8-Asbestos Survey Taylorsville High School.pdf
PDF 3 MB Posted
- Attached to
- Construction: Taylorsville High School Addition
- Solicitation number
- DB27-011-RFP
- Issued by
- Salt Lake County, Utah
About this file
Asbestos Survey Report Summary
This is an asbestos survey and assessment report prepared by R & R Environmental, Inc. for the Granite School District regarding Taylorsville High School located at 5225 South Redwood Road in Taylorsville, Utah 84123. The survey was conducted in response to planned renovation activities at the facility and was performed between December 18, 2025, and January 4, 2026, by Utah Certified Asbestos Building Inspector Jamison Moss. The assessment identified multiple asbestos-containing materials (ACM) throughout the building, including friable and non-friable materials. A total of 310 representative bulk samples were collected from suspect materials and submitted to Eurofins Reservoirs Environmental, Inc. (NVLAP accredited laboratory) for analysis via Polarized Light Microscopy (PLM) in accordance with EPA Method 600/M4-82-020.
The survey identified asbestos-containing materials in various building systems and locations, including thermal system insulation end sealant (~6,120 square feet with up to 11% chrysotile asbestos, friable and undamaged), pipe gaskets scattered throughout (~15,370 linear feet with 75% chrysotile, non-friable and undamaged), 12-inch vinyl floor tile and mastic scattered throughout (49,452 square feet with up to 11% chrysotile in mastic and up to 2% in tile, non-friable and undamaged), fiber cement materials in various locations (up to 18% chrysotile, non-friable and undamaged), exterior waterproofing (2,474 square feet with up to 60% chrysotile, undamaged), above ceiling debris (~150,000 square feet with up to 15% chrysotile, friable and damaged), and assumed asbestos in fire-rated materials including safes, vault doors, door frames, and roofing materials. The report notes that some quantities and locations may be hidden in wall cavities and above ceilings not accessible during the survey, and it provides professional determinations while acknowledging that no asbestos survey can completely eliminate uncertainty regarding the presence of ACM in a structure.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AN ASBESTOS SURVEY AND ASSESSMENT
FOR THE
GRANITE SCHOOL DISTRICT
TAYLORSVILLE HIGH SCHOOL
5225 SOUTH REDWOOD ROAD
TAYLORSVILLE, UTAH 84123
February 2, 2026
Prepared for:
Granite School District
2500 South State Street
South Salt Lake City, UT 84115
PH: (385) 646-5000
Prepared by:
R & R Environmental, Inc. (R & R)
47 West 9000 South, Suite #2
Sandy, Utah 84070 dave@rrenviro.com
Phone (801) 541-1035
TABLE OF CONTENTS
ASBESTOS
1.0 INTRODUCTION
2.0 EXECUTIVE SUMMARY
3.0 SAMPLING METHODS
4.0 SURVEY RESULTS
5.0 CONCLUSIONS
6.0 LIMITATIONS AND EXCLUSION OF WARRANTY.……………………………………………………6
List of Appendices
Appendix A Sample Log
Appendix B Laboratory Report
Appendix C Photo Log
Appendix D Floor Plans
Appendix E State of Utah Certifications
Asbestos Survey Report Page 1 Taylorsville High School Granite School District
1.0 INTRODUCTION
R & R Environmental, Inc. (R & R) was contacted to conduct an asbestos survey for the Granite
School District, Taylorsville High School located at 5225 South Redwood Road in Taylorsville, Utah 84123. The Taylorsville High School is scheduled to undergo a renovation. The survey consisted of a visual assessment of the building for suspect asbestos containing materials (ACM) and bulk sampling of the materials. The fieldwork component of this survey was conducted by
Mr. Jamison Moss who is a Utah Certified Asbestos Building Inspector and occurred between
December 18 and January 4 2026.
This report presents the conditions and observations noted on the visit dates.
The following general information is included in this survey report:
• Executive Summary (Section 2.0)
• Sampling Methods (Section 3.0)
• Analytical Results (Section 4.0)
• Conclusions (5.0)
• Limitations and Exclusion of Warranty (6.0)
Asbestos Survey Report Page 2
Granite School District
2.0 EXECUTIVE SUMMARY
The asbestos-containing material (ACM) identified at the Taylorsville High School located at 5225
South Redwood Road in Taylorsville, Utah 84123 is as follows:
Material Location Quantity % Asbestos Friable Condition Photo #
Above Ceiling Debris Above
Ceilings ~150,000 ft2 Up to
15% Chrysotile Yes Damaged 2
TSI-End Sealant (Latex) 1 Throughout ~6,120 ft2 Up to
11% Chrysotile Yes Undamaged 3
Drinking Fountain
Undercoat (Black) Hallways 14 ft2 5% Chrysotile No Undamaged 4
Sink Undercoat (Black) Scattered
Throughout 61 ft2
Up to
4% Chrysotile No Undamaged 5
Fiber Cement
Fume Hood I101 75 ft2 Up to
18% Chrysotile No Undamaged 6
Fiber Cement
Welding Wall Welding 720 ft2 Up to
15% Chrysotile No Undamaged 7
Fiber Cement
Board
AHU
Suite/Roof 5,815 ft2 10% Chrysotile No Undamaged 8
Pipe Gasket
(Steam/Cold)1
Scattered
Throughout ~15,370 ft2 75% Chrysotile No Undamaged 9
Pipe Thread
Sealant
(Natural Gas) 1
Scattered
Throughout ~4,685 ft2 6% Chrysotile No Undamaged 10
Exterior Waterproofing Exterior 2,474 ft2 Up to
60% Chrysotile No Undamaged 11
12" Vinyl Floor
Tile (Various
Colors/Designs)
& Mastic
Scattered
Throughout 49,452 ft2
Up to
11% Chrysotile
(Mastic)
Up to
2% Chrysotile
(Tile)
No Undamaged 12
Fire Rated Safes South AHU
& Police 3 ea Assumed No Undamaged 13
Fire Rated
Vault Doors Office/Police 2 ea Assumed No Undamaged 14
Fire Rated
Door/Frames
(Metal/Wood)
Throughout 338 ea Assumed No Undamaged 15
Fire Rated Curtains Stage 9,500 ft2 Assumed No Undamaged 16
Boiler Boiler Room 5 ea Assumed No Undamaged 17
Roofing Materials Roof ~205,000 ft2 Assumed No Undamaged 18
Notes:
1- Quantities are an estimate based off of the visible area against the total square footage of the building.
Some quantities and locations may be hidden in wall cavities above ceiling not accessible at time of survey.
