This document is a Second Floor Life Safety Plan architectural drawing for a U.S. Coast Guard Facilities Design & Construction Center project located in New Orleans, Louisiana. The plan shows the layout of a multi-tenant facility with detailed room dimensions, exit capacities, and life safety compliance information.

The drawing indicates a second floor occupancy load of 343 people and specifies exit capacity requirements using both NFPA and IBC (International Building Code) standards. Multiple exit routes are defined with specific travel distances (ranging from 92 feet to 221 feet) and door/stair exit capacities calculated using both NFPA and IBC formulas. The plan identifies required exit capacity for various zones, including 24 people, 147 people, and 148 people for different sections. Life safety features marked on the plan include illuminated exit signs, fire extinguishers (F.E.), 1-hour rated partitions, and 1/2-hour rated partitions per code. The drawing references Sheet G101 for additional code data and was prepared by BROADMOOR/BOH BROS. The plan is drawn to a scale of 3/32" = 1'-0" and is dated 1/23/09, with the project number listed as 32-D2001 and drawing number G103 (Sheet 5 of 40).

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

260 SQ. FT. 245 SQ. FT. 245 SQ. FT. 245 SQ. FT. 245 SQ. FT. 241 SQ. FT. 245 SQ. FT. 244 SQ. FT. 245 SQ. FT. 244 SQ. FT. 269 SQ. FT.

392 SQ. FT.

270 SQ. FT. 274 SQ. FT.

SQ. FT.

392 SQ. FT.

1019 SQ. FT.

43 SQ. FT.

SQ. FT.

259 SQ. FT. 264 SQ. FT.274 SQ. FT.

204 SQ. FT.

175 SQ. FT.

75 SQ. FT.

30 SQ. FT.

392 SQ. FT.

2377 SQ. FT.

109 SQ. FT.

109 SQ. FT.

109 SQ. FT.

115 SQ. FT.

96 SQ. FT.

SQ. FT.

148 SQ. FT. 280 SQ. FT.

280 SQ. FT.

147 SQ. FT. 318 SQ. FT.

105 SQ. FT.

143 SQ. FT.

105 SQ. FT.

1235 SQ. FT.

24 SQ. FT.

1172 SQ. FT.

1994 SQ. FT.

109 SQ. FT. 111 SQ. FT. 120 SQ. FT.

1044 SQ. FT.

402 SQ. FT.

138 SQ. FT. 135 SQ. FT. 251 SQ. FT. 163 SQ. FT. 96 SQ. FT.

2402 SQ. FT.

113 SQ. FT.108 SQ. FT.91 SQ. FT.115 SQ. FT.113 SQ. FT.161 SQ. FT.106 SQ. FT.159 SQ. FT.159 SQ. FT.106 SQ. FT.313 SQ. FT.163 SQ. FT.253 SQ. FT. 106 SQ. FT. 106 SQ. FT. 113 SQ. FT.

609 SQ. FT.

108 SQ. FT.

702 SQ. FT.

629 SQ. FT.300 SQ. FT.

1952 SQ. FT.

189 SQ. FT.189 SQ. FT.

276 SQ. FT.

575 SQ. FT.

57 SQ. FT.

1807 SQ. FT.

S

Q

F

T

31 SQ. FT.

1153 SQ. FT.

71 SQ. FT.

SQ. FT.

TRAVEL DISTANCE 143'-0"

EXIT DISTANCE 190'-0"

EXIT DISTANCE 204'-6"

T R

A V

E L

D

I S

T A

N C

E

TRAVEL DISTANCE 92'-0"

EXIT DISTANCE 178'-0"

EXIT DISTANCE 221'-0"

NFPA

STAIR EXIT CAPACITY

53/.3= 176 PEOPLE

IBC

STAIR EXIT CAPACITY

53/.2= 265 PEOPLE

NFPA

STAIR EXIT CAPACITY

56/.3= 186 PEOPLE

IBC

STAIR EXIT CAPACITY

56/.2= 280 PEOPLE

REQ'D. EXIT CAPACITY

24 PEOPLE

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

NFPA

STAIR EXIT CAPACITY

53/.3= 176 PEOPLE

IBC

STAIR EXIT CAPACITY

53/.2= 265 PEOPLE

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

NFPA

STAIR EXIT CAPACITY

56/.3= 186 PEOPLE

IBC

STAIR EXIT CAPACITY

56/.2 = 280 PEOPLE

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

REQ'D. EXIT CAPACITY

148 PEOPLE

REQ'D. EXIT CAPACITY

147 PEOPLE

REQ'D. EXIT CAPACITY

24 PEOPLE

SECOND FLOOR OCCUPANY LOAD: 343

REFER TO SHEET G101 FOR ADDITIONAL CODE DATA

1 HR. RATED PARTITION

ILLUMINATED EXIT SIGN

RE: SPECIAL SYSTEMS PLAN

F.E.

FIRE EXTINGUISHER

PER CODE

1/2 HR. RATED PARTITION

30 SQ. FT.