800-PG-8710.3.1 Updated WFF Flex Hose Handling.pdf

PDF 2 MB Posted

Attached to
NASA Sounding Rocket Operations Contract (NSROC) IV - FINAL Request for Proposal, eLibrary Federal contract opportunity
Solicitation number
80GSFC21R0037-eLibrary
Issued by
National Aeronautics and Space Administration Goddard Space Center

About this file

This directive establishes requirements for flexible hose procurement, testing, identification, installation, and use at Wallops Flight Facility and its sites. It defines methods and procedures for obtaining, maintaining, inspecting, installing, using, and testing all types of flexible hoses. The directive applies to all ground-based flexible hoses used to transport hazardous/toxic liquids/gases, cryogenics, or above 150 psig and larger than 1/4 inch inside diameter. It establishes acceptance criteria for Type I permanently installed hoses and Type II non-dedicated hoses. Inspection, installation, containment, and transportation requirements are provided. Training and record keeping procedures are also outlined.

View the file

Other files for this federal contract opportunity

Other files attached to NASA Sounding Rocket Operations Contract (NSROC) IV - FINAL Request for Proposal, eLibrary, newest first.
File Type Posted
NSROC CBA IAMAW 11.01.21 final FULLY EXECUTED.pdf PDF
Rocket_Report_1st_quarter_2019.pdf PDF
Rocket Report 2nd quarter 2021.pdf PDF
Rocket_Report_3rd_quarter_2019.pdf PDF
Rocket Report 4th quarter 2020.pdf PDF
Rocket Report 1st quarter 2021.pdf PDF
SRPO Annual Report 2017.pdf PDF
Rocket Report 1st quarter 2020.pdf PDF
SRWG_Findings_Jan_2021.pdf PDF
Sounding rocket litho 2017.pdf PDF
SRWG_Findings_July_2020.pdf PDF
GSFC-STD-8009T-SRPO WFF Range Safety Manual Rev B.pdf PDF
300-PG-8730.6.1 ESD Control Plan.pdf PDF
800-WI-8715.2.1B Severe Weather Notification.pdf PDF
810-PG-5100.1.3G NSROC Development and Routine Project Assignments Process.pdf PDF
GPR 4220.1.pdf PDF
GPR 1700.7.pdf PDF
GPR 1860.2.pdf PDF
GPR 8730.1.pdf PDF
GPR 8710.8.pdf PDF
GPR 8500.5.pdf PDF
GPR 5340.3.pdf PDF
NPR 2190.1.pdf PDF
GPR 8500.8.pdf PDF
GPR 1700.8.pdf PDF
GPR 1800.5.pdf PDF
NPR 8735.2.pdf PDF
810-FORM-0003H SRPO MRR Checklist.pdf PDF
NPD 1490.1.pdf PDF
NPD 4200.1.pdf PDF
NPR 1441.1.pdf PDF
GPR 8730.6.pdf PDF
NPD 6000.1.pdf PDF
NPD 2540.1.pdf PDF
NPD 1440.6.pdf PDF
803-PG-3410.2.2 WFF Safety Office Training and Certification Program.pdf PDF
NPD 1280.1.pdf PDF
NPR 8705.6.pdf PDF
810-FORM-0002G SRPO DR Checklist.pdf PDF
810-FORM-0004H SRPO MCR Checklist.pdf PDF
NPR 8715.5.pdf PDF
NPR 4200.1.pdf PDF
SRPO Cryogenic Safety Users Guide Revision A Final.pdf PDF
NSROC III NNG16WA70C Attachment M - Contract Historical Data 19-20.pdf PDF
SRPO Technology Roadmap June 2021.pdf PDF
NSROC III List of Ongoing Work - October 2021.pdf PDF
SRPO Annual Report 2016.pdf PDF
Rocket_Report_4th_quarter_2019.pdf PDF
SR User Handbook Final_July 2015.pdf PDF
SRPO Annual Report 2019.pdf PDF
Show all 50

NASA Sounding Rocket Operations Contract (NSROC) IV - FINAL Request for Proposal, eLibrary has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DIRECTIVE NO. 800-PG-8710.3.1A APPROVED BY Signature: Original Signed by

EFFECTIVE DATE: June 26, 2014 NAME: David L. Pierce

EXPIRATION DATE: June 26, 2022 TITLE: Director, Wallops Flight Facility

CHECK THE GSFC DIRECTIVES MANAGEMENT SYSTEM AT

http://gdms.gsfc.nasa.gov TO VERIFY THAT THIS IS THE CORRECT VERSION PRIOR TO USE.