Asbestos Survey Report Page 3
Granite School District
GRANITE SCHOOL DISTRICT, TAYLORSVILLE HIGH SCHOOL
5225 SOUTH REDWOOD ROAD, TAYLORSVILLE, UTAH 84123
DATE OF SURVEY: DECEMBER 2025
NESHAP - REGULATED
ASBESTOS-CONTAINING MATERIALS (R-ACM)
1. Friable asbestos material (>1% asbestos and can be crumbled, pulverized, or reduced to powder by hand pressure)
X Thermal system insulation (TSI)*
Textured ceiling material (TCM)*
Spray-on insulation or fireproofing*
Blown-in insulation*
Ceiling tiles/panels*
X Plaster, gypsum board, gypsum board joint compound*
X Cloth materials* (Fire Rated Curtains)
Paper materials* (HVAC Paper Tape and Insulating Board)
Electrical wiring insulation*
Sink undercoating (loose)*
X Other* (Above Ceiling Debris)
2. Category I ACM which has become friable
Packings
Gaskets
Resilient floor coverings
Asphalt roofing products (Dust Debris, Roofing Underlayment Debris, Flashing Material)
3. Category I ACM that will be or has been subjected to sanding, grinding, cutting, or abrading
Packings
X Gaskets
Asphalt roofing products
4. Category II ACM that has a high probability of becoming or has become friable during demolition or renovation operations
X Asbestos cement materials (TransiteTM)* (Fume hoods, Welding Panels, Wall Panels)
Asphalt, tar and rubber-base ACM products other than roofing products*
Non-asphalt and non-paper roofing products*
Paint*
Fire brick and/or mortar*
Stainless steel sink undercoating (solid)*
Encapsulated TCM*
Encapsulated TSI*
Mastic for floor tile, ceiling tile, cove molding, etc.*
X Other (Boiler, Fire Rated Safe, Vault Door)
Asbestos Survey Report Page 4
Granite School District
GRANITE SCHOOL DISTRICT, TAYLORSVILLE HIGH SCHOOL
5225 SOUTH REDWOOD ROAD, TAYLORSVILLE, UTAH 84123
DATE OF SURVEY: DECEMBER 2025
NESHAP NON-REGULATED
ASBESTOS-CONTAINING MATERIAL (N-R-ACM)
1. > 1% asbestos
2. Category I Non-friable (cannot be crumbled, pulverized, or reduced to powder by hand pressure)
ACM with >1% asbestos by new PLM procedure
Packings
X Gaskets
X Asphalt roofing products
3. Category II Non-friable ACM with >1% asbestos by new PLM procedure (Category includes items meeting Category I definition but not specifically listed in that category)
X Asbestos cement materials (TransiteTM)* (Fume hoods, Welding Panels, Wall Panels)
X Asphalt, tar and rubber-base ACM products other than roofing products*
X Non-asphalt and non-paper roofing products*
Paint* (Silver Paint Sealant)
Fire brick and/or mortar*
X Sink undercoating (solid)* (Sinks and Drinking Fountains)
X Mastic for floor tile, ceiling tile, cove molding, etc.*
X Other* (Fire Rated Door/Frame, etc)
Notes:
1. (*) Denotes R&R’s interpretation of materials included in this category.
2. New PLM procedure is outlined in Appendix A, Subpart F, 40 CFR, Part 783, Section 1, Polarized Light Microscopy.
3. The Environmental Protection Agency (EPA) National Emission Standard for Hazardous Air
Pollutants (NESHAP) asbestos revision as outlined in 40 CFR, Part 61, became effective
November 20, 1990. The asbestos classification system outlined in the revision and included in this section is dynamic in nature. Asbestos materials classified as “NON-REGULATED” at the time of the survey may become “REGULATED” due to ongoing or planned maintenance, renovation, or demolition actions, which can transform a material containing greater than 1% asbestos from a “non-friable” and NON-REGULATED to a friable and REGULATED condition.
Classification of ACM in this section and in the executive summary of this report is, therefore, based on the observations of the surveyor at the time of the survey and may or may not be appropriate at later dates.
4. Maintenance, renovation, demolition, weathering, normal wear, water, or other damage can alter the “NON-REGULATED” status of materials, and necessitate precautions required for handling them as “REGULATED” asbestos-materials.
Asbestos Survey Report Page 5
Granite School District
3.0 SAMPLING METHODS
Survey procedures were based on those outlined in Title 40 Code of Federal Regulation (CFR)
Part 763, USEPA Asbestos Hazard Emergency Response Act, and the Asbestos Model
Accreditation Plan (effective April 4, 1994). The procedures included visual observation, physical inspection, bulk sample collection, and condition assessment of suspect ACM. The number of samples collected was based on the amount and accessibility of each homogeneous material, with consideration given for the type, age, and condition.
Three-hundred ten (310) samples were collected from the suspect materials to assess the presence of asbestos (or lack thereof) in building materials/systems. Each sample collected was placed into a sealable plastic bag or tub, marked with a unique sample identification code, and packaged for subsequent shipment to the laboratory for analysis. Individual sample identification consisted of a numeric code denoting the sampling media/location.
After packaging and labeling, samples were submitted under proper chain-of-custody to
Reservoirs Environmental, Inc., Denver, Colorado. The National Voluntary Laboratory
Accreditation Program (NVLAP), Lab Code 101896 accredits Reservoirs for asbestos analysis.
Samples were analyzed via Polarized Light Microscopy (PLM) utilizing EPA Method 600/M4-
82-020. Please note that USEPA and OSHA regulations define an ACM as a material containing more than one (1) percent asbestos, by volume, as determined by PLM analysis. In the case of multi-layer systems (e.g., floor tile/mastic layers), the laboratory analyzed and reported each layer separately.
4.0 SURVEY RESULTS
Three-hundred ten (310) representative samples submitted for analytical determination. A summary of analytical results for samples collected and analyzed for this survey are in Appendix
B (Laboratory Results) and are discussed below by building material/system type. Photographs of the buildings where samples were taken are included as Appendix C. Floor Plans of the building where samples were taken are included in Appendix D
Asbestos Survey Report Page 6
Granite School District
5.0 CONCLUSIONS
Asbestos-containing materials were identified in the building. See Executive Summary for details.
6.0 LIMITATIONS AND EXCLUSION OF WARRANTY
This asbestos survey and assessment was performed using procedures and a level of diligence typically exercised by professional consultants performing similar services. However, asbestos-containing material (ACM) can be present in a structure, but not identified using ordinary investigative procedures.
No asbestos survey can completely, eliminate uncertainty regarding the presence of ACM.
R&R Environmental, Inc.’s level of diligence and investigative procedures are intended to reduce, but not eliminate, potential uncertainty regarding the presence of ACM. The procedures used for this survey attempt to establish a balance between the competing goals of limiting investigative costs, time, and building damage, and reducing the uncertainty about unknown conditions. Therefore, the determinations in this report should not be construed as a guarantee that all ACM present in the subject property has been included in this report.
This report presents R&R Environmental, Inc.’s professional determinations, which are dependent upon information obtained during performance of consulting services. R&R
Environmental, Inc. assumes no responsibility for omissions or errors resulting from inaccurate information provided by sources outside of R&R Environmental, Inc.
No warranty or guarantee, expressed or implied, is made regarding the findings, conclusions, or recommendations contained in this report. The limitations presented above supersede the requirements or provisions of all other contracts or scopes of work, implied, or otherwise, except stated or acknowledged herein.
Asbestos Survey Report Page 7
Granite School District
AN ASBESTOS SURVEY AND ASSESSMENT
OF THE
GRANITE SCHOOL DISTRICT
TAYLORSVILLE HIGH SCHOOL
5225 SOUTH REDWOOD ROAD
TAYLORSVILLE, UTAH 84123
During the month of December and January 2025, R & R Environmental, Inc. (R & R) of Sandy, Utah, conducted an asbestos survey and assessment of the Granite School District, Taylorsville
High School located at 5225 South Redwood Road in Taylorsville, Utah 84123. Bulk samples of suspect asbestos-containing materials were collected and analyzed. The condition of all friable and non-friable asbestos-containing materials was, assessed. The following accredited inspector conducted the survey and assessment.
Inspected by:
Jamison Moss Date
State of Utah, Division of Air Quality Inspector
Certification Number: ASB-6674
State of Utah Company Certification: ASBC-237
This report was reviewed by:
David C. Roskelley, MSPH, CIH, CSP Date
State of Utah, Division of Air Quality Inspector
Certification Number: ASB-1370
AHERA Inspector #5 PSI 65451 I
Certified Safety Professional #15774
Certified Industrial Hygienist #8529
State of Utah Company Certification: ASBC-237
Appendix A
Sample Log
SAMPLE LOG
Sample #
Material/
Homogenous Area Sample Location Quantity
Lab Result
(%/Type)
Assessment
THS-001
Door Caulk
(Tan Glaze) Exterior 1,144 ft2 None Detected Undamaged
THS-002
Door Caulk
(Tan Glaze) Exterior 1,144 ft2 None Detected Undamaged
THS-003
Door Caulk
(White) Boiler Exterior 63 ft2 None Detected Undamaged
THS-004
Door Caulk
(White) Exterior 63 ft2 None Detected Undamaged
THS-005
Door/Window Caulk
(Dark Brown) Ceramics ~3,025 ft2 None Detected Undamaged
THS-006
Door/Window Caulk
(Dark Brown) B Hall ~3,025 ft2 None Detected Undamaged
THS-007
Wall Cap Sealant
(Gray) Exterior 25 ft2 None Detected Undamaged
THS-008
Wall Cap Sealant
(Gray) Exterior 25 ft2 None Detected Undamaged
THS-009 Door Caulk (Gray) Chiller 138 ft2 None Detected Undamaged
THS-010 Door Caulk (Gray) F208 138 ft2 None Detected Undamaged
THS-011 AHU Sealant (Black) North AHU Suite 13 ft2 None Detected Undamaged
THS-012 AHU Sealant (Black) North AHU Suite 13 ft2 None Detected Undamaged
THS-013 Fire Stop Putty (Red) SW AHU Suite >220 ft2 None Detected Undamaged
THS-014 Fire Stop Putty (Red) SW AHU Suite >220 ft2 None Detected Undamaged
THS-015 CMU Joint Caulk Boiler ~2,640 ft2 None Detected Undamaged
THS-016 CMU Joint Caulk Wood ~2,640 ft2 None Detected Undamaged
THS-017 Door Caulk (Black) Pool Exterior 17 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-018 Door Caulk (Black) Pool Exterior 17 ft2 None Detected Undamaged
THS-019 2' x 2' Ceiling Panel A Hall 14,420 ft2 None Detected Undamaged
THS-020 2' x 2' Ceiling Panel Weight Room Office 14,420 ft2 None Detected Undamaged
THS-021
2' x 4' Ceiling Panel
(Dotted) Library 93,532 ft2 None Detected Undamaged
THS-022
2' x 4' Ceiling Panel
(Dotted) Cafeteria 93,532 ft2 None Detected Undamaged
THS-023
12" Ceiling Tile #1
(Crevasse & Pinhole) D2 Hall 37,436 ft2 None Detected Undamaged
THS-024
12" Ceiling Tile #1
(Crevasse & Pinhole) Dance 37,436 ft2 None Detected Undamaged
THS-025
12" Ceiling Tile #1
Adhesive D2 Hall 37,436 ft2 None Detected Undamaged
THS-026
12" Ceiling Tile #1
Adhesive Dance 37,436 ft2 None Detected Undamaged
THS-027
12" Ceiling Tile #2
("Textured" Crevasse
& Pinhole)
F107 5,532 ft2 None Detected Undamaged
THS-028
12" Ceiling Tile #2
("Textured" Crevasse
& Pinhole)
F203 5,532 ft2 None Detected Undamaged
THS-029
12" Ceiling Tile #2
Adhesive F107 5,532 ft2 None Detected Undamaged
THS-030
12" Ceiling Tile #2
Adhesive F203 5,532 ft2 None Detected Undamaged
THS-031
2' x 4' Ceiling Panel
(Smooth) H113 5,299 ft2 None Detected Undamaged
THS-032
2' x 4' Ceiling Panel
(Smooth) I209 5,299 ft2 None Detected Undamaged
THS-033 4' x 4' Skylight Panels Library 2,166 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-034 4' x 4' Skylight Panels Commons 2,166 ft2 None Detected Undamaged
THS-035 Drinking Fountain Tar #1 J204 5 ft2 None Detected Undamaged
THS-036 Drinking Fountain Tar #1 Cheer 5 ft2 None Detected Undamaged
THS-037 Dust Hopper Sealant Dust Hopper 12 ft2 None Detected Undamaged
THS-038 Dust Hopper Sealant Dust Hopper 12 ft2 None Detected Undamaged
THS-039 Conduit/Pipe Wrap (Tar) SE AHU Suite 87 ft2 None Detected Undamaged
THS-040 Conduit/Pipe Wrap (Tar) Chiller 87 ft2 None Detected Undamaged
THS-041 White Caulk Cooling Tower 10 ft2 None Detected Undamaged
THS-042 White Caulk Cooling Tower 10 ft2 None Detected Undamaged
THS-043
Vinyl Cove Base
(Light Brown) & Mastic F206 492 ft2 None Detected Undamaged
THS-044
Vinyl Cove Base
(Light Brown) & Mastic A103 Storage 492 ft2 None Detected Undamaged
THS-045
Vinyl Cove Base
(Dark Brown) & Mastic Sound Room 115 ft2 None Detected Undamaged
THS-046
Vinyl Cove Base
(Dark Brown) & Mastic Custodial 115 ft2 None Detected Undamaged
THS-047
Vinyl Cove Base
(Gray) & Mastic H Hall 1,253 ft2 None Detected Undamaged
