1 Ediz Hook Rd Port Angeles WA Inspection Record Tank 8 FOR REFERENCE.pdf
PDF 95 KB Posted
- Attached to
- 1000-gallon Fuel Tank Replacement
- Solicitation number
- 70Z03325Q201900002
About this file
The document is an STI SP001 AST (Aboveground Storage Tank) Record for Tank 8, completed by NW Tank Lining & Inspection, Inc. on June 26, 2018, for the US Coast Guard Air Station in Port Angeles, WA. The tank is a horizontal, rectangular, double-wall design manufactured by Hoover Containment Systems in September 2003, with a 1,000-gallon capacity for storing gasoline. Key technical specifications include a UL 2085 build standard, steel dike spill control, elevated steel supports, embedded bolt anchoring, and multiple venting systems including 2" and 6" vents from different manufacturers.
The tank features several safety and environmental protection elements, such as an inherent grounding type, a Morrison Bros. clock gauge for level detection, a guillotine valve for overfill prevention, and a concrete-filled secondary containment. The tank is categorized as a Category 1 AST with coated steel construction and an installation date matching its manufacturing date. While some historical information like original thickness and last repair date is marked as unknown, the record provides a comprehensive technical overview of the tank's design, infrastructure, and safety features.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STI SP001 AST Record
NW TANK LINING & INSPECTION, INC.
COMPLIANCE TESTING · INSPECTION SERVICES
ENVIRONMENTAL ENGINEERING · LININGS
INDUSTRIAL PROTECTIVE COATINGS · RESTORATION
1-888-TLC-TANK (852-8265)
FORM COMPLETED BY FACILITY INFORMATION
Name
Michael Driggs
Title
SP001 Inspector
Name
USCG Air Station/Sector Field Office
Regulatory ID Number
Company
NWTLI
Date
June 26, 2018
Address
Ediz Hook Rd, Port Angeles, WA 98362
OWNER INFORMATION INSTALLER INFORMATION
Name Name
Owners Tank ID Tank 8 Serial L-600389 Initial Service Date Unknown Other
Design: ■ UL 2085 ☐ SwRI ☐ Unknown ■ Nameplate / Tag
☐ API ☐ Other
■ Horizontal ☐ Vertical ■ Rectangular
MFG
Hoover Containment Systems, Inc.
Model
LP 1000 P
Date of MFG
September 2003
Last Repair Date
Unknown
Last Change Date
Unknown
Dimensions AST Category
■ Category 1
☐ Category 2
☐ Category 3
Original Thickness
Floor Unknown
Shell Unknown
Roof/Ends Unknown
Construction
☐ Bare Steel ☐ Cathodic Protection; Install Date:
■ Coated Steel ⤷(☐ Galvanic or ☐ Impressed)
☐ Double-Bottom ☐ Concrete Encased Steel
■ Double-Wall ☐ Lined Inside; Date of Lining:
☐ Stainless Steel ☐ Bare Steel
■ Other: Concrete Filled Secondary
Capacity
1,000 gallons
Contents
Gasoline
Spill Control
☐ Earthen Dike ■ Steel Dike
☐ Concrete ☐ None
■ Other: Outerwall
Tank Supports
■ Elevated Supports
■ Steel ☐ Concrete
☐ Other:
Release Prevention Barrier
☐ Concrete ☐ Syn Liner
☐ Clay Liner ■ Steel
☐ None
☐ Other:
■ Install Date: Date of MFG
Continual Release Detection Method
☐ Release Prevention Barrier
☐ Elevated Tank
☐ Double-Bottom Tank
■ Double-Wall Tank
☐ CE-AST
☐ Other:
Anchoring Type
Embedded bolts into concrete slab through MFG`d feet
Grounding Type
Inherently
Primary Venting
Method
2” Pipe with PV Vent Cap
Primary E-Venting
Method
6” Clay & Bailey E-Vent
Secondary Venting
Method
None
Secondary E-Venting
Method
6” Morrison Bros . E-Vent
Vehicular Protection
Method
UL2085 Build Standard
Method of Level Detection
Method
Morrison Bros. Clock Gauge
Overfill Prevention
Method
Guillotine Valve
Notes:
File details come from the government source that posted it. Updated .