4 AUGUST AMMENDMENT_1ST FLOOR LIFE SAFETY PLAN A32L02001G102-G102.pdf
PDF 519 KB Posted
- Attached to
- USCG - JANITORIAL SERVICES - BASE NEW ORLEANS
- Solicitation number
- 70Z08426QAA850800
About this file
This is a First Floor Life Safety Plan for the U.S. Coast Guard Integrated Support Command New Orleans facility located at 2701 Loyola Drive, Metairie, Louisiana 70002. The document is an architectural drawing (Sheet G102 of 405) dated 1/23/09 prepared by Broadmoor/Boh Bros., a joint venture design firm.
The plan details occupancy loads, exit capacities, and egress routes throughout the first floor of the facility. The first floor has a total occupancy load of 624 people, with specific areas designated by occupant load ratios (1/15, 1/30, 1/50, 1/100, 1/200, and 1/300 depending on space use) ranging from 2 to 239 people per area. Exit capacity calculations are provided for both International Building Code (IBC) and NFPA standards, with door exits calculated at .15 or .2 square feet per person and stair exits at .2 or .3 square feet per person. The plan identifies the main entrance/exit with a capacity of 260 people serving an assembly occupancy load of 120. Fire safety elements include illuminated exit signs, wall-mounted and portable fire extinguishers positioned throughout the floor, 1-hour and 1/2-hour rated partitions, and multiple exit routes with documented exit distances ranging from 56 feet 6 inches to 141 feet 6 inches to ensure compliance with life safety codes.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SQ. FT.
395 SQ. FT.
1741 SQ. FT.
18 SQ. FT.
1736 SQ. FT.
321 SQ. FT.
552 SQ. FT.
125 SQ. FT.
2497 SQ. FT.
SQ. FT.
SQ. FT.
102 SQ. FT.
SQ. FT.
129 SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
81 SQ. FT.
20 SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
2452 SQ. FT.
595 SQ. FT.
541 SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
99 SQ. FT.
228 SQ. FT.
SQ. FT.
596 SQ. FT.
114 SQ. FT.
110 SQ. FT.
68 SQ. FT.
283 SQ. FT.
97 SQ. FT.
104 SQ. FT.
131 SQ. FT.
91 SQ. FT.
168 SQ. FT.
392 SQ. FT.
102 SQ. FT.
94 SQ. FT.
94 SQ. FT.
SQ. FT.
SQ. FT.
148 SQ. FT.
172 SQ. FT.
SQ. FT.
124 SQ. FT. 124 SQ. FT. 124 SQ. FT.
123 SQ. FT.
SQ. FT.
SQ. FT.
143 SQ. FT.
398 SQ. FT.
316 SQ. FT.
SQ. FT.
174 SQ. FT.
75 SQ. FT.
29 SQ. FT.
57 SQ. FT.
60 SQ. FT.
42 SQ. FT.
127 SQ. FT.
91 SQ. FT.
170 SQ. FT.
363 SQ. FT.
123 SQ. FT.
312 SQ. FT.
243 SQ. FT.
372 SQ. FT.
SQ. FT.
SQ. FT.
90 SQ. FT.
117 SQ. FT.
120 SQ. FT.
120 SQ. FT.
118 SQ. FT.
SQ. FT.
148 SQ. FT.
SQ. FT.
SQ. FT.
NFPA
STAIR EXIT CAPACITY
56/.3= 186 PEOPLE
52 SQ. FT.
DOOR EXIT CAPACITY
68/.15 = 453 PEOPLE
FIRST FLOOR OCCUPANY LOAD: 624
REFER TO SHEET G101 FOR ADDITIONAL CODE DATA
1 HR. RATED PARTITION
EXIT DISTANCE 91'-0"EXIT DISTANCE 126'-0"
EXIT DISTANCE
56'-6"
EXIT DISTANCE 141'-6"
EXIT DISTANCE
79'-0"
E X
I T
D
I S
T A
N C
E
EXIT DISTANCE 102'-6"
EXIT DISTANCE 87'-6"
EXIT DISTANCE124'-6"
875.0
SQ. FT.
645 SQ. FT.
812 SQ. FT.
565 SQ. FT.
535.0
SQ. FT.
526.0
SQ. FT.
SQ. FT.
682 SQ.
FT.
57 SQ.
FT.
SQ. FT.
ILLUMINATED EXIT SIGN
RE: LIGHTING PLAN/ E101
F.E.
FIRE EXTINGUISHER
PER CODE
IBC
DOOR EXIT CAPACITY
68/.2 = 340 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
68/.15 = 453 PEOPLE
IBC
DOOR EXIT CAPACITY
68/.2 = 340 PEOPLE
NFPA
IBC
IBC
STAIR EXIT CAPACITY
56/.2 = 280 PEOPLE
NFPA
STAIR EXIT CAPACITY
56/.3= 186 PEOPLE
IBC
STAIR EXIT CAPACITY
56/.2 = 280 PEOPLE
NFPA
STAIR EXIT CAPACITY
53/.3= 176 PEOPLE
IBC
STAIR EXIT CAPACITY
53/.2= 265 PEOPLE
NFPA
STAIR EXIT CAPACITY
53/.3= 176 PEOPLE
IBC
STAIR EXIT CAPACITY
53/.2= 265 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
68/.15 = 453 PEOPLE
IBC
DOOR EXIT CAPACITY
68/.2 = 340 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
68/.15 = 453 PEOPLE
IBC
DOOR EXIT CAPACITY
68/.2 = 340 PEOPLE
NFPA
DOOR EXIT CAPACITY
68/.15 = 453 PEOPLE
IBC
DOOR EXIT CAPACITY
68/.2 = 340 PEOPLE
NFPA
SQ. FT.
OCCUPANT LOAD 1/15
239 PEOPLE
OCCUPANT LOAD 1/200
12 PEOPLE
MAIN ENTRANCE / EXIT
ASSEMBLY OCCUPANT LOAD = 120
MAIN ENTRANCE / EXIT CAPACITY =260
OCCUPANT LOAD 1/50
35 PEOPLE
OCCUPANT LOAD 1/30
58 PEOPLE
OCCUPANT LOAD 1/300
2 PEOPLE
DOOR EXIT CAPACITY
68/.15 = 453 PEOPLE
IBC
DOOR EXIT CAPACITY
68/.2 = 340 PEOPLE
NFPA
SQ. FT.
SQ. FT.
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
1/2 HR. RATED PARTITION
REQ'D. EXIT CAPACITY
30 PEOPLE
REQ'D. EXIT CAPACITY
12 PEOPLE
REQ'D. EXIT CAPACITY
120 PEOPLE
REQ'D. EXIT CAPACITY
120 PEOPLE
REQ'D. EXIT CAPACITY
35 PEOPLE
REQ'D. EXIT CAPACITY
34 PEOPLE
REQ'D. EXIT CAPACITY
65 PEOPLE
REQ'D. EXIT CAPACITY
30 PEOPLE
WALL MOUNTED FIRE
EXTINGUISHER
OCCUPANT LOAD 1/100
24 PEOPLE
REQ'D. EXIT CAPACITY
60 PEOPLE
310 SQ.
FT.