| WO Bldg 1 | Alarm | CM/PM | 01/29/2021 | Standard Corrective Maint | After troubleshooting, found bad enclosure tamper switch. Replaced switch and resolved alarm issue. Closed ticket. | 01/29/2021 | ||
| WO Bldg 1 | Bollard | CM/PM | 01/13/2021 | Standard Corrective Maint | Tested bollards on WO1 circle. Bollards do not respond to remote commands, but the operate manually. Per Karl Thrash, raise bollards due to presidential inauguration events. FDA will notify when to have them lowered. | 01/14/2021 | ||
| WO Bldg 1 | Communication Failure | CM/PM | 01/25/2021 | Standard Corrective Maint | Found DDC halted and not communicating. Reset device and restored communications. Monitored device overnight and it is still working properly. Closed ticket. | 01/25/2021 | ||
| WO Bldg 1 | Communication Failure | CM/PM | 08/03/2021 | Standard Corrective Maint | Local Alarm tested and working | 08/17/2021 | ||
| WO Bldg 1 | Communication Failure | CM/PM | 08/03/2021 | Standard Corrective Maint | Local Alarm tested and working | 08/17/2021 | ||
| WO Bldg 1 | Communication Failure | CM/PM | 08/03/2021 | Standard Corrective Maint | Local Alarm tested and working | 08/17/2021 | ||
| WO Bldg 1 | Communication Failure | CM/PM | 08/03/2021 | Standard Corrective Maint | 08/17/2021 | |||
| WO Bldg 1 | Door | CM/PM | 01/20/2021 | Standard Corrective Maint | Upon arrival tested door and found no issues. Door was on holiday schedule when service call place and was reason it would not operate. Checks ok. | 01/21/2021 | ||
| WO Bldg 1 | Reader | CM/PM | 09/03/2021 | Standard Corrective Maint | Replaced defective reader and tested. Checks ok. | 09/03/2021 | ||
| WO Bldg 1 | Reader | CM/PM | 09/08/2021 | Standard Corrective Maint | Tested reader upon arrival and found reader working normally. Turnstile granted access every time badge was presented. Checks ok | 09/08/2021 | ||
| WO Bldg 1 | SFAULTS | CM/PM | 03/11/2021 | Standard Corrective Maint | Reset halted Act E and tested door. Checks ok. | 03/11/2021 | ||
| WO Bldg 1 | Turnstile | CM/PM | 09/01/2021 | Standard Corrective Maint | Replaced turnstile readers and tested. Checked OK at time of service. Complete. | 09/01/2021 | ||
| WO Bldg 2 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 | ||
| WO Bldg 2 | Alarm | CM/PM | 02/03/2021 | Standard Corrective Maint | Repair completed by John Kettle and system checks ok. | 02/03/2021 | ||
| WO Bldg 2 | Alarm | CM/PM | 03/02/2021 | Standard Corrective Maint | Motorola technician returned and repaired the issue causing communications issues. Closed ticket. | 03/16/2021 | Motorola technician will return to change settings in new system to correct issue. Tentatively scheduled for March 16, 2021. | |
| WO Bldg 2 | Alarm | CM/PM | 03/02/2021 | Standard Corrective Maint | Opened panel door and rearranged cables so door could close correctly. | 03/03/2021 | ||
| WO Bldg 2 | Alarm | CM/PM | 09/20/2021 | Standard Corrective Maint | Replaced defective motion detector to correct issue. Checks ok. | 09/21/2021 | ||
| WO Bldg 2 | Bollard | CM/PM | 01/14/2021 | Standard Corrective Maint | After troubleshooting, discovered that local SQL service did not start with MDI after PC update.. Manually started the SQL service and restored functions. Ticket closed. | 01/14/2021 | ||
| WO Bldg 2 | BVMS Bosch Video Management Sysytem | CM/PM | 01/29/2021 | Standard Corrective Maint | Bosch workstation was replaced and system restored. Closed ticket. | 02/10/2021 | ||
| WO Bldg 2 | Camera | CM/PM | 10/05/2021 | Standard Corrective Maint | Tightened loose camera bracket. Complete. | 10/07/2021 | ||
| WO Bldg 2 | Communication Failure | CM/PM | 02/10/2021 | Standard Corrective Maint | After troubleshooting, found lines were communicating but displayed comm-fail in MDI. Server had to be restarted. Proper comm displaying after reboot. Monitored line for 24 hrs, no additional issues. | 02/11/2021 | ||
| WO Bldg 2 | Communication Failure | CM/PM | 02/24/2021 | Standard Corrective Maint | Mass comfail due to PBCOM halting in server. Reset PBCOM and restored comms. | 02/24/2021 | ||
| WO Bldg 2 | Communication Failure | CM/PM | 04/01/2021 | Standard Corrective Maint | Found multiple devices in panel halted due to power outage. Restored devices and communications. Closed ticket. | 04/02/2021 | ||
| WO Bldg 2 | Communication Failure | CM/PM | 08/15/2021 | Standard Corrective Maint | Arms and fast pass are no longer in use. Masked in system | 08/17/2021 | ||
| WO Bldg 2 | Communication Failure | CM/PM | 09/30/2021 | Standard Corrective Maint | Restored LCom | 10/12/2021 | ||
| WO Bldg 2 | Communication Failure | CM/PM | 10/12/2021 | Standard Corrective Maint | Comm. Fail issue corrected by John Kettle. System online and operational. Complete | 10/12/2021 | ||
| WO Bldg 2 | Door | CM/PM | 02/03/2021 | Standard Corrective Maint | Replaced reader and lift lock on jammed door | 02/08/2021 | ||
| WO Bldg 2 | Door | CM/PM | 02/11/2021 | Standard Corrective Maint | Found no issues with door. There's a 2-3 second delay on rex release to activate ADA exit button. Inconsistency experienced when pressing the button before the delay. Must allow doors to unlock (32-3 seconds) before pressing the exit ADA button. | 02/11/2021 | ||
| WO Bldg 2 | Locking Hardware | CM/PM | 10/01/2021 | Standard Corrective Maint | Reset the acte | 10/12/2021 | ||
| WO Bldg 2 | Locking Hardware | CM/PM | 10/05/2021 | Standard Corrective Maint | Reset ACT-E | 10/12/2021 | ||
| WO Bldg 2 | Locking Hardware | CM/PM | 10/06/2021 | Standard Corrective Maint | Reset ACT-E | 10/12/2021 | ||
| WO Bldg 2 | Locking Hardware | CM/PM | 10/28/2021 | Standard Corrective Maint | Replaced defective ActE and tested door. Operational check ok. Complete | 10/28/2021 | ||
| WO Bldg 2 | Monitor | CM/PM | 05/04/2021 | Standard Corrective Maint | Replaced Monitor | 08/18/2021 | ||
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 01/22/2021 | Standard Corrective Maint | During troubleshooting, tested device and terminal is non-responsive. Terminal needs replacement. Motorola rep will be onsite 1/27/2121 for system replacement planning. Currently, command center has 3 terminals operational. Closed ticket. | 01/25/2021 | ||
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 01/29/2021 | Standard Corrective Maint | During troubleshooting, tested device and terminal is non-responsive. Terminal needs replacement. Motorola rep is scheduled to be onsite on 2/16/21 for system replacement planning. Currently, command center has 2 terminals operational. Closed ticket. | 02/01/2021 | ||
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 01/29/2021 | Standard Corrective Maint | During troubleshooting, tested device and terminal is non-responsive. Terminal needs replacement. Motorola rep is scheduled to be onsite on 2/16/21 for system replacement planning. Currently, command center has 2 terminals operational. Closed ticket. | 02/01/2021 | ||
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 02/25/2021 | Standard Corrective Maint | Motorola radio install technician was called in to troubleshoot installation. He found head end wired incorrectly. Equipment was properly wired and restored proper communication to all radios. Closed ticket | 03/04/2021 | ||
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 04/06/2021 | Standard Corrective Maint | Reset the system | 04/14/2021 | ||
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 04/27/2021 | Standard Corrective Maint | Call completed...vendor replaced repeater processor. | 09/20/2021 | 8/17/21 - Contacted Communications Electronics for service. TW | |
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 09/03/2021 | Standard Corrective Maint | Call complete. Vendor replaced part to correct issue. | 09/20/2021 | Contacted Tyler with Communications Electronics. Waiting on his arrival with new parts | |
| WO Bldg 2 | RADIO (MOTOROLA) | CM/PM | 09/03/2021 | Standard Corrective Maint | Vendor replaced part to correct issue. Complete. | 09/20/2021 | Contacted Tyler with Communications Electronics. Waiting on his arrival with new parts | |
| WO Bldg 2 | Reader | CM/PM | 02/25/2021 | Standard Corrective Maint | Blown fuse. Replaced lock working again | 02/26/2021 | ||
| WO Bldg 2 | Reader | CM/PM | 02/26/2021 | Standard Corrective Maint | Replaced blown 3 amp power supply fuse with 5 amp fuse and tested door... will monitor door and power supply for next couple of days to insure that it is working normally. | 03/01/2021 | ||
| WO Bldg 2 | Reader | CM/PM | 09/08/2021 | Standard Corrective Maint | 09/10/2021 | |||
| WO Bldg 2 | Schedule | CM/PM | 02/01/2021 | Standard Corrective Maint | Edited and restored correct schedule. | 02/01/2021 | ||
| WO Bldg 2 | Work Station | CM/PM | 01/11/2021 | Standard Corrective Maint | Referred issue to ERIC. IT must change PC group policy to prevent it PC from locking up after PIV badge is removed. | 01/12/2021 | ||
| WO Bldg 2 | Work Station | CM/PM | 03/01/2021 | Standard Corrective Maint | Replaced bad cabinet fan. Issue resolved. Closed ticket | 03/04/2021 | ||
| WO Bldg 2 | Work Station | CM/PM | 04/23/2021 | Standard Corrective Maint | Corrected | 08/17/2021 | ||
| WO Bldg 2 | Work Station | CM/PM | 10/29/2021 | Standard Corrective Maint | System admin. restarted MDI workstation to correct issue. Will monitor workstation to insure proper operation. | 11/03/2021 | 11/1/21 System admin. currently working to resolve issue with John Kettle in MDI. | |
| WO Bldg 21 | Auto Photo | CM/PM | 03/14/2021 | Standard Corrective Maint | Found autophoto workstation working normally upon arrival. | 03/15/2021 | ||
| WO Bldg 21 | Auto Photo | CM/PM | 03/16/2021 | Standard Corrective Maint | Guard had manual picture selection on. Reset to automatic selection to correct issue. Complete | 03/16/2021 | ||
| WO Bldg 21 | Auto Photo | CM/PM | 04/19/2021 | Standard Corrective Maint | All auto-photo workstations were replaced. User profile is not working. IT has to clear user account in group policy. Forwarded issue to IT for resolution. | 04/19/2021 | ||
| WO Bldg 21 | Auto Photo | CM/PM | 11/08/2021 | Standard Corrective Maint | Password needs to be reset and passed on to Security to ensure they have the correct password. I don't have the ability to reset passwords. Recommend System Admin look into it. | 11/08/2021 | Security tried 2 different passwords, still could not login. | |
| WO Bldg 21 | Camera | CM/PM | 11/08/2021 | Standard Corrective Maint | Power tripped. Reset circuit breaker | 11/08/2021 | ||
| WO Bldg 21 | Door | CM/PM | 02/18/2021 | Standard Corrective Maint | Door locking mechanism is malfunctioning. Forwarded issue to facilities/Honeywell (Via Command Ctr.) for troubleshooting Dorma sliding door for resolution. | 02/18/2021 | ||
| WO Bldg 21 | Reader | CM/PM | 11/08/2021 | Standard Corrective Maint | Old style card reader burned out and non operational. Changed the card reader out and installed a spacer behind the reader. Reset the ACT-E due to power outage this morning. The system to be off schedule. | 11/08/2021 | ||
| WO Bldg 21 | SFAULTS | CM/PM | 11/08/2021 | Standard Corrective Maint | Reset circuit breaker. It Tripp and cut off the power. Reset the acte because the readers were not working/responding to badges. | 11/08/2021 | ||
| WO Bldg 22 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 | ||
| WO Bldg 22 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 | ||
| WO Bldg 22 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 | ||
| WO Bldg 22 | Auto Photo | CM/PM | 01/25/2021 | Standard Corrective Maint | Found guard's MDI account expired. Corrected expiration date. Tested account, issues resolved. | 01/25/2021 | ||
| WO Bldg 22 | Auto Photo | CM/PM | 04/14/2021 | Standard Corrective Maint | All auto-photo workstations were replaced. User profile is not working. IT has to clear user account in group policy. Forwarded issue to IT for resolution. | 04/14/2021 | ||
| WO Bldg 22 | Auto Photo | CM/PM | 04/19/2021 | Standard Corrective Maint | All auto-photo workstations were replaced. User profile is not working. IT has to clear user account in group policy. Forwarded issue to IT for resolution. | 04/19/2021 | ||
| WO Bldg 22 | Auto Photo | CM/PM | 09/20/2021 | Standard Corrective Maint | Found autophoto unit not connecting to FDA network. | |||
| Advised FDA IT to correct network issue. | 09/20/2021 | |||||||
| WO Bldg 22 | Auto Photo | CM/PM | 10/01/2021 | Standard Corrective Maint | 11/1/2021 FDA IT moved autophoto Cat5 cable to another newwork port and re-configured port. System admin. tested autophoto to insure signon good. Operational check ok. Complete | 11/01/2021 | Work station cannot connect to FDA servers. Contacted FDA IT to help troubleshot connection issue.Opened service ticket with FDA IT to trace network cable and label. | |
| WO Bldg 22 | BVMS Bosch Video Management Sysytem | CM/PM | 02/24/2021 | Standard Corrective Maint | After troubleshooting, found broken fiber termination. Re-terminated fiber connector and restore connection. Closed ticket. | 02/24/2021 | ||
| WO Bldg 22 | Camera | CM/PM | 02/22/2021 | Standard Corrective Maint | After troubleshooting, found broken fiber termination. Re-terminated fiber connector and restore connection. Closed ticket. | 02/24/2021 | ||
| WO Bldg 22 | Camera | CM/PM | 08/04/2021 | Standard Corrective Maint | camera is working | 10/15/2021 | ||
| WO Bldg 22 | Key Pad | CM/PM | 03/18/2021 | Standard Corrective Maint | Found damaged fiber termination to communication device. Repaired fiber and restored proper communications. Closed ticket. | 03/22/2021 | ||
| WO Bldg 22 | Key Pad | CM/PM | 10/25/2021 | Standard Corrective Maint | Keypad on schedule from 6am-6pm. |
Tenant doesn't have access to keypad outside of schedule hours.
| Operational check ok. Complete. | 10/25/2021 | |||||||
| WO Bldg 22 | Reader | CM/PM | 02/26/2021 | Standard Corrective Maint | Reset halted Act E and tested door. Door checks ok and S Fault cleared. | 02/26/2021 | ||
| WO Bldg 22 | Reader | CM/PM | 04/01/2021 | Standard Corrective Maint | Reader working | 04/07/2021 | ||
| WO Bldg 22 | Reader | CM/PM | 10/27/2021 | Standard Corrective Maint | Upon arrival tested reader and found operating normally. Tightened wire connections to reader. Operational checks ok. | 10/27/2021 | ||
| WO Bldg 22 | SFAULTS | CM/PM | 02/01/2021 | Standard Corrective Maint | Reset halted Act E and tested door. Checks ok. | 02/01/2021 | ||
| WO Bldg 22 | SFAULTS | CM/PM | 02/09/2021 | Standard Corrective Maint | Reset halted Act E causing issue. Tested reader and checks ok. Complete | 02/09/2021 | ||
| WO Bldg 22 | SFAULTS | CM/PM | 04/13/2021 | Standard Corrective Maint | Reset acte | 04/14/2021 | ||
| WO Bldg 31 | AED | CM/PM | 02/03/2021 | Standard Corrective Maint | Replaced inoperable device. Closed ticket. | 02/10/2021 | Found bad switch. Ordered replacement, awaiting parts. | |
| WO Bldg 31 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 | ||
| WO Bldg 31 | Battery | CM/PM | 08/03/2021 | Standard Corrective Maint | Corrected | 08/17/2021 | ||
| WO Bldg 31 | Battery | CM/PM | 08/03/2021 | Standard Corrective Maint | Corrected | 08/17/2021 | ||
| WO Bldg 31 | Battery | CM/PM | 08/03/2021 | Standard Corrective Maint | Corrected | 08/17/2021 | ||
| WO Bldg 31 | Battery | CM/PM | 08/03/2021 | Standard Corrective Maint | Corrected | 08/17/2021 | ||
| WO Bldg 31 | Bollard | CM/PM | 01/15/2021 | Standard Corrective Maint | Bollards were lowered with no problem. Returned later to raise the bollard. The special tool used that adapts to bollard manual drive broke. Used replacement tool to raise bollards. Closed ticket. | 01/15/2021 | ||
| WO Bldg 31 | Bollard | CM/PM | 05/07/2021 | Standard Corrective Maint | 09/01/2021 | 8/18/21 - Pending site visit by Concentric on 8/23/21 | ||
| WO Bldg 31 | Camera | CM/PM | 10/29/2021 | Standard Corrective Maint | ||||
| WO Bldg 32 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 | ||
| WO Bldg 32 | Alarm | CM/PM | 01/25/2021 | Standard Corrective Maint | After troubleshooting, found enclosure contact defective. Replaced contact, tested system with command center, all issues resolved. Closed ticket. | 01/25/2021 | ||
| WO Bldg 32 | Alarm | CM/PM | 04/15/2021 | Standard Corrective Maint | Found corrupt instance of MDI application. Restored data file from server and restored workstation communications. Closed ticket. | 04/15/2021 | ||
| WO Bldg 32 | Alarm | CM/PM | 10/22/2021 | Standard Corrective Maint | 10/27/21. We conducted a walk through of the SCIF and have identified the solution: 1. Reset password 2. trouble shoot system schedule error message this will be performed 10/28/21 |
11/1/21 SCIF rescheduled for 11/3/21 with Thomas Yates.
System admin reset password for Thomas Yates and restarted MDI server to correct error messages.
| Operational Check OK. | 11/03/2021 | |||||||
| WO Bldg 32 | Auto Photo | CM/PM | 01/14/2021 | Standard Corrective Maint | Guard was entering wrong password. Logged in with right credentials. No additional issues. | 01/14/2021 | ||
| WO Bldg 32 | Auto Photo | CM/PM | 03/15/2021 | Standard Corrective Maint | Found autophoto locked up due to app running in background causing it to lock up. Closed back ground app and restarted autophoto. Tested reader and found working normally again. Complete | 03/17/2021 | ||
| WO Bldg 32 | Auto Photo | CM/PM | 09/21/2021 | Standard Corrective Maint | Found autophoto not connecting to FDA network. Advised FDA IT to correct network issue to correct problem. | 09/21/2021 | ||
| WO Bldg 32 | BVMS Bosch Video Management Sysytem | CM/PM | 04/12/2021 | Emergency Corrective Maint | Workstation was restarted and restored. Closed ticket. | 04/13/2021 | ||
| WO Bldg 32 | Camera | CM/PM | 04/06/2021 | Standard Corrective Maint | EOL VG4 camera. No replacement available. Camera is out of scope. Recommended replacement to newer camera. | 04/06/2021 | ||
| WO Bldg 32 | Camera | CM/PM | 08/04/2021 | Standard Corrective Maint | Replaced defective workstation and reloaded Bosch 9.0. Returned and installed work station. Complete | 08/06/2021 | ||
| WO Bldg 32 | Camera | CM/PM | 09/15/2021 | Standard Corrective Maint | Found work station off. Turned unit on and tested. Checks OK. | 10/16/2021 | ||
| WO Bldg 32 | Communication Failure | CM/PM | 03/10/2021 | Standard Corrective Maint | Found PB communications restored upon arrival. Checks ok. | 03/10/2021 | ||
| WO Bldg 32 | Reader | CM/PM | 03/09/2021 | Standard Corrective Maint | Tested reader upon arrival and found it working normally. | 03/09/2021 | ||
| WO Bldg 32 | Reader | CM/PM | 03/09/2021 | Standard Corrective Maint | Tested reader upon arrival and found it working normally. | 03/09/2021 | ||
| WO Bldg 32 | Reader | CM/PM | 05/03/2021 | Standard Corrective Maint | Reader and lock works properly. Door may be slightly misaligned causing pressure on lock. Handled needed to be pulled on for lock to release | 05/04/2021 | ||
| WO Bldg 32 | SFAULTS | CM/PM | 02/01/2021 | Standard Corrective Maint | Replaced defective reader and blown fuse in Act E to correct issue with door. | 02/03/2021 | ||
| WO Bldg 32 | Visitor Management System | CM/PM | 10/08/2021 | Standard Corrective Maint | VMS system to be removed from service and scheduled for removal today. Complete | 10/12/2021 | ||
| WO Bldg 51 | Auto Photo | CM/PM | 03/10/2021 | Standard Corrective Maint | All auto-photo workstations were replaced. User profile is not working. IT has to clear user account in group policy. Forwarded issue to IT for resolution. | 03/10/2021 | ||
| WO Bldg 51 | Bollard | CM/PM | 01/13/2021 | Standard Corrective Maint | Could not test bollards, no hydraulic fluid in tank. All bollards set for maintenance in February 2021. Fluid will be refilled and system inspected. | 01/14/2021 | ||
| WO Bldg 51 | Bollard | CM/PM | 02/22/2021 | Standard Corrective Maint | Bollards raised and secured area. | 02/24/2021 | ||
| WO Bldg 51 | Bollard | CM/PM | 08/04/2021 | Standard Corrective Maint | Lowered Bollards | 08/05/2021 | ||
| WO Bldg 51 | Camera | CM/PM | 02/02/2021 | Standard Corrective Maint | Rebooted camera power to correct issue. Camera video restored but video slightly blurred due to camera age. | 02/02/2021 | ||
| WO Bldg 51 | Camera | CM/PM | 02/26/2021 | Standard Corrective Maint | Replaced defective camera | 03/02/2021 | ||
| WO Bldg 51 | Communication Failure | CM/PM | 02/16/2021 | Standard Corrective Maint | Found inoperable PB panel. Replaced panel and restored communications. | 02/17/2021 | ||
| WO Bldg 51 | Communication Failure | CM/PM | 03/30/2021 | Standard Corrective Maint | Powered down the SBC for a minute and re Powered the system back up. Checked Network cable and power. All good. System started communicating. System back in service. | 03/31/2021 | DDC on line 104 is not communicating. Panel located in data room 13C02. | |
| WO Bldg 51 | Reader | CM/PM | 02/01/2021 | Standard Corrective Maint | Reset acte | 02/08/2021 | ||
| WO Bldg 51 | Reader | CM/PM | 06/15/2021 | Standard Corrective Maint | Network switch was down due to maintenance | 06/25/2021 | ||
| WO Bldg 52 | AED | CM/PM | 01/08/2021 | Standard Corrective Maint | Found dead battery on sounder alarm switch. Replaced battery and restored function. | 01/12/2021 | ||
| WO Bldg 52 | AED | CM/PM | 02/26/2021 | Standard Corrective Maint | Duplicate ticket. AED stations alarm switch installed give the appearance of the cover door being open. No changes can be made to close the doors flushed. AED's are operating properly and alarming both local and to command center. No other issues found. Closed ticket | 03/04/2021 | ||
| WO Bldg 52 | Alarm | CM/PM | 10/13/2021 | Standard Corrective Maint | This is a Sentry RMS alarm point. Sentry RMS is an active BITS install. Disregard | 10/28/2021 | ||
| WO Bldg 52 | Camera | CM/PM | 04/26/2021 | Standard Corrective Maint | Camera was reset due to power loss )Building Maintenance). Reconfigured camera to properly display image. Closed ticket. | 04/26/2021 | ||
| WO Bldg 52 | Camera | CM/PM | 05/04/2021 | Standard Corrective Maint | Camera had lost power Restored proper home position | 05/04/2021 | ||
| WO Bldg 52 | Camera | CM/PM | 05/04/2021 | Standard Corrective Maint | 10/27/21 We are identifying the camera type and whether we have the same model on hand. We are also reaching out to BOSCH for a quote for a replacement if we do not have on hand. | 10/28/2021 | ||
| WO Bldg 52 | Camera | CM/PM | 10/19/2021 | Standard Corrective Maint | Flexidome needs to be replaced. Was not in use before malfunction because camera is blocked by equipment |
10/27/21. CSI will need to order two cameras for replacement of #5203 and the second will be a spare.
| WO Bldg 52 | Camera | CM/PM | 10/19/2021 | Standard Corrective Maint | 10/27/21 CSI will order replacement part. In the ceiling vg5 is not putting out video. Part number vg5-723-cce2. | |
| WO Bldg 52 | Communication Failure | CM/PM | 02/16/2021 | Standard Corrective Maint | Nodes showed communication fail in system, but devices were communicating properly. Reset nodes to clear false negative in system. Restored proper status display. | 02/17/2021 |
| WO Bldg 52 | Communication Failure | CM/PM | 09/20/2021 | Standard Corrective Maint | Had system administrator perform panel reset to correct issue. Checks ok. | 09/20/2021 |
| WO Bldg 52 | Preventative Maintenance | CM/PM | 01/22/2021 | Standard Corrective Maint | Met with Barbara Paul and replaced irradiator monitor device. Ms. Paul provided replacement part. Closed ticket. | 01/25/2021 |
| WO Bldg 52 | Reader | CM/PM | 01/06/2021 | Standard Corrective Maint | Found SBC board not polling. Reset board and tested system with system administrator. Tested reader and now working normally. | 01/06/2021 |
| WO Bldg 52 | Reader | CM/PM | 01/09/2021 | Standard Corrective Maint | Upon arrival I tested reader with valid badge holder and doors work normally. Made new reader number labels and installed. Checks ok. | 01/11/2021 |
| WO Bldg 52 | Reader | CM/PM | 02/08/2021 | Standard Corrective Maint | Found inoperable reader. Replaced reader and restored door functions. | 02/08/2021 |
| WO Bldg 52 | Reader | CM/PM | 02/16/2021 | Standard Corrective Maint | Bio reader was frozen in processing badge. Rebooted reader and restored functions. Tested reader functions multiple times and found no issues. Closed ticket. | 02/16/2021 |
| WO Bldg 52 | Reader | CM/PM | 03/09/2021 | Standard Corrective Maint | Reset DDC board to correct issue. | 03/09/2021 |
| WO Bldg 52 | Reader | CM/PM | 03/12/2021 | Standard Corrective Maint | Reinstalled reader and tested. Checks ok. | 03/12/2021 |
| WO Bldg 52 | Reader | CM/PM | 05/07/2021 | Standard Corrective Maint | 09/20/2021 | |
| WO Bldg 62 | AED | CM/PM | 08/03/2021 | Standard Corrective Maint | AED fixed | 08/17/2021 |
| WO Bldg 62 | Auto Photo | CM/PM | 08/16/2021 | Standard Corrective Maint | 09/01/2021 | |
| WO Bldg 62 | Camera | CM/PM | 09/21/2021 | Standard Corrective Maint | Found camera monitor using wrong camera input cable. Changed connection type to correct issue. Operational Check OK. | 09/21/2021 |
| WO Bldg 62 | Communication Failure | CM/PM | 05/02/2021 | Standard Corrective Maint | DDC went bad. Replaced | 05/04/2021 |
| WO Bldg 62 | Installation | CM/PM | 02/22/2021 | Standard Corrective Maint | Escort provided to Motorola radio technicians from 2/22 through 2/24/2021. | 02/24/2021 |
| WO Bldg 62 | Reader | CM/PM | 09/08/2021 | Standard Corrective Maint | Replaced reader...Checks OK | 09/08/2021 |
| WO Bldg 64 | Alarm | CM/PM | 03/30/2021 | Standard Corrective Maint | No issue with badge or reader were found. Closed ticket. | 03/31/2021 |
| WO Bldg 64 | Alarm | CM/PM | 10/25/2021 | Standard Corrective Maint | Replaced batteries in all AED units. |
Found AED cabinets are not wired into security system panels.
| New wire must be pulled and tied into MDI system. This work will be install project and approval from FDA necessary to complete. Waiting on approval. | 10/25/2021 | |||||||
| WO Bldg 64 | Communication Failure | CM/PM | 06/13/2021 | Standard Corrective Maint | Reset panel | 06/25/2021 | ||
| WO Bldg 64 | Locking Hardware | CM/PM | 02/11/2021 | Standard Corrective Maint | Repaired strike install at door frame. Door working ok. Closed ticket. | 02/17/2021 | Appointment set for 2/12/2021. | |
| WO Bldg 64 | Locking Hardware | CM/PM | 02/11/2021 | Standard Corrective Maint | Repaired strike install at door frame. Door working ok. Closed ticket. | 02/12/2021 | Appointment set for 2/12/2021. | |
| WO Bldg 64 | Reader | CM/PM | 03/19/2021 | Standard Corrective Maint | Spoke with POC from lab Ms. Stewart and readers don’t need to removed from wall at this time. | 03/19/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 04/01/2021 | Standard Corrective Maint | Upon arrival, found door handset unlocked. Tested reader and all other security system's devices and all are in good operating status. Guard used master key to lock handset. Confirmed door was secured and properly working. Closed ticket. | 04/01/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 06/15/2021 | Standard Corrective Maint | Reset ddc | 06/25/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 06/15/2021 | Standard Corrective Maint | Needed a key to lock the door | 06/25/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 06/15/2021 | Standard Corrective Maint | Needed a key to lock the door | 06/25/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 06/16/2021 | Standard Corrective Maint | Door working properly upon arrival | 06/25/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 09/08/2021 | Standard Corrective Maint | Replaced reader...Checks OK | 09/09/2021 | ||
| WO Bldg 64 | Reader | CM/PM | 09/08/2021 | Standard Corrective Maint | Reset ActE to correct S Fault...Checks OK | 09/09/2021 | ||
| WO Bldg 64 | SFAULTS | CM/PM | 01/05/2021 | Standard Corrective Maint | Replaced defective card reader and reset Act E. Tested reader with system administrator and reader working normally. Complete. | 01/06/2021 | ||
| WO Bldg 66 | Alarm | CM/PM | 02/18/2021 | Standard Corrective Maint | Found device and relabeled in system. | 02/19/2021 | ||
| WO Bldg 66 | Alarm | CM/PM | 03/14/2021 | Standard Corrective Maint | Found act-e inoperable. Replaced act-e, resolved issue. Closed ticket. | 03/15/2021 | ||
| WO Bldg 66 | Auto Photo | CM/PM | 01/07/2021 | Standard Corrective Maint | Checked system, found no issues, tested with card Reader. Possibly the monitor was sleep. | 01/07/2021 | ||
| WO Bldg 66 | Auto Photo | CM/PM | 03/24/2021 | Standard Corrective Maint | Known downtime issue. Autophoto workstation replaced with MDI SP5 Upgrade. | 03/26/2021 | ||
| WO Bldg 66 | Bollard | CM/PM | 01/12/2021 | Standard Corrective Maint | Bollard needs repair from Concentric/IST. Contract with Service company is being worked out by Tommy Worth. Bollards works manually. Closed ticket. | 01/12/2021 | ||
| WO Bldg 66 | Bollard | CM/PM | 01/13/2021 | Standard Corrective Maint | Duplicate ticket. Bollard needs repair from Concentric/IST. Contract with Service company is being worked out by Tommy Worth. Bollards works manually. Closed ticket. | 01/13/2021 | ||
| WO Bldg 66 | BVMS Bosch Video Management Sysytem | CM/PM | 04/20/2021 | Standard Corrective Maint | 66 upper doesn't have a Bvms workstation | 05/05/2021 | ||
| WO Bldg 66 | Camera | CM/PM | 11/02/2021 | Standard Corrective Maint | Restored fast address...Operational Check OK | 11/08/2021 | ||
| WO Bldg 66 | Locking Hardware | CM/PM | 09/21/2021 | Standard Corrective Maint | Found Locknetics maglock bad upon arrival onsite. Sent email to Joanna to order new maglock. Locknetics Model 101+ delay egress maglock. |
10/29/21 Spoke to Johana Davis.. part on order (awaiting part)
| WO Bldg 66 | Locking Hardware | CM/PM | 09/21/2021 | Standard Corrective Maint | Tested maglock upon arrival and found power disconnected. Applied power and maglock worked normally. Maglock tied into fire drop relay. Operational Check OK | 09/21/2021 | |
| WO Bldg 66 | Magnetometer-Walk Through Metal Detector | CM/PM | 02/11/2021 | Standard Corrective Maint | Magnetometer replaced. Closed ticket. | 04/01/2021 | Unit works but outputs a single alarm every 1-2 minutes. Currently working with Garrett tech support on resolution. |
Magnetometer to be replaced.
| WO Bldg 66 | Magnetometer-Walk Through Metal Detector | CM/PM | 02/20/2021 | Standard Corrective Maint | Duplicate ticket. Magnetometer is on schedule to be replaced. | 02/20/2021 | |
| WO Bldg 66 | Reader | CM/PM | 01/11/2021 | Standard Corrective Maint | WO66, R250, Data room 46C85. Old style card reader is not reading badges. Replaced the reader, added a spacer, tested and verified with command center. System is operational. | 01/12/2021 | |
| WO Bldg 66 | Reader | CM/PM | 02/03/2021 | Standard Corrective Maint | Checked card reader, card reader is reading badges properly. Did not change card reader out. | 02/03/2021 | |
| WO Bldg 66 | Reader | CM/PM | 02/18/2021 | Standard Corrective Maint | Act-e for reader needed a new fuse. Replaced fuse and restore reader functions. | 02/18/2021 | |
| WO Bldg 66 | Reader | CM/PM | 05/03/2021 | Standard Corrective Maint | Blown act e fuse. Replaced act e | 05/04/2021 | |
| WO Bldg 66 | Reader | CM/PM | 08/15/2021 | Standard Corrective Maint | Replaced reader | 08/17/2021 | |
| WO Bldg 66 | Reader | CM/PM | 09/07/2021 | Standard Corrective Maint | Replaced defective reader. Checks OK | 09/07/2021 | |
| WO Bldg 66 | SFAULTS | CM/PM | 03/12/2021 | Standard Corrective Maint | Reset halted Act E and tested door. Checks ok. | 03/15/2021 | |
| WO Bldg 71 | AED | CM/PM | 01/05/2021 | Standard Corrective Maint | Tried to reform door so door switch stayed closed. Tested with command center and and door switch was closed and not sending alarms. | 01/06/2021 | |
| WO Bldg 71 | AED | CM/PM | 01/08/2021 | Standard Corrective Maint | After troubleshooting, found low battery on local alarm device. Replaced battery. | 01/08/2021 | |
| WO Bldg 71 | Camera | CM/PM | 05/04/2021 | Standard Corrective Maint | 10/12/2021 | ||
| WO Bldg 71 | Camera | CM/PM | 05/04/2021 | Standard Corrective Maint | Reset camera. Live cleared up some in BVMS. Playback is clear. Picture also clear when logged directly into the camera | 05/04/2021 | |
| WO Bldg 71 | Communication Failure | CM/PM | 04/17/2021 | Standard Corrective Maint | Reset sbc | 04/23/2021 | |
| WO Bldg 71 | Communication Failure | CM/PM | 10/29/2021 | Standard Corrective Maint | Panel been restored by FDA IT. Panel back online...Complete | 11/08/2021 | Programmed new SBC board and replaced, reset DDC boards and system administrator cannot ping SBC IP address. Contacted FDA IT to test network switch port. Awaiting results from IT. |
| WO Bldg 71 | Locking Hardware | CM/PM | 09/16/2021 | Standard Corrective Maint | Found mag lock power disconnected upon arrival. Repowered up mag lock. It works normally and is connected to building fire drop relay. Door needs new crash bar with time delay to release door. Will advise pyshical security of issue for installation of new crash bar assembly. | 09/17/2021 | |
| WO Bldg 71 | Locking Hardware | CM/PM | 09/16/2021 | Standard Corrective Maint | Mag lock disconnected from power upon arrival. Powered mag lock and it is working normally. Need new crash bar with time delay to release door mag lock. Mag lock tied to building fire relay. Will advise physical security to install new crash bar. | 09/17/2021 | |
| WO Bldg 71 | Locking Hardware | CM/PM | 09/16/2021 | Standard Corrective Maint | Found mag lock disconnected from power upon arrival. Powered up mag lock and tested normally. Door needs a new crash bar with time delay to release door lock. Will advise physical security to have new crash bar installation. Mag lock tied to building fire relay. | 09/17/2021 | |
| WO Bldg 72 | Biometric Reader | CM/PM | 02/19/2021 | Standard Corrective Maint | Found reader not responding to badges. Reset reader and restored functions. |
| Note: Reader has been reset multiple times with the same issue. New bio reader ordered for replacement. | 02/19/2021 | ||||||
| WO Bldg 72 | Communication Failure | CM/PM | 03/30/2021 | Standard Corrective Maint | Reset sbc | 04/23/2021 | |
| WO Bldg 72 | Communication Failure | CM/PM | 04/24/2021 | Standard Corrective Maint | Found DDC board halted and not communicating. Reset DDC board and restored communications. | 04/26/2021 | |
| WO Bldg 72 | Communication Failure | CM/PM | 05/10/2021 | Standard Corrective Maint | Comms restored | 08/17/2021 | |
| WO Bldg 72 | Locking Hardware | CM/PM | 03/08/2021 | Emergency Corrective Maint | Found reader operating normally at time of service... tested the badge and door unlocked with no problems. | 03/09/2021 | |
| WO Bldg 72 | Reader | CM/PM | 01/07/2021 | Standard Corrective Maint | Card reader was reading and going through the process but the door would not unlock. The issue was related to the Main SBC was not communicating properly to the DDC output. System required an SBC reset. System reset and all readers tested. Test good. | 01/07/2021 | |
| WO Bldg 72 | Reader | CM/PM | 01/16/2021 | Standard Corrective Maint | Card Reader was not reading badges. Removed CR and checked all wiring. Card reader appeared to be dormant. Wiring looked good. Card Reader restarted and went through boot up process. Card reader tested by Mr Mario Ortega. Test good 5 times. | 01/18/2021 | |
| WO Bldg 72 | Reader | CM/PM | 02/17/2021 | Standard Corrective Maint | Waiting on further instruction on how to proceed | 05/04/2021 | |
| WO Bldg 72 | Reader | CM/PM | 03/10/2021 | Standard Corrective Maint | Replaced defective bio reader to correct issue. | 03/10/2021 | |
| WO Bldg 72 | Reader | CM/PM | 04/08/2021 | Standard Corrective Maint | The door is not securing because it's fall off the henge at the top. It was referred to maintenance | 04/23/2021 | |
| WO Bldg 72 | Reader | CM/PM | 04/15/2021 | Standard Corrective Maint | Ddc went bad | 04/16/2021 | |
| WO Bldg 72 | SFAULTS | CM/PM | 01/07/2021 | Standard Corrective Maint | Found contact magnet loose. Properly replaced it and set. Closed ticket. | 01/11/2021 | |
| WO Bldg 75 | AED | CM/PM | 01/02/2021 | Standard Corrective Maint | Upon arrival found door was closed and not sending out alarms. Door was flush with cabinet and required no adjustments. | 01/04/2021 | |
| WO Bldg 75 | Auto Photo | CM/PM | 10/12/2021 | Standard Corrective Maint | Upon arrival found autophoto unit signed on and operating normal. Printed test badge. Operational Check Ok. | 10/13/2021 | |
| WO Bldg 75 | Camera | CM/PM | 03/29/2021 | Standard Corrective Maint | Cameras restored by themselves. Checked camera operation with Command Center. Complete | 03/30/2021 | |
| WO Bldg 75 | Camera | CM/PM | 04/29/2021 | Standard Corrective Maint | Replaced defective camera and tested. Complete | 04/29/2021 | |
| WO Bldg 75 | Camera | CM/PM | 09/03/2021 | Standard Corrective Maint | Lift ordered to troubleshoot camera. |
To be delivered 9/13/22
| Camera repaired...call complete | 09/20/2021 | |||||||
| WO Bldg 75 | Door | CM/PM | 04/12/2021 | Standard Corrective Maint | Replaced reader | 04/14/2021 | ||
| WO Campus | Bollard | CM/PM | 01/13/2021 | Standard Corrective Maint | Bollard needs repair from Concentric/IST. Contract with Service company is being worked out by Tommy Worth. Bollards works manually. Closed ticket. | 01/14/2021 | ||
| WO Campus | Camera | CM/PM | 01/28/2021 | Standard Corrective Maint | Duplicate ticket. Bad VG4 camera. Camera removed from housing for possible replacement research. Bosch VG4 cameras reached EOL per manufacturer. | 01/29/2021 | ||
| WO Campus | Camera | CM/PM | 03/05/2021 | Standard Corrective Maint | Bypassed bad commend module and plugged camera directly into comnet module and camera video restored | 03/09/2021 | ||
| WO Campus | Camera | CM/PM | 03/08/2021 | Standard Corrective Maint | Damaged camera is part of uncompleted installation at Cherry Hill Gate. Ticket opened for tracking purposes. Closed ticket. | 03/09/2021 | ||
| WO Campus | Camera | CM/PM | 04/12/2021 | Standard Corrective Maint | Checked communications link for camera, link checked good. Camera stopped communicating. Reset camera, power up indicate camera is operating. | 04/16/2021 | ||
| WO Campus | Camera | CM/PM | 08/05/2021 | Standard Corrective Maint | Chesapeake corrected NetApp issue. They also placed a service call with NetApp to visit the site for further diagnosis. At this moment all cameras are recording. | 08/16/2021 | ||
| WO Campus | Commend-Code Blue Stations | CM/PM | 02/27/2021 | Standard Corrective Maint | Upon arrival, found fiber module not communicating. Reset power on module and device was properly restored. Monitored device for 48 hours for additional issues, but no other issues have come up from device. Closed ticket | 03/04/2021 | ||
| WO Campus | Commend-Code Blue Stations | CM/PM | 11/01/2021 | Standard Corrective Maint | Checked all Commend cameras with Command center. All cameras are operational except for two on open service tickets. None of the cameras are showing up on the Call up monitor. Checked the system in Command center and the video jet was down due to the AC power cord on the power transformer worked loose. The video jet booted up, I continued and still none of the cameras would show up after initiating a call. The Video Jet server appears not to be functioning. Need further troubleshooting. Update 11/2/21 0730 hrs.(Bosch Video Jet VIP-XDHD). Will verify configuration settings in Video Jet to determine its status. | |||
| WO Campus | Communication Failure | CM/PM | 03/30/2021 | Standard Corrective Maint | Account communicating properly. Closed ticket. | 03/30/2021 | ||
| WO Campus | Communication Failure | CM/PM | 04/05/2021 | Standard Corrective Maint | 10/12/2021 | 8/18/21 - Ordered new ComNet 2W media converter for SM fiber connection | ||
| WO Campus | Reader | CM/PM | 01/25/2021 | Standard Corrective Maint | Found reader pedestal broken from its base and on the ground. Issue is out of CM scope. Protected wires agaist water damage (Winter storm in forecast). Reported issue to FDA Security. Work order forwarded to FDA facilities. | 01/25/2021 | ||
| WO Campus | Visitor Management System | CM/PM | 03/05/2021 | Standard Corrective Maint | Test ticket. | 03/08/2021 | ||
| WO Ch Care | Communication Failure | CM/PM | 09/07/2021 | Standard Corrective Maint | Reset SBC board and system recovered. All checks ok. | 09/07/2021 | ||
| WO Cup | Camera | CM/PM | 03/23/2021 | Standard Corrective Maint | 10/29/21 Current installed switch is no longer available. (CWGE24MS2) |
Email sent To Johanna Davis to order new switch model (CNGE24MS2) Awaiting part arrival date.
| WO Cup | Camera | CM/PM | 03/23/2021 | Standard Corrective Maint | Duplicate ticket. Part on order under ticket 2473. | 10/29/2021 |
| WO Cup | Camera | CM/PM | 04/12/2021 | Standard Corrective Maint | Duplicate ticket. Part ordered under ticket 2473 | 10/29/2021 |
| WO Cup | Communication Failure | CM/PM | 03/20/2021 | Standard Corrective Maint | Per IT, default gateway IP address was changed. Updated panel configurations and restored communications. | 03/25/2021 |
| WO N Garag | Camera | CM/PM | 03/18/2021 | Standard Corrective Maint | Performed camera reset with Bosch service program. Camera rebooted and tested PTZ function and reset home positioning. Complete | 03/18/2021 |
| WO N Garag | Camera | CM/PM | 03/26/2021 | Standard Corrective Maint | Ordered new POE+ switch |
!0/29/21 Awaiting parts..
| WO N Garag | Camera | CM/PM | 04/16/2021 | Standard Corrective Maint | Reset camera POE switches and performed operational check on all listed camers. Complete. | 10/29/2021 | ||
| WO N Garag | Camera | CM/PM | 06/14/2021 | Standard Corrective Maint | Rebooted camera and performed operational check. All camera funtions normal as of 10/29/21 Complete. | 10/29/2021 | ||
| WO N Garag | Camera | CM/PM | 08/04/2021 | Standard Corrective Maint | Rebooted camera power. performed operational check. All camera fuctions opering normal as of | |||
| 10/29/21. Complete | 10/29/2021 | |||||||
| WO NE Garg | Communication Failure | CM/PM | 10/18/2021 | Standard Corrective Maint | Found SBC port dead. Replaced DDC board and changed node to 15. Also changed SBC port to 7. Mux fail corrected and back on line. | 10/25/2021 | ||
| WO Trk Scr | Ai Phone | CM/PM | 03/09/2021 | Standard Corrective Maint | Found power cord to master station knocked off disconnected under the desk. Reconnected power and restored device. Closed ticket. | 03/10/2021 | ||
| WO Trk Scr | BVMS Bosch Video Management Sysytem | CM/PM | 02/23/2021 | Standard Corrective Maint | Video Jet workstation was not booting up. Troubleshoot workstation and restored start-up files. System restored. | 02/23/2021 | ||
| WO Trk Scr | BVMS Bosch Video Management Sysytem | CM/PM | 02/25/2021 | Standard Corrective Maint | Changed cameras on screen | 02/26/2021 | ||
| WO Trk Scr | Camera | CM/PM | 09/14/2021 | Standard Corrective Maint | Camera operating normal. Truck screening cannot move camera from location onlt from command center. Complete | 09/20/2021 | ||
| WO Trk Scr | Gate | CM/PM | 10/27/2021 | Standard Corrective Maint | Tested gate operators and found multiple problems on three units. Will contact Concentric to come and give estimate to repair. Emailed Amanda from Concentric with list of opener issues. |
11/1/21 Waiting on answer from Amanda regarding requirements to have techs come out.
| WO Trk Scr | Monitor | CM/PM | 03/18/2021 | Standard Corrective Maint | Installed monitor and tested. | 03/18/2021 |
| WO Trk Scr | Monitor | CM/PM | 09/06/2021 | Standard Corrective Maint | HP mini computer for camera video gone bad. Sent email to PM Tommy Worth for quote from Chesapeake for new Bosch video jet. |
10/29/21 Will perform equment check on 11/1/21 to determine if unit still down.
Could not verify. Both Bosch monitors up and running 11/2/2021 -Jamel 11/02/2021