8--9- Plans- LIB125639 Draper Library HVAC Replacement.pdf
PDF 7 MB Posted
- Solicitation number
- SLCo LIB125639 Draper Library HVAC Replacement - CONST
- Issued by
- Utah
About this file
The documents are construction documents for the SLCO (Salt Lake County) Draper Library HVAC Remodel project, prepared by GSBS Architects and Focus Mechanical Consulting. The project involves a comprehensive mechanical, electrical, and architectural renovation of the Draper City Library located at 1136 Pioneer Road in Draper, Utah. The construction documents are dated 10/17/2025 and include detailed plans for demolishing existing HVAC systems and installing new mechanical equipment, including a chiller (CH-1), fan coils (FC-1 through FC-5), control valves, pumps, and associated infrastructure. The project scope encompasses modifications to the library's mechanical systems, electrical systems, and potentially some architectural elements to improve the building's heating, ventilation, and air conditioning capabilities.
The mechanical systems will be upgraded with a 20-ton air-cooled chiller with a pump package, variable frequency drives, and a buffer tank. The renovation includes replacing existing control valves, relocating thermostats, and installing new fan coils with cooling and heating capabilities. Electrical upgrades involve modifications to the existing electrical panel, installation of new circuit breakers, and potential power distribution changes. The project appears to be funded by Salt Lake County and is designed to enhance the library's mechanical and electrical infrastructure. The documents provide comprehensive technical details, including equipment schedules, piping diagrams, control schematics, and specific sequence of operations for the new HVAC systems, indicating a thorough and detailed approach to the library's infrastructure improvement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ALLEN
8044423-0301
JESSE DEE
L I
C E
N
S ED AR CH
I T
E C
T
S T
ATE OF UTA
H
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600P www.gsbsarchitects.com
1220 S. 300 W. SLC, UT 84101
801-486-2222
ELECTRICAL ENGINEERING:
EELD ELECTRICAL ENGINEERING
AND LIGHTING DESIGN LLC
259 WEST 1500 NORTH
HARRISVILLE, UTAH 84404
801.631.5776
MECHANICAL ENGINEERING:
FOCUS MECHANICAL CONSULTING
GSBS PROJECT NO.:
ISSUED DATE:
SLCO DRAPER LIBRARY HVAC REMODEL
CONSTRUCTION DOCUMENTS
10/17/2025
2022.055.14
SALT LAKE COUNTY
SLCO DRAPER
LIBRARY HVAC
REMODEL
1136 Pioneer Rd, Draper, UT 84020
Enter Address Here -->
10/17/2025
10/17/2025
334543-2202
MANSOUR
AGHDASI
NO.
PROJECT LOCATION
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600P www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
ABBREVIATIONS
VICINITY MAP DRAWING INDEX
REV
GRAPHIC SYMBOLS MATERIALS/LEGEND
BLOCKING, ROUGH WOOD
METAL (LARGE SCALE)
QUARRY/CERAMIC TILE
GRAVEL
EARTH
CONCRETE MASONRY UNIT
CONCRETE (POURED IN PLACE)
GYPSUM BOARD OR SETTING BEDS
INSULATION (BATT & BLANKET)
INSULATION (RIGID/SEMI-RIGID)
CONTINUOUS ROUGH WOOD
PLYWOOD
FACE BRICK
GRID
GRID
W1
100A
ELEVATION CONTROL POINT
OR DATUM POINT
EXTERIOR ELEVATION SYMBOL
ELEVATION IDENTIFICATION
SHEET WHERE ELEVATION IS DRAWN
WALL SECTION SYMBOL
SECTION REFERENCE/
SHEET WHERE SECTION IS DRAWN
BUILDING SECTION SYMBOL
SECTION REFERENCE/
SHEET WHERE SECTION IS DRAWN
DETAIL SYMBOL
DETAIL NUMBER/
SHEET WHERE DETAIL IS DRAWN
REVISION TAG
GRID LINES
NAME
#SHEET
SHEET
SHEET
SHEET
SHEET
SCALE
VIEW NAME
VIEW TITLE
VIEW NUMBER/
SHEET WHERE VIEW IS LOCATED
VIEW NAME/ VIEW SCALE
INTERIOR ELEVATION SYMBOL
ELEVATION IDENTIFICATION
SHEET WHERE ELEVATION IS DRAWN
#SHEET
ROOM TAG
ROOM NAME
ROOM NUMBER
WINDOW TAG
WINDOW OR STOREFRONT NUMBER
DOOR TAG
DOOR NUMBER
WOOD
COMPACTED FILL
FIREPROOFING
10/17/2025
2022.055.14
G001
DRAWING INDEX,
SYMBOLS AND
ABBREVIATIONS
SALT LAKE COUNTY
SLCO DRAPER
LIBRARY HVAC
REMODEL
1136 Pioneer Rd, Draper, UT 84020
Enter Address Here -->
CONSTRUCTION DOCUMENTS
ABV ABOVE
AFF ABOVE FINISH FLOOR
ADJ ADJUSTABLE
ALUM ALUMINUM
ASTM AMERICAN SOCIETY FOR TESTING MATERIALS
AB ANCHOR BOLT
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR ARCHITECT
AHJ AUTHORITY HAVING JURISDICTION (BUILDING
DEPARTMENT)
BP BASE PLATE
BSMT BASEMENT
BRG BEARING
BTWN BETWEEN
BITUM BITUMINOUS
BLKG BLOCKING
BD BOARD
BO BOTTOM OF
BLDG BUILDING
CLG CEILING
CL CENTER LINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONST CONSTRUCTION
CONT CONTINUOUS
CFOI CONTRACTOR FURNISHED OWNER INSTALLED
CJ CONTROL JOINT
COORD COORDINATE
DEMO DEMOLISH / DEMOLITION
DEPT DEPARTMENT
DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DW DISHWASHER
DBL DOUBLE
DN DOWN
DRWR DRAWER
DWGS DRAWINGS
EA EACH
ELEC ELECTRICAL
EL ELEVATION
ELEV ELEVATOR
EQ EQUAL
EPDM ETHYLENE PROPYLENE DIENE M-CLASS
(ROOFING)
EXIST EXISTING
EXP EXPANSION
EJ EXPANSION JOINT
EXT EXTERIOR
FT FEET / FOOT
FV FIELD VERIFY
FIN FINISH
FF FINISH FLOOR
FA FIRE ALARM
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FLR FLOOR
FD FLOOR DRAIN
FTG FOOTING
FDN FOUNDATION
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GALV GALVANIZED
GA GAUGE
GC GENERAL CONTRACTOR
GL GLASS / GLAZING
GLB GLUE LAMINATED BEAM
GND GROUND
GYP BD GYPSUM BOARD
HW HARDWARE
HVAC HEATING / VENTILATION / AIR CONDITIONING
H HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HYD HYDRANT
IN. INCHES OR INCH
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
JNT JOINT
LAV LAVATORY
LT WT LIGHT WEIGHT
MAINT MAINTENANCE
MFR MANUFACTURER
MO MASONRY OPENING
MAT MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO. NUMBER
OC ON CENTER
OPP OPPOSITE
OD OUTSIDE DIAMETER
OH OVERHEAD
OH DR OVERHEAD DOOR
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
PNT PAINTED OR PAINT
PTN PARTITION
PVMT PAVEMENT
PERP PERPENDICULAR
PLAM PLASTIC LAMINATE
PL PLATE
PLUM PLUMBING
PVC POLYVINYL CHLORIDE
PCF POUNDS PER CUBIC FOOT
PLF POUNDS PER LINEAL FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
QTY QUANTITY
RAD RADIUS
RE REFER / REFERENCE
RCP REFLECTED CEILING PLAN
REF REFRIGERATOR
REINF REINFORCED
REQ REQUIRED
REV REVISION
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
STC SOUND TRANSMISSION CLASS
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STRU STRUCTURAL
SUSP SUSPENDED
SYS SYSTEM
THRU THROUGH
T.O. TOP OF
TOA TOP OF ASPHALT
TOC TOP OF CURB
TOF TOP OF FOOTING
TOS TOP OF SLAB OR SIDEWALK
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VEN VENEER
FV VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
WC WATER CLOSET
WRB WEATHER RESISTIVE BARRIER
W WIDTH
W/ WITH
W/O WITHOUT
WD WOOD
NOTE:
ABBREVIATIONS FOR FINISHED
MATERIALS ARE DESCRIBED IN
THE FINISH LEGEND.
DRAWING INDEX
Sheet Number Sheet Name
GENERAL
G000 COVER SHEET
G001 DRAWING INDEX, SYMBOLS AND ABBREVIATIONS
ARCHITECTURAL
AE101 DEMO & NEW FLOOR PLAN, REFLECTED CEILING PLAN
AE102 DEMO & NEW FLOOR PLAN
AE201 INTERIOR ELEVATION, DETAIL & 3D VIEWS
MECHANICAL
MH001 SHEET INDEX, GENERAL NOTES, & ABBREVIATIONS
MD100 UNDER FLOOR MECHANICAL DEMO PLAN
MD101 MECHANICAL DEMO PLAN
MH100 UNDER FLOOR MECHANICAL REMODEL PLAN
MH101 MECHANICAL REMODEL PLAN
MH401 ENLARGED MECHANICAL PLANS
MH402 ENLARGED MECHANICAL PLANS
MH501 MECHANICAL DETAILS
MH601 MECHANICAL SCHEDULES
ELECTRICAL
E-001 GENERAL NOTES & DETAILS & SCHEDULES
EDL-101 LEVEL ONE FLOOR PLAN - DEMOLITION & LIGHTING
EP-101 MAIN FLOOR PLAN & MEZZANINE - POWER
Grand total: 17
1 2
DEMOLISH EXISTING FLOOR FINISH
FOR STOREFRONT CONSTRUCTION
4"
4"
E Q
E
Q
EQ.EQ.
1 2
AE201
VESTIBULE
NEW STOREFRONT WITH
DOUBLE SLIDING DOOR
NEW STOREFRONT
SF01
SF
1 2
NEW STOREFRONT SOFFIT
3' -0
EQ. EQ.
