This is an electrical bid set document for the Pierce County Library System's construction of a new Sumner Library facility located at 15126 Main Street East, Sumner, Washington. The project encompasses electrical systems design and installation for a 17,133 square-foot library building on a 73,573 square-foot parcel. The electrical scope includes power distribution, lighting systems, communications infrastructure, fire alarm systems, and electric vehicle charging stations. The bid set specifies the provision of new electrical and telecom services, parking and exterior area lighting, and EV charging infrastructure. Key electrical components include a 1,000-ampere main switchboard (MDP) with 208Y/120V, 3-phase, 4-wire service rated at 22 kAIC; multiple distribution panels (Lighting, Emergency Lighting, Plug Loads, Mechanical, Telecom, and EV); and integrated lighting and receptacle control systems with BACNET and Modbus TCP integration for energy monitoring. The electrical design incorporates a 12-kilowatt photovoltaic array to meet on-site renewable energy code requirements, with additional roof area reserved for future solar expansion per energy code solar readiness provisions.
The document establishes detailed electrical requirements in accordance with the 2023 National Electrical Code (NEC), the International Building Code (IBC), and Washington State adopted fire codes. All conduit work specifies minimum 3/4-inch conduit with #12 AWG conductors unless otherwise noted, with dedicated neutral conductors and properly sized equipment grounding conductors. The specifications require tamper-resistant receptacles for all 15-ampere and 20-ampere receptacles accessible to the public, compliance with arc flash safety requirements, and functional testing procedures for all automatic lighting controls. The design incorporates manual dimming controls allowing at least 50-percent illumination reduction in occupied spaces, occupancy sensor integration with emergency egress lighting, and programmable time switches controlling a maximum 2,500 square-foot area per switch. The project timeline shows a bid set issue date of March 25, 2026, with drawings prepared by Johnston Architects, LLC in Seattle, Washington, and the work is to be performed under the supervision of the Pierce County Library System.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. SYMBOLS LEGENDS ARE PROVIDED FOR REFERENCE PURPOSES ONLY. THE SYMBOLS REPRESENT THE TYPE OF DEVICES THAT MAY BE REQUIRED IN THE WORK; QUANTITIES AND LOCATIONS ARE AS SHOWN ON THE PLAN
SHEETS.
2. PROVIDE 3/4" CONDUIT & #12 CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH UNGROUNDED CONDUCTOR OF SINGLE PHASE LINE-NEUTRAL BRANCH CIRCUITS. DO NOT SHARE
NEUTRAL CONDUCTORS.
3. EACH FEEDER AND BRANCH CIRCUIT CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED IN
ACCORDANCE WITH NFPA 70, ARTICLE 250.
4. THE FOLLOWING IS PART OF THIS PROJECT AND ALL COSTS PERTAINING THERETO SHALL BE INCLUDED IN THE
BASE BID:
A. NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE
EXISTING SYSTEM AS REQUIRED.
B. POWER WIRING AND CABLE INSTALLATIONS SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS AND IN WALLS. EXPOSED WIRING SHALL BE INSTALLED IN APPROVED SURFACE METAL RACEWAY WHERE INDICATED.
C. LOCATIONS OF ALL WALL MOUNTED DEVICES SUCH AS SWITCHES, RECEPTACLES, AND OUTLETS ARE SHOWN
CASEWORK, DOORS AND RELITES.
D. PROVIDE PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS AS REQUIRED. PROVIDE SUITABLE FIRE RATED MATERIALS AND SEAL ALL CEILING, FLOOR, AND WALL PENETRATIONS TO MATCH FIRE RATING OF
SURFACES PENETRATED.
GENERAL NOTES
1. LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS ZONED ON THE LIGHTING PLANS. SWITCHING AND
DIMMING ZONES ARE INDICATED ADJACENT TO EACH FIXTURE.
2. MANUAL CONTROLS SHALL ALLOW OCCUPANTS TO UNIFORMLY REDUCE ILLUMINATION LEVELS AT LEAST 50%.
EXCEPTION: CORRIDORS, RESTROOMS, LOBBIES, MECHANICAL, ELECTRICAL, AND TELECOM ROOMS.
3. EACH AREA THAT IS REQUIRED TO HAVE A MANUAL CONTROL SHALL ALSO HAVE AUTOMATIC TIME SWITCH CONTROL. PROVIDE TIMED OVERRIDE SWITCHES THAT WILL SERVE A MAXIMUM AREA OF 2500 SF IN LOCATIONS
SHOWN ON PLANS. EXCEPTIONS:
A. EMERGENCY EGRESS LIGHTING CONTROLLED BY OCCUPANCY SENSORS.
B. LIGHTING IN SPACES CONTROLLED BY OCCUPANCY SENSORS.
4. LUMINAIRES PROVIDING MEANS OF EGRESS ILLUMINATION AND HAVING BOTH NORMAL AND EMERGENCY POWER SOURCES SHALL BE CONTROLLED BY A COMBINATION OF U.L. 924 LISTED EMERGENCY RELAYS AND OCCUPANCY SENSORS THAT ENABLES THE LIGHTING TO BE SHUT OFF WHEN THE AREAS SERVED ARE UNOCCUPIED AND AUTOMATICALLY ILLUMINATES IN THE EVENT OF NORMAL POWER SOURCE FAILURE OR ACTIVATION OF THE FIRE
ALARM SYSTEM.
5. THE MAXIMUM LIGHTING POWER THAT MAY BE CONTROLLED FROM A SINGLE SWITCH OR AUTOMATIC CONTROL SHALL NOT EXCEED THAT WHICH IS PROVIDED BY A 20 AMPERE CIRCUIT LOADED TO NOT MORE THAN 80 PERCENT.
6. PROVIDE FUNCTIONAL TESTING OF AUTOMATIC LIGHTING CONTROLS. SUBMIT WRITTEN PROCEDURES FOR FUNCTIONAL TESTING OF ALL AUTOMATIC CONTROLS WITH DESCRIPTION OF THE EXPECTED SYSTEM RESPONSE.
7. AT LEAST HALF OF ALL RECEPTACLES IN OFFICES, CONFERENCE ROOMS, PRINT/COPY ROOMS, BREAKROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS SHALL HAVE A MEANS TO AUTOMATICALLY TURN OFF RECEPTACLE POWER AT SPECIFIC PROGRAMMED TIMES. RECEPTACLES SHALL NOT BE CONTROLLED BY VACANCY SENSORS. USER PROGRAMMING FUNCTONS SHALL BE INTEGRATED WITH THE LIGHTING CONTROL SYSTEM.
LIGHTING AND RECEPTACLE CONTROLS NOTES
@ AT
A/C AIR CONDITIONING(ER)
A (AMP) AMPERE
AC ABOVE COUNTER, ALTERNATING
CURRENT
ADJ ADJUSTABLE
ADJT ADJACENT
AF ARC FLASH ENERGY
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
ANN ANNUNCIATOR
ARCH ARCHITECT; ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BKBD BACKBOARD
BKR BREAKER
BLDG BUILDING
C CONDUIT
CAP CAPACITY
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CLR CLEAR
COL COLUMN
COM COMMUNICATION
CPS CYCLES PER SECOND
CT CURRENT TRANSFORMER
CTL CONTROL
CU COPPER
DC DIRECT CURRENT
DISC SW DISCONNECT SWITCH
DISC DISCONNECT
DN DOWN
DWG DRAWING
E EXISTING, EAST
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EGC EQUIPMENT GROUNDING CONDUCTOR
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENTR ENTRANCE
EP EXPLOSION PROOF
EPO EMERGENCY POWER OFF
EQUIP/EQP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXT EXTERIOR
EXIST EXISTING
F FAHRENHEIT/FUSE
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FAP FIRE ALARM PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FD FIRE DAMPER
FDR FEEDER
FIXT FIXTURE
FLA FULL LOAD AMPS
FSD FIRE/SMOKE DAMPER
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GFPE GROUND FAULT PROTECTION FOR EQUIPMENT
GFR GROUND FAULT RELAY
H HEIGHT
HOA HAND OFF AUTOMATIC
HOR HORIZONTAL
HP HORSEPOWER
HR HOUR
HT HEIGHT
HW HOT WATER
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
IC INTERCOM
IES ILLUMINATING ENGINEERING SOCIETY
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC
ENGINEERS
IFC INTERNALTIONAL FIRE CODE
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN INCH
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LBS POUNDS
LF LINEAR FEET
LRA LOCKED ROTOR AMPS
LS LIFE SAFETY
LT LIGHT
LTG LIGHTING
LV LOW VOLTAGE
ABBREVIATIONS
MAG MAGNETIC
MAN MANUAL
MAT MATERIAL
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MECH MECHANICAL
MEZZ MEZZANINE
MG MOTOR GENERATOR
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MS MAGNETIC STARTER
MTD MOUNTED
MTG MOUNTING
MTR MOTOR
N NORTH; NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NEUT NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOC.
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OL OVERLOAD
OS OPTIONAL STANDBY
P PRIMARY
PA PUBLIC ADDRESS
PAR PARALLEL
PB PULL BOX
PE PHOTO ELECTRIC
PF POWER FACTOR
PH PHASE
PIV POST INDICATOR VALVE
PNL PANEL
POC POINT OF CONNECTION
PWR POWER
QTY QUANTITY
R (R) RELOCATE (D)
RAD RADIUS
REC RECEPTACLE
REF REFRIGERATOR
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S SOUTH
SC SECURITY
SD SMOKE DETECTOR
SECT SECTION
SF SUPPLY FAN
SHT SHEET
SPEC SPECIFICATION
SPL SPECIAL
SQ SQUARE
STOR STORAGE
SPD SURGE PROTECTION DEVICE
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
T THERMOSTAT
TB TERMINAL BOX
TC TIME CLOCK
TEL TELEPHONE
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UV UNIT VENTILATOR
V VOLT
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VM VOLTMETER
VOL VOLUME
W WATT, WEST, WIRELESS
W/ WITH
W/O WITHOUT
WH WATER HEATER
WHM WATTHOUR METER
WP WEATHERPROOF
X REACTANCE
XFMR TRANSFORMER
XMTR TRANSMITTER
Z IMPEDANCE
PROVIDE ELECTRICAL SYSTEMS INCLUDING POWER, LIGHTING, COMMUNICATIONS, AND FIRE ALARM TO SERVE A
NEW 17,133 SF LIBRARY ON A VACANT LOT.