04/14

Center-wide

Procedures and Guidelines (PG)

COMPLIANCE IS MANDATORY

Responsible Office: 800/Suborbital and Special Orbital Projects Directorate

Title: Wallops Flight Facility Flex Hose Handling and Installation

PREFACE

P.1 PURPOSE

This document establishes requirements for the procurement, testing, identification, installation, and use of Flex Hose Assemblies at the Wallops Flight Facility (WFF), its component facilities, field sites, and campaign locations. It defines the methods and procedures, by which personnel will procure, maintain, inspect, install, use, and test all types of flexible hoses.

P.2 APPLICABILITY

These requirements apply to all uses of flex hoses at WFF (whether NASA managed or tenant owned and operated) or under the auspices of WFF elsewhere. These requirements are imposed on tenants, contractors, experimenters, and external customers only to the extent indicated in their relevant agreements or contracts. Compliance at WFF managed facilities, field sites, and component facilities by tenants, contractors, experimenters, and external customers may be accomplished by analogous procedures if the procedures are at least as stringent and approved as equivalent by the Pressure Systems

Manager (PSM). These requirements apply to all ground based flex hoses used to transport hazardous or toxic liquids or gases, cryogenics, and to all ground based flex hoses which are greater than ½ inch

Inside Diameter (ID) and are used at above 150 psig, regardless of commodity. Flex hoses contained in systems approved by Underwriter’s Laboratory (UL), National Institute for Occupational Safety and

Health (NIOSH), or other safety certifying organizations are also excluded provided they are used as certified.

There is a 90 day grace period following the initial release of this document, and all subsequent revisions, to allow for implementation of the requirements.

P.3 AUTHORITY

a. NPD 8710.5, Policy for Pressure Vessels and Pressurized Systems

b. NASA-STD-8719.17, NASA Requirements for Ground-Based Pressure Vessels and Pressurized

Systems (PV/S)

c. GPR 8710.3, Certification and Recertification of Ground Based Pressure Vessels and Pressurized

Systems

DIRECTIVE NO. 800-PG-8710.3.1A Page 2 of 29

EFFECTIVE DATE: June 26, 2014

EXPIRATION DATE: June 26, 2022

04/14

P.4 REFERENCES

a. NASA-STD-8719.17, NASA Requirements for Ground-Based Pressure Vessels and Pressurized

Systems (PV/S)

b. GSFC-SH-HPST, Basic High Pressure Systems Training

P.5 CANCELLATION

N/A

P.6 SAFETY

General hazards associated with the use of flex hoses are identified in this document and mitigations are contained in the requirements prescribed by this document.

P.7 TRAINING

Personnel using flex hoses defined as a Type I or Type II flex hose shall receive general pressure systems safety awareness and job specific or “On the Job” training as documented by their supervisor.

This general pressure systems safety training must include GSFC-SH-HPST, the GSFC-Basic High

Pressure Systems Training course offered through System for Administration, Training, and Educational

Resources for NASA (SATERN) as an instructor led course. Alternative training may be submitted for review and approval by the PSM or designee on a case-by-case basis to satisfy the general pressure systems safety awareness training.

P.8 RECORDS

No unique records are generated as a result of this PG.

P.9 MEASUREMENT/VERIFICATION

N/A

PROCEDURES

In this document, a requirement is identified by “shall,” a good practice by “should,” permission by

“may” or “can,” expectation by “will,” and descriptive material by “is.”

