8. North Kansas City Appendix A.4 _ VA CBOC Information Transport Systems Specifications.pdf

PDF 3 MB Posted

Attached to
X1DB--North Kansas OPC 123, 283 ANSI/BOMA 135, 611 RSF
Solicitation number
36C10F25R0034
Issued by

About this file

This document is a detailed Information Transport Systems Specification for a Community Based Outpatient Clinic (CBOC) developed by the Department of Veterans Affairs Office of Information and Technology. The specification provides comprehensive technical requirements for telecommunications infrastructure, including rack and equipment configurations, power distribution, grounding, and cabling standards.

Key technical specifications include standardized rack elevations with Catalyst 3850 network switches, zone power distribution units (PDUs) with dual power inputs, rack-mounted UPS systems, and precise bonding and grounding protocols. The document outlines detailed requirements for patch panels, cable management, work area outlets, and telecommunications enclosures, specifying everything from cable tray sizes to outlet configurations. The specifications are designed to ensure a standardized, robust, and scalable telecommunications infrastructure for VA healthcare facilities, with a focus on reliability, power redundancy, and proper equipment installation and connectivity.

View the file

Other files

File Type Posted
36C10F25R0034 0003.docx DOCX document
VA OPC Kansas City_ MO_ RLP No_36C10F25R0034 _ Amendment No_ 3.pdf PDF
VA OPC Kansas City_ MO - RLP No_ 36C10F23Q0091 - Amendment No_ 2.pdf PDF
VA Northland KC QA Log _2025_06_17_ - FINAL.pdf PDF
36C10F25R0034 0002.docx DOCX document
Pre-bid Presentation - OPC N Kansas City _6_5_25.pdf PDF
VA OPC _ Northland Kansas City _ Pre-Bid Conference - Final Transcript.pdf PDF
VA OPC Kansas City MO RLP No 36C10F25R0034 Amendment No 1.pdf PDF
30 Pre-Bid Registration Form Updated.pdf PDF
36C10F25R0034 0001.docx DOCX document
3. North Kansas City Agency Specific Requirements_ASR - Cover Page.docx DOCX document
24. North Kansas City GSA Form 3517B - General Clauses.pdf PDF
18. North Kansas City VA Form 10091 _ VA-FSC Vendor File Request Form.pdf PDF
22. North Kansas City VA Handbook 6500.6.pdf PDF
13. North Kansas City Offering Entity Acknowledgement Form.docx DOCX document
36C10F25R0034.docx DOCX document
9. North Kansas City Appendix A.4.1 _ OIT Data Center Design Narrative.pdf PDF
15. North Kansas City Proposal to Lease Space _GSA Form 1364.pdf PDF
21. North Kansas City GSA Form 527 - Contractor's Qualifications and Financial Information.pdf PDF
26. North Kansas City Certification of Building Energy Performance.docx DOCX document
20. North Kansas City SF-330 _ Architect-Engineer Qualifications.pdf PDF
1. North Kansas City Global RLP GSA Template R100 for VA.pdf PDF
11. North Kansas City Appendix A.6 - Conceptual Floor Plan - 1st Floor.pdf PDF
27. North Kansas City DOL Wage Determination.doc DOC document
7. North Kansas City Appendix A.3 - Room Data Matrix.pdf PDF
11A. North Kansas City Appendix A.6 - Conceptual Floor Plan - 2nd Floor.pdf PDF
17. North Kansas City GSA Form 1217 - Lessor's Annual Cost Statement.pdf PDF
19. North Kansas City Past Performance Questionnaire.docx DOCX document
5. North Kansas City Appendix A.1 Project Room Contents.xlsx XLSX spreadsheet
2. North Kansas City Global Lease GSA Template L100 for VA.pdf PDF
6. North Kansas City Appendix A.2 - Lease Design Narrative.docx DOCX document
16. North Kansas City Attachment No. 1 to GSA Form 1364.xlsx XLSX spreadsheet
12. North Kansas City Appendix B Janitorial Services and Site Management.docx DOCX document
4. North Kansas City Appendix A - Program for Design.pdf PDF
14. North Kansas City Offeror Proposal Compliance Matrix.docx DOCX document
29. North Kansas City Northland Electric Vehicle Supply Equipment_EVSE_ Requirements.docx DOCX document
28. North Kansas City FAR 52.204-24 Representation Regarding Certain Telecom.pdf PDF
30. North Kansas City Pre-Bid Registration Form.pdf PDF
25. North Kansas City GSA Form 12000 for Prelease Fire Protection and Life Safety Evaluation for an Office Building.pdf PDF
10. North Kansas City Appendix A.5 - VA Lease Security Requirements_Level II.docx DOCX document
23. North Kansas City GSA Form 3516 _ Solicitation Provisions.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT:

DRAWING No:

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 1 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

COVER

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

DEVELOPED BY:

DATA CENTER AND INFRASTRUCTURE ENGINEERING

COMMUNITY BASED OUTPATIENT CLINIC (CBOC)

INSIDE PLANT

INFORMATION TRANSPORT SYSTEMS SPECIFICATIONS

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 2 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

LEGEND

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

LEGEND

ELECTRICAL

NOTES

TYP

DETAIL NUMBER

TYPICAL THROUGHOUT THIS

SHEET

ELECTRICAL

BONDING BUSBAR

ARCHITECTURAL

TELECOMMUNICATIONS TELECOMMUNICATIONS

ARCHITECTURAL

DETAIL NUMBER#

TYP

DETAIL NUMBER

DETAIL NUMBER

TYPICAL THROUGHOUT THIS SHEET

40" TELECOMMUNICATIONS CABINET WITH HORIZONTAL CABLE

CUTOUTS AND APPROPRIATE CABLE MANAGEMENT

ACCESSORIES, SUPPORTING 5KW REDUNDANT

DEMO WALL

NEW WALL

MECHANICAL MECHANICAL

CHANGES TO DESIGN WILL REQUIRE A NEW COMPUTATIONAL FLUID

DYNAMICS (CFD) ANALYSIS TO BE PERFORMED

FLOORPLANS ARE NOT TO SCALE

DOCUMENTS ARE NOT TO BE USED FOR CONSTRUCTION

COLD AISLE CONTAINMENT (PVC CURTAIN)

1 SERVICE PROVIDER ENTRANCE POINT

SERVICE BACKBONE (ENTRANCE ROOM-MAIN COMPUTER

ROOM)

MAIN CROSS CONNECT (CAMPUS/BUILDING DISTRIBUTOR) –

BACKBONE CABLING (MCR-TELECOMMUNCIATIONS ROOMS)

ENTRANCE ROOM (TR) INTERCONNECT

HORIZONTAL DISTRIBUTION TO WORK AREA OUTLETS (WAO)

ADDITIONAL CABINETS OR TELECOMMUNICATIONS RACKS TO

MEET REQUIREMENTS.

7 HORIZONTAL DISTRIBUTION AREA – SIDE A

8 HORIZONTAL DISTRIBUTION AREA – SIDE B

9 MAIN DISTRIBUTION AREA – SIDE A

10 MAIN DISTRIBUTION AREA – SIDE B

STANDARD DENSITY CABINET SUPPORTING 5KW

REDUNDANT

12 HIGH DENSITY CABINET SUPPORTING 10KW REDUNDANT

WIRE MESH CABLE TRAY MINIMUM OF 6"X 12" WITH SECOND

LEVEL OF FIBER CHANNEL PATHWAY (4" X 4")

BLUE CABLE TRAY PATH FOR CABLES TO THE A-SIDE MDA/

HDA

YELLOW CABLE TRAY PATH FOR CABLES TO THE B-SIDE MDA/

HDA

17 TELECOMMUNICATIONS CHANNEL RACK

SECONDARY BONDING BUSBAR PLACEMENT DETERMINED BY

OTHERS

PRIMARY BONDING BUSBAR PLACEMENT DETERMINED BY

OTHERS

MINIMUM TWO 110V 20A CONVENIENCE BUILDING POWER

OUTLETS PER WALL; PLACEMENT DETERMINED BY OTHERS. 1

30 AMP 208 VOLT THREE-PHASE TWIST LOCK RECEPTACLE

(L21-30R);8.5 FT AFF {WYE (5-WIRE)} COORDINATE

INSTALLATION LOCATION WITH TELECOMMUNICATIONS

CONTRACTOR

20 AMP 208 VOLT THREE-PHASE TWIST LOCK RECEPTACLE (L21-

20R);8.5 FT AFF {WYE (5-WIRE)} COORDINATE INSTALLATION

LOCATION WITH TELECOMMUNICATIONS CONTRACTOR

SERVICE PANEL FOR RACK POWER. IT LOAD ONLY. SHALL BE

EQUIPPED WITH POWER METER; MONITORED SOLUTION

PREFERRED. PLACEMENT PER OTHERS

SERVICE PANEL FOR DEDICATED ROOM AIR CONDITIONING. NON-IT

LOAD ONLY. SHALL BE EQUIPPED WITH POWER METER;

MONITORED SOLUTION PREFERRED. PLACEMENT PER OTHERS

1. LED LIGHTING PLACED IN AISLES DIRECTLY IN FRONT OF

AND BEHIND CABINET ROWS

2. LIGHTING OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION

3. 500 LUX IN THE HORIZONTAL PLANE AND 200 LUX IN THE

VERTICAL PLANE REQUIRED MEASURED AT 3 FT AFF IN

FRONT OF AND BEHIND EQUIPMENT CABINETS

POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO

SUPPORT TEN [10] SINGLE BREAKER 208V, 20 AMP, L21-20R

BUSWAY TAPS) FED FROM A SIDE SOURCE

POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO

SUPPORT TEN [10] SINGLE BREAKER 208V, 20 AMP, L21-20R

BUSWAY TAPS) FED FROM B SIDE SOURCE

WIRE MESH CABLE TRAY SIZE COMMENSURATE

WITH REQUIREMENTS

SLEEVE WITH BUSHING FIRESTOP AND INNERDUCT FOR

FIBER

CONDUIT WITH BUSHING FIRESTOP AND INNERDUCT FOR

FIBER

SLEEVE OR CONDUIT WITH BUSHING FIRESTOP AND

INNERDUCT FOR FIBER

TELECOMMUNICATIONS CHANNEL RACK, 19" RAILS, #12-24

TAPPED EIA HOLE PATTERN, 30" DEEP CHANNEL MINIMUM, 7'

HIGH, 45RU, WHITE

VERTICAL CABLE MANAGER WITH DOOR, 6" WIDE MINIMUM

SERVER CABINET, 45U, 24"X48" (NOMINAL), SQUARE

PUNCHED RAIL, SINGLE PERFORATED FRONT DOOR, SOLID

REAR DOOR (VERTICAL EXHAUST DUCT IMPLEMENTATION),

DOUBLE PERFORATED REAR DOOR (NO VED), TWO-POINT

KEYED LOCKS, WHITE,SOLID SIDE PANELS

OR

TELECOMMUNICATIONS CABINET, 7' HIGH, 45U, 40"X48"

(NOMINAL), SQUARE PUNCHED RAIL, SINGLE

PERFORATED FRONT DOOR, SOLID REAR DOOR

(VERTICAL EXHAUST DUCT IMPLEMENTATION), TWO-

POINT KEYED LOCKS, WHITE,SOLID SIDE PANELS

OR WIRE MESH CABLE TRAY SIZE COMMENSURATE WITH

REQUIREMENTS

POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO

SUPPORT FIVE [5] SINGLE BREAKER 208V, 20 AMP, L21-20R

BUSWAY TAPS) FED FROM A SIDE SOURCE

POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO

SUPPORT FIVE [5] 208V, 20 AMP, L21-20R BUSWAY TAPS) FED

FROM B SIDE SOURCE

BLUE CABLE PATH FOR A-SIDE UPS12

YELLOW CABLE PATH FOR B-SIDE UPS13

LIGHTING:

RETURN AIR DUCT

COMPUTER ROOM AIR CONDITIONER (SEE COMPUTATIONAL

FLUID DYNAMICS REPORT FOR SIZING)

REQUIRED CLEARANCE AROUND CRACS

ELECTRICAL SERVICE PANEL

OVERHEAD POWER DROP CORD WITH L21-20 RECEPTACLE

POWER BUSWAY TAP WITH SINGLE BREAKER 3' DROP

CORD WITH L21-20R FOR STANDARD-DENSITY CABINETS

POWER BUSWAY TAP WITH DUAL BREAKER AND TWO 3'

DROP CORDS WITH L21-20R FOR HIGH DENSITY CABINETS

TYPICAL UNSWITCHED 110 VOLT, 20 AMP DUPLEX

CONVENIENCE OUTLET

AC

SPLIT PACKAGE AIR CONDITIONER OR EQUIVALENT 24/7

SUPPLY AIR TO REJECT 5KW (17,000 BTU PER

TELECOMMUNICATIONS RACK)

AC

ADDITIONAL SPLIT PACKAGE AIR CONDITIONER OR LARGER

UNIT TO REJECT HEAT FROM ADDITIONAL RACKS (17,000

BTU PER TELECOMMUNICATIONS RACK)

4'X 8' AC GRADE ¾” TRADE SIZE PLYWOOD BACKBOARD

PAINTED HIGH-GLOSS WHITE WITH TWO COATS OF FIRE

RESISTANT PAINT FOR SERVICE PROVIDER / SECURITY /

VIDEO / ET CETERA

3 FT WIDE, 8 FT HIGH DOOR, FIRE RESISTANT TO ¾ HOUR OR

MORE PER AHJ

6 FT WIDE, 8 FT HIGH DOOR, NO CENTER MULLION, FIRE

RESISTANT TO ¾ HOUR OR MORE PER AHJ

STANDARD 25% OPEN PERFORATED FLOOR TILE

C R

A C

MODULAR UPS CABINET (POWER MODULES, BATTERIES,

POWER PANELS)

LED LIGHTING

POWER BUSWAY WITH METERED HEADEND FOR B SIDE

POWER DISTRIBUTION

POWER BUSWAY WITH METERED HEADEND FOR A SIDE

POWER DISTRIBUTION

C FIXED CAMERA, PAN/TILT/ZOOM, PASSIVE INFRARED

CAMERA - DUAL TECHNOLOGY”

PIV ENABLED TWO-FACTOR AUTHENTICATION KEYPAD

M

CEILING MOUNTED MOTION SENSOR (LOCATIONS AS

REQUIRED FOR FULL ROOM COVERAGE)

MOTION SENSOR LIGHT SWITCH

J

OVERHEAD POWER DROP CORD WITH L21-30 RECEPTACLE

POWER JUNCTION BOX FOR 60A CONNECTION

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 3 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SPECIFICATIONS

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

GENERIC TELECOMMUNICATIONS MEDIA AND INTERFACE SPECIFICATIONS FOR TELECOMMUNICATION SPACES

SPECIFICATIONPRIMARY ATTRIBUTEID SECONDARY ATTRIBUTE

1 COPPER PATCH PANELS

PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)

POSITION COUNT 48

FORM FACTOR ANGLED

SIZE ONE RACK UNIT

JACK COLOR CODING A-SIDE BLUE / B-SIDE YELLOW

CASSETTE CAPACITY 12 CASSETTES OR 6 DOUBLE CASSETTES

CASSETTE USER INTERFACES LC DUPLEX CONNECTORS

FIBER DISTRIBUTION PANELS CASSETTE BACKBONE INTERFACES MPO-12

PERFORMANCE CHARACTERISTICS OM4 LASER ENHANCED 40 GBE 50/125 MULTIMODE / OS1 9/125 SINGLE MODE

FORM FACTOR ONE (1) RU

3 UTP (HORIZONTAL AND FIRST LEVEL BACKBONE)

PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)

PERFORMANCE SPECIFICATIONS MEETS OR EXCEEDS TIA-EIA-568-C.2-10, TSB-155.

JACKET COLOR BLUE (HORIZONTAL), WHITE (1ST LEVEL BACKBONE)

PERFORMANCE CATEGORY OM4 LASER ENHANCED TO 40 GIGABIT ETHERNET (GBE) / OS1 / OS2

PERFORMANCE SPECIFICATIONS

LASER OPTIMIZED 50/125 MM FIBERS WITH AT LEAST 4,700 MHZ·KM AT 850 NM /

OS1 9/125 SM FIBERS (INTRA-BUILDING) / OS2 9/125 SM (INTER-BUILDING)

FIBER (HORIZONTAL AND FIRST LEVEL BACKBONE)

MODE MULTIMODE/SINGLE MODE (DISTRIBUTION TO TRS ONLY)

JACKET COLOR AQUA (OM4) / YELLOW (OS1/2)

MEDIA CONNECTOR PRE-TERMINATED WITH MPO, TYPE A

STRAND COUNT 12 OR 24

BUNDLING LOOSE TUBE

5 UTP PATCH CORDS

PERFORMANCE CATEGORY CATEGORY 6A, 26-GAUGE, STRANDED

PERFORMANCE SPECIFICATIONS CENTER TUNED TO HORIZONTAL MEDIA

JACKET COLOR BLUE

6 FIBER PATCH CORDS MODE MULTIMODE/SINGLE MODE (PATCH CORD TO TRS ONLY)

MEDIA CONNECTOR PRE-TERMINATED WITH DUPLEX LC

JACKET COLOR AQUA (OM4) / YELLOW (OS1/2)

PERFORMANCE SPECIFICATIONS

LASER OPTIMIZED 50/125 ΜM FIBERS WITH AT LEAST 4,700 MHZ·KM AT 850 NM /

OS1 9/125 SM FIBERS (INTRA-BUILDING) / OS2 9/125 SM (INTER-BUILDING)

PERFORMANCE CATEGORY OM4 / OS1 / OS2

TERMINATION METHOD FACTORY PRE-TERMINATED

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 4 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

GENERIC HEALTH CARE FACILITY

EQUIPMENT ROOM

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY EQUIPMENT ROOM 1

AC

SERVICE PANEL FOR

DEDICATED ROOM AIR

CONDITIONING. NON-IT

LOAD ONLY. SHALL BE

EQUIPPED WITH

SCHNEIDER EM3500

SERIES DIN RAIL METER

OR EQUIVALENT

SERVICE PANEL FOR RACK

POWER IN

TELECOMMUNICATION ROOM.

IT LOAD ONLY. SHALL BE

EQUIPPED WITH SCHNEIDER

EM3500 SERIES DIN RAIL

METER OR EQUIVALENT

TWO (2) CONDUITS

INTERCONNECTING NETWORK

SUPPORT CENTER WITH

ENTRANCE FACILITY. TRADE SIZE

CONDUIT OR SLEEVES WITH BUSHING AND

FIRESTOP OR OTHER AHJ-APPROVED

PENETRATION FOR HORIZONTAL

DISTRIBUTION FROM WORK AREA OUTLETS

AND TELECOMMUNICATION ROOMS

L21-30R

PRIMARY OR

SECONDARY BONDING

BUSBAR (PBB/SBB)

WIRE MESH CABLE TRAY SIZE

COMMENSURATE WITH

REQUIREMENTS

VERTICAL CABLE MANAGER WITH

DOOR, 6" WIDE

TYPICAL UNSWITCHED DUPLEX

CONVENIENCE OUTLETS

SPLIT PACKAGE AIR

CONDITIONER (32,600 BTU/H)

AC

L21-30R

ADDITIONAL SPLIT PACKAGE AIR

CONDITIONER (32,600 BTU) WHEN

NECESSARY

T

AIR CONDITIONER THERMOSTAT

TELECOMMUNICATIONS CHANNEL

RACK, 19" RAILS, #12-24 TAPPED

EIA HOLE PATTERN, MINIMUM 30"

DEEP, 7' HIGH, 45RU, WHITE

SERVER CABINET, 45U, 24"X48"

(NOMINAL), SQUARE PUNCHED

RAIL, SINGLE PERFORATED FRONT

DOOR, SOLID REAR DOOR, TWO-

POINT KEYED LOCKS, WHITE,SOLID

SIDE PANELS

3'-0"

RK-1 RK-2 RK-3 RK-4

NOTE:

THERE SHALL BE A MINIMUM OF ONE

TELECOMMUNICATIONS ROOM (TR) PER FLOOR.

