2-11 PCLS Sumner Library Bid Set - Plumbing.pdf
PDF 2 MB Posted
- Solicitation number
- 81325
- Issued by
- Pierce County, Washington
About this file
This is a plumbing bid set document for the Sumner Library construction project in Pierce County, Washington, prepared by Johnston Architects. The project involves construction of a new 17,133 square foot public library facility at 15126 Main Street East, Sumner, Washington, on a 73,573 square foot parcel. The plumbing scope encompasses a complete and functional system including sanitary waste and vent piping, domestic hot and cold water supply, roof drainage, and all associated fixtures and equipment. Key plumbing components specified include nine wall-hung water closets with flush valves, eight lavatories, three sinks, one floor sink, five floor drains with trap primers, one mop sink, one dual electric water cooler with bottle filler, two electric tankless water heaters, one domestic hot water heat pump system, roof drains, hose bibbs, and backflow preventers. The contractor must obtain all required permits, pay associated fees, comply with 2021 International State Building Code, Mechanical Code, Uniform Plumbing Code, Fire Code, and Washington State Energy Code, and perform work in accordance with manufacturer specifications and local ordinances.
The specifications require sanitary, waste, and vent piping to be no-hub cast iron or DWV copper, with hot and cold water piping consisting of hard-drawn copper tubing Type L with wrot copper fittings and lead-antimony-free solder. All hot and cold water piping must be insulated with glass fiber insulation and heat bonding tape. The contractor must provide seismic restraint in accordance with ASCE Standard 7 with calculations submitted by a licensed structural engineer, provide comprehensive commissioning with functional test procedures, submit all equipment product data for approval, use experienced installers, and instruct the owner in proper system operation. The document includes detailed plumbing schedules, foundation and floor plans, roof plans, fixture specifications with manufacturers and model numbers, sanitary and water service calculations indicating total fixture units of 89.50 and total GPM requirements of 48.0 at the point of connection, and comprehensive piping details and connection requirements for all systems including condensate drainage, backflow prevention, and isolation valves.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. THE SCOPE OF THE PLUMBING WORK CONSISTS OF WORK SHOWN ON THE PLANS AND AS DESCRIBED IN THE SPECIFICATIONS. IN CASE OF CONFLICT, THE SPECIFICATIONS SHALL GOVERN. PROVIDE A COMPLETE &
FUNCTIONAL SYSTEM.
2. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION. PAY ALL ROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF PATENTED DEVICES AND SYSTEMS.
3. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING LOUVERS, CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM ELEVATIONS, LOCATE DEVICES SO THAT THEY DO NOT CONFLICT WITH GENERAL CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NOR WITH ELECTRICAL SYSTEM (LIGHT SWITCHES, SPEAKERS, OUTLETS, ETC.).
4. COORDINATE WITH OTHER TRADES:
A. REFER TO ELECTRICAL DRAWINGS AND CONFIRM ELECTRICAL CHARACTERISTICS SHOWN FOR MECHANICAL EQUIPMENT (VOLTAGE, PHASE, HZ, ETC). MATCHES THAT OF THE MECHANICAL EQUIPMENT PROVIDED.
B. PROVIDE ADEQUATE CLEARANCE OF PLUMBING WORK FROM ELECTRICAL EQUIPMENT. MAINTAIN MINIMUM ACCESS OF 6-INCHES ABOVE CABLE TRAYS AND 18-INCHES TO THE SIDE OF CABLE TRAYS. CLEARANCE ABOVE CABLE TRAY SHOULD BE 1/2 THE WIDTH AND NOT LESS THAN 6-INCHES WHEN RUNNING PARALLEL WITH CABLE TRAY. AND NOT LESS THAN 6-INCHES WHEN RUNNING PERPENDICULAR TO THE CABLE TRAY.
5. ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED BY CODES, OR
RECOMMENDED BY MANUFACTURER ARE PROVIDED.
6. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTED SUBMITTALS. INSTALL MATERIAL IN PROPER RELATION TO ADJACENT CONSTRUCTION AND WITH UNIFORM
APPEARANCE FOR EXPOSED WORK.
7. THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT AND PIPING WILL BE INSTALLED AND REPORT ANY
CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE PLUMBING WORK.
8. THE COMMISSIONING SPECIFICATION, INCLUDING ALL FUNCTIONAL TEST PROCEDURES, SHALL BE PROVIDED
AND ENFORCED BY THE CONTRACTOR.
9. PROVIDE SEISMIC RESTRAINT IN ACCORDANCE WITH OSS C AND ASCE STANDARD 7. SUBMIT CALCULATIONS BY LICENSED STRUCTURAL ENGINEER. PRODUCTS MAY CONFORM TO SMACNA SEISMIC RESTRAINT GUIDELINES.
10. PROVIDE A SINGLE SUBMITTAL OF ALL PLUMBING EQUIPMENT AS SPECIFIED. AS A MINIMUM, SUBMIT PRODUCT DATA FOR ALL EQUIPMENT AND FIXTURES LISTED IN ACCOMPANYING SCHEDULES FOR APPROVAL.
11. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
12. ARRANGEMENT OF SYSTEMS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC, AND INDICATES THE MINIMUM REQUIREMENTS FOR PLUMBING WORK. TAKE FIELD MEASUREMENTS BEFORE PREPARING SHOP DRAWINGS, OBTAIN APPROVAL OF SHOP DRAWINGS BEFORE BEGINNING FABRICATION. BE RESPONSIBLE FOR ACCURACY OF DIMENSIONS AND LAYOUT. OVERHEAD PIPING SHALL BE ARRANGED TO OBTAIN MAXIMUM HEAD ROOM.
13. CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF PIPING NOT
ACTIVELY BEING WORKED ON.
14. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR
SERVICE FOR THREE YEARS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
15. DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN APPROVAL.
16. CONCEAL PIPING TO THE GREATEST EXTENT POSSIBLE.
17. INSTRUCT OWNER IN PROPER OPERATION OF SYSTEMS.
18. DRAWINGS DO NOT SHOW ALL OFFSETS WHICH MAY BE REQUIRED. MAKE OFFSETS WITH FITTINGS USING THE LEAST ANGLE OF OFFSET POSSIBLE. PIPING SHALL BE ROUTED TO AVOID ALL STRUCTURAL SUPPORTS, AND
COORDINATED WITH WORK OF OTHER TRADES.
19. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITION OF
THE FOLLOWING CODES AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION.
2021 INTERNATIONAL STATE BUILDING CODE (IBC)
2021 INTERNATIONAL STATE MECHANICAL CODE (IMC)
2021 UNIFORM STATE PLUMBING CODE (UPC)
2021 INTERNATIONAL STATE FIRE CODE (IFC)
2021 WASHINGTON STATE ENERGY CODE (WSEC) WITH LOCAL AMENDMENTS
GENERAL NOTES
1. SANITARY, WASTE, AND VENT PIPING (PLASTIC NOT ALLOWED) SHALL BE NO-HUB CAST IRON OR DWV COPPER.
2. HOT AND COLD WATER PIPING SHALL BE HARD DRAWN COPPER TUBING: TYPE L, ASSEMBLED WITH WROT
COPPER FITTINGS AND LEAD-AND ANTIMONY-FREE SOLDER.
3. INSULATE ALL HOT AND COLD WATER PIPING WITH GLASS FIBER INSULATION WITH ALL SERVICE JACKET. USE
HEAT BONDING TAPE TO CLOSE INSULATION; STAPLES AND PRESSURE TAPE ARE PROHIBITED.
4. PROVIDE ALL REQUIRED ACCESSORIES INCLUDING SHUT-OFFS AND CLEAN-OUTS. PROVIDE COMPONENTS WHICH PREVENT BACK-SIPHONAGE OR CROSS-CONNECTIONS. PROVIDE ISOLATION DEVICES TO REDUCE
SOUND TRANSMISSION.
5. PROVIDE STOPS FOR EACH WATER CONNECTION TO EACH FIXTURE OR ITEM OF EQUIPMENT.
6. DISINFECT WATER DISTRIBUTION SYSTEM. FLUSH AND TEST ALL SYSTEMS FOR PROPER OPERATION. ADJUST
SYSTEM TO PREVENT WATER HAMMER.
7. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR PLANS AND
SECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY.
8. REFER TO CIVIL DRAWINGS FOR UTILITY WORK 5'-0" BEYOND THE BUILDING LINE.
PIPING NOTES
A AIR
AFF ABOVE FINISHED FLOOR
ARRGT ARRANGEMENT
ATM ATMOSPHERE
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOB BOTTOM OF BEAM
BOS BOTTOM OF STEEL
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CLG CEILING, COOLING
CND CONDENSATE
CNTFGL CENTRIFUGAL
CO CLEANOUT
CONC CONCRETE
CONT CONTINUE, CONTROL
COMP COMPRESSOR
CP CIRCULATING PUMP
CTG CLEANOUT TO GRADE
CU FT CUBIC FEET
CV CONSTANT VOLUME
CW COLD WATER
dB DECIBELS
DCVA DOUBLE CHECK VALVE ASSEMBLY
DEG DEGREE
DF DRINKING FOUNTAIN
DI DE-IONIZED
DIA DIAMETER
DN DOWN
DS DOWNSPOUT
E EXISTING
EER ENERGY EFFICIENCY RATING
EFF EFFICIENCY
EL ELEVATION
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR, EXTERNAL
F FAHRENHEIT, FIRE LINE
FD FIRE DAMPER, FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FLA FULL LOAD AMPS
FLR FLOOR
FLTR FILTER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET
FV FACE VELOCITY
GA GAGE
GAL GALLONS
GALV GALVANIZED
GPM GALLONS PER MINUTE
HB HOSE BIBB
HD HEAD
HEX HEAT EXCHANGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER, HEAT PUMP
HW HOT WATER
HWC HOT WATER CIRCULATING
HWP HOT WATER PUMP
HZ HERTZ
ABBREVIATIONS
ID INDIRECT DRAIN
IE INVERT ELEVATION
IN INCH
INIT INITIAL
INT INTERIOR
KW KILOWATT
KWH KILOWATT HOURS
L LENGTH
LB POUND, LINEAR BAR
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MTR MOTOR
NC NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NUMBER, NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
ORD OVERFLOW ROOF DRAIN
ORL OVERFLOW RAIN LEADER
P PUMP, PLUMBING
PH PHASE
POC POINT OF CONNECTION
POS POSITIVE
P/T PRESSURE/TEMPERATURE
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RD ROOF DRAIN
REF REFERENCE
REQD REQUIRED
RL RAIN LEADER
RPBFP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
S SOIL
SD STORM DRAIN, SMOKE DAMPER
SPR SPRINKLER
SS STAINLESS STEEL, SANITARY SEWER
STP STANDPIPE
TEMP TEMPERATURE
TOT TOTAL
TP TRAP PRIMER, TOTAL PRESSURE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VENT, VOLT
VA VALVE
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
W WASTE, WATER, WATT, WIDTH
WG WATER GAGE
WH WATER HEATER, WALL HYDRANT
WTR WATER
VICINITY MAP
PROJECT LOCATION
SITE PLAN
PROJECT LOCATION
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :1
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
GENERAL NOTES,
ABBREVIATIONS,
AND SHEET INDEX
P0.00
JS/CR
JG
PLUMBING SHEET INDEX
P0.00 GENERAL NOTES, ABBREVIATIONS, AND SHEET INDEX
P0.01 PLUMBING LEGEND
P1.00 PLUMBING SCHEDULES
