The document is an STI SP001 AST (Aboveground Storage Tank) Record for Tank 8, completed by NW Tank Lining & Inspection, Inc. on June 26, 2018, for the US Coast Guard Air Station in Port Angeles, WA. The tank is a horizontal, rectangular, double-wall design manufactured by Hoover Containment Systems in September 2003, with a 1,000-gallon capacity for storing gasoline. Key technical specifications include a UL 2085 build standard, steel dike spill control, elevated steel supports, embedded bolt anchoring, and multiple venting systems including 2" and 6" vents from different manufacturers.

The tank features several safety and environmental protection elements, such as an inherent grounding type, a Morrison Bros. clock gauge for level detection, a guillotine valve for overfill prevention, and a concrete-filled secondary containment. The tank is categorized as a Category 1 AST with coated steel construction and an installation date matching its manufacturing date. While some historical information like original thickness and last repair date is marked as unknown, the record provides a comprehensive technical overview of the tank's design, infrastructure, and safety features.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STI SP001 AST Record

NW TANK LINING & INSPECTION, INC.

COMPLIANCE TESTING · INSPECTION SERVICES

ENVIRONMENTAL ENGINEERING · LININGS

INDUSTRIAL PROTECTIVE COATINGS · RESTORATION

1-888-TLC-TANK (852-8265)

FORM COMPLETED BY FACILITY INFORMATION

Name

Michael Driggs

Title

SP001 Inspector

Name

USCG Air Station/Sector Field Office

Regulatory ID Number

Company

NWTLI

Date

June 26, 2018

Address

Ediz Hook Rd, Port Angeles, WA 98362

OWNER INFORMATION INSTALLER INFORMATION

Name Name

Owners Tank ID Tank 8 Serial L-600389 Initial Service Date Unknown Other

Design: ■ UL 2085 ☐ SwRI ☐ Unknown ■ Nameplate / Tag

☐ API ☐ Other

■ Horizontal ☐ Vertical ■ Rectangular

MFG

Hoover Containment Systems, Inc.

Model

LP 1000 P

Date of MFG

September 2003

Last Repair Date

Unknown

Last Change Date

Unknown

Dimensions AST Category

■ Category 1

☐ Category 2

☐ Category 3

Original Thickness

Floor Unknown

Shell Unknown

Roof/Ends Unknown

Construction

☐ Bare Steel ☐ Cathodic Protection; Install Date:

■ Coated Steel ⤷(☐ Galvanic or ☐ Impressed)

☐ Double-Bottom ☐ Concrete Encased Steel

■ Double-Wall ☐ Lined Inside; Date of Lining:

☐ Stainless Steel ☐ Bare Steel

■ Other: Concrete Filled Secondary

Capacity

1,000 gallons

Contents

Gasoline

Spill Control

☐ Earthen Dike ■ Steel Dike

☐ Concrete ☐ None

■ Other: Outerwall

Tank Supports

■ Elevated Supports

■ Steel ☐ Concrete

☐ Other:

Release Prevention Barrier

☐ Concrete ☐ Syn Liner

☐ Clay Liner ■ Steel

☐ None

☐ Other:

■ Install Date: Date of MFG

Continual Release Detection Method

☐ Release Prevention Barrier

☐ Elevated Tank

☐ Double-Bottom Tank

■ Double-Wall Tank

☐ CE-AST

☐ Other:

Anchoring Type

Embedded bolts into concrete slab through MFG`d feet

Grounding Type

Inherently

Primary Venting

Method

2” Pipe with PV Vent Cap

Primary E-Venting

Method

6” Clay & Bailey E-Vent

Secondary Venting

Method

None

Secondary E-Venting

Method

6” Morrison Bros . E-Vent

Vehicular Protection

Method

UL2085 Build Standard

Method of Level Detection

Method

Morrison Bros. Clock Gauge

Overfill Prevention

Method

Guillotine Valve

Notes: