B01 Attachment J02-a Crownpoint Med Gas Renovation ADDENDUM 1.pdf
PDF 583 KB Posted
- Attached to
- Crownpoint Medical Gas Upgrade Construction
- Solicitation number
- 75H70126R00028
About this file
This is Addendum Number One to the Crownpoint Medical Gas Upgrade Design contract (HSSI161201200003I) issued by the Department of Health and Human Services, Indian Health Service (IHS), Office of Environmental Health and Engineering, Navajo Area Office on October 4, 2018. The addendum modifies the original "Issued for Construction" documents dated August 8, 2018 and applies to all registered plan holders.
The addendum contains revisions to two drawing sheets. Sheet MG-1 requires the contractor to re-label all medical gas piping above the ceiling to comply with NFPA 99, with gas pipe labels spaced no further than 20 feet apart and placed on both sides of separation walls. Sheet MG-5 includes five new keyed notes (D through H) for the Mechanical Room Piping Plan and Bulk Oxygen Storage Plan. These additions require: providing four warning signs on the fence around the bulk tank reading "NO SMOKING, NO OPEN FLAMES, OXYGEN"; installing a sign on the emergency oxygen fill connection; installing a Unistrut P6000 bolted steel frame (or equal) to elevate gas bottles 4 inches above grade with black air-dry enamel coating; providing anchorage bolts to secure the bulk oxygen storage tank to the slab with contractor coordination with the bulk tank supplier; and providing numbered tags on all shut-off valves at the bulk tank for labeling in the owner-provided shut-down procedure. No revisions to previous addenda or changes to procurement and contracting requirements were made. The addendum includes one attached revised drawing (MG-5X) showing the bulk oxygen storage plan layout with all keyed note locations.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CROWNPOINT MED GAS RENOVATION PROJECT NO. HHSI16109024T
CROWNPOINT MED GAS RENOVATION - Addendum No. 1 - Page 1 of 2
ADDENDUM NUMBER ONE (1)
Date: October 04, 2018
Project: Crownpoint Medical Gas Upgrade Design Contract No. HSSI161201200003I Hwy Junction 57, Route 9 Crownpoint, NM 87313
Owner: Department of Health and Human Services Indian Health Service (IHS) Office of Environmental Health and Engineering Navajo Area Office Highway 264, St. Michaels, Arizona 86511
From: Rock Gap Engineering LLC 3737 Princeton NE Suite 100 Albuquerque, New Mexico 87107-4205
TEL: (505) 344-2366
FAX: (505) 213-0563
To: Prospective Bidders
This Addendum forms a part of the Contract Documents and modifies the original “Issued for Construction” Documents dated August 8, 2018 as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject the Bidder to disqualification.
This Addendum consists of (2) pages plus (1) attached Revised Drawing.
1. NOTICE TO BIDDERS:
1.1 This Addendum is issued to all registered plan holders pursuant to the instructions to bidders and Conditions of the contract.
2. REVISIONS TO PREVIOUS ADDENDA:
1.1 None.
3. CHANGES TO PROCUREMENT REQUIREMENTS AND CONTRACTING
REQUIREMENTS:
3.1 None.
CROWNPOINT MED GAS RENOVATION PROJECT NO. HHSI16109024T
CROWNPOINT MED GAS RENOVATION - Addendum No. 1 - Page 2 of 2
4. CHANGES TO DRAWINGS:
4.1 SHEET MG-1 General Notes and Medical Equipment Schedules
A. REVISE Medical Gas General Note ‘P’ as follows:
1. “CONTRACTOR SHALL RE-LABEL ALL MEDICAL GAS PIPING
ABOVE CEILING TO COMPLY WITH NFPA 99. GAS PIPE LABELS
SHALL BE SPACED NO FURTHER THAN 20 FEET, AND ON BOTH
SIDES OF SEPARATION WALLS.”
4.2 SHEET MG-5 MECHANICAL ROOM PIPING PLAN AND BULK OXYGEN
STORAGE PLAN
A. REVISE Drawing as noted on attached sheet.
1. Add keyed note D as follows:
a. PROVIDE SIGN ON FENCE AROUND BULK TANK, 4
PLACES. SIGN TO READ “NO SMOKING, NO OPEN
FLAMES, OXYGEN”
2. Add keyed note E as follows:
a. PROVIDE SIGN ON EMERGENCY OXYGEN FILL
CONNECTION. SIGN TO READ “EMERGENCY OXYGEN FILL
CONNECTION”
3. Add keyed note F as follows:
a. INSTALL UNISTRUT FRAME ON GROUND TO ELEVATE
GAS BOTTLES 4” A.F.G. FRAME TO BE BOLTED STEEL,
UNISTRUT P6000 OR EQUAL. COAT FRAME WITH AIR-DRY
ENAMEL COATING. COLOR TO BE BLACK OR AS
COORDINATED WITH OWNER. MODIFY PIPING FROM
TANK TO HEADER FOR TANK HEIGHT CHANGE.
4. Add keyed note G as follows:
a. PROVIDE ANCHORAGE BOLTS FOR BULK OXYGEN
STORAGE TANK TO SLAB. CONTRACTOR TO
COORDINATE WITH BULK TANK SUPPLIER FOR FIELD
MODIFICATIONS TO TANK BASE FOR ATTACHMENT OF
POST-INSTALLED ANCHORS IN SLAB.
5. Add keyed note H as follows:
a. PROVIDE TAGS ON ALL SHUT-OFF VALVES AT BULK
TANK. NUMBER EACH VALVE FOR LABELING IN OWNER
PROVIDED SHUT-DOWN PROCEDURE.
End of Addendum
C
C
D
D
F
E
D
G
D
H
F
KEYED NOTES
SCALE: N.T.S.
BULK OXYGEN STORAGE PLAN
NORTH
APPROVED
REV DATE DESCRIPTION
DEPARTMENT OF HEALTH AND HUMAN SERVICES
INDIAN HEALTH SERVICE
OFFICE OF ENVIRONMENTAL HEALTH AND ENGINEERING
ALBUQUERQUE AREA OFFICE
5300 Homestead Road NE Albuquerque, New Mexico 87110
0 08/10/18 100% MEDICAL GAS UPGRADE - DESIGN
1 10/4/18 AMENDMENT #01 - CHANGES TO DRAWINGS
A. EXISTING MEDICAL AIR COMPRESSOR SHALL BE REPLACED, REMOVE COMPLETE. REMOVE &
REPLACE ALARM SENSORS FOR UNIT. REMOVE DOMESTIC WATER LINES AT EXISTING UNIT
AND CAP AT MAINS. PROVIDE AND INSTALL NEW MEDICAL AIR COMPRESSOR PACKAGED UNIT
(MAC-1). UNIT SHALL BE SKID MOUNTED AND LOCATED ON EXISTING HOUSEKEEPING PAD.
INSTALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS AND DETAILS. PROVIDE AND
INSTALL OUTSIDE AIR CONNECTIONS TO UNIT ACCORDING TO SECTION 5 OF NFPA 99. FURNISH
NEW PIPING AND FITTINGS FOR UNIT CONNECTIONS TO EXISTING PIPING. PROVIDE SOURCE
VALVE, PRESSURE REGULATORS, SIGNAGE PER NFPA 99, AND DRAIN TO MEET ALL REQUIRED
CODE ITEMS. EXTEND LINE SIZE DRAINS TO FLOOR SINK LOCATED AT HOUSEKEEPING PAD.
CONNECT NEW ALARMS TO MASTER ALARM LOCATED ON SHEET MG-4. COORDINATE FINAL
EQUIPMENT LOCATION WITH MVP-1 TO MAINTAIN RECOMMENDED SERVICE CLEARANCES.
B. EXISTING MEDICAL VACUUM PUMP EQUIPMENT SHALL BE REPLACED, REMOVE COMPLETE.
REMOVE & REPLACE ALARM SENSORS FOR UNIT. PROVIDE AND INSTALL NEW MEDICAL
VACUUM PUMP PACKAGED UNIT (MVP-1). UNIT SHALL BE SKID MOUNTED AND LOCATED ON
EXISTING HOUSEKEEPING PAD. INSTALL EQUIPMENT PER MANUFACTURER'S
RECOMMENDATIONS AND DETAILS. PROVIDE AND INSTALL 1-1/2" EXHAUST PIPING AT BOTH
BRAIDED FLEX CONNECTORS ON UNIT, MANIFOLD BOTH LINES TO A SINGLE STACK, RUN
THROUGH ROOF, TURN DOWN AND SCREEN OPENING. GOOSENECK EXHAUST PIPE SHALL BE
LOCATED 10'-0" AWAY FROM ALL AIR INTAKES ON ROOF. SEAL ROOF PENETRATION WEATHER
TIGHT. FURNISH NEW 2" PIPING AND FITTINGS FOR CONNECTIONS TO EXISTING PIPE
CONNECTIONS. INSTALL NEW ALARM SENSORS, BY PASS VALVE ASSEMBLY PER NFPA 99, AND
SIGNAGE TO MEET ALL REQUIRED CODE ITEMS. CONNECT NEW ALARMS TO MASTER ALARM
LOCATED ON SHEET MG-4. COORDINATE FINAL EQUIPMENT LOCATION WITH MAC-1 TO
MAINTAIN RECOMMENDED SERVICE CLEARANCES.
C. EXISTING BULK OXYGEN STORAGE SHALL BE SERVICED BY CERTIFIED MEDICAL SYSTEMS
TECHNICIAN. INSTALL NFPA COMPLIANT FINAL LINE ASSEMBLY. INSTALL REQUIRED PRESSURE
SWITCH. INSTALL EMERGENCY OXYGEN SUPPLY CONNECTION (EOSC), FIELD VERIFY
LOCATION AT TANK. INSTALL SOURCE VALVE TAG. INSTALL "IN USE" SWITCH AND RESERVE
LOW PRESSURE SWITCHES. CONNECT TO MASTER ALARM PANEL LOCATED ON SHEET MG-4.
D. PROVIDE SIGN ON FENCE AROUND BULK TANK, 4 PLACES. SIGN TO READ “NO SMOKING, NO
OPEN FLAMES, OXYGEN”.
E. PROVIDE SIGN ON EMERGENCY OXYGEN FILL CONNECTION. SIGN TO READ “EMERGENCY
OXYGEN FILL CONNECTION”.
F. INSTALL UNISTRUT FRAME ON GROUND TO ELEVATE GAS BOTTLES 4” A.F.G. FRAME TO BE
BOLTED STEEL, UNISTRUT P6000 OR EQUAL. COAT FRAME WITH AIR-DRY ENAMEL COATING.
COLOR TO BE BLACK OR AS COORDINATED WITH OWNER. MODIFY PIPING FROM TANK TO
HEADER FOR TANK HEIGHT CHANGE.
G. PROVIDE ANCHORAGE BOLTS FOR BULK OXYGEN STORAGE TANK TO SLAB. CONTRACTOR TO
COORDINATE WITH BULK TANK SUPPLIER FOR FIELD MODIFICATIONS TO TANK BASE FOR
ATTACHMENT OF POST-INSTALLED ANCHORS IN SLAB.
H. PROVIDE TAGS ON ALL SHUT-OFF VALVES AT BULK TANK. NUMBER EACH VALVE FOR LABELING
IN OWNER PROVIDED SHUT-DOWN PROCEDURE.