6-08 PCLS Sumner Library Bid Set - Mechanical.pdf
PDF 4 MB Posted
- Solicitation number
- 81325
- Issued by
- Pierce County, Washington
About this file
This is a mechanical systems specification document for the Pierce County Library System's Sumner Library construction project located at 15126 Main Street East, Sumner, Washington. The document establishes comprehensive technical requirements for all HVAC, ductwork, piping, and mechanical equipment installation for the new 17,133 square foot public library facility. The specification covers ductwork construction standards requiring G-90 galvanized steel per ASTM 527, rectangular and round ductwork fabrication in accordance with SMACNA standards, and installation of volume dampers, fire dampers, smoke dampers, and flexible duct connections. Equipment schedules specify one AAON RN020 rooftop heat pump unit with 20-ton cooling capacity and 7,800 CFM supply air, three Oxygen8 H15/H10 energy recovery ventilators for dedicated outside air supply, and one QMark 3-kW electric unit heater. The diffuser-grille schedule identifies multiple Titus ceiling and wall supply/return units with specific CFM ratings and noise criteria. Sound attenuator specifications call for IAC Quiet Duct units in both supply and return configurations.
The specification mandates compliance with the 2021 Washington State Energy Code, International Building Code, International Mechanical Code, and local Sumner ordinances, with all contractors responsible for obtaining required permits and paying associated fees. Duct insulation requirements vary by location and function, with R-values ranging from R-3.3 to R-16 depending on climate zone 4C placement and airflow conditions. All mechanical work must include shop drawing submittals, field verification of exact grille and diffuser locations, system balancing reports, as-built documentation, and comprehensive commissioning with functional testing of controls and sequences of operation. The contractor must provide an operating and maintenance manual to the building owner and ensure seismic restraint calculations per IBC and ASCE Standard 7 standards. All penetrations through fire-rated assemblies require UL-approved firestop materials, and thermostats must be mounted at 48 inches above finished floor to meet ADA accessibility requirements.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. PERFORM ALL SHEETMETAL WORK IN ACCORDANCE WITH CURRENT SMACNA STANDARDS.
2. CONSTRUCT DUCTS WITH G-90 OR BETTER GALVANIZED STEEL (ASTM 527) LFQ.
3. CONSTRUCT RECTANGULAR DUCTWORK TO MEET ALL FUNCTIONAL CRITERIA DEFINED IN CHAPTER 11, OF THE SMACNA HVAC DUCT CONSTRUCTION STANDARDS. PROVIDE DIAGONAL CREASING OR BEADING ON ALL PANELS WIDER THAN 18-INCHES, AND PANELS LESS THAN 18 GAGE. CONSTRUCT ROUND AND FLAT OVAL DUCTWORK IN
ACCORDANCE WITH CHAPTER 3 OF SMACNA HDCS.
4. DUCTMATE, METU, OR W.D.C.I. DUCT CONNECTION SYSTEMS ARE ACCEPTABLE. DUCTS CONSTRUCTED USING THESE SYSTEMS WILL REFER TO THE MANUFACTURER'S GUIDELINES FOR SHEET GAGE, INTERMEDIATE
REINFORCEMENT SIZE AND SPACING, AND JOINT REINFORCEMENTS.
5. PROVIDE COLLARS WHEREVER AN EXPOSED DUCT PASSES THROUGH A WALL, SLAB, OR CEILING:1-INCH WIDE, 18-GAGE ANGLE WITH MITERED CORNERS & SEAL WITH FIBERGLASS AND MASTIC.
6. STRAIGHT SPIN-IN FITTINGS WITH VOLUME DAMPER, AND QUADRANT SHALL ONLY BE USED ON LOW PRESSURE
FOR SINGLE RUNOUTS TO DIFFUSERS AND GRILLES; FLEX MASTER, ELGEN OR EQUIVALENT.
7. MEDIUM PRESSURE TAPS SHALL BE CONICAL OR SHOE FITTINGS.
8. ELBOWS IN RECTANGULAR OR SQUARE DUCTWORK SHALL HAVE AN INSIDE RADIUS EQUAL TO DIMENSION OF
ELBOW IN THE PLANE OF THE TURN.
9. ELBOWS IN ROUND DUCTWORK SHALL HAVE THE INSIDE RADIUS EQUAL TO DIMENSION OF ELBOW IN THE PLANE OF THE TURN. USE SEGMENTED, STANDING SEAM, PLEATED, OR STAMPED ELBOWS. ADJUSTABLE ELBOWS ARE
ALLOWED IF RADIUS CONFORMS TO ABOVE.
10. SQUARE CORNER INSERTS (TURNING VANES) SHALL BE SMACNA FIG. 4.3 DOUBLE THICKNESS, RUNNER TYPE 2
WITH 2-1/8-INCH SPACING.
11. VOLUME DAMPERS ARE NOT SHOWN GENERALLY. INCLUDE A DAMPER IN THE DUCT TO EACH SUPPLY, EXHAUST, OR RETURN OPENING; ALSO, IN EACH BRANCH DUCT WHERE THREE OR MORE OPENINGS ARE ASSOCIATED WITH THE BRANCH. LOCATE DAMPERS AT A POINT WHERE THE DUCT IS ACCESSIBLE AS FAR FROM THE OUTLET AS POSSIBLE. DO NOT PROVIDE VOLUME DAMPER ON SUPPLY DUCTWORK UPSTREAM OF TERMINAL UNITS.
DAMPERS SHALL BE RUSKIN MD25 OR MDRS25.
12. THOROUGHLY CLEAN ALL DEBRIS FROM THE INSIDE OF ALL DUCTWORK AND PLENUMS.
13. MECHANICAL DRAWINGS SHOW APPROXIMATE LOCATIONS FOR GRILLES AND DIFFUSERS. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT LOCATIONS. AFTER SHOP DRAWINGS ARE COMPLETED VERIFY EXACT LOCATION OF GRILLES AND DIFFUSERS IN THE FIELD. ENSURE THAT
DIFFUSER AND GRILLE FRAMES MATCH CEILING TYPES AND FINISH PRIOR TO ORDERING.
14. CONNECT FLEXIBLE DUCTS TO METAL DUCTS WITH A SLIP JOINT MADE USING FIRE RESISTANT MASTIC AND CLAMP, IDEAL "SNAP-LOCK" OR VENTLOCK "SURETIGHT NO. 670" AT EACH END. SUPPORT IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS. DO NOT INSTALL WITH ABRUPT BENDS OR OFFSETS.
MAXIMUM LENGTH 5-FEET. LOW PRESSURE INSULATED FLEXIBLE DUCT SHALL BE THERMAFLEX MK-E. HIGH
PRESSURE INSULATED FLEXIBLE DUCT SHALL BE THERAMFLEX MK-C.
15. DUCT SEALING SHALL MEET REQUIREMENTS LISTED IN CHAPTER 6 OF IMC AND WASHINGTON STATE ENERGY
CODE WITH LOCAL AMENDMENTS. IN ADDITION, PROVIDE SEAL CLASS A FOR ALL DUCTWORK.
SHEETMETAL NOTES
1. LOAD CALCULATIONS SHALL BE PERFORMED PER ASHRAE STANDARD 183 OR CHAPTER 3 OF THE WASHINGTON
STATE ENERGY CODE (WSEC) AS NOTED IN SECTION C403.1.2 OF THE WSEC.
2. THE OUTPUT CAPACITY OF HEATING AND COOLING EQUIPMENT AND SYSTEMS DO NOT EXCEED CALCULATED
LOADS PER SECTION C403.1.2 OF THE WSEC.
3. MECHANICAL VENTILATION SHALL BE PROVIDED PER SECTION 401.2 OF THE INTERNATIONAL MECHANICAL CODE
WITH FLOW REDUCTION CAPABILITY TO THE CODE MINIMUM.
4. EACH HVAC SYSTEM WITH TOTAL FAN MOTOR NAMEPLATE HORSEPOWER EXCEEDING 5 HORSEPOWER SHALL
MEET THE PROVISIONS OF SECTION C403.8.3 OF THE WSEC.
5. ZONE TEMPERATURE CONTROL SHALL BE CAPABLE OF A DEADBAND OF AT LEAST 5°F PER C403.4.1.2 OF THE
WSEC.
6. THERMOSTATS SHALL BE 7 DAY PROGRAMMABLE WITH MANUAL OVERRIDE FOR TEMPORARY OPERATION UP TO
TWO HOURS PER C403.4.2.2 OF THE WSEC.
7. ALL DUCT AND PIPING SYSTEMS SHALL BE INSULATED PER SECTION C403.10.1 & TABLE C403.10.1.1 OF THE WSEC. PROTECTION OF PIPE INSULATION EXPOSED TO WEATHER SHALL COMPLY WITH SECTION C403.10.3.1 OF
THE WSEC.
8. AIR HANDLING SYSTEMS SHALL HAVE OPTIMUM START CONTROLS PER SECTION C403.4.2.3 OF WSEC.
9. ALL DUCTWORK SHALL BE CONSTRUCTED AND SEALED PER SECTION C403.10.2 OF THE WSEC.
10. ALL LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND CONNECTIONS OF LOW-PRESSURE SUPPLY AND RETURN DUCTS SHALL BE SECURELY FASTENED AND SEALED WITH WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS-EMBEDDED-FABRIC SYSTEMS OR TAPES INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S
INSTALLATION INSTRUCTIONS.
EXCEPTION(S):
A. CONTINUOUSLY WELDED AND LOCKING-TYPE LONGITUDINAL JOINTS AND SEAMS ON DUCTS OPERATING AT
STATIC PRESSURES LESS THAN 2 INCHES W.G. PRESSURE CLASSIFICATION.
11. DUCTS AND PLENUMS DESIGNED TO OPERATE AT A STATIC PRESSURE GREATER THAN 2” WG SHALL BE INSULATED AND SEALED IN ACCORDANCE WITH SECTION C403.10.2.2 AND 10.2.3 OF THE WSEC.
12. OUTSIDE AIR INTAKES AND EXHAUST DUCTS SERVING CONDITIONED SPACE SHALL BE EQUIPPED WITH MOTORIZED DAMPERS WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE.
DAMPER LEAKAGE RATE SHALL COMPLY WITH SECTION C403.7.8.3 OF THE WSEC.
