This document is a Questions and Answers (Q&A) file for a federal contract (Solicitation Number 70LCHS25QPFB00041) related to Building 64 Retro-Commissioning. The Q&A addresses three specific technical inquiries about the Statement of Work (SOW), focusing on certification requirements, work responsibilities, and control systems for chiller plant equipment.

Key details include: (1) The government will not consider alternative certifications like BCxP in lieu of the CxA requirement, (2) The CxA certification is required for lead/supervisory roles, and (3) Chiller plant equipment will be controlled by the chiller manufacturer's factory controls, with the Automated Logic Controls (ALC) system managing start/stop and status functions. Programming changes for the Automated Logic System will be made by FLETC (Federal Law Enforcement Training Center), not the retro-commissioning provider.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

70LCHS25QPFB00041 Bldg 64 Retro-Commissioning Questions 0001

1. Regarding 10.1.14 of the updated SOW, will the government consider equivalent certifications such as BCxP and years of experience in lieu of CxA requirement?

No

2. Does the government intend all work to be completed by CxA or is that requirement strictly for discipline lead/supervisor? Lead/ Supervisory

2. Section 10.1.8 - Is the intent that the retro-commissioning provider actually makes the recommended/COR approved programming changes to the Automated Logic System, or will the actual programming be performed by the local Automated Logic branch/representative and then desired functionality verified by the retro-commissioning provider? If programming is to be by retro-commissioning provider, will the Automated Logic System access referred to in Section 10.1.10 include programming rights?

Recommended changes that will be made by FLETC

3. Section 10.1.9 - Is Chiller Plant equipment (Chillers, Pumps) controlled by the Chiller manufacturer's packaged/factory controls, or by the Automated Logic System?

Chiller controlled factory controls. ALC controls start stop, status etc