16 MFD-1701252-Drawings IFB.pdf
PDF 7 MB Posted
- Solicitation number
- 697DCK-24-R-00488
About this file
This document contains drawings and specifications for the refurbishment of the TRACON facilities at the Canton, OH and Mansfield, OH airports. The Federal Aviation Administration (FAA) has a requirement for this project with an estimated construction magnitude between $250,000 - $1,000,000. Key details include:
The solicitation number is 697DCK-24-R-00488. It is an unrestricted competition open to all offerors qualified under NAICS code 236220. A one-time site visit will be offered, with details to be provided in advance. Requests for Information must be submitted in writing by 8/20/24, with responses provided via amendment. The proposal due date and submission requirements are included in the solicitation attachment. The Southwestern Region of the Department of Transportation Federal Aviation Administration is the procuring agency for this requirement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
ENGINEERING SERVICES
TERMINAL
ATCT
GENERAL NOTES
VACATED TRACON AREA CONVERSION
OHMANSFIELD LAHM MUNICIPAL AIRPORTMANSFIELD
AF
SKM
JB
PROJECT ENGINEER MGR: ENGINEERING
07/15/2022 1701252
MFD-1701252-G014
m fd -1
-g
.d g n
THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U
IO
/2
:2
:1
A
M P lo tt e d b y
V
-C
E
G -E
D
B
F
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
RELEASED FOR:
847.294.8183
Des Plaines, IL 60018
2300 E. Devon, Suite 344
T4 Great Lakes Region
PTSI Managed Services Inc.
CONSTRUCTION - 07/15/2022
Y
Q
L
IT
INTEGRITY
IN
I
PORT SERVIC
GENERAL DEMOLITION NOTES:
EXISTING WALLS TO PROVIDE A SMOOTH AND FLUSH TRANSITION.
PREP EXISTING WALLS TO RECEIVE NEW FINISHES AS REQUIRED AND ALIGN ALL NEW WALLS TO 6.
WORK.
ITEMS SALVAGED FOR RE-USE SHALL BE CLEANED, STORED AND RE-INSTALLED AS REQUIRED BY NEW 5.
BROUGHT IMMEDIATELY TO THE RESIDENT ENGINEER ATTENTION.
ANY EVIDENCE OF HAZARDOUS MATERIALS (I.E ACM'S) PRIOR TO OR DURING CONSTRUCTION SHALL BE 4.
DEMOLITION.
NOTIFY RESIDENT ENGINEER OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING
DEMOLITION REQUIRED TO ACCOMMODATE NEW WORK. REFER TO NEW CONSTRUCTION PLANS.
ALL DIMENSION ON DEMOLITION PLANS ARE FOR ROUGH OPENINGS TO DETERMINE THE EXTENT OF 3.
THE OWNER.
NEW" CONDITION AND WILL MATCH EXISTING ADJACENT CONSTRUCTION AT NO ADDITIONAL COST TO
ACTIVITIES. ANY AREA DAMAGED AND NOT INDICATED TO BE REMOVED WILL BE REPAIRED TO "LIKE
PROTECT ALL EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE DURING CONSTRUCTION 2.
THE OWNER OR DISCARDED.
COORDINATE WITH RESIDENT ENGINEER ALL ITEMS THAT ARE TO BE REMOVED AND RETURNED TO 1.
GENERAL ARCHITECTURAL NOTES:
MATERIALS AND EQUIPMENT.
ENVIRONMENTAL CONDITIONS WHICH ARE REQUIRED TO MAINTAIN THE ORIGINAL QUALITY OF
MANUFACTURER'S INSTRUCTIONS REGARDING TEMPERATURE LIMITATIONS AND OTHER
FOREIGN MATTER OR MOISTURE FROM ANY SOURCE. COMPLY WITH MATERIAL AND EQUIPMENT
MANNER AS TO PREVENT DAMAGE, INCLUDING DAMAGE WHICH MIGHT RESULT FROM INTRUSIONS OF
TRANSPORT, DELIVER, HANDLE AND STORE MATERIALS AND EQUIPMENT AT THE JOB SITE IN SUCH A 16.
ALL WORK SHALL BE PLUMB, SQUARE, LEVEL, IN PROPER ALIGNMENT, AND SECURELY FASTENED.15.
SYSTEM.
DO NOT ALLOW ADHESIVE ODOR AND OTHER FUMES FROM CONSTRUCTION ACTIVITY TO ENTER HVAC 14.
EXPENSE AND TO THE SATISFACTION OF THE RESIDENT ENGINEER.
INCLUDED IN THE SCOPE OF THIS PROJECT, SHALL BE REPAIRED AND CORRECTED AT CONTRACTOR'S
ELEMENTS AND FIRE RATED ASSEMBLIES. ANY DAMAGE TO THE EXISTING BUILDING AND/OR SITE, NOT
EXTEND PATCH TO THE NEAREST NATURAL BREAK POINT. REPAIR FIREPROOFING ON STRUCTURAL
OCCURS. PATCH AND FINISH DISTURBED AREAS TO MATCH ADJACENT MATERIALS AND FINISHES.
PROVIDE PROTECTION FOR ALL EXISTING FINISHES TO REMAIN, AND REPAIR ANY DAMAGE THAT 13.
FURNISHED TO THE RESIDENT ENGINEER PRIOR TO THE COMMENCEMENT OF ANY WORK.
DEMOLITION AND CONSTRUCTION PHASES. A COPY OF SUCH INSURANCE COVERAGE SHALL BE
COPIES OF ALL APPLICABLE PERMITS SHALL BE MAINTAINED ON-SITE AND ADHERED TO DURING THE
NATIONAL BUILDING REGULATIONS OR CODES TO ADEQUATELY PROTECT PERSONS AND PROPERTY.
COSTS SHALL INCLUDE THE COST OF PROPER INSURANCE AS REQUIRED BY STATE AND LOCAL LAWS, THE CONTRACTOR SHALL APPLY FOR AND OBTAIN ALL PERMITS REQUIRED BY REGULATORY AGENCIES. 12.
CONCEAL PIPING, DUCTWORK WIRING AND CONDUITS.
CONDUITS ALLOW FOR MAXIMUM ACCESSIBILITY FOR MAINTENANCE AND REPAIRS. IN FINISHED AREAS
MECHANICAL AND SECURITY SYSTEMS AS REQUIRED SO THAT PIPING, WIRING, DUCTWORK AND
CONSTRUCTION TO REMAIN. ESTABLISH ROUTING FOR ELECTRICAL, TELECOMMUNICATION, PLUMBING, THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF NEW CONSTRUCTION WITH EXISTING 11.
FOR SERVICE INTERRUPTIONS A MINIMUM OF 14 BUSINESS DAYS PRIOR TO PLANNED INTERRUPTION.
THE SYSTEM. SERVICE OR UTILITY IN QUESTION. THE CONTRACTOR WILL MAKE REQUESTS IN WRITING
ACCEPTABLE SCHEDULE FOR THE INTERRUPTION, SWITCH OVER OR OTHER CHANGE IN OPERATION TO
CONTRACT TO PERFORM THE WORK, CONSULT RESIDENT ENGINEER TO ARRIVE AT A MUTUALLY
PRIOR TO ANY TEMPORARY INTERRUPTION OF SERVICES DEEMED ABSOLUTELY NECESSARY BY THE 10.
ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED.9.
CONSTRUCTION.
RESIDENT ENGINEER OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING NEW
ALL DIMENSIONS ARE FROM FINISHED WALL TO FINISHED WALL, UNLESS OTHERWISE NOTED. NOTIFY 8.
ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.
PROVIDE AND INSTALL ALL MANUFACTURED ITEMS, MATERIALS AND EQUIPMENT IN STRICT 7.
ACCORDANCE WITH FEDERAL, STATE AND LOCAL CODES AND REGULATIONS.
UNSATISFACTORY MATERIALS MUST BE REMOVED FROM THE PROJECT PROPERTY AND DISPOSED OF IN
LAWFULLY REMOVED ON A REGULAR BASIS. ALL WASTE, DEBRIS, UNUSED MATERIALS AND OTHER
THE WORK AREA IS TO BE KEPT CLEAN AND ORDERLY AT ALL TIMES. REFUSE AND DEBRIS SHALL BE 6.
SCOPE OF THE CONTRACT DOCUMENTS.
FEES AND PERMITS REQUIRED AND ASSOCIATED WITH ALL PHASES OF THE WORK AND WITHIN THE
CODES, ORDINANCES, AND REGULATIONS. CONTRACTOR WILL OBTAIN AND BE RESPONSIBLE FOR ALL
ALL WORK PERFORMED BY THE CONTRACTOR SHALL BE DONE IN ACCORDANCE WITH APPLICABLE 5.
