15 CAK-1701251 Drawings IFB.pdf
PDF 10 MB Posted
- Solicitation number
- 697DCK-24-R-00488
About this file
This document appears to be a set of drawings for the Invitation for Bid (IFB) associated with the federal contract opportunity for the "Refurbishment of TRACON Facilities at Canton, OH and Mansfield, OH".
The key details of the federal contract opportunity are:
The Federal Aviation Administration (FAA) has a requirement for the refurbishment of TRACON facilities in Canton, OH and Mansfield, OH. The estimated construction magnitude is between $250,000 - $1,000,000. A one-time site visit will be offered, with details provided prior to the visit. Requests for Information must be submitted in writing by 8/20/24 and responses will be provided via amendment. Proposals are due by the date and through the submission requirements outlined in the "Solicitation - 697DCK-24-R-00488" attachment. This is an unrestricted competition open to all offerors qualified under NAICS code 236220.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
10'
M
IN
ENGINEERING SERVICES
TERMINAL
ATCT
NEW CONSTRUCTION AND RCP PLAN
VACATED TRACON AREA CONVERSION
OHAKRON-CANTON REGIONAL AIRPORTAKRON
AF
EG
JB
PROJECT ENGINEER MGR: ENGINEERING
09/15/2022 1701251
CAK-1701251-A010
c a k -1
-a
.d g n
THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U
IO
/1
/2
:4
:2
A
P lo tt e d b y
V
-C
E
G -E
D
B
F
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
6TH FLOOR PLAN
SCALE: 1/4" = 1'-0"A010
CHUTE
ELEV
ROOM
READY/BREAK
TOILET
HALL
KITCHEN
RCP - 6TH FLOOR PLAN
SCALE: 1/4" = 1'-0"A010
A011
STAIR
QUIET
BREAK ROOM
LOCKER/
EQUIPMENT
DIMENSION TO NEW WALL
VMVM
EQUIPMENT
D604
ADA
30"X48"
CLEAR
SPACELOCKER
RELEASED FOR:
847.294.8183
Des Plaines, IL 60018
2300 E. Devon, Suite 344
T4 Great Lakes Region
PTSI Managed Services Inc.
CONSTRUCTION - 09/15/2022
Y
Q
L
IT
INTEGRITY
I
PORT SERVIC
IS
FOR OFFICIAL USE ONLY
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
SCALE: 1/4" = 1'-0"
4' 8'04'
REFER TO DRAWING M002 AND M003 FOR MECHANICAL FIXTURES INFORMATION.NOTE:
LEGEND:
LIGHTING FIXTURE
AIR INTAKE
DIFFUSER
EXISTING SPRINKLER HEAD
6TH FLOOR KEY PLAN
NOT TO SCALE
EDGES WITH SOUND ATTENUATING SEALANT.
47 AND LAYED ACROSS THE ENTIRETY OF THE QUIET ROOM ABOVE THE ACOUSTICAL CEILING TILES. SEAL ALL
GREATER TO PROVIDE AN STC RATING OF NOT LESS THAN 1/2" THICK OR EQUAL. PROVIDE BATT INSULATION 3
INSTALL OWENS CORNING FLEXIBLE FIBERGLASS SOUND ATTENUATION BATT INSULATION OR APPROVED
EXISTING RELOCATED VENDING MACHINES.
WALL MOUNTED CABINETS.
BASE BOARD HEATERS. NO WORK IS REQUIRED.
AND CONTRACTOR INSTALLED.
THE BASIS OF DESIGN: DENLAR 01030-F-IF-NFPA OR APPROVED EQUAL.RANGE AND HOOD PROVIDED BY FAA
INSTALL RESIDENTIAL TYPE RANGE WITH RE-CIRCULATING HOOD AND INTEGRAL FIRE SUPPRESSION SYSTEM.
OUTLETS TO BE USED FOR CONFERENCE TABLE USE, REFER TO ELECTRICAL DRAWINGS E007 AND E008.
INFORMATION.
NEW DIMMER SWITCH CONTROL. REFER TO DRAWING D002, E002, AND E020 FOR MORE LIGHTING
NEW LED FIXTURES, REFER TO DRAWING D002, E002, AND E020 FOR MORE LIGHTING INFORMATION.
REPLACE CEILING PANELS THROUGHOUT, EXISTING GRID TO REMAIN.
FLOOR. REFER TO SCHEDULE ON SHEET A011.