THS-048
Vinyl Cove Base
(Gray) & Mastic J202 1,253 ft2 None Detected Undamaged
THS-049
Vinyl Cove Base
(Maroon) & Mastic F106 711 ft2 None Detected Undamaged
THS-050
Vinyl Cove Base
(Maroon) & Mastic F207 711 ft2 None Detected Undamaged
THS-051
Vinyl Cove Base
(Black) & Mastic J204 Office 65 ft2 None Detected Undamaged
THS-052
Vinyl Cove Base
(Black) & Mastic F107 65 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-053 Duct Gasket (Khaki) SW AHU Suite 828 ft2 None Detected Undamaged
THS-054 Duct Gasket (Khaki) SE AHU Suite 828 ft2 None Detected Undamaged
THS-055 Duct Gasket (Gray) AHU Suite 190 ft2 None Detected Undamaged
THS-056 Duct Gasket (Gray) AHU Suite 190 ft2 None Detected Undamaged
THS-057
Insulation Pin
Adhesive (Duct) I Hall 1 ft2 None Detected Undamaged
THS-058
Insulation Pin
Adhesive (Duct) I Hall 1 ft2 None Detected Undamaged
THS-059 Duct Sealant (Gray) Wood ~9,900 ft2 None Detected Undamaged
THS-060 Duct Sealant (Gray) SW AHU Suite ~9,900 ft2 None Detected Undamaged
THS-061
Duct Sealant
(Army Green) NE AHU Suite ~7,200 ft2 None Detected Undamaged
THS-062
Duct Sealant
(Army Green) Custodial ~7,200 ft2 None Detected Undamaged
THS-063
Vibration Isolator
(Black) Custodial ~432 ft2 None Detected Undamaged
THS-064
Vibration Isolator
(Black) North AHU Suite ~432 ft2 None Detected Undamaged
THS-065 Black Caulk Cooling Tower 10 ft2 None Detected Undamaged
THS-066 Black Caulk Cooling Tower 10 ft2 None Detected Undamaged
THS-067 Pipe Thread Sealant Cooling Tower 25 ft2 None Detected Undamaged
THS-068 Pipe Thread Sealant Cooling Tower 25 ft2 None Detected Undamaged
THS-069
Carpet Adhesive
(Yellow) Faculty room 40,000 ft2 None Detected Undamaged
THS-070
Carpet Adhesive
(Yellow) Library 40,000 ft2 None Detected Undamaged
THS-071
Ceiling Texture
(Dotted) F1 Men’s Bathroom 3,166 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-072
Ceiling Texture
(Dotted) F1 Men’s Bathroom 3,166 ft2 None Detected Undamaged
THS-073
Ceiling Texture
(Dotted) F1 Men’s Bathroom 3,166 ft2 None Detected Undamaged
THS-074
Ceiling Texture
(Dotted) D2 Elevator Stairs 3,166 ft2 None Detected Undamaged
THS-075
Ceiling Texture
(Dotted) D2 Elevator Stairs 3,166 ft2 None Detected Undamaged
THS-076
Stair Tread
(Tan) & Mastic Commons 85 ft2 None Detected Undamaged
THS-077
Stair Tread
(Tan) & Mastic Commons 85 ft2 None Detected Undamaged
THS-078
Stair Tread
(Marble) & Mastic Commons 1,500 ft2 None Detected Undamaged
THS-079
Stair Tread
(Marble) & Mastic H Hall 1,500 ft2 None Detected Undamaged
THS-080
Vinyl Cove Base
(Marble) & Mastic E Hall Stairs 1,750 ft2 None Detected Undamaged
THS-081
Vinyl Cove Base
(Marble) & Mastic L Hall 1,750 ft2 None Detected Undamaged
THS-082
Insulation Pin
Adhesive (Brownish) North AHU Suite 11,808 ft2 None Detected Undamaged
THS-083
Insulation Pin
Adhesive (Brownish) AHU Suite 11,808 ft2 None Detected Undamaged
THS-084
Insulation Pin
Adhesive (Yellowish) Catwalk 480 ft2 None Detected Undamaged
THS-085
Insulation Pin
Adhesive (Yellowish) Catwalk 480 ft2 None Detected Undamaged
THS-086 Sink Undercoat (Black) Yearbook 61 ft2 4% Chrysotile Undamaged
THS-087 Sink Undercoat (Black) I102 61 ft2 2% Chrysotile Undamaged
Homogenous Area Sample Location Quantity
THS-088 Sink Undercoat (Gray) Ceramics 2 ft2 None Detected Undamaged
THS-089 Sink Undercoat (Gray) Ceramics 2 ft2 None Detected Undamaged
THS-090
Drinking Fountain
Undercoat (Black) I Hall 14 ft2 5% Chrysotile Undamaged
THS-091
Drinking Fountain
Undercoat (Black) H Hall 14 ft2 5% Chrysotile Undamaged
THS-092 Drinking Fountain Tar #2 Welding 1 ft2 None Detected Undamaged
THS-093 Drinking Fountain Tar #2 Welding 1 ft2 None Detected Undamaged
THS-094
Fiber Cement
(TransiteTM) Desk I101 Storage ~1,400 ft2 None Detected Undamaged
THS-095
Fiber Cement
(TransiteTM) Desk I101 ~1,400 ft2 None Detected Undamaged
THS-096
Fiber Cement
(TransiteTM) Counter I101 225 ft2 None Detected Undamaged
THS-097
Fiber Cement
(TransiteTM) Counter I104 225 ft2 None Detected Undamaged
THS-098
Fiber Cement
(TransiteTM) Sink I101 3 ea None Detected Undamaged
THS-099
Fiber Cement
(TransiteTM) Sink I101 3 ea None Detected Undamaged
THS-100 Caulk (White) South Men’s Bath 416 ft2 None Detected Undamaged
THS-101 Caulk (White) F2 Hall 416 ft2 None Detected Undamaged
THS-102
Fiber Cement
(TransiteTM)
Welding Wall
Welding 720 ft2 13% Chrysotile Undamaged
THS-103
Fiber Cement
(TransiteTM)
Welding Wall
Welding 720 ft2 15% Chrysotile Undamaged
THS-104
Fiber Cement
(TransiteTM)
Fume Hood
I101 75 ft2 18% Chrysotile Undamaged
Homogenous Area Sample Location Quantity
THS-105
Fiber Cement
(TransiteTM)
Fume Hood
I101 75 ft2 15% Chrysotile Undamaged
THS-106 Kiln Brick Ceramics 96 ft2 None Detected Undamaged
THS-107 Kiln Brick Ceramics 96 ft2 None Detected Undamaged
THS-108 Welding Brick Welding 50 ft2 None Detected Damaged
THS-109 Welding Brick Welding 50 ft2 None Detected Damaged
THS-110 Rubber Bumper Pad Loading Dock 16 ft2 None Detected Undamaged
THS-111 Rubber Bumper Pad Loading Dock 16 ft2 None Detected Undamaged
THS-112
Expansion Board
Material (Silver Board) G203 2,640 ft2 None Detected Undamaged
THS-113
Expansion Board
Material (Silver Board) G203 2,640 ft2 None Detected Undamaged
THS-114 2x4 Adhesive Library 8 ft2 None Detected Damaged
THS-115 2x4 Adhesive Library 8 ft2 None Detected Damaged
THS-116
Pipe Gasket
(Natural Gas) Boiler ~800 ft2 None Detected Undamaged
THS-117
Pipe Gasket
(Natural Gas) Boiler ~800 ft2 None Detected Undamaged
THS-118
Pipe Gasket
(Steam) Boiler ~7,685 ft2 75% Chrysotile Undamaged
THS-119
Pipe Gasket
(Steam) Boiler ~7,685 ft2 None Detected Undamaged
THS-120
Pipe Gasket
(Cold) Wood ~7,685 ft2 75% Chrysotile Undamaged
THS-121
Pipe Gasket
(Cold) Chiller ~7,685 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-122
Pipe Gasket
(Fire) Props Fire Riser ~350 ft2 None Detected Undamaged
THS-123
Pipe Gasket
(Fire) Wood Fire Riser ~350 ft2 None Detected Undamaged
THS-124
Pipe Thread Sealant
(Natural Gas) Ceramics ~4,685 ft2 6% Chrysotile Undamaged
THS-125
Pipe Thread Sealant
(Natural Gas) Boiler ~4,685 ft2 None Detected Undamaged
THS-126
Pipe Thread Sealant
(Steam) Boiler ~12,815 ft2 None Detected Undamaged
THS-127
Pipe Thread Sealant
(Steam) Boiler ~12,815 ft2 None Detected Undamaged
THS-128
Pipe Thread Sealant
(Cold) SW AHU Suite ~12,815 ft2 None Detected Undamaged
THS-129
Pipe Thread Sealant
(Cold) Wood ~12,815 ft2 None Detected Undamaged
THS-130
Pipe Thread Sealant
(Drain) Cheer Janitor ~350 ft2 None Detected Undamaged
THS-131
Pipe Thread Sealant
(Drain)
J2 South Men’s
Pipe Chase ~350 ft2 None Detected Undamaged
THS-132
Pipe Thread Sealant
(Fire) North AHU Suite ~8,885 ft2 None Detected Undamaged
THS-133
Pipe Thread Sealant
(Fire) Custodial ~8,885 ft2 None Detected Undamaged
THS-134
Pipe Thread Sealant
(Misc) I Hall ~150 ft2 None Detected Undamaged
THS-135
Pipe Thread Sealant
(Misc) Boiler ~150 ft2 None Detected Undamaged
THS-136
12" Vinyl Floor Tile
(Brown) & Mastic F107 20 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-137
12" Vinyl Floor Tile
(Brown) & Mastic F107 20 ft2 None Detected Undamaged
THS-138 Wall Packing (Red) Boiler >175 ft2 None Detected Undamaged
THS-139 Wall Packing (Red) South AHU Suite >175 ft2 None Detected Undamaged
THS-140
Wall Packing
(Black Mastic-Pipe) Boiler 6 ft2 None Detected Undamaged
THS-141
Wall Packing
(Black Mastic-Pipe) Boiler 6 ft2 None Detected Undamaged
THS-142 Brick & Mortar Exterior >160,000 ft2 None Detected Undamaged
THS-143 Brick & Mortar Aux Gym >160,000 ft2 None Detected Undamaged
THS-144
Wall Covering
(Beige Carpet) H108 13,760 ft2 None Detected Undamaged
THS-145
Wall Covering
(Beige Carpet) I207 13,760 ft2 None Detected Undamaged
THS-146
Wall Covering
(Maroon Carpet) G206 1,664 ft2 None Detected Undamaged
THS-147
Wall Covering
(Maroon Carpet) H111 1,664 ft2 None Detected Undamaged
THS-148
Wall Covering
(Blue Carpet) Sound Room 380 ft2 None Detected Undamaged
THS-149
Wall Covering
(Blue Carpet) Sound Room 380 ft2 None Detected Undamaged
THS-150
Wall Covering
(Multi-colored Carpet) H101 72 ft2 None Detected Undamaged
THS-151
Wall Covering
(Multi-colored Carpet) H101 72 ft2 None Detected Undamaged
THS-152 Black Mastic AHU Suite 656 ft2 None Detected Undamaged
THS-153 Black Mastic AHU Suite 656 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-154
Exterior
Waterproofing SE Exterior 2,474 ft2 Up to
60% Chrysotile Undamaged
THS-155
Exterior
Waterproofing NW Exterior 2,474 ft2 Up to
60% Chrysotile Undamaged
THS-156 12" Carbon Wall Tile Pool 600 ft2 None Detected Undamaged
THS-157 12" Carbon Wall Tile Pool 600 ft2 None Detected Undamaged
THS-158 TSI-Lagging Boiler ~21,450 LF None Detected Undamaged
THS-159 TSI-Lagging South AHU Suite ~21,450 LF None Detected Undamaged
THS-160 TSI-Lagging Custodial ~21,450 LF None Detected Undamaged
THS-161 TSI-Lagging Floor 2 South
Men’s Pipe Chase ~21,450 LF None Detected Undamaged
THS-162 TSI-Lagging Library ~21,450 LF None Detected Undamaged
THS-163 TSI-Lagging A Hall ~21,450 LF None Detected Undamaged
THS-164 TSI-Lagging Pool ~21,450 LF None Detected Undamaged
THS-165 TSI-End Sealant Boiler ~6,120 ft2 None Detected Undamaged
THS-166 TSI-End Sealant AHU Suite ~6,120 ft2 None Detected Undamaged
THS-167 TSI-End Sealant F1 Pipe Chase ~6,120 ft2 None Detected Undamaged
THS-168 TSI-End Sealant Cafeteria ~6,120 ft2 8% Chrysotile Undamaged
THS-169 TSI-End Sealant Locker Rooms ~6,120 ft2 6% Chrysotile Undamaged
THS-170 TSI-End Sealant Custodial ~6,120 ft2 6% Chrysotile Undamaged
THS-171 TSI-End Sealant Wood ~6,120 ft2 11% Chrysotile Undamaged
THS-172 TSI-Mudded Fittings North AHU Suite 17 ft2 None Detected Undamaged
THS-173 TSI-Mudded Fittings North AHU Suite 17 ft2 None Detected Undamaged
THS-174 TSI-Mudded Fittings Boiler 17 ft2 None Detected Undamaged
THS-175 TSI-Mudded Fittings Welding 17 ft2 None Detected Undamaged
THS-176 TSI-Mudded Fittings Welding 17 ft2 None Detected Undamaged
THS-177 TSI-Pipe Supports Pool Mechanical ~408 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-178 TSI-Pipe Supports Cafeteria ~408 ft2 None Detected Undamaged
THS-179 TSI-Pipe Supports Boiler ~408 ft2 None Detected Undamaged
THS-180 TSI-Pipe Supports North AHU Suite ~408 ft2 None Detected Undamaged
THS-181 TSI-Pipe Supports SE AHU Suite ~408 ft2 None Detected Undamaged
THS-182
TSI-Boiler Flue
(Metal) Boiler 268 ft2 None Detected Undamaged
THS-183
TSI-Boiler Flue
(Metal) Boiler 268 ft2 None Detected Undamaged
THS-184
TSI-Boiler Flue
