16 MFD-1701252-Drawings IFB.pdf

PDF 7 MB Posted

Attached to
Refurbishment of TRACON Facilities at Canton, OH and Mansfield, OH
Solicitation number
697DCK-24-R-00488
Issued by

About this file

This document contains drawings and specifications for the refurbishment of the TRACON facilities at the Canton, OH and Mansfield, OH airports. The Federal Aviation Administration (FAA) has a requirement for this project with an estimated construction magnitude between $250,000 - $1,000,000. Key details include:

The solicitation number is 697DCK-24-R-00488. It is an unrestricted competition open to all offerors qualified under NAICS code 236220. A one-time site visit will be offered, with details to be provided in advance. Requests for Information must be submitted in writing by 8/20/24, with responses provided via amendment. The proposal due date and submission requirements are included in the solicitation attachment. The Southwestern Region of the Department of Transportation Federal Aviation Administration is the procuring agency for this requirement.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

ENGINEERING SERVICES

TERMINAL

ATCT

GENERAL NOTES

VACATED TRACON AREA CONVERSION

OHMANSFIELD LAHM MUNICIPAL AIRPORTMANSFIELD

AF

SKM

JB

PROJECT ENGINEER MGR: ENGINEERING

07/15/2022 1701252

MFD-1701252-G014

m fd -1

-g

.d g n

THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

C O

N S

T R

U

IO

/2

:2

:1

A

M P lo tt e d b y

V

-C

E

G -E

D

B

F

H

8 7 6 5 4 3 2 1

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

REDLINE

APVD

RELEASED FOR:

847.294.8183

Des Plaines, IL 60018

2300 E. Devon, Suite 344

T4 Great Lakes Region

PTSI Managed Services Inc.

CONSTRUCTION - 07/15/2022

Y

Q

L

IT

INTEGRITY

IN

I

PORT SERVIC

GENERAL DEMOLITION NOTES:

EXISTING WALLS TO PROVIDE A SMOOTH AND FLUSH TRANSITION.

PREP EXISTING WALLS TO RECEIVE NEW FINISHES AS REQUIRED AND ALIGN ALL NEW WALLS TO 6.

WORK.

ITEMS SALVAGED FOR RE-USE SHALL BE CLEANED, STORED AND RE-INSTALLED AS REQUIRED BY NEW 5.

BROUGHT IMMEDIATELY TO THE RESIDENT ENGINEER ATTENTION.

ANY EVIDENCE OF HAZARDOUS MATERIALS (I.E ACM'S) PRIOR TO OR DURING CONSTRUCTION SHALL BE 4.

DEMOLITION.

NOTIFY RESIDENT ENGINEER OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING

DEMOLITION REQUIRED TO ACCOMMODATE NEW WORK. REFER TO NEW CONSTRUCTION PLANS.

ALL DIMENSION ON DEMOLITION PLANS ARE FOR ROUGH OPENINGS TO DETERMINE THE EXTENT OF 3.

THE OWNER.

NEW" CONDITION AND WILL MATCH EXISTING ADJACENT CONSTRUCTION AT NO ADDITIONAL COST TO

ACTIVITIES. ANY AREA DAMAGED AND NOT INDICATED TO BE REMOVED WILL BE REPAIRED TO "LIKE

PROTECT ALL EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE DURING CONSTRUCTION 2.

THE OWNER OR DISCARDED.

COORDINATE WITH RESIDENT ENGINEER ALL ITEMS THAT ARE TO BE REMOVED AND RETURNED TO 1.

GENERAL ARCHITECTURAL NOTES:

MATERIALS AND EQUIPMENT.

ENVIRONMENTAL CONDITIONS WHICH ARE REQUIRED TO MAINTAIN THE ORIGINAL QUALITY OF

MANUFACTURER'S INSTRUCTIONS REGARDING TEMPERATURE LIMITATIONS AND OTHER

FOREIGN MATTER OR MOISTURE FROM ANY SOURCE. COMPLY WITH MATERIAL AND EQUIPMENT

MANNER AS TO PREVENT DAMAGE, INCLUDING DAMAGE WHICH MIGHT RESULT FROM INTRUSIONS OF

TRANSPORT, DELIVER, HANDLE AND STORE MATERIALS AND EQUIPMENT AT THE JOB SITE IN SUCH A 16.

ALL WORK SHALL BE PLUMB, SQUARE, LEVEL, IN PROPER ALIGNMENT, AND SECURELY FASTENED.15.

SYSTEM.

DO NOT ALLOW ADHESIVE ODOR AND OTHER FUMES FROM CONSTRUCTION ACTIVITY TO ENTER HVAC 14.

EXPENSE AND TO THE SATISFACTION OF THE RESIDENT ENGINEER.

INCLUDED IN THE SCOPE OF THIS PROJECT, SHALL BE REPAIRED AND CORRECTED AT CONTRACTOR'S

ELEMENTS AND FIRE RATED ASSEMBLIES. ANY DAMAGE TO THE EXISTING BUILDING AND/OR SITE, NOT

EXTEND PATCH TO THE NEAREST NATURAL BREAK POINT. REPAIR FIREPROOFING ON STRUCTURAL

OCCURS. PATCH AND FINISH DISTURBED AREAS TO MATCH ADJACENT MATERIALS AND FINISHES.

PROVIDE PROTECTION FOR ALL EXISTING FINISHES TO REMAIN, AND REPAIR ANY DAMAGE THAT 13.

FURNISHED TO THE RESIDENT ENGINEER PRIOR TO THE COMMENCEMENT OF ANY WORK.

DEMOLITION AND CONSTRUCTION PHASES. A COPY OF SUCH INSURANCE COVERAGE SHALL BE

COPIES OF ALL APPLICABLE PERMITS SHALL BE MAINTAINED ON-SITE AND ADHERED TO DURING THE

NATIONAL BUILDING REGULATIONS OR CODES TO ADEQUATELY PROTECT PERSONS AND PROPERTY.

COSTS SHALL INCLUDE THE COST OF PROPER INSURANCE AS REQUIRED BY STATE AND LOCAL LAWS, THE CONTRACTOR SHALL APPLY FOR AND OBTAIN ALL PERMITS REQUIRED BY REGULATORY AGENCIES. 12.

CONCEAL PIPING, DUCTWORK WIRING AND CONDUITS.

CONDUITS ALLOW FOR MAXIMUM ACCESSIBILITY FOR MAINTENANCE AND REPAIRS. IN FINISHED AREAS

MECHANICAL AND SECURITY SYSTEMS AS REQUIRED SO THAT PIPING, WIRING, DUCTWORK AND

CONSTRUCTION TO REMAIN. ESTABLISH ROUTING FOR ELECTRICAL, TELECOMMUNICATION, PLUMBING, THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF NEW CONSTRUCTION WITH EXISTING 11.

FOR SERVICE INTERRUPTIONS A MINIMUM OF 14 BUSINESS DAYS PRIOR TO PLANNED INTERRUPTION.

THE SYSTEM. SERVICE OR UTILITY IN QUESTION. THE CONTRACTOR WILL MAKE REQUESTS IN WRITING

ACCEPTABLE SCHEDULE FOR THE INTERRUPTION, SWITCH OVER OR OTHER CHANGE IN OPERATION TO

CONTRACT TO PERFORM THE WORK, CONSULT RESIDENT ENGINEER TO ARRIVE AT A MUTUALLY

PRIOR TO ANY TEMPORARY INTERRUPTION OF SERVICES DEEMED ABSOLUTELY NECESSARY BY THE 10.

ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED.9.

CONSTRUCTION.

RESIDENT ENGINEER OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING NEW

ALL DIMENSIONS ARE FROM FINISHED WALL TO FINISHED WALL, UNLESS OTHERWISE NOTED. NOTIFY 8.

ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.

PROVIDE AND INSTALL ALL MANUFACTURED ITEMS, MATERIALS AND EQUIPMENT IN STRICT 7.

ACCORDANCE WITH FEDERAL, STATE AND LOCAL CODES AND REGULATIONS.

UNSATISFACTORY MATERIALS MUST BE REMOVED FROM THE PROJECT PROPERTY AND DISPOSED OF IN

LAWFULLY REMOVED ON A REGULAR BASIS. ALL WASTE, DEBRIS, UNUSED MATERIALS AND OTHER

THE WORK AREA IS TO BE KEPT CLEAN AND ORDERLY AT ALL TIMES. REFUSE AND DEBRIS SHALL BE 6.

SCOPE OF THE CONTRACT DOCUMENTS.

FEES AND PERMITS REQUIRED AND ASSOCIATED WITH ALL PHASES OF THE WORK AND WITHIN THE

CODES, ORDINANCES, AND REGULATIONS. CONTRACTOR WILL OBTAIN AND BE RESPONSIBLE FOR ALL

ALL WORK PERFORMED BY THE CONTRACTOR SHALL BE DONE IN ACCORDANCE WITH APPLICABLE 5.

SHALL BE FURNISHED.

THE GREATER QUANTITY AND THE HIGHER QUALITY (AS DETERMINED BY THE CONTRACTING OFFICER)

STRINGENT REQUIREMENTS (AS DETERMINED BY THE CONTRACTING OFFICER) SHALL GOVERN, AND

IN CASE OF CONFLICT BETWEEN OR WITHIN THE VARIOUS CONTRACT DOCUMENTS, THE MORE 4.

AREAS OF CONSTRUCTION.

TENANTS AND GENERAL PUBLIC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE THE

BARRICADES, DANGER SIGNALS AND SIGNS IN AREAS OF WORK FOR PROTECTION AND SAFETY OF

NOT BLOCK EXISTS. PROVIDE, ERECT AND MAINTAIN BARRICADES, DANGER SIGNALS AND MAINTAIN

MAINTAIN ALL BUILDING LIFE SAFETY, FIRE PROTECTION AND SECURITY SYSTEMS AT ALL TIMES. DO 3.

DURING CONSTRUCTION.

THE PROJECT SITE TO EMERGENCY AND SECURITY VEHICLES AT ALL TIMES AND WITHOUT DELAY

AND HAUL ROUTES IN A MANNER THAT ALLOWS UNOBSTRUCTED EMERGENCY ACCESS TO ALL AREAS OF

CONSTRUCTION PHASES OF THIS PROJECT, IN ADDITION, THE CONTRACTOR MUST MAINTAIN ACCESS

RESIDENT ENGINEER. LOCAL TRAFFIC ACCESS SHALL BE MAINTAINED DURING THE DEMOLITION AND

THE CONTRACTOR SHALL VERIFY AND COORDINATE ALL SITE AND BUILDING ACCESS WITH THE 2.

PROBLEM RESOLUTION WITHOUT DELAYING THE WORK.

AND DRAWINGS PRIOR TO PROCEEDING WITH ANY PORTION OF THE WORK. ALLOW TIME FOR

BUILDING CONDITIONS. NOTIFY RESIDENT ENGINEER OF ANY CONFLICTS BETWEEN FIELD CONDITIONS

THE CONTRACTOR SHALL VERIFY AND COORDINATE THE SCOPE OF WORK WITH EXISTING SITE AND 1.

DESIGN CODES AND CRITERIA:

- OBC 2017, OHIO BUILDING CODE

- IBC INTERNATIONAL BUILDING CODE

AND STANDARDS.

DRAWINGS WERE COMPLETED IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING CODES

APPLICABLE CODES, LOCAL AUTHORITIES HAVING JURISDICTION, REGULATIONS, AND STANDARDS, THESE

ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH DIVISION 26 OF THE CONTRACT DOCUMENTS, ALL

IS

FOR OFFICIAL USE ONLY

PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552

mfd-1701252-g014

2023-09-14T12:50:29-0500

DOUGLAS E WEAVER

2022-07-28T09:59:26-0500

RONALD M HUBRICH

MECHANICAL COVERSHEET

AK

BT

UR

MFD-1701252-M001

-m lo tt e

ANY AND ALL UTILITY/SYSTEM SHUTDOWNS.

THE RESIDENT ENGINEER, IN WRITING, 10 WORKING DAYS IN ADVANCE OF

COORDINATE WITH SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY AND 4.

RESIDENT ENGINEER PRIOR TO PROCEEDING WITH DEMOLITION.

BUILDING, THE SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY THE

INTEGRITY OF THE WHERE DEMOLITION WOULD AFFECT THE STRUCTURAL 3.

DAMAGE ADJOINING SURFACES OR EQUIPMENT INDICATED TO REMAIN.

MANNER THAT WILL NOT DEMOLITION SHALL BE PERFORMED IN SUCH A 2.

WORK.

REPORTED TO THE RESIDENT ENGINEER PRIOR TO STARTING DEMOLITION

CONSTRUCTION DOCUMENTS AND VERIFIED FIELD CONDITIONS SHALL BE

ROUTING OF EXISTING PIPING, ETC. ANY DISCREPANCIES BETWEEN THE

SIZES AND ROUTING OF EXISTING DUCTWORK, THE EXACT SIZES AND

SHALL VERIFY THE CONDITION OF ALL EXISTING EQUIPMENT, THE EXACT

SUBCONTRACTOR/CONTRACTOR BEFORE DEMOLITION WORK BEGINS THE 1.

SHALL BE PROVIDED TO THE ENGINEER OF RECORD FOR REVIEW.

SYSTEMS WITHIN THE SCOPE OF WORK. UPON COMPLETION OF WORK, A WRITTEN TEST & BALANCE AND OPERATION OF CONTROLS REPORT

AND BALANCE ALL MECHANICAL UPON COMPLETION OF WORK AN INDEPENDENT AND CERTIFIED TEST & BALANCE COMPANY SHALL TEST 18.

MECHANICAL SYSTEMS.INSTALL ALL BALANCING DEVICES NEEDED TO ACHIEVE PROPER ADJUSTING AND BALANCING OF 17.

DUCTWORK AND PIPING SHALL NOT RUN OVER ELECTRIC PANELS OR ELECTRIC EQUIPMENT.16.

ACCEPTANCE.UNLESS OTHERWISE NOTED, GUARANTEE ALL PARTS AND LABOR FOR ONE YEAR FROM DATE OF FINAL 15.

THIS SHALL INCLUDE PROVIDING SUFFICIENT SPACE TO MEET ALL OTHER TRADE CLEARANCE REQUIREMENTS.

INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, PLUMBING, FIRE PROTECTION, TELECOM, STRUCTURAL, CIVIL, AND GENERAL ARCHITECTURE.

WORK WITH THAT OF ALL OTHER TRADES IT SHALL BE THE RESPONSIBILITY OF THIS SUBCONTRACTOR/CONTRACTOR TO COORDINATE THEIR 14.

OTHERWISE, THE REUSE OF EXISTING DEVICES, MATERIALS, EQUIPMENT AND ASSOCIATED COMPONENTS AND ACCESSORIES IS PROHIBITED.

BE FIRST QUALITY. UNLESS INDICATED ALL EQUIPMENT, DUCTWORK, DEVICES, DAMPERS, CONTROLS, VALVES, PIPING, INSULATION, ETC SHALL 13.

CONTRACT DOCUMENTS SHALL BE IDENTIFIED AND BROUGHT THE RESIDENT ENGINEER'S ATTENTION PRIOR TO COMMENCING WORK.

THE CONTRACT DOCUMENTS PRIOR TO STARTING CONSTRUCTION. ANY DISCREPANCIES NOTED BETWEEN EQUIPMENT VENDOR PLANS AND

DRAWINGS AND COORDINATE THESE PLANS WITH THIS SUBCONTRACTOR/CONTRACTOR SHALL OBTAIN A FULL SET OF ALL EQUIPMENT VENDOR 12.

STARTING WORK.

DOCUMENTS AND MANUFACTURER'S REQUIREMENTS, THIS SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY THE RESIDENT ENGINEER PRIOR TO

WORK SHALL ADHERE TO THE MANUFACTURERS' RECOMMENDATIONS/REQUIREMENTS. IF A CONFLICT EXISTS BETWEEN THE DESIGN

DOCUMENTS/REQUIREMENTS PRIOR TO STARTING WORK. ALL REVIEW ALL APPLICABLE MANUFACTURERS' INSTALLATION AND MAINTENANCE 11.

SUBMIT LITERATURE FOR ALL EQUIPMENT AND MATERIALS TO THE ENGINEER OF RECORD FOR APPROVAL.

FOR PERFORMANCE AND MATERIALS. MANUFACTURER'S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY 10.

A COMPLETE INSTALLATION.FURNISH ANY MISCELLANEOUS ITEMS NORMALLY USED, SPECIFICALLY MENTIONED OR NOT, TO RENDER 9.

APPROVAL.

STRUCTURAL ENGINEER'S REVIEW AND STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY MANNER WITHOUT A 8.

VERIFY SIZES, LOCATIONS, INVERTS AND ELEVATIONS PRIOR TO RUNNING ANY DUCTWORK/PIPING.7.

ACCEPTANCE.

DISCREPANCIES BETWEEN THE DELIVERY AND CONSTRUCTION DOCUMENTS SHALL BE REPORTED TO RESIDENT ENGINEER PRIOR TO

PRIOR TO ACCEPTING DELIVERY. ANY SUBCONTRACTOR/CONTRACTOR SHALL FIELD INSPECT ALL GOVERNMENT FURNISHED MATERIALS 6.

OTHER TRADES.

SHALL INCLUDE, BUT NOT BE LIMITED TO, OFFSETTING EXISTING PIPING AND MODIFICATIONS REQUIRED FOR COORDINATION WITH ALL

NOT SHOWN ON DRAWINGS. MAKE ALL NECESSARY MODIFICATIONS TO EXISTING CONDITIONS TO PERFORM WORK OF THIS SECTION. THIS

LOCATIONS SHOWN ON DRAWINGS IS GUARANTEED. DETERMINE EXACT LOCATIONS OF EXISTING SYSTEMS/UTILITIES IN FIELD, WHETHER OR

NEITHER ACCURACY NOR COMPLETION OF ALL EXISTING CONDITIONS SHOWN ARE TAKEN FROM EXISTING DRAWINGS AND FIELD SURVEYS. 5.

THE WORK INVOLVED.

IN VIOLATION SHALL BE BROUGHT TO THE ATTENTION OF THE RESIDENT ENGINEER AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF

SHOWN ON THE DRAWINGS WHICH IS NO WORK SHALL BE INSTALLED IN VIOLATION OF ANY GOVERNING STANDARDS AND CODES. ANY WORK 4.

REGULATIONS. IN CASE OF DIFFERENCES THE MOST STRINGENT SHALL GOVERN.

AND LOCAL CODES, RULES AND ALL MECHANICAL WORK SHALL BE IN ACCORDANCE WITH FAA STANDARDS AND ALL APPLICABLE STATE 3.

GETTING THE EQUIPMENT INTO PLACE, AND BECOME THOROUGHLY FAMILIAR WITH ALL OF THE REQUIREMENTS OF THE CONTRACT.

WORK. DETERMINE, IN ADVANCE, THE METHODS OF INSTALLING AND CONNECTING THE APPARATUS, THE MEANS TO BE PROVIDED FOR

THE PREMISES AND ANY EXISTING BEFORE SUBMITTING A BID CAREFULLY STUDY THE CONSTRUCTION DOCUMENTS. CAREFULLY EXAMINE 2.

NOT SCALE THESE DRAWINGS.

MECHANICAL SYSTEM COMPONENTS. DO THESE DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO DEPICT THE GENERAL LOCATION OF 1.

SYMBOLS TYPE MATERIAL FINISH

S-1 SUPPLY DIFFUSER STEEL WHITE

REMARKS

1,2,3

& MODEL #

MANUFACTURER

SIZE

R-1 STEEL WHITE24x24

CEILING MOUNT3.

NC VALUE SHALL NOT EXCEED 30.2.

4-WAY ADJUSTABLE1.

RETURN GRILLE

PRICE #SCD

PRICE #80/F

24X24

2,3

COOLING PER ASHRAE 0.4%

LOCATION

DRY BULB WET BULB ASHRAE 99.6%

HEATING PER

75 DEG F

COOLING HEATING

DESIGN SETPOINTS

72.8 DEG F 1.5 DEG FMANSFILED, OH 88 DEG F 70 DEG F

POINT OF CONNECTION (POC)

POINT OF DISCONNECT (POD)

THERMOSTAT

CONTROLLER

HUMIDISTAT

SA

8"Ø

FLEX DUCT

MANUAL VOLUME DAMPER

2'x2' SUPPLY DIFFUSER

2'x2' RETURN GRILLE

ROOF ABOVE

SUPPLY DUCT UP TO FLOOR ABOVE/THRU

ROOF ABOVE

RETURN DUCT UP TO FLOOR ABOVE/THRU

45 DEGREE ENTRY

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW CONSTRUCTION

REGISTER/GRILLE: DEVICE TYPE/AIRFLOW/OPENING SIZE

DIFFUSER: DEVICE TYPE/AIRFLOW/NECK SIZE

SUPPLY DUCT

COLLAR

CEILING

SEALER

DRAW BAND WITH SILICONE OPPOSED BLADE DAMPER

CEILING DIFFUSER

HAND DAMPER

FLEX DUCT MAX. 6' - 0"

NECK SIZE

FLEX DUCT SIZE SHALL MATCH

MECHANICAL GENERAL NOTES: MECHANICAL LEGEND MECHANICAL DEMOLITION NOTES:

PROJECT DESIGN CONDITIONS

AIR DEVICE SCHEDULE

(SIDE OF DUCT CONNECTION)

TYPICAL DIFFUSER CONNECTION

NOT TO SCALE

M001 mfd-1701252-m001

2023-09-14T12:51:37-0500

DOUGLAS E WEAVER

2022-07-28T10:00:18-0500

RONALD M HUBRICH

DEMO AND NEW CONSTRUCTION

MECHANICAL PARTIAL GROUND FLOOR PLAN -

AK

UR

MFD-1701252-M002

LOCATION OF THE RELOCATED THERMOSTAT. 10.

RELOACTE EXISITNG THERMOSTAT. 9.

TIE IN 8"X6" DUCT FROM THE MAIN. 8.

TIE IN 8" DUCT FROM THE MAIN.7.

SUPPLY DUCT.

DEMOLISH EXISTING SUPPLY DUCT FROM UNIT#2. DEMOLISH DAMPER D-2 AND ASSOCIATED WIRING. CAP THE 6.

EMOLISH ABANDONED HUMIDISTAT. 5.

DEMOLISH OVERTEMP CONTROL PANEL SERVING DAMPER D2. 4.

THE DISPERSION TUBE LOCATED INSIDE THE SUPPLY DUCT AND SEAL THE OPENINGS AS REQUIRED.

DEMOILISH EXISTING HUMIDIFIER AND ASSOCIATED PIPING SERVING UNIT #1'S 20"x20" SUPPLY MAIN. DEMOLISH 3.

DISCONNECT AND DEMOLISH EXISTING RETURN GRILLE. 2.

DEMOLISH EXISTING SUPPLY DIFFUSER AND THE FLEX DUCT. SEAL THE OPENING IN THE MAIN DUCT. 1.

EXISTING TO BE REMOVED

DEMO TO THIS POINT

NEW CONSTRUCTION

CONNECT TO EXISTING

:4 lo tt e

WD WD

UNIT #1

UNIT #1

(TYP.)

6" x 6"

8"

S-1

R-1

ETR

X

20" X 20"

12" X 12" (ETR)

20" X 20"

6" x 6"

24" X 14" (ETR)

12" X 12" (ETR)

24" X 24"

24" X 24" DN (TYP.2)

OVER TEMP CONTROL PANEL

FLEX DUCT

(ETBR) 10"

DIFFUSER (TYP.)

(ETBR) 10" CLG

DAMPER D-2 NC

MOTORIZED

ROOM

THE EQUIPMENT

FROM UNIT #1 TO

FROM UNIT #2

16" X 14"

D-1B NO (ETR)

MOTORIZED DAMPER

D-1A NC (ETR)

24" X 24" DN (TYP.2)

THE EQUIPMENT

FROM UNIT #1 TO

D-1B NO (ETR)

D-1A NC (ETR)

116115

EQUIPMENT

MAIN ENTRYMAIN ENTRY

113ROOM

HALLWAY

TRACON

AT OFFICE AF UNIT OFFICE AF UNIT OFFICEAT OFFICE

CONFERENCE

WD WD

MECHANICAL PARTIAL GROUND FLOOR PLAN - DEMOLITION

SCALE: 1/4" = 1'-0"M002

MECHANICAL PARTIAL GROUND FLOOR PLAN - NEW WORK

SCALE: 1/4" = 1'-0"M002

SHEET NOTES:

DEMOLITION LEGEND

NEW CONSTRUCTION LEGEND

mfd-1701252-m002

2023-09-14T12:51:52-0500

DOUGLAS E WEAVER

2022-07-28T10:00:27-0500

RONALD M HUBRICH

2'-0"

GROUND FLOOR PLAN AND RCP PLAN

EG

MFD-1701252-A017

-a

-a lo tt e

AT OFFICE AF UNIT OFFICE

MAIN ENTRY

WD

4 4

GROUND FLOOR RCP PLAN

SCALE: 1/4" = 1'-0"A017

2GROUND FLOOR PLAN

SCALE: 1/4" = 1'-0"A017

2 2

WALL

HATCH FOR NEW

RENOVATION NOTES:

ON CONFERENCE TABLE. EXACT LOCATION TO BE COORDINATED WITH RE.

REFER TO E012 FOR POWER, CATV AND ETHERNET OUTLETS TO BE INSTALLED

REPLACE ALL 2' x 2' CEILING PANELS, EXISTING GRID TO REMAIN.

INFORMATION.

REFER TO ELECTRICAL. DRAWING D002 AND E012 FOR ADDITIONAL LIGHTING

EXISTING LIGHTING TO BE UPGRADED TO LED THROUGHOUT.

INSTALL NEW CEILING PANELS THROUGHOUT RENOVATED ROOM.

REPAIR WALLS, CLEAN, SAND, PAINT AND APPLY NEW VINYL BASE.

REPAIR BACK WALL WHERE WATER DISPENSER CONNECTIONS ARE LOCATED.

INSTALL NEW CARPET TILE. REPLACE THRESHOLD WITH NEW ADA APPROVED.

INSTALL NEW STUD DRYWALL, PAINT TO MATCH EXISTING, ADD VINYL BASE.

RCP LEGEND:

DIFUSSERS

AIR INTAKE

LIGHTING FIXTURE

GENERAL NOTES:

NEW FURNITURE TO BE PROVIDED BY FAA. COORDINATE EXACT LOCATIONS WITH RE DURING2.

REFER TO DRAWING G013 , E012, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.

FOR MECHANICAL FIXTURE INFORMATION

REFER TO DRAWINGS M001 AND M002

NOTE:

mfd-1701252-a017

2023-09-14T12:51:14-0500

DOUGLAS E WEAVER

2022-07-28T10:00:05-0500

RONALD M HUBRICH

J

6'-1"

16'-10"

EXISTING GROUND FLOOR PLAN

MFD-1701252-D001

-d

:0 lo tt e

SCALE: 1/4" = 1'-0"D001

WD

TRACON

1 4

6 6

2 6

SCALE: 1/4" = 1'-0"

4' 8'04'

DEMOLITION KEY NOTES:

EXISTING LOCKERS TO BE MOVED.

WATER DISPENSER (WD) AND CONNECTIONS TO REMAIN.

REMOVE EXISTING WALL CUTOFF OPENING TO EQUIPMENT ROOM.

REMOVE CARPET LAYER ON WALLS.

REMOVE EXISTING CEILING PANELS, GRID TO REMAIN.

REMOVE FLOOR CARPET AND VINYL TILES BELOW (IF EXISTING) THROUGHOUT ROOM.

WING WALL / NICHE ON NORTH-EAST CORNER TO REMAIN.

REMOVE WING WALL, MOVE CONTROL PANELS.

AND CEILING. REFER TO DRAWING D002 FOR MORE ELECTRICAL DEMOLITION PLAN INFORMATION.

REMOVE ALL FURNITURE, ELECTRONIC EQUIPMENT, CABINETS AND ACCESSORIES FROM FLOOR, WALL 1 mfd-1701252-d001

2023-09-14T12:50:42-0500

DOUGLAS E WEAVER

2022-07-28T09:59:37-0500

RONALD M HUBRICH

16'-10"

J

ELECTRICAL DEMOLITION PLAN

JR

MFD-1701252-D002

DISPOSE OF EXISTING LIGHT BULBS. REFER TO DRAWING E012 FOR MORE PROPOSED UPDATES 22.

TO THE MAXIMUM EXTENT POSSIBLE. COORDINATE WITH COR.

VERIFY ALL CONDUIT RUNS AND EQUIPMENT BEFORE DEMOLITION REMOVE ALL CONDUIT AND CABLE 21.

DEBRIS, EQUIPMENT, AND ASSOCIATED CONDUIT/CABLE.

SUBCONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND OFF-SITE DISPOSAL OF ALL DEMO 20.

STORE ALL THE TOOLS.

MAINTAIN A CLEAN CONSTRUCTION AREA BY CLEANING DAILY, REMOVE ALL DEBRIS AND PROPERLY 19.

PERIOD OF THE WORK.

DO NOT OBSTRUCT THE MEANS OF EGRESS FOR THE FACILITY AT ANY TIME THROUGHOUT THE 18.

ARCHITECTURAL DRAWINGS.

COORDINATE DEMOLITION SHOWN ON THIS DRAWING WITH DEMOLITION WORK AND NOTES SHOWN ON 17.

SHALL RELOCATE AND REINSTATE TO ORIGINAL WORKING CONDITION.

IF FIRE ALARM DEVICES ARE DISTURBED DURING THE PERFORMANCE OF THE WORK, CONTRACTOR 16.

SCHEDULE WORK TO AVOID DISRUPTIONS TO THE OCCUPANTS AND AIR TRAFFIC OPERATIONS.

THE BUILDING WILL BE OCCUPIED DURING THE PERFORMANCE OF THE WORK COORDINATE AND 15.

REQUIREMENTS.

IN ACCORDANCE WITH THE SCHEDULE DESCRIBED IN "SEQUENCE OF WORK". UNDER GENERAL

ELECTRICAL WORK DESCRIBED IN THESE DOCUMENTS SHALL BE COORDINATED WITH GENERAL WORK 14.

RELOCATE ANY EXISTING EQUIPMENT TO NEW WALL AS INDICATED.13.

EXISTING CONDUITS MAY BE MODIFIED AND REUSED FOR NEW WORK.12.

OF THE EXISTING LIGHTING MAY BE USED AS A TEMPORARY LIGHTING IF IT'S APPROVED BY THE RE.

PROVIDE TEMPORARY LIGHTING AND MAINTAIN BUILDING POWER DURING DEMOLITION. ALL OR PART 11.

REPAIRED TO MATCH EXISTING.

FINISHES AND SURFACES DAMAGED BY THE DEMOLITION OR CONSTRUCTION SHALL BE PATCHED AND 10.

COORDINATE ALL NECESSARY ARRANGEMENT WITH UTILITY, SSC, AIRPORT, AND RESIDENT ENGINEER.9.

MAINTAIN ALL SIGNAL, POWER, LIGHTING AND ALARMS CIRCUITS DURING ALL PHASES OF 8.

ON AND ALL EXISTING OUTLETS FROM THE WALLS BEING REDONE.

REMOVE ALL EXISTING LIGHTS AND THEIR CONTROLS FROM THE TRACON ROOM AREA BEING WORKED 7.

STORE SMOKE DETECTORS TO BE REINSTALLED BELOW NEW CEILING.

WHERE CONDUITS ARE INACCESSIBLE TO REMOVE AND/OR CAN BE REUSED, LEAVE THEM IN PLACE.

AND ASSOCIATED WIRING AND CONDUITS BACK TO THE POWER SOURCE FOR NEAREST OUTLET BOX/JB

DISCONNECT AND REMOVE LIGHTING FIXTURES, EXIT SIGNS, WIRING, WIRING DEVICES, SWITCHES 6.

FROM EACH FIXTURE AND DISPOSE OF BALLAST IN ACCORDANCE WITH FEDERAL AND STATE

FLORESCENT LIGHTS HAVE BALLASTS THAT MAY CONTAIN PCB MATERIAL. REMOVE EACH BALLAST 5.

PERFORMED. CONTRACTOR SHALL NOT OPEN OR CLOSE ANDY CIRCUIT BREAKER AT ANY TIME.

BREAKER OPERATION TO THE FAA IN WRITING AND AT LEAST 30 DAYS IN ADVANCE TO THE WORK BEING

ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMITTAL REQUESTS FOR CIRCUIT 4.

DEMOLITION.

ENSURE EQUIPMENT IS DE-ENERGIZED AND LOCKED-OUT/TAGGED-OUT BEFORE COMMENCING 3.

SYSTEMS. ALL DEMOLITION WORK SHALL BE COORDINATED WITH FAA PERSONNEL IN ADVANCE.

FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO DEMOLITION OF ELECTRICAL 2.

REFER TO DRAWING G002 , E002, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.

lo tt e

EXISTING GROUND ELECTRICAL FLOOR PLAN

SCALE: 1/4" = 1'-0"D002

BASE BLDG

SEE NOTE 22

SEE NOTE 22

mfd-1701252-d002

2023-09-14T12:50:58-0500

DOUGLAS E WEAVER

2022-07-28T09:59:51-0500

RONALD M HUBRICH

AND ABBREVIATIONS

ELECTRICAL NOTES, LEGEND

MFD-1701252-E011

-e

:4 lo tt e

GENERAL ELECTRICAL NOTES

GENERAL GROUNDING NOTES

ELECTRICAL ABBREVIATION

AC HH

AWG

GND

RGS

EES

EMT

FT

J-BOX

MTS

NEC

CCS

RF

PVC

SER

SPD

GEC

SLD

MDP

BFL

E/G

GFCI

GFE

LFM

SCH

TYP

MAIN-GP

COMM

MLO

SUPP-GP

WP

BSC

FRWK

MPGP

LPS

OSHA

NFPA

AIRCRAFT RATED HANDHOLE

MULTI-POINT GROUND PLATE

MAIN GROUND PLATE

EARTH ELECTRODE SYSTEM

GROUND CONDUCTOR

FRAMEWORK

BARE STRANDED COPPER

AMERICAN WIRE GAGE

SUPPLEMENTAL GROUND PLATE

MAIN LUG ONLY

POLYVINYL CHLORIDE CONDUIT

LIQUIDTIGHT FLEXIBLE METAL CONDUIT

COPPER-CLAD STEEL

COMMUNICATION

ENGINE GENERATOR

NATIONAL ELECTRIC CODE (NFPA 70)