1.0 ACCEPTANCE CRITERIA

All newly fabricated flex hose assemblies shall meet the following criteria:

1.1 Type I Flex Hose Assembly

DIRECTIVE NO. 800-PG-8710.3.1A Page 3 of 29

04/14

A Type I Flex Hose is a permanently-dedicated hose whose installation and placement are indicated by design-controlled engineering drawings. Once installed, the flex hose is considered to be an integral part of that installation. Type I hoses have an assigned drawing reference designator. Type I hoses shall be accepted and certified as part of the overall pressure system per NASA-STD-8719.17.

The retest requirement shall be determined as part of the system certification and maintenance plan.

1.1.1 Procurement Requirements

Procurement requirements shall be as defined on the Engineering Drawing.

As a minimum, the requirements specified below for a Type II hose shall be satisfied.

1.2 Type II Flex Hose Assembly

A Type II Flex Hose is a non-permanently installed and assigned, non-dedicated flex hose whose installation is authorized and controlled by an operations procedure. Hose and certification requirements will be established by the controlling procedure. This is probably the most common type of aerospace hose used in ground-based systems at WFF.

1.2.1 Procurement Requirements

1.2.1.1 The hose materials shall be appropriate for the commodity to be transferred (see Appendix C –

Material Restrictions).

1.2.1.2 The hose rated temperature range shall be appropriate for the expected internal and external temperatures.

1.2.1.3 The hose shall have a minimum rated burst pressure of 4 times the Maximum Allowable

Working Pressure (MAWP). Four to one (4:1) safety factor

1.2.1.4 The hose shall be hydrostatically tested to 1.5 times the MAWP or pneumatically tested at least to 1.1 times the MAWP by the manufacturer and provide a certificate of compliance.

1.2.1.5 A metal tag or band shall be attached to the hose by the manufacturer bearing the following information:

a. Manufacturer’s Name

b. Manufacturer’s Part Number

c. Fabrication Date (Month and Year)

d. Hydrostatic/Pneumatic Test Date (Month and Year)

e. Rated Working Pressure

f. Serial Number, if applicable

1.2.2 Optional New Hose Requirements

DIRECTIVE NO. 800-PG-8710.3.1A Page 4 of 29

04/14

If the requirements of Section 1.2.1 are not available from the manufacturer, or if the hose is internally manufactured, testing shall be performed per Section 1.2.1.4 by a competent test organization approved by the PV/S Manager (PSM) or designee.

The results of Section 1.2.1.4 and data supporting the requirement of Section 1.2.1.3 shall be submitted to the PSM and once accepted; a hose tag will be created and attached.

1.3 Type III Flex Hose Assembly

A Type III Flex Hose Assembly is a utility hose which is not a permanently installed, mobile, or special purpose hose for use with equipment where the normal working pressure is at 150 psig or below and the hose ID is ½” or less. This flex hose assembly may be used for the transport of all media except hazardous/toxic/cryogenic fluids. If the hose does not meet the above definition, then it is by definition a Type II hose.

NOTE: Shop air hoses are an example of a Type III Flex Hose Assembly. Type III flex hoses will not be discussed further in this document.

2.0 IDENTIFICATION REQUIREMENTS

2.1 Type I Flex Hoses

Type I flex hoses shall be identified with a metal tag containing the drawing number and the find number or reference designator as specified in the design drawing.

2.2 Type II Flex Hoses

2.2.1 The hose shall have the manufacturers tag affixed to the hose. (See Section 1.2.1.5)

2.2.2 The hose shall have an Identification Tag affixed to the hose containing the information shown in Figure 1. The “PVS Ident. Number” is a unique identifier assigned by the PSM associated with a unique hose and used to track data associated with the hose.

2.2.3 The hose shall have a visual inspection record attached to the back of the Identification Tag by the PVS group. (Figure 2)

The hose shall not be used beyond the listed expiration date.

2.2.4 The hose shall have a hose usage tag installed containing the following information (as shown in

Figure 3):

• Approved Media (GN2, GHe, BAir, Oxidizers, GOX, N2 H4, etc.)

• Operating Temp Range

• MAWP

• Size (1/2 in x 20ft, ¼ in x 40ft, etc.)

DIRECTIVE NO. 800-PG-8710.3.1A Page 5 of 29

• Cleanliness Level – (500D, 300A, etc.) when applicable

Figure 1. Hose Identification Tag

Figure 2. Visual Inspection Decal

Figure 3. Hose Usage Tag

PVS IDENT #

MANUFACTURER

P/N

GHE GN2 BAIR

TEMP -40 160F

MAWP 6000 PSIG

SIZE 1/2X30 FT

CLEAN 300D

DIRECTIVE NO. 800-PG-8710.3.1A Page 6 of 29

2.3 Requirements for Metal Tags

2.3.1 Metal tags (dog tags) as required by this document shall be fabricated from stainless steel or aluminum and marked in accordance with Sections 2.2.2 and 2.2.4.

2.3.2 The tags shall have no burrs or sharp edges which could tear or cut personnel or safety clothing such as Self Contained Atmospheric Protective Ensemble (SCAPE) suits.

2.3.3 Tags shall be attached to the flex hose assembly with stainless steel cable or number 16

American Wire Gauge (AWG) stainless steel wire and secured using an aluminum or stainless steel ferrule installed such that there are no exposed wire ends which could puncture skin, clothing, or gloves.

2.3.4 Tags should be installed within approximately 18 inches of each end of the hose. In the event the hose is shorter than 6 feet, the requirement to install tags (2) at each end of the hose is waived and one set of the tags shall be installed roughly in the center of the hose.

2.3.5 When tags or the attaching wires become damaged/frayed/illegible (as applicable), the owner shall repair/replace the tags.

3.0 INSPECTION CRITERIA

3.1 Type I Flex Hoses

The inspection criteria for Type I flex hoses shall be defined within the engineering drawing.

3.2 Type II Flex Hoses

The user shall perform the following inspections each time prior to putting the hose in service:

a. Check for broken braid or braid not secured to the end fitting. Broken or unsecured wires are not permitted. If the breaks are due to chafing, locate the source and either reroute, clamp, or use a suitable chafing guard.

b. Inspect welded and brazed fittings for cracks, corrosion, or discontinuities. No discrepancies are allowed.

c. Inspect all parts of the flex hose assembly for evidence of deformation, flattened areas, cut or broken braid, corrosion, or deterioration. No discrepancies are allowed.

d. Verify that the flex hose assembly has all required identification in accordance with Section 2 of this document.

e. Verify that the flex hose assembly is identified for the commodity type being transferred.

f. Verify the hose Visual Inspection Decal is applied and the hose is within its acceptable inspection life (current date is not after expiration date).

DIRECTIVE NO. 800-PG-8710.3.1A Page 7 of 29

4.0 INSTALLATION

4.1 Type I Flex Hoses

Type I Flex Hoses shall be installed per the Design Drawing.

4.2 Type II Flex Hoses

4.2.1 General Installation

The user shall perform the following tasks prior to putting the hose in service:

a. Verify pre-use inspection per Section 3.2 has been performed.

b. When required, verify that hoses have been properly controlled for cleanliness and that no visible evidence of contamination exists. Verify the cleanliness level specified on drawings, required in the operations procedure, or specified in the program/project plan has been accomplished and that the hose bears cleanliness certification.

c. Verify the hose will be used within its allowable temperature range.

d. Maintain cleanliness control while removing protective caps, plugs, or covers from flex hose and fittings and connecting fittings. Do not reuse caps, plugs, or covers unless they have been verified to be clean.

e. Ensure the flex hose and fittings and the fitting to which the flex hose is to be connected are free of chips, burrs, dents, nicks, pits, gouges, or foreign material that could endanger proper operation.

f. Visually inspect welded and brazed fittings for cracks, corrosion, or discontinuities. Inspect end fitting for cracks, tripping, or galled threads.

g. Verify that all seals and/or sealing surfaces are in good condition. If any defect/deterioration is detected, seals must be changed-out prior to installation.

h. Teflon tape shall be applied to male pipe thread fittings counter to the direction of tightening, leaving the forward two threads bare.

i. Lubrication of straight fitting threads shall be accomplished using a minimal amount of Krytox 240

AC or other approved lubricant. Do not allow lubricant to enter flow path. Lubricant shall be applied to male threads only after the respective nut has been started one complete turn.

j. Install flex hose in a neat and orderly manner and route in a manner that will not place an additional load on the hose or connecting hardware. (Reference Figures 4 through 9)

k. Avoid sharp bends in the flex hose and ensure that the bend radius is greater than the manufacturer’s minimum recommended bend radius. When not specified, the minimum bend radii shall be five (5) times the outside diameter of the hose. (Reference Table 1)

l. For large diameter flex hose, use transfer line saddles as specified in design drawings to support the hose as applicable.

m. While ensuring that the flex hose does not turn or twist and, where applicable, using appropriate type and size wrench, tighten to manufacturer’s recommended torque. If there is not a torque

DIRECTIVE NO. 800-PG-8710.3.1A Page 8 of 29

04/14 recommended or supplied within the procedure, use torque from Reference Table 2. Use of a backup wrench is recommended on B-nut type fittings.

n. Perform inspection of assembled hose for twist, kinks, excessive bends, fully secured restraints, and freedom of motion where applicable.

4.2.2 Installation to Flight Vehicle Interface

When flex hoses are routed through vehicle access doors and no equipment exists to provide support and/or protection to the flex hoses, the following guidelines should be used:

a. The flex hoses should be secured to the support structure using tie-wraps at approximately 12 inches or as close to the entry point as possible from the point of ingress to the flight vehicle. Wherever possible, flex hoses should be routed to the side or top of the access door/hatch of the flight vehicle.

b. The flex hoses should be attached starting at the flight vehicle interface and working back to the source and routed through areas of minimal traffic.

c. Tie-offs to movable platforms should have a “fluorescent orange” tag attached to each tie point to ensure removal prior to platform movement.

d. Edge protection to the flight vehicle and flex hoses routed through the door or hatch shall be provided.

e. Vehicle drag-on hoses should include tie-offs as close to the vehicle entry point as is practical and shall be tied to an end point of sufficient strength to resist the forces associated with a failed hose.

NOTE: Tie-offs are not allowed on tubing, electrical harness, or any sensitive equipment.

f. Flex hose routing in or near the flight vehicle should be adequately restrained to protect the vehicle, hoses, and Ground Support Equipment (GSE) from damage and to preclude potential personnel injury.

g. Routing of flex hoses on the floor is undesirable. Where routing of flex hoses on the floor/platform surface becomes the only viable alternative, covers should be used and/or the area should be roped off for controlled access.

4.2.3 Special Instructions

When installing or disconnecting a flex hose from a hardline system resulting in a loose hose end, ensure that the hose end is capped/plugged, properly integrity sealed and secured.

DIRECTIVE NO. 800-PG-8710.3.1A Page 9 of 29

Figure 4. Twisted/Untwisted Hose Installation

DIRECTIVE NO. 800-PG-8710.3.1A Page 10 of 29

Figure 5. Short/Large Bend Radii Hose Installation

NOTE:

KEEP THE BEND RADII OF THE HOSE AS LARGE AS

NECESSARY TO AVOID KINKING OF LINE AND

RESTRICTION OF FLOW, AND CONSISTENT WITH

MANUFACTURER’S LIMITATIONS

DIRECTIVE NO. 800-PG-8710.3.1A Page 11 of 29

Figure 6. Tight/Slack Hose Installation

DIRECTIVE NO. 800-PG-8710.3.1A Page 12 of 29

Figure 7. Elbow/Adapter Hose Installation Usage

DIRECTIVE NO. 800-PG-8710.3.1A Page 13 of 29

Figure 8. Flexing/Vibrating Hose Installation

DIRECTIVE NO. 800-PG-8710.3.1A Page 14 of 29

Figure 9. Fireproof/Metal Baffle Hose Installation Usage

DIRECTIVE NO. 800-PG-8710.3.1A Page 15 of 29

TYPE I AND TYPE II FLEX HOSE MINIMUM BEND RADIUS

HOSE SIZE

(ID INCH)

MINIMUM BEND RADIUS

(INCH)

¼ 3

3/8 5

½ 5-3/4

¾ 7-3/4

1 9-5/8

1-1/4 11

1-1/2 14

2 22

Table 1 - Flex Hose Minimum Bend Radius

DIRECTIVE NO. 800-PG-8710.3.1A Page 16 of 29

Table 2 – Flex Hose Fitting Torque Values

DIRECTIVE NO. 800-PG-8710.3.1A Page 17 of 29

5.0 CONTAINMENT/RESTRAINT AND SAFETY REQUIREMENTS

5.1 Type I Flex Hoses

Type I Flex Hoses shall be restrained per the Engineering Drawing requirements.

5.2 Type II Flex Hoses

Type II Flex Hoses which are six feet long or greater shall be installed so that restraint is provided on both the hose and adjacent structure at no greater than six- foot intervals and at each end to prevent whipping in the event of a burst.

Restraining devices shall be designed and demonstrated to contain a force not less than 1.5 times the open-line pressure forces. (See Table 3).

The manufacturers rated working load for the restraint shall be at least equal to 1.5 times the open line force working load.

NOTE: For example, for a ¼” inside diameter flex hose at 5000 psig, the restraint rating would be 0.2832 x 5000 x 1.5 = 2142 lbs.

Do not use hose clamp type restraining devices.

Table 3 - Open Line Force Calculation Factor

DIRECTIVE NO. 800-PG-8710.3.1A Page 18 of 29

5.2.1 Restraint Types and Limitations on Use

Hose restraint, regardless of type, must be supplied from the manufacturer as hose restraints and not as

“pulling grips” or as “support slings”. All flex hose restraints shall be manufactured from stainless steel cable.

Currently, three manufacturers are recognized as supplying acceptable flex hose restraints:

a. Kellems Division of Hubbell Wiring Devices

b. American Iron Works, Whip Sock, located in Oklahoma

c. AMTEK Corporation, Plainfield, CT.

Additional suppliers may be acceptable with PSM review and approval.

5.2.1.1 Containment Style Restraints

This type of restraint can be used with any style or pressure of hose provided the strength requirements of Section 5.2 and Table 3 are met. The manufacturers will request from the user the inside diameter of the hose, the media, and the MAWP of the hose to allow them to size the restraint. The end fittings shown in Figure 10 may not be available from all manufacturers.

All containment style hose restraints require the installation of a Stainless Steel worm style hose clamp located within 1 ½ inches of the weave end of the hose restraint (opposite the hose end) and tightened finger tight but less than 25 in-lbs torque.

DIRECTIVE NO. 800-PG-8710.3.1A Page 19 of 29

Figure10. End Fittings - Containment Style Hose Grips

DIRECTIVE NO. 800-PG-8710.3.1A Page 20 of 29

04/14

5.2.1.2 Universal Bale (sliding bar style).

This type of restraint may be used to confine hose ends and unions where substantial structural attachment points are available and the following limitations are met:

a. These restrains are prohibited from use on hose sizes less than ½ inch ID at any pressure or any diameter hose above 3000 psig operating pressure.

b. These restraints may be used on ½ inch ID and larger hoses to a maximum diameter and pressure as follows:

• ½” ID = 3000 psig maximum

• ¾” ID = 2150 psig maximum

• 1” ID = 1650 psig maximum

c. The bale must be tightly secured to the flex hose by a properly applied tie-wrap, 5/16 inch wide by a minimum of 6 inches long which uses a metallic locking tab (Federal Stock

Number (FSN) 5975-C-838-7450 or FSN 5975-00-838-7450 or equivalent). The tie-wrap must pass between the base nipples as they protrude through the keeper bar and around the hose (Reference Figure 11).

d. The tie-wrap shall be drawn as tight as possible to secure the base cables against the hose.

Excess tie-wrap may be cut off and corners chamfered to remove sharp edges. The structural attachment does not need a tie-wrap unless sliding of the base would cause slack in the restraint.

e. The bale hose attachment bolt shall be between 9 and 11 inches from the hose fitting.

f. There shall be a minimum amount of slack in the restraint, but it should not be so tight as to introduce a load onto the flex hose. Maximum slack should be 1 inch for every 6 inches of bale.

g. Reference Figure 12 and Figure 13 for approved restraint installation configuration.

h. Restraints with bronze keeper bars shall not be used within 25 feet of lines or systems containing ammonia or hypergolic propellants.

DIRECTIVE NO. 800-PG-8710.3.1A Page 21 of 29

Figure11. Tie-Wrap Installation

DIRECTIVE NO. 800-PG-8710.3.1A Page 22 of 29

Figure12. Kellems Support Sling (AMTEK Similar) shock

DIRECTIVE NO. 800-PG-8710.3.1A Page 23 of 29

Figure 13. Universal Bale Flex Hose Restraint Configuration

DIRECTIVE NO. 800-PG-8710.3.1A Page 24 of 29

04/14

5.2.2 Flex hose Stress

Design flex hose installations so that they shall not produce stress or strain in the hard lines or components beyond their design limits. Include stresses induced because of dimensional changes caused by pressure or temperature variations, or torque forces induced in the flex hose.

5.2.3 Temporary Installations

Temporary installations using chains or cables anchored to substantial fixed points, lead ingots or other weights are acceptable providing they meet the strength requirements of Section 5.2 and Table 3.

Protect the flex hose from kinking or abrasive chafing from the restraining device or damage from adjacent structures or moving parts that may cause reduction in strength. If anchor points are not available, the hose may be secured with 50-pound sand bags, lead ingots, proof load weights, or other suitable weights at intervals not to exceed 6 feet (two twenty-five pound weights may be used if they are applied at the same point on the hose = 50 pounds). Ensure that the hose is not chafed by the ground and if necessary the hose may be padded with the sand bags.

NOTE: DO NOT place the lead ingots or proof load weights directly on the hose.

6.0 TRANSPORTATION AND STORAGE

6.1 Type I Flex Hoses

When not installed into the assembly, transport and store Type I flex hoses in accordance with the requirements for Type II flex hoses.

6.2 Type II Flex Hoses

6.2.1 Storage

When storing flex hoses, the following criteria shall apply:

a. Flex hoses shall be stored in an indoor protected area with hose coils supported by hangers (not a single point), or lying flat on storage shelves or in drawers. Store hypergol-contaminated flex hoses in the same manner but in designated area approved by the WFF Safety Office.

b. Large diameter (greater than 1-1/4 ID) flex hoses shall be stored on racks that support the flex hose at various places along its length.

c. Cryogenic flex hoses should be placed in a suitable storage rack that allows maintaining cleanliness and dryness as required for the particular system involved.

6.2.2 Transportation

When transporting flex hoses, the following criteria shall apply:

a. Coil the flex hose and secure coils together. Coil radius shall be greater than the rated minimum bend radius (Reference Table 1). Place large diameter hose, such as cryogenic transfer hose, on a flat horizontal surface straight or in the form of a “U”.

b. Avoid placing any items such as tools, tool boxes, materials, etc., on top of the flex hose.

c. Avoid dragging the flex hose on the ground or hard surfaces.

DIRECTIVE NO. 800-PG-8710.3.1A Page 25 of 29

Appendix A – Definitions

A.1 Hydrostatic Test - A water pressure test of the hose when manufactured and as required thereafter by the design-controlled drawing to verify mechanical integrity and absence of leaks in the hose assembly. The hose must not be damaged or deformed or leak when subjected to its required pressure. The hydrostatic pressure is a minimum of 1 ½ times the hose’s maximum allowable working pressure (MAWP) unless otherwise specified by the design-controlled drawing or the manufacturer’s specification.

A.2 Hose Identification Tag and Visual Inspection Tag - A metal dog tag bearing critical data which allow the hose to be tracked back to the manufacturer and the manufacturer’s part number.

On the back of the metal tag, a flexible Visual Inspection Tag (decal) is attached which carries the date the hose received a visual inspection and the due date for the next required manual inspection. (Ref. Figure 1 and Figure 2). Per paragraph 2.2.2, a hose Identification Tag contains the following information:

• PVS Issued Identification Tracking Number

• Manufacturers Name

• Manufacturers Part Number

A.3 Hose Usage Tag - A metal dog tag which provides additional data regarding approved media, operating temp range, MAWP and cleanliness requirements, when applicable. (Reference Figure

3.) The Hose Usage Tag contains the following information:

• Approved Media (GN2, GHe, BAir, Oxidizers, GOX, N2 H4, etc.)

• Operating Temp Range

• MAWP

• Size (1/2 in x 20ft, ¼ in x 40ft, etc.)

• Cleanliness Level – when applicable

A.4 Pneumatic Test - A gas pressure test of the hose to verify mechanical integrity and an absence of leaks in the hose assembly. Such a test is to be performed only as required by special engineering instructions and no less frequently than every 5 years. The hose shall not be damaged or deformed or leak when subjected to 110% of the rated working pressure of the hose..

A.5 Pressure System - A system containing a gas or liquid media at greater than or less than ambient pressure. Pressure systems are subject to review and certifications under NASA-STD-8719.17 at all pressures. Specific category exclusions or assessed hazard exclusions may apply (see NASA-

STD-8719.17, section 4.2).

A.6 Reference Designator (Find Number) - An alphanumeric combination that provides a unique system identification of each flex hose as designated by the applicable design drawing (used for

Type I hoses only).

DIRECTIVE NO. 800-PG-8710.3.1A Page 26 of 29

04/14

A.7 Serial Number - A unique number assigned by the manufacturer to a specific flex hose to provide traceability.

A.8 System Test - A leak test of the hose while installed in the system. No leakage is allowed when subjected to the maximum system working pressure.

A.9 Type I Flex Hose Assembly - A permanently installed, dedicated hose whose installation and placement are indicated by design-controlled engineering drawings. Once installed, the flex hose is considered to be an integral part of that installation. Type I hoses have an assigned drawing reference designator. Type I hoses shall be certified as part of the overall pressure system per

NASA-STD-8719.17 and the retest requirement shall be determined as part of the system certification and maintenance plan.

A.10 Type II Flex Hose Assembly – A non-permanently installed and assigned, non-dedicated flex hose whose installation is authorized and controlled by a procedure. Hose identification and operating requirements will be established by the controlling procedure.

A.11 Type III Flex Hose Assembly - A utility hose which is not permanently installed, mobile, or special purpose hose for use with equipment where normal working pressure is 150 psig or below. This flex hose assembly may be used for the transport of all media except hazardous/toxic fluids. Shop air hoses are an example of a Type III Flex Hose Assembly. Type

III flex hoses that are ½” ID or less, and are used below 150 psig are exempted from these requirements.

DIRECTIVE NO. 800-PG-8710.3.1A Page 27 of 29

Appendix B – Acronyms

AWG American Wire Gauge

FSN Federal Stock Number

GSE Ground Support Equipment

ID Inside Diameter

MAWP Maximum Allowable Working Pressure

NIOSH National Institute for Occupational Safety and Health

PSM Pressure Systems Manager

PV/S Pressure Vessels & Pressurized Systems

SATERN System for Administration, Training, and Educational Resources for NASA

SCAPE Self Contained Atmospheric Protective Ensemble

UL Underwriter’s Laboratory

DIRECTIVE NO. 800-PG-8710.3.1A Page 28 of 29

Appendix C – Material Restrictions

1. Flex hose used for hypergolic fluids shall be permanently dedicated to that commodity shall not be used in any other system.

2. Flex hoses used for hydrogen service shall not contain any 17-4PH stainless steel parts that could come in contact with the media, nor shall 17-4PH stainless steel be specified in any procedure applicable to hydrogen service.

3. Flex hoses used for oxygen service shall be only those specified as being oxygen compatible and shall be dedicated to that commodity. They are prohibited from use in any other system.

4. Flex hoses or containment/restrains made of copper or copper containing materials shall not be used for ammonia or hypergolic fluids.

DIRECTIVE NO. 800-PG-8710.3.1A Page 29 of 29

CHANGE HISTORY LOG

Revision Effective Date Description of Changes

Baseline

6/26/14 Initial Release

6/13/19 Administratively extended for 1 year

5/13/20 Administratively extending for 1 year

A

07/29/2021

Administratively extending for 1 year while document is being converted to a GSFC Technical Standard