THE EQUIPMENT ROOM CAN SERVE AS A TR.

ADDITIONAL ROOMS SHOULD BE PROVIDED WHEN:

A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2

(10 000 FT2);

OR

B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE

WORK AREA EXCEEDS 90 M (295 FT).

NO RAISED FLOOR.

C

PIV/

KEYPAD

• MINIMUM 170 FT2

• STATIC DISSIPATING FLOOR

• NO DROP CEILING

• SLAB TO DECK ABOVE 12 FT

MINIMUM (16 FT PREFERRED)

• WALLS FULL HEIGHT TO DECK

ABOVE

4'X 8' AC GRADE ¾” TRADE

SIZE PLYWOOD BACKBOARD

PAINTED HIGH-GLOSS WHITE

WITH TWO COATS OF FIRE

RESISTANT PAINT FOR

SERVICE PROVIDER

EQUIPMENT

4'X 8' AC GRADE ¾” TRADE

SIZE PLYWOOD BACKBOARD

PAINTED HIGH-GLOSS WHITE

WITH TWO COATS OF FIRE

RESISTANT PAINT FOR

SECURITY EQUIPMENT

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 5 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

GENERIC HEALTH CARE FACILITY

TELECOMMUNICATIONS ROOM

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS

AC

SERVICE PANEL FOR

DEDICATED ROOM AIR

CONDITIONING. NON-IT

LOAD ONLY. SHALL BE

EQUIPPED WITH

SCHNEIDER EM3500

SERIES DIN RAIL METER

OR EQUIVALENT

SERVICE PANEL FOR RACK

POWER IN

TELECOMMUNICATION ROOM.

IT LOAD ONLY. SHALL BE

EQUIPPED WITH SCHNEIDER

EM3500 SERIES DIN RAIL

METER OR EQUIVALENT

CONDUITS INTERCONNECTING

NETWORK SUPPORT CENTER

WITH ENTRANCE FACILITY

CONDUIT OR SLEEVES WITH BUSHING AND

FIRESTOP OR OTHER AHJ-APPROVED

PENETRATION FOR HORIZONTAL DISTRIBUTION

FROM WORK AREA OUTLETS AND

TELECOMMUNICATION ROOMS

L21-30R

WIRE MESH CABLE TRAY SIZE

COMMENSURATE WITH

REQUIREMENTS

• MAXIMUM 170 FT2

• STATIC DISSIPATING

FLOOR

• NO DROP CEILING

• SLAB TO DECK 12 FT

MINIMUM (16 FT

PREFERRED)

• WALLS FULL HEIGHT TO

DECK

VERTICAL CABLE MANAGER WITH

DOOR, 6" WIDE

TYPICAL UNSWITCHED DUPLEX

CONVENIENCE OUTLETS

PRIMARY OR

SECONDARY BONDING

BUSBAR (PBB/SBB)

SPLIT PACKAGE AIR

CONDITIONER

AC

L21-30R

ADDITIONAL SPLIT PACKAGE AIR

CONDITIONER WHEN NECESSARY

T

AIR CONDITIONER THERMOSTAT

TELECOMMUNICATIONS RACK, 19" RAILS, #12-

24 TAPPED EIA HOLE PATTERN, 30" DEEP

CHANNEL, 7' HIGH, 45RU, WHITE

3'-0"

NOTE:

THERE SHALL BE A MINIMUM OF ONE

TELECOMMUNICATIONS ROOM (TR) PER FLOOR.

THE EQUIPMENT ROOM CAN SERVE AS A TR. ADDITIONAL

ROOMS SHOULD BE PROVIDED WHEN:

A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10

000 FT2);

OR

B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK

AREA EXCEEDS 90 M (295 FT).

NO RAISED FLOOR.

RK-1 RK-2 RK-3 RK-4

C

PIV/

KEYPAD

4'X 8' AC GRADE ¾” TRADE SIZE PLYWOOD

BACKBOARD PAINTED HIGH-GLOSS WHITE

WITH TWO COATS OF FIRE RESISTANT

PAINT FOR SERVICE PROVIDER EQUIPMENT

4'X 8' AC GRADE ¾” TRADE SIZE

PLYWOOD BACKBOARD PAINTED HIGH-

GLOSS WHITE WITH TWO COATS OF FIRE

RESISTANT PAINT FOR SECURITY

EQUIPMENT

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 6 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TELECOMMUNICATIONS ROOMS

IN ADMINISTRATIVE AREAS

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

AC AC

3 45

TY

P

T

AC

P

TY

P

T

AC

P

TY

P

T

NOTE:

THERE SHALL BE A MINIMUM OF ONE TELECOMMUNICATIONS ROOM (TR) PER FLOOR.

ADDITIONAL ROOMS SHOULD BE PROVIDED WHEN:

A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10,000 FT2);

OR

B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK AREA EXCEEDS 90 M (295 FT).

FLOOR SPACE REQUIREMENT:

1. MINIMUM OF 80 SQ FT FOR A ONE RACK TR

2. ADD AN ADDITIONAL 20 SQ FT PER ADDITIONAL RACK

GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS 2

GENERIC FLOOR PLAN FOR TELECOMMUNICATIONS ROOMS (TWO RACK REQUIREMENT)

(TELECOMMUNICATIONS SPACE SUPPORTING NETWORK DISTRIBUTION TO WORK AREA

OUTLETS)3

GENERIC FLOOR PLAN FOR TELECOMMUNICATIONS ROOMS (ONE RACK REQUIREMENT)

(TELECOMMUNICATIONS SPACE SUPPORTING NETWORK DISTRIBUTION TO WORK AREA

OUTLETS )

TELECOMMUNICATION ROOM NOTES1

M

C

M

C

J J

TY

P

'-0

'-0

'-0

15'-5 7/16"

8'-0"10'-0"

C

M

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 7 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL BACKBOARD

RESERVATIONS

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

AC AC T

RESERVED

VIDEO DISTRIBUTION

WAN/DEMARC

SECURITY POWER METERING

FIRE ALARM/

ANNOUNCIATOR

3'-0"

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 8 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL RACK ELEVATION

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9

10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9

10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9

10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

BladeUPS

Powerware

BladeUPS

Powerware

BladeUPS

Powerware

BladeUPS

Powerware

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

M ODE CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

M ODE CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C 38 50 -NM-4 -10 G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

RK-1

MAXIMUM OF 12 ANGLED CATEGORY 6A, 24 PORT

PATCH PANELS PER RACK. IF MORE THAN TWELVE (12)

PATCH PANELS ARE REQUIRED, INSTALL NEXT SET IN

RK-3.

1 RU BLANKING PANELS BETWEEN LOWEST

PATCH PANEL AND RU32

1 RU CABLE MANAGER. SIX POSITION

SPACING WITH DOOR AT RU31

3850 POE LAN SWITCH WITH 1100 WATT POWER

SUPPLIES. MAX OF SIX (6) PER RACK.