INSTALL NEW 3'-0" x 7'-0" 20 MINUTE RATED DOOR WITH LABELED H.M. FRAME AND TRANSITION STRIP AT
COVER EXISTING WALL OPENING, PAINT AND PROVIDE VINYL BASE TO MATCH EXISTING.
INSTALL NEW CARPET TILE FOR NEW QUIET ROOM.
INSTALL NEW VINYL FLOOR.
REPLACE EXISTING CABINETS, SINK, COUNTER-TOP WITH NEW.
PROVIDE FOR NEW KITCHEN PLUMBING WALL.
MATCH EXISTING.
INSTALL NEW SINGLE BOWL DROP-IN ADA SINK BY ELKAY. REFER TO SHEET DOO3, FIXTURE P1. SIZE TO
AND ENCLOSURE PANELS FOR NEW BREAK ROOM.
PROVIDE NEW METAL LOCKERS (20 COUNT) 15”W x 18”D x 72”H WITH SLOPED TOP, 4" X 4"H RECESSED BASE
FLOOR CARPET TILES TO REMAIN, PATCH AND CLEAN AS NECESSARY.
PAINT, AND PROVIDE VINYL BASE OVER ENTIRE WALL SURFACE.
FILL EXISTING NICHE WITH 3 5/8" METAL STUDS AND 5/8" GYPSUM BOARD, ALIGN WITH ADJACENT SURFACES, REPAIR, PAINT, AND PROVIDE VINYL BASE WHERE RADIATOR SYSTEM HAS BEEN REMOVED.
RECEPTACLE INFORMATION.
PROVIDE POWER OUTLET FOR RELOCATED VENDING MACHINES (VM), REFER TO DRAWING E002 FOR MORE
PROVIDE POWER AND TV OUTLET, REFER TO DRAWING E002 FOR MORE RECEPTACLE INFORMATION.
WITH ADJACENT SURFACES, PAINT AND PROVIDE NEW VINYL BASE.
FILL EXISTING OPENING WITH 3 5/8" METAL STUDS @ 16" O.C. AND 5/8" GYPSUM BOARD BOTH FACES, ALIGN
INSTALL NEW THRESHOLD AT ENTRY.
PRESENT ON AREAS TO BE WORKED.
CONDUCTED. PRECAUTIONARY MEASURES SHOULD BE TAKEN AS ASBESTOS COULD STILL BE
COMMENCING OF WORK. ALTHOUGH ASBESTOS ABATEMENT HAS BEEN PREVIOUSLY
ASBESTOS TESTING AND ABATEMENT MAY BE STILL REQUIRED FOR WORK AREA BEFORE5.
LOCATE POWER AND SIGNAL OUTLETS CLOSEST. TO THE CONFERENCE TABLE USE.4.
REFER TO SHEET A011 FOR FINISH SCHEDULE, DOOR SCHEDULE AND NEW DOOR DETAILS.3.
LOCATION WITH RESIDENT ENGINEER DURING CONSTRUCTION.
NEW FURNITURE AND KITCHEN APPLIANCES TO BE PROVIDED BY FAACOORDINATE EXACT 2.
REFER TO DRAWING G007, E006, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.1.
GENERAL NOTES:
KEYED NOTES:
EQUIPMENTROOM
TRACON
WORK AREA
cak-1701251-a010
2023-09-14T12:54:49-0500
DOUGLAS E WEAVER
2022-09-20T17:05:48-0500
RONALD M HUBRICH
2'-0"
1'-0"
2"
/4
1 15/16" 2 1/4"0" 1 9/16"
KITCHEN ROOM ELEVATIONS AND DETAILS
CAK-1701251-A011
:3 lo tt e
NEW KITCHEN WEST ELEVATION
SCALE: 1/2" = 1'-0"A011
KITCHEN NORTH ELEVATION
KITCHEN SOUTH ELEVATION
B36
SIDE SPLASH
MOLDING
OPEN KNEE
SPACE
SIDE SPLASH
MOLDING
PANEL TO MATCH
CABINET FINISH
B33
RANGE
RE-CIRCULATING HOOD WITH
INTEGRAL FIRE PROTECTON SYSTEM.
FAA PROVIDED AND CONTRACTOR INSTALLED.
BASIS OF DESIGN; DENLAR D1030-F-IF-NFPA
RESIDENTIAL TYPE RANGE.
OR APPROVED EQUAL.
FAA PROVIDED AND CONTRACTOR INSTALLED.