SITE DEVELOPMENT INCLUDES NEW ELECTRICAL AND TELECOM SERVICES, PARKING AND EXTERIOR AREA
LIGHTING, AND ELECTRIC VEHICLE CHARGING STATIONS.
REFER TO LIGHTING DESIGNER LT SHEETS AND CIVIL SITE PLAN C4.00 FOR ADDITIONAL LIGHTING AND SITE
ELECTRICAL RELATED WORK TO COMPLETE.
SCOPE OF WORK
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :3
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
GENERAL NOTES,
ABBREVIATIONS AND
SHEET INDEX
E0.00
CR
RG
ELECTRICAL SHEET INDEX
E0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
E0.01 ELECTRICAL LEGEND
E1.00 ELECTRICAL SCHEDULES
E2.00 ELECTRICAL SITE PLAN
E2.01 ELECTRICAL FLOOR PLAN
E2.02 ELECTRICAL LOW ROOF PLAN
E2.04 ELECTRICAL ROOF PLAN
E3.01 SYSTEMS FLOOR PLAN
E4.01 LIGHTING FLOOR PLAN
E5.01 DETAILS AND ENLARGED PLANS
E6.00 POWER ONE-LINE DIAGRAM
E8.00 PANEL SCHEDULES
E8.01 PANEL SCHEDULES
E8.02 PANEL SCHEDULES
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
REFER TO LT SERIES SHEETS FOR ADDITIONAL LIGHTING
RELATED INFORMATION INCLUDING LUMINAIRE
SCHEDULE AND ENERGY CODE COMPLIANCE FORMS
12/11/20252/26/20263/12/202602526262//
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
X-XX
N
DRAWING CONSTRUCTION ("FLAG") NOTE
EQUIPMENT IDENTIFIER
MATCHLINE
REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE
PREVIOUS RELEASE)
REVISION REFERENCE
EXISTING TO BE REMOVED (DASHED)
HEAVY LINEWEIGHT INDICATES NEW WORK
LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION
DETAIL REFERENCE
DETAIL IDENTIFICATION NUMBER
SHEET WHERE DETAIL IS DRAWN
ELEVATION REFERENCE
ELEVATION IDENTIFICATION
NUMBER SHEET WHERE ELEVATION IS DRAWN
SECTION REFERENCE SECTION
IDENTIFICATION NUMBER
SHEET WHERE SECTION IS DRAWN
NORTH REFERENCE
X
XX.XX
X
XX.XX
X
XX.XX
ACCESS PANEL
T
M
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
TRANSFORMER
DELTA
WYE
METER
SYMBOLS LEGEND - POWER
DESCRIPTION
CIRCUIT BREAKER
ST - INDICATES SHUNT TRIP
BREAKER WITH EXTERNAL GROUND FAULT RELAY AND CT
CIRCUIT BREAKER WITH INTEGRAL GROUND FAULT PROTECTION
CB
CB ENCLOSED CIRCUIT BREAKER (PLAN VIEW)
xxxA/xP - AMPS/POLESxxxA/xP
ENCLOSED CIRCUIT BREAKER (ONE-LINE DIAGRAM)
xxxA/xP - AMPS/POLES
G G
SYMBOL
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
M
M
SD
M
FSD
M
EQUIPMENT CONNECTION
MOTOR CONNECTION
SMOKE DAMPER
FIRE SMOKE DAMPER
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS
EQUIPMENT EMERGENCY SHUTDOWN SWITCH
3-POLE UNLESS NOTED OTHERWISE
3-POLE UNLESS NOTED OTHERWISE
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
CONDUIT CONCEALED IN CEILING SPACE OR IN WALL. PROVIDE MINIMUM
3/4" WITH #12 AWG CONDUCTORS AND DEDICATED NEUTRAL EACH
CIRCUIT UNLESS OTHERWISE NOTED ON PLAN. PROVIDE EQUIPMENT
GROUNDING CONDUCTORS SIZED PER NFPA 70.
CONDUIT - CONCEALED IN OR UNDER FLOOR
CONDUIT - ROUTED UNDERGROUND
LOW-VOLTAGE WIRING (CLASS B)
CONDUIT OR CABLE VERTICAL DOWN
CONDUIT OR CABLE VERTICAL UP
CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND
BREAK LINE
CONDUIT SEAL
EXPANSION FITTING
CONDUCTORS - CONNECTED
CONDUCTORS - NOT CONNECTED
JUNCTION BOX
PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE
HANDHOLE
MANHOLE
FLEXIBLE METAL CONDUIT
BRANCH CIRCUIT NUMBERS
PANEL DESIGNATION
HOME RUN TO SOURCE OF SUPPLY
PB
HH
MH
A-1,3,5
UG
LV
CABLE TRAY
J
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
XX
480Y/277V, 3Ø, 4W PANELBOARD
208Y/120V, 3Ø, 4W PANELBOARD
EQUIPMENT CABINET - TYPE AS NOTED
PANELBOARD
TRANSFER SWITCH ( AUTO )
AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL)
FEEDER TAG - REFER TO FEEDER SCHEDULE
XXXXXX
SYMBOLS LEGEND - GROUNDING
DESCRIPTIONSYMBOL
GROUND CONNECTION
GROUND ROD
SYMBOLS LEGEND - WIRING DEVICES
DESCRIPTIONSYMBOL
SPECIAL PURPOSE RECEPTACLE, NEMA TYPE AS SHOWN ON PLANS
FLUSH FLOOR POKE THRU WITH SPLIT-WIRED CONTROLLED/ NON-CONTROLLED
DUPLEX. REFER TO FLOOR PLANS FOR ADDITIOINAL DEVICES.
SIMPLEX RECEPTACLE NEMA 5-20R, WALL MTD AT +18" AFF UON
DUPLEX RECEPTACLE, NEMA 5-20R, WALL MTD AT +18" AFF UON
DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER, +18" AFF UON
DUPLEX WITH SPLIT WIRED CONTROLLED/ NON-CONTROLLED RECEPTACLE, +18" AFF
CONTROLLED DUPLEX RECEPTACLE OUTLET, WALL MTD AT +18" AFF UON
DUPLEX, QUAD; COORDINATE WITH ARCHITECTURAL ELEVATIONS, COUNTERTOP,
AND/OR CASEWORK FOR HEIGHT.
DUPLEX, QUAD WITH GROUND FAULT CIRCUIT INTERRUPTER, COORDINATE WITH
ARCHITECTURAL ELEVATIONS, COUNTERTOP, AND/OR CASEWORK FOR HEIGHT.
CEILING MOUNTED DUPLEX, QUAD RECEPTACLES, NEMA 5-20R
COMBINATION FLUSH MOUNTED FLOOR BOX WITH SPLIT-WIRED CONTROLLED/
NON-CONTROLLED DUPLEX. REFER TO FLOOR PLANS FOR ADDITIONAL DEVICES
QUAD (DOUBLE DUPLEX) NEMA 5-20R, WALL MTD AT +18" AFF UON
QUAD WITH ONE DUPLEX CONTROLLED, ONE DUPLEX NORMAL, +18" AFF UON
COMBINATION FLUSH MOUNTED FLOOR BOX WITH CONTROLLED QUAD OUTLET.
REFER TO FLOOR PLANS FOR ADDITIONAL DEVICES
COMBINATION FLUSH MOUNTED FLOOR BOX WITH ONE CONTROLLED DUPLEX AND
ONE NON-CONTROLLED DUPLEX. REFER TO FLOOR PLANS FOR ADDITIONAL DEVICES
FLUSH FLOOR POKE THRU WITH CONTROLLED DUPLEX
CEILING MOUNTED DUPLEX WITH SPLIT WIRED CONTROLLED/ NON-CONTROLLED
RECEPTACLE
CEILING MOUNTED QUAD; ONE CONTROLLED DUPLEX, ONE NON-CONTROLLED
DUPLEX
TWO SPLIT WIRED CONTROLLED/ NON-CONTROLLED DUPLEX RECEPTACLES IN A
DUAL GANG OUTLET BOX. COORDINATE WITH ARCHITECTURAL ELEVATIONS,
COUNTERTOP, AND/OR CASEWORK FOR HEIGHT AND POSITION.
TWO SPLIT WIRED CONTROLLED/ NON-CONTROLLED DUPLEX GFCI RECEPTACLES IN
A DUAL GANG OUTLET BOX. COORDINATE WITH ARCHITECTURAL ELEVATIONS,
COUNTERTOP, AND/OR CASEWORK FOR HEIGHT AND POSITION.
SPLIT / HALF CONTROLLED DUPLEX, WITH GFCI; COORDINATE W/ ARCHITECTURAL
ELEVATIONS, COUNTERTOP AND/OR CASEWORK FOR HEIGHT AND POSITION
SPLIT WIRED CONTROLLED/ NON-CONTROLLED DUPLEX RECEPTACLE. COORDINATE
WITH ARCHITECTURAL ELEVATIONS, COUNTERTOP, AND/OR CASEWORK FOR HEIGHT
AND POSITION.
COMBINATION FLUSH MOUNTED FLOOR BOX WITH CONTROLLED DUPLEX. REFER
TO FLOOR PLANS FOR ADDITIONAL DEVICES
SYMBOLS LEGEND - LIGHTING
DESCRIPTIONSYMBOL
L1 A - 1
Z-XXX-1
EM
LIGHT FIXTURE IDENTIFIER - REFER TO LUMINAIRE SCHEDULE
PANEL NAME - CIRCUIT NUMBER
SWITCH DESIGNATION - MIDDLE DIGITS REFER TO
ROOM NUMBER - END DIGITS REFER TO SWITCH LEG
SUBSCRIPT (IF APPLICABLE)
ILLUMINATED EXIT SIGN - SINGLE FACE ARROW INDICATES
DIRECTION OF EGRESS, UNIVERSAL MOUNT
ILLUMINATED EXIT SIGN - DOUBLE FACE ARROW INDICATES
DIRECTION OF EGRESS, UNIVERSAL MOUNT
BATTERY-POWERED EMERGENCY WALLPACK
COMBINATION BATTERY POWERED EMERGENCY WALLPACK
AND ILLUMINATED EXIT SIGN
SITE LIGHTING - YBI
SYMBOLS LEGEND - COMMUNICATIONS
DESCRIPTIONSYMBOL
WALL MOUNTED DATA DEVICE. MOUNT AT 18" AFF UNLESS OTHERWISE
NOTED. NUMBER INDICATES QUANTITY OF PORTS.
CEILING MOUNTED DATA DEVICE. COORDINATE WITH ARCHITECTURAL
CEILING PLANS. NUMBER INDICATES QUANTITY OF PORTS.
VIDEO PROJECTOR LOCATION. PROVIDE CABLING IN THE QUANTITY
INDICATED WITH 10'-0" SERVICE LOOP IN ACCESSIBLE CEILING SPACE.
MUD RING TO ACCOMMODATE PASS THROUGH FOR AUDIOVISUAL
CABLING. MOUNT AT 18" AFF UNLESS OTHERWISE NOTED. NUMBER
INDICATES NUMBER OF GANG SPACES.
DATA DEVICE MOUNTED IN FLOOR BOX. NUMBER INDICATES QUANTITY OF
PORTS. FLOOR BOX PROVIDED BY ELECTRICAL CONTRACTOR. SEE
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
VP
AP
CEILING MOUNTED INDOOR ACCESS POINT LOCATION. PROVIDE FLUSH
OUTLET BOX AND CABLING IN THE QUANTITY INDICATED WITH 10'-0"
SERVICE LOOP IN ACCESSIBLE CEILING SPACE.AP
WALL MOUNTED OUTDOOR ACCESS POINT LOCATION. PROVIDE CABLING
IN THE QUANTITY INDICATED WITH 10'-0" SERVICE LOOP IN ACCESSIBLE
CEILING SPACE.AP
WP
PLAIN TELEPHONE LINE OUTLETP
SYMBOLS LEGEND - SECURITY
DESCRIPTIONSYMBOL
CARD READER. COORDINATE EXACT LOCATION WITH ARCHITECT
(KP = KEYPAD)
(WP = WEATHERPROOF)
KEYPAD - ALARM PANEL
ELECTRIC STRIKE
DOOR/WINDOW CONTACT
REQUEST TO EXIT PUSHBUTTON
K
ES
DC
REX
CR
WP
S S AUDIO SENSOR - CONFIRM TYPE AND MOUNTING
ALARM BELL/SIREN - CONFIRM TYPE AND MOUNTING
SYMBOLS LEGEND - FIRE ALARM
DESCRIPTION
FIRE ALARM SYSTEM CONTROL PANEL
FIRE ALARM FLOW SWITCH
HI/LO AIR PRESSURE SWITCH
VALVE SUPERVISORY SWITCH
POST INDICATOR VALVE SUPERVISORY SWITCH
FIRE ALARM PULL STATION
FIRE/SMOKE DAMPER
SMOKE DAMPER
FIRE ALARM HORN ONLY
FIRE ALARM HORN STROBE, XX = CANDELA RATING
FIRE ALARM SPEAKER ONLY
FIRE ALARM SPEAKER STROBE, XX = CANDELA RATING
FIRE ALARM STROBE ONLY - WALL, XX = CANDELA RATING
FIRE ALARM STROBE ONLY - CEILING, XX = CANDELA RATING
FIRE ALARM BELL
FIRE FIGHTER PHONE JACK
HEAT DETECTOR, RATE OF RISE AND FIXED TEMPERATURE UON
SMOKE DETECTOR, PHOTOELECTRIC UON
FIRE ALARM DUCT SMOKE DETECTOR WITH SAMPLING TUBE
FLAME DETECTOR
GAS DETECTOR
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
ISOLATION MODULE
RELAY BLOCK
ESR - ELEVATOR STATUS/RECALL
FAC - FIRE ALARM COMMUNICATOR
FACP - FIRE ALARM CONTROL PANEL
FAA OR FARA - FIRE ALARM ANNUNCIATOR
HVA - HVAC OR EXHAUST STAIRWELL PRESSURIZATION
LCD - FIRE ALARM LCD ANNUNCIATOR
F - FIXED TEMPERATURE
R - RATE OF RISE ONLY
R/C - RATE COMPENSATION
BT - BEAM TRANSMITTER
BR - BEAM RECEIVER
I - IONIZATION
SYMBOL
FACP
R
ISO
AIM
AOM
S
F
FS
PS
PIV
VS
SD
SD
F
F
S
F
HI/LO AIR PRESSURE SWITCHDH
XX
XX
XX
XX
S
RECESSED DOWNLIGHT - ROUND/SQUARE
RECESSED ADJUSTABLE DOWNLIGHT - ROUND/SQUARE
RECESSED WALLWASH DOWNLIGHT - ROUND/SQUARE
SURFACE MOUNTED DOWNLIGHT - ROUND/SQUARE
SURFACE MOUNTED ADJUSTABLE DOWNLIGHT - ROUND/SQUARE
SURFACE MOUNTED WALLWASH DOWNLIGHT - ROUND/SQUARE
SUSPENDED LUMINAIRE - ROUND/SQUARE
SUSPENDED ADJUSTABLE LUMINAIRE - ROUND/SQUARE
SUSPENDED WALLWASH LUMINAIRE - ROUND/SQUARE
SUSPENDED RING LUMINAIRE
RECESSED LINEAR LUMINAIRE
SURFACE MOUNTED LINEAR LUMINAIRE
SUSPENDED LINEAR LUMINAIRE
TRACK
WALL MOUNTED LUMINAIRE - ROUND/SQUARE
STRIPLIGHT
WALL MOUNTED LINEAR LUMINAIRE,
MAY HAVE MORE THAN ONE SUPPORT
TROFFER
TROFFER, ARCHITECTURAL
LIGHT POLE, ROUND HEAD
LIGHT POLE, SQUARE HEAD
LIGHT POLE, COLUMNAR
GROUND MOUNTED ADJUSTABLE UPLIGHT
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :3
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
ELECTRICAL
LEGEND
E0.01
CR
RG
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
TO COMPLY WITH 2023 NEC 406.12, ALL 15A AND 20A, 120 AND 208V, NON-LOCKING RECEPTACLES SHALL BE TAMPER RESISTANT UNLESS THEY ARE NOT READILY ACCESSIBLE TO THE PUBLIC OR SPECIFICALLY
MEETING EXCEPTIONS LISTED IN ARTICLE 406.12.
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :3
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
ELECTRICAL
SCHEDULES
E1.00
CR
RG
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
EV ELECTRIC VEHICLE CHARGING STATION 7200 32.00 40.00 208 1 3/4" (2)#8, #10G
TP-1 TRAP PRIMER 0.006 6.40 115 1 3/4" (2)#12, #12G
DWH-1 DOMESTIC HOT WATER HEATING 4.50 4500 23.60 208 1 3/4" (2)#10, #10G
EWH-2 POINT OF USE ELECTRIC WATER HEATER 8.32 8320 40.00 208 1 3/4" (2)#8, #10G
EWH-1 POINT OF USE ELECTRIC WATER HEATER 8.32 8320 40.00 208 1 3/4" (2)#8, #10G
BF-1 VENTILATION FAN 0.43 431 10.00 115 1 3/4" (2)#12, #12G 2
EF-3 EXHAUST FAN 0.03 30 1.42 115 1 3/4" (2)#12, #12G 2
EF-2 EXHAUST FAN 0.07 70 1.50 115 1 3/4" (2)#12, #12G 2
EF-1 EXHAUST FAN 0.07 71 1.50 115 1 3/4" (2)#12, #12G 2
CDP-4 CONDENSATE PUMP 1/50 100 115 1 3/4" (2)#12, #12G 2
CDP-3 CONDENSATE PUMP 1/50 100 115 1 3/4" (2)#12, #12G 2
CDP-2 CONDENSATE PUMP 1/50 100 115 1 3/4" (2)#12, #12G 2
CDP-1 CONDENSATE PUMP 1/50 100 115 1 3/4" (2)#12, #12G 2
RCP-1 DOMESTIC HOT WATER CIRCULATION 1/5 1015 5.10 115 1 3/4" (2)#12, #12G 2
BCP-1 HEATING HOT WATER / BOILER PUMP 1/5 1015 5.10 115 1 3/4" (2)#12, #12G 2
P-8 HYDRONIC PUMP 2 2699 7.50 208 3 3/4" (4)#12, #12G VFD
P-7 HYDRONIC PUMP 2 2699 7.50 208 3 3/4" (4)#12, #12G VFD
P-6 HYDRONIC PUMP 3 3814 10.60 208 3 3/4" (4)#12, #12G VFD
P-5 HYDRONIC PUMP 3 3814 10.60 208 3 3/4" (4)#12, #12G VFD
P-4 HYDRONIC PUMP 2 2699 7.50 208 3 3/4" (4)#12, #12G VFD
P-3 HYDRONIC PUMP 2 2699 7.50 208 3 3/4" (4)#12, #12G VFD
P-2 HYDRONIC PUMP 3 3814 10.60 208 3 3/4" (4)#12, #12G VFD
P-1 HYDRONIC PUMP 3 3814 10.60 208 3 3/4" (4)#12, #12G VFD
B-1 BOILER 44980 125.00 125.00 125 208 3 1-1/2" (4) #1, #6G 200A/ 125A/ 3P
HP-1 HEAT PUMP 54696 138 152.00 175 208 3 2" (4) #2/0, #6G 1
FC-11 FAN COIL UNIT 2 1955 9.4 11.75 20 208 1 3/4" (3)#12, #12G
FC-10 FAN COIL UNIT 2 1955 9.4 11.75 20 208 1 3/4" (3)#12, #12G
FC-09 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-08 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-07 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-06 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-05 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-04 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-03 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-02 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
FC-01 FAN COIL UNIT 1 1040 5.0 6.25 15 208 1 3/4" (3)#12, #12G
UH-1 ELECTRIC UNIT HEATER 3 3016 14.5 20.00 20 208 1 3/4" (3)#12, #12G 2
ERV-3 ENERGY RECOVERY VENTILATOR 3744 18.0 21.80 25 208 1 3/4" (3)#12, #12G 30A / 25A / 1P
ERV-2 ENERGY RECOVERY VENTILATOR 8528 23.7 28.90 30 208 3 3/4" (4)#10, #10G 30A / 30A / 3P
ERV-1 ENERGY RECOVERY VENTILATOR 8528 23.7 28.90 30 208 3 3/4" (4)#10, #10G 30A / 30A / 3P
RTU-1 PACKAGED ROOFTOP UNIT 76646 213.0 245 250 208 3 2-1/2" (4) 250 kCMIL, #4G 400A / 250A / 3P 1
ID TAG EQUIPMENT DESCRIPTION HP KW VA FLA MCA MOCP VOLTAGE PHASE CONDUIT CONDUCTORS DISCONNECT REMARKS
2. PROVIDE MOTOR-RATED SWITCH AS DISCONNECT.
1. PROVIDE IN NEMA-3R WEATHERPROOF ENCLOSURE.
REMARKS:
D. REFER TO PLANS, PANEL SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL...
C. WHERE SUPPLIED WITH VFD, PROVIDE ADDITIONAL CONDUIT, CONDUCTORS, AND CONNECTIONS FROM VFD TO...
B. COORDINATE WITH MECHANICAL AND FIRE ALARM SYSTEMS TO PROVIDE DUCT SMOKE DETECTORS FOR HVAC UNITS SUPPLYIN...
A. DISCONNECTS ARE SHOWN AS "FRAME RATING / FUSE...
GENERAL NOTES:
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
J
CONDUIT KEY:
P POWER
S SPARE
PLASTIC WARNING TAPE, 4-MIL THICK, 6" WIDE,
READING: "WARNING BURIED POWER LINE BELOW", 12"
OC, TYP.