2 RU CABLE MANAGER. SIX POSITION

SPACING WITH DOOR.

1 RU CABLE MANAGER. SIX

POSITION SPACING WITH DOOR.

ZONE PDU

UPS

RK-2 RK-3

RK-4

TYPICAL RACK ELEVATION FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

1 2 3 4 5 6

7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G3 G4

NETWORK MODULE

TE3 TE4TE1 TE2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

M ODE

CONSOLE

37X

Catalys t 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

STAT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G 2 G3 G 4

NET WO RK MO DULE

T E3 T E4TE1 T E2

SPACE

RESERVED

FOR WAN

ROUTERS, IP

PBX,

SECURITY

EQUIPMENT,

ETC.

SPACE

RESERVED

FOR

SERVERS.

SERVICE PROVIDER MAIN CROSS CONNECT

FIRST LEVEL BACKBONE (FIBER)

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 9 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL RACK DETAIL

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

6" WIDE VERTICAL CABLE MANAGEMENT

P/N: OR-MM20VMD706 (OR EQUIVALENT)

MM20 VERTICAL CABLE MANAGEMENT "CAGE", WITH

DOOR, 6" X 8.61" X 7' , BLACK

CAPACITY: 350 CATEGORY 6 PATCH CORDS OR 245

CATEGORY 6A PATCH CORDS

6 in

TYPICAL RACK DIMENSIONS AND SPECIFICATIONS

NTS

P/N: OR-MM2073038-W (OR EQUIVALENT)

MIGHTY MO 20 CABLE MANAGEMENT RACK

30" CHANNEL DEPTH, 7' HIGH, WHITE FINISH OR EQUIVALENT

DIMENSIONS:

USABLE HEIGHT: 45RU

DEPTH (US): 30

HEIGHT (US): 7'

WIDTH (US): 23.75"

STATIC LOAD CAPACITY: 2000 LBS

SQUARE HOLE

FRONT AND REAR HEAVY DUTY PERFORATED SECURITY DOOR (OR-

MM20724PDHD-W)1

SECURITY DOOR FRONT

MOUNTING HARDWARE (OR-

MM2024DMFHD-W) OR

EQUIVALENT4

SECURITY DOOR REAR

MOUNTING HARDWARE (OR-

MM2024DMRHD-W) OR

EQUIVALENT5

PDU MOUNTING BRACKET KIT

(TWO KITS PER RACK)

P/N: OR-MM20PDUMB1D2W-W

OR EQUIVALENT6

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 10 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL CABINET DETAIL

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

TYPICAL ENCLOSURE SPECIFICATION

NTS

TYPICAL ENCLOSURE FRONT

NTS

TYPICAL ENCLOSURE SIDE VIEW

NTS

CP3210245 F-Series TeraFrame Gen 3 Cabinet System with accessories installed Configuration includes the following components:

Item Number Description (Qty) FF1N-113C-E42-B F-Series TeraFrame Gen 3 Cabinet System, 45 RMU, 84.6 in. (2149mm) H x 23.6" (600mm) W x 43.30"

(1100mm) D Square-Punched Rails, 2-Pair, Single, Perforated Metal Front Door, Two Point, Keyed Swing Handle Lock, Double Perforated Metal Rear Door, Two Point, Keyed Swing Handle Latch, Server Top Panel, 2 Solid Side

Panel, Glacier White, 6-Slide Frame

024-739003-E63 Frame, 6 Slide, 23.6'' (600 mm) W x 43.3'' (1100 mm) D x 45 RMU, Glacier White (1)

024-739060-E03 Door, TeraFrame, Front, Asssembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

024-739064-703 Lock Kit, 2-Point, Keyed, Front Door, 45 RMU (1)

024-739050-E03 Double Door Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

024-739054-703 Lock Kit, 2-Point Latching, Keyed, Perforated Door, 45 RMU (1)

024-739140-E12 Top Panel, 2-Piece, Brush, 23.6'' (600 mm) W x 43.3'' (1100 mm) D, Glacier White

024-739046-E63 Side Panel, 6 SLIDE, 43.3'' (1100 mm) D x 45 RMU, Glacier White (2)

024-739200-002 Kit,Common Parts Parts,Teraframe,UL,White (1)

024-739110-701 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)

39110-C01 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)

024-739240-003 Kit, Packaging, 600 W x 1075-1200D x 42U - 48U (1)

024-739029-001 Caster Kit, Two Swivel, Two Fixed, 1.6'' (41 mm) W x 2'' (51 mm) D x 2" (41 mm) H

39085-E03 Air Dam, 6 SLIDE, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

39137-703 Baying Seal Kit, 45U (2)

39132-E00 Bottom Panel, With Brush, 23.6'' (600 mm) W x 39.4" - 47.2" (1000 - 1200 mm) D, Glacier White (1)

31920-E03 Finger Cable Manager no Cover (2)

UL2416 This Cabinet and any included accessories are UL Listed under the NWIN category per the UL2416 Standard.

UL file number E227626. Note, the UL Listing only applies to cabinets manufactured in the United States.

(VENDOR TO PROVIDE 45 RU OF PLENAFILL BLANKING PANEL PER ENCLOSURE)

TYPICAL ENCLOSURE TOP VIEW WITH FOUR (4)

BRUSHED GROMMET CABLE OPENINGS

NTS

1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9

10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45

.6

23.6"43.3"

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 11 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL WORK AREA OUTLETS

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

TYPICAL WORK FLOOR MOUNT OUTLET4TYPICAL WALL MOUNT PHONE VOIP OUTLET3

ONE CATEGORY 6A

8P8C OUTLET ACTIVE

FOR TELEPHONY

TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY 6A

COMPONENT-COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45). EACH

CONNECTOR WILL BE TERMINATED TO HIGH QUALITY CATEGORY 6A HORIZONTAL

CABLING WHICH WILL TERMINATE IN THE TELECOMMUNICATIONS ROOM AS SPECIFIED

ELSEWHERE IN THIS DESIGN PACKAGE.

ALL HORIZONTAL UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.

TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO RJ45s. HIGH DENSITY FACEPLATES WILL BE ISNTALLED WITH FOUR RJ45s.

FACEPLATE MATERIAL AND COLOR DETERMINED BY OTHERS.

THIS SHEET DETAILS A GENERIC FACEPLATE SPECIFICATION.

NOTES:

ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING ON WHITE

FIELD. MACHINE PRINTED. FURTHER GUIDANCE ON ADMINISTRATION MAY BE

SPECIFIED IN OTHER SECTIONS OF THIS DESIGN PACKAGE.

TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA

OUTLET CONFIGURATION2

STANDARD DENSITY WALL MOUNTED WORK AREA OUTLET

CONFIGURATION1

SINGLE GANG WORKBOX

WITH TWO CONNECTOR

CHASSIS.

SINGLE GANG

WORKBOX WITH ONE

CONNECTOR CHASSIS.

FOUR CATEGORY 6A 8P8C

OUTLETS ACTIVE FOR

TELEPHONY/DATA

FOUR POSITION FACEPLATE

MOUNTED ON SINGLE GANG

WORKBOX. FACEPLATE COLOR

SPECIFIED BY OTHERS.

TWO CATEGORY 6A 8P8C

OUTLETS ACTIVE FOR

TELEPHONY/DATA

FOUR POSITION FACEPLATE MOUNTED

ON SINGLE GANG WORKBOX.

FACEPLATE COLOR SPECIFIED BY

OTHERS.

MINIMUM OF FOUR

CATEGORY 6A 8P8C

OUTLETS FOR DATA OR

TELEPHONY

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 12 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TYPICAL RACK POWER

DISTRIBUTION

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

NOTIONAL POWER SCHEMATIC FOR INFORMATION ONLY – NOT FOR CONSTRUCTION

TYPICAL ZONE PDU UNIT WITH REAR DETAIL AND ADAPTORS REQUIRED FOR VERTICAL PDU5

APC AP7900 RACK PDU, SWITCHED, 1U, 15A, 100/120V, (8)5-15 APC

SWITCHED RACK PDU , INPUT: 120V (OR EQUIVALENT)

30 Amp 3-Phase PDU BASE UNIT – FRONT

(ZONIT ZON-C-ZPDU1)

REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS

WITH L21-30R RECEPTACLES

(OR EQUIVALENT)

30 Amp 3-Phase PDU BASE UNIT – REAR

FOUR (4) L21-20R

SIX (6) NEMA 5-15/20 T-SLOT

(OR EQUIVALENT)

110 Volt PDU FOR PLACEMENT AS NEEDED4

PDU INPUTS REQUIRE

TWO L21-30Rs

POWER SCHEMATIC FOR POWER RACK- LEVEL REDUNDANCY1

THE CORRECT SPECIFICATION FOR THE PDU IS TO FEED IT WITH A TWO POWER SOURCES. POWER INPUTS SHOULD ORIGINATE FROM TWO INDEPENDENT POWER SOURCES. EACH INPUT WILL USE IDENTICAL SPECS:

WYE (5-WIRE) CONFIGURED, 208V, 30A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.

NOTE:

ONE ZONE PDU FOR TWO

SERVER CABINETS/

NETWORK RACKS

NOTE:

THIS DESIGN PROVIDES DIVERSE POWER INPUTS FOR ACTIVE EQUIPMENT BY SPLITTING THE

SOURCE POWER ACROSS TWO INPUTS ON THE ZONE PDU. EACH INPUT WILL SUPPORT TWO

EQUIPMENT-FACING PDUs. EACH SERVER CABINET WILL CONTAIN A MINIMUM OF TWO EQUIPMENT- FACING PDUs – EACH WILL BE ENERGIZED BY SEPARATE ZONE PDU INPUTS.

208 VOLT PDU FOR EQUIPMENT POWER – TO BE ENERGIZED BY ZONE

PDU3

REQUIRES ONE (1) L21-

20R

20A 120/ 208V

Y

DUAL 3-PHASE 480 VOLT INPUTS

(WITH 480 – 208

TRANSFORMER)

BUS OR FEEDER

3-PHASE 208-VOLT 30-AMP PDU

PDU PDU

COMPUTER

ZONE PDU

“ZERO U” VERTICAL PDU

DUAL POWER SUPPLY

DUAL INPUT UPS 250-500 kVA

UPS RACK MOUNT UPS

MAIN

POWER

POWER

ON

GROUP B

0FF

0N

MAIN

POWER

POWER

ON

GROUP A

0FF

0N

GROUP A

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

GROUP B

0FF

0N

A

0FF

0N

B

0FF

0N

C

0FF

0N

0FF

0N

0FF

0N

A B CA B C

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

PHASE Z PHASE Y PHASE X

GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B LEG 1

LEG 2

APC AP8861 RPDU OR EQUIVALENT; RACK PDU 2G, METERED; L21-20 PLUG;

THREE PHASE; 120/208V INPUT; 20A; ZERO U,

5.7 KW, 208V, (36) C13 & (6) C19 & (2) 5-20 OUTLETS; FOR USE IN

TELECOMMUNCIATION ROOMS AND LOCATIONS WITH LEGACY 110V ONLY

EQUIPMENT

RACK/ENCLOSURE

ZONE PDU

RACK/ENCLOSURE

PDU

B

PDU

A

BUS A BUS B

RACKED

EQUIPMENT

PS1 PS2

RACKED

EQUIPMENT

PDU

B

PDU

A PS1 PS2

RACK-MOUNT

UPS

RACK-MOUNT

UPS

LEG2LEG1

Rack

PDU

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 13 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

POWER DISTRIBUTION

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

POWER SCHEMATIC RACKS – REAR VIEW1

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

40 40

41 41

42 42

43 43

44 44

45 45

RACK/ENCLOSURE

ZONE PDU

RACK/ENCLOSURE

L21-30P SIDE A

REQUIRES A 208V, 30A, THREE-PHASE CIRCUIT,

TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE.

L21-30P SIDE B

REQUIRES A 208V, 30A, THREE-PHASE CIRCUIT, TERMINATING

IN A NEMA L21-30R LOCKING RECEPTACLE.

PDU

B

PDU

A

BUS A BUS B

RACKED EQUIPMENT

PS1 PS2

RACKED EQUIPMENT

PDU

B

PDU

A PS1 PS2

RACK-MOUNT UPS RACK-MOUNT UPS

A

B

OZ

GROUP B

OX OY

OX

GROUP A

OY OZ

OY

GROUP B

OZ OX

OZ

GROUP A

OX OY

LEG 1 LEG 2 LEG 2LEG 1

PHASE Z PHASE Y PHASE X

GRP A

GRP B L EG 1

L EG 2 GRP A

GRP B LEG 1

LEG 2 GRP A

GRP B L EG 1

L EG 2

ZONE PDU

30A 3-PHASE ZONE PDU BASE UNIT – REQUIRES

TWO 30A 3-PHASE (WYE) CIRCUITS WITH L21-30R

RECEPTACLES

LEG2LEG1

RACK-MOUNTED 5 KW, 208V UNINTERRUPTIBLE POWER

SUPPLY (UPS) WITH NEMA 20A L21-20P INPUT AND L21-

20R OUTPUT

ZONE PDU

30A 3-PHASE ZONE PDU BASE UNIT – REQUIRES

TWO 30A 3-PHASE (WYE) CIRCUITS WITH L21-30R

RECEPTACLES

R ac k P

D U

R ac k P

D U

R ac k P

D U

R ac k P

D U

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 14 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

BONDING

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

12"

4"

ANSI/EIA/TIA COMPLIANT BUSBAR

CHATSWORTH P/N: 40158-012 OR

EQUIVALENT

ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D “COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS”, NFPA 70, AND

IN COMPLIANCE WITH LOCAL CODES.

ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.

3 TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB)

NETWORK EQUIPMENT MUST BE GROUNDED. NEVER DEFEAT THE GROUND CONDUCTOR OR OPERATE

THE EQUIPMENT IN THE ABSENCE OF A SUITABLY INSTALLED GROUND CONDUCTOR. THESE DEVICES WILL BE BONDED TO THE RACK BONDING BUSBAR (RBB) IN THE SAME RACK. EACH DEVICE WILL

HAVE A DEDICATED UNIT BONDING CONDUCTOR (UBC). THE UBC WILL NOT BE SHARED.

RACK BONDING CONDUCTOR

(RBC) - 6 AWG

TELECOMMUNICATIONS EQUIPMENT BONDING

CONDUCTOR (TEBC) – 6 AWG

INDIVIDUAL EQUIPMENT BONDING

CONDUCTORS FROM EACH PIECE OF

EQUIPMENT AND RACK TO THE RACK

BONDING CONDUCTOR

RACK BONDING CONDUCTOR (RBC)

EXTENDED TO BOTTOM OF RACK TO

ACCOMMODATE FUTURE GROWTH

RACK ISOLATION PADS (IF

APPLICABLE)

SERVER

CABINET

NETWORK

RACK

TO PBB/

SBB

TO PBB/SBB

PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENTS

EARTHING EXAMPLE (CISCO 6509/9606)

Ref: CISCO PRODUCT INSTALLATION GUIDE

NOTES:

O I

O I

Catalyst 9600 Series

RFID

C9606R

C9606-FAN

RFID

O I

O I

C9600-SUP-1

SS

SS

Catalyst 9600 Series Supervisor Module

C9600-SUP-1

SS

SS

Catalyst 9600 Series Supervisor Module

C9600-LC-48YLCatalyst 9600 Series Ethernet Switching Module

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

C9600-LC-24CCatalyst 9600 Series Ethernet Switching Module

17 18 19 20 21 22 23 249 10 11 12 13 14 15 161 2 3 4 5 6 7 8

C9600-LC-48YLCatalyst 9600 Series Ethernet Switching Module

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

C9600-LC-48YLCatalyst 9600 Series Ethernet Switching Module

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

TWO-HOLE

COMPRESSI

ON LUG

UBC

SYSTEM

GROUND

LOCATION

CISCO 9606CISCO 6509

SYSTEM GROUND

LOCATION

TWO-HOLE

COMPRESSION LUG

GROUNDING PAD

UBC

SCREWS

(M4)

TWO-HOLE COMPRESSION LUGS (RACKS

SHALL NOT BE MODIFIED IF ONLY ONE-

HOLE IS PROVIDED; USE ONE-HOLE

COMPRESSION LUGS IN THIS CASE)

TOP-MOUNTED RACK BONDING BUSBAR

(RBB)

UNIT BONDING CONDUCTOR

(UBC) - 6 AWG

GROUNDING TERMINAL

(TYPICAL EACH PIECE OF

EQUIPMENT)

IRREVERSIBLE CRIMP CONNECTOR

TELECOMMUNICATIONS EQUIPMENT

BONDING CONDUCTOR (TEBC) – 6 AWG

RACK BONDING CONDUCTOR

(RBC) - 6 AWG

IRREVERSIBLE CRIMP CONNECTOR

IRREVERSIBLE CRIMP

CONNECTOR

CABLE TRAY BONDING

CONDUCTOR. TYPICAL AT

EACH SECTION CONNECTION

POINT

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) –

6 AWG

SCREWS

(M4)

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 15 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

CBOC ITS NAMING STANDARDS

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

• RACK = RK1 THROUGH RK4. LABELED LEFT TO RIGHT WHEN LOOKING AT THE FRONT OF THE RACK. APPLIES TO RACKS AND CABINETS.

• UTP PATCH PANEL = CPL-RACK NAME-01 THROUGH 45. EXAMPLE: CPL-RK1-01 FOR THE PANEL LOCATED IN RACK UNIT #1 IN RACK #1.

• UTP PATCH PANEL POSITION = PANEL ID.01 THROUGH 24. EXAMPLE CPL-RK1-01.01

• FIBER DISTRIBUTION PANEL = FDP-RACK NAME-01 THROUGH 45. EXAMPLE: FDP-RK1-01 FOR THE PANEL IN RACK UNIT #1 RACK #1.

• FIBER DISTRIBUTION CASSETTE = FDC-RACK NAME-01 THROUGH 45.1 THROUGH 3. EXAMPLE: FDC-RK1-01.1 FOR THE CASSETTE IN POSITION #1 IN

PANEL LOCATED IN RACK UNIT #1 IN RACK #1.

• UTP PATCH CORDS = CCA[SOURCE.PORT]/[DESTINATION.PORT]. EXAMPLE CCA[CPL-RK1-01.01]/[CPL-RK2-02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE COPPER PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK UNIT #2.

• FIBER PATCH CORDS = FCA[SOURCE.PORT]/[DESTINATION.PORT]. EXAMPLE FCA[FDP-RK1-01.01.01]/[FDP-RK2-02.02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE FIBER PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK UNIT #2.

• FACEPLATE = TR ROOM NUMBER-PATCH PANEL ID.PORT. EXAMPLE. 1A-CPL-RK1-01.1 FOR TELECOMMUNICATIONS ROOM 1, UTP PANEL IN RACK #1, RACK UNIT #1, PORT POSITION #1.

EXAMPLE INSIDE PLANT ADMINISTRATION1

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 16 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TELECOMMUNICATIONS

ENCLOSURE (TOP VIEW)

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

RBB

TYPICAL TOP-DOWN VIEW

NTS

CONDUIT OR SLEEVES WITH BUSHING AND

FIRESTOP FOR HORIZONTAL DISTRIBUTION

AS NEEDED

TYPICAL WALL-

MOUNTED CABINET

W

T

A/C GRADE ¾ TRADE SIZE PLYWOOD BACKBOARD.

PAINTED WITH TWO COATS OF FIRE RESISTANT BRIGHT

HIGH-GLOSS WHITE PAINT.

MULTIPLE DEDICATED 20-A, 120 VAC SINGLE

PHASE CIRCUIT DUPLEX OUTLET TO

NEAREST AVAILABLE POWER PANEL

PBB

ELECTRONIC EQUIPMENT BONDED TO RBB; RBB

BONDED TO TEBC; TEBC BONDED TO PBB ALL

USING A MINIMUM OF 6 AWG

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 17 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TELECOMMUNICATIONS

ENCLOSURE (ELEVATION VIEW)

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

PRESS

T O

RESET

PRESS

T O

RESET

Smart-UPS 3000

Esc

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C5e

MODE CONSOLE

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

ST AT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G 3 G 4

NETWORK MO DULE

TE3 TE4TE1 TE2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C5e

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C5e

LINK

LINK

LINK

LINK CLASS 1

LASER

ASR 1001

AUXCONMGMT

LINKUSB

BF

MAJ

MIN

CRIT

STAT

PWR

STA

TU

S

S P

A -5

X 1G

E -V

A/L

A/L

A/L

A/L

A/L

RACK MOUNT PDU. L5-20 INPUT. NEMA 5-15

OUTPUT. 1 RU. TWO PER ENCLOSURE. ONE

ENERGIZED BY UPS. ONE ENERGIZED BY WALL

OUTLET.

RESERVED FOR SERVICE

PROVIDER, DVRs, AND

OTHER

TELECOMMUNICATIONS

EQUIPMENT.

LOCKING 110 VOLT 20 AMP OUTLETS. ONE OUTLET ASSIGNED

TO PDU. ONE OUTLET ASSIGNED TO UPS. EACH ENERGIZED BY

SEPARATE ONE-POLE 20 AMP BREAKERS.

VA ROUTER

PATCH PANELS TO WORK

AREAS

ANALOG TELEPHONY

PATCH PANEL (IF

REQUIRED)

FIBER PATCH PANEL FOR

INCOMING CIRCUITS

1 RU CABLE MANAGER

VA LAN SWITCH

SHELF FOR NON-RACKMOUNT EQUIPMENT

1 RU CABLE MANAGER

HOOK AND LOOP STRAPS

EVERY 12 INCHES.

CABLE TO WORKSTATIONS

CABLE FROM SP AND

CABLE TO OTHER CAMPUS

BUILDINGS

QUAD OUTLET (5-20) FOR

BACKBOARD MOUNTED

EQUIPMENT

QUAD OUTLET (5-20) FOR

BACKBOARD MOUNTED

EQUIPMENT

4 FOOT BY 8 FOOT ¾ INCH PLYWOOD BACKBOARD.

A/C GRADE. PAINTED WHITE WITH FIRE RESISTANT

PAINT IF PERMITTED BY AHJ

ELEVATION FOR TELECOMMUNICATIONS ENCLOSURE

CUBE-iT Wall-Mount Cabinet;

Gen 3; 48"H x 24"W x 30"D (1220 mm x 610 mm x 760 mm); 26U; #12-24 Tapped Rails; Tempered Glass Door;

Glacier White or Equivalent

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C5e

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

C5e

MODE CONSOLE

37X

Catalyst 3850 48 PoE+

25X 36X13X 24X01X 12X 48X

PoEDUPLX

ACTV

ST AT

SYST

SPEED

XPS

STACK

S-PWR

C3850-NM-4-10G

G1 G2 G 3 G 4

NETWORK MO DULE

TE3 TE4TE1 TE2

VA LAN SWITCH

PATCH PANELS TO WORK

AREAS (MAX 96

POSITIONS)

TELECOMMUNICATIONS

BONDING BUSBAR

RACK MOUNT UPS. L5-20

INPUT. L5-20 OUTPUT.

CAPACITY NTE 1920 VA. 2

RU. METERED

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 18 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TELECOMMUNICATIONS

ENCLOSURE (ELEVATION)

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

TELECOMMUNICATIONS

BONDING BUSBAR (PBB)

BONDING CONDUCTOR TO

PANEL BOARD GROUND

LUG

RACK BONDING BUSBAR

(RBB)

BOND RBB TO CABINET BONDING LUG. AWG #6

BOND RBB TO PBB.

AWG #6

S-PW R 1

XPS

S-PW R 2

RESET

CONSOLE SERIAL MGMT

AC OK PS OK PWR-C1 -1100WAC AC OK PS OK PWR-C1-1100 WAC

BOND RBB TO EACH SWITCH AND ROUTER

CHASSIS

USE TWO-HOLE LUGS FOR

BONDING CONNECTOR

1 BONDING TOPOLOGY FOR TELECOMMUNICATIONS ENCLOSURES

Department of Veterans Affairs

IT Operations and Services Solution Delivery

DATE

ISSUE:

DESCRIPTIONMARK

FILE: CBOC DESIGN TEMPLATE-v1_1.vsd

DESIGNED BY: KEVIN GRZELKA, CTDC

CHECKED BY:

DOC VERSION No:

SHEET TITLE

PRINT DATE: Jul 8, 2021

ISSUE DATE: Jul 8, 2021

SHEET: 19 OF 19

1.1

CBOC INFORMATION

TRANSPORT SYSTEMS

SPECIFICATIONS

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

TELECOMMUNICATIONS

ENCLOSURE SPECIFICATIONS

MICHAEL JULIAN, RCDD

KELLY BATES, DCIE

ENTERPRISE DATA CENTER AND

INFRASTRUCTURE ENGINEERING

REAR HINGE AND PANEL2

10 SPECIFICATIONS

VERTICAL CABLE MANAGEMENT. TWO KITS FOR PRIMARY. ONE KIT FOR

SECONDARY.

FAN FILTER KIT AND LIGHT KIT (ONE PER

CABINET).

5 BRUSH KIT (ONE PER CABINET)

8 FAN KIT QTY 1 PER CABINET

9 FRONT AND REAR RAIL KIT

SPECIFICATIONS

DESCRIPTION:

Wall-mount enclosure with lockable front door and swing-out rear access to equipment. Tempered glass front door.

PRIMARY:

CUBE-iT Wall-Mount Cabinet; Gen 3; 48"H x 24"W x 30"D (1220 mm x 610 mm x 760 mm); 26U; #12-24 Tapped Rails; Tempered Glass Door; Glacier White. 12419- E48 CUBE-It or Equivalent

SECONDARY:

CUBE-iT Wall-Mount Cabinet; Gen 3; 24"H x 24"W x 30"D (610 mm x 610 mm x 760 mm); 12U; #12-24 Tapped Rails; Tempered Glass Door; Black. 12419-724 or Equivalent.

USE:

For indoor use only, in environmentally controlled areas; may not be used outdoors, in harsh environments, or in air-handling spaces

SIZE:

• Height: 48" (1220 mm)

• Width: 24" (610 mm); 19" EIA rack-mount

• Depth: 30" (760 mm)

INTERIOR:

• Height: 26U

• Width: 19" EIA rack-mount

• Threaded #12-24 equipment mounting holes

• 19"W, EIA-310-D compliant

• Fan assemblies with filter kits

• For use with small equipment such as modems, routers and fiber modules in 19” EIA racks

• 1U; Includes multiples tie-down points

• Supports up to 20 lb (9.1 kg) of equipment

SHELF (TWO PER CABINET)

REQUIRED GROUND JUMPERS1

6 POWER STRIP (TWO PER CABINET)

File details come from the government source that posted it. Updated .