P2.00 PLUMBING FOUNDATION PLAN
P2.01 PLUMBING FLOOR PLAN
P2.02 PLUMBING LOW ROOF PLAN
P2.03 PLUMBING ROOF PLAN
P4.00 PLUMBING DETAILS & SECTIONS
P4.01 PLUMBING DIAGRAMS
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
03/12/2026
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
X-XX
N
DRAWING CONSTRUCTION ("FLAG") NOTE
EQUIPMENT IDENTIFIER
MATCHLINE
REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE
PREVIOUS RELEASE)
REVISION REFERENCE
EXISTING TO BE REMOVED (DASHED)
HEAVY LINEWEIGHT INDICATES NEW WORK
LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION
DETAIL REFERENCE
DETAIL IDENTIFICATION NUMBER
SHEET WHERE DETAIL IS DRAWN
ELEVATION REFERENCE
ELEVATION IDENTIFICATION
NUMBER SHEET WHERE ELEVATION IS DRAWN
SECTION REFERENCE SECTION
IDENTIFICATION NUMBER
SHEET WHERE SECTION IS DRAWN
NORTH REFERENCE
X
XX.XX
X
XX.XX
X
XX.XX
ACCESS PANEL
SYMBOLS LEGEND - PIPING VALVES
SYMBOL DESCRIPTION
CAP
UNION
WYE STRAINER
GATE VALVE
GLOBE VALVE
BALL VALVE
PLUG VALVE
NEEDLE VALVE
PRESSURE REDUCING VALVE
BALANCING / FLOW MEASUREMENT VALVE
RELIEF VALVE
CHECK VALVE
PIPE TURNING DOWN / AWAY
PIPE TURNING UP / TOWARDS
PIPE DOWN TEE / AWAY
PIPE UP TEE / TOWARDS
PLUG
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC
FLANGE
BUTTERFLY VALVE
ANGLE VALVE
WYE STRAINER WITH CAPPED HOSE END BLOWDOWN VALVE
BACKFLOW PREVENTER - DCVA OR RPBP
AUTOMATIC CONTROL VALVE - TWO WAY
M
AUTOMATIC CONTROL VALVE - THREE WAY
M
SYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMS
SYMBOL DESCRIPTION
PIPING OR DUCTED AIRFLOW
NON-DUCTED AIRFLOW
FLOW CONTINUATION ARROW
PUMP
FAN
ELECTRIC MOTOR/STARTER ASSEMBLY
ELECTRIC ACTUATOR (VALVE AND DAMPER)
FLOW DIRECTION
M
M
X SENSOR
T THERMOSTAT (T-STAT)
SD SMOKE DETECTOR
H HUMIDISTAT
CO2 CARBON DIOXIDE
CO CARBON MONOXIDE
NO2 NITROGEN DIOXIDE
SYMBOLS LEGEND - PIPING
SYMBOL DESCRIPTION
FLEXIBLE CONNECTION IN PIPING
MANUAL AIR VENT (MAV), AUTOMATIC AIR VENT (AAV)
PRESSURE GAUGE
THERMOMETER
THERMOMETER WELL
SIGHT GLASS
MAV AAV
STEAM TRAP ASSEMBLYS
X F/T = FLOAT AND THERMOSTATIC
IB = INVERTED BUCKET
T = THERMOSTATIC
I = IMPULSE
O = ORIFICE
PIPE ANCHOR
A
PIPE ALIGNMENT GUIDE
PIPE SUPPORT
PS
CONTROL VALVE STATION
FLOW METER
PIPE BREAK
FM
HOSE BIB, WALL HYDRANT
PRESSURE / TEMPERATURE TEST PORTP/T
FLOOR DRAIN
FUNNEL DRAIN
FLOOR SINK (SQUARE AND ROUND)
FLOOR CLEANOUT, GRADE CLEANOUT
WALL CLEANOUT
SYMBOLS LEGEND - PIPING
SYMBOL DESCRIPTION
HIGH PRESSURE STEAMHPS
MEDIUM PRESSURE STEAMMPS
LOW PRESSURE STEAMLPS
HIGH PRESSURE CONDENSATEHPC
MEDIUM PRESSURE CONDENSATEMPC
LOW PRESSURE CONDENSATELPC
PUMPED CONDENSATEPC
HEATING WATER SUPPLYHWS
HEATING WATER RETURNHWR
CHILLED WATER SUPPLYCHS
CHILLED WATER RETURNCHR
CONDENSER WATER SUPPLYCWS
CONDENSER WATER RETURNCWR
COOLING COIL CONDENSATECND
REFRIGERANT SUCTIONRS
REFRIGERANT LIQUIDRL
NATURAL GASNG
PROPANELPG
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :1
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING LEGEND
P0.01
JS/CR
JG
DRAWING ISSUE
# DATE DESCRIPTION
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :1
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING
SCHEDULES
P1.00
JS/CR
JG
-- WATER HAMMER ARRESTOR -- -- -- -- -- - - ZURN WILKINS 1260XL
LEAD FREE WATER HAMMER ARRESTOR, CERTIFIED TO NSF/ANSI STANDARD 372, DEVICE SHALL BE PRE-CHARGED AND SEALED AT THE FACTORY. INSTALL PER PDI
RECOMMENDATION.
-- SINGLE WATER CLOSET CARRIER 4 2 -- -- -- - - ZURN ZN 1204-N4
INDUSTRY STANDARD SINGLE TOILET NARROW WALL CLOSET CARRIER WITH EPOXY COATED CAST IRON FITTING, 4" NO HUB WASTE AND 2" VENT CONNECTION, EPOXY COATED CAST IRON PATENTED COMPRESSION SEAL FACEPLATE ASSEMBLY, EPOXY COATED CAST IRON FOOT SUPPORTS ADJUSTABLE FOR STANDARD AND WHEELCHAIR HEIGHT, ADJUSTABLE ABS NIPPLE WITH INTEGRAL TEST CAP AND NEOPRENE BOWL GASKET, PLATED HARDWARE AND CHROME CAP NUTS. (MINIMUM
14" WALL CAVITY)
-- DOUBLE WATER CLOSET CARRIER 4 2 -- -- -- - - ZURN ZN1202-ND4
INDUSTRY STANDARD BACK-TO-BACK THIN WALL CLOSET CARRIER WITH EPOXY COATED CAST IRON FITTING, 4" NO HUB WASTE AND 2" VENT CONNECTION, EPOXY COATED CAST IRON PATENTED COMPRESSION SEAL FACEPLATE ASSEMBLY, EPOXY COATED CAST IRON FOOT SUPPORTS ADJUSTABLE FOR STANDARD AND WHEELCHAIR HEIGHT, ADJUSTABLE ABS NIPPLE WITH INTEGRAL TEST CAP AND NEOPRENE BOWL GASKET, PLATED HARDWARE AND CHROME CAP NUTS. (MINIMUM
16" WALL CAVITY)
TP-1 TRAP PRIMER -- -- 1/2 -- -- - -
PRECISION PLUMBING PRODUCT
MP-500
ELECTRIC TRAP PRIMER VALVE WITH DISTRIBUTION SYSTEM FOR UP TO 4 TRAPS. 115V/1PH.
RD-1 ROOF DRAIN 6 -- -- -- -- - - ZURN Z164
12” DIAMETER COMBINATION MAIN ROOF AND OVERFLOW DRAIN WITH LOW SILHOUETTE CAST IRON DOMES AND DOUBLE TOP-SET® DECK PLATE, DURA-COATED CAST IRON BODIES WITH COMBINATION MEMBRANE FLASHING CLAMP/GRAVEL GUARDS, AND NO-HUB OUTLET. COORDINATE BODY HEIGHT DIMENSION WITH ROOF
CONSTRUCTION TYPE.
PF-6 SINK/FAUCET 1-1/4" 1-1/4" 1/2 1/2 -- 1.5 1
SINK:
ELKAY LUSTERTONE CLASSIC
FAUCET:
DELTA TRINSIC 559HA-GPM-DST
STAINLESS STEEL, 14-1/2" X 14-1/2" X 5-1/2" SINGLE BOWL UNDERMOUNT ADA SINK WITH PERFECT DRAIN ELUHAD121255PD. PROVIDE SINK TAILPIECE WITH INDIRECT DRAIN CONNECTION WHERE DRAIN CONNECTION IS NOTED PER PLANS. ASME 112.18.1 / CSAB125.1.
PF-5 KITCHEN SINK/FAUCET 1-1/4" 1-1/4" 1/2 1/2 -- 1.5 1
SINK:
ELKAY CROSSTOWN
ECTSRAD25226TBG
FAUCET:
PEERLESS P7946LF-1.0
25" X 22" X 6", CHROME, ROUGH FINISH, SINGLE HOLE. SINGLE HANDLE LEVER PULL DOWN FAUCET, CHROME FINISH, ADA COMPLIANT, 1.0 GPM, ASME 112.18.1 /
CSAB125.1.
PF-4 MOP SINK 3 2 1/2 1/2 -- 3 3
SINK:
JUST MANUFACTURING
B-33213J
FAUCET:
CHICAGO FAUCETS 897 SERIES
TOP, BOWL AND APRON FABRICATED OF 16 GAUGE TYPE 304 STAIN-LESS STEEL, JUST MODEL# J-127- B 3" DRAIN, AND (2) 14 GAUGE STAINLESS STEEL WALL CLIPS, HOSE AND HOSE BRACKET, & MOP HANGER. POLISHED CHROME-PLATED CAST BRASS SERVICE SINK FAUCET WITH QUARTER TURN CERAMIC DISC CARTRIDGES.
ADJUSTABLE 2-1/2” LONG SWIVEL INLETS WITH INTEGRAL STOPS, CAST BRASS VACUUM BREAKER SPOUT, 3/4” HOSE THREADED OUTLET, 2-1/2” VANDAL RESISTANT
COLOR-CODED BRASS LEVEL HANDLES, PAIL HOOK, & WALL BRACE.
PF-3
WATER CLOSET, WALL HUNG - ADA
EXPOSED SENSOR FLUSH VALVE
4 2 1 -- -- 4 4
WATER CLOSET:
AMERICAN STANDARD
AFWALL MILLENIUM FLOWISE
VALVE:
AMERICAN STANDARD 6065721.002
SELECTRONIC TOUCH-FREE
ELONGATED SEAT, 1.1/1.28 GPF FLUSHOMETER, ELECTRONIC FLUSH WITH LITHIUM BATTERY CR-P2 8V FLUSH VALVE.
PF-2 LAVATORY SINK 1-1/4 1-1/4 1/2 1/2 -- 1 1
LAVATORY:
KOHLER K-2882-0
19-3/4" RECTANGLE, ADA COMPLIANT LEVER HANDLE, MOUNTING HARDWARE, 1/2” NPSM COUPLING NUTS FOR STANDARD LAVATORY RISERS, POP-UP HOLE
PLUGGED.
PF-1 LAVATORY FAUCET 1-1/4 1-1/4 1/2 1/2 -- 1 1
FAUCET (PF-1):
NEXTGEN SELECTRONIC
TOUCHLESS 775B103.002 CR-P2
0.5 GPM VANDAL-RESISTANT PRESSURE COMPENSATING MALE AERATOR (COMPLYING WITH ANSI A112.18.1M STANDARD FOR FLOW). PROVIDE SINK TAILPIECE WITH
INDIRECT DRAIN CONNECTION WHERE DRAIN CONNECTION IS NOTED PER PLANS.
FS-1 FLOOR SINK 3 2 -- -- -- - 6 ZURN Z1901
12”X12” SANI-FLOR RECEPTOR WITH 8" SUMP DEPTH, CAST IRON BODY WITH ACID RESISTING PORCELAIN ENAMEL INTERIOR AND TOP, SQUARE SLOTTED GRATE AND
ANTI-SPLASH ABS INTERIOR DOME STRAINER, & 1/2” TRAP PRIMER CONNECTION.
FD-2 FLOOR DRAIN (HUB) 3 1-1/2 -- -- -- - 6 ZURN ZN415-5BE FUNNEL FLOOR DRAIN WITH MEDIUM-DUTY 5" ROUND NICKEL BRONZE STRAINER AND 4" ROUND FUNNEL.
FD-1 FLOOR DRAIN 3 1-1/2 -- -- -- - 6 ZURN Z415B CAST IRON BODY, 5" DIAMETER ADJUSTABLE NICKEL BRONZE STRAINER. PROVIDE WITH 1/2" TRAP PRIMER CONNECTION.
WF-1
DUAL ELECTRIC WATER COOLER W/ BOTTLE
FILLER
1-1/2 1-1/2 3/8 -- -- 115V 0.5 0.5 EZWS-ERPBM28K EZH2O BOTTLE FILLING STATION WITH BI-LEVEL FOUNTAIN, REFRIGERATED.
WVFP-1 WATER VAPOR FIREPLACE -- -- 1/2" -- -- 0.5 - NETZERO FIRE NZWP60B WITH NZW72F FIREBOX WITH BLACK GLAS LINER.
HB-1 HOSE BIBB - FREEZE PROOF -- -- 3/4 -- -- 2.5 - ZURN Z1320-C
ECOLOTROL WALL HYDRANT, SELF-DRAINING, NON-FREEZE, ANTI-SIPHON WALL HYDRANT, 3/4" FEMALE SOLDER & 3/4” MALE THREADED PIPE INLET CONNECTION, STANDARD 3/4” HOSE CONNECTION OUTLET, WITH VANDAL-RESISTANT INTEGRAL VACUUM BREAKER, AND CHROME-PLATED ROUGH BRONZE BOX, & OPERATING
KEY.
DCVA-3 BACKFLOW PREVENTOR (FIRE PROTECTION) -- -- 6" -- -- - - ZURN WILKINS 350AST DOUBLE CHECK BACKFLOW PREVENTER. LEAD FREE. STAINLESS STEEL BODY WITH INTEGRAL SHUT OFF VALVES AND TEST COCKS. MAX PRESSURE DROP x PSI AT xx GPM FOR X".
DCVA-2 BACKFLOW PREVENTOR (HYDRONIC) -- -- 3/4" -- -- - - ZURN WILKINS 350AST
DOUBLE CHECK BACKFLOW PREVENTER. LEAD FREE. STAINLESS STEEL BODY WITH INTEGRAL SHUT OFF VALVES AND TEST COCKS. MAX PRESSURE DROP x PSI AT xx GPM FOR X".
DCVA-1 BACKFLOW PREVENTOR (DCW) -- -- 2-1/2" -- -- - - ZURN WILKINS 350AST
DOUBLE CHECK BACKFLOW PREVENTER. LEAD FREE. STAINLESS STEEL BODY WITH INTEGRAL SHUT OFF VALVES AND TEST COCKS. MAX PRESSURE DROP x PSI AT xx GPM FOR X".
W V CW HW TW
MARK DESCRIPTION
ROUGH-IN CONNECTION IN ELEC
NOTES
QTY
SUPPLY
FU EA.
DRAIN FU
EA. MAKE AND MODEL REMARKS
2. MANUFACTURER LISTED IS BASIS OF DESIGN. PROVIDE LISTED OR EQUAL APPROVED BY OWNER.
1. COORDINATE MOUNTING HEIGHTS AND HANDING WITH ARCHITECTURAL DRAWINGS AND FIELD CONDITIONS.
REMARKS:
PLUMBING FIXTURE SCHEDULE
EWH-2 UNDER LAV COUNTER RR -FLR 28 WORKROOM CHRONOMITE CM-40L/208 INSTANT FLOW TANKLESS 0.2 8.32 2 57 70F - 110F 40 208/1/60 NOTE 4 - 1, 2, 3
EWH-1 UNDER LAV COUNTER RR -FLR 28 CHILDREN'S RR CHRONOMITE CM-40L/208 INSTANT FLOW TANKLESS 0.2 8.32 2 57 70F - 110F 40 208/1/60 NOTE 4 - 1, 2, 3
AMPS V/PH/HZ
EQUIP. NO LOCATION SERVICE
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
SERIES
TANK DESCRIPTION
TURN ON
(GPM)
INPUT
(KW)
NUMBER
OFAERATORS
TEMP
RISE
(DEG F)
LWT (DEG F)
ELECTRICAL DIMENSIONS
DIAXHEIGHT (IN)
SHIPPING
WEIGHT (LBS)
OPERATING
WEIGHT (LBS)
REMARKS
1. OPERATING PRESSURE 30 PSI- 150 PSI , PRESSURE RELIEF AND TEMPERATURE RELIEF SHALL BE PIPED INDIRECTLY TO NEAREST JANITOR SINK OR OTHER APPROVAL RECEPTOR
REMARKS:
POINT OF USE ELECTRIC WATER HEATER SCHEDULE
DRAWING ISSUE
# DATE DESCRIPTION
9 12/11/2025 Correction Cycle #2
11 2026/03/25 BID SET
sancalc 06/07/25
MINIMUM BUILDING GRAVITY DRAIN SIZE = 4" AT 1/4"/FT OR 1/8"/FT SLOPE
TOTAL FIXTURE UNITS 89.50
1 FLOOR SINK 6.00 6.00
5 FLOOR DRAIN 6.00 30.00
9 WATER CLOSET, FLUSH VALVE (PF-3) 4.00 36.00
1 WATER FOUNTAIN (WF-1) 0.50 0.50
1 MOP SINK (PF-4) 3.00 3.00
1 BREAK ROOM SINK (PF-5) 1.50 1.50
3 SINK (PF-6) 1.50 4.50
8 LAVATORY (PF-2) 1.00 8.00
DOMESTIC FIXTURES
QUANTITY DESCRIPTION
UNITS PER
PUBLIC
GENERAL
TOTAL
UNITS
SANITARY CALCULATION
watercalc 06/07/25
BUILDING COLD WATER MAIN 2-1/2"
TOTAL FIXTURE UNITS AT POINT OF CONNECTION 45.5
TOTAL GPM AT POINT OF CONNECTION 48.0
FLOW IN GPM 48.0 46.00 16.50
FIXTURE UNIT SUBTOTAL 45.5 41.25 12.75
9 WATER CLOSET, FLUSH VALVE (PF-3) 1.28 GPF 2.5 22.5 22.50 0.00
1 WATER FOUNTAIN (WF-1) 1.1 GPM 0.5 0.5 0.50 0.00
1 MOP SINK (PF-4) 12 GPM 3.0 3.0 2.25 2.25
1 BREAK ROOM SINK (PF-5) 1.25 GPM 1.5 1.5 1.13 1.13
3 SINK (PF-6) 1.25 GPM 1.5 4.5 3.38 3.38
8 LAVATORY (PF-2) 0.5 GPM 1.0 8.0 6.00 6.00
2 HOSE BIBB (HB-1) 8 GPM 2.5 5.0 5.00 0.00
1 WATER VAPOR FIREPLACE (WVFP-1) 0.5 GPM 0.5 0.5 0.50 0.00
DOMESTIC
ITEM DESCRIPTION
FIXTURE
UNIT EACH
TOTAL
UNITS (COMB)
(.75)
COLD
WATER
(.75)
HOT
WATER
WATER SERVICE CALCULATION
DWH-1 MECH ROOM DOMESTIC HOT WATER AOSMITH HPTS-80 ELEC 36 69 23.6 220/1/60 940
FLA V/P/HZ
OPERATING
(LBS)
EQUIP NO LOCATION SERVICE MANUFACTURER MODEL FUEL TYPE DIAM " HEIGHT
ELECTRICAL WEIGHT
REMARKS
REMARKS:
DOMESTIC HOT WATER HEAT PUMP SCHEDULE
CC
DD
AA
EE
FF
UP TO FCO
1 1/4" W UP
TO PF-6
4"W UP
TO PF-3 4" W UP
TO PF-3
4" W
GG
1.3
1.3
1.7
1.7
9.1
9.1
TC-08 TC-07 TC-06 TC-05 TC-03 TC-02 TC-01TC-04 TC-01TC-02TC-03TC-04TC-05TC-06TC-07TC-08
CDP-1
SLOPE 1/8" PER FOOT TO
CONDENSATE PUMP (TYP.)
1-1/4" W UP
TO PF-5
2" V UP
4" W UP
TO FD-2
UP TO TRAP PRIMER
UP TO TRAP PRIMER
3" W UP
TO FD-2
2" V UP
3" W UP
TO FS-1
2-1/2" CW UP
TO DCVA-1
4" W UP
TO PF-3
1-1/2" W UP
TO PF-6
2" V UP
3" W UP TO FD-1
1-1/2" W UP TO PF-2
1-1/2" W UP TO PF-2
1-1/2" W UP TO WF-1
3" W UP TO FD-1
1-1/2" W UP TO PF-2
1-1/4" W UP TO PF-6
4" W UP TO PF-3
UP TO TRAP PRIMER
1-1/4" W UP TO PF-6
4" W UP
TO PF-3 1-1/4" W UP
TO PF-2
4" W UP
TO PF-3
3" W UP
TO PF-4
4" W 3" W
UP TO TRAP PRIMER
BB
3" W UP
TO FD-1
3 3
3/4" CND
4" W
I.E. 64.6'
I.E. 62.9'
P4.00
P4.00
P4.00
2" V UP
2" V UP
2" V UP
CW UP TO TP-1
3/4" CND
CDP-2CDP-3
SEE MECHANICAL
SCHEDULES FOR PUMPS
AND TRENCH COILS
2" V UP
UP TO FCO
4" W
4" W
2 1/2" CW
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :1
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING
FOUNDATION PLAN
P2.00
JS/CR
JG
PLAN | SCALE: 1/8" = 1'-0"
PLUMBING FOUNDATION PLAN
1. 4" SANITARY WASTE CONNECTION TO CITY.
2. 2-1/2" CW CONNECTION TO METER.
3. PROVIDE AUTOMATIC AIR VENT.
FLAG NOTES #
0' 8' 16'
SHEET NOTES
A. INSULATE PIPING AND DUCTWORK ACCORDING TO INSULATION SCHEDULES.
DRAWING ISSUE
# DATE DESCRIPTION
AA
EE
FF
PF-3
PF-2
PF-6
EWH-1
1" CW
1 1/4" CW
DCVA-1
DWH-1
1 1/4" CW
GG
1.3
1.3
1.7
1.7
9.1
9.1
3/4" CW
3/4" DCW DN TO
WATERPLACE
TC-09TC-10TC-11
TC-12
TC-13
TC-14
TC-B1 TC-B2TC-15 TC-16 TC-17
3/ 4"
C W
HB-1
3/4" CND
3/4" CND
CDP-4
3/4" CND DN
TO CDP-1
SLOPE 1/8" PER FOOT,
DRAIN TO NEAREST
SINK TAILPIECE
3/4" CND
SLOPE 1/8" PER
FOOT TO CDP-4
HB-1
3/4" CW
PF-3
FS-1
FD-2
FD-1 FD-1
RCP-11 1/2" HW
TP-1
1" C
W
1" CW
2 1/2" CW
2" CW
3/4" HWC
PF-6
1/
2" H
W
PF-4
3" V
2" V
2" V
1-1/4" VPF-5
2" V
2" V DN
3" VTR
1" CW
PF-6
1-1/2" V
2" V
PF-3
(TYP 4)
1" CW
3" V
2" V2" V
1 1/2" CW
1 1/2" HW
2" V
1-1/4" V
PF-3
PF-2
1-1/4" V
1-1/2" V
1-1/2" V
2" V
1 1/2" HW
PF-3PF-2PF-2PF-3
PF-6
EWH-2
2" V
1-1/4" V 1-1/4" V
1 1/4" CW
3/ 4"
C W
2" V
WF-1
1/
2" C
W
PF-2
(TYP 4) 1" CW
3/4" CW
TP-1
3/4" CW
TP-1
FD-2
BB
TP-1
FM
3" VTR
FD-1
P4.00
P4.00
2" VTR
2" V
TP-1
COMBINE 4" RAINLEADER
AND OVERFLOW IN
VERTICAL PIPING
COMBINE 3" RAINLEADER
AND OVERFLOW IN
VERTICAL PIPING
SLOPE 1/8" PER
FOOT TO CDP-5
CDP-5
3/4" CND
PIPING AND CDP-5
BELOW RAISED FLOOR
SLOPE 1/8" PER FOOT,
DRAIN TO NEAREST
SINK TAILPIECE
SLOPE 1/8" PER FOOT,
DRAIN TO NEAREST
SINK TAILPIECE
2" V
SEE MECHANICAL
SCHEDULES FOR PUMPS
AND TRENCH COILS
SEE MECHANICAL
SCHEDULES FOR PUMPS
AND TRENCH COILS
3" FCO
3" FCO
2" V
3" V
3" V
COMBINE 4" RAINLEADER
AND OVERFLOW IN
VERTICAL PIPING
FM
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :2
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING FLOOR
PLAN
P2.01
JS/CR
JG
PLAN | SCALE: 1/8" = 1'-0"
PLUMBING FLOOR PLAN
1. ROUTE PIPING IN CHASE. NO VERTICAL PIPING IN SHEAR WALL.
2. DRAIN TO STORM SEWER BY OTHERS.
3. PROVIDE VACUUM BREAKER.
4. MOUNT HOSE BIBB 18" ABOVE GRADE. CENTER ON PERPENDICULAR INTERIOR
WALL TO ALLOW FREEZE PROTECTION OF HOSE BIBB VALVE.
5. PROVIDE ABOVE GRADE CLEANOUT ON DRAIN PIPING BELOW SINK.
6. PROVIDE FLOW METER ON COLD WATER SUPPLY BRANCH TO HEAT PUMP
WATER HEATER UPSTREAM OF HOT WATER RECIRC CONNECTION.
FLAG NOTES #SHEET NOTES
A. INSULATE ALL PIPING ACCORDING TO INSULATION SCHEDULES.
0' 8' 16'
DRAWING ISSUE
# DATE DESCRIPTION
AA
EE
FF
RTU-1
HP-1
GG
1.3
1.3
1.7
1.7
9.1
9.1
2" VTR
BB
3" VTR
3" VTR
3" ORL/RL UP
3" ORL/RL UP
3" ORL/RL UP
3" ORL/RL UP
2" ORL/RL UP
3" R
L
3" RL
3" ORL
3" O
R L
3" ORL
3" RL
3" ORL
3" RL
3" ORL
3" RL
3" ORL/RL UP
ROUTE PIPING DOWN WITHIN
PITCHED ROOF PLENUM TO
BELOW BEAM (APPROX. 13' AFF)
4" O
R L
4" R
L
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :2
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING LOW
ROOF PLAN
P2.02
JS/CR
JG
PLAN | SCALE: 1/8" = 1'-0"
PLUMBING LOW ROOF PLAN
0' 8' 16'
DRAWING ISSUE
# DATE DESCRIPTION
AA
EE
FF
HP-1
RTU-1
RD-1
RD-1
RD-1
RD-1
RD-1
GG
1.3
1.3
1.7
1.7
9.1
9.1
2" VTR
BB
3" VTR
3" VTR
RD-1
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :2
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING ROOF
PLAN
P2.03
JS/CR
JG
PLAN | SCALE: 1/8" = 1'-0"
PLUMBING ROOF PLAN
0' 8' 16'
DRAWING ISSUE
# DATE DESCRIPTION
NOTES:
1. SIZE RODS, SPRING CUSHION, AND
HORIZONTAL MEMBER APPROVED TO
SATISFY LOAD REQUIREMENT W/ SAFETY
FACTOR OF 5.
2. DO NOT EXCEED ALLOWABLE LOAD LIMITS.
W / OR W/OUT PROTECTIVE
SADDLE OR SHIELD AS REQUIRED
W / OR W/OUT TYPE 48 SPRING
ISOLATOR AS REQUIRED PER
SPECIFICATIONS
ATTACH TO STRUCTURE
TYPE 1 CLEVIS HANGER
INSULATE AS
REQUIRED BY CODE
W/ OR W/OUT PROTECTIVE
SADDLE OR SHIELD AS REQUIRED
INSULATE PIPE AS REQUIRED
BY SPECIFICATIONS
HANGAR RODS
W/ OR W/OUT TYPE 48 SPRING
ISOLATOR AS REQUIRED PER
SPECIFICATIONS
ATTACH TO STRUCTURE
NOT TO ROOF DECK (TYP)
SEISMIC BRACE AS REQUIRED
NON-INSULATED PIPE
ANGLE IRON OR
UNISTRUT TYPE SUPPORT
ATTACH TO STRUCTURE
AND SEISMIC BRACE AS
REQUIRED
CALCIUM SILCATE SUPPORT
WITH GALVANIZED STEEL
JACKET OR SHIELD AS
REQUIRED
ROLLER PIPE SUPPORT. USE
IN CONJUNCTION WITH
ANCHORS AND GUIDES AS
REQUIRED.
