8--9- Plans- LIB125639 Draper Library HVAC Replacement.pdf

PDF 7 MB Posted

Attached to
SLCo LIB125639 Draper Library HVAC Replacement - CONST
Solicitation number
SLCo LIB125639 Draper Library HVAC Replacement - CONST
Issued by
Utah

About this file

The documents are construction documents for the SLCO (Salt Lake County) Draper Library HVAC Remodel project, prepared by GSBS Architects and Focus Mechanical Consulting. The project involves a comprehensive mechanical, electrical, and architectural renovation of the Draper City Library located at 1136 Pioneer Road in Draper, Utah. The construction documents are dated 10/17/2025 and include detailed plans for demolishing existing HVAC systems and installing new mechanical equipment, including a chiller (CH-1), fan coils (FC-1 through FC-5), control valves, pumps, and associated infrastructure. The project scope encompasses modifications to the library's mechanical systems, electrical systems, and potentially some architectural elements to improve the building's heating, ventilation, and air conditioning capabilities.

The mechanical systems will be upgraded with a 20-ton air-cooled chiller with a pump package, variable frequency drives, and a buffer tank. The renovation includes replacing existing control valves, relocating thermostats, and installing new fan coils with cooling and heating capabilities. Electrical upgrades involve modifications to the existing electrical panel, installation of new circuit breakers, and potential power distribution changes. The project appears to be funded by Salt Lake County and is designed to enhance the library's mechanical and electrical infrastructure. The documents provide comprehensive technical details, including equipment schedules, piping diagrams, control schematics, and specific sequence of operations for the new HVAC systems, indicating a thorough and detailed approach to the library's infrastructure improvement.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ALLEN

8044423-0301

JESSE DEE

L I

C E

N

S ED AR CH

I T

E C

T

S T

ATE OF UTA

H

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600P www.gsbsarchitects.com

1220 S. 300 W. SLC, UT 84101

801-486-2222

ELECTRICAL ENGINEERING:

EELD ELECTRICAL ENGINEERING

AND LIGHTING DESIGN LLC

259 WEST 1500 NORTH

HARRISVILLE, UTAH 84404

801.631.5776

MECHANICAL ENGINEERING:

FOCUS MECHANICAL CONSULTING

GSBS PROJECT NO.:

ISSUED DATE:

SLCO DRAPER LIBRARY HVAC REMODEL

CONSTRUCTION DOCUMENTS

10/17/2025

2022.055.14

SALT LAKE COUNTY

SLCO DRAPER

LIBRARY HVAC

REMODEL

1136 Pioneer Rd, Draper, UT 84020

Enter Address Here -->

10/17/2025

10/17/2025

334543-2202

MANSOUR

AGHDASI

NO.

PROJECT LOCATION

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600P www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

ABBREVIATIONS

VICINITY MAP DRAWING INDEX

REV

GRAPHIC SYMBOLS MATERIALS/LEGEND

BLOCKING, ROUGH WOOD

METAL (LARGE SCALE)

QUARRY/CERAMIC TILE

GRAVEL

EARTH

CONCRETE MASONRY UNIT

CONCRETE (POURED IN PLACE)

GYPSUM BOARD OR SETTING BEDS

INSULATION (BATT & BLANKET)

INSULATION (RIGID/SEMI-RIGID)

CONTINUOUS ROUGH WOOD

PLYWOOD

FACE BRICK

GRID

GRID

W1

100A

ELEVATION CONTROL POINT

OR DATUM POINT

EXTERIOR ELEVATION SYMBOL

ELEVATION IDENTIFICATION

SHEET WHERE ELEVATION IS DRAWN

WALL SECTION SYMBOL

SECTION REFERENCE/

SHEET WHERE SECTION IS DRAWN

BUILDING SECTION SYMBOL

SECTION REFERENCE/

SHEET WHERE SECTION IS DRAWN

DETAIL SYMBOL

DETAIL NUMBER/

SHEET WHERE DETAIL IS DRAWN

REVISION TAG

GRID LINES

NAME

#SHEET

SHEET

SHEET

SHEET

SHEET

SCALE

VIEW NAME

VIEW TITLE

VIEW NUMBER/

SHEET WHERE VIEW IS LOCATED

VIEW NAME/ VIEW SCALE

INTERIOR ELEVATION SYMBOL

ELEVATION IDENTIFICATION

SHEET WHERE ELEVATION IS DRAWN

#SHEET

ROOM TAG

ROOM NAME

ROOM NUMBER

WINDOW TAG

WINDOW OR STOREFRONT NUMBER

DOOR TAG

DOOR NUMBER

WOOD

COMPACTED FILL

FIREPROOFING

10/17/2025

2022.055.14

G001

DRAWING INDEX,

SYMBOLS AND

ABBREVIATIONS

SALT LAKE COUNTY

SLCO DRAPER

LIBRARY HVAC

REMODEL

1136 Pioneer Rd, Draper, UT 84020

Enter Address Here -->

CONSTRUCTION DOCUMENTS

ABV ABOVE

AFF ABOVE FINISH FLOOR

ADJ ADJUSTABLE

ALUM ALUMINUM

ASTM AMERICAN SOCIETY FOR TESTING MATERIALS

AB ANCHOR BOLT

ANOD ANODIZED

APPROX APPROXIMATE

ARCH ARCHITECTURAL OR ARCHITECT

AHJ AUTHORITY HAVING JURISDICTION (BUILDING

DEPARTMENT)

BP BASE PLATE

BSMT BASEMENT

BRG BEARING

BTWN BETWEEN

BITUM BITUMINOUS

BLKG BLOCKING

BD BOARD

BO BOTTOM OF

BLDG BUILDING

CLG CEILING

CL CENTER LINE

CLR CLEAR

COL COLUMN

CONC CONCRETE

CMU CONCRETE MASONRY UNIT

CONST CONSTRUCTION

CONT CONTINUOUS

CFOI CONTRACTOR FURNISHED OWNER INSTALLED

CJ CONTROL JOINT

COORD COORDINATE

DEMO DEMOLISH / DEMOLITION

DEPT DEPARTMENT

DTL DETAIL

DIA DIAMETER

DIM DIMENSION

DW DISHWASHER

DBL DOUBLE

DN DOWN

DRWR DRAWER

DWGS DRAWINGS

EA EACH

ELEC ELECTRICAL

EL ELEVATION

ELEV ELEVATOR

EQ EQUAL

EPDM ETHYLENE PROPYLENE DIENE M-CLASS

(ROOFING)

EXIST EXISTING

EXP EXPANSION

EJ EXPANSION JOINT

EXT EXTERIOR

FT FEET / FOOT

FV FIELD VERIFY

FIN FINISH

FF FINISH FLOOR

FA FIRE ALARM

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FLR FLOOR

FD FLOOR DRAIN

FTG FOOTING

FDN FOUNDATION

GAL GALLON

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GALV GALVANIZED

GA GAUGE

GC GENERAL CONTRACTOR

GL GLASS / GLAZING

GLB GLUE LAMINATED BEAM

GND GROUND

GYP BD GYPSUM BOARD

HW HARDWARE

HVAC HEATING / VENTILATION / AIR CONDITIONING

H HEIGHT

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HYD HYDRANT

IN. INCHES OR INCH

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

JNT JOINT

LAV LAVATORY

LT WT LIGHT WEIGHT

MAINT MAINTENANCE

MFR MANUFACTURER

MO MASONRY OPENING

MAT MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MTL METAL

MIN MINIMUM

MISC MISCELLANEOUS

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO. NUMBER

OC ON CENTER

OPP OPPOSITE

OD OUTSIDE DIAMETER

OH OVERHEAD

OH DR OVERHEAD DOOR

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

PNT PAINTED OR PAINT

PTN PARTITION

PVMT PAVEMENT

PERP PERPENDICULAR

PLAM PLASTIC LAMINATE

PL PLATE

PLUM PLUMBING

PVC POLYVINYL CHLORIDE

PCF POUNDS PER CUBIC FOOT

PLF POUNDS PER LINEAL FOOT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED

QTY QUANTITY

RAD RADIUS

RE REFER / REFERENCE

RCP REFLECTED CEILING PLAN

REF REFRIGERATOR

REINF REINFORCED

REQ REQUIRED

REV REVISION

RD ROOF DRAIN

RM ROOM

RO ROUGH OPENING

SCHED SCHEDULE

SECT SECTION

SHT SHEET

SIM SIMILAR

STC SOUND TRANSMISSION CLASS

SPEC SPECIFICATION

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STRU STRUCTURAL

SUSP SUSPENDED

SYS SYSTEM

THRU THROUGH

T.O. TOP OF

TOA TOP OF ASPHALT

TOC TOP OF CURB

TOF TOP OF FOOTING

TOS TOP OF SLAB OR SIDEWALK

TOW TOP OF WALL

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VEN VENEER

FV VERIFY IN FIELD

VERT VERTICAL

VEST VESTIBULE

WC WATER CLOSET

WRB WEATHER RESISTIVE BARRIER

W WIDTH

W/ WITH

W/O WITHOUT

WD WOOD

NOTE:

ABBREVIATIONS FOR FINISHED

MATERIALS ARE DESCRIBED IN

THE FINISH LEGEND.

DRAWING INDEX

Sheet Number Sheet Name

GENERAL

G000 COVER SHEET

G001 DRAWING INDEX, SYMBOLS AND ABBREVIATIONS

ARCHITECTURAL

AE101 DEMO & NEW FLOOR PLAN, REFLECTED CEILING PLAN

AE102 DEMO & NEW FLOOR PLAN

AE201 INTERIOR ELEVATION, DETAIL & 3D VIEWS

MECHANICAL

MH001 SHEET INDEX, GENERAL NOTES, & ABBREVIATIONS

MD100 UNDER FLOOR MECHANICAL DEMO PLAN

MD101 MECHANICAL DEMO PLAN

MH100 UNDER FLOOR MECHANICAL REMODEL PLAN

MH101 MECHANICAL REMODEL PLAN

MH401 ENLARGED MECHANICAL PLANS

MH402 ENLARGED MECHANICAL PLANS

MH501 MECHANICAL DETAILS

MH601 MECHANICAL SCHEDULES

ELECTRICAL

E-001 GENERAL NOTES & DETAILS & SCHEDULES

EDL-101 LEVEL ONE FLOOR PLAN - DEMOLITION & LIGHTING

EP-101 MAIN FLOOR PLAN & MEZZANINE - POWER

Grand total: 17

1 2

DEMOLISH EXISTING FLOOR FINISH

FOR STOREFRONT CONSTRUCTION

4"

4"

E Q

E

Q

EQ.EQ.

1 2

AE201

VESTIBULE

NEW STOREFRONT WITH

DOUBLE SLIDING DOOR

NEW STOREFRONT

SF01

SF

1 2

NEW STOREFRONT SOFFIT

3' -0

EQ. EQ.

3'-0"

E Q

E

Q

1 2

DEMOLISH EXISTING CEILING FOR

STOREFRONT CONSTRUCTION

DEMOLISH LIGHT FIXTURE FOR

STOREFRONT CONSTRUCTION,

SALVAGE LIGHT FIXTURE FOR

REINSTALLATION

EQ

EQ

3' -0

EQ EQ

3'-0"

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600P www.gsbsarchitects.com

ALLEN

8044423-0301

JESSE DEE

L I

C E

N

S ED AR CH

I T

E C

T

S T

ATE OF UTA

H

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

RESERVED FOR CONSULTANT LOGO

10/17/2025

2022.055.14

DEMO & NEW FLOOR

PLAN, REFLECTED

CEILING PLAN

SALT LAKE COUNTY

SLCO DRAPER

LIBRARY HVAC

REMODEL

1136 Pioneer Rd, Draper, UT 84020

Enter Address Here -->

CONSTRUCTION DOCUMENTS

AE101

10/17/2025

1/4" = 1'-0"AE101

1 DEMOLITION PLAN - LEVEL ONE

1/4" = 1'-0"AE101

2 FLOOR & WALL TYPES PLAN - LEVEL ONE

1/4" = 1'-0"AE101

3 REFLECTED CEILING PLAN - LEVEL ONE

1/4" = 1'-0"AE101

4 DEMOLITION REFLECTED CEILING PLAN - LEVEL ONE

DEMOLISH EXISTING SCREEN SYSTEM

EXISTING MECH. EQUIPMENT

FILL CUT POST WITH CONCRETE

TRENCH FOR WATER LINE AND ELECTRICAL

CONDUIT, CORE THROUGH WALL

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600P www.gsbsarchitects.com

ALLEN

8044423-0301

JESSE DEE

L I

C E

N

S ED AR CH

I T

E C

T

S T

ATE OF UTA

H

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

RESERVED FOR CONSULTANT LOGO

10/17/2025

2022.055.14

DEMO & NEW FLOOR

PLAN

SALT LAKE COUNTY

SLCO DRAPER

LIBRARY HVAC

REMODEL

1136 Pioneer Rd, Draper, UT 84020

Enter Address Here -->

CONSTRUCTION DOCUMENTS

AE102

10/17/2025

1/4" = 1'-0"AE102

1 DEMO SITE PLAN - LEVEL ONE

1/4" = 1'-0"AE102

2 SITE PLAN - LEVEL ONE

SC

H

E D

. C

LN

G

H E

IG

H

T

SC

H

E D

. C

LN

G

H E

IG

H

T

AE201

AE201

AE201

AE201

INSIDE OF VESTIBULE INSIDE OF LOBBY

SPRAY FOAM TO CREATE AIR TIGHT

SEAL AROUND STRUCTURE

EXISTING STRUCTURE

EXTEND DRYWALL TO STRUCTURE ABOVE

M A

TC

H

E X

IS

TI

N G

M A

TC

H

E X

IS

TI

N G

EXISTING SLOPED GLASS

STRUCTURAL SEALANT

AE201

AE201

AE201

LEVEL 1

100' - 0"

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600P www.gsbsarchitects.com

ALLEN

8044423-0301

JESSE DEE

L I

C E

N

S ED AR CH

I T

E C

T

S T

ATE OF UTA

H

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

RESERVED FOR CONSULTANT LOGO

10/17/2025

2022.055.14

INTERIOR ELEVATION,

DETAIL & 3D VIEWS

SALT LAKE COUNTY

SLCO DRAPER

LIBRARY HVAC

REMODEL

1136 Pioneer Rd, Draper, UT 84020

Enter Address Here -->

CONSTRUCTION DOCUMENTS

AE201

10/17/2025

1/2" = 1'-0"AE201

1 STOREFRONT ELEVATION 01

AE201

2 3D View 2

AE201

5 3D View 3

AE201

3 3D View 1

1 1/2" = 1'-0"AE201

4 DRYWALL SOFFIT DETAIL

3" = 1'-0"AE201

6 STOREFRONT DETAIL @ EXISTING GALSS

1/2" = 1'-0"AE201

7 STOREFRONT ELEVATION 02

3" = 1'-0"AE201

8 MULLION BASE DETAIL

3" = 1'-0"AE201

9 CORNER MULLION DETAIL, TYP.

BALL VALVE

GATE VALVE

SHUT-OFF VALVE (GENERIC, UNSPECIFIED TYPE)

BUTTERFLY VALVE

CHECK VALVE

PRESSURE REGULATING VALVE

2-WAY CONTROL VALVE, ELECTRIC ACTUATOR

SOLENOID VALVE

M

3-WAY CONTROL VALVE, ELECTRIC ACTUATOR

M

STRAINER WITH BLOWOFF VALVE, PIPED TO DRAIN

STRAINER WITH VALVE, HOSE END, & CAP

S

CALIBRATED BALANCE VALVE

RELIEF VALVE

PRESSURE & TEMPERATURE TEST PORT

PRESSURE GAUGE W/ COCK

TEMPERATURE SENSOR

T

P

PRESSURE SENSOR

VENTURI-TYPE FLOW MEASURING DEVICE

THERMOMETER WELL

UNION

CONCENTRIC REDUCER

ECCENTRIC REDUCER, FLAT ON BOTTOM

FLEXIBLE PIPE CONNECTOR

PUMP (STYLE AS INDICATED IN SCHEDULE)

PIPE ALIGNMENT GUIDE

PIPE ANCHOR

PIPING SYMBOLS

FIRE DAMPER

SMOKE DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE & SMOKE DAMPER

MANUAL BALANCE DAMPER

MOTORIZED AUTOMATIC DAMPER

SUPPLY DUCT RISE

RETURN DUCT RISE

SUPLY DUCT DROP

SUPPLY DIFFUSER (RECTANGULAR OR ROUND)

EXHAUST GRILLE (RECTANGULAR OR ROUND)

EXHAUST DUCT RISE

EXHAUST DUCT DROP

RETURN GRILLE (WITH SOUNDBOOT IF NOT DUCTED)

FLEXIBLE DUCT

ELBOW WITH TURNING VANES

BRANCH SPIN-IN WITH MANUAL DAMPER

HIGH EFFICIENCY BRANCH TAKE-OFF

ACCESS DOOR

RETURN DUCT DROP

DUCT SYMBOLS

F

FS

S

DUCT SIZE (INCHES) AND TYPE

FIRST VALUE = VISIBLE DIMENSION

KEYED NOTE

REVISION TAG

EQUIPMENT TAG (KEYED TO SCHEDULE)

POINT OF REMOVAL FROM EXISTING

POINT OF CONNECTION TO EXISTING

SHEET NO.

DETAIL OR VIEW TAG

ANNOTATIONS

WALL THERMOSTAT W/EQUIPMENT TAG

HUMIDITY SENSOR OR HUMIDISTAT

CARBON DIOXIDE (CO2) SENSOR

CARBON MONOXIDE (CO) SENSOR

FLOW DIRECTION OR DIFFUSER THROW DIRECTION

A101

VIEW NO.

A101

SHEET NO.

SECTION VIEW TAG

VIEW NO.

CO2

T

RTU-1

CO

H

AHU-1

16/12 RA

AIRFLOW (CFM)

DIFFUSER OR GRILLE NO.

(SEE SCHEDULE)

AIR TERMINAL TAG

BD

M

ELBOW UP

ELBOW DOWN

BRANCH OR TEE W/ BOTTOM CONNECTION

BRANCH OR TEE W/ TOP CONNECTION

COMPRESSED AIR

CHILLED WATER RETURN

CONDENSER WATER SUPPLY

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

DOMESTIC COLD WATER

STEAM

STEAM CONDENSATE

HEATING WATER SUPPLY

OVERFLOW ROOF DRAIN

NATURAL GAS (LINE PRESSURE)

HEATING WATER RETURN

LINE TYPES

DOMESTIC HOT WATER RECIRCULATION

CA

CHS

CHR

CS

CR

S

DOMESTIC HOT WATER

SC

GR (xx%PG)

GR (xx%PG)

GLYCOL SUPPLY (% PROPYLENE GLYCOL)

GLYCOL RETURN (% PROPYLENE GLYCOL)

G (x PSI)

HWR

HWS

OD

ROOF DRAIN

SOFTENED WATER

RD

SW

PURE WATER (RO OR DI, REFER TO SPECS)PW

VACUUMVAC

VENTV

SANITARY WASTE (ABOVE GRADE)W

SANITARY WASTE (BELOW GRADE)

FIRE SERVICEF

CONDENSATE OR EQUIPMENT DRAIND

GREASE WASTEGW

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:1

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

SHEET INDEX, GENERAL

NOTES, & ABBREVIATIONS

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

CONSTRUCTION DOCUMENTS

MH001MH001

ABBREVIATIONS

(E) EXISTING, TO REMAIN

(X) EXISTING, TO BE DEMOLISHED

AFF ABOVE FINISHED FLOOR

AH AIR HANDLER

APD AIR PRESSURE DROP

AS AIR SEPARATOR

BHP BRAKE HORSE POWER

CBV CALIBRATED BALANCE VALVE

CFM CUBIC FEET PER MINUTE

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

COTG CLEAN OUT TO GRADE

CV CONTROL VALVE

DB DRY BULB

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EFT ENTERING FLUID TEMPERATURE

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

FCO FLOOR CLEANOUT

FLA FULL LOAD AMPS

FO FLAT OVAL (DUCT TYPE)

FT FEET

GAL GALLONS

GEA GREASE EXHAUST AIR

GPM GALLONS PER MINUTE

HP HORSEPOWER

IN INCHES

IN. WG INCHES OF WATER GAUGE

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LFT LEAVING FLUID TEMPERATURE

MCA MINIMUM CIRCUIT AMPACITY

MOP MAXIMUM OVERCURRENT PROTECTION

MPSA MEDIUM PRESSURE SUPPLY AIR

NPSHA NET POSITIVE SUCTION HEAD AVAILABLE

NPSHR NET POSITIVE SUCTION HEAD REQUIRED

OA OUTSIDE AIR

PG PROPYLENE GLYCOL

PSI POUNDS PER SQUARE INCH

PSIA PSI, ABSOLUTE PRESSURE

PSIG PSI, GAUGE PRESSURE

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

VOLT/PH VOLTAGE / PHASE

VTR VENT THROUGH ROOF

WB WET BULB

WCO WALL CLEANOUT

WPD WATER PRESSURE DROP

SHEET INDEX

# SHEET NAME

MH001 SHEET INDEX, GENERAL NOTES, & ABBREVIATIONS

MD100 UNDER FLOOR MECHANICAL DEMO PLAN

MD101 MECHANICAL DEMO PLAN

MH100 UNDER FLOOR MECHANICAL REMODEL PLAN

MH101 MECHANICAL REMODEL PLAN

MH401 ENLARGED MECHANICAL PLANS

MH402 ENLARGED MECHANICAL PLANS

MH501 MECHANICAL DETAILS

MH601 MECHANICAL SCHEDULES

DEFERRED SUBMITTALS

CONTRACTOR SHALL PROVIDE COMPLETE DEFERRED SUBMITTALS TO THE ENGINEER AND OWNER IN

ACCORDANCE WITH THE DESCRIPTIONS BELOW. FOLLOWING REVIEW BY OWNER AND ENGINEER,

PROVIDE A COPY OF THE DEFERRED SUBMITTAL TO THE BUILDING OFFICIAL IN ACCORDANCE WITH

IBC 2021 107.3.4.1.

ITEM DRAWING OR SPECIFICATION REFERENCE

SEISMIC RESTRAINT DESIGN OF

NON-STRUCTURAL COMPONENTS

230548

BID ALTERNATES SUMMARY

SUBMIT BID PRICING FOR THE BASE BID AS DESCRIBED. SUBMIT PRICING FOR EACH BID ALTERNATE SEPARATELY, CLEARLY LISTED AS AN AMOUNT TO BE ADDED TO, OR DEDUCTED FROM, THE BASE BID IF ACCEPTED. REFER TO ADDITIONAL NOTES IN THE DRAWINGS AND SPECIFICATIONS FOR

GREATER DETAIL ON BID ALTERNATES.

PORTION OF WORK DESCRIPTION

BASE BID

ALL WORK DEPICTED IN THE DRAWINGS AND SPECIFICATIONS, UNLESS

NOTED AS PART OF A BID ALTERNATE.

BID ALTERNATE #1 <<provide description here>>

O

SET

10/17/2025

1 2 3 4 5 6 7 8

A

B

C

D

REFRIGERANT LINESET (E)

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:1

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

UNDER FLOOR MECHANICAL

DEMO PLAN

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MD100MD100

KEYED NOTES

1 DEMOLISH EXISTING REFRIGERANT LINESET.

0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"

UNDER FLOOR MECHANICAL DEMO PLAN

GENERAL DEMOLITION NOTES

A. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT LOCATION OF ALL EXISTING CONDITIONS RELEVANT TO

THE SCOPE OF WORK.

B. EXISTING MECHANICAL SYSTEMS ARE DEPICTED DIAGRAMMATICALLY. LOCATIONS OF MECHANICAL AND

PLUMBING COMPONENTS ARE APPROXIMATE AND DO NOT SHOW ALL TRANSITIONS, OFFSETS, ETC.

LOCATION AND ORIENTATION MAY DIFFER SLIGHTLY IN RELATION TO OTHER COMPONENTS.

C. DO NOT SHUT-OFF/PUT OUT SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL

DOWNTIME WITH THE OWNER'S PERSONNEL.

D. COMPONENTS THAT ARE TO BE DEMOLISHED ARE SHOWN IN BOLD, DASHED OUTLINES. COMPONENTS

THAT ARE EXISTING TO REMAIN ARE SHOWN IN LIGHT, SOLID OUTLINES.

E. CONTRACTOR SHALL REMOVE FROM THE JOBSITE ANY MATERIALS CALLED OUT TO BE DEMOLISHED AND

RECYCLE ALL RECYCLABLE MATERIALS, AND LEGALLY DISPOSE OF ALL OTHER MATERIALS.

F. REPAIR, REPLACE AND/OR REPAINT TO MATCH EXISTING ALL SURFACES DAMAGED DURING DEMOLITION

OR INSTALLATION OF EQUIPMENT.

CONSTRUCTION DOCUMENTSO

ACU-5 (X) ACU-4 (X) ACU-3 (X) PAC-1 (X) ACU-2 (X) ACU-1 (X)

1 1 1 1 12

T

T

T

1 2 3 4 5 6 7 8

A

B

C

D

MH402

MH401

MH402

MH401

(MEZZANINE ABOVE) (MEZZANINE ABOVE)

REFRIGERANT LINESET (E)

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:2

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

MECHANICAL DEMO PLAN

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MD101MD101

KEYED NOTES

1 RECOVER REFRIGERANT FROM SPLIT SYSTEM. DEMOLISH CONDENSING UNIT AND LINESET.

2 RECOVER REFRIGERANT FROM SPLIT SYSTEM. REMOVE CONDENSING UNIT AND PREPARE FOR

REINSTALLATION.

3 REMOVE SECTION OF EQUIPMENT YARD WALL.

4 DEMOLISH BRANCH DUCT. CAP DUCT DROP IN WALL.

5 REMOVE THERMOSTAT AND PREPARE FOR RELOCATION. PATCH WALL.

6 DEMOLISH EXISTING REFRIGERANT LINESET.

GENERAL DEMOLITION NOTES

A. DO NOT SCALE DRAWINGS. FIELD VERIFY EXACT LOCATION OF ALL EXISTING CONDITIONS RELEVANT TO

THE SCOPE OF WORK.

B. EXISTING MECHANICAL SYSTEMS ARE DEPICTED DIAGRAMMATICALLY. LOCATIONS OF MECHANICAL AND

PLUMBING COMPONENTS ARE APPROXIMATE AND DO NOT SHOW ALL TRANSITIONS, OFFSETS, ETC.

LOCATION AND ORIENTATION MAY DIFFER SLIGHTLY IN RELATION TO OTHER COMPONENTS.

C. DO NOT SHUT-OFF/PUT OUT SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL

DOWNTIME WITH THE OWNER'S PERSONNEL.

D. COMPONENTS THAT ARE TO BE DEMOLISHED ARE SHOWN IN BOLD, DASHED OUTLINES. COMPONENTS

THAT ARE EXISTING TO REMAIN ARE SHOWN IN LIGHT, SOLID OUTLINES.

E. CONTRACTOR SHALL REMOVE FROM THE JOBSITE ANY MATERIALS CALLED OUT TO BE DEMOLISHED AND

RECYCLE ALL RECYCLABLE MATERIALS, AND LEGALLY DISPOSE OF ALL OTHER MATERIALS.

F. REPAIR, REPLACE AND/OR REPAINT TO MATCH EXISTING ALL SURFACES DAMAGED DURING DEMOLITION

OR INSTALLATION OF EQUIPMENT.

0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"

MECHANICAL DEMO PLAN

CONSTRUCTION DOCUMENTSO

1 2 3 4 5 6 7 8

A

B

C

D

3" CHS UP

3" CHR UP

3" CHR

3" CHS

SEE SHEET MH100

FOR CONTINUATION

CV-6A

CV-6B

CV-6C

CV-6D

CV-6E 1

CV-6F 1

CV-6G 1CV-6H 1CV-6I 1

3/4" DCW UP

TO YH-1

3/4" DCW

3/4" DCW UP

2" (E) WATER SERVICE DN

2" (E) WATER SERVICE

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:3

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

UNDER FLOOR MECHANICAL

REMODEL PLAN

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MH100MH100

KEYED NOTES

1 REPLACE EXISTING CONTROL VALVE.

GENERAL NOTES

A. PROVIDE A COMPLETE OPERATING SYSTEM UPON COMPLETION OF THIS PROJECT.

B. INSTALL ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE CURRENTLY ADOPTED EDITIONS OF

THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL FIRE CODE

AND INTERNATIONAL PLUMBING CODE.

C. INSTALL ALL EQUIPMENT ACCORDING TO MANUFACTURER’S INSTRUCTIONS.

D. PLANS ARE DIAGRAMATIC IN NATURE AND DO NOT SHOW EVERY ELBOW, OFFSET, TRANSITION, AND

OTHER INCIDENTAL ITEMS THAT MAY BE NECESSARY FOR A COMPLETE SYSTEM. PROVIDE ALL DUCT, PIPE, FITTINGS, TRANSITIONS AND OTHER ITEMS NECESSARY TO PROVIDE A FUNCTIONING SYSTEM AS

CONVEYED BY THE DRAWINGS, WHETHER OR NOT SUCH ITEMS ARE SHOWN ON THE DRAWINGS.

E. PROVIDE SUBMITTALS ON ITEMS LISTED IN MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES TO

THE ENGINEER FOR REVIEW PRIOR TO ORDER, PURCHASE OR INSTALLATION.

F. AT PROJECT CLOSE-OUT, PROVIDE AS-BUILT DRAWINGS AND OPERATION & MAINTENANCE MANUALS IN

PDF FORMAT. SUBMIT TO ENGINEER.

G. ALL EQUIPMENT, DUCTWORK, AND PIPING SHALL BE SEISMICALLY RESTRAINED IN ACCORDANCE WITH APPLICABLE CODE. USE IMPORTANCE FACTOR OF 1.5 FOR NATURAL GAS AND FIRE PROTECTION

PIPING, AND IMPORTANCE FACTOR 1.0 FOR ALL OTHER EQUIPMENT AND UTILITIES, UNLESS

OTHERWISE NOTED. ALL DETAILS AND DRAWINGS REQUIRED BY LOCAL AUTHORITY ARE TO BE

PRODUCED BY A LICENSED ENGINEER HIRED BY THE CONTRACTOR. SUBMIT COPY OF STAMPED AND

SIGNED SHOP DRAWINGS AND CALCULATIONS TO ENGINEER.

H. PRESSURE TEST ALL NATURAL GAS, COMPRESSED AIR, AND WATER PIPING AT 150% OF OPERATING

PRESSURE FOR 4 HOURS.

0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"

UNDER FLOOR MECHANICAL REMODEL PLAN

CONSTRUCTION DOCUMENTSO

CH-1 PAC-1

AS-1

8ø SA

10ø SA

FC-5

T

1 2 3 4 5 6 7 8

A

B

C

D

MH401

MH402

MH402

MH401

(MEZZANINE ABOVE) (MEZZANINE ABOVE)

3" CHR

3" CHS

REFRIGERANT LINESET (E)

SEE SHEET MH101

FOR CONTINUATION

3/4" CHR

3/4" CHS

CV-5A

T

FC-5

N/A

10/12 SA

145-

8ø SA

8ø SA T

FC-2

C

T

FC-1

C

N/A

16/14 SA

14/10 RA

T

FC-4

T

FC-3

C T

AH-1

C

3" CHS

3" CHR

YH-1 5

3/4" D

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:4

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

MECHANICAL REMODEL PLAN

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MH101MH101

KEYED NOTES

1 SEE 4/MH401 FOR CONTINUATION.

2 RELOCATED THERMOSTAT.

3 NEW THERMOSTAT.

4 REINSTALL CONDENSING UNIT IN A LOCATION THAT PROVIDES ADEQUATE CLEARANCE FOR THE NEW

CHILLER. RECONNECT POWER, CONTROLS, AND REFRIGERANT LINESET.

5 PROVIDE 3 CUBIC FEET OF GRAVEL AROUND DRAIN HOLE OF YARD HYDRANT.

GENERAL NOTES

A. PROVIDE A COMPLETE OPERATING SYSTEM UPON COMPLETION OF THIS PROJECT.

B. INSTALL ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE CURRENTLY ADOPTED EDITIONS OF

THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL FIRE CODE

AND INTERNATIONAL PLUMBING CODE.

C. INSTALL ALL EQUIPMENT ACCORDING TO MANUFACTURER’S INSTRUCTIONS.

D. PLANS ARE DIAGRAMATIC IN NATURE AND DO NOT SHOW EVERY ELBOW, OFFSET, TRANSITION, AND

OTHER INCIDENTAL ITEMS THAT MAY BE NECESSARY FOR A COMPLETE SYSTEM. PROVIDE ALL DUCT, PIPE, FITTINGS, TRANSITIONS AND OTHER ITEMS NECESSARY TO PROVIDE A FUNCTIONING SYSTEM AS

CONVEYED BY THE DRAWINGS, WHETHER OR NOT SUCH ITEMS ARE SHOWN ON THE DRAWINGS.

E. PROVIDE SUBMITTALS ON ITEMS LISTED IN MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES TO

THE ENGINEER FOR REVIEW PRIOR TO ORDER, PURCHASE OR INSTALLATION.

F. AT PROJECT CLOSE-OUT, PROVIDE AS-BUILT DRAWINGS AND OPERATION & MAINTENANCE MANUALS IN

PDF FORMAT. SUBMIT TO ENGINEER.

G. ALL EQUIPMENT, DUCTWORK, AND PIPING SHALL BE SEISMICALLY RESTRAINED IN ACCORDANCE WITH APPLICABLE CODE. USE IMPORTANCE FACTOR OF 1.5 FOR NATURAL GAS AND FIRE PROTECTION

PIPING, AND IMPORTANCE FACTOR 1.0 FOR ALL OTHER EQUIPMENT AND UTILITIES, UNLESS

OTHERWISE NOTED. ALL DETAILS AND DRAWINGS REQUIRED BY LOCAL AUTHORITY ARE TO BE

PRODUCED BY A LICENSED ENGINEER HIRED BY THE CONTRACTOR. SUBMIT COPY OF STAMPED AND

SIGNED SHOP DRAWINGS AND CALCULATIONS TO ENGINEER.

H. PRESSURE TEST ALL NATURAL GAS, COMPRESSED AIR, AND WATER PIPING AT 150% OF OPERATING

PRESSURE FOR 4 HOURS.

0' 4' 8' 16'6'SCALE: 1/8" = 1'-0"

MECHANICAL REMODEL PLAN

CONSTRUCTION DOCUMENTSO

FC-1

C

D

C

D

B

8ø SA

/1

SA

FC-2

FC-3

FC-4

B

16/14 SA

MH501

14/10 RA

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:4

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

ENLARGED MECHANICAL

PLANS

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MH401MH401

KEYED NOTES

1 SEE SHEET MH101 FOR CONTINUATION.

GENERAL NOTES

A. ENLARGED MECHANICAL GENERAL NOTES.

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM MECHANICAL REMODEL

PLAN

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM MECHANICAL DEMO

PLAN

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MEZZANINE MECHANICAL DEMO PLAN

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MEZZANINE MECHANICAL REMODEL PLAN

CONSTRUCTION DOCUMENTSO

C

D

C

D

3" CHS

3" CHR 3" CHS DN

3" CHR DN

FC-1

3/ 4"

C

HR

3/ 4"

C

HS

GLYCOL (E)

SC(E)

PRV(E)

3/4" DCW DN

2" (E) WATER SERVICE DN

CV-1A

CV-1B

1/

4" C

HR

1/

4" C

HS

3/ 4"

D

3/4" GLYCOL FEED

P

B

FC-4

FC-3

FC-2

B

3" C

HS

3"

C

HR

CV-3A

CV-2A

CV-4A

CV-4B

CV-2B

CV-3B

2" CHR

2" CHS

1 1/2" CHS

1 1/2" CHR

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:4

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

ENLARGED MECHANICAL

PLANS

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MH402MH402

KEYED NOTES

1 DEMOLISH EXISTING REFRIGERANT LINESET.

2 CONNECT CONDENSATE DRAIN TO TAIL PIECE OF LAVATORY.

3 CONNECT TO EXISTING CONDENSATE DRAIN PIPE

4 PROVIDE PRESSURE SENSOR AND SOLENOID VALVE ON CHILLED WATER GLYCOL LINE. IF PRESSURE DROPS BELOW 20 PSI, OPEN SOLENOID VALVE AND START GLYCOL FEED PUMP UNTIL PRESSURE IS

ABOVE 25 PSI.

5 CONNECT TO EXISTING GLYCOL FEED PUMP PIPING. INTERLOCK NEW PRESSURE SENSOR AND

SOLENOID VALVE TO OPERATE GLYCOL FEED PUMP WHEN PRESSURE IN CHILLED WATER SYSTEM IS

LOW (IN ADDITION TO CURRENT HEATING WATER FEED PRESSURE SENSOR AND SOLENOID).

GENERAL NOTES

A. ENLARGED MECHANICAL GENERAL NOTES.

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM MECHANICAL PIPING

DEMO PLAN

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM MECHANICAL PIPING

REMODEL PLAN

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MEZZANINE MECHANICAL PIPING DEMO PLAN

0' 2' 4' 8'3'SCALE: 1/4" = 1'-0"

ENLARGED MEZZANINE MECHANICAL PIPING REMODEL

PLAN

CONSTRUCTION DOCUMENTSO

SET

10/17/2025

P

SET RELIEF VALVE PRESSURE FOR 75 PSI. PIPE DISCHARGE TO GLYCOL FEED TANK..

1/2" BALL VALVE MANUAL AIR VENT

UNION OR FLANGE, TYP.

STRAINER

SHUTOFF VALVE, TYP.

1/2" BALL VALVE DRAIN

PRESSURE AND

TEMPERATURE TEST PORT, TYP.

CALIBRATED BALANCE VALVE

(NOT REQUIRED FOR PRESSURE

INDEPENDENT CONTROL VALVES)

M

CHILLER

ANCHOR CHILLER TO EXISTING

PAD PER SEISMIC ANCHOR

DEFERRED SUBMITTAL

2" VALVES (FOR

INITIAL PIPE CLEANING

AND FLUSH)

THERMOMETER (TYP.)

BALANCE VALVE

GROOVED PIPE CONNECTION

BUTTERFLY VALVE (TYP.)

STRAINER (20 MESH)

PRESSURE GAUGE (TYP.)

FLEXIBLE

CONNECTION (TYP.)

CH-1

VFD

VFD

T

T

CHILLED WATER RETURN

TEMPERATURE: AI

CHILLED WATER SUPPLY

TEMPERATURE: AI

BACNET

POINTS TO MAP THROUGH BACNET INTERFACE:

PUMP SPEED, PUMP STATUS, ENTERING WATER

TEMPERATURE, LEAVING WATER TEMPERATURE,

CHILLER % COMMAND, CHILLER STATUS, CHILLER

COMMAND

SEQUENCE OF OPERATIONS

A. OPERATE CHILLER WHEN THERE IS A CALL FOR COOLING (AT LEAST ONE CHILLED

WATER VALVE WITH A COMMAND OF OVER 10% FOR 10 MINUTES (ADJ.). CHILLER WILL

START PUMPS AND MODULATE CHILLER CAPACITY TO MEET CHWS SETPOINT.

B. BUILDING AUTOMATION SYSTEM WILL PROVIDE A CHWS SETPOINT TO CHILLER. CHWS

WILL BE RESET USING TRIM AND RESPOND LOGIC SO THAT MAXIMUM CHILLED WATER

VALVE COMMAND IS 95% (ADJ.)

C. GENERATE AN ALARM ON BUILDING AUTOMATION SYSTEM IF THERE ARE ANY CHILLER

ALARMS. FAN COIL

M

M

CV-#B: HEATING VALVE COMMAND: AO

CV-#A: CHILLED VALVE COMMAND: AO

T

SUPPLY AIR

TEMPERATURE : AI

T

MT M

OUTSIDE AIR TEMPERATURE : AI

OUTSIDE AIR DAMPER : AI

RETURN AIR DAMPER : AI

RETURN AIR TEMPERATURE : AI

SEQUENCE OF OPERATIONS

A. OPERATE FAN COIL FAN CONTINUOUSLY DURING OCCUPIED HOURS. OPERATE FAN COIL WHEN REQUIRED TO MEET THE UNOCCUPIED TEMPERATURE SETPOINTS. PROVIDE OPTIMIZED START IN THE MORNING HOURS TO ACHIEVE OCCUPIED SETPOINT BY THE TIME THE BUILDING IS SCHEDULED TO BE OCCUPIED.

B. CONTROL OUTSIDE AIR DAMPER MINIMUM POSITION TO MAINTAIN CO2 BELOW 800 PPM. USE ECONOMIZER MODE FOR CONTROL OF OUTSIDE AIR DAMPERS AND RETURN AIR DAMPERS WHEN COOLING IS NEEDED

AND OUTSIDE AIR TEMPERATURE IS LESS THAN RETURN AIR TEMPERATURE.

C. MODULATE CHILLED WATER CONTROL VALVE AND HEATING WATER CONTROL VALVE TO MAINTAIN SPACE

TEMPERATURE AT SETPOINT.

D. WHEN SPACE TEMPERATURE FALLS MORE THAN 3F BELOW UNOCCUPIED SETPOINT DURING ONOCCUPIED HOURS (HEATING MODE) OR RISES MORE THAN 3F ABOVE UNOCCUPIED SETPOINT DURING UNOCCUPIED HOURS (COOLING MODE), START FAN COIL IN UNOCCUPIED MODE. OPERATE FAN COIL UNTIL SPACE TEMPERATURE IS 3F MORE THAN SETPOINT (HEATING) OR 3F LESS THAN SETPOINT (COOLING) AND THEN

SHUT DOWN FAN COIL.

E. GENERATE AN ALARM ON THE BAS WHEN:

FAN COIL STATUS DOES NOT MATCH COMMAND,

SPACE TEMPERATURE HAS BEEN ABOVE 80F FOR MORE THAN 15 MINUTES (OCCUPIED HOURS)

SPACE TEMPERATURE HAS BEEN BELOW 65F FOR MORE THAN 15 MINUTES (OCCUPIED HOURS)

T SPACE TEMPERATURE: AI

C CARBON DIOXIDE SENSOR: AI

UNOCCUPIED

HEATING

OCCUPIED

COOLING

SPACE TEMPERATURE SETPOINT

FC-3

FC-2

10/16 SA (E)

16/28 OA (E)

16/24 SA (E)

14/10 RA

16/14 SA

M

22/18 RA (E) THROUGH WALL

12/14 OA

M M

(DAMPER ON OTHER SIDE OF WALL)

MEZZANINE FLOOR

16/24 OA

SUPPORT FAN COIL FROM

STRUCTURE OVERHEAD WITH

THREADED ROD AND METAL CHANNEL

THROUGH WALL

THROUGH WALL

F

T

T

10 PUMP (P-6 & 7)

STRAINER

BUTTERFLY VALVE

VFD

VALVE FOR PRESSURE POINT

EXPANSION TANK (ET-1)

FLOW SWITCH

EVAPORATOR

AUTOMATIC AIR VENT

MANUAL AIR BLEED

DRAIN VALVE

BUFFER TANK (BT-1)

TEMPERATURE SENSOR

LEGEND

1/2" BALL VALVE MANUAL AIR VENT

UNION OR FLANGE, TYP.

STRAINER

SHUTOFF VALVE, TYP.

1/2" BALL VALVE DRAIN

M

PRESSURE AND

TEMPERATURE TEST PORT, TYP.

3-WAY CONTROL VALVE

CALIBRATED BALANCE VALVE

FC-5

M

CV-5A: CHILLED WATER VALVE

COMMAND: AO

SEQUENCE OF OPERATIONS

A. START FAN COIL WHEN COOLING IS NEEDED. MODULATE CHILLED WATER VALVE TO

MEET SPACE TEMPERATURE SETPOINT. STOP FAN COIL WHEN SPACE TEMPERATURE

SETPOINT IS SATISFIED.

B. MODULATE PERIMETER RADIANT HEATER CONTROL VALVE WHEN HEATING IS

NEEDED

T SPACE TEMPERATURE: AI

M

CV-6A: PERIMETER RADIANT

HEATER VALVE COMMAND: AO

SEQUENCE OF OPERATIONS

A. MODULATE PERIMETER RADIANT HEATER CONTROL VALVE WHEN HEATING IS

NEEDED

M

CV-6#: PERIMETER RADIANT

HEATER VALVE COMMAND: AO

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:5

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

MECHANICAL DETAILS

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MH501MH501

SCALE: NONE

COIL PIPING DETAIL - HEATING COIL

SCALE: NONE

CHILLER CONNECTION DETAIL

SCALE: NONE

CHILLER CONTROL SCHEMATIC

SCALE: NONE

FC-1, 2, 3, & 4 CONTROL SCHEMATIC

SCALE: NONE

FC-2/FC-3 SECTION VIEW

SCALE: NONE

CHILLER PUMP PACKAGE PIPING DETAIL

SCALE: NONE

COIL PIPING DETAIL - COOLING COIL

SCALE: NONE

FC-5 CONTROL SCHEMATIC

SCALE: NONE

PERIMETER HEATING CONTROL SCHEMATIC

CONSTRUCTION DOCUMENTSO

SE

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600 801.521.791

P F www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

REVREV

:1

:5

P M

R

A u to d e s k S tu ff

R e v it

L o c a l M o d e ls

-0

D ra p e r

L ib ra ry

M E C

H V m o d e le rB X

P D

.r v t

10/17/2025

25-017

MECHANICAL SCHEDULES

DRAPER CITY

LIBRARY

1136 PIONEER RD

DRAPER, UT 84020

SCHEMATIC DESIGN REVIEW

SET

MH601MH601

2. POWERED THROUGH CHILLER SINGLE POINT ELECTRICAL CONNECTION

1. PROVIDE WITH VARIABLE FREQUENCY DRIVE

P-7 CHILLED WATER 35 80 40% PROPYLENE GLYCOL 3500 1.9 5 208/3 ARMSTRONG 4392 2X2X6 INCLUDED AS A PUMP PACKAGE ON THE CHILLER

P-6 CHILLED WATER 35 80 40% PROPYLENE GLYCOL 3500 1.9 5 208/3 ARMSTRONG 4392 2X2X6 INCLUDED AS A PUMP PACKAGE ON THE CHILLER

BHP HP VOLT/PH

PLAN

CODE

SYSTEM

SERVED

FLOW

(GPM)

HEAD PRESSURE

(FT. W.G.)

FLUID RPM

ELECTRICAL

MANUFACTURER & MODEL NOTES

PUMP (P)

AS-1 35 5 6.3/25.3 SPIROTHERM VDT200

PLAN

CODE

FLOW

(GPM)

PRESSURE DROP

(FT. W.G.)

DIAMETER/HEIGHT

(IN)

MANUFACTURER & MODEL

AIR & DIRT SEPARATOR (ADS)

5 PERFORATED CEILING GRID / LAY-IN 22X22 24 X 24 940 0.05 NA <15 TITUS 8R

4 PERFORATED CEILING GRID / LAY-IN 22X10 24 X 12 400 0.05 NA <15 TITUS 8R

3 PLAQUE FACE CEILING GRID / LAY-IN 12 24 X 24 600 0.13 16 21 TITUS OMNI

2 PLAQUE FACE CEILING GRID / LAY-IN 10 24 X 24 435 0.11 14 20 TITUS OMNI

1 PLAQUE FACE CEILING GRID / LAY-IN 8 24 X 24 315 0.09 12 21 TITUS OMNI

PLAN

CODE

TYPE CEILING / MOUNTING

NECK SIZE

(IN)

FACE SIZE

(IN)

AIFLOW

(CFM)

PRESSURE DROP

(IN. W.G.)

THROW

(FT.)

NOISE

(NC)

MANUFACTURER & MODEL NOTES

GRILLES, REGISTERS, DIFFUSERS SCHEDULE

FC-5 600 60 0.5 2.25 208/3 .5 3.9 0.5 76.8/59.1 57.7/52.3 40% PPG 44 53 2.7 7 MERV 8 28 36 10 TRANE FCCB060

FC-4 4000 470 0.6 2.51 208/3 3 14 0.5 83.7/62 63.5/55.2 40% PPG 44 51.5 23.0 10 0.16 62.5 112 30% PPG 180 140 5.7 2 MERV 8 41 58 26 TRANE BCHE120

FC-3 800 125 0.6 2.49 208/3 1 5.75 0.5 78.1/60.9 55.5/53 40% PPG 44 55.1 3.4 6 0.14 59.5 109.2 30% PPG 180 140 1.2 2 MERV 8 30 30 17 TRANE BCHE024

FC-2 2400 100 0.6 2.5 208/3 3 14 0.5 75.5/57.1 55.5/49.6 40% PPG 44 52.3 12.0 11 0.15 67.2 103 30% PPG 180 140 2.3 2 MERV 8 36 58 18 TRANE BCH072

FC-1 1700 180 0.6 2.35 208/3 1 5.75 0.37 76.8/57.3 55.5/49.3 40% PPG 44 52.9 8.5 4.5 0.13 62.9 104 30% PPG 180 128 2.6 2 MERV 8 36 46 18 TRANE BCHE054

AIR PRESSURE

DROP

(IN. W.G.)

ENTERING AIR

TEMPERATURE

(DB/WB)

LEAVING AIR

TEMPERATURE

(DB/WB)

FLUID

ENTERING FLUID

TEMPERATURE (F)

LEAVING FLUID

TEMPERATURE (F)

FLUID

FLOW (GPM)

WATR PRESSURE

DROP (FT. W.G.)

AIR PRESSURE

DROP (IN. W.G.)

ENTERING AIR

TEMPERATURE

(DB/WB)

LEAVING AIR

TEMPERATURE

(DB/WB)

FLUID

ENTERING FLUID

TEMPERATURE (F)

LEAVING FLUID

TEMPERATURE (F)

FLUID

FLOW (GPM)

WATER PRESSURE

DROP (FT. W.G.)

MAX

LENGTH (IN)

MAX

WIDTH (IN)

MAX

HEIGHT (IN)

PLAN

CODE

AIRFLOW

(CFM)

OUTSIDE

AIRFLOW (CFM)

EXTERNAL STATIC

PRESSURE (IN. W.G.)

TOTAL STATIC

PRESSURE (IN. W.G.)

VOLT/PH

FAN

MOTOR (HP)

MCA

COOLING HEATING

FILTER

PHYSICAL

MANUFACTURER & MODEL

FAN COIL (FC)

1. SINGLE POINT ELECTRICAL CONNECTION ON CHILLER ALSO POWERS PUMPS, VFD

CH-1 20 16.94 16.1 208/3 120 175 40% PROPYLENE GLYCOL 52 53 44 20 97 TRANE CGAM

PROVIDE WITH PUMP PACKAGE INCLUDING PUMPS (P-6/7), PUMP VFD, 140 GALLON BUFFER TANK, 5 GAL EXPANSION TANK, ASSOCIATED PIPING AND CONTROLS

PLAN

CODE

NOMINAL

CAPACITY

(TONS)

IPLV NPLV VOLT/PH MCA MOP LIQUID

FLUID

FLOWRATE

(GPM)

ENTERING WATER

TEMPERATURE (F)

LEAVING WATER

TEMPERATURE (F)

EVAPORATOR PRESSURE

DROP (FT. W.G.)

AMBIENT

TEMPERATURE (F)

SOUND PRESSURE

LEVEL (@ 30 FT.)

MANUFACTURER & MODEL NOTES

AIR COOLED CHILLER (CH)

CV-6I BASEBOARD RADIANT 1 2-WAY MODULATING 5 YES

CV-6H BASEBOARD RADIANT 1 2-WAY MODULATING 5 YES

CV-6G BASEBOARD RADIANT 0.85 2-WAY MODULATING 5 YES

CV-6F BASEBOARD RADIANT 3.5 2-WAY MODULATING 5 YES

CV-6E BASEBOARD RADIANT 1.5 2-WAY MODULATING 5 YES

CV-6D BASEBOARD RADIANT 1 2-WAY MODULATING 5 YES

CV-6C BASEBOARD RADIANT 1.75 2-WAY MODULATING 5 YES

CV-6B BASEBOARD RADIANT 1.5 2-WAY MODULATING 5 YES

CV-6A BASEBOARD RADIANT 0.85 2-WAY MODULATING 5 YES

CV-5A FC-5 COOLING 2.7 3-WAY MODULATING 5 NO

CV-4B FC-4 HEATING 5.7 2-WAY MODULATING 5 YES

CV-4A FC-4 COOLING 24.9 3-WAY MODULATING 5 NO

CV-3B FC-3 HEATING 1.2 2-WAY MODULATING 5 YES

CV-3A FC-3 COOLING 3.4 3-WAY MODULATING 5 NO

CV-2B FC-2 HEATING 2.3 2-WAY MODULATING 5 YES

CV-2A FC-2 COOLING 12 3-WAY MODULATING 5 NO

CV-1B FC-1 HEATING 2.6 2-WAY MODULATING 5 YES

CV-1A FC-1 COOLING 8.5 3-WAY MODULATING 5 NO

PLAN

CODE

DUTY

FLOW

(GPM)

TYPE

PRESSURE

DROP (PSI)

PRESSURE

INDEPENDENT?

CONTROL VALVE (CV)

BT-1 CHILLER 143 3" PROVIDED WITH CHILLER PUMP PACKAGE PROVIDE WITH AUTOMATIC AIR VENT

PLAN

CODE

SYSTEM SERVED VOLUME

CONNECTION

SIZE (IN.)

MANUFACTURER & MODEL ACCESSORIES

BUFFER TANK (BT)

ET-1 4.8 4.8 Y PROVIDED WITH CHILLER PUMP PACKAGE

PLAN

CODE

MINIMUM TANK

VOLUME (GAL)

MINIMUM ACCEPTANCE

VOLUME (GAL)

ASME RATED? MANUFACTURER & MODEL

EXPANSION TANK (ET)

YH-1

NON-FREEZE POST HYDRANT WITH GALVANIZED

CASING AND ADJUSTABLE FLOW WHEEL LOCK HANDLE.

3/4"

PROVIDE FOR 5' BURY DEPTH OF WATER SUPPLY LINE. PROVIDE WITH

VACUUM BREAKER

J.R. SMITH 5909

PLAN

CODE

DESCRIPTION COLD HOT WASTE VENT NOTES BASIS OF DESIGN

PLUMBING SPECIALTIES

CONSTRUCTION DOCUMENTSO

MECHANICAL EQUIPMENT

SCHEDULE

NAME OF

MECHANICAL

EQUIPMENT

F A

N C

O

IL

F A

N C

O

IL

F A

N C

O

IL

A

IR

C O

O L

E D

P U

M P

M O

T O

R

D

A T

A

EQUIPMENT NO. FC-1,3 FC-2,4 FC-5 CH-1 P-6,7

RATING/WATTS 1 HP 3 HP .5 HP 5 HP

VOLTAGE 208 208 208 208 208

PHASE 3 3 3 3 3

AMPS 5.75 14.00 3.00 120 17.50

WIRE SIZE 3#12 3#12 3#12 3#1/0 3#10

GROUND WIRE 1#12 1#12 1#12 1#6 1#10

CONDUIT SIZE 3/4" 3/4" 3/4" 1-1/2" 3/4"

FUSE DISC. SW. 30 30 30 200 30

TYPE RKI FUSES 10 20 6 150 20

BREAKER SIZE 20 20 20 175 30

CIRCUIT

NOTES 1 1 1 1 1

NOTES:

STARTER IS FURNISHED WITH THE UNIT. PROVIDE SITE DISCONNECT. COORDINATE

EXACT LOCATION WITH MECHANICAL CONTRACTOR TO ENSURE PROPER CLEARANCE.

*THE ELECTRICAL CONTRACTOR IS TO COORDINATE WITH THE MECHANICAL

CONTRACTOR FOR EXACT LOCATIONS AND PROVIDE FUSE/BREAKER SIZE FOR EACH

EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS.

DETAIL

NOT TO

SCALE

SCALE:

D1

TYPICAL ROUGH−IN DETAIL

NOTES:

IN ACCORDANCE W/ IBC 711.3.2, OUTLETS ON OPPOSITE SIDES OF

FIRE RATED WALLS OR PARTITIONS IN THE SAME STUD SPACE

MUST BE SEPARATED BY MIN. OF 24" HORIZONTAL DISTANCE.

1. TYP. FOR WOOD & METAL STUD ROUGH-IN.

2. PLASTER RINGS NOT SHOWN.

3. LOCATE ALL OUTLET BOXES IN

ACCORDANCE W/ ARCH. & MECH. DWGS.,

AND W/ ALL APPLICABLE SHOP DWGS.

TYPICAL DUPLEX

OUTLET BOX

TYPICAL SWITCH

OUTLET BOX

BAR

STRAPS

BAR

STRAPS

TYPICAL WALL

OUTLETS

PROVIDE CONDUIT SUPPORTS IN

ACCORDANCE W/ NEC SPACING

REQUIREMENTS FOR THE TYPE OF

RACEWAY REQUIRED

AS REQUIRED FOR TYPE OF

CONSTRUCTION

STEEL CITY NO.

7501 BOX SUPPORT

DETAIL

NOT TO

SCALE

SCALE:

A

B

NOTES:

1. THE CONTRACTOR MUST COORDI NATE EXACT LOCATI ON OF THE DI SCONNECT WI TH THE MECHANI CAL

CONTRACTOR TO ELI MINATE ANY OBSTACLE (PI PE,CONCRETE PAD ETC. ) I N FRONT OF THE DISCONNECT.

IF THERE ARE ANY OBSTACLES, PROVI DE UNI STRUT AND INSTALL THE DI SCONNECT NEXT TO

MECHANI CAL EQUI PMENT I N ORDER TO PROVI DE THE REQUI RED CLEARANCE.

2. PROVI DE MINI MUM CLEARANCE AS FOLLOWS:

SYSTEM VOLTAGE

A B

42"

36" 30"

30"

DISCONNECT

SWITCH

FLEXIBLE LIQUID

TIGHT METALLIC

CONDUIT

MECHANICAL

EQUIPMENT

TYPICAL

CLEARED

SPACE

TYPICAL DISCONNECT CLEARANCE REQUIREMENTS

D2

DETAIL

NOT TO

SCALE

SCALE:

NOTE:

TYPI CAL DETAILS SHOWI NG GENERAL FI RE

STOPPI NG PROCEDURE . ACTUAL PROCEDURE

DEPENDS UPON ANNULAR SP ACE BETWEEN

PI PE AND/ OR I NSULATI ON AND OPENING.

FOLLOW MANUFACTURER' S I NSTRUCTI ONS.

DAMMING MATERIAL

(BACKER ROD, FIBERGLASS

OR MINERAL WOOL)

3M FIRE BARRIER

CP 25WB CAULK

FIRE RATED CONCRETE

FLOOR SLAB

CONDUIT OR

INSULATED CABLES

TYPICAL FIRESTOP FOR CABLES/CONDUIT

THROUGH CONCRETE FLOORINGD3

DETAIL

NOT TO

SCALE

SCALE:

NOTE:

TYPI CAL DETAILS SHOWI NG GENERAL FI RE

STOPPI NG PROCEDURE . ACTUAL PROCEDURE

DEPENDS UPON ANNULAR SP ACE BETWEEN

PI PE AND/ OR I NSULATI ON AND OPENING.

FOLLOW MANUFACTURER' S I NSTRUCTI ONS.

CP 25WB CAULK ON

BOTH SIDES OF WALL

INSULATED CABLES OR CONDUIT

FIRE RATED CONCRETE/CONCRETE

BLOCK WALL

DAMMING MATERIAL

(BACKER ROD, FIBER−GLASS

OR MINERAL WOOL)

NON−METALLIC SLEEVE MAY

EXTEND A MAX 2" (51 mm)

BEYOND THE WALL SURFACE

TYPICAL FIRESTOP FOR CABLES/CONDUIT

THROUGH CONCRETE WALLSD4

DETAIL

NOT TO

SCALE

SCALE:

D5

NOTE:

TYPICAL DETAIL SHOWING GENERAL FIRE

STOPPING PROCEDURE. ACTUAL PROCEDURE

DEPENDS UPON ANNULAR SPACE BETWEEN

PIPE AND/OR INSULATION AND OPENING.

FOLLOW MANUFACTURER'S INSTRUCTIONS.

1/4" MINIMUM DIAMETER

BEAD OF 3M FIRE BARRIER CP

25 CAULK OR MP MOLDABLE

PUTTY

METALLIC

CONDUIT

1/4" MINIMUM DIAMETER

BEAD OF 3M FIRE BARRIER

CP 25 CAULK OR MP

MOLDABLE PUTTY

1 OR 2 HOUR FIRE RATED

GYPSUM WALL BOARD

WOOD OR STEEL STUD

FIRESTOP FOR METAL CONDUIT

THROUGH GYPSUM WALL BOARD

NL

E

T−X X

X

M

J

T

S

TTB

M

CCTV

FACP

ELECTRICAL SYMBOLS LIST

SYMBOL DESCRIPTION

LIGHTING SYMBOLS

LIGHT FIXTURE TO STAY ON AT NIGHT (NIGHT LIGHT). PROVIDE UNSWITCHED LIGHTING CIRCUIT.

LIGHT FIXTURE ON EMERGENCY POWER PROVIDE BATTERY AS REQUIRED

LIGHTING FIXTURE CALL OUT. NUMBER INDICATES A SUGGESTED QUANTITY- TO BE VERIFIED

REFERENCE NOTES CALL OUT

DUAL TECH CEILING MOUNTED OCCUPANCY SENSOR TO CONTROL LIGHTING IN THE ROOM

PHOTOCELL

POWER SYMBOLS

DUPLEX CONVENIENCE OUTLET - 20 AMP

DUPLEX CONVENIENCE OUTLET - 20 AMP, GFCI PROTECTED.

JUNCTION BOX - SIZE AND FUNCTION AS REQUIRED

EACH ARROW INDICATES A HOME RUN. RUN GROUND CONDUCTOR REGARDLESS OF CONDUIT TYPE.

NUMBER OF CONDUCTORS AS REQUIRED

FUSED DISCONNECT SWITCH - SIZE AS REQUIRED-STANDARD HEIGHT TO BE 66" AFF TO THE TOP

FLUSH TELEPHONE, DATA OUTLET

FLUSH TELEPHONE OUTLET

FLUSH DATA OUTLET

MOTOR LOCATION

MECHANICAL EQUIPMENT CALL OUT

MANUAL DISCONNECT WITH THERMAL OVERLOAD PROTECTION

ELECTRICAL PANEL LOCATION

TELEPHONE TERMINAL BOARD

ELECTRICAL METER LOCATION

SPECIAL SYSTEMS SYMBOLS

CLOSED CIRCUIT TELEVISION CAMERA

FIRE ALARM CONTROL PANEL (FLUSH MOUNTED)

GENERAL NOTE SYMBOLS

WP INDICATES WEATHER PROOF EQUIPMENT

PC

XX−1

DETAIL

NOT TO

SCALE

SCALE:

CIRCUIT LENGTH (REFER TO THE CHART ABOVE

FOR WIRE SIZE, PROPERLY UPSIZE THE

GROUND CONDUCTOR AND CONDUIT SIZE)

#12

LAST EQUIPMENT

#10

#8

#6

#4

#3

#2

#1

#1/0

#4/0

60 FT

110 FT

170 FT

260 FT

410 FT

500 FT

640 FT

790 FT

910 FT

1600 FT

70 FT

110 FT

170 FT

270 FT

330 FT

430 FT

530 FT

600 FT

1060 FT

70 FT

100 FT

160 FT

200 FT

260 FT

320 FT

360 FT

640 FT

90 FT

130 FT

160 FT

210 FT

260 FT

300 FT

530 FT

110 FT

140 FT

180 FT

220 FT

260 FT

460 FT

#2/0 1080 FT 720 FT 430 FT 360 FT 310 FT

#3/0 1330 FT 890 FT 540 FT 450 FT 380 FT

110 FT

190 FT

290 FT

460 FT

710 FT

870 FT

1120 FT

1370 FT

130 FT

190 FT

300 FT

470 FT

580 FT

740 FT

920 FT

110 FT

180 FT

280 FT

350 FT

450 FT

550 FT

150 FT

230 FT

290 FT

370 FT

460 FT

200 FT

250 FT

320 FT

390 FT

450 FT

620 FT 530 FT

520 FT630 FT

1250 FT 750 FT

1050 FT

1880 FT

1570 FT

150 FT

260 FT

390 FT

610 FT

950 FT

1160 FT

170 FT

260 FT

410 FT

630 FT

770 FT

990 FT

1220 FT

150 FT

240 FT

380 FT

460 FT

590 FT

730 FT

200 FT

310 FT

380 FT

490 FT

610 FT

270 FT

330 FT

420 FT

520 FT

1490 FT

1830 FT

270 FT

450 FT

680 FT

1070 FT

2010 FT

300 FT

450 FT

710 FT

1340 FT

270 FT

420 FT

800 FT

350 FT

670 FT 570 FT

1640 FT 1090 FT 650 FT 540 FT 470 FT

LAST LIGHT FIXTURE

LAST OUTLET

NOTES:

1. UPSIZE WIRES AS NECESSARY TO MEET MAXIMUM

VOLTAGE DROP REQUIREMENTS TO THE END

DEVICE/EQUIPMENT AS REQUIRED BY NEC (3% DROP

TO PANEL + 2% DROP TO LAST DEVICE/EQUIPMENT)

2. FOR DISTANCES LONGER THAN SHOWN, UPSIZE

WIRES AS REQUIRED BY NEC TO COMPLY WITH THE

VOLTAGE DROP REQUIREMENTS.

3. UTILIZE THE SAME LOGIC TO UPSIZE CONDUCTORS

FOR BREAKER SIZES NOT SHOWN IN THE CHART.

COORDINATE WITH THE ENGINEER AS NECESSARY.

BRANCH PANEL

BREAKER SIZE

D8

TYPICAL BRANCH CIRCUIT CONDUCTOR SIZE DETAIL

(BASED ON DISTANCE AND VOLTAGE DROP)

WIRE

SIZE

COPPER

120 VOLT

A

M P

B R

E A

K E

R

DISTANCE

208 VOLT

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

277 VOLT 480 VOLT

A

M P

B R

E A

K E

R

DISTANCE

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

DISTANCE

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

DISTANCE

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

A

M P

B R

E A

K E

R

BREAKER SIZE

BREAKER SIZE

DETAIL

NOT TO

SCALE

SCALE:

36" FOR 208 V

48" FOR 480 V

D9

REQUIRED INDOOR INSTALLATION

SPACES FOR ELECTRICAL EQUIPMENT

WIDTH OF EQUIPMENT (MINIMUM 30")

HEIGHT OF

EQUIPMENT

(6’ MINIMUM)

6’ OR CEILING

HEIGHT

EXHAUST DUCT

DEDICATED ELECTRICAL SPACE

SPRINKLER ALLOWED

6 1/2 FT

WORKING SPACE

NOTES:

1. THE WIDTH OF THE WORKING SPACE SHALL BE AT LEAST 30" OR THE WIDTH OF THE

PANEL BOARD, WHICHEVER IS GREATER.

2. WORKING SPACE HEAD ROOM SHALL BE A MINIMUM OF 6.5'.

3. THE MAXIMUM HEIGHT OF CIRCUIT BREAKERS/DISCONNECT SWITCH HANDLE SHALL

NOT BE MORE THAN 6'6".

DETAIL

NOT TO

SCALE

SCALE:

RECESSED TROFFER

FIXTURE CLAMP − PROVIDE

ONE PER SIDE OF EACH

FIXTURE

LAY−IN GRID SYSTEM

WIRE HANGER AT EACH CORNER

OF FIXTURE (TYP) INDEPENDENT

OF CEILING SUPPORT SYSTEM

TYPICAL RECESSED FIXTURE MOUNTING DETAIL

D10

DETAIL

NOT TO

SCALE

SCALE:

D38

TYPICAL CONDUIT RACK SUPPORT DETAIL

CONDUIT CLAMP - 3/4" TO 1"

UNISTRUT 2 PIECE CHANNEL

PIPE STRAPS - 1 1/4" TO 6"

BEAM CLAMP, HANGER CLAMP,

OR APPROVED SUPPORT, AS

REQUIRED BY WEIGHT

SUPPORTED

UNISTRUT CHANNEL -

SIZE AS REQUIRED BY

WEIGHT SUPPORTED

RACEWAY 3/4" TO 6" (TYP.)

ALL THREAD ROD

SIZE AS REQUIRED

(MIN. 3/8")

DETAIL

NOT TO

SCALE

SCALE:

NOTES:

1. ALL CIRCUITS SHALL RUN IN CONDUIT (3/4" MINIMUM). MC CABLE IS ONLY ALLOWED IN

CONCEALED AREA FOR CONNECTION TO THE LIGHT FIXTURES (6 FEET MAX).

2. THIS DETAIL IS DIAGRAMMATIC IN NATURE AND IS NOT MEANT TO BE COMPREHENSIVE.

TYPICAL CONDUIT RUN DETAIL

D44

J

J

J

L

L

L

J

O

O

L

L

L

O

O

O

L

L

L

ELECTRICAL

PANEL

NOT ALLOWED

3/4" MIN. CONDUIT

MC CABLE NOT

ALLOWED

L

O

J

LIGHT FIXTURE

ELECTRICAL OUTLET

JUNCTION BOX

6 FEET MAX, MC

CABLE ALLOWED

IN CONCEALED

AREA

O

3/4" MINIMUM CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

3/4" MIN. CONDUIT

MC CABLE NOT ALLOWED

MC CABLE NOT ALLOWED

MC CABLE

NOT ALLOWED

MC CABLE

NOT ALLOWED

MC CABLE

NOT ALLOWED

6 FEET MAX, MC

CABLE ALLOWED

IN CONCEALED

AREA

6 FEET MAX, MC

CABLE ALLOWED

IN CONCEALED

AREA

1. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE (NEC) AND

ALL THE LOCAL CODES.

2. PROVIDE TAMPER-RESISTANCE RECEPTACLES IN THE AREAS WHERE KIDS ARE PRESENT, AND

AREAS REQUIRED BY NEC 406.12(3). INCLUDING DWELLING UNITS, GUEST ROOMS,

PRESCHOOL/ELEMENTARY/ CHILDCARE FACILITIES, WAITING ROOMS, ETC.

3. NOT MORE THAN THREE (3) CIRCUITS SHALL BE INSTALLED IN A 3/4" CONDUIT.

4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. DO NOT SHARE THE NEUTRAL

CONDUCTOR IN HOMERUNS. (NEC 210.4).

5. THE MINIMUM SIZE OF THE CONDUCTORS SHALL BE A NO. 12 AWG, THHN COPPER. UNLESS

INDICATED OTHERWISE ON THE DRAWINGS.

6. LIGHT FIXTURES, RACEWAYS AND OTHER ELECTRICAL DEVICES SHALL BE SUPPORTED FROM

THE STRUCTURE NOT FROM METAL OR WOOD CEILING DECK. UTILIZE UNISTRUTS IN BETWEEN

STRUCTURE AS NEEDED.

7. ALL J-BOXES SHALL BE RECESSED INTO THE FINISHED WALL/CEILING UNLESS THE FINISHED

WALL/CEILING IS CONCRETE AND IS NOT BEING FURRED OUT. ALL CONDUITS SHALL BE RUN

THROUGH THE STUDS BEHIND THE FINISHED WALL/CEILING. COORDINATE WITH

ENGINEER/ARCHITECT PRIOR TO ROUGH-IN FOR ANY EXPOSED CONDUITS/J-BOX THAT

CANNOT BE RUN INSIDE THE WALL/CEILING AND NEED TO BE SURFACE MOUNTED ON THE

FINISHED WALL/CEILING. SURFACE MOUNTED CONDUITS IN EXPOSED CEILING SHALL BE

INSTALLED CLOSE TO CEILING (AND NOT PENDANT MOUNTED BELOW THE

BEAMS/STRUCTURE).

8. PROVIDE GFCI PROTECTED OUTLETS FOR EVERY LOCATION SHOWN ON THE DRAWINGS. DO

NOT USE MULTIPLE LOCATION PROTECTION.

9. WHERE CIRCUIT CONDUCTORS ARE TO BE INCREASED IN SIZE TO MEET THE VOLTAGE DROP

REQUIREMENT, THE EQUIPMENT GROUNDING CONDUCTORS MUST BE INCREASED

ACCORDINGLY (NEC 250.122)

10. ALL J-BOXES SHALL HAVE A MINIMUM DEPTH OF 2-1/8" UNLESS OTHERWISE SPECIFIED.

SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD RINGS.

11. ALL THE HOMERUNS MUST BE ACCESSIBLE. DO NOT CARRY A HOMERUN FROM ONE DEVICE

TO ANOTHER WHICH IS TIED TO A SEPARATE HOMERUN INSIDE THE WALL. MARK ON ALL THE

J-BOXES THE CIRCUIT NAMES AND NUMBERS.

12. ALL J-BOXES IN FIRE RATED WALLS SHALL MEET THE FIRE RATING REQUIREMENT OF THE

WALL AND SHALL NOT BE INSTALLED LESS THAN 24" BACK-TO-BACK.

13. ALL DISCONNECTS SHALL BE OF A HEAVY-DUTY TYPE.

14. ALL DISCONNECTS, J-BOXES, AND CONDUITS EXPOSED TO THE OUTSIDE WEATHER AND

MECHANICAL ROOMS SHALL BE OF A NON-CORROSIVE, WEATHERPROOF TYPE.

15. ALL NEW EXPOSED CONDUITS MUST RUN AGAINST THE WALL OR CEILING. DO NOT PENDANT

MOUNT ANY CONDUIT FROM THE CEILING. EXPOSED CONDUITS ARE ONLY ALLOWED IN

EXPOSED CEILING AREA.

16. ALL MATERIALS USED IN INSTALLATION SHALL BE U.L. APPROVED AND NEW.

17. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (ROMEX NOT PERMITTED).

18. ALL EXTERIOR RECEPTACLES SHALL BE OF WEATHER-RESISTANT TYPE AS PER NEC 406.8.

19. NO CONDUITS SHALL RUN IN DUCT WORK.

20. CABLES OR RACEWAYS INSTALLED IN EXPOSED OR CONCEALED LOCATIONS UNDER METAL-

CORRUGATED SHEET ROOF DECKING SHALL BE INSTALLED AND SUPPORTED SO THAT THE

NEAREST OUTSIDE SURFACE OF THE CABLE OR RACEWAY IS NOT LESS THAN 38 MM (1 1/2 IN.)

FROM THE NEAREST SURFACE OF THE ROOF DECKING.

21. PROVIDE LATERAL AND LONGITUDINAL BRACING FOR ALL CONDUIT RACKS, CABLE TRAYS,

ETC., EXCEEDING 20 FEET IN LENGTH.

22. MINIMUM SIZE CONDUIT SHALL BE 3/4" FOR INTERIOR APPLICATION, AND 1" FOR CONDUIT

BURIED BELOW GRADE IN EXTERIOR APPLICATION.

23. LABELING IS REQUIRED FOR ALL PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL

CENTERS, MOTOR STARTERS, TRANSFORMERS, MAJOR JUNCTION BOXES, DISCONNECT

SWITCHES, BREAKERS, PUSH BUTTONS, ETC., INTERLOCKS AND RELAY PANELS.

24. USE RIGID STEEL, SET SCREW TYPE FITTINGS ONLY. DIE CAST FITTING SHALL NOT BE USED.

25. USE EPOXY ANCHORS TO SUPPORT THE ELECTRICAL EQUIPMENT. EXPANSION ANCHOR

BOLTS ARE NOT ACCEPTABLE.

26. AT THE END OF THE JOB, PROVIDE BLANK, MATCHING COVER PLATES FOR ALL J-BOXES

WHERE DEVICES HAVE NOT YET BEEN INSTALLED.

27. SEAL AROUND ALL CONDUIT PENETRATIONS THROUGH WALLS AND CEILINGS WITH A FIRE

RATED MATERIAL. 3M IS AN APPROVED MANUFACTURER.

28. PRIOR TO SUBMITTAL FOR A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND

INCLUDE IN THEIR BID PACKAGE ALL CHARGES RELATED TO EXISTING CONDITIONS AND

DEMOLITION WORK. PROVIDE SHOP DRAWINGS AS REQUIRED BY CONSTRUCTION

DOCUMENTS. ALL LABOR, MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A

PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT. REPLACE OR REPAIR

ALL DEFECTS DURING THE GUARANTEED PERIOD.

29. THE ELECTRICAL CONTRACTOR SHALL TERMINATE THE ELECTRICAL CONNECTIONS TO ALL

THE EQUIPMENT BY PROVIDING THE NECESSARY MALE/ FEMALE CONNECTOR, RECEPTACLE,

PLUG, ETC.

30. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE MECHANICAL

CONTRACTOR SO THAT NO PIPING, DUCTS, OR OTHER EQUIPMENT SHALL BE INSTALLED IN

THE ENTRY, PASS THROUGH ELECTRICAL ROOM OR SPACES ABOVE OR BELOW ELECTRICAL

PANELS.

31. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE,

CONNECTION REQUIREMENT, ETC.) OF EQUIPMENT FURNISHED UNDER OTHER DIVISIONS

WITH APPROVED SHOP DRAWINGS.

32. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER, IN WRITING, OF ANY

DISCREPANCIES FOUND BETWEEN THE INTENDED FUNCTION OF EQUIPMENT AND EQUIPMENT

SPECIFIED IN THE CONTRACT DOCUMENTS WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR

TO ISSUANCE OF THE FINAL ADDENDUM. FAILURE TO REPORT ANY DISCREPANCY (CATALOG

NUMBERS, DISCONTINUED ITEMS, ETC.) DOES NOT RELIEVE THE CONTRACTOR FROM

PROVIDING EQUIPMENT WHICH SHALL CONFORM TO AND FULFILL THE INTENT OF THE

CONTRACT DOCUMENTS. NOR SHALL IT BE USED AS A CONDITION TO OBTAIN ADDITIONAL

FUNDS FROM THE OWNER AFTER THE CONTRACT IS AWARDED. THE CONTRACTOR SHALL

REQUEST ALL CLARIFICATIONS OF CONTRACT DOCUMENT REQUIREMENTS, IN WRITING, TO

THE ARCHITECT/ ENGINEER WITH A MINIMUM OF FIVE (5) WORKING DAYS PRIOR TO ISSUANCE

OF THE FINAL ADDENDUM.

33. CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS

SPECIFICALLY NOTED OTHERWISE.

34. DETAILS ARE SHOWN ON DIFFERENT SHEETS. THE CONTRACTOR SHALL REFER TO THOSE

DETAILS WHETHER OR NOT CALLED IN REFERENCE NOTES.

35. PROVIDE MANUAL THERMAL SWITCHES WITH PILOT LIGHT.

36. PROVIDE A TYPED LABEL FOR ALL DUPLEX OUTLETS AND LIGHT SWITCHES TO INDICATE

WHICH CIRCUIT THEY ARE TIED TO.

37. CONTRACTOR MUST PAY FOR HIS OWN ELECTRICITY DURING CONSTRUCTION. COORDINATE

WITH THE LOCAL POWER COMPANY FOR SETTING UP TEMPORARY POWER.

38. THE OWNER MUST SCHEDULE INTERRUPTIONS OF SERVICE WHEN CONTRACTOR WISHES TO

MAKE UTILITY CONNECTIONS. NOTIFY, IN WRITING, THE OWNER'S REPRESENTATIVE 72 HOURS

PRIOR TO TIME WHEN INTERRUPTION IS DESIRED. INTERRUPTION MUST BE AT THE COUNTY'S

CONVENIENCE. OVERTIME, IF REQUIRED FOR THIS WORK, IS TO BE AT CONTRACTOR’S

EXPENSE.

39. UTILIZE INTERMEDIATE METAL CONDUIT (IMC) IN WET LOCATIONS OR AREAS SUBJECT TO

DAMAGE.

40. FLEXIBLE METAL CONDUIT: PROVIDE ZINC-COATED, FLEXIBLE METAL CONDUIT FOR

CONNECTIONS TO MOTORS, TRANSFORMERS, OR OTHER EQUIPMENT SUBJECT TO

MOVEMENT OR VIBRATION.

41. ALL CONDUCTORS SHALL BE IN CONDUIT (3/4" MINIMUM). MC CABLES IS NOT ALLOWED.

42. ALL UNDERGROUND CONDUITS SHALL BE BURIED 24 INCHES MINIMUM UNDER THE GROUND.

43. ALL METALLIC CONDUITS, JOINTS, FITTINGS, ETC. IN CONTACT WITH THE GROUND SHALL BE

SPIRAL WRAPPED WITH 3M SCOTCHRAP-51, 20 MIL TAPE (OR APPROVED EQUAL). 1/2" OVERLAP

IS REQUIRED.

44. ALL EMERGENCY PANELS AND EMERGENCY CIRCUIT BOXES SHALL BE LABELED IN RED.

45. PROVIDE TYPED PANEL INDEX FOR EXISTING ELECTRICAL PANELS AFFECTED BY THE SCOPE

OF THIS WORK. EXISTING/UNAFFECTED CIRCUITS IN THE PANEL SHALL BE ITALICIZED AND

CHANGED/ADDED CIRCUITS SHALL BE TYPED BOLD.

GENERAL NOTES:

334543-2202

MANSOUR

AGHDASI

NO.

375 WEST 200 SOUTH

SALT LAKE CITY, UT 84101

801.521.8600P www.gsbsarchitects.com

OWNER PROJECT NO.:

GSBS PROJECT NO.:

ISSUED DATE:

REVISIONS:

RE

V

REV

#1025

10/17/2025

2022.055.14

GENERAL NOTES &

DETAILS & SCHEDULES

SALT LAKE COUNTY

SLCO DRAPER

LIBRARY HVAC

REMODEL

1136 Pioneer Rd, Draper, UT 84020

CD Set

E-001

2. CIRCUIT NUMBERS ARE SCHEMATIC AND SHOW THE DESIGN INTENTION AND LOAD BALANCE REQUIREMENTS. CONTRACTORS SHALL VERIFY ALL EXISTING AVAILABLE CIRCUITS AND THOSE WHICH BECOME AVAILABLE AS A RESULT OF DEMOLITION. CONTRACTOR SHALL INDICATE ACTUAL CIRCUITS USED ON AS-BUILT DRAWINGS. THE CONTRACTOR IS TO INFORM GC/ENGINEER IF SUFFICIENT BREAKER SPACES DID NOT FREE UP, PRIOR TO ROUGH-IN.

1. PROVIDE NEW CIRCUIT BREAKERS AS NECESSARY.