(Metal) Boiler 268 ft2 None Detected Undamaged
THS-185
TSI-Boiler Flue
(Plaster) Boiler 67 ft2 None Detected Undamaged
THS-186
TSI-Boiler Flue
(Plaster) Boiler 67 ft2 None Detected Undamaged
THS-187
TSI-Boiler Flue
(Plaster) Boiler 67 ft2 None Detected Undamaged
THS-188 TSI-Tank #1 Boiler 175 ft2 None Detected Undamaged
THS-189 TSI-Tank #1 Boiler 175 ft2 None Detected Undamaged
THS-190 TSI-Tank #1 Boiler 175 ft2 None Detected Undamaged
THS-191 TSI-Tank #2 Boiler 225 ft2 None Detected Undamaged
THS-192 TSI-Tank #2 Boiler 225 ft2 None Detected Undamaged
THS-193 TSI-Tank #2 Boiler 225 ft2 None Detected Undamaged
THS-194 TSI-Tank #3 Welding 75 ft2 None Detected Undamaged
THS-195 TSI-Tank #3 Welding 75 ft2 None Detected Undamaged
THS-196 TSI-Tank #3 Welding 75 ft2 None Detected Undamaged
THS-197 TSI-Tank Insulation Boiler 216 ft2 None Detected Undamaged
THS-198 TSI-Tank Insulation Boiler 216 ft2 None Detected Undamaged
THS-199 TSI-Tank Insulation Boiler 216 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-200 Epoxy Flooring Auto 2,500 ft2 None Detected Undamaged
THS-201 Epoxy Flooring Auto 2,500 ft2 None Detected Undamaged
THS-202 Epoxy Flooring Auto 2,500 ft2 None Detected Undamaged
THS-203 Epoxy Flooring Auto 2,500 ft2 None Detected Undamaged
THS-204 Epoxy Flooring Auto 2,500 ft2 None Detected Undamaged
THS-205 AHU Liner North AHU Suite ~4,135 ft2 None Detected Undamaged
THS-206 AHU Liner AHU Suite ~4,135 ft2 None Detected Undamaged
THS-207 AHU Liner Welding ~4,135 ft2 None Detected Undamaged
THS-208 AHU Liner Custodial ~4,135 ft2 None Detected Undamaged
THS-209 AHU Liner Boiler ~4,135 ft2 None Detected Undamaged
THS-210 Ducting Liner Custodial ~6,235 ft2 None Detected Undamaged
THS-211 Ducting Liner SE AHU Suite ~6,235 ft2 None Detected Undamaged
THS-212 Ducting Liner Catwalk ~6,235 ft2 None Detected Undamaged
THS-213 Ducting Liner F208 ~6,235 ft2 None Detected Undamaged
THS-214 Ducting Liner J202 ~6,235 ft2 None Detected Undamaged
THS-215 Ducting Liner Pool Mechanical ~6,235 ft2 None Detected Undamaged
THS-216 Ducting Liner Wood ~6,235 ft2 None Detected Undamaged
THS-217
White Painted
Concrete Ceiling F106 50,600 ft2 None Detected Undamaged
THS-218
White Painted
Concrete Ceiling G111 50,600 ft2 None Detected Undamaged
THS-219
White Painted
Concrete Ceiling H201 50,600 ft2 None Detected Undamaged
THS-220
White Painted
Concrete Ceiling Auto 50,600 ft2 None Detected Undamaged
THS-221
White Painted
Concrete Ceiling H107 50,600 ft2 None Detected Undamaged
THS-222
White Painted
Concrete Ceiling H Hall 50,600 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-223
White Painted
Concrete Ceiling Pool 50,600 ft2 None Detected Undamaged
THS-224 CMU Blockfiller Boiler 43,470 ft2 None Detected Undamaged
THS-225 CMU Blockfiller Wood 43,470 ft2 None Detected Undamaged
THS-226 CMU Blockfiller Welding 43,470 ft2 None Detected Undamaged
THS-227 CMU Blockfiller Weightroom 43,470 ft2 None Detected Undamaged
THS-228 CMU Blockfiller Cafeteria 43,470 ft2 None Detected Undamaged
THS-229 CMU Blockfiller Dance Hall 43,470 ft2 None Detected Undamaged
THS-230 CMU Blockfiller Aux Gym 43,470 ft2 None Detected Undamaged
THS-231 Painted Brick Aux Gym North 40,500 ft2 None Detected Undamaged
THS-232 Painted Brick Aux Gym West 40,500 ft2 None Detected Undamaged
THS-233 Painted Brick Aux Gym South 40,500 ft2 None Detected Undamaged
THS-234 Painted Brick Aux Gym East 40,500 ft2 None Detected Undamaged
THS-235 Painted Brick Main Gym North 40,500 ft2 None Detected Undamaged
THS-236 Painted Brick Main Gym West 40,500 ft2 None Detected Undamaged
THS-237 Painted Brick Main Gym South 40,500 ft2 None Detected Undamaged
THS-238 Wall System Faculty room 30,830 ft2 None Detected Undamaged
THS-239 Wall System Sound Room 30,830 ft2 None Detected Undamaged
THS-240 Wall System A101 30,830 ft2 None Detected Undamaged
THS-241 Wall System Ceramics 30,830 ft2 None Detected Undamaged
THS-242 Wall System I207 30,830 ft2 None Detected Undamaged
THS-243 Wall System F201 30,830 ft2 None Detected Undamaged
THS-244 Wall System J202 30,830 ft2 None Detected Undamaged
THS-245 Plaster Auditorium 12,108 ft2 None Detected Undamaged
THS-246 Plaster Auditorium 12,108 ft2 None Detected Undamaged
THS-247 Plaster Auditorium 12,108 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-248 Plaster Auditorium 12,108 ft2 None Detected Undamaged
THS-249 Plaster Auditorium 12,108 ft2 None Detected Undamaged
THS-250 Plaster Sound Room 12,108 ft2 None Detected Undamaged
THS-251 Plaster Catwalk 12,108 ft2 None Detected Undamaged
THS-252
AHU Suite Insulation
& Seam Sealant North AHU Suite 11,808 ft2 None Detected Undamaged
THS-253
AHU Suite Insulation
& Seam Sealant NE AHU Suite 11,808 ft2 None Detected Undamaged
THS-254
AHU Suite Insulation
& Seam Sealant AHU Suite 11,808 ft2 None Detected Undamaged
THS-255
AHU Suite Insulation
& Seam Sealant AHU Suite 11,808 ft2 None Detected Undamaged
THS-256
AHU Suite Insulation
& Seam Sealant South AHU Suite 11,808 ft2 None Detected Undamaged
THS-257
AHU Suite Insulation
& Seam Sealant SE AHU Suite 11,808 ft2 None Detected Undamaged
THS-258
AHU Suite Insulation
& Seam Sealant SW AHU Suite 11,808 ft2 None Detected Undamaged
THS-259 Radiator Tar I Hall 32 ft2 None Detected Undamaged
THS-260 Radiator Tar B Hall 32 ft2 None Detected Undamaged
THS-261
Laminate Countertops
(Red) G203 16 ft2 None Detected Undamaged
THS-262
Laminate Countertops
(Red) I202 16 ft2 None Detected Undamaged
THS-263
12" Vinyl Floor Tile
(Yellow) & Mastic J Hall 75 ft2 None Detected Undamaged
THS-264
12" Vinyl Floor Tile
(Yellow) & Mastic J Hall 75 ft2 None Detected Undamaged
THS-265
Laminate Countertops
(Black) I102 1,424 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-266
Laminate Countertops
(Black) I110 1,424 ft2 None Detected Undamaged
THS-267
Laminate Countertops
(Brown) A101 48 ft2 None Detected Undamaged
THS-268
Laminate Countertops
(Brown) B101 48 ft2 None Detected Undamaged
THS-269
Laminate Countertops
(White) F107 16 ft2 None Detected Undamaged
THS-270
Laminate Countertops
(White) F107 16 ft2 None Detected Undamaged
THS-271
Laminate Countertops
(Orange) F201 32 ft2 None Detected Undamaged
THS-272
Laminate Countertops
(Orange) F201 32 ft2 None Detected Undamaged
THS-273
Laminate Countertops
(Blue) F108 80 ft2 None Detected Undamaged
THS-274
Laminate Countertops
(Blue) F108 80 ft2 None Detected Undamaged
THS-275
12" Vinyl Floor Tile
(Gray w/ Dark
Gray Flecks)
& Mastic
Sound Room 25 ft2
10% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-276
12" Vinyl Floor Tile
(Gray w/ Dark
Gray Flecks)
& Mastic
Cafeteria 25 ft2
11% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-277 I Joint Board Boiler 6 ft2 None Detected Undamaged
THS-278 I Joint Board Boiler 6 ft2 None Detected Undamaged
THS-279 Fiber Cement Board South AHU Suite 5,815 ft2 10% Chrysotile Undamaged
THS-280 Fiber Cement Board AHU Suite 5,815 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-281 Above Ceiling Debris I Hall ~150,000 ft2 7% Chrysotile Damaged
THS-282 Above Ceiling Debris B110 ~150,000 ft2 None Detected Damaged
THS-283 Above Ceiling Debris G Hall ~150,000 ft2 None Detected Damaged
THS-284 Above Ceiling Debris H Hall ~150,000 ft2 None Detected Damaged
THS-285 Above Ceiling Debris Sound Room ~150,000 ft2 None Detected Damaged
THS-286 Above Ceiling Debris Cafeteria ~150,000 ft2 4% Chrysotile Damaged
THS-287 Above Ceiling Debris South Laundry ~150,000 ft2 None Detected Damaged
THS-288
12" Vinyl Floor Tile
(Yellow Splotches)
& Mastic
Cafeteria 80 ft2
10% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-289
12" Vinyl Floor Tile
(Yellow Splotches)
& Mastic
Cafeteria 80 ft2
2% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-290
12" Vinyl Floor Tile
(Yellow/Tan Camo)
& Mastic
Cafeteria 50 ft2
4% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-291 Concrete Texture I Hall 950 ft2 None Detected Undamaged
THS-292 Concrete Texture G Hall 950 ft2 None Detected Undamaged
THS-293 Concrete Texture F1 Hall 950 ft2 None Detected Undamaged
THS-294 Above Ceiling Debris Custodial ~150,000 ft2 15% Chrysotile Damaged
THS-295 Painted Floor Commons 750 ft2 None Detected Undamaged
THS-296 Painted Floor Commons 750 ft2 None Detected Undamaged
THS-297 Painted Floor Commons 750 ft2 None Detected Undamaged
THS-298
12" Vinyl Floor Tile
(Blue speckle)
& Mastic
Student Body
Officers 300 ft2 None Detected Undamaged
Homogenous Area Sample Location Quantity
THS-299
12" Vinyl Floor Tile
(Blue speckle)
& Mastic
E Hall Janitor 300 ft2 None Detected Undamaged
THS-300
12" Vinyl Floor Tile
(White Speckled)
& Mastic
D2 Hall 32,000 ft2 None Detected Undamaged
THS-301
12" Vinyl Floor Tile
(White Speckled)
& Mastic
G Hall 32,000 ft2 None Detected Undamaged
THS-302
12" Vinyl Floor Tile
(Tan w/ Brown
Streaks) & Mastic
Library storage ~25,000 ft2
10% Chrysotile
(Mastic)
2% Chrysotile
(Tile)
Undamaged
THS-303
12" Vinyl Floor Tile
(Tan w/ Brown
Streaks) & Mastic
E Hall Stairs ~25,000 ft2
10% Chrysotile
(Mastic)
2% Chrysotile
(Tile)
Undamaged
THS-304
12" Vinyl Floor Tile
(Gray Speckled)
& Mastic
Cafeteria 15 ft2 None Detected Undamaged
THS-305
12" Vinyl Floor Tile
(Gray Speckled)
& Mastic
E Hall Janitor 15 ft2
8% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-306
12" Vinyl Floor Tile
(Gray-Multi Speckled)
& Mastic
Cafeteria 300 ft2
8% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
Homogenous Area Sample Location Quantity
THS-307
12" Vinyl Floor Tile
(Gray-Multi Speckled)
& Mastic
E Hall Janitor 300 ft2
2% Chrysotile
(Tile)
None Detected
(Mastic)
Undamaged
THS-308
12" Vinyl Floor Tile
(Yellow/Tan Camo)
& Mastic
Cafeteria 50 ft2
6% Chrysotile
(Mastic)
None Detected
(Tile)
Undamaged
THS-309 Freezer Wall Packing Kitchen 8 ft2 None Detected Undamaged
THS-310 Freezer Wall Packing Kitchen 8 ft2 None Detected Undamaged
Appendix B
Laboratory Report
January 05, 2026
Sincerely, Jeanne Spencer President
Subcontractor Number:
Laboratory Report: RES 715037-1
Project #/P.O. #: None Given
Project Description: Taylorsville High School
Jamison Moss R & R Environmental 47 West 9000 South #2 Sandy, UT 84070
Dear Jamison, Eurofins Reservoirs is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene Association (AIHA LAP), Lab ID 101533 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively.
Eurofins Reservoirs has analyzed the following samples for asbestos content as per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table. The results have been submitted to your office.
