITHER SIDE OF THE
METER AND A VALVE ON THE BYPASS. TITLE 11 8 EACH BYPASS SHALL
BE SEALED WITH A SEAL AFFIXED BY THE CITY OF BISMARCK AND
SUCH SEALS SHALL NOT BE REMOVED.
4. 4-INCH DOUBLE CLEANOUTS SHALL BE INSTALLED ON EITHER SIDE OF
THE OIL/WATER SEPARATOR. SEE DETAIL 9 ON SHEET C500.
5. SEE DETAIL 3 ON SHEET C501 FOR CITY OF BISMARCK SANITARY
SEWER MANHOLE DETAIL.
6. SEE DETAIL 2 ON SHEET C501 FOR ISOLATION VALVE DETAIL.
7. ALL UTILITIES TO BE BURIED IN UTILITY TRENCH. SEE DETAIL 4 ON
SHEET C501 FOR UTILITY TRENCH DETAIL.
8. SEE DETAIL 6 ON SHEET C501 FOR DOWNSPOUT AND…