PVC CONDUIT; TYP.
REFER TO ONE-LINE DIAGRAM FOR SIZE
#4 LAP @24" MAX, TYP.
#5 LONGITUDINAL BAR
CONDUIT SPACER; TYP.
#4/0 BARE, CU GROUNDING
CONDUCTOR; CONTINUOUS
3" CONCRETE ENCASEMENT
WITH RED DYE;
6" MINIMUM COMPACTED GRAVEL,
5/8" MINUS
REFER TO CIVIL FOR SPECIFIC DEPTH
AND ADDITIONAL INFORMATION
S S
P P
P P
FINISHED GRADE
M
IN
E Q
E Q
E Q
E Q
CC
DD
AA
EE
FF
GG
1.3
1.3
1.7
1.7
9.1
9.1
BB
aa aa aa aa aa aa llll llll llll llll llll llll llll nnnn nnnn nnnn nnnn nnnn nnnnnnnn mmmm mmmm mmmm mmmm mmmm mmmm mmmm mmmm mmmm pppp pppp qqqq qqqq qqqq qqqq qqqq qqqq qqqq qqqq rrrr rrrr uuuu uuuu ssss ssss ssss ssss ssss ssss ssss tttt tttt tttt tttt tttt tttt tttt ssss ssss tttt tttt tttt tttt ssss ssss ssss
ZB1 /8ZB1 /9 ZB1 /9
ZB1 /9
ZB1 /9
ZB3 /7
ZB3 /10
ZB3 /7
ZB3 /7
ZB3 /10
ZB3 /7
ZB1 /9
ZB1 /9
ZB4A /9
ZB4A /9
ZB4A /9
ZB1 /8
ZB1 /9
ZB4B /9
ZB1 /8
YB1 /8
YB1 /9YB1 /8
YB1 /9
YB1 /8
YB1 /8
YB1 /9
YB1 /8
YB1 /8
YB1 /9
YB1 /8
YB1 /9
YB1 /9
YB1 /8
YB1 /9
YB1 /9
YB1 /8
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /9
ZB1 /8
ZB3a /7
ZB3a /10
ZB3a /7
ZB1 /8
ZB1 /8
ZB1 /9
ZB1 /8
ZB1 /8
ZB1 /9
YB1 /9 YB1 /9
ZB1 /9ZB1 /9
EV-1,3
EV-5,7
EV-9,11
EV-13,15
EV-17,19
EV-21,23
LS9 /11
LS9 /11LS9 /11
LS9 /11
LS9 /11
(TYP. 6)
TYP. OF 6
PIV
mmmm
SECONDARY
FROM PSE
E2.00
TYP
ZB3 /10
UG
UG
U G
U G
LS9 /L-11
TYP. OF 6
U G
U G
U G
UG
UGUGUG
UG
VAULT
E 2.
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :3
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
ELECTRICAL SITE
PLAN
E2.00 Author Checker
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
PLAN | SCALE: 1" = 20'-0"
ELECTRICAL SITE PLAN
FLAG NOTES #
1. PROVIDE TYPE LS9 TO BE MOUNTED TO BEAMS AT THIS LOCATION. REFER TO
ARCHITECTURAL DETAILS.
2. REFER TO INTERIOR LIGHTING PLAN E4.01 FOR ADDITIONAL LIGHTING AT THIS LOCATION.
3. PROVIDE INFRASTRUCTURE ONLY (CONDUIT AND PULL STRING FROM PANEL EV TO
UNDERGROUND JUNCTION BOX) TO COMPLY WITH ENERGY CODE EV READY
REQUIREMENTS.
4. PROVIDE COMPLETE LEVEL 2 CHARGING SYSTEM. REFER TO SPECIFICATIONS SECTION
111136 VEHICLE CHARGING EQUIPMENT FOR ADDITIONAL INFORMATION.
5. APPROXIMATE LOCATION OF NEW ELECTRIC SERVICE FROM POLE MOUNTED UTILITY
TRANSFORMERS. REFER TO CIVIL SITE PLAN C4.00 FOR EXACT PLACEMENT AND
UNDERGROUND DUCTBANK ROUTING. REFER TO ELECTRICAL PLAN E2.01 AND POWER
ONE-LINE DIAGRAM ON E6.00 FOR ADDITIONAL INFORMATION.
6. PROVIDE (5)1-1/2" PVC COATED RIGID METAL CONDUITS THROUGH WALL AND EXTEND
OUT 5FT FROM BUILDING TO JOIN WITH (5)1-1/2 PVC CONDUITS BURIED AT 36" BELOW
GRADE. REFER TO CIVIL SITE PLAN C4.00 FOR CONTINUATION TO EV CHARGERS
LOCATION. REFER TO PANEL EV SCHEDULE ON E8.02 FOR CIRCUITING.
7. PROVIDE (2) 4" PVC COATED RIGID METAL CONDUITS THROUGH WALL AND EXTEND OUT
5FT FROM BUILDING TO JOIN WITH (2) 4" PVC CONDUITS BELOW GRADE. REFER TO
2/E5.01 FOR EXACT STUB UP LOCATION IN MDF ROOM AND REFER TO CIVIL PLAN C4.00
FOR CONTINUATION TO UTILITIES.
8. PROVIDE (6) PVC COATED RIGID METAL CONDUITS THROUGH BUILDING TO TERMINATE IN
MAIN ELECTRICAL ROOM. REFER TO ENLARGED ELECTRICAL ROOM PLAN 1/ E5.01 FOR
ADDITIONAL INFORMATION.
9. DETERMINE ADDITIONAL SLEEVES THROUGH BUILDING AND UNDERGROUND CONDUITS
REQUIRED TO SERVE SITE LIGHTING AND OTHER ELECTRIC DEVICES FROM PANELS IN
THE MAIN ELECTRICAL ROOM. COORDINATE WITH STRUCTURAL, LANDSCAPING, AND
CIVIL TO CONFIRM PENETRATIONS AND ROUTING THROUGH SITE.
10. APPROXIMATE LOCATION OF OUTDOOR UTILITY METER AND MAIN SERVICE
DISCONNECT. REFER TO FLOOR PLAN E2.01 AND POWER ONE-LINE DIAGRAM ON E6.00
FOR ADDITIONAL INFORMATION.
11. PROVIDE UNDERGROUND CONDUIT DUCTBANK. COORDINATE WITH CIVIL FOR EXACT
ROUTING AND PULL VAULT LOCATIONS. REFER TO CIVIL SITE PLAN C4.00 FOR
ADDITIONAL INFORMATION.
SHEET NOTES
A. REFER TO SPECIFICATION SECTIONS 260533.13 AND 270528 FOR ADDITIONAL
UNDERGROUND CONDUIT REQUIREMENTS.
B. CONTACT PUGET SOUND ENERGY CUSTOMER CONSTRUCTION SERVICES PROJECT
MANAGER AT (360)764-6738 TO COORDINATE ELECTRIC UTILITY SERVICE INSTALLATION
AND ENERGIZATION REQUIREMENTS.
PLAN | SCALE: NTS
DUCT BANK DETAIL
WP
WP
T
M M
CC
DD
AA
EE
FF
E5.01
MDP
M
METER
MAIN SECTION
24"Wx36"Dx91.5"H
GG
1.3
1.3
1.7
1.7
9.1
9.1
ABOVE
SEAT
ABOVE
SEAT
ABOVE
SEAT
ABOVE
SEAT
COMBO FAX/
PRINTER PRINTER
ABOVE
COUNTER
TYP. OF 5
LOCKABLE
ABOVE
CUSHION
LOCKABLE LOCKABLE
FLOOR
POWER
REC; TYP.
LOCKABLE
+42"
+42"
E5.01
ABOVE
TABLE HT
+27"
+27" +15"
BELOW
CUSHION
M
M
ADA ACTUATOR
ADA ACTUATOR
UC
REF
ABOVE COUNTER
REF
BB
ADA ACTUATOR
ADA ACTUATOR
MW
FUTURE
PRINTER
ABOVE COUNTER
TYP.