NOTES:
1. SIMILAR FOR NON-INSULATED PIPE AND CONDUIT.
2. SIMILAR FOR MASONRY OR CONCRETE WALL EXCEPT CORE DRILL OR CAST IN PLACE.
3. APPLIES FOR PLUMBING, HVAC, AND FIRE PROTECTION..
ESCUTCHEON PLATE WHERE
EXPOSED, COORDINATE WITH
ARCHITECT
INTERIOR STUD WALL
16 GA. GALV. STEEL SLEEVE SECURE
TO PARTITION - GROUT TIGHT
PIPE W/ OR W/OUT INSULATION
EXTERIOR SURFACE
16 GA. GALV. STEEL SLEEVE SECURE
TO PARTITION - GROUT TIGHT
PIPE
ESCUTCHEON PLATE,
COORDINATE WITH ARCHITECT
INSULATION AND JACKET
ESCUTCHEON PLATE WHERE
EXPOSED, COORDINATE
WITH ARCHITECT
FILL ANNULAR SPACE BETWEEN
PIPE AND SLEEVE COMPLETELY
WITH FIRECAULK (3M FIRE SAFING)
SEE ARCHITECTURAL FOR
FLOOR FINISH AND
FLASHING REQUIREMENTS
CORE DRILL, VERIFY
LOCATION WITH ARCHITECT
FLOOR DRAIN OR SINK
CONCRETE
STRUCTURE
1'
HW
CW
TANKLESS
ELECTRIC
WATER
HEATER
EXPANSION TANK
TEMP/PRESSURE RELIEF VALVE
PRESSURE GAUGE
CHECK VALVE (TYP)
THERMOMETER (TYP)
DIELECTRIC UNION (TYP)
FLEXIBLE CONNECTION (TYP)
ROOF DECK INSULATION
OVERFLOW EXTENSION (2" HEIGHT, FOR
OVERFLOW DRAINS ONLY)
ROOF DRAIN EXTENSION
UNDERDECK CLAMP
RAINLEADER, SIZE AS SHOWN ON PLAN;
INSULATE PER SPECIFICATIONS
SUMP RECEIVER
INSULATE ROOF DRAIN BOWL,
SEE SPECIFICATION
ROOF
MEMBRANE
CONCRETE
ROOF DECK
SLOPED ROOF
INSULATION
INDICATING ISOLATION VALVE (TYP)
DOUBLE CHECK VALVE
STRAINER WITH BLOWDOWN
FLOWFLOW
NOTES:
1. CONNECTIONS TO BE FLANGED OR GROOVED TYPE, AS OUTLINED IN THE
SPECIFICATIONS.
2. ACCESS & CLEARANCE SHALL BE PROVIDED FOR REQUIRED TESTING,
MAINTENANCE, & REPAIR: INCLUDING A MINIMUM OF 1'-0" BETWEEN LOWEST
PORTION OF ASSEMBLY, AND FLOOR
PRESSURE GAUGE W/ ISOLATION VALVE (TYP)
CONDENSATE
DRAIN PIPE ROUTED
IN THE WALL
P-TRAP
TAILPIECE WITH
INDIRECT DRAIN
BRANCH FITTING
SINK
CONNECT CONDENSATE
STUBBED OUT OF WALL TO
INDIRECT CONNECTION WITH
HOSE SLOPED TO DRAIN
ISOLATION VALVE
PRESSURE GAUGE
CHECK VALVE (TYP)
VACUUM BREAKER,
MOUNT AT +8-0" AFF
AQUASTAT TMV
THERMOMETER
DIELECTRIC UNION (TYP)
TEMP/PRESSURE RELIEF VALVE
PIPE TO NEAREST FLOOR DRAIN
AND TERMINATE WITH AN AIR GAP
1" WIDE, 16 GA STEEL STRAP
ANCHOR BOLT TO WALL/STRUCTURE
HOSE END DRAIN VALVE,
EXTEND TO FLOOR DRAIN
4" CONCRETE PAD WITH 1"
CHAMFERED EDGES (IF LEGS NOT
FURNISHED WITH WATER HEATER)
INCOMPRESSIBLE
INSULATION PAD
FLEXIBLE
CONNECTION (TYP)
BALANCING VALVE
ELECTRIC WATER
HEATER
CW
HW
W A
S T
E
HWC
FM
MONITOR MIN 80%
HW CAPACITY
RCP-1
1-1/2" DHW
110F
125F
80F55F
ET-3
105F
3/ 4"
H W
C
RCP-1
DCVA-3
DWH-1
TMV-1
MAIN DOMESTIC TEMP MIXING
ELECTRONIC THROTTLE VALVE (ETV)
AO SMITH ELECTRIC HEAT
PUMP WATER HEATER HPTS-50
50 GALLON STORAGE
ETV
CONTROLLER
SAZAN #
Johnston Architects, LLC 3131 Western Ave, Suite 510 Seattle, WA 98121 t 206.523.6150 f 206.523.9382
SHEET TITLE
SHEET NO.
P ri n te d
Drawn Checked
© 2025 JOHNSTON ARCHITECTS
600 Stewart St., Ste. 1400 Seattle, Washington 98101
Tel 206.267.1700 Fax 206.267.1701
911-24008
/1
/2
:2 :2
P
M
P C
L S
S U
M N
E R
L
IB
R A
R Y
M
A
IN
S T
R E
E T
E A
S T
S U
M N
E R
W
A
PLUMBING DETAILS
& SECTIONS
P4.00
JS/CR
JG
NOT TO SCALEP4.00
6 ELECTRIC WATER HEATER WITH RECIRC PUMP DETAIL
NOT TO SCALEP4.00
5 DOMESTIC WATER HEATER PIPING DIAGRAM
NOT TO SCALEP4.00
1 PIPING SUPPORT DETAIL
NOT TO SCALEP4.00
2 PIPE PENTRATION THRU WALLS DETAIL
NOT TO SCALEP4.00
3 FLOOR DRAIN DETAIL
DRAWING ISSUE
# DATE DESCRIPTION
11 2026/03/25 BID SET
NOT TO SCALEP4.00
4 TANKLESS ELECTRIC WATER HEATER DETAIL (WITH RECIRC PUMP)
NOT TO SCALEP4.00
7 ROOF DRAIN AND OVERFLOW DETAIL
NOT TO SCALEP4.00
8 DOUBLE CHECK VALVE BACKFLOW PREVENTER DETAIL
NOT TO SCALEP4.00
9 CONDENSATE DRAIN TAIL-PIECE TIE-IN DETAIL
FM
| Sheets |
| P0.00 - GENERAL NOTES, ABBREVIATIONS, AND SHEET INDEX |