3'-0"
E Q
E
Q
1 2
DEMOLISH EXISTING CEILING FOR
STOREFRONT CONSTRUCTION
DEMOLISH LIGHT FIXTURE FOR
STOREFRONT CONSTRUCTION,
SALVAGE LIGHT FIXTURE FOR
REINSTALLATION
EQ
EQ
3' -0
EQ EQ
3'-0"
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600P www.gsbsarchitects.com
ALLEN
8044423-0301
JESSE DEE
L I
C E
N
S ED AR CH
I T
E C
T
S T
ATE OF UTA
H
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
RESERVED FOR CONSULTANT LOGO
10/17/2025
2022.055.14
DEMO & NEW FLOOR
PLAN, REFLECTED
CEILING PLAN
SALT LAKE COUNTY
SLCO DRAPER
LIBRARY HVAC
REMODEL
1136 Pioneer Rd, Draper, UT 84020
Enter Address Here -->
CONSTRUCTION DOCUMENTS
AE101
10/17/2025
1/4" = 1'-0"AE101
1 DEMOLITION PLAN - LEVEL ONE
1/4" = 1'-0"AE101
2 FLOOR & WALL TYPES PLAN - LEVEL ONE
1/4" = 1'-0"AE101
3 REFLECTED CEILING PLAN - LEVEL ONE
1/4" = 1'-0"AE101
4 DEMOLITION REFLECTED CEILING PLAN - LEVEL ONE
DEMOLISH EXISTING SCREEN SYSTEM
EXISTING MECH. EQUIPMENT
FILL CUT POST WITH CONCRETE
TRENCH FOR WATER LINE AND ELECTRICAL
CONDUIT, CORE THROUGH WALL
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600P www.gsbsarchitects.com
ALLEN
8044423-0301
JESSE DEE
L I
C E
N
S ED AR CH
I T
E C
T
S T
ATE OF UTA
H
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
RESERVED FOR CONSULTANT LOGO
10/17/2025
2022.055.14
DEMO & NEW FLOOR
PLAN
SALT LAKE COUNTY
SLCO DRAPER
LIBRARY HVAC
REMODEL
1136 Pioneer Rd, Draper, UT 84020
Enter Address Here -->
CONSTRUCTION DOCUMENTS
AE102
10/17/2025
1/4" = 1'-0"AE102
1 DEMO SITE PLAN - LEVEL ONE
1/4" = 1'-0"AE102
2 SITE PLAN - LEVEL ONE
SC
H
E D
. C
LN
G
H E
IG
H
T
SC
H
E D
. C
LN
G
H E
IG
H
T
AE201
AE201
AE201
AE201
INSIDE OF VESTIBULE INSIDE OF LOBBY
SPRAY FOAM TO CREATE AIR TIGHT
SEAL AROUND STRUCTURE
EXISTING STRUCTURE
EXTEND DRYWALL TO STRUCTURE ABOVE
M A
TC
H
E X
IS
TI
N G
M A
TC
H
E X
IS
TI
N G
EXISTING SLOPED GLASS
STRUCTURAL SEALANT
AE201
AE201
AE201
LEVEL 1
100' - 0"
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600P www.gsbsarchitects.com
ALLEN
8044423-0301
JESSE DEE
L I
C E
N
S ED AR CH
I T
E C
T
S T
ATE OF UTA
H
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
RESERVED FOR CONSULTANT LOGO
10/17/2025
2022.055.14
INTERIOR ELEVATION,
DETAIL & 3D VIEWS
SALT LAKE COUNTY
SLCO DRAPER
LIBRARY HVAC
REMODEL
1136 Pioneer Rd, Draper, UT 84020
Enter Address Here -->
CONSTRUCTION DOCUMENTS
AE201
10/17/2025
1/2" = 1'-0"AE201
1 STOREFRONT ELEVATION 01
AE201
2 3D View 2
AE201
5 3D View 3
AE201
3 3D View 1
1 1/2" = 1'-0"AE201
4 DRYWALL SOFFIT DETAIL
3" = 1'-0"AE201
6 STOREFRONT DETAIL @ EXISTING GALSS
1/2" = 1'-0"AE201
7 STOREFRONT ELEVATION 02
3" = 1'-0"AE201
8 MULLION BASE DETAIL
3" = 1'-0"AE201
9 CORNER MULLION DETAIL, TYP.
BALL VALVE
GATE VALVE
SHUT-OFF VALVE (GENERIC, UNSPECIFIED TYPE)
BUTTERFLY VALVE
CHECK VALVE
PRESSURE REGULATING VALVE
2-WAY CONTROL VALVE, ELECTRIC ACTUATOR
SOLENOID VALVE
M
3-WAY CONTROL VALVE, ELECTRIC ACTUATOR
M
STRAINER WITH BLOWOFF VALVE, PIPED TO DRAIN
STRAINER WITH VALVE, HOSE END, & CAP
S
CALIBRATED BALANCE VALVE
RELIEF VALVE
PRESSURE & TEMPERATURE TEST PORT
PRESSURE GAUGE W/ COCK
TEMPERATURE SENSOR
T
P
PRESSURE SENSOR
VENTURI-TYPE FLOW MEASURING DEVICE
THERMOMETER WELL
UNION
CONCENTRIC REDUCER
ECCENTRIC REDUCER, FLAT ON BOTTOM
FLEXIBLE PIPE CONNECTOR
PUMP (STYLE AS INDICATED IN SCHEDULE)
PIPE ALIGNMENT GUIDE
PIPE ANCHOR
PIPING SYMBOLS
FIRE DAMPER
SMOKE DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE & SMOKE DAMPER
MANUAL BALANCE DAMPER
MOTORIZED AUTOMATIC DAMPER
SUPPLY DUCT RISE
RETURN DUCT RISE
SUPLY DUCT DROP
SUPPLY DIFFUSER (RECTANGULAR OR ROUND)
EXHAUST GRILLE (RECTANGULAR OR ROUND)
EXHAUST DUCT RISE
EXHAUST DUCT DROP
RETURN GRILLE (WITH SOUNDBOOT IF NOT DUCTED)
FLEXIBLE DUCT
ELBOW WITH TURNING VANES
BRANCH SPIN-IN WITH MANUAL DAMPER
HIGH EFFICIENCY BRANCH TAKE-OFF
ACCESS DOOR
RETURN DUCT DROP
DUCT SYMBOLS
F
FS
S
DUCT SIZE (INCHES) AND TYPE
FIRST VALUE = VISIBLE DIMENSION
KEYED NOTE
REVISION TAG
EQUIPMENT TAG (KEYED TO SCHEDULE)
POINT OF REMOVAL FROM EXISTING
POINT OF CONNECTION TO EXISTING
SHEET NO.
DETAIL OR VIEW TAG
ANNOTATIONS
WALL THERMOSTAT W/EQUIPMENT TAG
HUMIDITY SENSOR OR HUMIDISTAT
CARBON DIOXIDE (CO2) SENSOR
CARBON MONOXIDE (CO) SENSOR
FLOW DIRECTION OR DIFFUSER THROW DIRECTION
A101
VIEW NO.
A101
SHEET NO.
SECTION VIEW TAG
VIEW NO.
CO2
T
RTU-1
CO
H
AHU-1
16/12 RA
AIRFLOW (CFM)
DIFFUSER OR GRILLE NO.
(SEE SCHEDULE)
AIR TERMINAL TAG
BD
M
ELBOW UP
ELBOW DOWN
BRANCH OR TEE W/ BOTTOM CONNECTION
BRANCH OR TEE W/ TOP CONNECTION
COMPRESSED AIR
CHILLED WATER RETURN
CONDENSER WATER SUPPLY
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
DOMESTIC COLD WATER
STEAM
STEAM CONDENSATE
HEATING WATER SUPPLY
OVERFLOW ROOF DRAIN
NATURAL GAS (LINE PRESSURE)
HEATING WATER RETURN
LINE TYPES
DOMESTIC HOT WATER RECIRCULATION
CA
CHS
CHR
CS
CR
S
DOMESTIC HOT WATER
SC
GR (xx%PG)
GR (xx%PG)
GLYCOL SUPPLY (% PROPYLENE GLYCOL)
GLYCOL RETURN (% PROPYLENE GLYCOL)
G (x PSI)
HWR
HWS
OD
ROOF DRAIN
SOFTENED WATER
RD
SW
PURE WATER (RO OR DI, REFER TO SPECS)PW
VACUUMVAC
VENTV
SANITARY WASTE (ABOVE GRADE)W
SANITARY WASTE (BELOW GRADE)
FIRE SERVICEF
CONDENSATE OR EQUIPMENT DRAIND
GREASE WASTEGW
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:1
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
SHEET INDEX, GENERAL
NOTES, & ABBREVIATIONS
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
CONSTRUCTION DOCUMENTS
MH001MH001
ABBREVIATIONS
(E) EXISTING, TO REMAIN
(X) EXISTING, TO BE DEMOLISHED
AFF ABOVE FINISHED FLOOR
AH AIR HANDLER
APD AIR PRESSURE DROP
AS AIR SEPARATOR
BHP BRAKE HORSE POWER
CBV CALIBRATED BALANCE VALVE
CFM CUBIC FEET PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
COTG CLEAN OUT TO GRADE
CV CONTROL VALVE
DB DRY BULB
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EFT ENTERING FLUID TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
FCO FLOOR CLEANOUT
FLA FULL LOAD AMPS
FO FLAT OVAL (DUCT TYPE)
FT FEET
GAL GALLONS
GEA GREASE EXHAUST AIR
GPM GALLONS PER MINUTE
HP HORSEPOWER
IN INCHES
IN. WG INCHES OF WATER GAUGE
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LFT LEAVING FLUID TEMPERATURE
MCA MINIMUM CIRCUIT AMPACITY
MOP MAXIMUM OVERCURRENT PROTECTION
MPSA MEDIUM PRESSURE SUPPLY AIR
NPSHA NET POSITIVE SUCTION HEAD AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD REQUIRED
OA OUTSIDE AIR
PG PROPYLENE GLYCOL
PSI POUNDS PER SQUARE INCH
PSIA PSI, ABSOLUTE PRESSURE
PSIG PSI, GAUGE PRESSURE
RA RETURN AIR
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
VOLT/PH VOLTAGE / PHASE
VTR VENT THROUGH ROOF
WB WET BULB
WCO WALL CLEANOUT
WPD WATER PRESSURE DROP
SHEET INDEX
# SHEET NAME
MH001 SHEET INDEX, GENERAL NOTES, & ABBREVIATIONS
MD100 UNDER FLOOR MECHANICAL DEMO PLAN
MD101 MECHANICAL DEMO PLAN
MH100 UNDER FLOOR MECHANICAL REMODEL PLAN
MH101 MECHANICAL REMODEL PLAN
MH401 ENLARGED MECHANICAL PLANS
MH402 ENLARGED MECHANICAL PLANS
MH501 MECHANICAL DETAILS
MH601 MECHANICAL SCHEDULES
DEFERRED SUBMITTALS
CONTRACTOR SHALL PROVIDE COMPLETE DEFERRED SUBMITTALS TO THE ENGINEER AND OWNER IN
ACCORDANCE WITH THE DESCRIPTIONS BELOW. FOLLOWING REVIEW BY OWNER AND ENGINEER,
PROVIDE A COPY OF THE DEFERRED SUBMITTAL TO THE BUILDING OFFICIAL IN ACCORDANCE WITH
IBC 2021 107.3.4.1.