SHALL BE FURNISHED.
THE GREATER QUANTITY AND THE HIGHER QUALITY (AS DETERMINED BY THE CONTRACTING OFFICER)
STRINGENT REQUIREMENTS (AS DETERMINED BY THE CONTRACTING OFFICER) SHALL GOVERN, AND
IN CASE OF CONFLICT BETWEEN OR WITHIN THE VARIOUS CONTRACT DOCUMENTS, THE MORE 4.
AREAS OF CONSTRUCTION.
TENANTS AND GENERAL PUBLIC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE THE
BARRICADES, DANGER SIGNALS AND SIGNS IN AREAS OF WORK FOR PROTECTION AND SAFETY OF
NOT BLOCK EXISTS. PROVIDE, ERECT AND MAINTAIN BARRICADES, DANGER SIGNALS AND MAINTAIN
MAINTAIN ALL BUILDING LIFE SAFETY, FIRE PROTECTION AND SECURITY SYSTEMS AT ALL TIMES. DO 3.
DURING CONSTRUCTION.
THE PROJECT SITE TO EMERGENCY AND SECURITY VEHICLES AT ALL TIMES AND WITHOUT DELAY
AND HAUL ROUTES IN A MANNER THAT ALLOWS UNOBSTRUCTED EMERGENCY ACCESS TO ALL AREAS OF
CONSTRUCTION PHASES OF THIS PROJECT, IN ADDITION, THE CONTRACTOR MUST MAINTAIN ACCESS
RESIDENT ENGINEER. LOCAL TRAFFIC ACCESS SHALL BE MAINTAINED DURING THE DEMOLITION AND
THE CONTRACTOR SHALL VERIFY AND COORDINATE ALL SITE AND BUILDING ACCESS WITH THE 2.
PROBLEM RESOLUTION WITHOUT DELAYING THE WORK.
AND DRAWINGS PRIOR TO PROCEEDING WITH ANY PORTION OF THE WORK. ALLOW TIME FOR
BUILDING CONDITIONS. NOTIFY RESIDENT ENGINEER OF ANY CONFLICTS BETWEEN FIELD CONDITIONS
THE CONTRACTOR SHALL VERIFY AND COORDINATE THE SCOPE OF WORK WITH EXISTING SITE AND 1.
DESIGN CODES AND CRITERIA:
- OBC 2017, OHIO BUILDING CODE
- IBC INTERNATIONAL BUILDING CODE
AND STANDARDS.
DRAWINGS WERE COMPLETED IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING CODES
APPLICABLE CODES, LOCAL AUTHORITIES HAVING JURISDICTION, REGULATIONS, AND STANDARDS, THESE
ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH DIVISION 26 OF THE CONTRACT DOCUMENTS, ALL
IS
FOR OFFICIAL USE ONLY
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
mfd-1701252-g014
2023-09-14T12:50:29-0500
DOUGLAS E WEAVER
2022-07-28T09:59:26-0500
RONALD M HUBRICH
MECHANICAL COVERSHEET
AK
BT
UR
MFD-1701252-M001
-m lo tt e
ANY AND ALL UTILITY/SYSTEM SHUTDOWNS.
THE RESIDENT ENGINEER, IN WRITING, 10 WORKING DAYS IN ADVANCE OF
COORDINATE WITH SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY AND 4.
RESIDENT ENGINEER PRIOR TO PROCEEDING WITH DEMOLITION.
BUILDING, THE SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY THE
INTEGRITY OF THE WHERE DEMOLITION WOULD AFFECT THE STRUCTURAL 3.
DAMAGE ADJOINING SURFACES OR EQUIPMENT INDICATED TO REMAIN.
MANNER THAT WILL NOT DEMOLITION SHALL BE PERFORMED IN SUCH A 2.
WORK.
REPORTED TO THE RESIDENT ENGINEER PRIOR TO STARTING DEMOLITION
CONSTRUCTION DOCUMENTS AND VERIFIED FIELD CONDITIONS SHALL BE
ROUTING OF EXISTING PIPING, ETC. ANY DISCREPANCIES BETWEEN THE
SIZES AND ROUTING OF EXISTING DUCTWORK, THE EXACT SIZES AND
SHALL VERIFY THE CONDITION OF ALL EXISTING EQUIPMENT, THE EXACT
SUBCONTRACTOR/CONTRACTOR BEFORE DEMOLITION WORK BEGINS THE 1.
SHALL BE PROVIDED TO THE ENGINEER OF RECORD FOR REVIEW.
SYSTEMS WITHIN THE SCOPE OF WORK. UPON COMPLETION OF WORK, A WRITTEN TEST & BALANCE AND OPERATION OF CONTROLS REPORT
AND BALANCE ALL MECHANICAL UPON COMPLETION OF WORK AN INDEPENDENT AND CERTIFIED TEST & BALANCE COMPANY SHALL TEST 18.
MECHANICAL SYSTEMS.INSTALL ALL BALANCING DEVICES NEEDED TO ACHIEVE PROPER ADJUSTING AND BALANCING OF 17.
DUCTWORK AND PIPING SHALL NOT RUN OVER ELECTRIC PANELS OR ELECTRIC EQUIPMENT.16.
ACCEPTANCE.UNLESS OTHERWISE NOTED, GUARANTEE ALL PARTS AND LABOR FOR ONE YEAR FROM DATE OF FINAL 15.
THIS SHALL INCLUDE PROVIDING SUFFICIENT SPACE TO MEET ALL OTHER TRADE CLEARANCE REQUIREMENTS.
INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, PLUMBING, FIRE PROTECTION, TELECOM, STRUCTURAL, CIVIL, AND GENERAL ARCHITECTURE.
WORK WITH THAT OF ALL OTHER TRADES IT SHALL BE THE RESPONSIBILITY OF THIS SUBCONTRACTOR/CONTRACTOR TO COORDINATE THEIR 14.
OTHERWISE, THE REUSE OF EXISTING DEVICES, MATERIALS, EQUIPMENT AND ASSOCIATED COMPONENTS AND ACCESSORIES IS PROHIBITED.
BE FIRST QUALITY. UNLESS INDICATED ALL EQUIPMENT, DUCTWORK, DEVICES, DAMPERS, CONTROLS, VALVES, PIPING, INSULATION, ETC SHALL 13.
CONTRACT DOCUMENTS SHALL BE IDENTIFIED AND BROUGHT THE RESIDENT ENGINEER'S ATTENTION PRIOR TO COMMENCING WORK.
THE CONTRACT DOCUMENTS PRIOR TO STARTING CONSTRUCTION. ANY DISCREPANCIES NOTED BETWEEN EQUIPMENT VENDOR PLANS AND
DRAWINGS AND COORDINATE THESE PLANS WITH THIS SUBCONTRACTOR/CONTRACTOR SHALL OBTAIN A FULL SET OF ALL EQUIPMENT VENDOR 12.
STARTING WORK.
DOCUMENTS AND MANUFACTURER'S REQUIREMENTS, THIS SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY THE RESIDENT ENGINEER PRIOR TO
WORK SHALL ADHERE TO THE MANUFACTURERS' RECOMMENDATIONS/REQUIREMENTS. IF A CONFLICT EXISTS BETWEEN THE DESIGN
DOCUMENTS/REQUIREMENTS PRIOR TO STARTING WORK. ALL REVIEW ALL APPLICABLE MANUFACTURERS' INSTALLATION AND MAINTENANCE 11.
SUBMIT LITERATURE FOR ALL EQUIPMENT AND MATERIALS TO THE ENGINEER OF RECORD FOR APPROVAL.
FOR PERFORMANCE AND MATERIALS. MANUFACTURER'S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY 10.
A COMPLETE INSTALLATION.FURNISH ANY MISCELLANEOUS ITEMS NORMALLY USED, SPECIFICALLY MENTIONED OR NOT, TO RENDER 9.
APPROVAL.
STRUCTURAL ENGINEER'S REVIEW AND STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY MANNER WITHOUT A 8.
VERIFY SIZES, LOCATIONS, INVERTS AND ELEVATIONS PRIOR TO RUNNING ANY DUCTWORK/PIPING.7.
ACCEPTANCE.
DISCREPANCIES BETWEEN THE DELIVERY AND CONSTRUCTION DOCUMENTS SHALL BE REPORTED TO RESIDENT ENGINEER PRIOR TO
PRIOR TO ACCEPTING DELIVERY. ANY SUBCONTRACTOR/CONTRACTOR SHALL FIELD INSPECT ALL GOVERNMENT FURNISHED MATERIALS 6.
OTHER TRADES.