13. ECONOMIZER HEATING SYSTEM IMPACT SHALL COMPLY WITH SECTION C403.1.4 OF THE WSEC.
14. INTEGRATED ECONOMIZER CONTROL SHALL COMPLY WITH SECTION C403.5.1 OF THE WSEC.
15. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO THE BUILDING OWNER.
16. COMPLY WITH WASHINGTON STATE ENERGY CODE SECTION C408.1.3 DOCUMENTATION REQUIREMENTS INCLUDING ALL LOCAL JURISDICTION AMENDMENTS. INCLUDE THE DEVELOPMENT OF CONSTRUCTION AND AS-
BUILT DRAWINGS, PROJECT MANUALS, AND SYSTEM BALANCING REPORTS.
17. THE HVAC CONTROL SYSTEM SHALL BE TESTED TO ENSURE THAT THE CONTROL DEVICES, EQUIPMENT AND SYSTEMS ARE CALIBRATED, ADJUSTED, AND OPERATE IN ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS IN ACCORDANCE WITH SECTION C408.1.3 OF THE WSEC. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN ACCORDANCE WITH THE APPROVED PLANS AND
SPECIFICATIONS.
WASHINGTON STATE ENERGY CODE NOTES
1. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITION OF
THE FOLLOWING CODES AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION.
2021 INTERNATIONAL STATE BUILDING CODE (IBC)
2021 INTERNATIONAL STATE MECHANICAL CODE (IMC)
2021 UNIFORM STATE PLUMBING CODE (UPC)
2021 INTERNATIONAL STATE FIRE CODE (IFC)
2021 WASHINGTON STATE ENERGY CODE (WSEC)
2. THE SCOPE OF THE MECHANICAL WORK CONSISTS OF WORK SHOWN ON THE PLANS AND AS DESCRIBED IN THE SPECIFICATIONS. IN CASE OF CONFLICT, THE MORE STRINGENT REQUIREMENTS SHALL GOVERN. PROVIDE A
COMPLETE & FUNCTIONAL SYSTEM.
3. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION. PAY ALL ROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF PATENTED DEVICES
AND SYSTEMS.
4. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING LOUVERS, CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM ELEVATIONS, LOCATE MECHANICAL DEVICES SUCH AS TEMPERATURE SENSORS, HUMIDISTATS, PANELS, ETC.
SO THAT THEY DO NOT CONFLICT WITH GENERAL CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NOR
WITH ELECTRICAL SYSTEM (LIGHT SWITCHES, SPEAKERS, OUTLETS, ETC.).
5. COORDINATE WITH OTHER TRADES:
A. REFER TO ELECTRICAL DRAWINGS AND CONFIRM ELECTRICAL CHARACTERISTICS SHOWN FOR MECHANICAL EQUIPMENT (VOLTAGE, PHASE, HZ, ETC). MATCHES THAT OF THE MECHANICAL EQUIPMENT PROVIDED.
B. PROVIDE ADEQUATE CLEARANCE OF MECHANICAL WORK FROM ELECTRICAL EQUIPMENT. MAINTAIN MINIMUM
ACCESS OF 6-INCHES ABOVE CABLE TRAYS AND 18-INCHES TO THE SIDE OF CABLE TRAYS.
6. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AND ACCEPTED SUBMITTALS. INSTALL MATERIAL IN PROPER RELATION TO ADJACENT CONSTRUCTION AND WITH
UNIFORM APPEARANCE FOR EXPOSED WORK.
7. THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK, AND PIPING WILL BE INSTALLED AND REPORT ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE MECHANICAL WORK.
8. THE COMMISSIONING SPECIFICATION, INCLUDING ALL FUNCTIONAL TEST PROCEDURES, SHALL BE PROVIDED
AND ENFORCED BY THE CONTRACTOR.
9. PROVIDE A SINGLE SUBMITTAL OF ALL MECHANICAL EQUIPMENT AS SPECIFIED. AS A MINIMUM, SUBMIT PRODUCT DATA FOR ALL EQUIPMENT AND FIXTURES LISTED IN ACCOMPANYING SCHEDULES FOR APPROVAL.
10. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
11. ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED BY CODES, AND RECOMMENDED BY THE MANUFACTURER ARE PROVIDED.ADJUST TERMINAL EQUIPMENT LOCATIONS, BASED ON FIELD MEASUREMENTS TO AVOID INSTALLATION ABOVE IMOVEABLE FURNITURE. SITE CONDITIONS SHALL DETERMINE THE ACTUAL ARRANGEMENT OF THE WORK. TAKE FIELD MEASUREMENTS BEFORE PREPARING SHOP DRAWINGS, OBTAIN APPROVAL OF SHOP DRAWINGS BEFORE BEGINNING FABRICATION. CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURACY OF DIMENSIONS AND LAYOUT. OVERHEAD PIPING AND DUCTWORK
SHALL BE ARRANGED TO OBTAIN MAXIMUM HEAD ROOM.
12. ALL EXPOSED HORIZONTAL AND VERTICAL PIPING SHALL BE INSTALLED IN A NEAT ARRANGEMENT IN LOCATIONS WHICH ARE THE MOST INCONSPICUOUS. VERTICAL DROPS SHALL BE KEPT TO AN ABSOLUTE MINIMUM AND THEIR FINAL LOCATIONS SHALL BE COORDINATED AND RUN WITHIN CHASES, WALLS, OR SOFFITS WITH OTHER PLUMBING AND ELECTRICAL FEEDS. MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL DRAWINGS FOR CHASE AND SOFFIT LOCATIONS TO COORDINATE ALL EXPOSED PIPING ROUTING. ALL SUCH LOCATIONS
SHALL BE REVIEWED WITH ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
13. UPON CONTRACT AWARD, CONTRACTOR SHALL CONTACT LOCAL UTILITY COMPANY TO SCHEDULE UTILITY CONNECTIONS. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL UTILITY WORK, SECURE ALL
PERMITS AND INSPECTIONS.
14. CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF PIPING AND
DUCTWORK NOT ACTIVELY BEING WORKED ON.
15. MODIFY AND EXTEND EXISTING SERVICE TO ACCOMMODATE NEW WORK. RELOCATE EXISTING COMPONENTS
AS REQUIRED FOR THE NEW SYSTEM. COORDINATE WITH BUILDING MANAGEMENT.
16. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR
SERVICE FOR THREE YEARS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
17. DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN APPROVAL.
18. CONCEAL PIPING AND DUCTWORK TO THE GREATEST EXTENT POSSIBLE.
19. INSTRUCT OWNER IN PROPER OPERATION OF SYSTEMS.
20. FOR CLARITY, DRAWINGS ARE DIAGRAMATIC IN NATURE AND MAY HAVE TO BE ADAPTED TO COMPLY WITH BUILDING CONDITIONS. MAKE OFFSETS WITH FITTINGS USING THE LEAST ANGLE OF OFFSET POSSIBLE.
DUCTWORK & PIPING SHALL BE ROUTED TO AVOID ALL STRUCTURAL SUPPORTS AND COORDINATED WITH WORK
OF OTHER TRADES.
21. ALL DEVICES THAT UTILIZE ELECTRICITY SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR REPLACED. A LEVEL WORKING SPACE NOT LESS THAN 30 INCHES DEEP AND 30 INCHES WIDE SHALL BE PROVIDED IN FRONT OF THE CONTROL
SIDE TO SERVICE AN APPLIANCE.
22. CHANGES OR SUBSTITUTIONS OF EQUIPMENT WILL NOT BE ALLOWED WITHOUT SPECIFIC WRITTEN APPROVAL FROM THE ARCHITECT OR ENGINEER. ALL COSTS RESULTING FROM THE SELECTION OF OTHER THAN SPECIFIED EQUIPMENT SHALL BE BORNE BY THE CONTRACTOR, INCLUDING, BUT NOT LIMITED TO WORK AFFECTING OTHER
CONTRACTORS, THE OWNER, AND RE-DESIGN FEES.
23. ALL INDICATED WORK SHALL BE PERFORMED BY THE CONTRACTOR UNLESS OTHERWISE NOTED.
24. CONTRACTOR IS RESPONSIBLE FOR THE PROPER CARE OF ALL OWNER'S EQUIPMENT AND/OR FURNISHINGS WHICH ARE REQUIRED TO BE TEMPORARILY REMOVED, STORED, OR RELOCATED. CONTRACTOR SHALL REPLACE, REPAIR, OR REIMBURSE OWNER FOR ALL DAMAGES TO SUCH PROPERTIES AT FULL REPLACEMENT VALUE AND EQUIVALENCY. CONTRACTOR SHALL ADVISE OWNER FOR DISPOSITION OF REMOVED EQUIPMENT
AND/OR MATERIALS.
25. CONTRACTOR'S WORK MAY BE REQUIRED OUTSIDE OF THE DESIGNATED SPACE. ALL SYSTEMS BEING DEMOLISHED AND REMOVED, MODIFIED, AND/OR TERMINATED SHALL BE FIELD VERIFIED TO ENSURE NO WORK PERFORMED, INSIDE OR OUTSIDE OF THE DESIGNATED SPACE, SHALL DISRUPT ANY SERVICE OR SYSTEMS OF ANY OTHER AREAS. IF ANY CONDITIONS ARISE THAT ARE NOT IDENTIFIED ON THE DRAWINGS, IMMEDIATE NOTIFICATION SHALL BE PROVIDED TO THE ENGINEER AND OWNER. NO WORK SHALL PROCEED WITHOUT
APPROVALS FROM OWNER.
26. THE MECHANICAL CONTRACTOR SHALL MOUNT REQUIRED DUCT SMOKE DETECTORS SUPPLIED AND WIRED BY
THE ELECTRICAL CONTRACTOR.
27. ALL PENETRATIONS THRU FIRE RATED WALLS, FLOORS, AND CEILINGS THAT ARE NOT PROTECTED BY A LIFE SAFETY DAMPER SHALL BE SEALED WITH A UL APPROVED FIRESTOP MATERIAL SUITABLE FOR CONSTRUCTION MATERIAL TO MAINTAIN FIRE, SMOKE AND DRAFT INTEGRITY OF STRUCTURE. FIRE RESISTANT SEALER SHALL BE TESTED IN ACCORDANCE WITH ASTM E84. INSTALL SEALANT, INCLUDING FOAMING, PACKING AND OTHER ACCESSORY MATERIALS TO FILL OPENINGS WHERE FIRE-RATED PENETRATIONS OCCUR. COMPLY WITH
INSTALLATION REQUIREMENTS ESTABLISHED BY TESTERS AND INSPECTION AGENCY.
28. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER HANDLING, DISPOSAL AND ASSOCIATED COSTS OF ALL REFRIGERANT MATERIAL DURING THIS CONTRACT IN ACCORDANCE WITH ALL FEDERAL, STATE AND LOCAL
CODES AND/OR REGULATIONS.
29. THERMOSTATS SHALL BE MOUNTED AT 48" AFF TO MEET ADA REQUIREMENTS. PROVIDE TAMPER PROOF
COVERS IN PUBLIC AREAS AND WIRE GUARDS IN GYMNASIUMS.
30. ALL DUCTWORK SHALL BE CONNECTED TO MOTORIZED EQUIPMENT WITH FLEXIBLE DUCT CONNECTORS.
31. ALL DUCTWORK SIZES SHOWN ON DRAWINGS ARE CLEAR INTERNAL DIMENSIONS.
32. FURNISH AND INSTALL PIPE SLEEVES PASSING THROUGH EXTERIOR WALLS. SLEEVES SHALL BE STEEL PIPE:
ASTM A53, TYPE E, GRADE A, SCHEDULE 40, GALVANIZED PLAIN ENDS, 2" LONGER THAN WALL WIDTH.
33. THE CONTRACTOR SHALL PROVIDE A COMPLETE SET OF "AS-BUILT" DRAWINGS INDICATING THE PRECISE LOCATION OF ALL SYSTEMS, EQUIPMENT, DUCTWORK, PIPING AND ACCESS DOORS. THESE PLANS SHALL ALSO
INCLUDE ALL CHANGES AND DEVIATIONS FROM BID DOCUMENTS.
34. PROVIDE SEISMIC RESTRAINT IN ACCORDANCE WITH IBC AND ASCE STANDARD 7. SUBMIT CALCULATIONS BY LICENSED STRUCTURAL ENGINEER. PRODUCTS MAY CONFORM TO SMACNA SEISMIC RESTRAINT GUIDELINES.
A AIR, AMP
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AL ALUMINUM, ACOUSTICAL LINING
ARRGT ARRANGEMENT
ATM ATMOSPHERE
BC BLOWER COIL
BDD BACKDRAFT DAMPER
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BOB BOTTOM OF BEAM
BOD BOTTOM OF DUCT
BOS BOTTOM OF STEEL
BTUH BRITISH THERMAL UNITS PER HOUR
CA COMPRESSED AIR, COMBUSTION AIR
CAP CAPACITY
CC COOLING COIL
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CLG CEILING, COOLING
CNTFGL CENTRIFUGAL
CO CLEANOUT
CONC CONCRETE
CND CONDENSATE
CONT CONTINUE, CONTROL
COMP COMPRESSOR
COP COEFFICIENT OF PERFORMANCE
CP CIRCULATING PUMP
CR CONDENSATE RETURN
CRU CONDENSATE RETURN UNIT
CU CONDENSING UNIT
CU FT CUBIC FEET
CV CONSTANT VOLUME
CVTR CONVERTER
CW COLD WATER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
dB DECIBELS
DB DRY BULB
DCVA DOUBLE CHECK VALVE ASSEMBLY
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DF DRINKING FOUNTAIN
DI DE-IONIZED
DIA DIAMETER
DMPR DAMPER
DN DOWN
DS DOWNSPOUT
E EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATING
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
EL ELEVATION
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR, EXTERNAL
F FAHRENHEIT, FIRE LINE
FCU FAN COIL UNIT
FD FIRE DAMPER, FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FLA FULL LOAD AMPS
FLR FLOOR
FLTR FILTER
FLUE COMBUSTION FLUE GAS
FM FLOW METER
FOB FLAT ON BOTTOM
FO FLAT OVAL
FOT FLAT ON TOP
FPM FEET PER MINUTE
FPS FEET PER SECOND
FSD FIRE SMOKE DAMPER
FT FEET, FAN TERMINAL
FTU FAN TERMINAL UNIT
FV FACE VELOCITY
GA GAGE
GAL GALLONS
GALV GALVANIZED
GPM GALLONS PER MINUTE
GW GREASE WASTE
H HUMIDIFIER, HEIGHT
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HEX HEAT EXCHANGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER, HEAT PUMP
HPS HIGH PRESSURE STEAM
HTG HEATING
HW HOT WATER
HWC HOT WATER CIRCULATING
HWP HOT WATER PUMP
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HZ HERTZ
ABBREVIATIONS
ID INSIDE DIAMETER, INDIRECT DRAIN
IDU INDOOR FAN COIL UNIT
IE INVERT ELEVATION
IH INTAKE HOOD
IN INCH
INIT INITIAL
INT INTERIOR
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATT
KWH KILOWATT HOURS
L LENGTH
LAT LEAVING AIR TEMPERATURE
LB POUND, LINEAR BAR
LBS POUNDS
LD LINEAR DIFFUSER
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MD MANUAL DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MOCP MAXIMUM OVER CURRENT PROTECTION
MOD MOTOR OPERATED DAMPER
MTR MOTOR
NC NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NUMBER, NORMALLY OPEN
NTS NOT TO SCALE
OA OUTDOOR AIR
OC ON CENTER
OD OUTSIDE DIAMETER
ODU OUTDOOR CONDENSING UNIT
OPNG OPENING
ORD OVERFLOW ROOF DRAIN
ORL OVERFLOW RAIN LEADER
P PUMP, PLUMBING
PC PUMPED CONDENSATE
PCR PROCESS COOLING WATER RETURN
PCS PROCESS COOLING WATER SUPPLY
PD PRESSURE DROP
PH PHASE
POC POINT OF CONNECTION
POS POSITIVE
PR PUMPED RETURN
P/T PRESSURE/TEMPERATURE
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA RETURN AIR
RCP RECIRCULATING PUMP
RD ROOF DRAIN
REF REFERENCE
REQD REQUIRED
RF RETURN FAN
RG RETURN GRILLE
RH RELIEF HOOD, RELATIVE HUMIDITY, RADIANT
HEATER
RL RAIN LEADER
RPBP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
S SOIL
SA SUPPLY AIR
SD STORM DRAIN, SMOKE DAMPER
SENS SENSIBLE
SEER SEASONAL ENERGY EFFICIENCY RATING
SF SUPPLY FAN, SQUARE FEET
SG SUPPLY GRILLE
SL SOUNDLINING
SP STATIC PRESSURE
SPR SPRINKLER
SS STAINLESS STEEL, SANITARY SEWER
STP STANDPIPE
T THERMOSTAT
TEMP TEMPERATURE
TG TRANSFER GRILLE
TOD TOP OF DUCT
TOT TOTAL
TP TRAP PRIMER, TOTAL PRESSURE
TSP TOTAL STATIC PRESSURE
TU TERMINAL UNIT
TYP TYPICAL
UH UNIT HEATER
UON UNLESS OTHERWISE NOTED
V VENT, VOLT
VA VALVE
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
W WATT, WIDTH
WAGD WASTE ANESTHETIC GAS DISPOSAL
WB WET BULB
WG WATER GAGE
WH WATER HEATER, WALL HYDRANT
WSHP WATER SOURCE HEAT PUMP
WTR WATER
VICINITY MAP
PROJECT LOCATION
SITE PLAN
PROJECT LOCATION
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :3
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
GENERAL NOTES,
ABBREVIATIONS AND
SHEET INDEX
M0.00
JS/CR
JG
MECHANICAL SHEET INDEX
M0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
M0.01 MECHANICAL LEGEND
M1.00 MECHANICAL SCHEDULES
M1.01 MECHANICAL SCHEDULES
M1.02 MECHANICAL SCHEDULES
M2.01 HVAC FLOOR PLAN
M2.03 HVAC ROOF PLAN
MP2.01 HVAC PIPING FLOOR PLAN
MP2.02 HVAC PIPING LOW ROOF PLAN
M3.00 HVAC ENLARGED PLANS
M4.00 HVAC DETAILS & SECTIONS
M4.01 HVAC DETAILS & SECTIONS
M4.02 HVAC DETAILS & SECTIONS
M4.03 HVAC DIAGRAMS
M4.04 HVAC DIAGRAMS
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
03/12/2026
FD FD
SDSD
FSDFSD
MM
BDDBDD
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
X-XX
N
DRAWING CONSTRUCTION ("FLAG") NOTE
EQUIPMENT IDENTIFIER
MATCHLINE
REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE
PREVIOUS RELEASE)
REVISION REFERENCE
EXISTING TO BE REMOVED (DASHED)
HEAVY LINEWEIGHT INDICATES NEW WORK
LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION
DETAIL REFERENCE
DETAIL IDENTIFICATION NUMBER
SHEET WHERE DETAIL IS DRAWN
ELEVATION REFERENCE
ELEVATION IDENTIFICATION
NUMBER SHEET WHERE ELEVATION IS DRAWN
SECTION REFERENCE SECTION
IDENTIFICATION NUMBER
SHEET WHERE SECTION IS DRAWN
NORTH REFERENCE
X
XX.XX
X
XX.XX
X
XX.XX
ACCESS PANEL
SYMBOLS LEGEND - AIR HANDLING
SYMBOL DESCRIPTION
SUPPLY AIR DUCT - UP
SUPPLY AIR DUCT - DOWN
RETURN AIR DUCT - UP
RETURN AIR DUCT - DOWN
FLAT-OVAL DUCT - TURNING TOWARD
FLAT-OVAL DUCT - TURNING AWAY
INCLINE RISE (R) OR DROP (D) IN DIRECTION OF ARROW
FLEXIBLE CONNECTION
ACCESS DOOR (AD) OR ACCESS PANEL (AP)
VOLUME DAMPER
FIRE DAMPER
SMOKE DAMPER
FIRE SMOKE DAMPER
MOTOR OPERATED DAMPER
BACKDRAFT DAMPER
FLEXIBLE DUCT
R
AP
AD
FD
OUTSIDE AIR DUCT - UP
OUTSIDE AIR DUCT - DOWN
EXHAUST AIR DUCT - UP
EXHAUST AIR DUCT - DOWN
SYMBOLS LEGEND - PIPING
SYMBOL DESCRIPTION
FLEXIBLE CONNECTION IN PIPING
MANUAL AIR VENT (MAV), AUTOMATIC AIR VENT (AAV)
PRESSURE GAUGE
THERMOMETER
THERMOMETER WELL
SIGHT GLASS
MAV AAV
STEAM TRAP ASSEMBLYS
X F/T = FLOAT AND THERMOSTATIC
IB = INVERTED BUCKET
T = THERMOSTATIC
I = IMPULSE
O = ORIFICE
PIPE ANCHOR
A
PIPE ALIGNMENT GUIDE
PIPE SUPPORT
PS
CONTROL VALVE STATION
FLOW METER
PIPE BREAK
FM
SYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMS
SYMBOL DESCRIPTION
PIPING OR DUCTED AIRFLOW
NON-DUCTED AIRFLOW
FLOW CONTINUATION ARROW
PUMP
FAN
ELECTRIC MOTOR/STARTER ASSEMBLY
ELECTRIC ACTUATOR (VALVE AND DAMPER)
FLOW DIRECTION
M
M
X SENSOR
T THERMOSTAT (T-STAT)
SD SMOKE DETECTOR
H HUMIDISTAT
CO2 CARBON DIOXIDE
CO CARBON MONOXIDE
NO2 NITROGEN DIOXIDE
SYMBOLS LEGEND - AIR HANDLING
SYMBOL DESCRIPTION
ROUND, 90° ELBOW, CENTERLINE RADIUS = 1.5 X DIA
RECTANGULAR, 90° ELBOW, CENTERLINE RADIUS = 1.5 X DUCT WIDTH
RECTANGULAR OR ROUND, 90° ELBOW,
CENTERLINE RADIUS = 1.5 X DUCT WIDTH
MITERED ELBOW WITH TURNING VANES
45° BRANCH CONNECTION
RECTANGULAR BRANCH TO RECTANGULAR DUCT
WITH TAPERED HIGH EFFICIENCY TAKE-OFF
ROUND OR RECTANGULAR DUCT WITH CONICAL TAKE-OFF TO
ROUND BRANCH DUCT
ROUND OR RECTANGULAR DUCT WITH CONICAL TAKE-OFF TO
ROUND BRANCH DUCT
TRANSITION OR REDUCER - NOTED FOT (FLAT ON TOP) OR FOB
(FLATON BOTTOM) IF REQUIRED
RECTANGULAR TO ROUND TRANSITION
MITERED ELBOW WITHOUT TURNING VANES
SYMBOLS LEGEND - AIR HANDLING
SYMBOL DESCRIPTION
THERMOSTAT
DOOR UNDERCUT
T
10x10 100A
DIFFUSER IDENTIFIER
CONNECTION SIZE
AIR FLOW (CFM)
DIFFUSER TYPE MARK
CEILING SUPPLY DIFFUSER
CEILING RETURN AND TRANSFER GRILLE
AIRFLOW, SUPPLY
AIRFLOW, RETURN AND EXHAUST
SIDEWALL GRILLE DIFFUSER
U
CEILING EXHAUST GRILLE
WALL EXHAUST GRILLE
LINEAR DIFFUSER
SYMBOLS LEGEND - PIPING VALVES
SYMBOL DESCRIPTION
CAP
UNION
WYE STRAINER
GATE VALVE
GLOBE VALVE
BALL VALVE
PLUG VALVE
NEEDLE VALVE
PRESSURE REDUCING VALVE
BALANCING / FLOW MEASUREMENT VALVE
RELIEF VALVE
CHECK VALVE
PIPE TURNING DOWN / AWAY
PIPE TURNING UP / TOWARDS
PIPE DOWN TEE / AWAY
PIPE UP TEE / TOWARDS
PLUG
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC
FLANGE
BUTTERFLY VALVE
ANGLE VALVE
WYE STRAINER WITH CAPPED HOSE END BLOWDOWN VALVE
BACKFLOW PREVENTER - DCVA OR RPBP
AUTOMATIC CONTROL VALVE - TWO WAY
M
AUTOMATIC CONTROL VALVE - THREE WAY
M
SYMBOLS LEGEND - CONTROL DIAGRAMS
SYMBOL DESCRIPTION
CONTROL POINT / SENSORX
ANALOG INPUTAI
ANALOG OUTPUTAO
DIGITAL INPUTDI
DIGITAL OUTPUTDO
COMMUNICATIONSCOM
AUXILLARY
ALARMA
START / STOPSS
CURRENT TRANSMITTERCT
CURRENT SENSORCS
TEMPERATURE SENSORT
DIFFERENTIAL PRESSURE SENSOR
SMOKE DETECTORSD
TEMPERATURE CONTROL VALVE
MODULATING ACTUATOR
HUMIDISTATH
CARBON DIOXIDE SENSOR
NITROUS DIOXIDE SENSOR
CARBON MONOXIDE SENSORCO
AUX
DPS
TCV
MOD
CO2
NO2
LOW VOLTAGE WIRING
SYMBOLS LEGEND - PIPING
SYMBOL DESCRIPTION
HIGH PRESSURE STEAMHPS
MEDIUM PRESSURE STEAMMPS
LOW PRESSURE STEAMLPS
HIGH PRESSURE CONDENSATEHPC
MEDIUM PRESSURE CONDENSATEMPC
LOW PRESSURE CONDENSATELPC
PUMPED CONDENSATEPC
HEATING WATER SUPPLYHWS
HEATING WATER RETURNHWR
CHILLED WATER SUPPLYCHS
CHILLED WATER RETURNCHR
CONDENSER WATER SUPPLYCWS
CONDENSER WATER RETURNCWR
COOLING COIL CONDENSATECND
REFRIGERANT SUCTIONRS
REFRIGERANT LIQUIDRL
NATURAL GASNG
PROPANELPG
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :3
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
MECHANICAL
LEGEND
M0.01
JS/CR
JG
DRAWING ISSUE
# DATE DESCRIPTION
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:0
:2
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
MECHANICAL
SCHEDULES
M1.00
JS/CR
JG
RTU-1 ROOFTOP MAIN AAON RN020 20 7800 0 YES 1 2.0 BACKWARD CURVED ALUMINUM 7.05 10 2 2.0 BACKWARD CURVED ALUMINUM 1.4 2 240 210 89 67 55 52 11.07 186 68 90 3.4 500 2" MERV 13 13 0.25 0.75 55 21.3 213 245 250 208/3/60 95 3636 1-5
QTY
EXT SP
(IN WG)
TYPE
FAN
(BHP)
EACH
MOTOR
(HP)
EACH
QTY
EXT SP
(IN WG)
TYPE
FAN
(BHP)
EACH
MOTO
R (HP)
EACH
TOTAL
LOAD
(MBH)
SENSIBL
E LOAD
(MBH)
EAT DB
(DEG F)
EAT WB
(DEG F)
LAT DB
(DEG F)
LAT WB
(DEG F)
LOAD COIL
EER
TOTAL
LOAD
(MBH)
EAT DB
(DEG F)
LAT DB
(DEG F)
COP
MAX
FACE
VEL
(FPM)
TYPE
MERV
RATING
INITIAL
PD
(IN WG)
FINAL PD
(IN WG)
KW FLA FLA MCA MOCP V/PH/HZ
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL
NOMINAL
CAP
(TONS)
SUPPLY
AIR
(CFM)
MIN
OUTSIDE
AIR
(CFM)
ECONOMIZER
SUPPLY FAN RETURN FAN
COOLING HEATING FILTERS ELEC HEAT ELECTRICAL
MAX
SOUND
PRESSURE
(dBA)
OPERATING
WEIGHT
(LBS)
REMARKS
5. PROVIDE MERV 13 FILTER ON SUPPLY AND RECIRCULATED AIR.
4. PROVIDE BACNET COMPATIBLE INTERFACE CARD.
3. PROVIDE HIGH EFFICIENCY UNIT WITH VARIABLE SCROLL COMPRESSOR. PROVIDE MODULATING HEAT PUMP WITH SCR CONTROL ELECTRIC HEAT.
2. PROVIDE FULL ECONMIZER WITH POWER RETURN. OUTSIDE AIR VENTILATION PROVIDED BY DOAS UNITS.
1. PROVIDE EXTENDED MANUFACTURER'S INSULATED ROOF CURB FOR HORIZONTAL DISCHARGE.
REMARKS:
PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE (HEAT PUMP)
WINTER 86.3 776 830 0.75 0.31 24 23 64.4 45.6 880 0.75 0.31 70 52.9 38.3 37.8
ERV-3 WORKROOM 111 OUTSIDE AIR OXYGEN8 H10 HRV
SUMMER 86.2 776 830 0.75 0.31 86 63.7 76.5 60.4 880 0.75 0.31 75 63 83.5 65.6
21.8 25 208/1/60 622 1
WINTER 80.9 938 1310 0.75 0.38 24 23 62.2 44.5 1160 0.75 0.38 70 52.9 38.1 37.7
ERV-2
MAIN COLLECTION
OUTSIDE AIR OXYGEN8 H15 HRV
SUMMER 80.8 938 1310 0.75 0.38 86 63.7 77.1 60.6 1160 0.75 0.38 75 63 83.6 65.7
28.9 30 208/1/60 718 1
WINTER 80.9 938 1310 0.75 0.38 24 23 62.2 44.5 1160 0.75 0.38 70 52.9 38.1 37.7
ERV-1 CHILDRENS 145 OUTSIDE AIR OXYGEN8 H15 HRV
SUMMER 80.8 938 1310 0.75 0.38 86 63.7 77.1 60.6 1160 0.75 0.38 75 63 83.6 65.7
28.9 30 208/1/60 718 1
AIRFLOW
(CFM)
ESP
(IN WG)
MOTOR
(W/CFM)
EAT DB
(DEG F)
EAT WB
(DEG F)
LAT DB
(DEG F)
LAT WB
(DEG F)
AIRFLOW
(CFM)
ESP
(IN WG)
MOTOR
(W/CFM)
EAT DB
(DEG F)
EAT WB
(DEG F)
LAT DB
(DEG F)
LAT WB
(DEG F)
MCA MOCP V/PH/HZ
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL MODE EFFICIENCY
AIR
VELOCITY
(FPM)
SUPPLY AIR EXHAUST AIR SINGLE POINT ELEC CONNECTION
WEIGHT
(LBS)
REMARKS
1. PROVIDE MERV 13 FILTERS ON OUTSIDE AIR SUPPLY TO BUILDING.
REMARKS:
ENERGY RECOVERY VENTILATOR SCHEDULE
UH-1 92 FIRE QMARK MUH03-81 3 1 350 14.5 20 208/1/60 27 1
MANUFACTURER SERIES FLA MOCP V/PH/HZ
EQUIP. NO LOCATION
BASIS OF DESIGN
CAPACITY
(KW)
NO. OF
STAGES
AIRFLOW
(CFM)
ELECTRICAL OPERATING
WEIGHT
(LBS)
REMARKS
1. PROVIDE SINGLE-STAGE LINE VOLTAGE PROGRAMMABLE WALL MOUNTED THERMOSTAT, UL LISTING, PRIMARY AND SECONDARY
OVER-TEMPERATURE PROTECTION, DISCONNECT PROVIDED BY CONTRACTOR.
REMARKS:
ELECTRIC UNIT HEATER SCHEDULE
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
RELIEF OR EXHAUST AIR CONDITIONED SPACE, DOWNSTREAM OF AN AUTO SHUTOFF DAMPER R-16
RETURN OR EXHAUST AIR CONDITIONED SPACE, DOWNSTREAM OF ENERGY RECOVERY MEDIA, UPSTREAM OF AN AUTO SHUTOFF DAMPER, CLIMATE ZONE 4C R-8
CONDITIONED SPACE, DOWNSTREAM OF ENERGY RECOVERY MEDIA, UPSTREAM OF AN AUTO SHUTOFF DAMPER, CLIMATE ZONE 4C R-8
CONDITIONED SPACE THAT THE DUCT DIRECTLY SERVES, DUCT AIR 55°F OR GREATER AND 105°F OR LESS NONESUPPLY AIR
CONDITIONED SPACE WHEREIN THE DUCT CONVEYS AIR, DUCT AIR LESS THAN 55°F OR GREATER THAN 105°F NONE
CONDITIONED SPACE, DUCT AIR LESS THAN 55°F OR GREATER THAN 105°F R-3.3
IN BUILDING ENVELOPE ASSEMBLY R-16
UNCONDITIONED SPACE, DUCT AIR WITHIN 15°F OF SURROUNDING AIR TEMP R-3.3
UNCONDITIONED SPACE R-6
SUPPLY OR RETURN AIR
OUTSIDE BUILDING, CLIMATE ZONE 4C R-8
CONDITIONED SPACE, LESS THAN 2800 CFM R-7
CONDITIONED SPACE DOWNSTREAM OF AUTO SHUTOFF DAMPER, CLIMATE ZONE 4C R-8OUTDOOR AIR
CONDITIONED SPACE, UPSTREAM OF AUTO SHUTOFF DAMPER, CLIMATE ZONE 4C MORE THAN 2800 CFM R-16
DUCT TYPE LOCATION MINIMUM R-VALUE
2. SEE SECTION C403.10.1.2 FOR DETAILS.
1. R-VALUES ASSUME ZONE 4C. SEE WSEC FOR ALTERNATE REGIONS.
REMARKS:
DUCT INSULATION SCHEDULE
RG-4 CEILING RETURN DIFFUSER TITUS 50F EGG-CRATE, SURFACE MOUNTED 25 1,3,5
RG-3 CEILING RETURN DIFFUSER TITUS OMNI 1-SLOT, 24X24 PLAQUE FACE, SURFACE MOUNTED 25 1,2,3
RG-2 CEILING RETURN DIFFUSER TITUS OMNI 1-SLOT, 12X12 PLAQUE FACE, SURFACE MOUNTED 25 1,2,3
RG-1 CEILING RETURN DIFFUSER TITUS DAT 1-SLOT, 24X24 PLAQUE FACE, LAY-IN 25 1,2,3
SG-1 WALL SUPPLY GRILLE TITUS 300RL DOUBLE DEFLECTION GRILLE 25 1,3,4
SL-2 WALL SUPPLY DIFFUSER TITUS FL LINEAR SLOT DIFFUSER, SIDEWALL OR CEILING MOUNTED, BORDER 55 30 1,3
SL-1 WALL SUPPLY DIFFUSER TITUS FL LINEAR SLOT DIFFUSER, SIDEWALL OR CEILING MOUNTED, BORDER 22 25 1,3
CD-3 CEILING SUPPLY DIFFUSER TITUS OMNI 1-SLOT, 24X24 PLAQUE FACE, SURFACE MOUNTED 25 1,2,3
CD-2 CEILING SUPPLY DIFFUSER TITUS OMNI 1-SLOT, 12X12 PLAQUE FACE, SURFACE MOUNTED 25 1,2,3
CD-1 CEILING SUPPLY DIFFUSER TITUS DAT 1-SLOT, 24X24 PLAQUE FACE, LAY-IN 25 1,2,3
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL DESCRIPTION MAX NC REMARKS
5. STEEL, WHITE, 1/2"X1/2"X1/2" GRID
4. STEEL, WHITE, 3/4" BLADE SPACING
3. BORDER TO MATCH CEILING/WALL TYPE
2. STEEL, WHITE, ROUND NECK, SEE MECHANICAL FLOOR PLANS FOR NECK SIZE
1. SEE MECHANICAL FLOOR PLANS FOR DUCT SIZE AND CFM
REMARKS:
DIFFUSER-GRILLE SCHEDULE
S-2 RTU-1 RETURN RETURN RISER IAC QUIET DUCT 46X22 7800 0.24 -1100 9 15 26 31 30 17 15 13
S-1 RTU-1 SUPPLY SUPPLY RISER IAC QUIET DUCT 46X22 7800 0.24 1100 8 13 23 29 28 17 14 13
63 125 250 500 1000 2000 4000 8000
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL
SIZE
HxWxL
(IN)
AIRFLOW
(CFM)
MAX PD
(IN WG)
VELOCITY
(FPM)
DYNAMIC INSERTION LOSS BY OCTAVE BAND
OPERATING
WEIGHT
(LBS)
REMARKS
REMARKS:
SOUND ATTENUATOR SCHEDULE
03/25/2026
3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :4
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
MECHANICAL
SCHEDULES
M1.01
JS/CR
JG
1. SEE 2021 WSEC TABLE C403.10.3 FOR ALTERNATE THICKNESSES/CONDUCTIVITY RANGES.18
REMARKS:
< 40 0.20-0.26 50 0.5 1.0 1.0 1.0 1.5
40-60 0.21-0.27 75 0.5 0.5 1.0 1.0 1.0
105-140 0.21-0.28 100 1.0 1.0 1.5 1.5 1.5
141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0
201-250 0.27-0.30 150 2.5 2.5 2.5 3.0 3.0
251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 4.5
> 350 0.32-0.34 250 4.5 5.0 5.0 5.0 5.0
CONDUCTIVITY
MEAN RATING
TEMPERATURE (°F)
<1 1 TO <1-1/2 1-1/2 TO 4 4 TO 8 ≥8
FLUID OPERATING
TEMPERATURE (°F)
INSULATION CONDUCTIVITY NOMINAL PIPE SIZE (IN.)
MINIMUM PIPE INSULATION THICKNESS
FC-11 VESTIBULE SOUTH VESTIBULE SOUTH ENVIROTECH HDD BCU 16 1340.0 1.25 1402 1 1/2 644 30.4 33.4 8.1 1 1/8" 2.1 45 55 75 67 55 54.8 29.8 7.2 5/8" 2.5 125 110 65 90 11.75 9.4 20 208/1/60 337 1,2
FC-10 WORKROOM WORKROOM ENVIROTECH HDD BCU 16 1430.0 1.25 1430 1 1 710 30.8 35.6 8.6 1 1/8" 2.2 45 55 75 67 55 54.8 16.3 3.9 5/8" 2.3 125 110 65 90 11.75 9.4 20 208/1/60 325 1,2
FC-09 EAST OFFICES OFFICE 1 / OFFICE 2 / ENTRY /... ENVIROTECH HDD BCU 16 1165.0 1.25 1287 1 1/2 494 24.3 29.0 7.0 7/8" 7.8 45 55 75 67 55 54.8 6.3 1.5 5/8" 8.4 125 110 65 90 6.25 5 15 208/1/60 278 1,2
FC-08 BREAK ROOM BREAK ROOM ENVIROTECH HDD BCU 08 505.0 1.15 1398 1 1/2 236 10.0 12.5 3.0 5/8" 7.3 45 55 75 67 55 54.8 7.8 1.9 5/8" 1.5 125 110 65 90 6.25 5 15 208/1/60 215 1,2
FC-07 PUBLIC MEETING PUBLIC MEETING / STORAGE ENVIROTECH HDD BCU 16 1170.0 1.25 1288 1 1/2 497 20.8 29.1 7.0 7/8" 7.8 45 55 75 67 55 54.8 14.5 3.5 5/8" 8.4 125 110 65 90 6.25 5 15 208/1/60 278 1,2
FC-06 VESTIBULE NORTH VESTIBULE NORTH ENVIROTECH HDD BCU 12 490.0 1.20 1152 1 1/2 206 8.8 12.2 3.0 7/8" 4.0 45 55 75 67 55 54.8 24.1 5.8 5/8" 1.2 125 110 65 90 6.25 5 15 208/1/60 256 1,2
FC-05 COMMUNITY ROOM STUDY 1 / STUDY 2 ENVIROTECH HDD BCU 08 400.0 1.25 1400 1 1/2 224 8.6 9.9 2.4 5/8" 2.8 45 55 75 67 55 54.8 0.9 0.2 5/8" 1.4 125 110 65 90 6.25 5 15 208/1/60 215 1,2
FC-04 COMMUNITY ROOM COMMUNITY ROOM / OFFICE ENVIROTECH HDD BCU 16 855.0 1.25 1232 1 1/2 331 16.9 21.3 5.2 7/8" 6.0 45 55 75 67 55 54.8 9.2 2.2 5/8" 3.4 125 110 65 90 6.25 5 15 208/1/60 278 1,2
FC-03 TEENS TEENS ENVIROTECH HDD BCU 08 415.0 1.25 1361 1 1/2 214 6.9 10.2 2.5 7/8" 2.0 45 55 75 67 55 54.8 19.1 4.6 5/8" 5.3 125 110 65 90 6.25 5 15 208/1/60 215 1,2
FC-02 TEEN STUDY TEEN STUDY / STORAGE ENVIROTECH HDD BCU 16 770.0 1.25 1214 1 1/2 292 12.9 19.2 4.6 7/8" 7.2 45 55 75 67 55 54.8 6.6 1.6 5/8" 5.5 125 110 65 90 6.25 5 15 208/1/60 278 1,2
FC-01 PROGRAM ROOM PROGRAM ROOM / STORAGE ENVIROTECH HDD BCU 16 925.0 1.25 1239 1 1/2 359 17.9 23.0 5.6 7/8" 8.7 45 55 75 67 55 54.8 5.0 1.2 5/8" 3.6 125 110 65 90 6.25 5 15 208/1/60 278 1,2
AIRFLOW
(CFM)
ESP
(IN WG)
RPM
MOTOR
QTY
MOTOR SIZE
(HP)
MOTOR
WATTS
SENSIBLE LOAD
(MBH)
TOTAL LOAD
(MBH)
WATER FLOW RATE
(GPM)
COIL CONN.
(IN.)
MAX PD
(FT)
EWT
(DEG F)
LWT
(DEG F)
EAT DB
(DEG F)
EAT WB
(DEG F)
LAT DB
(DEG F)
LAT WB
(DEG F)
TOTAL LOAD
(BTUH)
WATER FLOW RATE
(GPM)
COIL CONN.
(IN.)
MAX PD
(FT)
EWT
(DEG F)
LWT
(DEG F)
EAT DB
(DEG F)
LAT DB
(DEG F)
MCA FLA MAX FUSE V/PH/HZ
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL
FAN COOLING COIL HEATING COIL ELECTRICAL OPERATING
WEIGHT
(LBS)
REMARKS
2. SELECT TERMINAL UNIT ORIENTATION FOR CODE AND MANUFACTURER REQUIRED ACCESS AND CLEARANCE REQUIREMENTS. ORIENTATION SELECTION TO BE SUBMITTED WITH CONTRACTOR SHOP DRAWINGS.
1. EXTERNAL STATIC PRESSURE INCLUDES AN ALLOWANCE OF 0.75 IN.W.G. FOR DIRTY FILTERS.
REMARKS:
FOUR PIPE FAN COIL UNIT SCHEDULE
AS-2 MECH ROOM HEATING WATER TACO 4902AT NPT 2.5 60 2.5 150 THREADED 2.5 16.5 30
AS-1 MECH ROOM CHILLED WATER TACO 4902AT NPT 2.5 75 2.5 150 THREADED 2.5 16.5 30
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL TYPE SIZE (IN)
MAX FLOW
(GPM)
PRESSURE DROP
(FT)
MAX OPERATING PRESSURE
(PSIG)
CONNECTION TYPE
DIA
(IN)
HEIGHT
(IN)
OPERATING
WEIGHT (LBS)
REMARKS
REMARKS:
AIR SEPARATOR SCHEDULE
PF-1 MECH ROOM WATER TREATMENT WESSEL CPFTA-5 5
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL
CAPACITY
(GAL)
OPERATING WEIGHT
(LBS)
REMARKS
1.
REMARKS:
POT FEEDER SCHEDULE
DRAWING ISSUE
# DATE DESCRIPTION
9 12/11/2025 Correction Cycle #2
11 2026/03/25 BID SET
BT-2 MECH ROOM HHW TACO MPT A NOZZLES @180 DEG 150 300 4 36 99 3 2 1/2 1,2,3,4
BT-1 MECH ROOM CHW TACO MPT A NOZZLES @180 DEG 150 300 4 36 99 3 2 1/2 1,2,3,4
DIA
(IN)
LENGTH/
HEIGHT (IN)
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL TYPE
MAX
OPERATING
PRESS
(PSIG)
TANK
VOLUME
(GAL)
# OF
NOZZLES
DIMENSIONS
NOZZLE SIZE (IN)
SYSTEM PIPING
CONNECTIONS
(IN)
REMARKS
4. PROVIDE ANCHOR CLIPS.
3. PROVIDE FACTORY 2" INSULATION SILICON/FIBERGLASS.
2. 3/4" NPTTEMPERATURE AND PRESSURE PORTS LOCATED AT TANK AND AT EACH NOZZLE QTY (5).
1. FLANGED CONNECTIONS.
REMARKS:
BUFFER TANK SCHEDULE
HP-1 ROOFTOP MECH WELL HHW/CHW WATER FURNACE 900 TRUE CLIMATE 348 88 95 67 55 17 9.5/11.0 249 45 17 100 125 6 1.9 2 152 138 175 208/3/60 R454B 2398 1,2,3,4,5,6,7,8
TOTAL
(MBH)
WATER
FLOW
(GPM)
AMBIENT TEMP
(DEG F)
EWT
(DEG F)
LWT
(DEG F)
WTR PD
(FT)
EER/IPLV
TOTAL
(MBH)
WATER FLOW
(GPM)
AMBIENT
TEMP
(DEG F)
EWT
(DEG F)
LWT
(DEG F)
MAX
WTR PD
(FT)
COP QTY
MAX INPUT
(KW/TON)
MCA FLA MOCP V/PH/HZ
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL
COOLING CAPACITY HEATING CAPACITY COMPRESSOR ELECTRICAL
REFRIGERANT
(TYPE)
OPERATING
WEIGHT
(LBS)
REMARKS
8. PROVIDE HOT AND COLD HYDRONIC STRAINERS.
7. PROVIDE HOT AND COLD TEMPERATURE HEADERS.
6. PROVIDE HOT AND COLD BYPASS HEADERS.
5. PROVIDE MOUNTING SKID.
4. PROVIDE HYDROLINK CONTROLLER.
3. PROVIDE SEISMIC VIBRATION ISOLATION .
2. PROVIDE LOW AMBINET SPEED CONTROL.
1. CONFIGURE TO PROVIDE HEATED AND CHILLED WATER FOR 4 PIPE HYDORNIC SYSTEM.
REMARKS:
AIR TO WATER HEAT PUMP SCHEDULE
ET-2 MECH... CHILLED WATER TACO CA90-150 BLADDER 125 23 23 20 30 1 -
ET-1 MECH... HEATING... TACO CA90-150 BLADDER 125 23 23 20 30 1 -
EQUIP NO LOCATION SERVICE
MANUFACTURE
R
MODEL TYPE
MAX
OPERATIN...
TANK
VOLU...
MAX
ACCEPTANC...
REQUIRED AIR
CHARGE...
DIA
(IN)
LENGTH/
HEIGH...
SYSTEM
CONNECTI...
REMARK
S
REMARKS:
EXPANSION TANK SCHEDULE
RCP-1 MECH ROOM DHWC TACO IL0011 INLINE CIRC 17 15 65 NA 2 1-1/2 1-1/2 - 1/8 115/1/60 SPEED CONTROL 1,5
BCP-1 MECH ROOM HHW / BOILER TACO IL133 INLINE CIRC 22 25 65 NA 3 1-1/2 1-1/2 - 3/4 115/1/60 SPEED CONTROL 1,5
P-8 MECH ROOM HHW SECONDARY TACO SKS INLINE VERTICAL 40 65 65 40 6 2 2 1.7 2 208/3/60 YES-PUMP MOUNTED 1,3,5
P-7 MECH ROOM HHW SECONDARY TACO SKS INLINE VERTICAL 40 65 65 40 6 2 2 1.7 2 208/3/60 YES-PUMP MOUNTED 1,3,5
P-6 MECH ROOM CHW SECONDARY TACO SKS INLINE VERTICAL 75 65 65 75 6 2.5 2.5 2 3 208/3/60 YES-PUMP MOUNTED 1,3,5
P-5 MECH ROOM CHW SECONDARY TACO SKS INLINE VERTICAL 75 65 65 75 6 2.5 2.5 2 3 208/3/60 YES-PUMP MOUNTED 1,3,5
P-4 MECH ROOM HHW PRIMARY TACO SKS INLINE VERTICAL 40 40 65 40 6 2 2 1.7 2 208/3/60 YES-PUMP MOUNTED 1,3,5
P-3 MECH ROOM HHW PRIMARY TACO SKS INLINE VERTICAL 40 40 65 40 6 2 2 1.7 2 208/3/60 YES-PUMP MOUNTED 1,3,5
P-2 MECH ROOM CHW PRIMARY TACO SKS INLINE VERTICAL 75 40 65 75 6 2.5 2.5 2.5 3 208/3/60 YES-PUMP MOUNTED 1,3,5
P-1 MECH ROOM CHW PRIMARY TACO SKS INLINE VERTICAL 75 40 65 75 6 2.5 2.5 2.5 3 208/3/60 YES-PUMP MOUNTED 1,3,5
SPEED
(RPM)
HP V/PH/HZ
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL TYPE
DESIGN
FLOW
(GPM)
HEAD
(FT)
PUMP
EFFICIENCY
MIN
FLOW
(GPM)
NET
POSITIVE
SUCTION
HEAD
(FT)
DISCHARGE
SIZE
(IN)
SUCTION
SIZE
(IN)
PUMP
BHP
MOTOR
VFD
WEIGHT
(LBS)
REMARKS
5. BALANCE CONTRACTOR TO ACHIEVE FLOW AS INDICATED BY VARYING PUMP SPEED.
4. SUPPORT VERTICAL PUMP PER INSTALLATION DETAILS ON DRAWINGS.
3. PROVIDE AND INSTALL SUPPORT BASE PER INSTALLATION DETAILS ON MECHANICAL DRAWINGS AND AS SPECIFIED.
2. PROVIDE FACTORY MOUNTED SPEED CONTROLLER.
1. PROVIDE WITH A SUCTION DIFFUSER TO ACCOMMODATE SUCTION CONNECTION SIZE AND PIPE SIZE INDICATED ON DRAWINGS.
REMARKS:
HYDRONIC PUMP SCHEDULE
B-1 MECH ROOM SUPPLEMENTAL HEAT AOSMITH DVE-120 ELECTRIC 45 22 5 110 125 120 125 208/3/60 390 1350 1,2,3
FLA V/P/HZ SHIPPING... OPERATING...
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL FUEL TYPE
SIZE
(KW)
WATER FLOW
(GPM)
PD
(FT)
EWT
(DEG F)
LWT
(DEG F)
WATER
STORAGE
(GAL)
ELECTRICAL WEIGHT
REMARKS
3. PROVIDE AND INSTALL LINE FROM DRAIN CONNECTION TO FLOOR DRAIN
2. PROVIDE LINE SIZE FROM PRV TO FLOOR DRAIN OR FUNNEL DRAIN
1. PROVIDE HOUSEKEEPING PAD
REMARKS:
BOILER SCHEDULE
3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :4
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
MECHANICAL
SCHEDULES
M1.02
JS/CR
JG
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
TC-17 TEENS PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 10.5 2.20 0.40 45 55 80 67 7.2 1.02 0.13 125 110 68 57 - - 24VDC 110
TC-16 TEENS PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 10.5 2.20 0.40 45 55 80 67 7.2 1.02 0.13 125 110 68 57 - - 24VDC 110
TC-15 TEENS PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 10.5 2.20 0.40 45 55 80 67 7.2 1.02 0.13 125 110 68 57 - - 24VDC 110
TC-14 CHILDRENS CORNER PERIMETER HEATING/COOLING JAGA CLIMA CANAL 13-T180 235 1300 20 4.6 6.5 1.37 1.30 45 55 80 67 3.4 0.48 1.30 125 110 68 57 - - 24VDC 64
TC-13 CHILDRENS CORNER PERIMETER HEATING/COOLING JAGA CLIMA CANAL 13-T180 235 1300 20 4.6 6.5 1.37 1.30 45 55 80 67 3.4 0.48 1.30 125 110 68 57 - - 24VDC 64
TC-12 CHILDRENS CORNER PERIMETER HEATING/COOLING JAGA CLIMA CANAL 13-T180 235 1300 20 4.6 6.5 1.37 1.30 45 55 80 67 3.4 0.48 1.30 125 110 68 57 - - 24VDC 64
TC-11 CHILDRENS CORNER PERIMETER HEATING/COOLING JAGA CLIMA CANAL 13-T160 205 1300 18 3.7 5.2 1.09 0.65 45 55 80 67 2.7 0.38 0.65 125 110 68 57 - - 24VDC 57
TC-10 CHILDRENS CORNER PERIMETER HEATING/COOLING JAGA CLIMA CANAL 13-T180 235 1300 20 4.6 6.5 1.37 1.30 45 55 80 67 3.4 0.48 1.30 125 110 68 57 - - 24VDC 64
TC-09 CHILDRENS CORNER PERIMETER HEATING/COOLING JAGA CLIMA CANAL 13-T180 235 1300 20 4.6 6.5 1.37 1.30 45 55 80 67 3.4 0.48 1.30 125 110 68 57 - - 24VDC 64
TC-08 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-120 235 1300 24 4.7 6.8 1.43 0.29 45 55 80 67 3.3 0.46 0.10 125 110 68 57 - - 24VDC 63
TC-07 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 13.3 2.80 0.40 45 55 80 67 6.4 0.90 0.13 125 110 68 57 - - 24VDC 110
TC-06 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-120 235 1300 24 4.7 6.8 1.43 0.29 45 55 80 67 3.3 0.46 0.10 125 110 68 57 - - 24VDC 63
TC-05 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-120 235 1300 24 4.7 6.8 1.43 0.29 45 55 80 67 3.3 0.46 0.10 125 110 68 57 - - 24VDC 63
TC-04 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 13.3 2.80 0.40 45 55 80 67 6.4 0.90 0.13 125 110 68 57 - - 24VDC 110
TC-03 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-120 235 1300 24 4.7 6.8 1.43 0.29 45 55 80 67 3.3 0.46 0.10 125 110 68 57 - - 24VDC 63
TC-02 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 13.3 2.80 0.40 45 55 80 67 6.4 0.90 0.13 125 110 68 57 - - 24VDC 110
TC-01 ADULT PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-200 440 1300 39 9.3 13.3 2.80 0.40 45 55 80 67 6.4 0.90 0.13 125 110 68 57 - - 24VDC 110
TC-B2 TEENS PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-105 - - - - - - - - - - - - - - - - - - - - - 55 1
TC-B1 TEENS PERIMETER HEATING/COOLING JAGA CLIMA CANAL 19-105 - - - - - - - - - - - - - - - - - - - - - 55 1
AIRFLOW
(CFM)
RPM
MOTOR
(W)
SENSIBLE LOAD
(MBH)
TOTAL
LOAD (MBH)
WATER
FLOW RATE
(GPM)
MAX PD
(FT)
EWT
(DEG F)
LWT
(DEG F)
EAT DB
(DEG F)
EAT WB
(DEG F)
TOTAL
LOAD
(BTUH)
WATER
FLOW RATE
(GPM)
MAX PD
(FT)
EWT
(DEG F)
LWT
(DEG F)
EAT DB
(DEG F)
LAT DB
(DEG F)
MCA MOCP V/PH/HZ
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL
FAN COOLING COIL HEATING COIL ELECTRICAL OPERATI
NG
WEIGHT
(LBS)
REMARKS
1. EMPTY TRENCH FOR CONTINUOUS INSTALLATION IN TEENS AREA.
REMARKS:
FOUR PIPE TRENCH COIL UNIT SCHEDULE
BF-1 STACKS MIXING / DESTRATIFICATION BIG ASS FAN ESSENCE 8' CEILING MOUNTED 6,223 - DIRECT 31.7 10 431 W 115/1/60 75
EF-3 CUSTODIAL EXHAUST GREENHECK CSP-A390-VG CEILING MOUNTED 150 0.5 DIRECT 1220 1.42 30 W 115/1/60 24 1,2
EF-2 ELEC ROOM EXHAUST GREENHECK CSP-A390-VG CEILING MOUNTED 300 0.5 DIRECT 1356 1.5 71 W 115/1/60 24 1,3
EF-1 TELECOM EXHAUST GREENHECK CSP-A390-VG CEILING MOUNTED 300 0.5 DIRECT 1356 1.5 71 W 115/1/60 24 1,3
MANUFACTURER SERIES CFM INCHES W.G. FLA SIZE (W OR HP) V/PH/HZ
EQUIP NO. LOCATION SERVICE
BASIS OF DESIGN
TYPE
VOLUME STATIC PRESSURE
DRIVE TYPE FAN RPM
MOTOR OPERATING WEIGHT
(LBS)
REMARKS
3. FAN MOTOR PROVIDED WITH VARI-GREEN DRIVE TO MEET FRACTIONAL MOTOR HORSEPOWER REQUIREMENTS PER 2021 WASHINGTON STATE ENERGY CODE.
2. FAN MOTOR HP BELOW 1/12 (62 W), TOTAL MOTOR HP COMPLIANCE NOT REQUIRED.
1. PROVIDE VIBRATION ISOLATORS, TIME DELAY SWITCH.
REMARKS:
FAN SCHEDULE
15,984 245 1,325 1,355 2,680 2,680 3,450 550
ERV-1 153 STOR 68 - 0 - - 0.12 8.2 8 1.0 8 15 - 0
ERV-1 152 TEEN STUDY RM 546 50 20 5 100 0.06 32.8 133 1.0 133 170 0 0
NA 151 TELECOM 84 - 0 - - - - 0 1.0 0 0 - 0
ERV-2 150 TEENS 472 10 10 5 50 0.12 56.6 107 1.0 107 140 - 0
ERV-1 147 STOR 96 - 0 - - 0.12 11.5 12 1.0 12 20 - 0
ERV-1 146 PROGRAM RM 534 50 20 5 100 0.06 32.0 132 1.0 132 170 0 0
ERV-1 145 CHILDRENS 1,121 10 20 5 100 0.12 134.5 235 1.0 235 295 - 0
ERV-1 140 ADULTS 1,287 10 25 5 125 0.12 154.4 279 1.0 279 350 - 0
NA 136 CHILDREN RR 83 - 0 - - - - 0 1.0 0 0 50/70 ( e) 100
ERV-2 135 SENSORY RM 154 50 5 5 25 0.06 9.2 34 1.0 34 45 0 0
ERV-2 134 OFFICE 119 5 2 5 10 0.06 7.1 17 1.0 17 25 0 0
ERV-2 133 COMMUNITY RM 355 50 12 5 60 0.06 21.3 81 1.0 81 110 0 0
ERV-2 132 STUDY 2 122 50 4 5 20 0.06 7.3 27 1.0 27 40 0 0
ERV-2 131 STUDY 1 142 50 4 5 20 0.06 8.5 29 1.0 29 40 0 0
ERV-1/ERV-2 130 MAIN COLLECTION 4,856 10 50 5 250 0.12 582.7 833 1.0 833 1,040 - 0
NA 121 CUST 76 - 0 - - - - 0 1.0 0 0 - 0
NA 120 STAFF RR 77 - 0 - - - - 0 1.0 0 0 50/70 ( e) 50
ERV-3 119 WELLNESS RM 94 5 2 5 10 0.06 5.6 16 1.0 16 25 0 0
NA 118 MECH 185 - 0 - - - - 0 1.0 0 0 - 0
NA 117 ELEC 64 - 0 - - - - 0 1.0 0 0 - 0
ERV-3 116 BREAK RM 272 5 5 5 25 0.06 16.3 41 1.0 41 60 0 0
ERV-3 114 OFFICE 2 130 5 2 5 10 0.06 7.8 18 1.0 18 25 0 0
ERV-3 113 OFFICE 1 129 5 2 5 10 0.06 7.7 18 1.0 18 25 0 0
ERV-3 112 STOR 106 - 0 - - 0.12 12.7 13 1.0 13 20 - 0
ERV-3 111 WORKROOM 1,807 5 12 5 60 0.06 108.4 168 1.0 168 215 0 0
NA 108 MENS RR 217 - 0 - - - - 0 1.0 0 0 50/70 ( e) 150
NA 107 WOMENS RR 215 - 0 - - - - 0 1.0 0 0 50/70 ( e) 150
NA 106 RR 84 - 0 - - - - 0 1.0 0 0 50/70 ( e) 50
NA 105 RR 83 - 0 - - - - 0 1.0 0 0 50/70 ( e) 50
ERV-3 104 STOR 88 - 0 - - 0.12 10.6 11 1.0 11 20 - 0
ERV-3 103 PUBLIC MEETING 777 65 40 8 300 0.06 46.6 347 1.0 347 440 - 0
NA 102 VEST 168 - 0 - - - - 0 1.0 0 0 - 0
ERV-2 101 LOBBY 1,206 10 10 5 50 0.06 72.4 122 1.0 122 160 0 0
NA 100 VEST 168 - 0 - - - - 0 1.0 0 0 - 0
Az Pz Rp Vbzp Ra Vbza Vbz Ez Voz Vot
VENTILATOR ROOM NUMBER ROOM NAME
TOTAL AREA
(SQFT)
DEFAULT OCCUPANT
DENSITY #/1,000 SQFT
ZONE NO.