ITEM DRAWING OR SPECIFICATION REFERENCE
SEISMIC RESTRAINT DESIGN OF
NON-STRUCTURAL COMPONENTS
230548
BID ALTERNATES SUMMARY
SUBMIT BID PRICING FOR THE BASE BID AS DESCRIBED. SUBMIT PRICING FOR EACH BID ALTERNATE SEPARATELY, CLEARLY LISTED AS AN AMOUNT TO BE ADDED TO, OR DEDUCTED FROM, THE BASE BID IF ACCEPTED. REFER TO ADDITIONAL NOTES IN THE DRAWINGS AND SPECIFICATIONS FOR
GREATER DETAIL ON BID ALTERNATES.
PORTION OF WORK DESCRIPTION
BASE BID
ALL WORK DEPICTED IN THE DRAWINGS AND SPECIFICATIONS, UNLESS
NOTED AS PART OF A BID ALTERNATE.
BID ALTERNATE #1 <<provide description here>>
O
SET
10/17/2025
1 2 3 4 5 6 7 8
A
B
C
D
REFRIGERANT LINESET (E)
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:1
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
UNDER FLOOR MECHANICAL
DEMO PLAN
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MD100MD100
KEYED NOTES
1 DEMOLISH EXISTING REFRIGERANT LINESET.
0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"
UNDER FLOOR MECHANICAL DEMO PLAN
GENERAL DEMOLITION NOTES
A. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT LOCATION OF ALL EXISTING CONDITIONS RELEVANT TO
THE SCOPE OF WORK.
B. EXISTING MECHANICAL SYSTEMS ARE DEPICTED DIAGRAMMATICALLY. LOCATIONS OF MECHANICAL AND
PLUMBING COMPONENTS ARE APPROXIMATE AND DO NOT SHOW ALL TRANSITIONS, OFFSETS, ETC.
LOCATION AND ORIENTATION MAY DIFFER SLIGHTLY IN RELATION TO OTHER COMPONENTS.
C. DO NOT SHUT-OFF/PUT OUT SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL
DOWNTIME WITH THE OWNER'S PERSONNEL.
D. COMPONENTS THAT ARE TO BE DEMOLISHED ARE SHOWN IN BOLD, DASHED OUTLINES. COMPONENTS
THAT ARE EXISTING TO REMAIN ARE SHOWN IN LIGHT, SOLID OUTLINES.
E. CONTRACTOR SHALL REMOVE FROM THE JOBSITE ANY MATERIALS CALLED OUT TO BE DEMOLISHED AND
RECYCLE ALL RECYCLABLE MATERIALS, AND LEGALLY DISPOSE OF ALL OTHER MATERIALS.
F. REPAIR, REPLACE AND/OR REPAINT TO MATCH EXISTING ALL SURFACES DAMAGED DURING DEMOLITION
OR INSTALLATION OF EQUIPMENT.
CONSTRUCTION DOCUMENTSO
ACU-5 (X) ACU-4 (X) ACU-3 (X) PAC-1 (X) ACU-2 (X) ACU-1 (X)
1 1 1 1 12
T
T
T
1 2 3 4 5 6 7 8
A
B
C
D
MH402
MH401
MH402
MH401
(MEZZANINE ABOVE) (MEZZANINE ABOVE)
REFRIGERANT LINESET (E)
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:2
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
MECHANICAL DEMO PLAN
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MD101MD101
KEYED NOTES
1 RECOVER REFRIGERANT FROM SPLIT SYSTEM. DEMOLISH CONDENSING UNIT AND LINESET.
2 RECOVER REFRIGERANT FROM SPLIT SYSTEM. REMOVE CONDENSING UNIT AND PREPARE FOR
REINSTALLATION.
3 REMOVE SECTION OF EQUIPMENT YARD WALL.
4 DEMOLISH BRANCH DUCT. CAP DUCT DROP IN WALL.
5 REMOVE THERMOSTAT AND PREPARE FOR RELOCATION. PATCH WALL.
6 DEMOLISH EXISTING REFRIGERANT LINESET.
GENERAL DEMOLITION NOTES
A. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT LOCATION OF ALL EXISTING CONDITIONS RELEVANT TO
THE SCOPE OF WORK.
B. EXISTING MECHANICAL SYSTEMS ARE DEPICTED DIAGRAMMATICALLY. LOCATIONS OF MECHANICAL AND
PLUMBING COMPONENTS ARE APPROXIMATE AND DO NOT SHOW ALL TRANSITIONS, OFFSETS, ETC.
LOCATION AND ORIENTATION MAY DIFFER SLIGHTLY IN RELATION TO OTHER COMPONENTS.
C. DO NOT SHUT-OFF/PUT OUT SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL
DOWNTIME WITH THE OWNER'S PERSONNEL.
D. COMPONENTS THAT ARE TO BE DEMOLISHED ARE SHOWN IN BOLD, DASHED OUTLINES. COMPONENTS
THAT ARE EXISTING TO REMAIN ARE SHOWN IN LIGHT, SOLID OUTLINES.
E. CONTRACTOR SHALL REMOVE FROM THE JOBSITE ANY MATERIALS CALLED OUT TO BE DEMOLISHED AND
RECYCLE ALL RECYCLABLE MATERIALS, AND LEGALLY DISPOSE OF ALL OTHER MATERIALS.
F. REPAIR, REPLACE AND/OR REPAINT TO MATCH EXISTING ALL SURFACES DAMAGED DURING DEMOLITION
OR INSTALLATION OF EQUIPMENT.
0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"
MECHANICAL DEMO PLAN
CONSTRUCTION DOCUMENTSO
1 2 3 4 5 6 7 8
A
B
C
D
3" CHS UP
3" CHR UP
3" CHR
3" CHS
SEE SHEET MH100
FOR CONTINUATION
CV-6A
CV-6B
CV-6C
CV-6D
CV-6E 1
CV-6F 1
CV-6G 1CV-6H 1CV-6I 1
3/4" DCW UP
TO YH-1
3/4" DCW
3/4" DCW UP
2" (E) WATER SERVICE DN
2" (E) WATER SERVICE
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:3
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
UNDER FLOOR MECHANICAL
REMODEL PLAN
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MH100MH100
KEYED NOTES
1 REPLACE EXISTING CONTROL VALVE.
GENERAL NOTES
A. PROVIDE A COMPLETE OPERATING SYSTEM UPON COMPLETION OF THIS PROJECT.
B. INSTALL ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE CURRENTLY ADOPTED EDITIONS OF
THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL FIRE CODE
AND INTERNATIONAL PLUMBING CODE.
C. INSTALL ALL EQUIPMENT ACCORDING TO MANUFACTURER’S INSTRUCTIONS.
D. PLANS ARE DIAGRAMATIC IN NATURE AND DO NOT SHOW EVERY ELBOW, OFFSET, TRANSITION, AND
OTHER INCIDENTAL ITEMS THAT MAY BE NECESSARY FOR A COMPLETE SYSTEM. PROVIDE ALL DUCT, PIPE, FITTINGS, TRANSITIONS AND OTHER ITEMS NECESSARY TO PROVIDE A FUNCTIONING SYSTEM AS
CONVEYED BY THE DRAWINGS, WHETHER OR NOT SUCH ITEMS ARE SHOWN ON THE DRAWINGS.
E. PROVIDE SUBMITTALS ON ITEMS LISTED IN MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES TO
THE ENGINEER FOR REVIEW PRIOR TO ORDER, PURCHASE OR INSTALLATION.
F. AT PROJECT CLOSE-OUT, PROVIDE AS-BUILT DRAWINGS AND OPERATION & MAINTENANCE MANUALS IN
PDF FORMAT. SUBMIT TO ENGINEER.
G. ALL EQUIPMENT, DUCTWORK, AND PIPING SHALL BE SEISMICALLY RESTRAINED IN ACCORDANCE WITH APPLICABLE CODE. USE IMPORTANCE FACTOR OF 1.5 FOR NATURAL GAS AND FIRE PROTECTION
PIPING, AND IMPORTANCE FACTOR 1.0 FOR ALL OTHER EQUIPMENT AND UTILITIES, UNLESS
OTHERWISE NOTED. ALL DETAILS AND DRAWINGS REQUIRED BY LOCAL AUTHORITY ARE TO BE
PRODUCED BY A LICENSED ENGINEER HIRED BY THE CONTRACTOR. SUBMIT COPY OF STAMPED AND
SIGNED SHOP DRAWINGS AND CALCULATIONS TO ENGINEER.
H. PRESSURE TEST ALL NATURAL GAS, COMPRESSED AIR, AND WATER PIPING AT 150% OF OPERATING
PRESSURE FOR 4 HOURS.
0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"
UNDER FLOOR MECHANICAL REMODEL PLAN
CONSTRUCTION DOCUMENTSO
CH-1 PAC-1
AS-1
8ø SA
10ø SA
FC-5
T
1 2 3 4 5 6 7 8
A
B
C
D
MH401
MH402
MH402
MH401
(MEZZANINE ABOVE) (MEZZANINE ABOVE)
3" CHR
3" CHS
REFRIGERANT LINESET (E)
SEE SHEET MH101
FOR CONTINUATION
3/4" CHR
3/4" CHS
CV-5A
T
FC-5
N/A
10/12 SA
145-
8ø SA
8ø SA T
FC-2
C
T
FC-1
C
N/A
16/14 SA
14/10 RA
T
FC-4
T
FC-3
C T
AH-1
C
3" CHS
3" CHR
YH-1 5
3/4" D
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:4
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
MECHANICAL REMODEL PLAN
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MH101MH101
KEYED NOTES
1 SEE 4/MH401 FOR CONTINUATION.
2 RELOCATED THERMOSTAT.
3 NEW THERMOSTAT.
4 REINSTALL CONDENSING UNIT IN A LOCATION THAT PROVIDES ADEQUATE CLEARANCE FOR THE NEW
CHILLER. RECONNECT POWER, CONTROLS, AND REFRIGERANT LINESET.