J 10
+18"
+18"
J 10
M
FUTURE
PRINTER
TEEN STUDY
ROOM
PROGRAM
ROOM
SENSORY
RM
TEENS
STUDY 1
STUDY 2
OFFICE
COMMUNITY
ROOM
CHILDREN'S
COLLECTION
ADULTS
PUBLIC
MEETING
WORKROOM
OFFICE 1
OFFICE 2
BREAK
ROOM
FAMILY/USER
ASSISTED
RESTROOM
N VESTIBULE
S VESTIBULE
TELECOM
STORAGE
MECHANICAL
STORAGE
ELECTRICAL
WELLNESS
RM
WOMEN'S
RESTROOM
MEN'S
RESTROOM
RESTROOM
RESTROOM
STAFF RR
CUSTODIAL
STORAGE
STORAGE
FIRE
SPRINKLER
HALL
101x
STACK AREA
109x
COMPUTERS
122X
P-41P-41 P-41 P-41
P-45
P-45
P-41 P-45
P-45
P-41 P-41 P-41
P-47
P-47
P-47
P-47 P-47
P-47 P-47P-47
P-49
P-36
P-38
P-20P-22
P-44
P-44
P-40
P-53 P-51
P-55
P-18
P-6
P-4
P -2
P -2
P -2
P-25 P-31
P-49
P-49
P-49
P-44
P-44
P-40
P-40
P-42
P-36 P-36 P-36 P-36 P-36 P-36
P-38 P-38 P-38 P-38 P-38
P-40
P-40
P-53
P-53
P-55 P-55 P-55
P-55P-55
P-24
P-24 P-58 P-58
P-24
P-26 P-26
P-28
P-28 P-28
P-28
P-26 P-26
P-26P-26
P-34
P-34
P-32
P-33
P-31
P-31
P -2
P -2
P -2
P -2
P-27
P-25
P-23P-25
P-9
P-35
P-35
P-37 P-35
P-7
P -7
P -5
P-9 P-9
P-3
P-3
P-9
P-18
P-18
P-14 P-14
P-16 P-16
P-16
P-14
P-12
P-14
P-12
P-4
P-2 P-2 P-6
P-2P-2
P-4
P-4
P-10
P-4
P-15
P-17
P-19 P-21
P-21
P-21
P-9
P-4
P-8P-8
P-4
P-32P-32
P-32P-32
P-32
P-30 P-30 P-30 P-30
P-30
P-30P-30P-30
P-50
P-50
P-43
P-43
P-9 P-1
P-1
P-46
P-42
MA-35,37
EWH-1
MA-31,33
EWH-2
M
CDP-3
M
CDP-1
M
CDP-5
MB-33MB-33
M
CDP-2
MB-33
MB-33
WF-1
MB-42
CDP-2
CDP-3
CDP-5
MB-2,4
FC-01
MB-6,8
FC-02
MB-10,12
FC-03
MB-14,16
FC-04
MB-18,20
FC-05
MB-22,24
FC-06
MB-26,28
FC-07
MB-30,32
FC-08
MB-34,36
FC-09
MB-38,40
FC-10
MB-35,37
FC-11
UH-01
MB-27,29
EF-3
MB-31
MB-1,3,5
ERV-1
MB-7,9,11
ERV-2
MB-13,15
ERV-3
P-38P-38 P-38
P-40
P-40
P-40
P-36 P-36 P-36
(TYP. 27)
ADA ACTUATOR
P-54
WEATHERPROOF
ENCLOSURE
P-56
CDP-4
MB-33
TYP OF (5)
TYP OF (4)
J J P-14 P-14
P-55 P-55 P-55 P-55
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :3
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
ELECTRICAL FLOOR
PLAN
E2.01
CR
RG
PLAN | SCALE: 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN
0' 8' 16'
6. COORDINATE LOCATION OF STANDARD HEIGHT RECEPTACLE SO AS TO BE
ALIGNED WITH RECEPTACLES AT TV HEIGHT.
7. COORDINATE WITH FURNITURE SO AS TO PLACE OUTLET BOX AT CORNER TABLE
LEG.
8. FLOOR OUTLET TO SERVE ABOVE COUNTER POWER AND DATA RECEPTACLES
FOR SELF CHECK COMPUTERS. REFER TO ARCHITECTURAL FOR ADDTIONAL
INFORMATION.
9. PROVIDE DEDICATED CIRCUIT CONNECTION TO ELECTRIC WATER FEATURE.
COORDINATE EXACT LOCATION WITH MECHANICAL.
10. PROVIDE FLOOR OUTLETS AND CONDUIT TO SERVE POWER AND DATA
RECEPTACLES MOUNTED TO CASEWORK AT LOCATIONS SHOWN.
11. PROVIDE FLOOR RECEPTACLE, FULLY CONTROLLED BY PROGRAMMABLE
LIGHTING AND RECEPTACLE CONTROL SYSTEM. COORDINATE EXACT
PLACEMENT WITH ARCHITECT PRIOR TO ROUGH-IN TO ALIGN WITH BOOK STACK
AND ALLOW FOR TWO ROWS OF TYPE LS1 STACK LIGHTS TO PLUG INTO. REFER
TO LIGHTING PLAN LT201 FOR ADDITIONAL INFORMATION.
12. PROVIDE SINGLE RECEPTACLE AT APPROXIMATELY 4" AFF TO BOTTOM.
COORDINATE EXACT LOCATION OF RECEPTACLE WITH CHANGING TABLE
INSTALLATION INSTRUCTIONS.
13. PROVIDE FLIP-UP TYPE DUPLEX RECEPTACLE (MOCKETT # PCS82A/EE WITH
CUSTOM MODIFIED 20A, HARDWIRED, AND UL LISTED CONNECTION. REFER TO
NOTE C ON THIS SHEET FOR FINISH. COORDINATE PLACEMENT WITH
ARCHITECTURAL PRIOR TO ROUGH-IN.
14. PROVIDE MODULAR SNAP-IN TYPE OVAL DUPLEX RECEPTACLE (PRADO UNIFIT
SERIES WITH ACCESSORIES) AND COORDINATE PLACEMENT WITH
ARCHITECTURAL PRIOR TO ROUGH-IN. EACH UNIFIT RECEPTACLE SHOWN SHALL
BE INDIVIDUALLY FED WITH DEDICATED MANUFACTURER'S POWER CABLE FROM
A COMMON ACCESSIBLE STANDARD J-BOX WHERE SPLICE IS MADE TO A
COMMON CIRCUIT HOMERUN. COORDINATE LOCATION OF CIRCUIT J-BOX WITH
ARCHITECT PRIOR TO ROUGH-IN. REFER TO NOTE C ON THIS SHEET FOR FINISH.
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
FLAG NOTES #
1. POWER AND DATA OUTLETS FOR CATALOG COMPUTERS. COORDINATE EXACT
PLACEMENT WITH ARCHITECTURAL PRIOR TO ROUGH-IN.
2. PROVIDE DUPLEX POWER AND 2 PORT DATA WITHIN RECESSED MOUNTED
OUTLET BOXES, LOCATED BEHIND MONITOR. COORDINATE EXACT LOCATION
AND MOUNTING TO CENTER OF TV MONITOR HEIGHT WITH ARCHITECT AND AV
DESIGN PRIOR TO ROUGH-IN. REFER TO SHEET E3.01 FOR ADDITIONAL
INFORMATION.
3. PROVIDE OUTLETS WITH BLANK COVERPLATE AND EXTEND CIRCUIT AND DATA
PIGTAILS FOR FUTURE USE. COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN. REFER TO SHEET E3.01 FOR
ADDITIONAL INFORMATION.
4. ADA DOOR OPENER SYSTEM. COORDINATE WITH VENDOR AND ARCHITECT TO
PROVIDE POWER AND INTERCONNECTIONS BETWEEN MOTORS, ACTUATORS,
AND LOCKING MECHANISM.
5. MOUNT RECEPTACLE CENTERED ON VERTICAL SIDING.
SHEET NOTES
A. UNLESS NOTED OTHERWISE, RECEPTACLES AND EQUIPMENT ARE FED FROM
PANELS IN MAIN ELECTRICAL ROOM.
B. PROVIDE TAMPER RESISTANT TYPE 15A AND 20A, 120 AND 208V, NON-LOCKING
RECEPTACLES WHERE ACCESSIBLE TO THE PUBLIC ON THIS FLOOR, UNLESS
SPECIFICALLY LISTED IN THE EXCEPTIONS IN NEC 406.12.
C. REFER TO ARCHITECTURAL SHEET A220 FINISH PLAN SHEET NOTES 3,4,5,6, AND 7
FOR RECEPTACLE COLOR AND TRIM FINISH REQUIREMENTS.
W P W
P
M
J
J
M
CC
DD
AA
EE
FF
GG
1.3
1.3
1.7
1.7
9.1
9.1
RTU-1
BB
MECHANICAL
WELL
P-48
RTU-1
MA-32,34,36
HP-1
MA-26,28,30
EM-6
EM-6
BF-1
MB-21
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :3
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
ELECTRICAL LOW
ROOF PLAN
E2.02
CR
RG
PLAN | SCALE: 1/8" = 1'-0"
ELECTRICAL LOWER ROOF
0' 8' 16'
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
FLAG NOTES #
1. PROVIDE CIRCUITRY AND INFRASTRUCTURE FOR INSTALLATION OF MECHANICAL
WELL LIGHTING FIXTURE. SEE LT SERIES SHEETS FOR LIGHTING FIXTURE TYPE
AND LOCATION.
CC
DD
AA
EE
FF
GG
1.3
1.3
1.7
1.7
9.1
9.1
BB
MECHANICAL
WELL
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :4
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
ELECTRICAL ROOF
PLAN
E2.04
CR
RG
1. PROVIDE ROOF MOUNTED, PHOTOVOLTAIC ARRAY WITHIN SPACE AS
SHOWN. AREA IS BASED ON CODE REQUIRED ON-SITE RENEWABLE
ENERGY CALCULATION. EXACT DIMENSIONS DEPENDANT ON SPECIFIC
VENDOR REQUIREMENTS.
2. AREA OF ROOF RESERVED TO COMPLY WITH SOLAR READINESS
REQUIREMENT OF ENERGY CODE.
FLAG NOTES #
PLAN | SCALE: 1/8" = 1'-0"
ELECTRICAL ROOF PLAN
0' 8' 16'
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
1,200 SQ FT
4,140 SQ FT
ON-SITE RENEWABLE ENERGY CALCULATIONS
SECTION C411.1 ON-SITE RENEWABLE ENERGY
PV CAPACITY 1 = 0.5 W/SF * 17,050 SF = 8,525 W
SECTION C406 ON-SITE RENEWABLE ENERGY
PV CAPACITY 2 = 0.1 W/SF * 17,050 SF = 1,705 W
PV CAPACITY 1 + PV CAPACITY 2 = 8,525 W + 1,705 W = 10,230 W OR 10.23 KW
ROUNDED UP TO 12 KW
ROOF AREA REQUIRED = 12,000 W /10 W/SF = 1,200 SF 1
SOLAR READY CALCULATIONS
IN ACCORDANCE WITH SECTION C411.3
ROOF AREA = 10,350 SF
40% OF ROOF AREA = 4,140 SF
ELECTRICAL SERVICE
1,000 AMPS * 208 VOLTS * 1.73 * 20% / 10W/SF = 7,200 SF
SOLAR READY ZONE EQUAL TO 4,140 SF IS SHOWN ON THE ROOF PLAN
11 11
2 CR
C R
T V
CR
4 4
2 2 2
CR CR
C R
2 2 2 2
2 2
C R
CR
DC
DC
DC
D C
DC
K
DC
DC
2 2
2 2
C R
DC
S
S
S
S
S
S
S
S
S
D C
FAC
S
S
A
S
C R
F A
A
S
S
S
S
S
S
F
F
F
S
S
C R
S
F F
F
S
CC
DD
AA
EE
FF
GG
1.3
1.3
1.7
1.7
9.1
9.1
AP
AP
AP
AP
AP
TYP.