OF PEOPLE
CFM PER
PERSON
Rp*Pz
(CFM)
CFM PER
SQFT
Ra*Rz
(CFM)
Vbzp+Vbza
(CFM)
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
Voz=Vbz/Ez
(CFM)
SCHEDULED OUTDOOR
AIRFLOW (CFM)
REQUIRED EXHAUST
AIRFLOW RATE (CFM)
SCHEDULED EXHAUST
AIRFLOW (CFM)
REQUIRED OUTSIDE AIR FLOW RATE
ERV-1
CC
DD
AA
EE
24X14 24X12
(TYP 4)
FC-02
34X1434X14
6"Ø
FC-03
24X12 24X12
10"Ø
X
14 10"Ø
10"Ø 10"Ø
FC-04
24X1224X12
FF
CD-1
6"Ø
12"Ø
385RG-1
CD-1
8"Ø
CD-1
6"Ø
8X8
100RG-4
(TYP 2)
"Ø
X
CD-2
6"Ø
UH-1
12"Ø
14X14
585RG-2
CD-1
6"Ø
FD
CD-1
6"Ø
T FC-08
12"Ø
405RG-1
CD-3
10X10
EF-2
T
"Ø
"Ø
CD-1
8"Ø
CD-1
10"Ø
300 CD-1
10"Ø
"Ø
CD-3
12X12
8X8
50RG-4
(TYP 2)
FC-07
EF-2
CD-1
6"Ø
CD-1
8"Ø
(TYP 2)
22X22
500RG-1
CD-1
10"Ø
230 CD-1
10"Ø
230CD-1
10"Ø
CD-1
10"Ø
CD-1
8"Ø
CD-1
10"Ø
46X22 SA UP
CD-1
10"Ø
CD-1
6"Ø
CD-1
8"Ø
22X22
680RG-1
8"Ø 8" Ø
"Ø
22X22
175RG-1
T
CD-1
8"Ø
CD-1
8"Ø
200TFC-09
20X30
28X2422"Ø
(TYP 2)
(TYP 2)
TC-09TC-10
TC-12
TC-13
CD-3
12X12
CD-2
6"Ø
CD-2
6"Ø
CD-1
8"Ø
"Ø
8X8
200RG-2
X
"Ø
GG
1.3
1.3
1.7
1.7
9.1
9.1
12"Ø
8" Ø
TC-06 TC-03 TC-02 TC-01
TC-16 TC-17TC-15
T
FC-01
CD-1
6"Ø
CD-3
10X10
10X10
325CD-4
TC-14
TC-11
BF-1
CD-3
12X12
CD-1
6"Ø
(TYP 2)
(TYP 2)
14"Ø
14"Ø
"Ø
8"Ø
"Ø
8X8
190RG-2CD-3
8X8
8"Ø
190RG-1
10X10
315RG-2
CD-1
6"Ø
8" Ø
CD-1
6"Ø
24X24
580RG-1
(TYP 2)
EF-1
T EF-1
16X12
300RG-2
8" Ø
8"Ø
14"Ø
225SL-1
(TYP 28)
TC-07 TC-04
CD-2
6"Ø
TC-05TC-08
TC-B1 TC-B2
"Ø
48-1-1.0"
14X10 70% FREE AREA
SCREENED RETURN AIR
OPENING, 240 CFM (TYP 5)
(TYP 2)
T
FC-05
CD-3
10X10
8" Ø
"Ø
8" Ø
8" Ø
8" Ø
46X22
RA UP
6"Ø
10"Ø
6" Ø
6"Ø
8"Ø
"Ø
"Ø
"Ø
"Ø
"Ø
16"Ø
8" Ø
8" Ø
8"Ø
X
12"Ø
12"Ø
415RG-3 CD-3
10X10
6" Ø
46X22
12"Ø
T
FC-10
10"Ø
10X10
215RG-2
6"Ø
14"Ø
12"Ø
410RG-1
20X14
X
8X8
50RG-4
CD-1
6"Ø
T T FC-03FC-02
EF-3
16"Ø
BB
14X6 70% FREE AREA
SCREENED RETURN AIR
OPENING, 200 CFM (TYP 3)
"Ø
X
X
(TYP 2)
X
X
14X6
14X6
10"Ø
8"Ø
14X10 70% FREE AREA
SCREENED RETURN AIR
OPENING, 230 CFM (TYP 5)
16X12 70% FREE AREA
SCREENED RETURN AIR
OPENING, 300 CFM
14X6 70% FREE AREA
SCREENED RETURN AIR
OPENING, 135 CFM (TYP 5)
300SL-2
600SL-2
SD
(TYP 4)
6"Ø
20"Ø
1950RG-1
(TYP 4)
X
X
24X1224X12
FC-05
10"Ø
10"Ø
12"Ø
10"Ø
X
FC-07
24X12
FC-08
8" Ø
6"Ø
24X12
6" Ø
(TYP 2)
X
CD-1
10"Ø
10"Ø 8"Ø
24X24
585RG-1
FC-09
FC-10
FC-11
10"Ø
22X6
FC-04
T
8X8
50RG-4
ERV-2
ERV-1
X
22X10
"Ø
10"Ø
14"Ø
ERV-3
"Ø
48-1-3.0"
48-1-1.5"
T
T
"Ø
46X22
X
SL-1
SL-2
12"Ø
FC-06
M
MM
M
M M
M
M
T
10"Ø
M3.00
CO₂
CO₂
CO₂
CO₂
CO₂ CO₂
CO₂
10"Ø
M
CD-3
10X10
CD-3
12X12
12"Ø
FC-01
12X12
460RG-2
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/2
/2
:0
:0
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
HVAC FLOOR PLAN
M2.01
JS/CR
JG
1. INSTALL TEMPERATURE SENSOR FOR HP-1 IN RETURN AIR PATHWAY.
FLAG NOTES #SHEET NOTES
A. INSULATE PIPING AND DUCTWORK ACCORDING TO INSULATION SCHEDULES.
B. ALL SUPPLY AND RETURN GRILLES, REGISTERS AND DIFFUSERS INSTALLED IN
GYPSUM, GYPSORB OR OTHER HARD LID INACCESSIBLE CEILING TYPES
REQUIRE CABLE OPERATED DAMPERS OR EQUIVALENT MEANS TO BALANCE
AIRFLOW. SEE GRD SCHEDULE.
C. PROVIDE ALL THERMOSTATS IN PUBLICLY ACCESSIBLE AREAS WITH
TAMPERPROOF ENCLOSURE.
D. MOUNT CARBON DIOXIDE SENSORS AT 48" AFF ADJACENT TO THERMOSTAT
(IF PRESENT). CONFIRM FINAL LOCATION ON WALL WITH ARCHITECT PRIOR TO
INSTALLATION.
0' 8' 16'
2.
8"Ø
CD-2 200
4. 16X16 TRANSFER AIR OPENING ABOVE HALLWAY CEILING.
5. OUTSIDE AIR DUCT TO ROOF HOOD.
6. EXHAUST AIR DUCT TO ROOF HOOD.
7. 1" SOUNDLINER FROM OUTLET OF SUPPLY DUCT SILENCER IN VERTICAL
RISER THROUGH FULL EXTENT OF 46X22 DUCT.
8. 1" SOUNDLINER THROUGH SECOND ELBOW UPSTREAM OF RETURN DUCT
SILENCER IN VERTICAL RISER.
3.
6"Ø
CD-2 40
PLAN | SCALE: 1/8" = 1'-0"
HVAC FLOOR PLAN
DRAWING ISSUE
# DATE DESCRIPTION
03/25/2026
AA
EE
FF
HP-1
RTU-1
50X21 RA CONNECTION
TRANSITION TO 46X22 RA DN
48X34 SA CONNECTION
TRANSITION TO 46X22 RISER DN
GG
1.3
1.3
1.7
1.7
9.1
9.1
BB
M4.01
TYP
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :5
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
HVAC ROOF PLAN
M2.03
JS/CR
JG
FLAG NOTES #SHEET NOTES
A. INSULATE PIPING AND DUCTWORK ACCORDING TO INSULATION SCHEDULES.
PLAN | SCALE: 1/8" = 1'-0"
HVAC ROOF PLAN
0' 8' 16'
DRAWING ISSUE
# DATE DESCRIPTION
9.1
9.1
2" HWR
2 1/2" CHWS
2 1/2" CHWR
2 1/2" CHWS
1" CW
2" HWR
2" HWS
1 1/4" HWS
1 1/4" HWS
2" H
W S
2" HWS
ET-2
BT-2
BT-1
B-1
ET-1
2" HWS
2 1/2" CHWR
2 1/2" CHWS
P-7 P-8
P-5
P-1
P-3 P-4
P-6
P-2
BCP-1
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :5
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
HVAC ENLARGED
PLANS
M3.00
JS/CR
JG
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
PLAN | SCALE: 3/4" = 1'-0"
ENLARGED HVAC PIPING - MECHANICAL ROOM
NOTES:
1. SIMILAR FOR NON-INSULATED PIPE AND CONDUIT.
2. SIMILAR FOR MASONRY OR CONCRETE WALL EXCEPT CORE DRILL OR CAST IN PLACE.
3. APPLIES FOR PLUMBING, HVAC, AND FIRE PROTECTION..
ESCUTCHEON PLATE WHERE
EXPOSED, COORDINATE WITH
ARCHITECT
INTERIOR STUD WALL
16 GA. GALV. STEEL SLEEVE SECURE
TO PARTITION - GROUT TIGHT
PIPE W/ OR W/OUT INSULATION
EXTERIOR SURFACE
16 GA. GALV. STEEL SLEEVE SECURE
TO PARTITION - GROUT TIGHT
PIPE
ESCUTCHEON PLATE,
COORDINATE WITH ARCHITECT
INSULATION AND JACKET
ESCUTCHEON PLATE WHERE
EXPOSED, COORDINATE
WITH ARCHITECT
FILL ANNULAR SPACE BETWEEN
PIPE AND SLEEVE COMPLETELY
WITH FIRECAULK (3M FIRE SAFING)
NOTES:
1. SIZE RODS, SPRING CUSHION, AND
HORIZONTAL MEMBER APPROVED TO
SATISFY LOAD REQUIREMENT W/ SAFETY
FACTOR OF 5.
2. DO NOT EXCEED ALLOWABLE LOAD LIMITS.
W / OR W/OUT PROTECTIVE
SADDLE OR SHIELD AS REQUIRED
W / OR W/OUT TYPE 48 SPRING
ISOLATOR AS REQUIRED PER
SPECIFIC…