5 PROVIDE 3 CUBIC FEET OF GRAVEL AROUND DRAIN HOLE OF YARD HYDRANT.
GENERAL NOTES
A. PROVIDE A COMPLETE OPERATING SYSTEM UPON COMPLETION OF THIS PROJECT.
B. INSTALL ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE CURRENTLY ADOPTED EDITIONS OF
THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL FIRE CODE
AND INTERNATIONAL PLUMBING CODE.
C. INSTALL ALL EQUIPMENT ACCORDING TO MANUFACTURER’S INSTRUCTIONS.
D. PLANS ARE DIAGRAMATIC IN NATURE AND DO NOT SHOW EVERY ELBOW, OFFSET, TRANSITION, AND
OTHER INCIDENTAL ITEMS THAT MAY BE NECESSARY FOR A COMPLETE SYSTEM. PROVIDE ALL DUCT, PIPE, FITTINGS, TRANSITIONS AND OTHER ITEMS NECESSARY TO PROVIDE A FUNCTIONING SYSTEM AS
CONVEYED BY THE DRAWINGS, WHETHER OR NOT SUCH ITEMS ARE SHOWN ON THE DRAWINGS.
E. PROVIDE SUBMITTALS ON ITEMS LISTED IN MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES TO
THE ENGINEER FOR REVIEW PRIOR TO ORDER, PURCHASE OR INSTALLATION.
F. AT PROJECT CLOSE-OUT, PROVIDE AS-BUILT DRAWINGS AND OPERATION & MAINTENANCE MANUALS IN
PDF FORMAT. SUBMIT TO ENGINEER.
G. ALL EQUIPMENT, DUCTWORK, AND PIPING SHALL BE SEISMICALLY RESTRAINED IN ACCORDANCE WITH APPLICABLE CODE. USE IMPORTANCE FACTOR OF 1.5 FOR NATURAL GAS AND FIRE PROTECTION
PIPING, AND IMPORTANCE FACTOR 1.0 FOR ALL OTHER EQUIPMENT AND UTILITIES, UNLESS
OTHERWISE NOTED. ALL DETAILS AND DRAWINGS REQUIRED BY LOCAL AUTHORITY ARE TO BE
PRODUCED BY A LICENSED ENGINEER HIRED BY THE CONTRACTOR. SUBMIT COPY OF STAMPED AND
SIGNED SHOP DRAWINGS AND CALCULATIONS TO ENGINEER.
H. PRESSURE TEST ALL NATURAL GAS, COMPRESSED AIR, AND WATER PIPING AT 150% OF OPERATING
PRESSURE FOR 4 HOURS.
0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"
MECHANICAL REMODEL PLAN
CONSTRUCTION DOCUMENTSO
FC-1
C
D
C
D
B
8ø SA
/1
SA
FC-2
FC-3
FC-4
B
16/14 SA
MH501
14/10 RA
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:4
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
ENLARGED MECHANICAL
PLANS
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MH401MH401
KEYED NOTES
1 SEE SHEET MH101 FOR CONTINUATION.
GENERAL NOTES
A. ENLARGED MECHANICAL GENERAL NOTES.
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MECHANICAL ROOM MECHANICAL REMODEL
PLAN
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MECHANICAL ROOM MECHANICAL DEMO
PLAN
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MEZZANINE MECHANICAL DEMO PLAN
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MEZZANINE MECHANICAL REMODEL PLAN
CONSTRUCTION DOCUMENTSO
C
D
C
D
3" CHS
3" CHR 3" CHS DN
3" CHR DN
FC-1
3/ 4"
C
HR
3/ 4"
C
HS
GLYCOL (E)
SC(E)
PRV(E)
3/4" DCW DN
2" (E) WATER SERVICE DN
CV-1A
CV-1B
1/
4" C
HR
1/
4" C
HS
3/ 4"
D
3/4" GLYCOL FEED
P
B
FC-4
FC-3
FC-2
B
3" C
HS
3"
C
HR
CV-3A
CV-2A
CV-4A
CV-4B
CV-2B
CV-3B
2" CHR
2" CHS
1 1/2" CHS
1 1/2" CHR
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:4
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
ENLARGED MECHANICAL
PLANS
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MH402MH402
KEYED NOTES
1 DEMOLISH EXISTING REFRIGERANT LINESET.
2 CONNECT CONDENSATE DRAIN TO TAIL PIECE OF LAVATORY.
3 CONNECT TO EXISTING CONDENSATE DRAIN PIPE
4 PROVIDE PRESSURE SENSOR AND SOLENOID VALVE ON CHILLED WATER GLYCOL LINE. IF PRESSURE DROPS BELOW 20 PSI, OPEN SOLENOID VALVE AND START GLYCOL FEED PUMP UNTIL PRESSURE IS
ABOVE 25 PSI.
5 CONNECT TO EXISTING GLYCOL FEED PUMP PIPING. INTERLOCK NEW PRESSURE SENSOR AND
SOLENOID VALVE TO OPERATE GLYCOL FEED PUMP WHEN PRESSURE IN CHILLED WATER SYSTEM IS
LOW (IN ADDITION TO CURRENT HEATING WATER FEED PRESSURE SENSOR AND SOLENOID).
GENERAL NOTES
A. ENLARGED MECHANICAL GENERAL NOTES.
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MECHANICAL ROOM MECHANICAL PIPING
DEMO PLAN
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MECHANICAL ROOM MECHANICAL PIPING
REMODEL PLAN
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MEZZANINE MECHANICAL PIPING DEMO PLAN
0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"
ENLARGED MEZZANINE MECHANICAL PIPING REMODEL
PLAN
CONSTRUCTION DOCUMENTSO
SET
10/17/2025
P
SET RELIEF VALVE PRESSURE FOR 75 PSI. PIPE DISCHARGE TO GLYCOL FEED TANK..
1/2" BALL VALVE MANUAL AIR VENT
UNION OR FLANGE, TYP.
STRAINER
SHUTOFF VALVE, TYP.
1/2" BALL VALVE DRAIN
PRESSURE AND
TEMPERATURE TEST PORT, TYP.
CALIBRATED BALANCE VALVE
(NOT REQUIRED FOR PRESSURE
INDEPENDENT CONTROL VALVES)
M
CHILLER
ANCHOR CHILLER TO EXISTING
PAD PER SEISMIC ANCHOR
DEFERRED SUBMITTAL
2" VALVES (FOR
INITIAL PIPE CLEANING
AND FLUSH)
THERMOMETER (TYP.)
BALANCE VALVE
GROOVED PIPE CONNECTION
BUTTERFLY VALVE (TYP.)
STRAINER (20 MESH)
PRESSURE GAUGE (TYP.)
FLEXIBLE
CONNECTION (TYP.)
CH-1
VFD
VFD
T
T
CHILLED WATER RETURN
TEMPERATURE: AI
CHILLED WATER SUPPLY
TEMPERATURE: AI
BACNET
POINTS TO MAP THROUGH BACNET INTERFACE:
PUMP SPEED, PUMP STATUS, ENTERING WATER
TEMPERATURE, LEAVING WATER TEMPERATURE,
CHILLER % COMMAND, CHILLER STATUS, CHILLER
COMMAND
SEQUENCE OF OPERATIONS
A. OPERATE CHILLER WHEN THERE IS A CALL FOR COOLING (AT LEAST ONE CHILLED
WATER VALVE WITH A COMMAND OF OVER 10% FOR 10 MINUTES (ADJ.). CHILLER WILL
START PUMPS AND MODULATE CHILLER CAPACITY TO MEET CHWS SETPOINT.
B. BUILDING AUTOMATION SYSTEM WILL PROVIDE A CHWS SETPOINT TO CHILLER. CHWS
WILL BE RESET USING TRIM AND RESPOND LOGIC SO THAT MAXIMUM CHILLED WATER
VALVE COMMAND IS 95% (ADJ.)
C. GENERATE AN ALARM ON BUILDING AUTOMATION SYSTEM IF THERE ARE ANY CHILLER
ALARMS. FAN COIL
M
M
CV-#B: HEATING VALVE COMMAND: AO
CV-#A: CHILLED VALVE COMMAND: AO
T
SUPPLY AIR
TEMPERATURE : AI
T
MT M
OUTSIDE AIR TEMPERATURE : AI
OUTSIDE AIR DAMPER : AI
RETURN AIR DAMPER : AI
RETURN AIR TEMPERATURE : AI
SEQUENCE OF OPERATIONS
A. OPERATE FAN COIL FAN CONTINUOUSLY DURING OCCUPIED HOURS. OPERATE FAN COIL WHEN REQUIRED TO MEET THE UNOCCUPIED TEMPERATURE SETPOINTS. PROVIDE OPTIMIZED START IN THE MORNING HOURS TO ACHIEVE OCCUPIED SETPOINT BY THE TIME THE BUILDING IS SCHEDULED TO BE OCCUPIED.
B. CONTROL OUTSIDE AIR DAMPER MINIMUM POSITION TO MAINTAIN CO2 BELOW 800 PPM. USE ECONOMIZER MODE FOR CONTROL OF OUTSIDE AIR DAMPERS AND RETURN AIR DAMPERS WHEN COOLING IS NEEDED
AND OUTSIDE AIR TEMPERATURE IS LESS THAN RETURN AIR TEMPERATURE.
C. MODULATE CHILLED WATER CONTROL VALVE AND HEATING WATER CONTROL VALVE TO MAINTAIN SPACE
TEMPERATURE AT SETPOINT.
D. WHEN SPACE TEMPERATURE FALLS MORE THAN 3F BELOW UNOCCUPIED SETPOINT DURING ONOCCUPIED HOURS (HEATING MODE) OR RISES MORE THAN 3F ABOVE UNOCCUPIED SETPOINT DURING UNOCCUPIED HOURS (COOLING MODE), START FAN COIL IN UNOCCUPIED MODE. OPERATE FAN COIL UNTIL SPACE TEMPERATURE IS 3F MORE THAN SETPOINT (HEATING) OR 3F LESS THAN SETPOINT (COOLING) AND THEN
SHUT DOWN FAN COIL.