RES 715037-1 is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Eurofins Reservoirs will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed, as received and with the information provided by the customer. This report must not be used to claim endorsement of products or analytical results by NVLAP or any agency of the U.S. Government. This report shall not be reproduced except in full, without written approval from Eurofins Reservoirs. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call 303-964-1986.
by Camryn Baumgartner
01/05/202601/05/202601/05/202601/05/2026
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
4955 Yarrow St, Suite 100, Arvada, CO 80002
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non- AAAA SubSubSubSub AsbestosAsbestosAsbestosAsbestos FibrousFibrousFibrousFibrous YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 715037 -715037 -715037 -715037 - THS-01THS-01THS-01THS-01 A Gray caulk w/ blue paint 100 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-02THS-02THS-02THS-02 A Gray caulk w/ blue paint 100 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-03THS-03THS-03THS-03 A Gray glazing 2 NDNDNDND 0 100.0 B White caulk w/ blue paint 98 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-04THS-04THS-04THS-04 A White caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-05THS-05THS-05THS-05 A Brown caulk w/ blue paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-06THS-06THS-06THS-06 A Brown caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-07THS-07THS-07THS-07 A Gray caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-08THS-08THS-08THS-08 A Gray caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-09THS-09THS-09THS-09 A Gray caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-10THS-10THS-10THS-10 A Off-white caulk 100 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-11THS-11THS-11THS-11 A Brown caulk 100 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-12THS-12THS-12THS-12 A Dark-gray caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-13THS-13THS-13THS-13 A Gray caulk w/ red paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-14THS-14THS-14THS-14 A Gray caulk w/ red paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-15THS-15THS-15THS-15 A White caulk 100 NDNDNDND 0 100.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
RES Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
RES 715037-1
R & R Environmental None Given Taylorsville High School January 02, 2026 EPA 600/R-93/116 - Short Report, Bulk Priority January 03 - January 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 715037 -715037 -715037 -715037 - THS-16THS-16THS-16THS-16 A White caulk w/ orange paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-17THS-17THS-17THS-17 A Grayish-brown caulk w/ blue paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-18THS-18THS-18THS-18 A Grayish-brown caulk 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-19THS-19THS-19THS-19 A Tan/white ceiling tile 100 NDNDNDND 80 20.0 715037 -715037 -715037 -715037 - THS-20THS-20THS-20THS-20 A Tan/white ceiling tile 100 NDNDNDND 70 30.0 715037 -715037 -715037 -715037 - THS-21THS-21THS-21THS-21 A Tan/white ceiling tile 100 NDNDNDND 75 25.0 715037 -715037 -715037 -715037 - THS-22THS-22THS-22THS-22 A Tan/white ceiling tile 100 NDNDNDND 75 25.0 715037 -715037 -715037 -715037 - THS-23THS-23THS-23THS-23 A White caulk 45 NDNDNDND 0 100.0 B White ceiling tile 55 NDNDNDND 85 15.0 715037 -715037 -715037 -715037 - THS-24THS-24THS-24THS-24 A Brown adhesive 100 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-25THS-25THS-25THS-25 A Beige/white ceiling tile 100 NDNDNDND 75 25.0 715037 -715037 -715037 -715037 - THS-26THS-26THS-26THS-26 A Brown adhesive 3 NDNDNDND 1 99.0 B White/brown drywall 97 NDNDNDND 15 85.0 715037 -715037 -715037 -715037 - THS-27THS-27THS-27THS-27 A Tan/white ceiling tile 100 NDNDNDND 75 25.0 715037 -715037 -715037 -715037 - THS-28THS-28THS-28THS-28 A Tan/white ceiling tile 100 NDNDNDND 80 20.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
RES Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
RES 715037-1
R & R Environmental None Given Taylorsville High School January 02, 2026 EPA 600/R-93/116 - Short Report, Bulk Priority January 03 - January 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
715037 -715037 -715037 -715037 - THS-29THS-29THS-29THS-29 A Tan/white ceiling tile 40 NDNDNDND 80 20.0 B Brown adhesive 60 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-30THS-30THS-30THS-30 A Brown adhesive 3 NDNDNDND 0 100.0 B Tan ceiling tile 22 NDNDNDND 75 25.0 C White/brown drywall 75 NDNDNDND 20 80.0 715037 -715037 -715037 -715037 - THS-31THS-31THS-31THS-31 A Brown/white drywall ceiling tile 100 NDNDNDND 70 30.0 715037 -715037 -715037 -715037 - THS-32THS-32THS-32THS-32 A Brown/white drywall ceiling tile 100 NDNDNDND 35 65.0 715037 -715037 -715037 -715037 - THS-33THS-33THS-33THS-33 A White/silver foam ceiling tile 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-34THS-34THS-34THS-34 A White/silver foam ceiling tile 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-35THS-35THS-35THS-35 A Gray sealant 100 NDNDNDND 4 96.0 715037 -715037 -715037 -715037 - THS-36THS-36THS-36THS-36 A Off-white sealant 100 NDNDNDND 3 97.0 715037 -715037 -715037 -715037 - THS-37THS-37THS-37THS-37 A Clear caulk w/ yellow paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-38THS-38THS-38THS-38 A Clear caulk w/ yellow/blue paint 100 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-39THS-39THS-39THS-39 A Black foamy resinous material w/ white sealant 100 NDNDNDND TR 100.0 715037 -715037 -715037 -715037 - THS-40THS-40THS-40THS-40 A Black foamy resinous material w/ white sealant 100 NDNDNDND TR 100.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
RES Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
RES 715037-1
R & R Environmental None Given Taylorsville High School January 02, 2026 EPA 600/R-93/116 - Short Report, Bulk Priority January 03 - January 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 715037 -715037 -715037 -715037 - THS-41THS-41THS-41THS-41 A Off-white glazing 4 NDNDNDND 0 100.0 B Clear caulk 96 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-42THS-42THS-42THS-42 A Off-white glazing 2 NDNDNDND 0 100.0 B Clear caulk 98 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-43THS-43THS-43THS-43 A Brown adhesive 4 NDNDNDND 0 100.0 B Brown cove base 96 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-44THS-44THS-44THS-44 A Brown adhesive 2 NDNDNDND 0 100.0 B Brown cove base 98 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-45THS-45THS-45THS-45 A Brown adhesive 3 NDNDNDND TR 100.0 B Brown cove base 97 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-46THS-46THS-46THS-46 A Brown adhesive 1 NDNDNDND TR 100.0 B Off-white adhesive 3 NDNDNDND TR 100.0 C Brown cove base 96 NDNDNDND 0 100.0 715037 -715037 -715037 -715037 - THS-47THS-47THS-47THS-47 A Beige adhesive 5 NDNDNDND TR 100.0 B Gray cove base 95 NDNDNDND 0 100.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
RES Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
RES 715037-1
R & R Environmental None Given Taylorsville High School January 02, 2026 EPA 600/R-93/116 - Short Report, Bulk Priority January 03 - January 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986
(866) RES-IENV
https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample…