NIEHS_Sprinkler_Inspection_Report_0001.pdf
PDF 9 MB Posted
- Solicitation number
- 75N99025R00029
About this file
This is a collection of fire protection system inspection reports for multiple NIEHS (National Institute of Environmental Health Sciences) buildings conducted on various dates in 2025. The reports cover kitchen auto extinguishing systems, sprinkler systems, and a clean agent suppression system across Buildings 101, 102-103, 104, 105, and 110 located at 111 TW Alexander Drive, Durham, NC 27709.
The inspections revealed several deficiencies requiring attention. Kitchen auto extinguishing systems in multiple buildings need 5-year internal and gauge testing as well as 3-year air testing. Building 103's dry sprinkler system failed due to overdue internal/gauge testing and air testing requirements. Building 105's sprinkler system is out of service due to ongoing project work. Building 110's pre-action system requires 3-year air leak testing. Building 104's pre-action system failed due to out-of-date air/water gauges needing replacement and overdue 3-year air testing. The clean agent suppression system in Building 104 passed all inspections with no deficiencies noted. Most other systems, including various control valves, tamper switches, water flow switches, and main drain tests, passed their quarterly or semi-annual inspections. The reports include detailed maintenance checklists, equipment specifications, pressure readings, and inspector certifications with completion dates ranging from February to May 2025.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
System Information
LOCATION DESCRIPTION BARCODE MANUFACTURER MODEL SERIAL NUMBER SERVICE TYPE SIZE
Front Hood — Ansul R-102 — Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes N/A N/A 3 N/A 3
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
48”x 10’ 1-10’ single bank baffle standard
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
N/A N/A N/A N/A
Cylinder Details
Kitchen Hood Cylinder
LOCATION DESCRIPTION BARCODE MANUFACTURER MODEL SERIAL NUMBER
Cylinder 1 — Ansul R-102 —
AGENT SIZE LAST HYDRO TANK PRESSURE CARTRIDGE WEIGHT PSI
Ansulex 3 gal 07/22/2016 N/A N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(1) Range Range 12”x 25” Electric Pass 1N 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(2) Griddle Griddle 36”x 20.5” Electric Pass 1N 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(3) Charbroiler Char Broiler 24”x 19.5” Electric Pass 1N 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(4) Fryer Fryer 14”x 21” Electric Pass 230 1
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Yes
Check cartridge weight (replace if needed)? Yes
Kitchen Auto Extinguishing Systems–Semi-Annual
Customer: NIEHS Building: NIEHS
Address: 111 TW Alexander Dr, Durham, NC 27709
Kitchen Auto Extinguishing Systems | 02/26/2025 Page 2 of 7
Maintenance Items Results
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2024
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? N/A
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Tamper seal(s) installed? Yes
Building fire alarm connected / activated? Pass
Actuation line vacuum test performed (every 6 months)? N/A
Distribution piping network last purged with dry air or nitrogen? No
Exhaust fan(s) operating? Yes
Make-up/return air fan(s) shut down? Yes
Air filters/spacers reinstalled? Yes
Personnel instructed in manual operation of system ? Yes
Class K extinguisher with placard present? Yes
Last regulator test date (every 12 years)? 02/26/2024
System returned to normal operation? Yes
Service and certification tag on system? Yes
Kitchen Auto Extinguishing Systems–Semi-Annual
Customer: NIEHS Building: NIEHS
Kitchen Auto Extinguishing Systems | 02/26/2025 Page 3 of 7
System Information
LOCATION DESCRIPTION BARCODE MANUFACTURER MODEL SERIAL NUMBER SERVICE TYPE SIZE
Rear Hood — Ansul R-102 — Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip N/A N/A N/A 5 N/A 5
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
53”x 9’ (4)-9’ single banks baffle standard
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
N/A N/A N/A N/A
Cylinder Details
Kitchen Hood Cylinder
LOCATION DESCRIPTION BARCODE MANUFACTURER MODEL SERIAL NUMBER
Cylinder 1 — Ansul R-102 —
AGENT SIZE LAST HYDRO TANK PRESSURE CARTRIDGE WEIGHT PSI
Ansulex 3 gal 07/21/2016 N/A N/A N/A
Kitchen Hood Tank Secondary
LOCATION DESCRIPTION BARCODE MANUFACTURER MODEL SERIAL NUMBER
Cylinder 2 — Ansul R-102 —
AGENT SIZE LAST HYDRO TANK PRESSURE CARTRIDGE WEIGHT PSI
Ansulex 3 gal 05/02/2024 N/A N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(1) Tilt Skillet Tilt Skillet 44”x 27” Electric Pass 3N 3
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(2) Fryer 1 Fryers with Drip
Board 19.5”x 23.5” Electric Pass 3N 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(3) Fryer 2 Fryers with Drip
Board 19.5”x 23.5” Electric Pass 3N 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
(4) Range Range 36”x 24” Electric Pass 245, 1N 2
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Kitchen Auto Extinguishing Systems–Semi-Annual
Customer: NIEHS Building: NIEHS
Kitchen Auto Extinguishing Systems | 02/26/2025 Page 4 of 7
Terms And Conditions
1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.
2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY
(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR
AFTER DECEMBER 31, 1999.
3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.
4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:
a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease
b. need for air monitoring, respiratory protection, or other medical risk
c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building
d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.
5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report
6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.
Kitchen Auto Extinguishing Systems–Semi-Annual
Customer: NIEHS Building: NIEHS
Kitchen Auto Extinguishing Systems | 02/26/2025 Page 6 of 7
DEVICE NOTE IMAGE APPENDICES
Kitchen Auto Extinguishing Systems–Semi-Annual
Customer: NIEHS Building: NIEHS
Kitchen Auto Extinguishing Systems | 02/26/2025 Page 7 of 7
CUSTOMER NAME: NIEHS
BUILDING NAME: NIEHS - Building 102 - 103 BUILDING ADDRESS: 111 TW Alexander Dr, Durham, NC 27709 INSPECTION TYPE: Sprinkler FREQUENCY: Quarterly
WORK ORDER: 58840210
INSPECTION START DATE: 05/28/2025
INSPECTION END DATE: 05/28/2025
INSPECTOR:
INSPECTOR LICENSE:
ACCOUNT NAME:
OFFICE ADDRESS:
OFFICE PHONE:
OFFICE LICENSE:
TIMEZONE: EDT
SPRINKLER INSPECTION REPORT
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
Dry System loading dock building 103
— Dry System — — — 05/28/2025
FUNCTIONAL
FAILURE
FAILURE REASON: 1) 5 year internal and gauge testing is due
2) 3 year air testing is due
General
To be Answered with the Owner
1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No
2. Have there been any changes or repairs to the fire protection systems since the last inspection? No
3. Are Special Ladders or Lifts Required to perform the 5 Year Internal Pipe Inspection? If So, please list Size and Type. (12 Foot Stepladder, 20 Foot Scissor Lift Etc…)
No
To be Answered by the Inspector
1. Inspection and Testing Performed in accordance with NFPA 25 Edition NFPA 25-2014
2. Number Of Water Gauges 4
3. Number Of Air Gauges 4
4. Are all Tanks, Fire Pumps, and Fire Department Connections Inspected and Tested Per NFPA 25? Yes
5. All Systems Restored To Normal Yes
Water Supplies
1. Type City
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 102 - 103
Sprinkler | 05/28/2025 Page 1 of 5
Devices
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Control Valve 1 1 0 0
Dry System 1 0 1 0
Fire Dept. Connection 1 1 0 0
High/Low Air Device 1 1 0 0
Tamper Switch 1 1 0 0
Water Flow Switch 1 1 0 0
DRY SYSTEMS
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Dry System loading dock building 103
Dry System — 05/28/2025 Failed
Make and Model Tyco
What Size Is This Dry Pipe Valve 3
Hydraulic Name Plate Present Yes
Valve Enclosure Secured Yes
Valve Enclosure Heater Operational Yes
Do dry valves appear to be protected from freezing? Yes
Valve Enclosures Temperature Greater Than 40 F Yes
Visually Inspect - Is Intermediate Chamber Free From Leakage Yes
Are the air pressure and priming water levels normal? Yes
Does the Air Supply operate satisfactorily? Yes
Visually Inspect - Is Exterior Of The Valve In Good Condition And Both Gauges Operable Yes
Visually Inspect - Are Trim Valves In Their Appropriate Open Or Closed Positions Yes
Valve Seat Leak Tight Yes
Trim Piping Leak Tight Yes
System Gauges Undamaged And Reading Within Limits Yes
Wet Gauge PSI 100
Dry Gauge PSI 38
Quantity of Auxiliary / Low Point drains drained during this inspection? 1
All Wet Pipe Protected From Freezing Yes
Date of Last Full Flow Dry Trip Test 09/24/2024
Reason for failure: (Functional Failure) 1) 5 year internal and gauge testing is due
2) 3 year air testing is due
FIRE DEPARTMENT CONNECTIONS
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 103 Fire Dept. Connection — 05/28/2025 Passed
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 102 - 103
Sprinkler | 05/28/2025 Page 2 of 5
1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.
2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY
(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR
AFTER DECEMBER 31, 1999.
3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.
4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:
a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease
b. need for air monitoring, respiratory protection, or other medical risk
c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building
d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.
5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report
6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 102 - 103
Sprinkler | 05/28/2025 Page 4 of 5
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 102 - 103
Sprinkler | 05/28/2025 Page 5 of 5
General
To be Answered with the Owner
1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No
2. Have there been any changes or repairs to the fire protection systems since the last inspection? No
3. Have you had an internal pipe inspection performed in the last 5 years? No
4. Are Special Ladders or Lifts Required to perform the 5 Year Internal Pipe Inspection? If So, please list Size and Type. (12 Foot Stepladder, 20 Foot Scissor Lift Etc…)
No
To be Answered by the Inspector
1. Inspection and Testing Performed in accordance with NFPA 25 Edition NFPA 25-2014
2. Number Of Water Gauges 2
3. Number Of Air Gauges 2
4. Are all Tanks, Fire Pumps, and Fire Department Connections Inspected and Tested Per NFPA 25? Yes
5. All Systems Restored To Normal Yes
Water Supplies
1. Type City
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 101
Sprinkler | 05/28/2025 Page 2 of 13
1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.
2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY
(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR
AFTER DECEMBER 31, 1999.
3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.
4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:
a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease
b. need for air monitoring, respiratory protection, or other medical risk
c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building
d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.
5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report
6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 101
Sprinkler | 05/28/2025 Page 12 of 13
Customer: NIEHS Building: NIEHS - Building 101
Sprinkler | 05/28/2025 Page 13 of 13
BUILDING NAME: NIEHS - Building 105 BUILDING ADDRESS: 111 TW Alexander Dr, Durham, NC 27709 INSPECTION TYPE: Sprinkler FREQUENCY: Quarterly
WORK ORDER: 58840200
INSPECTION START DATE: 05/28/2025
INSPECTION END DATE: 05/28/2025
INSPECTOR:
INSPECTOR LICENSE:
ACCOUNT NAME:
OFFICE ADDRESS:
OFFICE PHONE:
OFFICE LICENSE:
TIMEZONE: EDT
SPRINKLER INSPECTION REPORT
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
Building 105 dry
System
— Dry System — — — 05/28/2025
FUNCTIONAL
FAILURE
FAILURE REASON: 1) 5 year internal and gauge testing is due
2) 3 year air testing is due
3) System is out of service due to project
Building 105 dry
System
— Main Drain Test — — — 05/28/2025 VISUAL FAILURE —
FAILURE REASON: Water is Shut off to system due to project being performed.
General
To be Answered with the Owner
1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No
2. Have there been any changes or repairs to the fire protection systems since the last inspection?
System out of service
Yes
3. Are Special Ladders or Lifts Required to perform the 5 Year Internal Pipe Inspection? If So, please list Size and Type. (12 Foot Stepladder, 20 Foot Scissor Lift Etc…)
No
To be Answered by the Inspector
1. Inspection and Testing Performed in accordance with NFPA 25 Edition NFPA 25-2014
2. Number Of Water Gauges 2
3. Number Of Air Gauges 1
4. All Systems Restored To Normal Yes
Water Supplies
1. Type City
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 105
Sprinkler | 05/28/2025 Page 1 of 5
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Dry System 1 0 1 0
Main Drain Test 1 0 1 0
DRY SYSTEMS
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 105 dry System Dry System — 05/28/2025 Failed
Make and Model Tyco
What Size Is This Dry Pipe Valve 2.5
Hydraulic Name Plate Present Yes
Valve Enclosure Secured Yes
Valve Enclosure Heater Operational Yes
Do dry valves appear to be protected from freezing? Yes
Valve Enclosures Temperature Greater Than 40 F Yes
Visually Inspect - Is Intermediate Chamber Free From Leakage Yes
Are the air pressure and priming water levels normal? Yes
Does the Air Supply operate satisfactorily? Yes
Visually Inspect - Is Exterior Of The Valve In Good Condition And Both Gauges Operable Yes
Visually Inspect - Are Trim Valves In Their Appropriate Open Or Closed Positions Yes
Valve Seat Leak Tight Yes
Trim Piping Leak Tight Yes
System Gauges Undamaged And Reading Within Limits Yes
Dry Gauge PSI 35
Quantity of Auxiliary / Low Point drains drained during this inspection? 1
All Wet Pipe Protected From Freezing Yes
Trim Valves Sealed Yes
Reason for failure: (Functional Failure) 1) 5 year internal and gauge testing is due
2) 3 year air testing is due
3) System is out of service due to project
MAIN DRAIN TESTS
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 105 dry
System Main Drain Test — 05/28/2025 Failed
Test pipe located At fenced in riser enclosure
Size of test pipe 2”
Previous Main Drain Test Date 09/25/2024
Previous Main Drain Static Pressure 75
Previous Main Drain Residual Pressure 70
Main Drain PSI Comparable to previous? No
Main drain opened & free of obstruction discoloration? No
Reason for failure: (Visual Failure) Water is Shut off to system due to project being performed.
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 105
1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.
2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY
(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR
AFTER DECEMBER 31, 1999.
3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.
4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:
a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease
b. need for air monitoring, respiratory protection, or other medical risk
c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building
d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.
5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report
6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 105
Customer: NIEHS Building: NIEHS - Building 105
BUILDING NAME: NIEHS - Building 110 BUILDING ADDRESS: 111 TW Alexander Dr, Durham, NC 27709 INSPECTION TYPE: Sprinkler FREQUENCY: Quarterly
WORK ORDER: 58851550
INSPECTION START DATE: 05/28/2025
INSPECTION END DATE: 05/28/2025
INSPECTOR:
INSPECTOR LICENSE:
ACCOUNT NAME:
OFFICE ADDRESS:
OFFICE PHONE:
OFFICE LICENSE:
TIMEZONE: EDT
SPRINKLER INSPECTION REPORT
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
— Building 110 — Pre-Action System — — — 05/28/2025
FUNCTIONAL
FAILURE
FAILURE REASON: 1) 3 year air leak testing appears due.
General
To be Answered with the Owner
1. Have there been any changes in the occupancy classification, machinery or operations since the last inspection? No
2. Have there been any changes or repairs to the fire protection systems since the last inspection? No
3. Have you had an internal pipe inspection performed in the last 5 years? Yes
4. Date the internal pipe inspection was performed? 09/27/2023
5. Are Special Ladders or Lifts Required to perform the 5 Year Internal Pipe Inspection? If So, please list Size and Type. (12 Foot Stepladder, 20 Foot Scissor Lift Etc…)
No
To be Answered by the Inspector
1. Inspection and Testing Performed in accordance with NFPA 25 Edition NFPA 25-2014
2. Number Of Water Gauges 2
3. Number Of Air Gauges 1
4. All Systems Restored To Normal Yes
Water Supplies
1. Type City
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 110
Sprinkler | 05/28/2025 Page 1 of 6
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Control Valve 1 1 0 0
High/Low Air Device 1 1 0 0
Pre-Action System 1 0 1 0
Tamper Switch 1 1 0 0
Water Flow Switch 1 1 0 0
Main Drain Test 1 1 0 0
PRE ACTION SYSTEMS
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 110 Pre-Action System — 05/28/2025 Failed
Make and Model Reliable DDX
What Size Is This Pre-Action Valve 2.5
Hydraulic Name Plate Present? No
Is this Pre-Action System a Single or Double Interlock System Double Interlock
Valve Enclosure Secured Yes
Valve Enclosure Heater Operational Yes
Valve Enclosures Temperature Greater Than 40 F Yes
Pre-Action Equipment Protected From Freezing Yes
Visually Inspect - Is Exterior Of The Valve In Good Condition And Both Gauges Operable Yes
Visually Inspect - Are Trim Valves In Their Appropriate Open Or Closed Positions Yes
Valve Seat Leak Tight Yes
Trim Piping Leak Tight Yes
System Gauges Undamaged And Reading Within Limits Yes
Wet Gauge PSI 155
Dry Gauge PSI 40
Pre-Action Maintaining Test Air Yes
Are the air pressure and priming water levels normal? Yes
Test Low Air Pressure Alarm Yes
Date of Last Full Flow Pre-Action Trip Test 02/08/2024
Date of Check Valve Internal Inspection 09/27/2023
Date the internal pipe inspection was performed? 09/27/2023
Date of Gauges Replacement 09/27/2023
Date of Internal Inspection of PreAction Strainers, Filters, And Restriction Orifices. 09/27/2023
Reason for failure: (Functional Failure) 1) 3 year air leak testing appears due.
Sprinkler–Quarterly
Customer: NIEHS Building: NIEHS - Building 110
Sprinkler | 05/28/2025 Page 2 of 6
MAIN DRAIN TESTS
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 110 pre-action Main Drain Test — 05/28/2025 Passed
Test pipe located Building 110 riser room
Size of test pipe 2”
Previous Main Drain Test Date 03/05/2025
Previous Main Drain Static Pressure 150
Static supply pressure 150
Time to return to normal system pressure 2 sec
Static supply pressure after completion of test 160
Main Drain PSI Comparable to previous? Yes
Main drain opened & free of obstruction discoloration? Yes
CONTROL VALVES AGG
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 110 reaction Control Valve — 05/28/2025 Passed
Type and Size Butterfly
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Secured in a Locked Enclosure
Free from External Leaks? Yes
WATER FLOW SWITCHES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 110 preaction Water Flow Switch — 05/28/2025 Passed
Quarterly Visual Inspection - Is flow switch free of damage with its electrical connections secure? Yes
TAMPER SWITCHES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Building 110 reaction control valve Tamper Switch — 05/28/2025 Passed
Quarterly Visual Inspection - Is tamper switch free of damage with its electrical connections secure? Yes
SUPERVISORY POINTS
#…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .