Roof Eval 2012 Clinic Moisture Study.pdf

PDF 15 MB Posted

Attached to
Western Oregon Roofing Replacement
Solicitation number
75H70126Q00020
Issued by

About this file

This is a technical data package containing the results of a roof moisture study conducted by A-Tech/Northwest, Inc. for the Portland Area Indian Health Service at the Chemawa Health Center Clinic Building #-022 in Salem, Oregon (Project #12267, dated December 5, 2012).

The study examined two single-ply roof assemblies (Roof A and Roof B) covering a total of 20,142 square feet. Roof A, comprising 15,289 square feet with a single-ply Duralast mechanically attached membrane installed in 2002, showed 4.55% total wet area (695 sq. ft.) with moisture penetration levels ranging from 0.05% to 4.15%. Roof B, covering 4,853 square feet with a single-ply Duralast membrane installed in 2007, exhibited 2.99% total wet area (145 sq. ft.) with moisture penetration from 0% to 2.95%. Both roofs utilize polyisocyanurate insulation over metal decks and have experienced intermittent interior leakage. The report recommends a planned roof management program (RMP) with regular visual inspections (minimum twice yearly) and electronic moisture studies every 4-5 years. Two long-term options are proposed: Option #1 involves membrane removal, insulation salvage and recovery with additional insulation installation; Option #2 recommends complete removal and replacement. The study concludes the roofs are manageable for the next five years with proper maintenance, with major work anticipated around 2020. The document includes detailed moisture contour maps, photographs, technical specifications on roof construction materials, and comprehensive guidance on repair procedures, material selection, and contractor qualifications for roof maintenance operations.

View the file

Other files

File Type Posted
75H70126Q00020-A00003.pdf PDF
75H70126Q00020-A00002.pdf PDF
Material Sub. 2001 Duro-last Roofing.pdf PDF
Roof Eval 2012 Clinic Visual inspection.pdf PDF
75H70126Q00020-A00001.pdf PDF
Clinic moderization Proj. 2015 Roofing 1.pdf PDF
Roof Eval 2012 Shop Visual Inspection.pdf PDF
Clinic moderization Proj. 2015 Roofing 2.pdf PDF
Material Sub. 2001 Foam insolation.pdf PDF
Dental expansion Proj. 2005 roofing.pdf PDF
9-US DOL WD OR20260104 Dated 1-2-2026.pdf PDF
2-Shop roof S.jpeg JPEG file
6-Clinic Roof North side.jpeg JPEG file
8-ICRA.docx DOCX document
7-Clinic Roof NW.jpeg JPEG file
5-Clinic Roof N faceing.jpeg JPEG file
4-Clinic Roof faceing South.jpeg JPEG file
3-Clinic Roof Dental.jpeg JPEG file
1-SOW.docx DOCX document
B01 75H70126Q00020.pdf PDF
A11 Pre-Solicitation SAM notice DRAFT.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .