This is a First Floor Life Safety Plan for the U.S. Coast Guard Integrated Support Command New Orleans facility located at 2701 Loyola Drive, Metairie, Louisiana 70002. The document is an architectural drawing (Sheet G102 of 405) dated 1/23/09 prepared by Broadmoor/Boh Bros., a joint venture design firm.

The plan details occupancy loads, exit capacities, and egress routes throughout the first floor of the facility. The first floor has a total occupancy load of 624 people, with specific areas designated by occupant load ratios (1/15, 1/30, 1/50, 1/100, 1/200, and 1/300 depending on space use) ranging from 2 to 239 people per area. Exit capacity calculations are provided for both International Building Code (IBC) and NFPA standards, with door exits calculated at .15 or .2 square feet per person and stair exits at .2 or .3 square feet per person. The plan identifies the main entrance/exit with a capacity of 260 people serving an assembly occupancy load of 120. Fire safety elements include illuminated exit signs, wall-mounted and portable fire extinguishers positioned throughout the floor, 1-hour and 1/2-hour rated partitions, and multiple exit routes with documented exit distances ranging from 56 feet 6 inches to 141 feet 6 inches to ensure compliance with life safety codes.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SQ. FT.

395 SQ. FT.

1741 SQ. FT.

18 SQ. FT.

1736 SQ. FT.

321 SQ. FT.

552 SQ. FT.

125 SQ. FT.

2497 SQ. FT.

SQ. FT.

SQ. FT.

102 SQ. FT.

SQ. FT.

129 SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

81 SQ. FT.

20 SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

2452 SQ. FT.

595 SQ. FT.

541 SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

SQ. FT.

99 SQ. FT.

228 SQ. FT.

SQ. FT.

596 SQ. FT.

114 SQ. FT.

110 SQ. FT.

68 SQ. FT.

283 SQ. FT.

97 SQ. FT.

104 SQ. FT.

131 SQ. FT.

91 SQ. FT.

168 SQ. FT.

392 SQ. FT.

102 SQ. FT.

94 SQ. FT.

94 SQ. FT.

SQ. FT.

SQ. FT.

148 SQ. FT.

172 SQ. FT.

SQ. FT.

124 SQ. FT. 124 SQ. FT. 124 SQ. FT.

123 SQ. FT.

SQ. FT.

SQ. FT.

143 SQ. FT.

398 SQ. FT.

316 SQ. FT.

SQ. FT.

174 SQ. FT.

75 SQ. FT.

29 SQ. FT.

57 SQ. FT.

60 SQ. FT.

42 SQ. FT.

127 SQ. FT.

91 SQ. FT.

170 SQ. FT.

363 SQ. FT.

123 SQ. FT.

312 SQ. FT.

243 SQ. FT.

372 SQ. FT.

SQ. FT.

SQ. FT.

90 SQ. FT.

117 SQ. FT.

120 SQ. FT.

120 SQ. FT.

118 SQ. FT.

SQ. FT.

148 SQ. FT.

SQ. FT.

SQ. FT.

NFPA

STAIR EXIT CAPACITY

56/.3= 186 PEOPLE

52 SQ. FT.

DOOR EXIT CAPACITY

68/.15 = 453 PEOPLE

FIRST FLOOR OCCUPANY LOAD: 624

REFER TO SHEET G101 FOR ADDITIONAL CODE DATA

1 HR. RATED PARTITION

EXIT DISTANCE 91'-0"EXIT DISTANCE 126'-0"

EXIT DISTANCE

56'-6"

EXIT DISTANCE 141'-6"

EXIT DISTANCE

79'-0"

E X

I T

D

I S

T A

N C

E

EXIT DISTANCE 102'-6"

EXIT DISTANCE 87'-6"

EXIT DISTANCE124'-6"

875.0

SQ. FT.

645 SQ. FT.

812 SQ. FT.

565 SQ. FT.

535.0

SQ. FT.

526.0

SQ. FT.

SQ. FT.

682 SQ.

FT.

57 SQ.

FT.

SQ. FT.

ILLUMINATED EXIT SIGN

RE: LIGHTING PLAN/ E101

F.E.

FIRE EXTINGUISHER

PER CODE

IBC

DOOR EXIT CAPACITY

68/.2 = 340 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

68/.15 = 453 PEOPLE

IBC

DOOR EXIT CAPACITY

68/.2 = 340 PEOPLE

NFPA

IBC

IBC

STAIR EXIT CAPACITY

56/.2 = 280 PEOPLE

NFPA

STAIR EXIT CAPACITY

56/.3= 186 PEOPLE

IBC

STAIR EXIT CAPACITY

56/.2 = 280 PEOPLE

NFPA

STAIR EXIT CAPACITY

53/.3= 176 PEOPLE

IBC

STAIR EXIT CAPACITY

53/.2= 265 PEOPLE

NFPA

STAIR EXIT CAPACITY

53/.3= 176 PEOPLE

IBC

STAIR EXIT CAPACITY

53/.2= 265 PEOPLE

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

68/.15 = 453 PEOPLE

IBC

DOOR EXIT CAPACITY

68/.2 = 340 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

IBC

DOOR EXIT CAPACITY

34/.2 = 170 PEOPLE

NFPA

DOOR EXIT CAPACITY

68/.15 = 453 PEOPLE

IBC

DOOR EXIT CAPACITY

68/.2 = 340 PEOPLE

NFPA

DOOR EXIT CAPACITY

68/.15 = 453 PEOPLE

IBC

DOOR EXIT CAPACITY

68/.2 = 340 PEOPLE

NFPA

SQ. FT.

OCCUPANT LOAD 1/15

239 PEOPLE

OCCUPANT LOAD 1/200

12 PEOPLE

MAIN ENTRANCE / EXIT

ASSEMBLY OCCUPANT LOAD = 120

MAIN ENTRANCE / EXIT CAPACITY =260

OCCUPANT LOAD 1/50

35 PEOPLE

OCCUPANT LOAD 1/30

58 PEOPLE

OCCUPANT LOAD 1/300

2 PEOPLE

DOOR EXIT CAPACITY

68/.15 = 453 PEOPLE

IBC

DOOR EXIT CAPACITY

68/.2 = 340 PEOPLE

NFPA

SQ. FT.

SQ. FT.

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

DOOR EXIT CAPACITY

34/.15 = 226 PEOPLE

1/2 HR. RATED PARTITION

REQ'D. EXIT CAPACITY

30 PEOPLE

REQ'D. EXIT CAPACITY

12 PEOPLE

REQ'D. EXIT CAPACITY

120 PEOPLE

REQ'D. EXIT CAPACITY

120 PEOPLE

REQ'D. EXIT CAPACITY

35 PEOPLE

REQ'D. EXIT CAPACITY

34 PEOPLE

REQ'D. EXIT CAPACITY

65 PEOPLE

REQ'D. EXIT CAPACITY

30 PEOPLE

WALL MOUNTED FIRE

EXTINGUISHER

OCCUPANT LOAD 1/100

24 PEOPLE

REQ'D. EXIT CAPACITY

60 PEOPLE

310 SQ.

FT.