Question Responses_70Z08425QDL950035.pdf

PDF 3 MB Posted

Attached to
Fire Alarm Panel at USCG STA Milford Haven
Solicitation number
70Z08425QDL950035
Issued by

About this file

This document contains Question Responses for a fire alarm system upgrade at the U.S. Coast Guard Station Milford Haven. The responses detail current system conditions and replacement requirements, including that the existing Gamewell by Honeywell fire alarm system has been updated/changed twice in the last 8-10 years. The facility lacks a sprinkler system, with only the galley having a separate APC system. Key upgrade specifications include replacing all sensors, pull stations, horns, and strobes, with a preference to reduce from multiple sensors to a single multi-criteria sensor in the grid ceiling. Contractors performing work must possess a valid RealId. The most recent inspection from 2024 did not show system discrepancies, though the 2025 inspection was not completed due to alarm system issues. A facility layout drawing is included for reference, showing the floor plan of the building.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Inspection/Testing Records

a. The most recent inspection we have available is from 2024 and did not show discrepancies in the system, the 2025 inspection was not completed due to discrepancies in the alarm system.

b. There is no acceptance/commissioning paperwork available for the current system as it was done during a self-help install. To my knowledge during talks with CEU the system has been updated/changed twice in the last 8-10 years.

2. Building/System Drawing

a. I have included a facility layout drawing for reference. No other drawings are present.

b. The facility is not equipped with a sprinkler system. The galley is the only area which has a separate APC system.

3. Notification Appliances

a. All sensors are to be replaced as well as pull stations and horns/strobes. The current system utilizes a smoke or heat sensor in the grid ceiling as well as a smoke or heat sensor in the overhead. We would like to see that dropped to a single multi-criteria sensor in the grid ceiling with no sensors in the overhead.

4. Additional Reference

a. Any contractors utilized for work on premises must be in possession of a valid RealID.

5. Are any as-built drawings available for the existing fire alarm system at USCG Station Milford Haven ?Floor plan attached.

6. Could you please confirm the manufacturer of the existing fire alarm system.

Gamewell by Honeywell

Question Responses_70Z08425QDL950035

Blank Page

File details come from the government source that posted it. Updated .