Questions_FirePanel_70Z08425QDL950035.pdf

PDF 78 KB Posted

Attached to
Fire Alarm Panel at USCG STA Milford Haven
Solicitation number
70Z08425QDL950035
Issued by

About this file

This document appears to be a set of questions and answers regarding a fire alarm system replacement project for the U.S. Coast Guard Station Milford Haven. The current system is a Gamewell by Honeywell fire alarm system that has been updated multiple times in the last 8-10 years. The proposed replacement involves a one-for-one replacement of all system components, including sensors, pull stations, horns/strobes, panel, and wiring, with a preference to reduce from two sensors (grid ceiling and overhead) to a single multi-criteria sensor in the grid ceiling.

Key details include: the facility lacks a sprinkler system (except in the galley, which has a separate APC system), contractors must possess a valid RealID, and there are no as-built drawings available. The government is seeking clarification on whether a Mass Notification/Voice Evacuation system is required, with a preference for a system that can also function as a general PA system. The most recent inspection from 2024 did not show discrepancies, but the 2025 inspection was not completed due to alarm system issues. The project involves completely replacing the existing fire alarm infrastructure while maintaining the current device layout.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Inspection/Testing Records

a. The most recent inspection we have available is from 2024 and did not show discrepancies in the system, the 2025 inspection was not completed due to discrepancies in the alarm system.

b. There is no acceptance/commissioning paperwork available for the current system as it was done during a self-help install. To my knowledge during talks with CEU the system has been updated/changed twice in the last 8-10 years.

2. Building/System Drawing

a. I have included a facility layout drawing for reference. No other drawings are present.

b. The facility is not equipped with a sprinkler system. The galley is the only area which has a separate APC system.

3. Notification Appliances

a. All sensors are to be replaced as well as pull stations and horns/strobes. The current system utilizes a smoke or heat sensor in the grid ceiling as well as a smoke or heat sensor in the overhead. We would like to see that dropped to a single multi-criteria sensor in the grid ceiling with no sensors in the overhead.

4. Additional Reference

a. Any contractors utilized for work on premises must be in possession of a valid RealID.

5. Are any as-built drawings available for the existing fire alarm system at USCG Station Milford Haven ?Floor plan attached.

6. Could you please confirm the manufacturer of the existing fire alarm system.

Gamewell by Honeywell

7) Should we install devices per the existing layout (one-for-one replacements in current locations), or does the Government prefer a current code–compliant layout based on today’s NFPA/USCG criteria (which may shift quantities/locations after survey)?

one for one replacement of our current system. All components, sounding devices, sensors, panel, and wiring will be replaced.

8)Should notification appliances be replaced or reused? Is a Mass Notification / Voice Evacuation system required, or only a standard fire alarm system?

With the mass notification alarm, our question is, if it also acts a general PA system, then yes we want that. If it only voices emergencies then we want just the fire alarm sounding system.

9)Could you provide a copy of the 2024 fire alarm inspection report (or the most recent available)?

We will not provide the inspection report because we want the entire system replaced.