4 AUGUST AMMENDMENT_2ND FLOOR LIFE SAFETY PLAN A32L02001G103-G103.pdf
PDF 425 KB Posted
- Attached to
- USCG - JANITORIAL SERVICES - BASE NEW ORLEANS
- Solicitation number
- 70Z08426QAA850800
About this file
This document is a Second Floor Life Safety Plan architectural drawing for a U.S. Coast Guard Facilities Design & Construction Center project located in New Orleans, Louisiana. The plan shows the layout of a multi-tenant facility with detailed room dimensions, exit capacities, and life safety compliance information.
The drawing indicates a second floor occupancy load of 343 people and specifies exit capacity requirements using both NFPA and IBC (International Building Code) standards. Multiple exit routes are defined with specific travel distances (ranging from 92 feet to 221 feet) and door/stair exit capacities calculated using both NFPA and IBC formulas. The plan identifies required exit capacity for various zones, including 24 people, 147 people, and 148 people for different sections. Life safety features marked on the plan include illuminated exit signs, fire extinguishers (F.E.), 1-hour rated partitions, and 1/2-hour rated partitions per code. The drawing references Sheet G101 for additional code data and was prepared by BROADMOOR/BOH BROS. The plan is drawn to a scale of 3/32" = 1'-0" and is dated 1/23/09, with the project number listed as 32-D2001 and drawing number G103 (Sheet 5 of 40).
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
260 SQ. FT. 245 SQ. FT. 245 SQ. FT. 245 SQ. FT. 245 SQ. FT. 241 SQ. FT. 245 SQ. FT. 244 SQ. FT. 245 SQ. FT. 244 SQ. FT. 269 SQ. FT.
392 SQ. FT.
270 SQ. FT. 274 SQ. FT.
SQ. FT.
392 SQ. FT.
1019 SQ. FT.
43 SQ. FT.
SQ. FT.
259 SQ. FT. 264 SQ. FT.274 SQ. FT.
204 SQ. FT.
175 SQ. FT.
75 SQ. FT.
30 SQ. FT.
392 SQ. FT.
2377 SQ. FT.
109 SQ. FT.
109 SQ. FT.
109 SQ. FT.
115 SQ. FT.
96 SQ. FT.
SQ. FT.
148 SQ. FT. 280 SQ. FT.
280 SQ. FT.
147 SQ. FT. 318 SQ. FT.
105 SQ. FT.
143 SQ. FT.
105 SQ. FT.
1235 SQ. FT.
24 SQ. FT.
1172 SQ. FT.
1994 SQ. FT.
109 SQ. FT. 111 SQ. FT. 120 SQ. FT.
1044 SQ. FT.
402 SQ. FT.
138 SQ. FT. 135 SQ. FT. 251 SQ. FT. 163 SQ. FT. 96 SQ. FT.
2402 SQ. FT.
113 SQ. FT.108 SQ. FT.91 SQ. FT.115 SQ. FT.113 SQ. FT.161 SQ. FT.106 SQ. FT.159 SQ. FT.159 SQ. FT.106 SQ. FT.313 SQ. FT.163 SQ. FT.253 SQ. FT. 106 SQ. FT. 106 SQ. FT. 113 SQ. FT.
609 SQ. FT.
108 SQ. FT.
702 SQ. FT.
629 SQ. FT.300 SQ. FT.
1952 SQ. FT.
189 SQ. FT.189 SQ. FT.
276 SQ. FT.
575 SQ. FT.
57 SQ. FT.
1807 SQ. FT.
S
Q
F
T
31 SQ. FT.
1153 SQ. FT.
71 SQ. FT.
SQ. FT.
TRAVEL DISTANCE 143'-0"
EXIT DISTANCE 190'-0"
EXIT DISTANCE 204'-6"
T R
A V
E L
D
I S
T A
N C
E
TRAVEL DISTANCE 92'-0"
EXIT DISTANCE 178'-0"
EXIT DISTANCE 221'-0"
NFPA
STAIR EXIT CAPACITY
53/.3= 176 PEOPLE
IBC
STAIR EXIT CAPACITY
53/.2= 265 PEOPLE
NFPA
STAIR EXIT CAPACITY
56/.3= 186 PEOPLE
IBC
STAIR EXIT CAPACITY
56/.2= 280 PEOPLE
REQ'D. EXIT CAPACITY
24 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
NFPA
STAIR EXIT CAPACITY
53/.3= 176 PEOPLE
IBC
STAIR EXIT CAPACITY
53/.2= 265 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
NFPA
STAIR EXIT CAPACITY
56/.3= 186 PEOPLE
IBC
STAIR EXIT CAPACITY
56/.2 = 280 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
REQ'D. EXIT CAPACITY
148 PEOPLE
REQ'D. EXIT CAPACITY
147 PEOPLE
REQ'D. EXIT CAPACITY
24 PEOPLE
SECOND FLOOR OCCUPANY LOAD: 343
REFER TO SHEET G101 FOR ADDITIONAL CODE DATA
1 HR. RATED PARTITION
ILLUMINATED EXIT SIGN
RE: SPECIAL SYSTEMS PLAN
F.E.
FIRE EXTINGUISHER
PER CODE
1/2 HR. RATED PARTITION
30 SQ. FT.
File details come from the government source that posted it. Updated .