SHALL INCLUDE, BUT NOT BE LIMITED TO, OFFSETTING EXISTING PIPING AND MODIFICATIONS REQUIRED FOR COORDINATION WITH ALL
NOT SHOWN ON DRAWINGS. MAKE ALL NECESSARY MODIFICATIONS TO EXISTING CONDITIONS TO PERFORM WORK OF THIS SECTION. THIS
LOCATIONS SHOWN ON DRAWINGS IS GUARANTEED. DETERMINE EXACT LOCATIONS OF EXISTING SYSTEMS/UTILITIES IN FIELD, WHETHER OR
NEITHER ACCURACY NOR COMPLETION OF ALL EXISTING CONDITIONS SHOWN ARE TAKEN FROM EXISTING DRAWINGS AND FIELD SURVEYS. 5.
THE WORK INVOLVED.
IN VIOLATION SHALL BE BROUGHT TO THE ATTENTION OF THE RESIDENT ENGINEER AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF
SHOWN ON THE DRAWINGS WHICH IS NO WORK SHALL BE INSTALLED IN VIOLATION OF ANY GOVERNING STANDARDS AND CODES. ANY WORK 4.
REGULATIONS. IN CASE OF DIFFERENCES THE MOST STRINGENT SHALL GOVERN.
AND LOCAL CODES, RULES AND ALL MECHANICAL WORK SHALL BE IN ACCORDANCE WITH FAA STANDARDS AND ALL APPLICABLE STATE 3.
GETTING THE EQUIPMENT INTO PLACE, AND BECOME THOROUGHLY FAMILIAR WITH ALL OF THE REQUIREMENTS OF THE CONTRACT.
WORK. DETERMINE, IN ADVANCE, THE METHODS OF INSTALLING AND CONNECTING THE APPARATUS, THE MEANS TO BE PROVIDED FOR
THE PREMISES AND ANY EXISTING BEFORE SUBMITTING A BID CAREFULLY STUDY THE CONSTRUCTION DOCUMENTS. CAREFULLY EXAMINE 2.
NOT SCALE THESE DRAWINGS.
MECHANICAL SYSTEM COMPONENTS. DO THESE DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO DEPICT THE GENERAL LOCATION OF 1.
SYMBOLS TYPE MATERIAL FINISH
S-1 SUPPLY DIFFUSER STEEL WHITE
REMARKS
1,2,3
& MODEL #
MANUFACTURER
SIZE
R-1 STEEL WHITE24x24
CEILING MOUNT3.
NC VALUE SHALL NOT EXCEED 30.2.
4-WAY ADJUSTABLE1.
RETURN GRILLE
PRICE #SCD
PRICE #80/F
24X24
2,3
COOLING PER ASHRAE 0.4%
LOCATION
DRY BULB WET BULB ASHRAE 99.6%
HEATING PER
75 DEG F
COOLING HEATING
DESIGN SETPOINTS
72.8 DEG F 1.5 DEG FMANSFILED, OH 88 DEG F 70 DEG F
POINT OF CONNECTION (POC)
POINT OF DISCONNECT (POD)
THERMOSTAT
CONTROLLER
HUMIDISTAT
SA
8"Ø
FLEX DUCT
MANUAL VOLUME DAMPER
2'x2' SUPPLY DIFFUSER
2'x2' RETURN GRILLE
ROOF ABOVE
SUPPLY DUCT UP TO FLOOR ABOVE/THRU
ROOF ABOVE
RETURN DUCT UP TO FLOOR ABOVE/THRU
45 DEGREE ENTRY
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW CONSTRUCTION
REGISTER/GRILLE: DEVICE TYPE/AIRFLOW/OPENING SIZE
DIFFUSER: DEVICE TYPE/AIRFLOW/NECK SIZE
SUPPLY DUCT
COLLAR
CEILING
SEALER
DRAW BAND WITH SILICONE OPPOSED BLADE DAMPER
CEILING DIFFUSER
HAND DAMPER
FLEX DUCT MAX. 6' - 0"
NECK SIZE
FLEX DUCT SIZE SHALL MATCH
MECHANICAL GENERAL NOTES: MECHANICAL LEGEND MECHANICAL DEMOLITION NOTES:
PROJECT DESIGN CONDITIONS
AIR DEVICE SCHEDULE
(SIDE OF DUCT CONNECTION)
TYPICAL DIFFUSER CONNECTION
NOT TO SCALE
M001 mfd-1701252-m001
2023-09-14T12:51:37-0500
DOUGLAS E WEAVER
2022-07-28T10:00:18-0500
RONALD M HUBRICH
DEMO AND NEW CONSTRUCTION
MECHANICAL PARTIAL GROUND FLOOR PLAN -
AK
UR
MFD-1701252-M002
LOCATION OF THE RELOCATED THERMOSTAT. 10.
RELOACTE EXISITNG THERMOSTAT. 9.
TIE IN 8"X6" DUCT FROM THE MAIN. 8.
TIE IN 8" DUCT FROM THE MAIN.7.
SUPPLY DUCT.
DEMOLISH EXISTING SUPPLY DUCT FROM UNIT#2. DEMOLISH DAMPER D-2 AND ASSOCIATED WIRING. CAP THE 6.
EMOLISH ABANDONED HUMIDISTAT. 5.
DEMOLISH OVERTEMP CONTROL PANEL SERVING DAMPER D2. 4.
THE DISPERSION TUBE LOCATED INSIDE THE SUPPLY DUCT AND SEAL THE OPENINGS AS REQUIRED.
DEMOILISH EXISTING HUMIDIFIER AND ASSOCIATED PIPING SERVING UNIT #1'S 20"x20" SUPPLY MAIN. DEMOLISH 3.
DISCONNECT AND DEMOLISH EXISTING RETURN GRILLE. 2.
DEMOLISH EXISTING SUPPLY DIFFUSER AND THE FLEX DUCT. SEAL THE OPENING IN THE MAIN DUCT. 1.
EXISTING TO BE REMOVED
DEMO TO THIS POINT
NEW CONSTRUCTION
CONNECT TO EXISTING
:4 lo tt e
WD WD
UNIT #1
UNIT #1
(TYP.)
6" x 6"
8"
S-1
R-1
ETR
X
20" X 20"
12" X 12" (ETR)
20" X 20"
6" x 6"
24" X 14" (ETR)
12" X 12" (ETR)
24" X 24"
24" X 24" DN (TYP.2)
OVER TEMP CONTROL PANEL
FLEX DUCT
(ETBR) 10"
DIFFUSER (TYP.)
(ETBR) 10" CLG
DAMPER D-2 NC
MOTORIZED
ROOM
THE EQUIPMENT
FROM UNIT #1 TO
FROM UNIT #2
16" X 14"
D-1B NO (ETR)
MOTORIZED DAMPER
D-1A NC (ETR)
24" X 24" DN (TYP.2)
THE EQUIPMENT
FROM UNIT #1 TO
D-1B NO (ETR)
D-1A NC (ETR)
116115
EQUIPMENT
MAIN ENTRYMAIN ENTRY
113ROOM
HALLWAY
TRACON
AT OFFICE AF UNIT OFFICE AF UNIT OFFICEAT OFFICE
CONFERENCE
WD WD
MECHANICAL PARTIAL GROUND FLOOR PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"M002
MECHANICAL PARTIAL GROUND FLOOR PLAN - NEW WORK
SCALE: 1/4" = 1'-0"M002
SHEET NOTES:
DEMOLITION LEGEND
NEW CONSTRUCTION LEGEND
mfd-1701252-m002
2023-09-14T12:51:52-0500
DOUGLAS E WEAVER
2022-07-28T10:00:27-0500
RONALD M HUBRICH
2'-0"
GROUND FLOOR PLAN AND RCP PLAN
EG
MFD-1701252-A017
-a
-a lo tt e
AT OFFICE AF UNIT OFFICE
MAIN ENTRY
WD
4 4
GROUND FLOOR RCP PLAN
SCALE: 1/4" = 1'-0"A017
2GROUND FLOOR PLAN
SCALE: 1/4" = 1'-0"A017
2 2
WALL
HATCH FOR NEW
RENOVATION NOTES:
ON CONFERENCE TABLE. EXACT LOCATION TO BE COORDINATED WITH RE.
REFER TO E012 FOR POWER, CATV AND ETHERNET OUTLETS TO BE INSTALLED
REPLACE ALL 2' x 2' CEILING PANELS, EXISTING GRID TO REMAIN.
INFORMATION.
REFER TO ELECTRICAL. DRAWING D002 AND E012 FOR ADDITIONAL LIGHTING
EXISTING LIGHTING TO BE UPGRADED TO LED THROUGHOUT.
INSTALL NEW CEILING PANELS THROUGHOUT RENOVATED ROOM.
REPAIR WALLS, CLEAN, SAND, PAINT AND APPLY NEW VINYL BASE.
REPAIR BACK WALL WHERE WATER DISPENSER CONNECTIONS ARE LOCATED.
INSTALL NEW CARPET TILE. REPLACE THRESHOLD WITH NEW ADA APPROVED.
INSTALL NEW STUD DRYWALL, PAINT TO MATCH EXISTING, ADD VINYL BASE.
RCP LEGEND:
DIFUSSERS
AIR INTAKE
LIGHTING FIXTURE
GENERAL NOTES:
NEW FURNITURE TO BE PROVIDED BY FAA. COORDINATE EXACT LOCATIONS WITH RE DURING2.
REFER TO DRAWING G013 , E012, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.
FOR MECHANICAL FIXTURE INFORMATION
REFER TO DRAWINGS M001 AND M002
NOTE:
mfd-1701252-a017
2023-09-14T12:51:14-0500
DOUGLAS E WEAVER
2022-07-28T10:00:05-0500
RONALD M HUBRICH
J
6'-1"
16'-10"
EXISTING GROUND FLOOR PLAN
MFD-1701252-D001
-d
:0 lo tt e
SCALE: 1/4" = 1'-0"D001
WD
TRACON
1 4
6 6
2 6
SCALE: 1/4" = 1'-0"
4' 8'04'
DEMOLITION KEY NOTES:
EXISTING LOCKERS TO BE MOVED.
WATER DISPENSER (WD) AND CONNECTIONS TO REMAIN.
REMOVE EXISTING WALL CUTOFF OPENING TO EQUIPMENT ROOM.
REMOVE CARPET LAYER ON WALLS.
REMOVE EXISTING CEILING PANELS, GRID TO REMAIN.
REMOVE FLOOR CARPET AND VINYL TILES BELOW (IF EXISTING) THROUGHOUT ROOM.
WING WALL / NICHE ON NORTH-EAST CORNER TO REMAIN.
REMOVE WING WALL, MOVE CONTROL PANELS.
AND CEILING. REFER TO DRAWING D002 FOR MORE ELECTRICAL DEMOLITION PLAN INFORMATION.
REMOVE ALL FURNITURE, ELECTRONIC EQUIPMENT, CABINETS AND ACCESSORIES FROM FLOOR, WALL 1 mfd-1701252-d001
2023-09-14T12:50:42-0500
DOUGLAS E WEAVER
2022-07-28T09:59:37-0500
RONALD M HUBRICH
16'-10"
J
ELECTRICAL DEMOLITION PLAN
JR
MFD-1701252-D002
DISPOSE OF EXISTING LIGHT BULBS. REFER TO DRAWING E012 FOR MORE PROPOSED UPDATES 22.
TO THE MAXIMUM EXTENT POSSIBLE. COORDINATE WITH COR.
VERIFY ALL CONDUIT RUNS AND EQUIPMENT BEFORE DEMOLITION REMOVE ALL CONDUIT AND CABLE 21.
DEBRIS, EQUIPMENT, AND ASSOCIATED CONDUIT/CABLE.
SUBCONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND OFF-SITE DISPOSAL OF ALL DEMO 20.
STORE ALL THE TOOLS.
MAINTAIN A CLEAN CONSTRUCTION AREA BY CLEANING DAILY, REMOVE ALL DEBRIS AND PROPERLY 19.
PERIOD OF THE WORK.
DO NOT OBSTRUCT THE MEANS OF EGRESS FOR THE FACILITY AT ANY TIME THROUGHOUT THE 18.
ARCHITECTURAL DRAWINGS.
COORDINATE DEMOLITION SHOWN ON THIS DRAWING WITH DEMOLITION WORK AND NOTES SHOWN ON 17.
SHALL RELOCATE AND REINSTATE TO ORIGINAL WORKING CONDITION.
IF FIRE ALARM DEVICES ARE DISTURBED DURING THE PERFORMANCE OF THE WORK, CONTRACTOR 16.
SCHEDULE WORK TO AVOID DISRUPTIONS TO THE OCCUPANTS AND AIR TRAFFIC OPERATIONS.
THE BUILDING WILL BE OCCUPIED DURING THE PERFORMANCE OF THE WORK COORDINATE AND 15.
REQUIREMENTS.
IN ACCORDANCE WITH THE SCHEDULE DESCRIBED IN "SEQUENCE OF WORK". UNDER GENERAL
ELECTRICAL WORK DESCRIBED IN THESE DOCUMENTS SHALL BE COORDINATED WITH GENERAL WORK 14.
RELOCATE ANY EXISTING EQUIPMENT TO NEW WALL AS INDICATED.13.
EXISTING CONDUITS MAY BE MODIFIED AND REUSED FOR NEW WORK.12.
OF THE EXISTING LIGHTING MAY BE USED AS A TEMPORARY LIGHTING IF IT'S APPROVED BY THE RE.
PROVIDE TEMPORARY LIGHTING AND MAINTAIN BUILDING POWER DURING DEMOLITION. ALL OR PART 11.
REPAIRED TO MATCH EXISTING.
FINISHES AND SURFACES DAMAGED BY THE DEMOLITION OR CONSTRUCTION SHALL BE PATCHED AND 10.
COORDINATE ALL NECESSARY ARRANGEMENT WITH UTILITY, SSC, AIRPORT, AND RESIDENT ENGINEER.9.
MAINTAIN ALL SIGNAL, POWER, LIGHTING AND ALARMS CIRCUITS DURING ALL PHASES OF 8.
ON AND ALL EXISTING OUTLETS FROM THE WALLS BEING REDONE.
REMOVE ALL EXISTING LIGHTS AND THEIR CONTROLS FROM THE TRACON ROOM AREA BEING WORKED 7.
STORE SMOKE DETECTORS TO BE REINSTALLED BELOW NEW CEILING.
WHERE CONDUITS ARE INACCESSIBLE TO REMOVE AND/OR CAN BE REUSED, LEAVE THEM IN PLACE.
AND ASSOCIATED WIRING AND CONDUITS BACK TO THE POWER SOURCE FOR NEAREST OUTLET BOX/JB
DISCONNECT AND REMOVE LIGHTING FIXTURES, EXIT SIGNS, WIRING, WIRING DEVICES, SWITCHES 6.
FROM EACH FIXTURE AND DISPOSE OF BALLAST IN ACCORDANCE WITH FEDERAL AND STATE
FLORESCENT LIGHTS HAVE BALLASTS THAT MAY CONTAIN PCB MATERIAL. REMOVE EACH BALLAST 5.
PERFORMED. CONTRACTOR SHALL NOT OPEN OR CLOSE ANDY CIRCUIT BREAKER AT ANY TIME.
BREAKER OPERATION TO THE FAA IN WRITING AND AT LEAST 30 DAYS IN ADVANCE TO THE WORK BEING
ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMITTAL REQUESTS FOR CIRCUIT 4.
DEMOLITION.
ENSURE EQUIPMENT IS DE-ENERGIZED AND LOCKED-OUT/TAGGED-OUT BEFORE COMMENCING 3.
SYSTEMS. ALL DEMOLITION WORK SHALL BE COORDINATED WITH FAA PERSONNEL IN ADVANCE.
FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO DEMOLITION OF ELECTRICAL 2.
REFER TO DRAWING G002 , E002, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.
lo tt e
EXISTING GROUND ELECTRICAL FLOOR PLAN
SCALE: 1/4" = 1'-0"D002
BASE BLDG
SEE NOTE 22
SEE NOTE 22
mfd-1701252-d002
2023-09-14T12:50:58-0500
DOUGLAS E WEAVER
2022-07-28T09:59:51-0500
RONALD M HUBRICH
AND ABBREVIATIONS
ELECTRICAL NOTES, LEGEND
MFD-1701252-E011
-e
:4 lo tt e
GENERAL ELECTRICAL NOTES
GENERAL GROUNDING NOTES
ELECTRICAL ABBREVIATION
AC HH
AWG
GND
RGS
EES
EMT
FT
J-BOX
MTS
NEC
CCS
RF
PVC
SER
SPD
GEC
SLD
MDP
BFL
E/G
GFCI
GFE
LFM
SCH
TYP
MAIN-GP
COMM
MLO
SUPP-GP
WP
BSC
FRWK
MPGP
LPS
OSHA
NFPA
AIRCRAFT RATED HANDHOLE
MULTI-POINT GROUND PLATE
MAIN GROUND PLATE
EARTH ELECTRODE SYSTEM
GROUND CONDUCTOR
FRAMEWORK
BARE STRANDED COPPER
AMERICAN WIRE GAGE
SUPPLEMENTAL GROUND PLATE
MAIN LUG ONLY
POLYVINYL CHLORIDE CONDUIT
LIQUIDTIGHT FLEXIBLE METAL CONDUIT
COPPER-CLAD STEEL
COMMUNICATION
ENGINE GENERATOR
NATIONAL ELECTRIC CODE (NFPA 70)
NATIONAL FIRE PROTECTION ASSOCIATION
OPERATIONAL SAFETY AND HEALTH ADMINISTRATION
LIGHTNING PROTECTION SYSTEM
SERVICE ENTRANCE RATED
RADIO FREQUENCY
SINGLE LINE DIAGRAM
GROUNDING ELECTRODE CONDUCTOR
MANUAL TRANSFER SWITCH
FEET
ELECTRICAL METALLIC TUBING
JUNCTION BOX
RIGID GALVANIZED STEEL CONDUIT
SCHEDULE
GROUND FAULT CIRCUIT INTERRUPTER
SURGE PROTECTIVE DEVICE
TYPICAL
GOVERNMENT FURNISHED EQUIPMENT
MAIN DISTRIBUTION PANEL
CONDUIT
BELOW FROST LINE
DIA DIAMETER
DESIGN CODES AND CRITERIA
WEATHERPROOF
TBD TO BE DETERMINED
AVG
ELECTRICAL LEGEND
H. TITLE 47 PART 15 FOR CLASS B DEVICES (CFR)
G. TITLE 47 PART 15 FOR CLASS A DEVICES (CFR)
F. NFPA 70E
E. IEEE C2
D. FAA-C-1217
C. FAA-C-1391
B. FAA-STD-019
A. NFPA 70 (NEC)
STANDARDS:
DRAWINGS WERE COMPLETED IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING CODES AND
APPLICABLE CODES, LOCAL AUTHORITIES HAVING JURISDICTION, REGULATIONS, AND STANDARDS. THESE
ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH DIVISION 26 OF THE CONTRACT DOCUMENT/DRAWINGS, ALL 1.
AIR FORCE
AVERAGE
COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE
ONLY PERFORM SPLICES AT RECEPTACLES AND JUNCTION BOXES. 20.
OCCUPANTS DURING THE PERFORMANCE OF THE WORK AS THE FACILITY WILL BE OCCUPIED AND IN OPERATION.
COORDINATE AND SCHEDULE WORK WITH RE AND FACILITY MANAGER TO AVOID DISRUPTIONS TO THE EQUIPMENT AND 19.
CONTINUITY. PROVIDE ALL NECESSARY CORRECTIONS TO MAKE THE SYSTEM READY FOR OPERATION AGAIN.
TEST ALL NEW, RELOCATED, AND EXISTING CIRCUITS/DEVICES AFFECTED BY NEW WORK FOR GROUNDING AND POWER 18.
NEW OR AFFECTED PANELBOARDS.
IDENTIFY AND MARK UP ANY CHANGES TO THE PANEL DIRECTORIES AFFECTED BY NEW WORK. PROVIDE NEW DIRECTORIES FOR
FIELD VERIFY THE ACCURACY OF THE EXISTING BRANCH CIRCUITS AND MARK UP THE DRAWINGS WITH ANY DIFFERENCES. RE-17.
EQUIPMENT NOT INTENDED TO BE REMOVED.
EXERCISE DUE CARE IN THE REMOVAL OF ELECTRICAL DEVICES AND EQUIPMENT NOT TO INTERRUPT POWER TO ANY OTHER 16.
TIME.
IN WRITING 30 DAYS IN ADVANCE OF THE WORK BEING PERFORMED. DO NOT OPEN OR CLOSE ANY CIRCUIT BREAKER AT ANY
ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMIT ALL REQUESTS FOR CIRCUIT BREAKER OPERATION TO THE FAA 15.
BEFORE ORDER NEW MATERIALS.
VERIFY LOCATION OF EXISTING CABLE TRAYS, WIREWAYS, PANELBOARDS, AND DEVICE/MATERIALS TO BE UPGRADED/MODIFIED
VISIT THE JOB SITE TO BECOME COMPLETELY FAMILIAR WITH THE EXISTING CONDITIONS PRIOR TO BEGINING WORK. FIELD 14.
LISTED OR ACCEPTED BY A GENERALLY INDUSTRIAL STANDARD ORGANIZATION.
LABEL ALL COMPONENTS AND MATERIALS FOR THEIR SPECIFIC APPLICATION. ENSURE ALL COMPONENTS ARE UL 13.
ALL ELECTRICAL EQUIPMENT MUST BE MARKED WITH THE APPROPRIATE SAFETY AND WARNING LABELS.12.
DRAWINGS.
SHALL BE SIZED, AT MINIMUM, 14 AWG UNLESS OTHERWISE REQUIRED BY MANUFACTURER OR NOTED ON THE
FOR GENERAL USE, SHALL BE SOLID. CONDUCTORS 10 AWG AND LARGER MAY BE STRANDED. CONTROL WIRE
MINIMUM BRANCH CIRCUIT CONDUCTOR SIZE SHALL BE 12 AWG. CONDUCTORS SIZED 12 AWG AND SMALLER, 11.
MINIMUM OF 72 HOURS ADVANCE NOTICE.
PROCEDURES PRIOR TO EACH ELECTRICAL OUTAGE. COORDINATE ANY POTENTIAL OUTAGES WITH FAA WITH A REVIEW THESE
STRICTLY ENFORCE LOCKOUT/TAGOUT (LOTO) PROCEDURES PER NFPA 70E, LATEST EDITION THROUGHOUT THIS PROJECT. 10.
USE A MINIMUM 3/4" CONDUIT FOR POWER DISTRIBUTION INTERIOR WIRING, UNLESS OTHERWISE NOTED.9.
NOT ALLOWED.
PROVIDE EACH CIRCUIT WITH AN INDIVIDUAL NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE 8.
INSTALLATION AND UPON INSTALLATION COMPLETION.
TEST CABLES IN ACCORDANCE WITH SPECIFICATION 26 08 00.13 TESTING AND INSPECTING ELECTRICAL EQUIPMENT PRIOR TO 7.
WIRING HAS BEEN INSTALLED.
TERMINATE EACH RGS CONDUIT WITH THREADED SEALING HUB. SEAL BOTH ENDS OF ALL CONDUITS WITH DUCT SEAL AFTER 6.
DRAWINGS.
INCLUDE ANY ADDITIONAL APPURTENANCE NECESSARY FOR PROPER FUNCTION OF THE SYSTEM EVEN NOT SHOWN ON THE 5.
APPLY ANTI-SEIZE COMPOUND TO ALL THREADS ON BOLTS, AND SCREWS.4.
INSTRUCTIONS, NEC, NEMA, AND FAA STANDARDS AND ORDERS.
EACH PIECE OF EQUIPMENT INSTALLED UNDER THE CONTRACT. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER
PROVIDE ALL REQUIRED CONDUITS, CABLES, JUNCTION BOXES, FITTINGS, SUPPORTS, ETC TO COMPLETE BRANCH CIRCUITS FOR 3.
SPACE ACCORDING TO THE NEC CODE AND OSHA.
AVOID SPACE CONFLICT. INSTALLATION OF THE EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF THE WORKING
ALL EQUIPMENT DIMENSIONS SHOWN ARE NOMINAL. FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH EQUIPMENT TO 2.
BE THREADED TYPE ONLY. EMT ONLY FOR INDOOR WIRING. EMT FITTINGS SHALL BE COMPRESSION TYPE ONLY.
OUTDOOR INSTALLATION. PVC COATED RGS ONLY FOR UNDERGROUND INSTALLATION. RGS CONDUIT FITTINGS SHALL
PERMITTED FOR GROUND CONDUCTORS OR BURIED RACEWAYS UNLESS INDICATED OTHERWISE. RGS CONDUIT ONLY FOR
PERMITTED RACEWAY TYPES ARE EMT, RGS, PVC-COATED RGS, AND PVC SCHEDULE 80. PVC RACEWAY SHALL ONLY BE 1.
APPROPRIATE COATING TO PREVENT CORROSION AFTER INSTALLATION.
REMOVE PAINT FROM THE AREA WHERE GROUND LUGS ARE TO BE INSTALLED. SEAL THE AREA WITH PAINT OR THE3.
PROVIDE SUPPLY SIDE GROUND BONDING JUMPER SIZED PER THE LATEST EDITION OF THE NEC.2.
ACCORDANCE WITH FAA-STD-019 (LATEST EDITION).
GROUND METAL PARTS, CONDUITS, EQUIPMENT, INTERFACE BOXES, AND JUNCTION BOXES IN 1.
DP-1
EX
SPD
X/Y/Z = POLE SIZE
= FRAME SIZE
= FUSE SIZE
EXIT SIGN WITH EMERGENCY LIGHT
SURGE PROTECTIVE DEVICE
FUSED AT [Y]A
FUSIBLE DISCONNECT [X]A/[Z]
DUPLEX RECEPTACLE
RECESSED/FLUSH MOUNTED
QUAD RECEPTACLE
SURFACE MOUNTED
CONDUIT, FLEXIBLE
CONDUIT, CAPPED
CONDUIT STUB UP
CONDUIT STUB DOWN
SOLID WHETHER CONCEALED OR EXPOSED
HOME RUN TO PANEL DP BREAKER, SHOWN
SAME AS BRANCH CIRCUIT - BUT CONCEALED
ABOVE GROUND EXOTHERMIC WELD
EES (BURIED) GROUND CONDUCTOR
UNDERGROUND POWER CONDUIT
DOWN CONDUCTOR
UG
WITH MOUNTED UTILITY METER
UTILITY COMPANY TRANSFORMER
WITH (2)-12 AWG CONDUCTOR(S) PLUS (1)-12 AWG GROUND
BRANCH CIRCUIT, SURFACE MOUNTED 3/4" RACEWAY,
WHEN MORE THAN 3 IN 3/4" RACEWAY
CROSS MARKS DENOTE NUMBER OF 12 AWG CONDUCTOR(S)
RECESSED CEILING MOUNTED LED LIGHTING FIXTURE
ABOVE GROUND, CONDUCTOR
SYMBOL DESCRIPTION
OH OVERHEAD CONDUCTORS
DESCRIPTIONSYMBOL
120V, 20A, SPECIFICATION GRADE
THREE POLE SWITCH
AC
AIR CONDITIONER CONTROLS / THERMOSTAT
SINGLE POLE SWITCH
DIMMER SWITCHD
DEMOLITION
SINGLE RECEPTACLE
(GFCI)
DUPLEX RECEPTACLE (GFCI)
ETHERNET PORT BOX
TELEPHONE
DISTRIBUTION PANELBOARD
SURFACE-MOUNTED ELECTRICAL
DISTRIBUTION PANELBOARD
RECESSED ELECTRICAL
WRAPAROUND LIGHT
CEILING MOUNTED LED LIGHTING FIXTURE
EXISTING STEPLIGHT FIXTURE
EMERGENCY LIGHT (SINGLE)
EMERGENCY LIGHT (DUAL)
DUPLEX RECEPTACLE
SINGLE RECEPTACLE
QUAD RECEPTACLE
PCB POLYCHLORINATED BIPHENYLS
AGL ABOVE GRADE LEVEL
AT AIR TRAFFIC
ATCT AIR TRAFFIC CONTROL TOWER
DIST DISTRIBUTION
ELEV ELEVATOR
PNL PANEL
MAY BE USED ON THIS PROJECT
NOT ALL SYMBOLS AND ABBREVIATIONS
mfd-1701252-e011
2023-09-14T12:52:12-0500
DOUGLAS E WEAVER
2022-07-28T10:00:38-0500
RONALD M HUBRICH
AND LOCAL AREA NETWORK DATA PLAN
PROPOSED GROUND FLOOR POWER, LIGHTING
MFD-1701252-E012
:5 lo tt e
EQUIPMENTHALLWAY
ELEV
ELEV
SERVICE ROOM
LINK
STORAGE
W
UP
STAIR
NEW WALL
DPN-A, #12
DPN-A, #12
#14
DPN-A,
DPN-A, #22
DPN-A, #16
PROPOSED GROUND FLOOR POWER, LIGHTING, AND LOCAL AREA NETWORK DATA PLAN
SCALE: 1/4" = 1'-0"E012
EX
D 9
B A
MOUNTING TO BE DETERMINED IN THE FIELD BY RE.
INSTALL (4) ETHERNET PORT IN EACH SIDE OF THE TABLE AS FAA REQUIREMENTS. EXACT LOCATION AND
PROVIDE CONNECTION BETWEEN CATV OUTLET, TABLE RECEPTACLES, COMMUNICATION CONNECTIONS AND
EXACT LOCATIONS TO BE DETERMINED IN THE FIELD BY RE.
INSTALL A TABLE MOUNTED QUAD RECEPTACLE AND BOX. SUPPLY POWER FROM DPN-A PANEL BREAKER 22.
ON SITE STAFF'S REQUEST.
PROVIDE A CTAV OUTLET AT 72" AFF FOR TV CONNECTIONS AND 1" C FROM JBOX TO 6" ABOVE CEILING. PER
PROVIDE AND INSTALL NEW EMERGENCY LED SIGN.
STAFF'S REQUEST.
INSTALL NEW ETHERNET PORT BOX BY USING NEAREST ETHERNET PORT FOR CONNECTIONS PER ON SITE
EXISTING ELECTRICAL PANEL MDP FOR PANELS DPE-A, DPN-B, DPN-A.
PANEL SCHEDULE INFORMATION.
EXISTING 225A ELECTRICAL DISTRIBUTION PANEL DPE-A. REFER TO DRAWING E004 FOR MORE EXISTING
SCHEDULE INFORMATION.
EXISTING ELECTRICAL DISTRIBUTION PANEL DPN-B. REFER TO DRAWING E003 FOR MORE EXISTING PANEL
SCHEDULE INFORMATION.
EXISTING ELECTRICAL DISTRIBUTION PANEL DPN-A. REFER TO DRAWING E003 FOR MORE EXISTING PANEL
AND E020 FOR MORE POWER WIRING AND LED INFORMATION.
PROVIDE AND INSTALL, NEW LED LIGHT BULB IN THE EXISTING LIGHT FIXTURE. REFER TO DRAWING E013
PROVIDE AND INSTALL NEW DUPLEX RECEPTACLE. REFER TO DRAWING E013 FOR MORE POWER WIRING
FOR MORE POWER WIRING AND LED INFORMATION.
PROVIDE AND INSTALL NEW LED WRAPAROUND LIGHTING FIXTURES. REFER TO DRAWING E013 AND E020
KEYED NOTES:
LEGEND:
-NEW
-EXISTING
PANELBOARD DPN-A.
ROUTE WRAPAROUND LIGHTING 12 AWG CONDUCTOR(S) TO EXISTING ELECTRICAL DISTRIBUTION 3.
FAA-C-1217.
ENSURE ALL INTERIOR POWER DISTRIBUTION WIRING ARE IN ACCORDANCE WITH THE LATEST EDITION OF 2.
REFER TO DRAWING G013, E011, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.
mfd-1701252-e012
2023-09-14T12:52:32-0500
DOUGLAS E WEAVER
2022-07-28T10:00:49-0500
RONALD M HUBRICH
MFD FACILITY PANEL SCHEDULES
MFD-1701252-E013
lo tt e
AMP
SPACE
HVAC #1 TRACON ROOM
LPE-A RADAR PANEL
BUS RATING
MAIN
CKT.
NO.
*ACTUAL CIRCUIT BREAKER INFORMATION MAY BE DIFFERENT THAN SHOWN.
225 AMPS
225A CIRCUIT BREAKER
BUS CONN.
BREAKER
POLE
EXISTING ELECTRICAL PANELBOARD DPN-A
E013
EXISTING ELECTRICAL PANELBOARD MDP
EXISTING ELECTRICAL PANELBOARD DPN-B
EXISTING PANEL SCHEDULE*
PANEL
SERVICE VOLTAGE
PHASE
DESCRIPTION
EXIT LIGHTS
EMERGENCY & NIGHT LIGHTS
TRACON WALL LIGHTS
GATE CONTROL
DPE-A
120/208 VOLTS
MOUNTING
MIN. AIC
MFD TRACON
SURFACE
10 KA
DAMPER MOTORS
1 20
1 30
1 40
1 100
FED FROM MDP PANEL
PARKING LOT LIGHTS
SPARE
LPE-D TELCO PANEL
HVAC #2 EQUIPMENT ROOM
LPE-C TRACON PANEL
LPE-E CAB PANEL
LPE-B COMMUNICATIONS PANEL
RTU RECEPTACLE
HVAC #3 HUMIDIFIER
DPN-B
POLE AMP
HVAC #2 HUMIDIFIER
100 AMPS
100A CIRCUIT BREAKER
SECURITY LIGHTS
1 35
1 70
LIGHT STATION CONTROL PANEL
HVAC #1 HUMIDIFIER & HVAC #3 OFFICES
HVAC
SPACE 31 32 SPACE
SPACE 33 34 SPACE
SPACE 35 36 SPACE
SPACE 37 38 SPACE
SPACE 39 40 SPACE
SPACE 41 42 SPACE
SMOKE HOUSE LIGHT & HEATER
SPARE 151
60 3
PANEL "B"
MDP
400 AMPS
300A CIRCUIT BREAKER
FED FROM
GRID POWER
SPARE 31 32
33 34
35 36
37 38
39 40
41 42
HEATER #3
PANEL "A"
ELEVATOR
A/C UNIT
20 1
100 3
100 3
LEGEND:
-CIRCUIT
NEW BRANCH
-NEW
-EXISTING
DUPLEX RECEPTACLE SPARE **
NEW FUTURE WALL
15 1
WRAPAROUND LIGHTING SPARE**
NEW CONFERENCE ROOM LED
RESTROOM EXHAUST FAN
SSCC ROOM
DUPLEX / EQUIPMENT ROOM /
T.O. UNIT ROOM
DUPLEX TRACON /EQUIPMEN -
LIGHTED STATUS BOARD
DUPLEX TRACON /
LINK HEATER
SECRETARY - A.T. TRAINING
2ND ENTRY LIGHTS -
LIGHTS RESTROOM
OFFICE
LIGHTS TRACON / T.O. UNIT
DIMMERS - EQUIPMENT ROOM EAST
DPN-A
DIMMERS - EQUIPMENT ROOM CENTER
DIMMERS - EQUIPMENT ROOM WEST
A.T. CHIEF OFFICE RECEPTACLE
SECRETARY RECEPTACLE
100 AMPS
100A CIRCUIT BREAKER
LIGHTS - PARKING LOT
LIGHTS - OUTSIDE & PHOTO CELL
CONFERENCE ROOM
DUPLEX A.T. OFFICE /
31 32
DUPLEX SECRETARY / A.T. CHIEF 33 34
35 36
T.O. UNIT ROOM
DUPLEX / EQUIPMENT -
DUPLEX - SSCC / AT CHIEF 37 38 ENTRANCE HEATER
MICROWAVE TO
DUPLEX - SERVICE ROOM -
39 40
DUPLEX ON ROOF/GFCI 41 42 LINK HEATER
SPARE 1
A. T. OFFICE RECEPTACLE
MICROWAVE RECEPTACLE
REFRIGERATOR RECEPTACLE
LIGHTS ENTRANCE
HOT WATER HEATER
LIGHTS - A.T. OFFICE/CONFERENCE ROOM
HALL LIGHTS - A.T. OFFICE/CONFERENCE
A.T. OFFICE / RESTROOMS
DUPLEX SECRETARY /
HEATER #3
HEATER #5
** SEE NOTE 3 AND 4.
SCHEDULE CLOUDED REGIONS ON THIS DRAWING FOR NEW BRANCH CIRCUIT LOCATIONS.
REPLACE EXISTING SPARE BREAKERS WITH NEW, 20A, CIRCUIT BREAKER. REFER TO THE PANEL 4.
AND FLUSH-MOUNTED DUPLEX RECEPTACLES VIA SPARE CKT #12, 14, 16, AND 22 AS NECESSARY.
PROVIDE NEW 12 AWG POWER WIRING TO THE NEW CEILING-MOUNTED LED WRAPAROUND LIGHTING 3.
PERFORM NEW WORK SHOWN IN CLOUDED REGION OF PANEL SCHEDULE.2.
DPN-A.
FIELD VERIFY IF EXISTING ELECTRICAL PANEL MDP SERVES POWER FOR SUB-PANELS DPE-A, DPN-B, AND 1.
EXISTING ELECTRICAL PANELBOARD DPE-A
PANEL "C"
mfd-1701252-e013
2023-09-14T12:52:51-0500
DOUGLAS E WEAVER
2022-07-28T10:00:59-0500
RONALD M HUBRICH
SCHEDULE & LIGHTING FIXTURE DETAIL
CONFERENCE ROOM LUMINARIE
MFD-1701252-E014
lo tt e
CLS-SE3
SINGLE FACE, NO ARROWS
RED LETTERS, BATTERY RUN TIME 90 MINUTES,
CAD BATTERY,
CEILING MOUNTED, LED EXIT LIGHTING UNIT, NI-
SUSPENDED
(TYPICAL)
JUNCTION BOX
NEW OR EXISTING
FEET (TYPICAL)
FIXTURE WHIP MAXIMUM LENGTH 6
NEW FLEXIBLE METAL CONDUIT
STRUCTURE
SUPPORT SYSTEM OR BUILDING
EXISTING UNISTRUT-TYPE
NEW RECESSED FIXTURE
EACH END
CORNERS OF FIXTURE WITH 5 TWISTS AT
GALV 12 GA SUSPENSION WIRE AT 2
CONDUIT EMT
NEW OR EXISTING
LBL4 LP840 RFD230716
(TO BE FCC PART 15 CLASS B COMPLIANT)
4'-0" LED WRAPAROUND WITH CLASS B DRIVER
ND-EML
WA-SW-SC-UNV-X1-
P8622-LED4-MO-
NON DIMMING
DIM TO DARK
@ H = 8'-0"
RECESSED
1204000K LEDs DIM TO DARK
EMERGENCY LIGHT
2' X 2' RECESSED TROFFER W/BATTERY PACK
LUMINAIRE SCHEDULE
LABEL QTY. CATALOG NUMBER DESCRIPTION LAMP
MANUFACTURER VOLTS MOUNTING
RECESSED
LITHONIA 120
DRIVER
4000K LEDs 120
RECESSED FIXTURE MOUNTING DETAIL
E014
LITHONIA LBL4 LP840 RFD230716
(TO BE FCC PART 15 CLASS B COMPLIANT)
4'-0" LED WRAPAROUND WITH CLASS B DRIVER
LIGHTING
HUBBELL
DUAL/LITE
4000K LEDs PROVIDE LUTRON 1% DIMMING DRIVER OPTION.
---LED LAMPS
LIGHTING
PRUDENTIAL
RECESSED0
LIGHT FIXTURES.
COMPLETE REQUIREMENTS OF CFR TITLE 47 PART 15 FOR CLASS A AND/OR CLASS B DEVICES FOR LED 5.
INSTALLATION OF LIGHTING FIXTURES AND SUPPORTS TO MEET PROJECT SPECIFICATIONS AND SEISMIC 4.
LAYOUT AND KEEP FLEXIBLE CONDUIT RUNS TO A MAXIMUM OF 6 FEET.
PROVIDE NEW CONDUIT AND WIRING FROM EXISTING JUNCTION BOXES TO SUPPORT NEW LIGHTING 3.
COMPLETE ASSEMBLY.
COMPATIBILITY AND COMPLIANCE WITH LIGHTING CONTROL SYSTEM, PROPER FIT, AND A SECURE AND
SHALL BE VERIFIED (CONSULT WITH LIGHTING MANUFACTURER) PRIOR TO INSTALLATION TO ENSURE
MOUNTING BRACKETS AND ACCESSORIES ALL LUMINAIRE BALLASTS, DRIVERS, ROW LENGTH OPTIONS, 2.
COR AND WILL BE REVIEWED BY THE ENGINEER OF RECORD FOR COMPLIANCE AND APPROVAL.
EXCEED. SUBSTITUTIONS FOR THE SPECIFIED FIXTURES SHALL BE SUBMITTED IN ADVANCE TO THE FAA
OF QUALITY, APPEARANCE, AND PERFORMANCE THAT ANY SUBSTITUTED FIXTURES MUST MATCH OR
ON THIS DRAWINGS ESTABLISH A LEVEL THE FIXTURES SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE 1.