E. GENERATE AN ALARM ON THE BAS WHEN:
FAN COIL STATUS DOES NOT MATCH COMMAND,
SPACE TEMPERATURE HAS BEEN ABOVE 80F FOR MORE THAN 15 MINUTES (OCCUPIED HOURS)
SPACE TEMPERATURE HAS BEEN BELOW 65F FOR MORE THAN 15 MINUTES (OCCUPIED HOURS)
T SPACE TEMPERATURE: AI
C CARBON DIOXIDE SENSOR: AI
UNOCCUPIED
HEATING
OCCUPIED
COOLING
SPACE TEMPERATURE SETPOINT
FC-3
FC-2
10/16 SA (E)
16/28 OA (E)
16/24 SA (E)
14/10 RA
16/14 SA
M
22/18 RA (E) THROUGH WALL
12/14 OA
M M
(DAMPER ON OTHER SIDE OF WALL)
MEZZANINE FLOOR
16/24 OA
SUPPORT FAN COIL FROM
STRUCTURE OVERHEAD WITH
THREADED ROD AND METAL CHANNEL
THROUGH WALL
THROUGH WALL
F
T
T
10 PUMP (P-6 & 7)
STRAINER
BUTTERFLY VALVE
VFD
VALVE FOR PRESSURE POINT
EXPANSION TANK (ET-1)
FLOW SWITCH
EVAPORATOR
AUTOMATIC AIR VENT
MANUAL AIR BLEED
DRAIN VALVE
BUFFER TANK (BT-1)
TEMPERATURE SENSOR
LEGEND
1/2" BALL VALVE MANUAL AIR VENT
UNION OR FLANGE, TYP.
STRAINER
SHUTOFF VALVE, TYP.
1/2" BALL VALVE DRAIN
M
PRESSURE AND
TEMPERATURE TEST PORT, TYP.
3-WAY CONTROL VALVE
CALIBRATED BALANCE VALVE
FC-5
M
CV-5A: CHILLED WATER VALVE
COMMAND: AO
SEQUENCE OF OPERATIONS
A. START FAN COIL WHEN COOLING IS NEEDED. MODULATE CHILLED WATER VALVE TO
MEET SPACE TEMPERATURE SETPOINT. STOP FAN COIL WHEN SPACE TEMPERATURE
SETPOINT IS SATISFIED.
B. MODULATE PERIMETER RADIANT HEATER CONTROL VALVE WHEN HEATING IS
NEEDED
T SPACE TEMPERATURE: AI
M
CV-6A: PERIMETER RADIANT
HEATER VALVE COMMAND: AO
SEQUENCE OF OPERATIONS
A. MODULATE PERIMETER RADIANT HEATER CONTROL VALVE WHEN HEATING IS
NEEDED
M
CV-6#: PERIMETER RADIANT
HEATER VALVE COMMAND: AO
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:5
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
MECHANICAL DETAILS
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MH501MH501
SCALE: NONE
COIL PIPING DETAIL - HEATING COIL
SCALE: NONE
CHILLER CONNECTION DETAIL
SCALE: NONE
CHILLER CONTROL SCHEMATIC
SCALE: NONE
FC-1, 2, 3, & 4 CONTROL SCHEMATIC
SCALE: NONE
FC-2/FC-3 SECTION VIEW
SCALE: NONE
CHILLER PUMP PACKAGE PIPING DETAIL
SCALE: NONE
COIL PIPING DETAIL - COOLING COIL
SCALE: NONE
FC-5 CONTROL SCHEMATIC
SCALE: NONE
PERIMETER HEATING CONTROL SCHEMATIC
CONSTRUCTION DOCUMENTSO
SE
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600 801.521.791
P F www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
REVREV
:1
:5
P M
R
A u to d e s k S tu ff
R e v it
L o c a l M o d e ls
-0
D ra p e r
L ib ra ry
M E C
H V m o d e le rB X
P D
.r v t
10/17/2025
25-017
MECHANICAL SCHEDULES
DRAPER CITY
LIBRARY
1136 PIONEER RD
DRAPER, UT 84020
SCHEMATIC DESIGN REVIEW
SET
MH601MH601
2. POWERED THROUGH CHILLER SINGLE POINT ELECTRICAL CONNECTION
1. PROVIDE WITH VARIABLE FREQUENCY DRIVE
P-7 CHILLED WATER 35 80 40% PROPYLENE GLYCOL 3500 1.9 5 208/3 ARMSTRONG 4392 2X2X6 INCLUDED AS A PUMP PACKAGE ON THE CHILLER
P-6 CHILLED WATER 35 80 40% PROPYLENE GLYCOL 3500 1.9 5 208/3 ARMSTRONG 4392 2X2X6 INCLUDED AS A PUMP PACKAGE ON THE CHILLER
BHP HP VOLT/PH
PLAN
CODE
SYSTEM
SERVED
FLOW
(GPM)
HEAD PRESSURE
(FT. W.G.)
FLUID RPM
ELECTRICAL
MANUFACTURER & MODEL NOTES
PUMP (P)
AS-1 35 5 6.3/25.3 SPIROTHERM VDT200
PLAN
CODE
FLOW
(GPM)
PRESSURE DROP
(FT. W.G.)
DIAMETER/HEIGHT
(IN)
MANUFACTURER & MODEL
AIR & DIRT SEPARATOR (ADS)
5 PERFORATED CEILING GRID / LAY-IN 22X22 24 X 24 940 0.05 NA <15 TITUS 8R
4 PERFORATED CEILING GRID / LAY-IN 22X10 24 X 12 400 0.05 NA <15 TITUS 8R
3 PLAQUE FACE CEILING GRID / LAY-IN 12 24 X 24 600 0.13 16 21 TITUS OMNI
2 PLAQUE FACE CEILING GRID / LAY-IN 10 24 X 24 435 0.11 14 20 TITUS OMNI
1 PLAQUE FACE CEILING GRID / LAY-IN 8 24 X 24 315 0.09 12 21 TITUS OMNI
PLAN
CODE
TYPE CEILING / MOUNTING
NECK SIZE
(IN)
FACE SIZE
(IN)
AIFLOW
(CFM)
PRESSURE DROP
(IN. W.G.)
THROW
(FT.)
NOISE
(NC)
MANUFACTURER & MODEL NOTES
GRILLES, REGISTERS, DIFFUSERS SCHEDULE
FC-5 600 60 0.5 2.25 208/3 .5 3.9 0.5 76.8/59.1 57.7/52.3 40% PPG 44 53 2.7 7 MERV 8 28 36 10 TRANE FCCB060
FC-4 4000 470 0.6 2.51 208/3 3 14 0.5 83.7/62 63.5/55.2 40% PPG 44 51.5 23.0 10 0.16 62.5 112 30% PPG 180 140 5.7 2 MERV 8 41 58 26 TRANE BCHE120
FC-3 800 125 0.6 2.49 208/3 1 5.75 0.5 78.1/60.9 55.5/53 40% PPG 44 55.1 3.4 6 0.14 59.5 109.2 30% PPG 180 140 1.2 2 MERV 8 30 30 17 TRANE BCHE024
FC-2 2400 100 0.6 2.5 208/3 3 14 0.5 75.5/57.1 55.5/49.6 40% PPG 44 52.3 12.0 11 0.15 67.2 103 30% PPG 180 140 2.3 2 MERV 8 36 58 18 TRANE BCH072
FC-1 1700 180 0.6 2.35 208/3 1 5.75 0.37 76.8/57.3 55.5/49.3 40% PPG 44 52.9 8.5 4.5 0.13 62.9 104 30% PPG 180 128 2.6 2 MERV 8 36 46 18 TRANE BCHE054
AIR PRESSURE
DROP
(IN. W.G.)
ENTERING AIR
TEMPERATURE
(DB/WB)
LEAVING AIR
TEMPERATURE
(DB/WB)
FLUID
ENTERING FLUID
TEMPERATURE (F)
LEAVING FLUID
TEMPERATURE (F)
FLUID
FLOW (GPM)
WATR PRESSURE
DROP (FT. W.G.)
AIR PRESSURE
DROP (IN. W.G.)
ENTERING AIR
TEMPERATURE
(DB/WB)
LEAVING AIR
TEMPERATURE
(DB/WB)
FLUID
ENTERING FLUID
TEMPERATURE (F)
LEAVING FLUID
TEMPERATURE (F)
FLUID
FLOW (GPM)
WATER PRESSURE
DROP (FT. W.G.)
MAX
LENGTH (IN)
MAX
WIDTH (IN)
MAX
HEIGHT (IN)
PLAN
CODE
AIRFLOW
(CFM)
OUTSIDE
AIRFLOW (CFM)
EXTERNAL STATIC
PRESSURE (IN. W.G.)
TOTAL STATIC
PRESSURE (IN. W.G.)
VOLT/PH
FAN
MOTOR (HP)
MCA
COOLING HEATING
FILTER
PHYSICAL
MANUFACTURER & MODEL
FAN COIL (FC)
1. SINGLE POINT ELECTRICAL CONNECTION ON CHILLER ALSO POWERS PUMPS, VFD
CH-1 20 16.94 16.1 208/3 120 175 40% PROPYLENE GLYCOL 52 53 44 20 97 TRANE CGAM
PROVIDE WITH PUMP PACKAGE INCLUDING PUMPS (P-6/7), PUMP VFD, 140 GALLON BUFFER TANK, 5 GAL EXPANSION TANK, ASSOCIATED PIPING AND CONTROLS
PLAN
CODE
NOMINAL
CAPACITY
(TONS)
IPLV NPLV VOLT/PH MCA MOP LIQUID
FLUID
FLOWRATE
(GPM)
ENTERING WATER
TEMPERATURE (F)
LEAVING WATER
TEMPERATURE (F)
EVAPORATOR PRESSURE
DROP (FT. W.G.)
AMBIENT
TEMPERATURE (F)
SOUND PRESSURE
LEVEL (@ 30 FT.)