AP
AP
WP
AP
WP
AP
WP
AP
WP
AP
WP
TYP
AP
REX
+42"
+42"
E5.01
UNDERGROUND COMMUNICATION UTILITY
CONDUIT ENTRANCE TO MDF; REFER TO
CIVIL PLANS
BB
AP
AP
J
ABOVE COUNTER
TYP.
FUTURE
PRINTER
AP
+18" +18"
ABOVE COUNTER
TYP. OF 3
WP
3 FUTURE
PRINTER
PROGRAM
ROOM
TEEN STUDY
ROOM
STORAGE
COLLECTION
TEENS
TELECOM
STUDY 1
STUDY 2
OFFICE
COMMUNITY
ROOM
N VESTIBULE
PUBLIC
MEETING
MECHANICAL
BREAK
ROOM
STORAGE
FIRE
SPRINKLER
OFFICE 1
OFFICE 2
ELECTRICAL
MEN'S
RESTROOM
WOMEN'S
RESTROOM
108 STAFF RR
WELLNESS
RM
CUSTODIAL
RESTROOM
RESTROOM
WORKROOM
S VESTIBULE
STACK AREA
109x
ADULTS
CHILDREN'S
SENSORY
RM
HALL
101x
STORAGE
WORKROOM
FAMILY/USER
ASSISTED
RESTROOM
E5.01
TG7
185 cd
WP
VS FS
RTU-1
RETURN
STORAGE
S
21 21
21 21
2 22
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :4
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
SYSTEMS FLOOR
PLAN
E3.01
CR
RG
PLAN | SCALE: 1/8" = 1'-0"
SYSTEMS FLOOR PLAN
0' 8' 16'
6. COORDINATE EXACT PLACEMENT OF DUCT SMOKE DETECTOR ASSOCIATED WITH
RTU-1 ON ROOF WITH MECHANICAL PRIOR TO ROUGH-IN. REFER TO M2.01 FOR
ADDITIONAL INFORMATION.
7. PROVIDE CEILING MOUNTED DATA OUTLET FOR POE MICROPHONE.
8. OUTLET TO SERVE ABOVE COUNTER POWER AND DATA RECEPTACLES FOR SELF
CHECK COMPUTERS. REFER TO ARCHITECTURAL FOR ADDITIONAL
INFORMATION.
9. PROVIDE FLOOR OUTLETS AND CONDUIT TO SERVE POWER AND DATA
RECEPTACLES MOUNTED TO CASEWORK AT LOCATIONS SHOWN.
10. WIRELESS ACCESS POINT, OUTDOOR WEATHERPROOF, MOUNTED TO RECESSED
WALL OUTLET BOX JUST BELOW CANOPY CEILING. PROVIDE WITH CONDUIT TO
NEAREST INDOOR ACCESSIBLE CEILING SPACE.
DRAWING ISSUE
# DATE DESCRIPTION
10 2026/03/23 elec updates
11 2026/03/25 BID SET
FLAG NOTES #
1. POWER AND DATA OUTLETS FOR CATALOG COMPUTERS.
2. PROVIDE DUPLEX POWER AND 2 PORT DATA WITHIN RECESSED MOUNTED
OUTLET BOXES, LOCATED BEHIND MONITOR. COORDINATE EXACT LOCATION
AND MOUNTING HEIGHT TO CENTER OF TV MONITOR WITH ARCHITECT AND AV
DESIGN PRIOR TO ROUGH-IN. REFER TO POWER PLAN FOR CIRCUITING.
3. PROVIDE OUTLETS WITH BLANK COVERPLATE AND EXTEND CIRCUIT AND DATA
PIGTAILS FOR FUTURE USE. COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN. ALSO REFER TO E2.01.
4. PROVIDE CEILING MOUNTED DATA OUTLET FOR PEOPLE COUNTER.
5. PROVIDE CEILING MOUNTED DATA OUTLET FOR OWNER PROVIDED POE
SPEAKER.
SHEET NOTES
A. COORDINATE DATA COMMUNICATIONS, TV, AND SECURITY SYSTEM OUTLETS
WITH ARCHITECTURAL FEATURES INCLUDING CASEWORK, COUNTERTOPS,
SEATING, DOOR FRAMES, ETC. REFER TO ARCHITECTURAL ELEVATIONS FOR
ADDITIONAL INFORMATION.
B. ROUTE CONDUIT CONCEALED OR COORDINATE WITH ARCHITECTURAL TO BE AS
CONCEALED AS POSSIBLE.
C. PROVIDE FIRE ALARM SYSTEM AND NOTIFICATION/DETECTION COVERAGE AS
REQUIRED BY NFPA-72 2022, WA STATE ADOPTED IFC-2021 AND CITY OF SUMNER
FIRE CODE 15.24. FIRE ALARM LAYOUT IS DIAGRAMMATIC, FINAL LAYOUT TBD BY
FIRE ALARM SHOP WITH EXACT CEILING AND WALL DEVICE LOCATIONS
SUBMITTED FOR REVIEW AND APPROVAL BY ARCHITECT.
11. DATA OUTLETS IN THE COMMUNITY ROOM SHALL BE SERVED FROM AN INTERNET
CONNECTION AND LAN THAT IS SEPARATE FROM THE REST OF THE LIBRARY.
12. MOUNT DEVICE ON TOP OF NEAREST BEAM.
13. PROVIDE SINGLE DOOR CONTACTOR.
14. PROVIDE DOUBLE DOOR CONTACTOR.
15. PROVIDE ELECTRIFIED LOCK WITH CARD READER.
16. PROVIDE SIREN. CONFIRM TYPE WITH SECURITY CONTRACTOR.
17. PROVIDE CELLULAR COMMUNICATOR FOR BUILDING FIRE ALARM CONTROL
PANEL. PROVIDE AUX POWER AND TROUBLE MONITORING FROM BUILDING FACP
IN MECH ROOM. COMMUNICATOR SHOWN HERE FOR EASE OF EXTERNAL
ANTENNA INSTALLATION (AS NECESSARY).
18. PROVIDE SIGNAGE ON DOOR INDICATING THAT THE BUILDING FIRE ALARM
CONTROL PANEL IS LOCATED WITHIN.
19. CONFIRM LOCATION WITH AHJ PRIOR TO ROUGH-IN. AT MINIMUM RECOMMEND
DUAL-ACTION STYLE AND PROTECTIVE GUARD AS CHILDREN'S AREA MAY BE A
CAUSE FOR FALSE ALARMS.
20. WIRELESS ACCESS POINT, CEILING MOUNTED TO FLUSH OUTLET BOX.
21. COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH IN.
22. 1" CONDUIT BACK TO ROOM TELECOM 129
PC PC PC
PC PC
PC
PC
PCPC
PC
PC
PC
PC
PC
PC PC
PC PC
PC
PC
PC
PC
PC
PC
PC
PCPC
PC
PC
PC
PC
PC
PC
O S
W W
O S
O S
O S
O S
OSOS
WW
O S
O S
O S
W
OS
O S
W W
OS OS
W
OS
OS
O S
OS
W
PC
W
W W
W W
W
W
W
W
W
O S
W
PC
OS
O S
PC
PC
PC
PC
PC
PC
PC
PCPC
PC
PC
PC
PC
PC
PC
WW
O S
O S
O S
W
OS
O S
W W
OS OS
W
OS
OS
O S
W
PC
W
W
W
W
O S
W
PC
J J
J
J J
J
J
J
OS
J
J
J
J
J
J
J
J
JJ
E5.01
E5.01
TEEN STUDY
ROOM
PROGRAM
ROOM
SENSORY
RM
TEENS
STUDY 1
STUDY 2
OFFICE
COMMUNITY
ROOM
CHILDREN'S
COLLECTION
ADULTS
PUBLIC
MEETING
WORKROOM
OFFICE 1
OFFICE 2
BREAK
ROOM
FAMILY/USER
ASSISTED
RESTROOM
N VESTIBULE
S VESTIBULE
TELECOM
STORAGE
MECHANICAL
STORAGE
ELECTRICAL
WELLNESS
RM
WOMEN'S
RESTROOM
MEN'S
RESTROOM
RESTROOM
RESTROOM
STAFF RR
CUSTODIAL
STORAGE
STORAGE
FIRE
SPRINKLER
HALL
101x
STACK AREA
109x
COMPUTERS
122X fff ggg
CC
DD
AA
EE
FF
GG
1.3
1.3
1.7
1.7
9.1
9.1
BB
DLZ1
DLZ2
DLZ1
DLZ1
DLZ1
DLZ2
DLZ1
DLZ2
DLZ1 DLZ2
DLZ1
DLZ2
DLZ1 DLZ2
DLZ1
DLZ2
DLZ1
DLZ2
DLZ1
DLZ1
DLZ1
DLZ2
DLZ1DLZ2
DLZ2
DLZ1
DLZ1
DLZ2
DLZ1
a b c d d d d d d d d d d d d p p p f f f f h-1 i i i j k k l l l m n n p p p p p p p p p r q r s t u u u v v v w w w w w w w w w w w w x x x x x x y y y y y y z bb cc dd ff gg gggg gg gg gg hhii jj kk ll mm nn pp qq qq qq qq rr rr rr rr rr rr rr rr rr rr rr rr rr rr rr rr ss tt uu vv ww yy zz zz aaa aaa aaa aaa aaa aaaaaa aaa aaa aaa aaa aaa aaa aaa aaa bbb bbb bbb bbb bbb ccc ccc ddd ggg hhhhhh iiiiii jjj jjj lll mmm nnn nnn ppp qqq qqq qqq rrrrrr sss sss ttt uuu vvv www yyy xxx zzz zzz zzz zzz aaaa bbbb cccc dddd ffff gggg hhhhhhhhhhhhhhhh iiii jjjj jjjj
5 6
3 3 vvvv vvvv vvvv iiiiiiii
DR3 /EM-1
DR1 /EM-1
DR1 /L-2
DR1 /EM-3
DR1 /EM-1
DR1 /EM-1
DR1 /EM-1
LP3 /L-11
LP2 /L-2
LP2 /EM-1
LP2 /EM-1
LP2 /L-2
