This document is a comprehensive table detailing federal facility energy management requirements across three key legislative acts: the Energy Policy Act of 2005, the Energy Independence & Security Act of 2007, and Executive Order 13834 for Efficient Federal Operations. The requirements cover multiple areas including energy intensity reduction, renewable energy consumption, building metering, energy and water efficiency measures, building performance standards, leasing guidelines, energy-efficient product procurement, and water reduction strategies.
Key requirements include mandates such as 3% annual energy reduction from 2003 baseline, increasing renewable electricity consumption percentages, installing meters in federal buildings, designating facility energy managers, conducting energy audits, benchmarking building performance, procuring Energy Star products, and reducing potable and non-potable water consumption by 20% from 2007 baseline. The document provides a detailed crosswalk of evolving federal energy efficiency regulations, tracking changes and additions across different legislative periods from 2005 to 2018, with specific section references for each requirement.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140F1B25R0004_Amd_0001.pdf | ||
| Phase_I___Request_for_Information_(RFI)_Summary_0001.pdf | ||
| 7__Design_Build_General_Requirements_(1).pdf | ||
| 11__General_Requirement.pdf | ||
| 1__Statement_of_Work_(SOW).pdf | ||
| 4__360_FW4_Construction_Management.pdf | ||
| 6__CHK_Office_Space_Design.pdf | ||
| Sol_140F1B25R0004.pdf | ||
| 2__16_CADD_Stds_January_2016.pdf | ||
| 3__360_FW_1_-_Summary_of_Construction_Permits.pdf | ||
| 10__USFWS_Submittal_Exchange_Template_(D-B).pdf | ||
| 5__CHK_Bunkhouse_Design_Checklist.pdf | ||
| 9__PreOccupancyResidentialChecklist.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11‐7‐2018
FACILITY ENERGY MANAGEMENT REQUIREMENTS
Topic Energy Policy Act of 2005 (EPAct 2005)
(P.L. 109‐58) Aug 8, 2005
Energy Independence & Security Act of 2007
(EISA) (P.L. 110‐140)
Dec 19, 2007
Executive Order 13834 Efficient Federal Operations
May 17, 2018 Energy Intensity Reduction
Superseded 3% Annual Energy Reduction (2008 ‐ 2015) from 2003 Baseline ‐ 30% by 2015 [Sec 431]
Achieve and maintain annual reductions in building energy use and demonstrate incremental reduction [Sec 2(a)]
Renewable Energy Consumption
Renewable electricity consumed as a percent of facility electricity use:
3% FY2007 – FY2009
5% FY2010 – FY2012
7.5% FY2013 and beyond
[Sec 203]
For each new Federal building or major renovation, if LCC effective, not less than 30% of the hot water demand shall be met through installation and use of solar hot water heaters.
[Sec 523]
Meet statutory requirements relating to the consumption of renewable energy and electricity [Sec 2(b)]
Building Metering Install electric meter all appropriate 1Federal buildings by 2012 [Sec 103]
No later than October 1, 2016, install meters for natural gas and steam at appropriate buildings.
[Sec 434(b)]
Install water meters in federal buildings where appropriate and in accordance with FEMP guidance.
[EO Imp Instr Sec 7‐Draft]
Energy & Water Efficiency Measures
(EISA Covered Facilities2)
Designate a Facility Energy Manager for each covered facility
Annually report covered facilities footprint data in FEMP’s Compliance Tracking System (CTS) – energy & water consumption, GSF
Conduct energy and water evaluations (audits) in 25% of covered facilities annually, so that every facility is evaluated once every 4 years. Identify energy and water efficiency measures and report findings (implementation cost, energy/water savings, energy/water cost savings) in CTS
1 See FEMP’s Metering Guidance for “appropriate” building criterion.
2 Covered facilities are agency designated facilities that comprise at least 75% of their total facility energy use. A covered facility may be defined as a group of facilities at a single location or multiple locations managed as an integrated operation. A covered facility may also be a single building, if so identified by the agency.
Topic Energy Policy Act of 2005 (EPAct 2005)
(P.L. 109‐58) Aug 8, 2005
Energy Independence & Security Act of 2007
(EISA) (P.L. 110‐140)
Dec 19, 2007
Executive Order 13834 Efficient Federal Operations
May 17, 2018 Report implemented energy and water conservation projects at covered facilities in CTS (implementation costs, funding source, energy/water savings, renewable energy generation)
Conduct follow‐up activities (M&V) on implemented projects to verify savings and report findings in CTS
Benchmark metered buildings over 5000 GSF in Energy Star Portfolio Manager and export data into CTS. (Building level monthly energy consumption and cost, operation hours, occupancy, # of computers, location, etc.)
Most data in CTS is public access.
[Sec 432]
Building Performance
New buildings designs must be 30% more energy efficient than relevant code, if cost effective, or highest efficiency attained that is cost effective.
[Sec 109]
New building designs or major renovations shall reduce fossil fuel‐generated energy consumption 55% (2010) compared to 2003 similar building so that by 2030 achieves a 100% reduction of fossil fuel‐generated energy consumption3.
[Sec 433]
Leasing Beginning 2011, no Federal agency shall enter into a contract to lease space in a building that has not earned the Energy Star label. Exceptions:
No space available that meets functional needs Agency proposes to remain in building previously occupied
3 FEMP has not implemented regulations regarding the requirement of EISA Sec 433 for fossil fuel reduction.
Topic Energy Policy Act of 2005 (EPAct 2005)
(P.L. 109‐58) Aug 8, 2005
Energy Independence & Security Act of 2007
(EISA) (P.L. 110‐140)
Dec 19, 2007
Executive Order 13834 Efficient Federal Operations
May 17, 2018 Building or space w/in a building is of historical, architectural, or cultural significance Lease is for less than 10,000 gsf
Buildings w/o Energy Star label includes provisions requiring prior to occupancy or 1 yr after signing lease for previously agency occupied space, the space is renovated to include all energy efficient improvements that are LCC effective over the life of the lease.
[Sec 435]
Energy Efficient Products and Procurement
Energy Star® or Federal Energy Management Program (FEMP) designated products must be procured for available energy consuming products.
[Sec 104]
Directs agencies to purchase products that use not more than 1 watt in standby power or if not available, the lowest wattage available.
[Sec 524]
Energy Savings Performance Contracts
Permanently reauthorization of ESPC.
[Sec 514]
Utilize performance contracting to achieve energy, water, building modernization, and infrastructure goals.
[Sec 2(d)]
Life Cycle Cost Analysis
For building energy systems ‐ analysis period changed from 25 years to 40 years.
[Sec 441]
Stormwater Management
Maintain or restore, for Federal properties over 5,000 square feet, the property’s pre‐ development hydrology as to temperature, rate, volume, and duration of flow.
[Sec 438]
Reporting & Tracking Each Federal Agency must issue an annual report that describes the status of initiatives
Topic Energy Policy Act of 2005 (EPAct 2005)
(P.L. 109‐58) Aug 8, 2005
Energy Independence & Security Act of 2007
(EISA) (P.L. 110‐140)
Dec 19, 2007
Executive Order 13834 Efficient Federal Operations
May 17, 2018 to improve energy efficiency, reduce energy costs, and reduce GHG emissions.
[Sec 527]
Water Reduction Reduce potable and non‐potable water consumption [Sec 2 (c)] Achieve 20% water use intensity reduction from the 2007 baseline and demonstrate annual progress [EO Impl Instr Sec 3]