NATIONAL FIRE PROTECTION ASSOCIATION

OPERATIONAL SAFETY AND HEALTH ADMINISTRATION

LIGHTNING PROTECTION SYSTEM

SERVICE ENTRANCE RATED

RADIO FREQUENCY

SINGLE LINE DIAGRAM

GROUNDING ELECTRODE CONDUCTOR

MANUAL TRANSFER SWITCH

FEET

ELECTRICAL METALLIC TUBING

JUNCTION BOX

RIGID GALVANIZED STEEL CONDUIT

SCHEDULE

GROUND FAULT CIRCUIT INTERRUPTER

SURGE PROTECTIVE DEVICE

TYPICAL

GOVERNMENT FURNISHED EQUIPMENT

MAIN DISTRIBUTION PANEL

CONDUIT

BELOW FROST LINE

DIA DIAMETER

DESIGN CODES AND CRITERIA

WEATHERPROOF

TBD TO BE DETERMINED

AVG

ELECTRICAL LEGEND

H. TITLE 47 PART 15 FOR CLASS B DEVICES (CFR)

G. TITLE 47 PART 15 FOR CLASS A DEVICES (CFR)

F. NFPA 70E

E. IEEE C2

D. FAA-C-1217

C. FAA-C-1391

B. FAA-STD-019

A. NFPA 70 (NEC)

STANDARDS:

DRAWINGS WERE COMPLETED IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING CODES AND

APPLICABLE CODES, LOCAL AUTHORITIES HAVING JURISDICTION, REGULATIONS, AND STANDARDS. THESE

ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH DIVISION 26 OF THE CONTRACT DOCUMENT/DRAWINGS, ALL 1.

AIR FORCE

AVERAGE

COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

ONLY PERFORM SPLICES AT RECEPTACLES AND JUNCTION BOXES. 20.

OCCUPANTS DURING THE PERFORMANCE OF THE WORK AS THE FACILITY WILL BE OCCUPIED AND IN OPERATION.

COORDINATE AND SCHEDULE WORK WITH RE AND FACILITY MANAGER TO AVOID DISRUPTIONS TO THE EQUIPMENT AND 19.

CONTINUITY. PROVIDE ALL NECESSARY CORRECTIONS TO MAKE THE SYSTEM READY FOR OPERATION AGAIN.

TEST ALL NEW, RELOCATED, AND EXISTING CIRCUITS/DEVICES AFFECTED BY NEW WORK FOR GROUNDING AND POWER 18.

NEW OR AFFECTED PANELBOARDS.

IDENTIFY AND MARK UP ANY CHANGES TO THE PANEL DIRECTORIES AFFECTED BY NEW WORK. PROVIDE NEW DIRECTORIES FOR

FIELD VERIFY THE ACCURACY OF THE EXISTING BRANCH CIRCUITS AND MARK UP THE DRAWINGS WITH ANY DIFFERENCES. RE-17.

EQUIPMENT NOT INTENDED TO BE REMOVED.

EXERCISE DUE CARE IN THE REMOVAL OF ELECTRICAL DEVICES AND EQUIPMENT NOT TO INTERRUPT POWER TO ANY OTHER 16.

TIME.

IN WRITING 30 DAYS IN ADVANCE OF THE WORK BEING PERFORMED. DO NOT OPEN OR CLOSE ANY CIRCUIT BREAKER AT ANY

ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMIT ALL REQUESTS FOR CIRCUIT BREAKER OPERATION TO THE FAA 15.

BEFORE ORDER NEW MATERIALS.

VERIFY LOCATION OF EXISTING CABLE TRAYS, WIREWAYS, PANELBOARDS, AND DEVICE/MATERIALS TO BE UPGRADED/MODIFIED

VISIT THE JOB SITE TO BECOME COMPLETELY FAMILIAR WITH THE EXISTING CONDITIONS PRIOR TO BEGINING WORK. FIELD 14.

LISTED OR ACCEPTED BY A GENERALLY INDUSTRIAL STANDARD ORGANIZATION.

LABEL ALL COMPONENTS AND MATERIALS FOR THEIR SPECIFIC APPLICATION. ENSURE ALL COMPONENTS ARE UL 13.

ALL ELECTRICAL EQUIPMENT MUST BE MARKED WITH THE APPROPRIATE SAFETY AND WARNING LABELS.12.

DRAWINGS.

SHALL BE SIZED, AT MINIMUM, 14 AWG UNLESS OTHERWISE REQUIRED BY MANUFACTURER OR NOTED ON THE

FOR GENERAL USE, SHALL BE SOLID. CONDUCTORS 10 AWG AND LARGER MAY BE STRANDED. CONTROL WIRE

MINIMUM BRANCH CIRCUIT CONDUCTOR SIZE SHALL BE 12 AWG. CONDUCTORS SIZED 12 AWG AND SMALLER, 11.

MINIMUM OF 72 HOURS ADVANCE NOTICE.

PROCEDURES PRIOR TO EACH ELECTRICAL OUTAGE. COORDINATE ANY POTENTIAL OUTAGES WITH FAA WITH A REVIEW THESE

STRICTLY ENFORCE LOCKOUT/TAGOUT (LOTO) PROCEDURES PER NFPA 70E, LATEST EDITION THROUGHOUT THIS PROJECT. 10.

USE A MINIMUM 3/4" CONDUIT FOR POWER DISTRIBUTION INTERIOR WIRING, UNLESS OTHERWISE NOTED.9.

NOT ALLOWED.

PROVIDE EACH CIRCUIT WITH AN INDIVIDUAL NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE 8.

INSTALLATION AND UPON INSTALLATION COMPLETION.

TEST CABLES IN ACCORDANCE WITH SPECIFICATION 26 08 00.13 TESTING AND INSPECTING ELECTRICAL EQUIPMENT PRIOR TO 7.

WIRING HAS BEEN INSTALLED.

TERMINATE EACH RGS CONDUIT WITH THREADED SEALING HUB. SEAL BOTH ENDS OF ALL CONDUITS WITH DUCT SEAL AFTER 6.

DRAWINGS.

INCLUDE ANY ADDITIONAL APPURTENANCE NECESSARY FOR PROPER FUNCTION OF THE SYSTEM EVEN NOT SHOWN ON THE 5.

APPLY ANTI-SEIZE COMPOUND TO ALL THREADS ON BOLTS, AND SCREWS.4.

INSTRUCTIONS, NEC, NEMA, AND FAA STANDARDS AND ORDERS.

EACH PIECE OF EQUIPMENT INSTALLED UNDER THE CONTRACT. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER

PROVIDE ALL REQUIRED CONDUITS, CABLES, JUNCTION BOXES, FITTINGS, SUPPORTS, ETC TO COMPLETE BRANCH CIRCUITS FOR 3.

SPACE ACCORDING TO THE NEC CODE AND OSHA.

AVOID SPACE CONFLICT. INSTALLATION OF THE EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF THE WORKING

ALL EQUIPMENT DIMENSIONS SHOWN ARE NOMINAL. FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH EQUIPMENT TO 2.

BE THREADED TYPE ONLY. EMT ONLY FOR INDOOR WIRING. EMT FITTINGS SHALL BE COMPRESSION TYPE ONLY.

OUTDOOR INSTALLATION. PVC COATED RGS ONLY FOR UNDERGROUND INSTALLATION. RGS CONDUIT FITTINGS SHALL

PERMITTED FOR GROUND CONDUCTORS OR BURIED RACEWAYS UNLESS INDICATED OTHERWISE. RGS CONDUIT ONLY FOR

PERMITTED RACEWAY TYPES ARE EMT, RGS, PVC-COATED RGS, AND PVC SCHEDULE 80. PVC RACEWAY SHALL ONLY BE 1.

APPROPRIATE COATING TO PREVENT CORROSION AFTER INSTALLATION.

REMOVE PAINT FROM THE AREA WHERE GROUND LUGS ARE TO BE INSTALLED. SEAL THE AREA WITH PAINT OR THE3.

PROVIDE SUPPLY SIDE GROUND BONDING JUMPER SIZED PER THE LATEST EDITION OF THE NEC.2.

ACCORDANCE WITH FAA-STD-019 (LATEST EDITION).

GROUND METAL PARTS, CONDUITS, EQUIPMENT, INTERFACE BOXES, AND JUNCTION BOXES IN 1.

DP-1

EX

SPD

X/Y/Z = POLE SIZE

= FRAME SIZE

= FUSE SIZE

EXIT SIGN WITH EMERGENCY LIGHT

SURGE PROTECTIVE DEVICE

FUSED AT [Y]A

FUSIBLE DISCONNECT [X]A/[Z]

DUPLEX RECEPTACLE

RECESSED/FLUSH MOUNTED

QUAD RECEPTACLE

SURFACE MOUNTED

CONDUIT, FLEXIBLE

CONDUIT, CAPPED

CONDUIT STUB UP

CONDUIT STUB DOWN

SOLID WHETHER CONCEALED OR EXPOSED

HOME RUN TO PANEL DP BREAKER, SHOWN

SAME AS BRANCH CIRCUIT - BUT CONCEALED

ABOVE GROUND EXOTHERMIC WELD

EES (BURIED) GROUND CONDUCTOR

UNDERGROUND POWER CONDUIT

DOWN CONDUCTOR

UG

WITH MOUNTED UTILITY METER

UTILITY COMPANY TRANSFORMER

WITH (2)-12 AWG CONDUCTOR(S) PLUS (1)-12 AWG GROUND

BRANCH CIRCUIT, SURFACE MOUNTED 3/4" RACEWAY,

WHEN MORE THAN 3 IN 3/4" RACEWAY

CROSS MARKS DENOTE NUMBER OF 12 AWG CONDUCTOR(S)

RECESSED CEILING MOUNTED LED LIGHTING FIXTURE

ABOVE GROUND, CONDUCTOR

SYMBOL DESCRIPTION

OH OVERHEAD CONDUCTORS

DESCRIPTIONSYMBOL

120V, 20A, SPECIFICATION GRADE

THREE POLE SWITCH

AC

AIR CONDITIONER CONTROLS / THERMOSTAT

SINGLE POLE SWITCH

DIMMER SWITCHD

DEMOLITION

SINGLE RECEPTACLE

(GFCI)

DUPLEX RECEPTACLE (GFCI)

ETHERNET PORT BOX

TELEPHONE

DISTRIBUTION PANELBOARD

SURFACE-MOUNTED ELECTRICAL

DISTRIBUTION PANELBOARD

RECESSED ELECTRICAL

WRAPAROUND LIGHT

CEILING MOUNTED LED LIGHTING FIXTURE

EXISTING STEPLIGHT FIXTURE

EMERGENCY LIGHT (SINGLE)

EMERGENCY LIGHT (DUAL)

DUPLEX RECEPTACLE

SINGLE RECEPTACLE

QUAD RECEPTACLE

PCB POLYCHLORINATED BIPHENYLS

AGL ABOVE GRADE LEVEL

AT AIR TRAFFIC

ATCT AIR TRAFFIC CONTROL TOWER

DIST DISTRIBUTION

ELEV ELEVATOR

PNL PANEL

MAY BE USED ON THIS PROJECT

NOT ALL SYMBOLS AND ABBREVIATIONS

mfd-1701252-e011

2023-09-14T12:52:12-0500

DOUGLAS E WEAVER

2022-07-28T10:00:38-0500

RONALD M HUBRICH

AND LOCAL AREA NETWORK DATA PLAN

PROPOSED GROUND FLOOR POWER, LIGHTING

MFD-1701252-E012

:5 lo tt e

EQUIPMENTHALLWAY

ELEV

ELEV

SERVICE ROOM

LINK

STORAGE

W

UP

STAIR

NEW WALL

DPN-A, #12

DPN-A, #12

#14

DPN-A,

DPN-A, #22

DPN-A, #16

PROPOSED GROUND FLOOR POWER, LIGHTING, AND LOCAL AREA NETWORK DATA PLAN

SCALE: 1/4" = 1'-0"E012

EX

D 9

B A

MOUNTING TO BE DETERMINED IN THE FIELD BY RE.

INSTALL (4) ETHERNET PORT IN EACH SIDE OF THE TABLE AS FAA REQUIREMENTS. EXACT LOCATION AND

PROVIDE CONNECTION BETWEEN CATV OUTLET, TABLE RECEPTACLES, COMMUNICATION CONNECTIONS AND

EXACT LOCATIONS TO BE DETERMINED IN THE FIELD BY RE.

INSTALL A TABLE MOUNTED QUAD RECEPTACLE AND BOX. SUPPLY POWER FROM DPN-A PANEL BREAKER 22.

ON SITE STAFF'S REQUEST.

PROVIDE A CTAV OUTLET AT 72" AFF FOR TV CONNECTIONS AND 1" C FROM JBOX TO 6" ABOVE CEILING. PER

PROVIDE AND INSTALL NEW EMERGENCY LED SIGN.

STAFF'S REQUEST.

INSTALL NEW ETHERNET PORT BOX BY USING NEAREST ETHERNET PORT FOR CONNECTIONS PER ON SITE

EXISTING ELECTRICAL PANEL MDP FOR PANELS DPE-A, DPN-B, DPN-A.

PANEL SCHEDULE INFORMATION.

EXISTING 225A ELECTRICAL DISTRIBUTION PANEL DPE-A. REFER TO DRAWING E004 FOR MORE EXISTING

SCHEDULE INFORMATION.

EXISTING ELECTRICAL DISTRIBUTION PANEL DPN-B. REFER TO DRAWING E003 FOR MORE EXISTING PANEL

SCHEDULE INFORMATION.

EXISTING ELECTRICAL DISTRIBUTION PANEL DPN-A. REFER TO DRAWING E003 FOR MORE EXISTING PANEL

AND E020 FOR MORE POWER WIRING AND LED INFORMATION.

PROVIDE AND INSTALL, NEW LED LIGHT BULB IN THE EXISTING LIGHT FIXTURE. REFER TO DRAWING E013

PROVIDE AND INSTALL NEW DUPLEX RECEPTACLE. REFER TO DRAWING E013 FOR MORE POWER WIRING

FOR MORE POWER WIRING AND LED INFORMATION.

PROVIDE AND INSTALL NEW LED WRAPAROUND LIGHTING FIXTURES. REFER TO DRAWING E013 AND E020

KEYED NOTES:

LEGEND:

-NEW

-EXISTING

PANELBOARD DPN-A.

ROUTE WRAPAROUND LIGHTING 12 AWG CONDUCTOR(S) TO EXISTING ELECTRICAL DISTRIBUTION 3.

FAA-C-1217.

ENSURE ALL INTERIOR POWER DISTRIBUTION WIRING ARE IN ACCORDANCE WITH THE LATEST EDITION OF 2.

REFER TO DRAWING G013, E011, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.

mfd-1701252-e012

2023-09-14T12:52:32-0500

DOUGLAS E WEAVER

2022-07-28T10:00:49-0500

RONALD M HUBRICH

MFD FACILITY PANEL SCHEDULES

MFD-1701252-E013

lo tt e

AMP

SPACE

HVAC #1 TRACON ROOM

LPE-A RADAR PANEL

BUS RATING

MAIN

CKT.

NO.

*ACTUAL CIRCUIT BREAKER INFORMATION MAY BE DIFFERENT THAN SHOWN.

225 AMPS

225A CIRCUIT BREAKER

BUS CONN.

BREAKER

POLE

EXISTING ELECTRICAL PANELBOARD DPN-A

E013

EXISTING ELECTRICAL PANELBOARD MDP

EXISTING ELECTRICAL PANELBOARD DPN-B

EXISTING PANEL SCHEDULE*

PANEL

SERVICE VOLTAGE

PHASE

DESCRIPTION

EXIT LIGHTS

EMERGENCY & NIGHT LIGHTS

TRACON WALL LIGHTS

GATE CONTROL

DPE-A

120/208 VOLTS

MOUNTING

MIN. AIC

MFD TRACON

SURFACE

10 KA

DAMPER MOTORS

1 20

1 30

1 40

1 100

FED FROM MDP PANEL

PARKING LOT LIGHTS

SPARE

LPE-D TELCO PANEL

HVAC #2 EQUIPMENT ROOM

LPE-C TRACON PANEL

LPE-E CAB PANEL

LPE-B COMMUNICATIONS PANEL

RTU RECEPTACLE

HVAC #3 HUMIDIFIER

DPN-B

POLE AMP

HVAC #2 HUMIDIFIER

100 AMPS

100A CIRCUIT BREAKER

SECURITY LIGHTS

1 35

1 70

LIGHT STATION CONTROL PANEL

HVAC #1 HUMIDIFIER & HVAC #3 OFFICES

HVAC

SPACE 31 32 SPACE

SPACE 33 34 SPACE

SPACE 35 36 SPACE

SPACE 37 38 SPACE

SPACE 39 40 SPACE

SPACE 41 42 SPACE

SMOKE HOUSE LIGHT & HEATER

SPARE 151

60 3

PANEL "B"

MDP

400 AMPS

300A CIRCUIT BREAKER

FED FROM

GRID POWER

SPARE 31 32

33 34

35 36

37 38

39 40

41 42

HEATER #3

PANEL "A"

ELEVATOR

A/C UNIT

20 1

100 3

100 3

LEGEND:

-CIRCUIT

NEW BRANCH

-NEW

-EXISTING

DUPLEX RECEPTACLE SPARE **

NEW FUTURE WALL

15 1

WRAPAROUND LIGHTING SPARE**

NEW CONFERENCE ROOM LED

RESTROOM EXHAUST FAN

SSCC ROOM

DUPLEX / EQUIPMENT ROOM /

T.O. UNIT ROOM

DUPLEX TRACON /EQUIPMEN -

LIGHTED STATUS BOARD

DUPLEX TRACON /

LINK HEATER

SECRETARY - A.T. TRAINING

2ND ENTRY LIGHTS -

LIGHTS RESTROOM

OFFICE

LIGHTS TRACON / T.O. UNIT

DIMMERS - EQUIPMENT ROOM EAST

DPN-A

DIMMERS - EQUIPMENT ROOM CENTER

DIMMERS - EQUIPMENT ROOM WEST

A.T. CHIEF OFFICE RECEPTACLE

SECRETARY RECEPTACLE

100 AMPS

100A CIRCUIT BREAKER

LIGHTS - PARKING LOT

LIGHTS - OUTSIDE & PHOTO CELL

CONFERENCE ROOM

DUPLEX A.T. OFFICE /

31 32

DUPLEX SECRETARY / A.T. CHIEF 33 34

35 36

T.O. UNIT ROOM

DUPLEX / EQUIPMENT -

DUPLEX - SSCC / AT CHIEF 37 38 ENTRANCE HEATER

MICROWAVE TO

DUPLEX - SERVICE ROOM -

39 40

DUPLEX ON ROOF/GFCI 41 42 LINK HEATER

SPARE 1

A. T. OFFICE RECEPTACLE

MICROWAVE RECEPTACLE

REFRIGERATOR RECEPTACLE

LIGHTS ENTRANCE

HOT WATER HEATER

LIGHTS - A.T. OFFICE/CONFERENCE ROOM

HALL LIGHTS - A.T. OFFICE/CONFERENCE

A.T. OFFICE / RESTROOMS

DUPLEX SECRETARY /

HEATER #3

HEATER #5

** SEE NOTE 3 AND 4.

SCHEDULE CLOUDED REGIONS ON THIS DRAWING FOR NEW BRANCH CIRCUIT LOCATIONS.

REPLACE EXISTING SPARE BREAKERS WITH NEW, 20A, CIRCUIT BREAKER. REFER TO THE PANEL 4.

AND FLUSH-MOUNTED DUPLEX RECEPTACLES VIA SPARE CKT #12, 14, 16, AND 22 AS NECESSARY.

PROVIDE NEW 12 AWG POWER WIRING TO THE NEW CEILING-MOUNTED LED WRAPAROUND LIGHTING 3.

PERFORM NEW WORK SHOWN IN CLOUDED REGION OF PANEL SCHEDULE.2.

DPN-A.

FIELD VERIFY IF EXISTING ELECTRICAL PANEL MDP SERVES POWER FOR SUB-PANELS DPE-A, DPN-B, AND 1.

EXISTING ELECTRICAL PANELBOARD DPE-A

PANEL "C"

mfd-1701252-e013

2023-09-14T12:52:51-0500

DOUGLAS E WEAVER

2022-07-28T10:00:59-0500

RONALD M HUBRICH

SCHEDULE & LIGHTING FIXTURE DETAIL

CONFERENCE ROOM LUMINARIE

MFD-1701252-E014

lo tt e

CLS-SE3

SINGLE FACE, NO ARROWS

RED LETTERS, BATTERY RUN TIME 90 MINUTES,

CAD BATTERY,

CEILING MOUNTED, LED EXIT LIGHTING UNIT, NI-

SUSPENDED

(TYPICAL)

JUNCTION BOX

NEW OR EXISTING

FEET (TYPICAL)

FIXTURE WHIP MAXIMUM LENGTH 6

NEW FLEXIBLE METAL CONDUIT

STRUCTURE

SUPPORT SYSTEM OR BUILDING

EXISTING UNISTRUT-TYPE

NEW RECESSED FIXTURE

EACH END

CORNERS OF FIXTURE WITH 5 TWISTS AT

GALV 12 GA SUSPENSION WIRE AT 2

CONDUIT EMT

NEW OR EXISTING

LBL4 LP840 RFD230716

(TO BE FCC PART 15 CLASS B COMPLIANT)

4'-0" LED WRAPAROUND WITH CLASS B DRIVER

ND-EML

WA-SW-SC-UNV-X1-

P8622-LED4-MO-

NON DIMMING

DIM TO DARK

@ H = 8'-0"

RECESSED

1204000K LEDs DIM TO DARK

EMERGENCY LIGHT

2' X 2' RECESSED TROFFER W/BATTERY PACK

LUMINAIRE SCHEDULE

LABEL QTY. CATALOG NUMBER DESCRIPTION LAMP

MANUFACTURER VOLTS MOUNTING

RECESSED

LITHONIA 120

DRIVER

4000K LEDs 120

RECESSED FIXTURE MOUNTING DETAIL

E014

LITHONIA LBL4 LP840 RFD230716

(TO BE FCC PART 15 CLASS B COMPLIANT)

4'-0" LED WRAPAROUND WITH CLASS B DRIVER

LIGHTING

HUBBELL

DUAL/LITE

4000K LEDs PROVIDE LUTRON 1% DIMMING DRIVER OPTION.

---LED LAMPS

LIGHTING

PRUDENTIAL

RECESSED0

LIGHT FIXTURES.

COMPLETE REQUIREMENTS OF CFR TITLE 47 PART 15 FOR CLASS A AND/OR CLASS B DEVICES FOR LED 5.

INSTALLATION OF LIGHTING FIXTURES AND SUPPORTS TO MEET PROJECT SPECIFICATIONS AND SEISMIC 4.

LAYOUT AND KEEP FLEXIBLE CONDUIT RUNS TO A MAXIMUM OF 6 FEET.

PROVIDE NEW CONDUIT AND WIRING FROM EXISTING JUNCTION BOXES TO SUPPORT NEW LIGHTING 3.

COMPLETE ASSEMBLY.

COMPATIBILITY AND COMPLIANCE WITH LIGHTING CONTROL SYSTEM, PROPER FIT, AND A SECURE AND

SHALL BE VERIFIED (CONSULT WITH LIGHTING MANUFACTURER) PRIOR TO INSTALLATION TO ENSURE

MOUNTING BRACKETS AND ACCESSORIES ALL LUMINAIRE BALLASTS, DRIVERS, ROW LENGTH OPTIONS, 2.

COR AND WILL BE REVIEWED BY THE ENGINEER OF RECORD FOR COMPLIANCE AND APPROVAL.

EXCEED. SUBSTITUTIONS FOR THE SPECIFIED FIXTURES SHALL BE SUBMITTED IN ADVANCE TO THE FAA

OF QUALITY, APPEARANCE, AND PERFORMANCE THAT ANY SUBSTITUTED FIXTURES MUST MATCH OR

ON THIS DRAWINGS ESTABLISH A LEVEL THE FIXTURES SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE 1.

mfd-1701252-e014

2023-09-14T12:53:13-0500

DOUGLAS E WEAVER

2022-07-28T10:01:07-0500

RONALD M HUBRICH

AND INDEX OF DRAWINGS

COVER SHEET, VICINITY MAP,

RDS

MFD-1701252-G012

lo tt e

MANSFIELD, OHIO

MANSFIELD LAHM MUNICIPAL AIRPORT (MFD)

AIR TRAFFIC CONTROL TOWER (ATCT)