mfd-1701252-e014
2023-09-14T12:53:13-0500
DOUGLAS E WEAVER
2022-07-28T10:01:07-0500
RONALD M HUBRICH
AND INDEX OF DRAWINGS
COVER SHEET, VICINITY MAP,
RDS
MFD-1701252-G012
lo tt e
MANSFIELD, OHIO
MANSFIELD LAHM MUNICIPAL AIRPORT (MFD)
AIR TRAFFIC CONTROL TOWER (ATCT)
VICINITY MAP
TRANSPO
OF
ST
TES
EN
OF
IC
AVIA
TRAT
SI
NI
INDEX OF DRAWINGS
DRAWING NO. DESCRIPTION
MFD-1701252-E014
MFD-1701252-E013
MFD-1701252-E012
MFD-1701252-E011
MFD-1701252-M002
MFD-1701252-M001
MFD-1701252-A017
MFD-1701252-D002
MFD-1701252-D001
MFD-1701252-G014
MFD-1701252-G013
MFD-1701252-G012
CONFERENCE ROOM LUMINARIE SCHEDULE & LIGHTING FIXTURE DETAIL
PANEL SCHEDULES
PROPOSED GROUND FLOOR POWER, LIGHTNING, AND LOCAL AREA NETWORK DATA PLAN
ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS
MECHANICAL PARTIAL GROUND FLOOR PLAN - DEMO AND NEW CONSTRUCTION
MECHANICAL COVERSHEET
GROUND FLOOR PLAN AND RCP PLAN
ELECTRICAL DEMOLITION PLAN
GENERAL NOTES
LEGEND AND ABBREVIATIONS
COVER SHEET, VICINITY MAP, AND INDEX OF DRAWINGS
mfd-1701252-g012
2023-09-14T12:50:01-0500
DOUGLAS E WEAVER
2022-07-28T09:58:56-0500
RONALD M HUBRICH
LEGEND AND ABBREVIATIONS
MFD-1701252-G013
:3 lo tt e
ABBREVIATIONS
WITH SEQUENCED FLASHERS
- AMPERESAMP
- ABOVE GROUND/GRADE LEVELAGL
- AMBIENT LIGHT SENSORALS
ALSF - HIGH INTENSITY APPROACH LIGHTING SYSTEM
AOA - AIR OPERATIONS AREA
- APPROXIMATELYAPPROX
ARP - AIRPORT REFERENCE POINT
- AIRPORT SURFACE DETECTION EQUIPMENTASDE
ASOS - AUTOMATED SURFACE OBSERVATION
SYSTEM (NWS)
ASR - AIRPORT SURVEILLANCE RADAR
ATCT - AIRPORT TRAFFIC CONTROL TOWER
AWG - AMERICAN WIRE GAUGE
BGL - BELOW GROUND/GRADE LEVEL
BLDG - BUILDING
BOT - BOTTOM
BSC - BARE STRANDED COPPER
BSCU - BARE SOLID COPPER
CCM - CONCRETE CABLE MARKER
CJ - CONTROL JOINT
COMM - COMMUNICATIONS
CONC - CONCRETE
CONT - CONTINUE, CONTINUATION, CONTINUOUS
COR - CONTRACTING OFFICER'S REPRESENTATIVE
DEB - DIRECT EARTH BURIAL
DIM - DIMENSION
DISC - DISCONNECT
DME - DISTANCE MEASURING EQUIPMENT
DU - DISTRIBUTION UNIT
E/G - ENGINE-GENERATOR
EES - EARTH ELECTRODE SYSTEM (COUNTERPOISE)
EFGS - END-FIRE GLIDE SLOPE
EJ - EXPANSION JOINT
EL - ELEVATION (HEIGHT)
ELD - ELECTRICAL LINE DISTRIBUTION
ELEC - ELECTRIC
EMERG - EMERGENCY
EMT - ELECTRIC METALLIC TUBING
EQUIP - EQUIPMENT
EXIST - EXISTING
EX/EXT - EXTERIOR, EXTERNAL
F/O - FIBER OPTIC
FDN - FOUNDATION
FDP - FIBER DISTRIBUTION PANEL
FF - FINISH FLOOR
FFM - FAR FIELD MONITOR
FOD - FOREIGN OBJECT DEBRIS
FT - FOOT/FEET
GALV - GALVANIZED
GEC - GROUNDING ELECTRODE CONDUCTOR
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
GFM - GOVERNMENT FURNISHED MATERIAL
GND - GROUND
GRP - GEOGRAPHICAL REFERENCE POINT
GRSC - GALVANIZED RIGID STEEL CONDUIT
GS - GLIDE SLOPE
HDPE - HIGH DENSITY POLYETHYLENE
HT - HEIGHT
HH - HANDHOLE
HV - HIGH VOLTAGE
HZ - HERTZ
ICC - INDIVIDUAL CONTROL CABINET
ILS - INSTRUMENT LANDING SYSTEM
IM - INNER MARKER
KHZ - KILO-HERTZ
KV - KILO-VOLT
KVA - KILO-VOLT AMPERE
KW - KILO-WATT
LHA - LAMP HOUSING ASSEMBLY
LIR - LOW IMPACT RESISTANT
LOC - LOCALIZER
LOM - LOCATOR - OUTER MARKER
- HEATING, VENTILATING AND AIR CONDITIONINGHVAC
NORTH ARROW
A010
DETAIL MARKER
A012
EXTENDED SECTION CUT
SECTION CUT
ELEVATION SYMBOL
LEGEND
C001
MAY BE USED ON THIS PROJECT
NOT ALL SYMBOLS AND ABBREVIATIONS
LC
REVISED AREA
ENCOMPASS
CLOUD TO
B120ROOM/AREA NUMBER
DEMOLITION
REVISION
REVISION DESIGNATION
NUMBER, POUNDS
CENTERLINE
FEET OR MINUTES
INCHES OR SECONDS
DEGREE
AT
NEW WORK
EXISTING WORK
EXISTING WORK TO BE REMOVED
PL
GLIDE SLOPE CRITICAL AREA
RUNWAY SAFETY AREA
RUNWAY OBJECT FREE AREA
FENCE
PROPERTY LINE
SITE ACCESS ROUTE
STAGING AREA
UNDERGROUND POWER CONDUIT UG
- MEAN SEA LEVELMSL
- MULTI-POINT (GROUND)MP
- MINIMUMMIN
- MEGAHERTZMHZ
- MANHOLEMH
- MAXIMUMMAX
WITH RUNWAY ALIGNMENT INDICATOR LIGHTS (RAIL)
- MEDIUM INTENSITY APPROACH LIGHTING SYSTEM (MALS)MALSR
WITH SEQUENCED FLASHERS
- MEDIUM INTENSITY APPROACH LIGHTING SYSTEMMALSF
- RUNWAY END IDENTIFIER LIGHTSREIL
- REFERENCEREF
- RESIDENT ENGINEER (FAA/TSSC)RE
- RECEIVERRCVR
- REINFORCED CONCRETE PIPERCP
- RUNWAY ALIGNMENT INDICATOR LIGHTSRAIL
- RUNWAYR/W
- POLYVINYL CHLORIDE CONDUITPVC
- POUNDS PER SQUARE INCHPSI
- POUNDS PER SQUARE FOOTPSF
- PAIRPR
- POWER POLE/UTILITY POLEPP
- POINT OF STARTPOS
- POINT OF BEGINNINGPOB
- POINT OF INTERCEPTPOI
- PANELPNL
- PROPERTY LINE, PLATEPL
- POWER AND CONTROL UNITPCU
- PRECISION APPROACH PATH INDICATOR LIGHTSPAPI
- OUTER MARKEROM
- OBJECT FREE AREAOFA
- OUTSIDE DIAMETER/OVERFLOW DRAINOD
- NATIONAL WEATHER SERVICENWS
- NOTICE TO AIRMENNOTAM
- NATIONAL GEODETIC VERTICAL DATUMNGVD
- NATIONAL ELECTRIC CODENEC
- NON-DIRECTIONAL BEACONNDB
- NORTH AMERICAN VERTICAL DATUMNAVD
- NORTH AMERICAN DATUMNAD
- NOT APPLICABLEN/A
- TRANSMITTERXMTR
- TRANSFORMERXFMR
- WELDED WIRE FABRICWWF
- VISUAL APPROACH SLOPE INDICATORVASI
- UNINTERRUPTIBLE POWER SOURCE/SUPPLYUPS
- TYPICALTYP
- TRANSIENT VOLTAGE SURGE SUPPRESSORTVSS
- TAXIWAY SAFETY AREATSA
- TOP OF STEELTOS
- TAXIWAY OBJECT FREE AREATOFA
- TOP OF CONCRETETOC
- TELEPHONE COMPANYTELCO
- TAXIWAYT/W
- TO BE DETERMINEDTBD
- STATIONSTA
- SYSTEM SUPPORT CENTER (FAA)SSC
WITH RUNWAY ALIGNMENT INDICATOR LIGHTS
SSALR - SIMPLIFIED SHORT APPROACH LIGHTING SYSTEM
- SYSTEM MANAGEMENT OFFICE (FAA)SMO
- SURGE ARRESTORSA
- RUNWAY VISUAL RANGE RVR
- REMOTE TRANSMITTER/RECEIVERRTR
- RIGID STEEL CONDUIT/RIGID GALVANIZED STEELRSC/RGS
- RUNWAY SAFETY AREARSA
- REMOTE RADIO CONTROL SYSTEMRRCS
- RUNWAY PROTECTION ZONERPZ
- RIGHT-OF-WAYROW
- RUNWAY OBJECT FREE AREAROFA
- RADIO FREQUENCYRF
- REVISIONREV
- RUNWAY EDGE LIGHTSREL
mfd-1701252-g013
2023-09-14T12:50:15-0500
DOUGLAS E WEAVER
2022-07-28T09:59:13-0500
RONALD M HUBRICH
File details come from the government source that posted it. Updated .