AP1 /L-4
LR1 /EM-1 LR1 /L-2 LR1 /L-2
AR1 /L-2
LR2 /L-4
LR2 /L-2
DR1 /L-2
DR1 /EM-3
DR1 /L-4
DR1 /L-17 DR1 /L-2
DR1 /L-6
DR1 /L-6
AR1 /L-2
AR1 /L-2
AR1 /L-2
AR1 /L-2
AP1 /L-6
AP1 /L-6
DR2a /L-11
DR1 /EM-1
DR2a /L-11
DR1 /EM-1
DR1 /EM-3
DR1 /L-4
DR1 /L-4 DR1 /L-4
CP2A /EM-1
DR1 /L-17
LP2 /EM-7
LP2 /EM-7LP2 /EM-7
LS5 /EM-8
LS5 /EM-12
LR3a/TR1 /EM-1
DR1 /L-6 DR1 /L-6
DR1 /L-2DR1 /L-2
LR2 /L-2
LR2 /L-4
LR2 /L-4 LR2 /L-4
LR2a /L-4 LR2a /L-4
DR1 /EM-1
DR1 /EM-1
DR1 /EM-3
CP1 /L-6 CP1 /L-6 CP1 /L-6
CP1 /L-6CP1 /L-6CP1 /L-6
DR2a /EM-1
DR2a /EM-1
DR2a /L-11 DR2a /EM-2
LR1 /L-2
LR1 /EM-1LR1 /EM-1LR1 /EM-1LR1 /EM-1LR1 /EM-1LR1 /EM-1
LR1 /L-2 LR1 /L-2 LR1 /L-2 LR1 /L-2
LR1 /L-2
LR1 /L-2
LR1 /EM-1
AR1 /L-2
AR1 /L-2
AR1 /L-2
LR2 /L-4
LR1 /EM-7 LR1 /EM-7 LR1 /EM-7
DR3 /L-6
DR3 /L-6
DR3 /L-6
DR3 /L-6DR3 /L-6
DR1b /L-6DR1b /L-6
DR2b /L-11DR2b /L-11DR2b /L-11
DR1 /EM-1
LR1 /EM-1
LR1 /L-2LR1 /EM-1
LR1 /L-2
LR1 /L-2
LR1 /L-2
LR1 /L-2
LR1 /L-2LR1 /L-2
XS1 /EM-4
LP1 /EM-11
LP1 /EM-9
LP1 /EM-11
LP1 /EM-9 AP1 /EM-1
DR3 /EM-7
DR3 /EM-7
DR3 /L-6
DR3 /L-6DR3 /L-6
DR3 /L-6
DR3 /EM-7 DR3 /EM-7 DR3 /EM-7 DR3 /EM-7 DR3 /EM-7 DR3 /EM-7
DR3 /EM-7
DR3 /EM-7 DR3 /EM-7
DR3 /EM-7DR3 /EM-7
DR3 /EM-7 DR3 /EM-7
DR3 /EM-7DR3 /EM-7DR3 /EM-7DR3 /EM-7DR3 /EM-7DR3 /EM-7
DR3 /EM-5 DR3 /L-6 DR3 /L-6 DR3 /EM-7 DR3 /L-6
DR3 /L-6DR3 /EM-7DR3 /L-6DR3 /L-6
DR3 /EM-7
DR3 /EM-7
DR3 /EM-7 DR3 /L-6 DR3 /L-6 DR3 /EM-7 DR3 /L-6
DR3 /L-6DR3 /EM-7DR3 /L-6DR3 /L-6DR3 /EM-7
DR1 /L-6 DR1 /L-6
DR1 /L-6DR1 /L-6
PD1 /L-6
PD1 /L-6
DR3 /L-6 DR3 /EM-1 DR3 /L-6
DR3 /L-6DR3 /EM-3DR3 /L-6
DR3 /L-6 DR3 /EM-1DR3 /L-6
DR3 /L-6DR3 /EM-3DR3 /L-6
DR3 /L-6 DR3 /EM-1DR3 /L-6
DR3 /L-6DR3 /EM-3DR3 /L-6
DR3 /L-6 DR3 /EM-1 DR3 /L-6
DR3 /EM-3DR3 /EM-1
DR3 /L-2 DR3 /L-2
E5.01
AP1 /L-2
XS1 /EM-4
XS1 /EM-4
XS1 /EM-4 XS1 /EM-4
XS1 /EM-4
XS1 /EM-4
XS1 /EM-4
XS1 /EM-4
AP1 /L-4
LS
/L -2
LS6 /EM-1
MS1 /L-4 MS1 /L-4
MS1 /L-4
MS1 /L-4
MS1 /L-4
MS1 /L-4 MS1 /L-4
MS1 /EM-1
LS10 /EM-1
LS5 /EM-8
LS5 /EM-10
t
XS1 /EM-4
TS-1 /L-14
TS-1 /L-15
TS-1 /L-12
TS-1 /L-13
xx
LS-8 /L-6
LS11 /L-6 uuu h-2
CS2 /L-6 CS2 /L-6
ggg
CS2 /L-6
fff
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :5
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
LIGHTING FLOOR
PLAN
E4.01
CR
RG
PLAN | SCALE: 1/8" = 1'-0"
LIGHTING FLOOR PLAN
0' 8' 16'
FLAG NOTES #
1. PROVIDE COVE FIXTURE TYPE LS7 TO BE MOUNTED CONTINUOUSLY WITHIN ARCHITECTURAL COVE AT
THIS LOCATION. REFER TO ARCHITECTURAL DETAILS FOR MOUNTING.
2. PROVIDE A CONTINUOUS RUN OF TS1 TO BE MOUNTED TO UPPER MULLIONS AT THIS LOCATION WITH (4)
TYPE TH1 TRACK HEADS. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING.
3. PROVIDE LIGHTED MIRROR TYPE MS1 TO BE MOUNTED TO WALL CENTERED OVER SINK AT THIS LOCATION.
4. PROVIDE FIXTURE TYPE LS8 TO BE INTEGRATED ALONG THE EDGE OF EACH SHELF AT THIS LOCATION FOR
THE ENTIRE LENGTH OF THE SHELF. REFER TO ARCHITECTURAL DETAIL.
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
5. PROVIDE FIXTURE TYPE LS5 TO BE MOUNTED CONTINUOUSLY TO LOWER HORIZONTAL MULLIONS AT THIS LOCATION. FIXTURES SHALL BE INITIALLY ADJUSTED TO LIGHT CURVED CEILING. ADITIONAL ADJUSTMENTS TO BE MADE DURING AIMING. REFER TO ARCHITECRTURAL DETAILS AND ELEVATIONS FOR
MOUNTING.
6. REFER TO SITE LIGHTING PLAN E2.00 FOR ADDITIONAL LIGHTING AT THIS LOCATION.
7. PROVIDE (10) LR3 MODULES WITHIN TR1 TRACK AT THIS LOCATION. TR1 TRACK TO HAVE TWO CIRCUITS.
PLAN NORTH (3) LR3 FIXTURES TO BE CONTROLLED SEPARATELY FROM (7) PLAN SOUTH FIXTURES.
8. PROVIDE FIXTURE TYPE LS6 TO BE MOUNTED UNDER CABINETS AT THIS LOCATION. REFER TO
ARCHITECTURAL DETAILS.
9. PROVIDE CONTROL STATION FOR ALL LIGHTING IN PUBLIC SPACES (STACKS, CHILDRENS, TEENS, ADULTS, LOBBY, VESTIBULE, RR CORRIDOR, ETC,) UNLESS OTHERWISE NOTED.
10. PROVIDE SEPARATE SHADE CONTROLS NEXT TO MAIN LIGHTING SWITCHING STATION TO CONTROL MECHO SHADES IN TEENS, CHILDREN'S, AND ADULTS AREAS. CONNECT TO MECHO SHADE SYSTEM PER VENDOR
INSTALLATION INSTRUCTIONS.
11. PROVIDE SHADE CONTROL AND CONNECT TO MECHO SHADE SYSTEM PER VENDOR INSTALLATION
INSTRUCTIONS. ARCHITECTURAL DETAILS.
12. PROVIDE COMPLETE MECHO-SHADE SYSTEM ALONG THIS WINDOW. REFER TO ARCHITECTURAL PLANS
FOR EXTENT OF COVERAGE AND VENDOR SHOP DRAWINGS FOR SPECIFIC MOTOR LOCATION
CONNECTIONS. RESERVE A MINIMUM OF EIGHT (8) 20, 120V CIRCUITS FROM PANEL P TO SERVCE ALL
SHADES FROM. REFER TO FLAG NOTES 10 AND 11 ABOVE FOR CONTROL STATION LOCATIONS.
13. PROVIDE FIXTURE TYPE LS11 TO BE MOUNTED WITHIN ARCHITECTURAL COVE AT THIS LOCATION. REFER
TO ARCHITECTURAL DETAILS.
14. COORDINATE EXACT LOCATION OF LIGHTING CONTROLS WITH ARCHITECTURAL.
SHEET NOTES
A. FIXTURES OF THE SAME TYPE WITHIN A ROOM ARE ON THE SAME CONTROL ZONE UNLESS OTHERWISE
NOTED.
B. DASHED LINE WITHIN ROOMS INDICATES ENERGY CODE DEFINED BOUNDARIES FOR DAYLIT ZONES AS
FOLLOWS:
DLZ1 PRIMARY DAYLIGHT ZONE
DLZ2 SECONDARY DAYLIGHT ZONE
C. EACH FIXTURE SHALL BE ON ONLY ONE DAYLIGHT ZONE. IF A LINEAR FIXTURE IS PARTIALLY ON DLZ1 AND
PARTIALLY ON DLZ2, THE ENTIRE FIXTURE SHALL BE ON DLZ1.
M
M
M
M
M
M
M M
M M
M M
M M
F A
C
PS
P
M
M
DD
MA-39,41
9.1
9.1
LLCSP
MB P
MDP
DIST SECTION
MECHANICAL
ELECTRICAL
P-11
P-11
P-11
DWH-1
RCP-1
MA-43
MA-38,40,42
B-1
BCP-1
MA-29
MB-19
EF-2
MA
P-1
P-2
MA-2,4,6
MA-1,3,5
P-3
P-4
MA-8,10,12
MA-7,9,11
P-8
P-7
MA-19,21,23
MA-20,22,24
P-5
MA-13,15,17
MA-14,16,18
P-6
EV
LIGHTING INVERTERAP1 /EM-3
AP1 /L-17
AP1 /EM-3
AP1 /L-17
AP1 /EM-3
+96" AFF
+96" AFF
F
P-52
AA
MDF
SECURITY PANEL 120V
COORDINATE EXACT LOCATION
WITH VENDOR (SONITROL)
UTILITY CONDUITS STUB UP;
REFER TO CIVIL SITE PLAN
FOR CONTINUATION
STANDARD 12" LADDER TYPE
CABLE TRAY MOUNTED AT
24" ABOVE TOP OF RACK
IT RACK
20A, 120V QUAD
RECEPTACLE; TYP.
TTB
TELECOM
INTRUSION PANEL
ACCESS MODULE PANEL
MDF-4MDF-2
MDF-8
MDF-5
MDF-3
MDF-7
MDF-6
MDF-1
MB-23EF-1
ACCESS
MODULE PANEL
(STACKED
TYP. 2)
INTRUSION
SUB-PANEL
AP1 /L-17
AP1 /L-17
AP1 /EM-3
PATCH PANEL
NETWORK SWITCH
UTILITY SERVICE
EQUIPMENT
18" WIDE RACK WITH
STANDARD SIZED KEYSTONES
IT RACK
FROM COMMUNICATIONS UTILITY
(2) 4" CONDUIT WITH
UTILITY SERVICE CABLE
CAT 6 CABLE
CAT 6 CABLE
CAT 6 CABLE
WAP
DATA PORTS
IP PHONES
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :5
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
DETAILS AND
ENLARGED PLANS
E5.01
CR
RG
PLAN | SCALE: 1/2" = 1'-0"
ENLARGED PLAN - MECH AND ELECTRICAL ROOMS
FLAG NOTES #
1. COORDINATE WITH DIVISION 23 TO PROVIDE POWER TO VFD AND CONDUIT AND
WIRING TO CONTROLLED MOTOR(S) INDICATED ON PLAN.
2. COORDINATE WITH CONTROLS AND SECURITY SYSTEM VENDORS FOR EXACT
LOCATION OF DATA OUTLETS AND PATHWAY TO IDF ROOM.
3. COORDINATE FIXTURE MOUNTING LOCATIONS WITH CONDUITS, DUCTWORK, AND
PIPING TO MAINTAIN CODE CLEARANCES AND MINIMIZE ANY BLOCKING OF
ILLUMINATION.
4. PROVIDE FIRE ALARM CONTROL PANEL AND DEDICATED 120VAC CIRCUIT.
COORDINATE EXACT LOCATION WITH OTHER EQUIPMENT AND PROVIDE SYSTEM
WITH COMPLETE COMMUNICATIONS WITH MONITORING COMPANY AND RELAY
WITH TG7 TRANSMITTER.
PLAN | SCALE: 1/2" = 1'-0"
ENLARGED PLAN - MDF ROOM
PLAN | SCALE: 12" = 1'-0"
COMMUNICATIONS RISER
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
MAIN SWITCHBOARD ’MDP’, 1000A 208Y/120V, 3Ø, 4W, 42 kAIC
ADDITIONAL METERING REQUIREMENTS:
PROVIDE SWITCHBOARD AND DISTRIBUTION PANEL FEEDERS WITH END USE
POWER METERING SYSTEM, COMPLETE WITH MODBUS TCP AND BACNET
INTEGRATION. SYSTEM SHALL HAVE THE ABILITY TO MEASURE AND DISPLAY
ENERGY USE BY EACH OF THE CATEGORY TYPES LISTED IN WA ENERGY CODE AS
WELL AS THOSE REQUIRED BY THE LEED ADVANCED ENERGY METERING
CREDIT.
REFER TO DIAGRAM FOR METERING CATEGORIES APPLICABLE TO THIS PROJECT.
FEEDER SIZING CONVENTION:
xxxY AMPACITY AND 3PHASE 4WIRE W/ GROUND xxxD AMPACITY AND 3PHASE 3WIRE W/ GROUND xxxYT AMPACITY AND 3PHASE 4WIRE W/ TRANSFORMER BONDING
= 200A, 2-1/2"C with (4)250Al, #4 Al GND
= 600A, (2) 3"C with (4)500 kCMIL Al, #2/0 Al GND
= 1000A, (4) 3" PVC-SCH 80 with (4)350 kCMIL Al, #4/0 Al GND
+(2)SPARE 3"C
+(2)SPARE 3"C
PROVIDE COMPLETE GROUNDING AND BONDING OF SYSTEM
ADDITIONAL LIGHTING AND RECEPTACLE CONTROL REQUIREMENTS:
PROVIDE ADDRESSABLE LIGHTING CONTROL SYSTEM (LCSP) WITH ADDITIONAL
FUNCTIONALITY TO ALLOW USER SCHEDULING OF ON/OFF TIMES FOR
CONTROLLED RECEPTACLES WHERE REQUIRED BY ENERGY CODE.
22kAIC TYP.22kAIC TYP.
= 800A, (3) 3"C with (4)400 kCMIL Al, #3/0 Al GND xxxYU AMPACITY AND 3PHASE 4WIRE UNDERGROUND SERVICE LATERAL
ALUMINUM FOR 100A AND ABOVE FEEDERS. EQUIVALENT SIZED CU MAY ALSO BE USED.
= 100A, 1-1/2"C with (4)#1Al, #6 Al GND
= 1200A, (4) 3-1/2" PVC-SCH 80 with (4)500 kCMIL Al, 250kCMIL Al GND
Size per NEC 250.66
G F
P
M M M M M M M
M
LOWER ROOF
EXTERIOR GRADE LEVEL LEVEL 1 - ELECTRICAL ROOM LEVEL 1 - TELECOM MDF ROOM
UPPER ROOF
1000YU
200Y
1000YU
100Y 200Y 600Y 200Y800Y 200Y
600Y
1000YU
A
0A
0A 40
0A S
P A
C E
LIGHTING
PANEL L
100A
EMERGENCY
LTG
INVERTER
PANEL EM
MINUTE
BATTERY
PLUG
LOADS
PANEL P
200A
0A
EV
CHARGERS
PANEL EV
600A
0A
MDF
PANEL
200A
0A
MECH
PANEL MA
800A
0A
12 kW RENEWABLE ENERGY SYSTEM
(PV ARRAY)
A
G R
ID
T
IE
LIGHTING AND RECEPTACLE
CONTROL SYSTEM
LCSP
5 KVA
100Y
MECH
PANEL MB
100A
800Y
100Y
1200YU
FROM PUGET SOUND ENERGY (PSE)
UTILITY TRANSFORMERS, POLE MOUNTED
SECONDARY SERVICE AT 208Y/120V, 3Ø, 4W
P.S.E METER,
SERVICE POINT,
AND MAIN
SERVICE
DISCONNECT
(NEMA 3R)
L1
LIGHTING
P1
PLUG
LOADS
H1
HVAC
EV
ELECTRIC
VEHICLES
PV
SYSTEM
P2
PLUG
LOADS
H2
FANS
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :5
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
POWER ONE-LINE
DIAGRAM
E6.00
CR
RG
PLAN | SCALE: 12" = 1'-0"
POWER ONE-LINE DIAGRAM
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
WELL AS
CREDIT.THOSE REQUIRED
3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:5 :5
A
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PANEL SCHEDULES
E8.00
CR
RG
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
FED FROM SERVICE MAIN BREAKER ON EXTERIOR OF BUILDING.
REFER TO ONE-LINE DIAGRAM FOR MORE INFORMATION
NOTES:
CALC. DEMAND CURRENT: 990 A
Mechanical 211193 VA 100.00% 211193 VA CONN. CURRENT: 1004 A
EV Charger 43200 VA 125.00% 54000 VA CALC. DEMAND LOAD: 356657 VA
Receptacle 41740 VA 61.98% 25870 VA CONN. LOAD: 361574 VA
Other 660 VA 100.00% 660 VA
Motor 2356 VA 106.49% 2509 VA
Lighting 9780 VA 100.00% 9780 VA
Equipment 52680 VA 100.00% 52680 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
6 3 200 A 0.0 kVA 12KW PV
5 3 600 A 43.2 kVA PANEL EVC
4 3 100 A 2.4 kVA PANEL MDF
3 3 800 A 263.2 kVA PANEL MA
2 3 200 A 43.2 kVA PANEL P
1 3 100 A 9.6 kVA PANEL LTG
CKT POLES OPD Load DESCRIPTION/NAMEPLATE NOTES
BUS AMPS: 1000 A SPECIAL:
MAIN DEVICE: A.I.C. RATING: 22kAIC
LOCATION: ELECTRICAL 110 VOLTAGE: 120/208 Wye V. 3 ø 4 W.
DISTRIBUTION PANEL: MDP
Notes:
Total Est. Demand Current: 27 A
Total Conn. Current: 27 A
Total Est. Demand: 9614 VA
Other 474 VA 100.00% 474 VA Total Conn. Load: 9614 VA
Lighting 9180 VA 100.00% 9180 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 31 A 24 A 26 A
Total Load: 3638 VA 2885 VA 3092 VA
17 LTG - TRACK 20 A 1 52 VA -- 1 -- SPACE 18
15 LTG - TRACK 20 A 1 42 VA -- 1 -- SPACE 16
13 LTG - TRACK 20 A 1 84 VA 200 VA 1 20 A LTG - TRACK 14
11 LTG - EXTERIOR 20 A 1 1047 VA 42 VA 1 20 A LTG - TRACK 12
9 LTG - EXTERIOR 20 A 1 930 VA 200 VA 1 20 A LTG - EXTERIOR 10
7 LTG - EXTERIOR 20 A 1 300 VA 255 VA 1 20 A LTG - EXTERIOR 8
5 -- -- -- -- 1405 VA 550 VA 1 20 A LTG - INTERIOR 6
3 -- -- -- -- 1283 VA 459 VA 1 20 A LTG - INTERIOR 4
1 LIGHTING INVERTER 30 A 3 2020 VA 805 VA 1 20 A LTG - INTERIOR 2
C K T
# ITEM
N O T E
A M P S
P O L E A B C
P O L E
A M P S
N O T
E ITEM
C K T
MLO
100 A
A.I.C. RATING: 22,000
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: RECESSED
ELECTRICAL 110 MDP TYPE: BOLT-ON
LOCATION: FED FROM: VOLTAGE: 120/208 Wye 3-PH, 4-WIRE
PANEL L SCHEDULE
THIS PANEL SCHEDULE REPRESENTS CIRCUITS CONTAINED WITHIN AN EMERGENCY LIGHTING INVERTER
SYSTEM RATED AT 4.8KVA, 208V, 3PH NORMAL POWER INPUT, 90 MINUTE BATTERY BACKUP;
EMERG-POWER…