VICINITY MAP

TRANSPO

OF

ST

TES

EN

OF

IC

AVIA

TRAT

SI

NI

INDEX OF DRAWINGS

DRAWING NO. DESCRIPTION

MFD-1701252-E014

MFD-1701252-E013

MFD-1701252-E012

MFD-1701252-E011

MFD-1701252-M002

MFD-1701252-M001

MFD-1701252-A017

MFD-1701252-D002

MFD-1701252-D001

MFD-1701252-G014

MFD-1701252-G013

MFD-1701252-G012

CONFERENCE ROOM LUMINARIE SCHEDULE & LIGHTING FIXTURE DETAIL

PANEL SCHEDULES

PROPOSED GROUND FLOOR POWER, LIGHTNING, AND LOCAL AREA NETWORK DATA PLAN

ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS

MECHANICAL PARTIAL GROUND FLOOR PLAN - DEMO AND NEW CONSTRUCTION

MECHANICAL COVERSHEET

GROUND FLOOR PLAN AND RCP PLAN

ELECTRICAL DEMOLITION PLAN

GENERAL NOTES

LEGEND AND ABBREVIATIONS

COVER SHEET, VICINITY MAP, AND INDEX OF DRAWINGS

mfd-1701252-g012

2023-09-14T12:50:01-0500

DOUGLAS E WEAVER

2022-07-28T09:58:56-0500

RONALD M HUBRICH

LEGEND AND ABBREVIATIONS

MFD-1701252-G013

:3 lo tt e

ABBREVIATIONS

WITH SEQUENCED FLASHERS

- AMPERESAMP

- ABOVE GROUND/GRADE LEVELAGL

- AMBIENT LIGHT SENSORALS

ALSF - HIGH INTENSITY APPROACH LIGHTING SYSTEM

AOA - AIR OPERATIONS AREA

- APPROXIMATELYAPPROX

ARP - AIRPORT REFERENCE POINT

- AIRPORT SURFACE DETECTION EQUIPMENTASDE

ASOS - AUTOMATED SURFACE OBSERVATION

SYSTEM (NWS)

ASR - AIRPORT SURVEILLANCE RADAR

ATCT - AIRPORT TRAFFIC CONTROL TOWER

AWG - AMERICAN WIRE GAUGE

BGL - BELOW GROUND/GRADE LEVEL

BLDG - BUILDING

BOT - BOTTOM

BSC - BARE STRANDED COPPER

BSCU - BARE SOLID COPPER

CCM - CONCRETE CABLE MARKER

CJ - CONTROL JOINT

COMM - COMMUNICATIONS

CONC - CONCRETE

CONT - CONTINUE, CONTINUATION, CONTINUOUS

COR - CONTRACTING OFFICER'S REPRESENTATIVE

DEB - DIRECT EARTH BURIAL

DIM - DIMENSION

DISC - DISCONNECT

DME - DISTANCE MEASURING EQUIPMENT

DU - DISTRIBUTION UNIT

E/G - ENGINE-GENERATOR

EES - EARTH ELECTRODE SYSTEM (COUNTERPOISE)

EFGS - END-FIRE GLIDE SLOPE

EJ - EXPANSION JOINT

EL - ELEVATION (HEIGHT)

ELD - ELECTRICAL LINE DISTRIBUTION

ELEC - ELECTRIC

EMERG - EMERGENCY

EMT - ELECTRIC METALLIC TUBING

EQUIP - EQUIPMENT

EXIST - EXISTING

EX/EXT - EXTERIOR, EXTERNAL

F/O - FIBER OPTIC

FDN - FOUNDATION

FDP - FIBER DISTRIBUTION PANEL

FF - FINISH FLOOR

FFM - FAR FIELD MONITOR

FOD - FOREIGN OBJECT DEBRIS

FT - FOOT/FEET

GALV - GALVANIZED

GEC - GROUNDING ELECTRODE CONDUCTOR

GFCI - GROUND FAULT CIRCUIT INTERRUPTER

GFM - GOVERNMENT FURNISHED MATERIAL

GND - GROUND

GRP - GEOGRAPHICAL REFERENCE POINT

GRSC - GALVANIZED RIGID STEEL CONDUIT

GS - GLIDE SLOPE

HDPE - HIGH DENSITY POLYETHYLENE

HT - HEIGHT

HH - HANDHOLE

HV - HIGH VOLTAGE

HZ - HERTZ

ICC - INDIVIDUAL CONTROL CABINET

ILS - INSTRUMENT LANDING SYSTEM

IM - INNER MARKER

KHZ - KILO-HERTZ

KV - KILO-VOLT

KVA - KILO-VOLT AMPERE

KW - KILO-WATT

LHA - LAMP HOUSING ASSEMBLY

LIR - LOW IMPACT RESISTANT

LOC - LOCALIZER

LOM - LOCATOR - OUTER MARKER

- HEATING, VENTILATING AND AIR CONDITIONINGHVAC

NORTH ARROW

A010

DETAIL MARKER

A012

EXTENDED SECTION CUT

SECTION CUT

ELEVATION SYMBOL

LEGEND

C001

MAY BE USED ON THIS PROJECT

NOT ALL SYMBOLS AND ABBREVIATIONS

LC

REVISED AREA

ENCOMPASS

CLOUD TO

B120ROOM/AREA NUMBER

DEMOLITION

REVISION

REVISION DESIGNATION

NUMBER, POUNDS

CENTERLINE

FEET OR MINUTES

INCHES OR SECONDS

DEGREE

AT

NEW WORK

EXISTING WORK

EXISTING WORK TO BE REMOVED

PL

GLIDE SLOPE CRITICAL AREA

RUNWAY SAFETY AREA

RUNWAY OBJECT FREE AREA

FENCE

PROPERTY LINE

SITE ACCESS ROUTE

STAGING AREA

UNDERGROUND POWER CONDUIT UG

- MEAN SEA LEVELMSL

- MULTI-POINT (GROUND)MP

- MINIMUMMIN

- MEGAHERTZMHZ

- MANHOLEMH

- MAXIMUMMAX

WITH RUNWAY ALIGNMENT INDICATOR LIGHTS (RAIL)

- MEDIUM INTENSITY APPROACH LIGHTING SYSTEM (MALS)MALSR

WITH SEQUENCED FLASHERS

- MEDIUM INTENSITY APPROACH LIGHTING SYSTEMMALSF

- RUNWAY END IDENTIFIER LIGHTSREIL

- REFERENCEREF

- RESIDENT ENGINEER (FAA/TSSC)RE

- RECEIVERRCVR

- REINFORCED CONCRETE PIPERCP

- RUNWAY ALIGNMENT INDICATOR LIGHTSRAIL

- RUNWAYR/W

- POLYVINYL CHLORIDE CONDUITPVC

- POUNDS PER SQUARE INCHPSI

- POUNDS PER SQUARE FOOTPSF

- PAIRPR

- POWER POLE/UTILITY POLEPP

- POINT OF STARTPOS

- POINT OF BEGINNINGPOB

- POINT OF INTERCEPTPOI

- PANELPNL

- PROPERTY LINE, PLATEPL

- POWER AND CONTROL UNITPCU

- PRECISION APPROACH PATH INDICATOR LIGHTSPAPI

- OUTER MARKEROM

- OBJECT FREE AREAOFA

- OUTSIDE DIAMETER/OVERFLOW DRAINOD

- NATIONAL WEATHER SERVICENWS

- NOTICE TO AIRMENNOTAM

- NATIONAL GEODETIC VERTICAL DATUMNGVD

- NATIONAL ELECTRIC CODENEC

- NON-DIRECTIONAL BEACONNDB

- NORTH AMERICAN VERTICAL DATUMNAVD

- NORTH AMERICAN DATUMNAD

- NOT APPLICABLEN/A

- TRANSMITTERXMTR

- TRANSFORMERXFMR

- WELDED WIRE FABRICWWF

- VISUAL APPROACH SLOPE INDICATORVASI

- UNINTERRUPTIBLE POWER SOURCE/SUPPLYUPS

- TYPICALTYP

- TRANSIENT VOLTAGE SURGE SUPPRESSORTVSS

- TAXIWAY SAFETY AREATSA

- TOP OF STEELTOS

- TAXIWAY OBJECT FREE AREATOFA

- TOP OF CONCRETETOC

- TELEPHONE COMPANYTELCO

- TAXIWAYT/W

- TO BE DETERMINEDTBD

- STATIONSTA

- SYSTEM SUPPORT CENTER (FAA)SSC

WITH RUNWAY ALIGNMENT INDICATOR LIGHTS

SSALR - SIMPLIFIED SHORT APPROACH LIGHTING SYSTEM

- SYSTEM MANAGEMENT OFFICE (FAA)SMO

- SURGE ARRESTORSA

- RUNWAY VISUAL RANGE RVR

- REMOTE TRANSMITTER/RECEIVERRTR

- RIGID STEEL CONDUIT/RIGID GALVANIZED STEELRSC/RGS

- RUNWAY SAFETY AREARSA

- REMOTE RADIO CONTROL SYSTEMRRCS

- RUNWAY PROTECTION ZONERPZ

- RIGHT-OF-WAYROW

- RUNWAY OBJECT FREE AREAROFA

- RADIO FREQUENCYRF

- REVISIONREV

- RUNWAY EDGE LIGHTSREL

mfd-1701252-g013

2023-09-14T12:50:15-0500

DOUGLAS E WEAVER

2022-07-28T09:59:13-0500

RONALD M HUBRICH