MANUFACTURER & MODEL NOTES
AIR COOLED CHILLER (CH)
CV-6I BASEBOARD RADIANT 1 2-WAY MODULATING 5 YES
CV-6H BASEBOARD RADIANT 1 2-WAY MODULATING 5 YES
CV-6G BASEBOARD RADIANT 0.85 2-WAY MODULATING 5 YES
CV-6F BASEBOARD RADIANT 3.5 2-WAY MODULATING 5 YES
CV-6E BASEBOARD RADIANT 1.5 2-WAY MODULATING 5 YES
CV-6D BASEBOARD RADIANT 1 2-WAY MODULATING 5 YES
CV-6C BASEBOARD RADIANT 1.75 2-WAY MODULATING 5 YES
CV-6B BASEBOARD RADIANT 1.5 2-WAY MODULATING 5 YES
CV-6A BASEBOARD RADIANT 0.85 2-WAY MODULATING 5 YES
CV-5A FC-5 COOLING 2.7 3-WAY MODULATING 5 NO
CV-4B FC-4 HEATING 5.7 2-WAY MODULATING 5 YES
CV-4A FC-4 COOLING 24.9 3-WAY MODULATING 5 NO
CV-3B FC-3 HEATING 1.2 2-WAY MODULATING 5 YES
CV-3A FC-3 COOLING 3.4 3-WAY MODULATING 5 NO
CV-2B FC-2 HEATING 2.3 2-WAY MODULATING 5 YES
CV-2A FC-2 COOLING 12 3-WAY MODULATING 5 NO
CV-1B FC-1 HEATING 2.6 2-WAY MODULATING 5 YES
CV-1A FC-1 COOLING 8.5 3-WAY MODULATING 5 NO
PLAN
CODE
DUTY
FLOW
(GPM)
TYPE
PRESSURE
DROP (PSI)
PRESSURE
INDEPENDENT?
CONTROL VALVE (CV)
BT-1 CHILLER 143 3" PROVIDED WITH CHILLER PUMP PACKAGE PROVIDE WITH AUTOMATIC AIR VENT
PLAN
CODE
SYSTEM SERVED VOLUME
CONNECTION
SIZE (IN.)
MANUFACTURER & MODEL ACCESSORIES
BUFFER TANK (BT)
ET-1 4.8 4.8 Y PROVIDED WITH CHILLER PUMP PACKAGE
PLAN
CODE
MINIMUM TANK
VOLUME (GAL)
MINIMUM ACCEPTANCE
VOLUME (GAL)
ASME RATED? MANUFACTURER & MODEL
EXPANSION TANK (ET)
YH-1
NON-FREEZE POST HYDRANT WITH GALVANIZED
CASING AND ADJUSTABLE FLOW WHEEL LOCK HANDLE.
3/4"
PROVIDE FOR 5' BURY DEPTH OF WATER SUPPLY LINE. PROVIDE WITH
VACUUM BREAKER
J.R. SMITH 5909
PLAN
CODE
DESCRIPTION COLD HOT WASTE VENT NOTES BASIS OF DESIGN
PLUMBING SPECIALTIES
CONSTRUCTION DOCUMENTSO
MECHANICAL EQUIPMENT
SCHEDULE
NAME OF
MECHANICAL
EQUIPMENT
F A
N C
O
IL
F A
N C
O
IL
F A
N C
O
IL
A
IR
C O
O L
E D
P U
M P
M O
T O
R
D
A T
A
EQUIPMENT NO. FC-1,3 FC-2,4 FC-5 CH-1 P-6,7
RATING/WATTS 1 HP 3 HP .5 HP 5 HP
VOLTAGE 208 208 208 208 208
PHASE 3 3 3 3 3
AMPS 5.75 14.00 3.00 120 17.50
WIRE SIZE 3#12 3#12 3#12 3#1/0 3#10
GROUND WIRE 1#12 1#12 1#12 1#6 1#10
CONDUIT SIZE 3/4" 3/4" 3/4" 1-1/2" 3/4"
FUSE DISC. SW. 30 30 30 200 30
TYPE RKI FUSES 10 20 6 150 20
BREAKER SIZE 20 20 20 175 30
CIRCUIT
NOTES 1 1 1 1 1
NOTES:
STARTER IS FURNISHED WITH THE UNIT. PROVIDE SITE DISCONNECT. COORDINATE
EXACT LOCATION WITH MECHANICAL CONTRACTOR TO ENSURE PROPER CLEARANCE.
*THE ELECTRICAL CONTRACTOR IS TO COORDINATE WITH THE MECHANICAL
CONTRACTOR FOR EXACT LOCATIONS AND PROVIDE FUSE/BREAKER SIZE FOR EACH
EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS.
DETAIL
NOT TO
SCALE
SCALE:
D1
TYPICAL ROUGH−IN DETAIL
NOTES:
IN ACCORDANCE W/ IBC 711.3.2, OUTLETS ON OPPOSITE SIDES OF
FIRE RATED WALLS OR PARTITIONS IN THE SAME STUD SPACE
MUST BE SEPARATED BY MIN. OF 24" HORIZONTAL DISTANCE.
1. TYP. FOR WOOD & METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOWN.
3. LOCATE ALL OUTLET BOXES IN
ACCORDANCE W/ ARCH. & MECH. DWGS.,
AND W/ ALL APPLICABLE SHOP DWGS.
TYPICAL DUPLEX
OUTLET BOX
TYPICAL SWITCH
OUTLET BOX
BAR
STRAPS
BAR
STRAPS
TYPICAL WALL
OUTLETS
PROVIDE CONDUIT SUPPORTS IN
ACCORDANCE W/ NEC SPACING
REQUIREMENTS FOR THE TYPE OF
RACEWAY REQUIRED
AS REQUIRED FOR TYPE OF
CONSTRUCTION
STEEL CITY NO.
7501 BOX SUPPORT
DETAIL
NOT TO
SCALE
SCALE:
A
B
NOTES:
1. THE CONTRACTOR MUST COORDI NATE EXACT LOCATI ON OF THE DI SCONNECT WI TH THE MECHANI CAL
CONTRACTOR TO ELI MINATE ANY OBSTACLE (PI PE,CONCRETE PAD ETC. ) I N FRONT OF THE DISCONNECT.
IF THERE ARE ANY OBSTACLES, PROVI DE UNI STRUT AND INSTALL THE DI SCONNECT NEXT TO
MECHANI CAL EQUI PMENT I N ORDER TO PROVI DE THE REQUI RED CLEARANCE.
2. PROVI DE MINI MUM CLEARANCE AS FOLLOWS:
SYSTEM VOLTAGE
A B
42"
36" 30"
30"
DISCONNECT
SWITCH
FLEXIBLE LIQUID
TIGHT METALLIC
CONDUIT
MECHANICAL
EQUIPMENT
TYPICAL
CLEARED
SPACE
TYPICAL DISCONNECT CLEARANCE REQUIREMENTS
D2
DETAIL
NOT TO
SCALE
SCALE:
NOTE:
TYPI CAL DETAILS SHOWI NG GENERAL FI RE
STOPPI NG PROCEDURE . ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SP ACE BETWEEN
PI PE AND/ OR I NSULATI ON AND OPENING.
FOLLOW MANUFACTURER' S I NSTRUCTI ONS.
DAMMING MATERIAL
(BACKER ROD, FIBERGLASS
OR MINERAL WOOL)
3M FIRE BARRIER
CP 25WB CAULK
FIRE RATED CONCRETE
FLOOR SLAB
CONDUIT OR
INSULATED CABLES
TYPICAL FIRESTOP FOR CABLES/CONDUIT
THROUGH CONCRETE FLOORINGD3
DETAIL
NOT TO
SCALE
SCALE:
NOTE:
TYPI CAL DETAILS SHOWI NG GENERAL FI RE
STOPPI NG PROCEDURE . ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SP ACE BETWEEN
PI PE AND/ OR I NSULATI ON AND OPENING.
FOLLOW MANUFACTURER' S I NSTRUCTI ONS.
CP 25WB CAULK ON
BOTH SIDES OF WALL
INSULATED CABLES OR CONDUIT
FIRE RATED CONCRETE/CONCRETE
BLOCK WALL
DAMMING MATERIAL
(BACKER ROD, FIBER−GLASS
OR MINERAL WOOL)
NON−METALLIC SLEEVE MAY
EXTEND A MAX 2" (51 mm)
BEYOND THE WALL SURFACE
TYPICAL FIRESTOP FOR CABLES/CONDUIT
THROUGH CONCRETE WALLSD4
DETAIL
NOT TO
SCALE
SCALE:
D5
NOTE:
TYPICAL DETAIL SHOWING GENERAL FIRE
STOPPING PROCEDURE. ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SPACE BETWEEN
PIPE AND/OR INSULATION AND OPENING.
FOLLOW MANUFACTURER'S INSTRUCTIONS.
1/4" MINIMUM DIAMETER
BEAD OF 3M FIRE BARRIER CP
25 CAULK OR MP MOLDABLE
PUTTY
METALLIC
CONDUIT
1/4" MINIMUM DIAMETER
BEAD OF 3M FIRE BARRIER
CP 25 CAULK OR MP
MOLDABLE PUTTY
1 OR 2 HOUR FIRE RATED
GYPSUM WALL BOARD
WOOD OR STEEL STUD
FIRESTOP FOR METAL CONDUIT
THROUGH GYPSUM WALL BOARD
NL
E
T−X X
X
M
J
T
S
TTB
M
CCTV
FACP
ELECTRICAL SYMBOLS LIST
SYMBOL DESCRIPTION
LIGHTING SYMBOLS
LIGHT FIXTURE TO STAY ON AT NIGHT (NIGHT LIGHT). PROVIDE UNSWITCHED LIGHTING CIRCUIT.
LIGHT FIXTURE ON EMERGENCY POWER PROVIDE BATTERY AS REQUIRED
LIGHTING FIXTURE CALL OUT. NUMBER INDICATES A SUGGESTED QUANTITY- TO BE VERIFIED
REFERENCE NOTES CALL OUT
DUAL TECH CEILING MOUNTED OCCUPANCY SENSOR TO CONTROL LIGHTING IN THE ROOM
PHOTOCELL
POWER SYMBOLS
DUPLEX CONVENIENCE OUTLET - 20 AMP
DUPLEX CONVENIENCE OUTLET - 20 AMP, GFCI PROTECTED.
JUNCTION BOX - SIZE AND FUNCTION AS REQUIRED
EACH ARROW INDICATES A HOME RUN. RUN GROUND CONDUCTOR REGARDLESS OF CONDUIT TYPE.
NUMBER OF CONDUCTORS AS REQUIRED
FUSED DISCONNECT SWITCH - SIZE AS REQUIRED-STANDARD HEIGHT TO BE 66" AFF TO THE TOP
FLUSH TELEPHONE, DATA OUTLET
FLUSH TELEPHONE OUTLET
FLUSH DATA OUTLET
MOTOR LOCATION
MECHANICAL EQUIPMENT CALL OUT
MANUAL DISCONNECT WITH THERMAL OVERLOAD PROTECTION
ELECTRICAL PANEL LOCATION
TELEPHONE TERMINAL BOARD
ELECTRICAL METER LOCATION
SPECIAL SYSTEMS SYMBOLS
CLOSED CIRCUIT TELEVISION CAMERA
FIRE ALARM CONTROL PANEL (FLUSH MOUNTED)
GENERAL NOTE SYMBOLS
WP INDICATES WEATHER PROOF EQUIPMENT
PC
XX−1
DETAIL
NOT TO
SCALE
SCALE:
CIRCUIT LENGTH (REFER TO THE CHART ABOVE
FOR WIRE SIZE, PROPERLY UPSIZE THE
GROUND CONDUCTOR AND CONDUIT SIZE)
#12
LAST EQUIPMENT
#10
#8
#6
#4
#3
#2
#1
#1/0
#4/0
60 FT
110 FT
170 FT
260 FT
410 FT
500 FT
640 FT
790 FT
910 FT
1600 FT
70 FT
110 FT
170 FT
270 FT
330 FT
430 FT
530 FT
600 FT
1060 FT
70 FT
100 FT
160 FT
200 FT
260 FT
320 FT
360 FT
640 FT
90 FT
130 FT
160 FT
210 FT
260 FT
300 FT
530 FT
110 FT
140 FT
180 FT
220 FT
260 FT
460 FT
#2/0 1080 FT 720 FT 430 FT 360 FT 310 FT
#3/0 1330 FT 890 FT 540 FT 450 FT 380 FT
110 FT
190 FT
290 FT
460 FT
710 FT
870 FT
1120 FT
1370 FT
130 FT
190 FT
300 FT
470 FT
580 FT
740 FT
920 FT
110 FT
180 FT
280 FT
350 FT
450 FT
550 FT
150 FT
230 FT
290 FT
370 FT
460 FT
200 FT
250 FT
320 FT
390 FT
450 FT
620 FT 530 FT
520 FT630 FT
1250 FT 750 FT
1050 FT
1880 FT
1570 FT
150 FT
260 FT
390 FT
610 FT
950 FT
1160 FT
170 FT
260 FT
410 FT
630 FT
770 FT
990 FT
1220 FT
150 FT
240 FT
380 FT
460 FT
590 FT
730 FT
200 FT
310 FT
380 FT
490 FT
610 FT
270 FT
330 FT
420 FT
520 FT
1490 FT
1830 FT
270 FT
450 FT
680 FT
1070 FT
2010 FT
300 FT
450 FT
710 FT
1340 FT
270 FT
420 FT
800 FT
350 FT
670 FT 570 FT
1640 FT 1090 FT 650 FT 540 FT 470 FT
LAST LIGHT FIXTURE
LAST OUTLET
NOTES:
1. UPSIZE WIRES AS NECESSARY TO MEET MAXIMUM
VOLTAGE DROP REQUIREMENTS TO THE END
DEVICE/EQUIPMENT AS REQUIRED BY NEC (3% DROP
TO PANEL + 2% DROP TO LAST DEVICE/EQUIPMENT)
2. FOR DISTANCES LONGER THAN SHOWN, UPSIZE
WIRES AS REQUIRED BY NEC TO COMPLY WITH THE
VOLTAGE DROP REQUIREMENTS.
3. UTILIZE THE SAME LOGIC TO UPSIZE CONDUCTORS
FOR BREAKER SIZES NOT SHOWN IN THE CHART.
COORDINATE WITH THE ENGINEER AS NECESSARY.
BRANCH PANEL
BREAKER SIZE
D8
TYPICAL BRANCH CIRCUIT CONDUCTOR SIZE DETAIL
(BASED ON DISTANCE AND VOLTAGE DROP)
WIRE
SIZE
COPPER
120 VOLT
A
M P
B R
E A
K E
R
DISTANCE
208 VOLT
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
277 VOLT 480 VOLT
A
M P
B R
E A
K E
R
DISTANCE
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
DISTANCE
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
DISTANCE
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
A
M P
B R
E A
K E
R
BREAKER SIZE
BREAKER SIZE
DETAIL
NOT TO
SCALE
SCALE:
36" FOR 208 V
48" FOR 480 V
D9
REQUIRED INDOOR INSTALLATION
SPACES FOR ELECTRICAL EQUIPMENT
WIDTH OF EQUIPMENT (MINIMUM 30")
HEIGHT OF
EQUIPMENT
(6’ MINIMUM)
6’ OR CEILING
HEIGHT
EXHAUST DUCT
DEDICATED ELECTRICAL SPACE
SPRINKLER ALLOWED
6 1/2 FT
WORKING SPACE
NOTES:
1. THE WIDTH OF THE WORKING SPACE SHALL BE AT LEAST 30" OR THE WIDTH OF THE
PANEL BOARD, WHICHEVER IS GREATER.
2. WORKING SPACE HEAD ROOM SHALL BE A MINIMUM OF 6.5'.
3. THE MAXIMUM HEIGHT OF CIRCUIT BREAKERS/DISCONNECT SWITCH HANDLE SHALL
NOT BE MORE THAN 6'6".
DETAIL
NOT TO
SCALE
SCALE:
RECESSED TROFFER
FIXTURE CLAMP − PROVIDE
ONE PER SIDE OF EACH
FIXTURE
LAY−IN GRID SYSTEM
WIRE HANGER AT EACH CORNER
OF FIXTURE (TYP) INDEPENDENT
OF CEILING SUPPORT SYSTEM
TYPICAL RECESSED FIXTURE MOUNTING DETAIL
D10
DETAIL
NOT TO
SCALE
SCALE:
D38
TYPICAL CONDUIT RACK SUPPORT DETAIL
CONDUIT CLAMP - 3/4" TO 1"
UNISTRUT 2 PIECE CHANNEL
PIPE STRAPS - 1 1/4" TO 6"
BEAM CLAMP, HANGER CLAMP,
OR APPROVED SUPPORT, AS
REQUIRED BY WEIGHT
SUPPORTED
UNISTRUT CHANNEL -
SIZE AS REQUIRED BY
WEIGHT SUPPORTED
RACEWAY 3/4" TO 6" (TYP.)
ALL THREAD ROD
SIZE AS REQUIRED
(MIN. 3/8")
DETAIL
NOT TO
SCALE
SCALE:
NOTES:
1. ALL CIRCUITS SHALL RUN IN CONDUIT (3/4" MINIMUM). MC CABLE IS ONLY ALLOWED IN
CONCEALED AREA FOR CONNECTION TO THE LIGHT FIXTURES (6 FEET MAX).
2. THIS DETAIL IS DIAGRAMMATIC IN NATURE AND IS NOT MEANT TO BE COMPREHENSIVE.
TYPICAL CONDUIT RUN DETAIL
D44
J
J
J
L
L
L
J
O
O
L
L
L
O
O
O
L
L
L
ELECTRICAL
PANEL
NOT ALLOWED
3/4" MIN. CONDUIT
MC CABLE NOT
ALLOWED
L
O
J
LIGHT FIXTURE
ELECTRICAL OUTLET
JUNCTION BOX
6 FEET MAX, MC
CABLE ALLOWED
IN CONCEALED
AREA
O
3/4" MINIMUM CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
3/4" MIN. CONDUIT
MC CABLE NOT ALLOWED
MC CABLE NOT ALLOWED
MC CABLE
NOT ALLOWED
MC CABLE
NOT ALLOWED
MC CABLE
NOT ALLOWED
6 FEET MAX, MC
CABLE ALLOWED
IN CONCEALED
AREA
6 FEET MAX, MC
CABLE ALLOWED
IN CONCEALED
AREA
1. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE (NEC) AND
ALL THE LOCAL CODES.
2. PROVIDE TAMPER-RESISTANCE RECEPTACLES IN THE AREAS WHERE KIDS ARE PRESENT, AND
AREAS REQUIRED BY NEC 406.12(3). INCLUDING DWELLING UNITS, GUEST ROOMS,
PRESCHOOL/ELEMENTARY/ CHILDCARE FACILITIES, WAITING ROOMS, ETC.
3. NOT MORE THAN THREE (3) CIRCUITS SHALL BE INSTALLED IN A 3/4" CONDUIT.
4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. DO NOT SHARE THE NEUTRAL
CONDUCTOR IN HOMERUNS. (NEC 210.4).
5. THE MINIMUM SIZE OF THE CONDUCTORS SHALL BE A NO. 12 AWG, THHN COPPER. UNLESS
INDICATED OTHERWISE ON THE DRAWINGS.
6. LIGHT FIXTURES, RACEWAYS AND OTHER ELECTRICAL DEVICES SHALL BE SUPPORTED FROM
THE STRUCTURE NOT FROM METAL OR WOOD CEILING DECK. UTILIZE UNISTRUTS IN BETWEEN
STRUCTURE AS NEEDED.
7. ALL J-BOXES SHALL BE RECESSED INTO THE FINISHED WALL/CEILING UNLESS THE FINISHED
WALL/CEILING IS CONCRETE AND IS NOT BEING FURRED OUT. ALL CONDUITS SHALL BE RUN
THROUGH THE STUDS BEHIND THE FINISHED WALL/CEILING. COORDINATE WITH
ENGINEER/ARCHITECT PRIOR TO ROUGH-IN FOR ANY EXPOSED CONDUITS/J-BOX THAT
CANNOT BE RUN INSIDE THE WALL/CEILING AND NEED TO BE SURFACE MOUNTED ON THE
FINISHED WALL/CEILING. SURFACE MOUNTED CONDUITS IN EXPOSED CEILING SHALL BE
INSTALLED CLOSE TO CEILING (AND NOT PENDANT MOUNTED BELOW THE
BEAMS/STRUCTURE).
8. PROVIDE GFCI PROTECTED OUTLETS FOR EVERY LOCATION SHOWN ON THE DRAWINGS. DO
NOT USE MULTIPLE LOCATION PROTECTION.
9. WHERE CIRCUIT CONDUCTORS ARE TO BE INCREASED IN SIZE TO MEET THE VOLTAGE DROP
REQUIREMENT, THE EQUIPMENT GROUNDING CONDUCTORS MUST BE INCREASED
ACCORDINGLY (NEC 250.122)
10. ALL J-BOXES SHALL HAVE A MINIMUM DEPTH OF 2-1/8" UNLESS OTHERWISE SPECIFIED.
SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD RINGS.
11. ALL THE HOMERUNS MUST BE ACCESSIBLE. DO NOT CARRY A HOMERUN FROM ONE DEVICE
TO ANOTHER WHICH IS TIED TO A SEPARATE HOMERUN INSIDE THE WALL. MARK ON ALL THE
J-BOXES THE CIRCUIT NAMES AND NUMBERS.
12. ALL J-BOXES IN FIRE RATED WALLS SHALL MEET THE FIRE RATING REQUIREMENT OF THE
WALL AND SHALL NOT BE INSTALLED LESS THAN 24" BACK-TO-BACK.
13. ALL DISCONNECTS SHALL BE OF A HEAVY-DUTY TYPE.
14. ALL DISCONNECTS, J-BOXES, AND CONDUITS EXPOSED TO THE OUTSIDE WEATHER AND
MECHANICAL ROOMS SHALL BE OF A NON-CORROSIVE, WEATHERPROOF TYPE.
15. ALL NEW EXPOSED CONDUITS MUST RUN AGAINST THE WALL OR CEILING. DO NOT PENDANT
MOUNT ANY CONDUIT FROM THE CEILING. EXPOSED CONDUITS ARE ONLY ALLOWED IN
EXPOSED CEILING AREA.
16. ALL MATERIALS USED IN INSTALLATION SHALL BE U.L. APPROVED AND NEW.
17. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (ROMEX NOT PERMITTED).
18. ALL EXTERIOR RECEPTACLES SHALL BE OF WEATHER-RESISTANT TYPE AS PER NEC 406.8.
19. NO CONDUITS SHALL RUN IN DUCT WORK.
20. CABLES OR RACEWAYS INSTALLED IN EXPOSED OR CONCEALED LOCATIONS UNDER METAL-
CORRUGATED SHEET ROOF DECKING SHALL BE INSTALLED AND SUPPORTED SO THAT THE
NEAREST OUTSIDE SURFACE OF THE CABLE OR RACEWAY IS NOT LESS THAN 38 MM (1 1/2 IN.)
FROM THE NEAREST SURFACE OF THE ROOF DECKING.
21. PROVIDE LATERAL AND LONGITUDINAL BRACING FOR ALL CONDUIT RACKS, CABLE TRAYS,
ETC., EXCEEDING 20 FEET IN LENGTH.
22. MINIMUM SIZE CONDUIT SHALL BE 3/4" FOR INTERIOR APPLICATION, AND 1" FOR CONDUIT
BURIED BELOW GRADE IN EXTERIOR APPLICATION.
23. LABELING IS REQUIRED FOR ALL PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL
CENTERS, MOTOR STARTERS, TRANSFORMERS, MAJOR JUNCTION BOXES, DISCONNECT
SWITCHES, BREAKERS, PUSH BUTTONS, ETC., INTERLOCKS AND RELAY PANELS.
24. USE RIGID STEEL, SET SCREW TYPE FITTINGS ONLY. DIE CAST FITTING SHALL NOT BE USED.
25. USE EPOXY ANCHORS TO SUPPORT THE ELECTRICAL EQUIPMENT. EXPANSION ANCHOR
BOLTS ARE NOT ACCEPTABLE.
26. AT THE END OF THE JOB, PROVIDE BLANK, MATCHING COVER PLATES FOR ALL J-BOXES
WHERE DEVICES HAVE NOT YET BEEN INSTALLED.
27. SEAL AROUND ALL CONDUIT PENETRATIONS THROUGH WALLS AND CEILINGS WITH A FIRE
RATED MATERIAL. 3M IS AN APPROVED MANUFACTURER.
28. PRIOR TO SUBMITTAL FOR A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND
INCLUDE IN THEIR BID PACKAGE ALL CHARGES RELATED TO EXISTING CONDITIONS AND
DEMOLITION WORK. PROVIDE SHOP DRAWINGS AS REQUIRED BY CONSTRUCTION
DOCUMENTS. ALL LABOR, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A
PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT. REPLACE OR REPAIR
ALL DEFECTS DURING THE GUARANTEED PERIOD.
29. THE ELECTRICAL CONTRACTOR SHALL TERMINATE THE ELECTRICAL CONNECTIONS TO ALL
THE EQUIPMENT BY PROVIDING THE NECESSARY MALE/ FEMALE CONNECTOR, RECEPTACLE,
PLUG, ETC.
30. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE MECHANICAL
CONTRACTOR SO THAT NO PIPING, DUCTS, OR OTHER EQUIPMENT SHALL BE INSTALLED IN
THE ENTRY, PASS THROUGH ELECTRICAL ROOM OR SPACES ABOVE OR BELOW ELECTRICAL
PANELS.
31. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE,
CONNECTION REQUIREMENT, ETC.) OF EQUIPMENT FURNISHED UNDER OTHER DIVISIONS
WITH APPROVED SHOP DRAWINGS.
32. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER, IN WRITING, OF ANY
DISCREPANCIES FOUND BETWEEN THE INTENDED FUNCTION OF EQUIPMENT AND EQUIPMENT
SPECIFIED IN THE CONTRACT DOCUMENTS WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR
TO ISSUANCE OF THE FINAL ADDENDUM. FAILURE TO REPORT ANY DISCREPANCY (CATALOG
NUMBERS, DISCONTINUED ITEMS, ETC.) DOES NOT RELIEVE THE CONTRACTOR FROM
PROVIDING EQUIPMENT WHICH SHALL CONFORM TO AND FULFILL THE INTENT OF THE
CONTRACT DOCUMENTS. NOR SHALL IT BE USED AS A CONDITION TO OBTAIN ADDITIONAL
FUNDS FROM THE OWNER AFTER THE CONTRACT IS AWARDED. THE CONTRACTOR SHALL
REQUEST ALL CLARIFICATIONS OF CONTRACT DOCUMENT REQUIREMENTS, IN WRITING, TO
THE ARCHITECT/ ENGINEER WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE
OF THE FINAL ADDENDUM.
33. CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS
SPECIFICALLY NOTED OTHERWISE.
34. DETAILS ARE SHOWN ON DIFFERENT SHEETS. THE CONTRACTOR SHALL REFER TO THOSE
DETAILS WHETHER OR NOT CALLED IN REFERENCE NOTES.
35. PROVIDE MANUAL THERMAL SWITCHES WITH PILOT LIGHT.
36. PROVIDE A TYPED LABEL FOR ALL DUPLEX OUTLETS AND LIGHT SWITCHES TO INDICATE
WHICH CIRCUIT THEY ARE TIED TO.
37. CONTRACTOR MUST PAY FOR HIS OWN ELECTRICITY DURING CONSTRUCTION. COORDINATE
WITH THE LOCAL POWER COMPANY FOR SETTING UP TEMPORARY POWER.
38. THE OWNER MUST SCHEDULE INTERRUPTIONS OF SERVICE WHEN CONTRACTOR WISHES TO
MAKE UTILITY CONNECTIONS. NOTIFY, IN WRITING, THE OWNER'S REPRESENTATIVE 72 HOURS
PRIOR TO TIME WHEN INTERRUPTION IS DESIRED. INTERRUPTION MUST BE AT THE COUNTY'S
CONVENIENCE. OVERTIME, IF REQUIRED FOR THIS WORK, IS TO BE AT CONTRACTOR’S
EXPENSE.
39. UTILIZE INTERMEDIATE METAL CONDUIT (IMC) IN WET LOCATIONS OR AREAS SUBJECT TO
DAMAGE.
40. FLEXIBLE METAL CONDUIT: PROVIDE ZINC-COATED, FLEXIBLE METAL CONDUIT FOR
CONNECTIONS TO MOTORS, TRANSFORMERS, OR OTHER EQUIPMENT SUBJECT TO
MOVEMENT OR VIBRATION.
41. ALL CONDUCTORS SHALL BE IN CONDUIT (3/4" MINIMUM). MC CABLES IS NOT ALLOWED.
42. ALL UNDERGROUND CONDUITS SHALL BE BURIED 24 INCHES MINIMUM UNDER THE GROUND.
43. ALL METALLIC CONDUITS, JOINTS, FITTINGS, ETC. IN CONTACT WITH THE GROUND SHALL BE
SPIRAL WRAPPED WITH 3M SCOTCHRAP-51, 20 MIL TAPE (OR APPROVED EQUAL). 1/2" OVERLAP
IS REQUIRED.
44. ALL EMERGENCY PANELS AND EMERGENCY CIRCUIT BOXES SHALL BE LABELED IN RED.
45. PROVIDE TYPED PANEL INDEX FOR EXISTING ELECTRICAL PANELS AFFECTED BY THE SCOPE
OF THIS WORK. EXISTING/UNAFFECTED CIRCUITS IN THE PANEL SHALL BE ITALICIZED AND
CHANGED/ADDED CIRCUITS SHALL BE TYPED BOLD.
GENERAL NOTES:
334543-2202
MANSOUR
AGHDASI
NO.
375 WEST 200 SOUTH
SALT LAKE CITY, UT 84101
801.521.8600P www.gsbsarchitects.com
OWNER PROJECT NO.:
GSBS PROJECT NO.:
ISSUED DATE:
REVISIONS:
RE
V
REV
#1025
10/17/2025
2022.055.14
GENERAL NOTES &
DETAILS & SCHEDULES
SALT LAKE COUNTY
SLCO DRAPER
LIBRARY HVAC
REMODEL
1136 Pioneer Rd, Draper, UT 84020
CD Set
E-001
2. CIRCUIT NUMBERS ARE SCHEMATIC AND SHOW THE DESIGN INTENTION AND LOAD BALANCE REQUIREMENTS. CONTRACTORS SHALL VERIFY ALL EXISTING AVAILABLE CIRCUITS AND THOSE WHICH BECOME AVAILABLE AS A RESULT OF DEMOLITION. CONTRACTOR SHALL INDICATE ACTUAL CIRCUITS USED ON AS-BUILT DRAWINGS. THE CONTRACTOR IS TO INFORM GC/ENGINEER IF SUFFICIENT BREAKER SPACES DID NOT FREE UP, PRIOR TO ROUGH-IN.
1. PROVIDE NEW CIRCUIT BREAKERS AS NECESSARY.