NEW DOOR
D603
REF.
EXIST
OPENING
3'-0"
6'-6"
10'-0"
2'-6"
10'-0"
2'-9"3'-0"2'-9" 2'-9"
11'-6"
NEW SINGLE BOWL
DROP-IN ADA SINK
BY ELKAY. REFER TO SHEET
P003, FIXTURE P1. SIZE TO
MATCH EXISTING.
D603
DOOR
NO.
A 3'0"x 7'-0"
GLASS
1 3/4"
THICK
DOOR
JAMB
MAT'L
THRES.
HARDWARE
REMARKS
4 7/8"
*CONTRACTOR TO VERIFY DIMENSIONS AND THICKNESS OF ALL DOORS
WOOD PANEL
TYPE ALUMINIUM EXTERIOR
TYPE 1
MTL HINGES
DOOR PULL
WEATHER STRIPPING
2 ea
2 ea 1 ea
FRAME
* DOORS TO MATCH EXISTING
1 3/4"
4 7/8"
PANELS
WOOD PANEL
(W x H)
3'0"x 7'-0" ---
DOOR SCHEDULE
SIZE
D604 A
TYPE
NUMBER
RESTROOM NO WORK
MATERIAL
N/A N/A
ROOM FINISH SCHEDULE
602 READY / BREAK ROOM
ROOM NAME
QUIET ROOM
NEW BREAK ROOM
EQUIPMENT ROOM
FLOOR
BASE NORTH
N/A
EAST SOUTH WEST MATERIAL
GYP 8'-0"
CEILING
HEIGHT
WALLS
VCT RUBBER N/A GYP
CARPET PAINT GYP
N/A N/A N/A
GYP
N/A N/A N/A
TILE
CARPET
TILE
RUBBER
PAINT
PAINT PAINT
8'-0"
MATCH EXISTING
MATCH EXISTING,
ONLY AT NEW WALL
CORE EDGES
1/2" PLYWOOD
3/4" MDF DOORS
DOOR PULLS
4" CAULKED MOLDING
COUNTER TOP WITH
GUARD
BACKSPLASH
SOLID SURFACE
(PLAM-3)
KITCHEN CABINETS AT SINK DETAIL
SCALE: 1" = 1'-0"A011
KITCHEN CABINETS DETAIL
SCALE: 1" = 1'-0"A011
SLOPED TOP
SINK
SLOPED TOP
TYP. U.N.O
MELAMINE FINISH
WITH STANDARD
ADJUSTABLE 3/4" MDF
LED LIGHT
SPLASH GUARD
COUNTERTOP SIDE
GUARD
BACKSPLASH
WITH 4"CAULKED MOLDING
SOLID SURFACE COUNTERTOP
WITH PLYWOOD
HARDWOOD TRIM
4" RUBBER BASE
MELAMINE FINISH
SHELF W/ STNDRD
ADJUSTABLE 3/4" MDF
4" RUBBER BASE
TO PANEL FACE BOARD
ANGLE PLYWOOD SCORED
P003, FIXTURE P1. SIZE TO
BY ELKAY. REFER TO SHEET
DROP-IN ADA SINK BY ELKAY.
NEW SINGLE BOWL
COUNTERTOP
SPLASH GUARD
COUNTERTOP SIDE
DOOR THRESHOLD DETAIL
SCALE: 3" = 1'-0"A011
HEAD DOOR DETAIL
JAMB DOOR DETAIL
HOLLOW METAL
DOOR FRAME-RATED
GYP. BOARD
5/8" TYPE "X"
1 LAYER
INSULATION
3-1/2" BATT
LOCATIONS
DOOR JAMB
AT ALL
METAL STUDS
DOUBLE 3-5/8"
STUDS.
3-5/8" METAL
DOOR AS SCHED.
SOLID CORE
CARPET FLOORING
IN HEIGHT ABOVE FIN. FLR.
NOT TO EXCEED 1/2"
TRANSITION STRIP
(BEYOND)
DOOR FRAME
SCHED.
DOOR AS
SOLID CORE
INSULATION
3-1/2" BATT
LOCATIONS
DOOR JAMB
AT ALL
METAL STUDS
DOUBLE 3-5/8"
STUDS.
3-5/8" METAL
DOOR AS SCHED.
1' 2'01'
SCALE: 1" = 1'-0"
SCALE: 1/2" = 1'-0"
5'1' 2'01'
SCALE: 3" = 1'-0"
9"6"3"3" 0
2. KITCHEN CABINET FINISH IS TO BE COORDINATED WITH RESIDENT ENGINEER.
COORDINATE EXACT LOCATIONS WITH RESIDENT ENGINEER.
KITCHEN APPLIANCES ARE TO BE PROVIDED BY FAA. 1.
cak-1701251-a011
2023-09-14T12:55:06-0500
DOUGLAS E WEAVER
2022-09-20T17:06:08-0500
RONALD M HUBRICH
7'-7"
DEMOLITION FLOOR PLAN
CAK-1701251-D001
-d lo tt e
VM VM
LOCKER ROOM
READY/BREAK ROOM
1 5 8
7 17 2
8 11
EQUIPMENT RM
EXISTING 6TH FLOOR PLAN
SCALE: 1/4" = 1'-0"D001
FR
DEMOLITION KEY NOTES:
REMOVE ALL OBSOLETE FURNITURE FROM TRACON ROOM, ELECTRONIC EQUIPMENT, CABINETS
ANACCESSORIES FROM FLOOR WALL AND CEILING. PATCH ALL SURFACES AS REQUIRED.
REMOVE WATER DISPENSER AND REMOVE NICHE LOCATED ON TRACON ROOM, PATCH WALL OPENING, CAP
EXISTING PLUMBING ON BACK WALL
EXISTING SOUNDPROOF BOARDS TO REMAIN, PAINT ALL OTHER SURFACES
REMOVE EXISTING BASE BOARD HEATER, REPAIR BACK DRYWALL AS NEEDED, PAINT AND PROVIDE
VINYL BASE AS NECESSARY.
NON-DIMMABLE LIGHT FIXTURES TO BE REPLACED. PROVIDE NEW DIMMER SWITCH CONTROL.
(REFER TO ELECTRICAL)
REMOVE EXISTING NON-RATED WALL TO EQUIPMENT ROOM.
PROVIDE 3'-4" x 7'-2" ROUGH OPENING FOR NEW 20 MIN. DOOR TO KITCHEN.
REMOVE EXISTING CEILING PANELS, EXISTING GRID TO REMAIN.
REMOVE KITCHEN BACK WALL, RE ROUTE PLUMBING TO NEW WALL LOCATION.
REMOVE EXISTING KITCHEN FURNACES, CABINETS, COUNTER SPACE, KITCHEN SINK AND SOFFIT AREA
FIXTURES, HOOD AND FIRE SUPPRESSION SYSTEM.
REMOVE EXISTING KITCHEN VINYL FLOOR, PREP FLOOR SURFACE FOR NEW FINISH MATERIAL.
RELOCATE EXISTING SODA MACHINE LOCATED IN KITCHEN TO NEW LOCKER/BREAK ROOM.
REMOVE EXISTING LOCKERS.
RELOCATE EXISTING VENDING MACHINE IN EXISTING LOCKER ROOM TO NEW LOCKER/BREAK ROOM.
REMOVE EXISTING VINYL FLOORING IN EXISTING LOCKER ROOM, PREP FOR NEW FINISH MATERIAL.
PROVIDE 3'-4" x 7'-2" ROUGH OPENING FOR NEW 20 MINUTE DOOR FROM HALLWAY.
EXISTING FIRE ALARM AND CLIMATE CONTROL PANELS TO REMAIN.
DELINEATES DEMOLITION AREA
REMOVE EXISTING WALL. SEE NOTE NO. 218
6TH FLOOR KEY PLAN
REMOVE THE TWO EXISTING DUPLEX RECEPTACLES AND THE EXISTING QUADRUPLEX RECEPTACLE 19
TO MAKE SPACE FOR ADA LOCKERS.
cak-1701251-d001
2023-09-14T12:54:22-0500
DOUGLAS E WEAVER
2022-09-20T17:05:18-0500
RONALD M HUBRICH
7'-7"
ELECTRICAL DEMOLITION PLAN
BE
KAH
CAK-1701251-D002
lo tt e
SCALE: 1/4" = 1'-0"D002
UPDOWN
VM
PNL C-2
PNL C2-A
PNL A-1
EQUIPMENT RM
LOCKER
VM
KEY PLAN
6TH FLOOR
STAIRWAY WILL BE CHARGED TO THE RESPONSIBILITY OF THE SUBCONTRACTOR.
DURING CONSTRUCTION, OPERATIONALLY AND COSMETICALLY. ANY DAMAGE TO THE ELEVATOR OR
ACCESS TO WORK SITE WILL BE THE STAIRWAY OR ELEVATOR. PROTECT THE ELEVATOR AND STAIRWAYT.
STORE ALL THE TOOLS.
MAINTAIN A CLEAN CONSTRUCTION AREA BY CLEANING DAILY. REMOVE ALL DEBRIS AND PROPERLYS.
OF THE WORK.
DO NOT OBSTRUCT THE MEANS OF EGRESS FOR THE FACILITY AT ANY TIME THROUGHOUT THE PERIODR.
ON ARCHITECTURAL DRAWINGS.
COORDINATE DEMOLITION SHOWN ON THIS DRAWING WITH DEMOLITION WORK AND NOTES SHOWNQ.
MUST RELOCATE AND REINSTATE TO ORIGINAL WORKING CONDITION.
IF FIRE ALARM DEVICES ARE DISTURBED DURING THE PERFORMANCE OF THE WORK, CONTRACTORP.
TRAFFIC OPERATIONS.
SCHEDULE WORK TO AVOID DISRUPTIONS TO THE OCCUPANTS, AIRPORT ADMIN STAFF AND AIR
THE BUILDING WILL BE OCCUPIED DURING THE PERFORMANCE OF THE WORK. COORDINATE ANDO.
REQUIREMENTS.
IN ACCORDANCE WITH THE SCHEDULE DESCRIBED IN "SEQUENCE OF WORK" UNDER GENERAL
ELECTRICAL WORK DESCRIBED IN THESE DOCUMENTS MUST BE COORDINATED WITH GENERAL WORKN.
RELOCATE EQUIPMENT TO NEW WALLS AS INDICATED.M.
EXISTING CONDUITS MAY BE MODIFIED AND REUSED FOR NEW WORK.L.
OF THE EXISTING LIGHTING MAY BE USED AS A TEMPORARY LIGHTING IF IT'S APPROVED BY THE R.E.
PROVIDE TEMPORARY LIGHTING AND MAINTAIN BUILDING POWER DURING DEMOLITION. ALL OR PARTK.
REPAIRED TO MATCH EXISTING.
FINISHES AND SURFACES DAMAGED BY THE DEMOLITION OR CONSTRUCTION MUST BE PATCHED ANDJ.
SYSTEM AND KITCHEN STOVE FIRE SUPPRESSION HOOD SYS.
SSC, AIRPORT, AND RESIDENT ENGINEER; INCLUDING THE SAFE HANDLING OF THE SIEMENS FIRE
SUBCONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL NECESSARY ARRANGEMENT WITH UTILITY,I.
KITCHEN STOVE HOOD SYSTEM, AND ALARMS CIRCUITS DURING ALL PHASES OF CONSTRUCTION.
ELECTRICAL CONTRACTOR SHALL MAINTAIN ALL SIGNAL, POWER, LIGHTNING, SIEMENS FIRE PANEL,H.
ON AND ALL EXISTING OUTLETS FROM THE WALLS BEING REDONE.
REMOVE ALL EXISTING LIGHTS AND THEIR CONTROLS FROM THE TRACON ROOM AREA BEING WORKEDG.
STORE SMOKE DETECTORS TO BE REINSTALLED BELOW NEW CEILING.
WHERE CONDUITS ARE INACCESSIBLE TO REMOVE AND/OR CAN BE REUSED, LEAVE THEM IN PLACE.
AND ASSOCIATED WIRING AND CONDUITS BACK TO THE POWER SOURCE OR NEAREST OUTLET BOX/JB.
DISCONNECT AND REMOVE LIGHTING FIXTURES, EXIT SIGNS, WIRING, WIRING DEVICES, SWITCHESF.
FROM EACH FIXTURE AND DISPOSE OF BALLAST IN ACCORDANCE WITH FEDERAL AND STATE
FLUORESCENT LIGHTS HAVE BALLASTS THAT MAY CONTAIN PCB MATERIAL. REMOVE EACH BALLASTE.
WORK BEING PREFORMED. DO NOT OPEN OR CLOSE ANY CIRCUIT BREAKER AT ANY TIME.
BREAKER OPERATION TO THE FAA IN WRITING AND AT LEAST 24 HOURS IN ADVANCE TO THE
ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMIT ALL REQUESTS FOR CIRCUITD.
DEMOLITION.
ENSURE EQUIPMENT IS DE-ENERGIZED AND LOCKED-OUT/TAGGED-OUT BEFORE COMMENCINGC.
ADMIN STAFF PERSONNEL IN ADVANCE.
ELECTRICAL SYSTEMS. ALL DEMOLITION WORK MUST BE COORDINATED WITH FAA AND AIRPORT
FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO DEMOLITION OF BUILDINGB.
REFER TO DRAWING G002, E006, AND M002 FOR SYMBOL LEGEND AND ABBREVIATIONS.A.
KEYED NOTE:
EXISTING RECEPTACLE AND AC CONTROLS INFORMATION
REFER TO DRAWING E007 (KEYED NOTE 13 AND KEYED NOTE 15) FOR MORE NEW LOCATION FOR1 cak-1701251-d002
2023-09-14T12:54:38-0500
DOUGLAS E WEAVER
2022-09-20T17:05:36-0500
RONALD M HUBRICH
AND ABBREVIATIONS
ELECTRICAL NOTES, LEGEND
PROGRAM ENGINEER MGR: ENGINEERING
CAK-1701251-E006
-e lo tt e
GENERAL ELECTRICAL NOTES
GROUNDING NOTES
ELECTRICAL ABBREVIATION
AC HH
AWG
GND
RGS
EES
EMT
FT
J-BOX
MTS
NEC
CCS
RF
PVC
SER
SPD
GEC
SLD
MDP
BFL
E/G
GFCI
GFE
LFM
SCH
TYP
MAIN-GP
COMM
MLO
SUPP-GP
WP
BSC
FRWK
MPGP
LPS
OSHA
NFPA
AGL
AIRCRAFT RATED HANDHOLE
MULTI-POINT GROUND PLATE
MAIN GROUND PLATE
EARTH ELECTRODE SYSTEM
GROUND CONDUCTOR
FRAMEWORK
BARE STRANDED COPPER
AMERICAN WIRE GAGE
SUPPLEMENTAL GROUND PLATE
MAIN LUG ONLY
POLYVINYL CHLORIDE CONDUIT
LIQUIDTIGHT FLEXIBLE METAL CONDUIT
COPPER-CLAD STEEL
COMMUNICATION
ENGINE GENERATOR
NATIONAL ELECTRIC CODE (NFPA 70)
NATIONAL FIRE PROTECTION ASSOCIATION
OPERATIONAL SAFETY AND HEALTH ADMINISTRATION
LIGHTNING PROTECTION SYSTEM
SERVICE ENTRANCE RATED
RADIO FREQUENCY
SINGLE LINE DIAGRAM
GROUNDING ELECTRODE CONDUCTOR
MANUAL TRANSFER SWITCH
FEET
ELECTRICAL METALLIC TUBING
JUNCTION BOX
RIGID GALVANIZED STEEL CONDUIT
SCHEDULE
GROUND FAULT CIRCUIT INTERRUPTER
SURGE PROTECTIVE DEVICE
TYPICAL
GOVERNMENT FURNISHED EQUIPMENT
MAIN DISTRIBUTION PANEL
CONDUIT
BELOW FROST LINE
MAY BE USED ON THIS PROJECT
NOT ALL SYMBOLS AND ABBREVIATIONS
DIA DIAMETER
DESIGN CODES AND CRITERIA
WEATHERPROOF
TBD TO BE DETERMINED
AVG
ELECTRICAL LEGEND
H. TITLE 47 PART 15 FOR CLASS B DEVICES (CFR)
G. TITLE 47 PART 15 FOR CLASS A DEVICES (CFR)
F. NFPA 70E
E. IEEE C2
D. FAA-C-1217
C. FAA-C-1391
B. FAA-STD-019
A. NFPA 70 (NEC)
REGULATIONS, AND STANDARDS. THESE APPLICABLE CODES OF THE FOLLOWING CODES AND STANDARDS:
ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH DIVISION 26 OF THE CONTRACT DOCUMENT/DRAWINGS, ALL 1.
ABOVE GRADE LEVEL
AVERAGE
COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE
CONSULT WITH COTR FOR RELOCATION, ADDITION/SUBTRACTION OF ANY LIGHTING FIXTURES, SWITCHES, RECEPTACLES, ETC.22.
ROUTING, BENDS, FITTINGS, ELBOWS, NIPPLES, NEEDED JUNCTION BOXES, AND REQUIRED SUPPORTS IN THE FIELD.
THE INTENT OF THE DRAWINGS IS TO SHOW THE SCOPE OF WORK IN A DIAGRAMMATIC FORM. DETERMINE THE EXACT CONDUIT 21.
ONLY PERFORM SPLICES AT RECEPTACLES AND JUNCTION BOXES. UNDERGROUND CONDUCTOR SPLICING ARE NOT PERMITTED. 20.
DURING THE PERFORMANCE OF THE WORK AS THE FACILITY WILL BE OCCUPIED AND IN OPERATION.
COORDINATE AND SCHEDULE WORK WITH RE AND FACILITY MANAGER TO AVOID DISRUPTIONS TO THE EQUIPMENT AND OCCUPANTS 19.
CONTINUITY. PROVIDE ALL NECESSARY CORRECTIONS TO MAKE THE SYSTEM READY FOR OPERATION AGAIN.
TEST ALL NEW, RELOCATED, AND EXISTING CIRCUITS/DEVICES AFFECTED BY NEW WORK FOR GROUNDING AND POWER 18.
NEW OR AFFECTED PANELBOARDS.
IDENTIFY AND MARK UP ANY CHANGES TO THE PANEL DIRECTORIES AFFECTED BY NEW WORK. PROVIDE NEW DIRECTORIES FOR
FIELD VERIFY THE ACCURACY OF THE EXISTING BRANCH CIRCUITS AND MARK UP THE DRAWINGS WITH ANY DIFFERENCES. RE-17.
EQUIPMENT NOT INTENDED TO BE REMOVED.
EXERCISE DUE CARE IN THE REMOVAL OF ELECTRICAL DEVICES AND EQUIPMENT NOT TO INTERRUPT POWER TO ANY OTHER 16.
WRITING 30 DAYS IN ADVANCE OF THE WORK BEING PERFORMED. DO NOT OPEN OR CLOSE ANY CIRCUIT BREAKER AT ANY TIME.
ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMIT ALL REQUESTS FOR CIRCUIT BREAKER OPERATION TO THE FAA IN 15.
ORDER NEW MATERIALS.
LOCATION OF EXISTING CABLE TRAYS, WIREWAYS, PANELBOARDS, AND DEVICE/MATERIALS TO BE UPGRADED/MODIFIED BEFORE
VISIT THE JOB SITE TO BECOME COMPLETELY FAMILIAR WITH THE EXISTING CONDITIONS PRIOR TO BEGINING WORK. FIELD VERIFY 14.
MANUFACTOR OR CONTRACTOR DRAWINGS.
THE MINIMUM CONTROL CONDUCTOR SIZE ALLOWED FOR USE IS 14 AWG, UNLESS OTHERWISE NOTED BY?
STRANDED TYPE CONDUCTORS ARE ALLOWED ONLY FOR SIZE 10 AWG OR LARGER.?
SOLID TYPE CONDUCTORS ARE ALLOWED ONLY FOR CONDUCTOR SIZE 12 AWG OR SMALLER.?
THE MINIMUM CONDUCTOR SIZE ALLOWED FOR USE IS 12 AWG.?
THE FOLLOWING REQUIREMENTS MUST BE MET FOR BRANCH CIRCUIT CONDUCTORS:13.
ALL ELECTRICAL EQUIPMENT MUST BE MARKED WITH THE APPROPRIATE SAFETY AND WARNING LABELS.12.
MINIMUM OF 72 HOURS ADVANCE NOTICE.
PROCEDURES PRIOR TO EACH ELECTRICAL OUTAGE. COORDINATE ANY POTENTIAL OUTAGES WITH FAA WITH A THESE
STRICTLY ENFORCE LOCKOUT/TAGOUT (LOTO) PROCEDURES PER NFPA 70E, LATEST EDITION THROUGHOUT THIS PROJECT. REVIEW 11.
GROUND CONDUCTORS ARE NOT ALLOWED.
PROVIDE EACH CIRCUIT WITH AN INDIVIDUAL UNGROUNDED, GROUNDED, AND EQUIPMENT GROUND CONDUCTOR. SHARED 10.
NOT ALLOWED.
PROVIDE EACH CIRCUIT WITH AN INDIVIDUAL NEUTRAL AND EQUIPMENT GROUND CONDUCTOR. SHARED NEUTRALS ARE 9.
UPON INSTALLATION COMPLETION.
TEST CABLES IN ACCORDANCE WITH SPECIFICATION SECTION OF ELECTRICAL EQUIPMENT TESTING PRIOR TO INSTALLATION AND 8.
WIRING HAS BEEN INSTALLED.
TERMINATE EACH RGS CONDUIT WITH THREADED SEALING HUB. SEAL BOTH ENDS OF ALL CONDUITS WITH DUCT SEAL AFTER 7.
DRAWINGS.
INCLUDE ANY ADDITIONAL APPURTENANCE NECESSARY FOR PROPER FUNCTION OF THE SYSTEM EVEN NOT SHOWN ON THE 6.
APPLY ANTI-SEIZE COMPOUND TO ALL THREADS ON BOLTS, AND SCREWS.5.
INSTRUCTIONS, NEC, NEMA, AND FAA STANDARDS AND ORDERS.
EACH PIECE OF EQUIPMENT INSTALLED UNDER THE CONTRACT. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER
PROVIDE ALL REQUIRED CONDUITS, CABLES, JUNCTION BOXES, FITTINGS, SUPPORTS, ETC TO COMPLETE BRANCH CIRCUITS FOR 4.
SPACE ACCORDING TO THE NEC CODE AND OSHA.
AVOID SPACE CONFLICT. INSTALLATION OF THE EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF THE WORKING
ALL EQUIPMENT DIMENSIONS SHOWN ARE NOMINAL. FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH EQUIPMENT TO 3.
BE THREADED TYPE ONLY. EMT ONLY FOR INDOOR WIRING. EMT FITTINGS SHALL BE COMPRESSION TYPE ONLY.
OUTDOOR INSTALLATION. PVC COATED RGS ONLY FOR UNDERGROUND INSTALLATION. RGS CONDUIT FITTINGS SHALL
PERMITTED FOR GROUND CONDUCTORS OR BURIED RACEWAYS UNLESS INDICATED OTHERWISE. RGS CONDUIT ONLY FOR
PERMITTED RACEWAY TYPES ARE EMT, RGS, PVC-COATED RGS, AND PVC SCHEDULE 80. PVC RACEWAY SHALL ONLY BE 2.
OUTDOOR CONNECTIONS.”
PROVIDE ALL THE NECESSARY WEATHER RESISTANT ENCLOSURES AND CORROSION RESISTANT, WATERTIGHT, FITTINGS FOR 1.
TO PREVENT MOISTURE FROM REACHING THE BONDING AREA PER FAA-STD-019, LATEST EDITION.PETROLEUM BASE
PROVIDE CORROSION PROTECTION BY SEALING THE BOND CONNECTION WITH A MOISTURE POINT, SILICONE, OR5.
APPROPRIATE COATING TO PREVENT CORROSION AFTER INSTALLATION.
REMOVE PAINT FROM THE AREA WHERE GROUND LUGS ARE TO BE INSTALLED. SEAL THE AREA WITH PAINT OR THE4.
PROVIDE SUPPLY SIDE GROUND BONDING JUMPER SIZED PER THE LATEST EDITION OF THE NEC.3.
ACCORDANCE WITH FAA-STD-019 (LATEST EDITION).
GROUND METAL PARTS, CONDUITS, EQUIPMENT, INTERFACE BOXES, AND JUNCTION BOXES IN 2.
COPPER CONDUCTOR.
BOND TO EES ALL FACILITY ENTRANCE CONDUITS WITH A 2 AWG BARE-STRANDED 1.
AT AIR TRAFFIC
ATCT AIR TRAFFIC CONTROL TOWER
DIST DISTRIBUTION
RM ROOM
ELEV ELEVATOR
PNL PANEL
DP-1
EX
SPD
X/Y/Z = POLE SIZE
= FRAME SIZE
= FUSE SIZE
EXIT SIGN WITH EMERGENCY LIGHT
SURGE PROTECTIVE DEVICE
FUSED AT [Y]A
FUSIBLE DISCONNECT [X]A/[Z]
DUPLEX RECEPTACLE
RECESSED/FLUSH MOUNTED
QUAD RECEPTACLE
SURFACE MOUNTED
CONDUIT, FLEXIBLE
CONDUIT, CAPPED
CONDUIT STUB UP
CONDUIT STUB DOWN
SOLID WHETHER CONCEALED OR EXPOSED
HOME RUN TO PANEL DP BREAKER, SHOWN
SAME AS BRANCH CIRCUIT - BUT CONCEALED
ABOVE GROUND EXOTHERMIC WELD
EES (BURIED) GROUND
UNDERGROUND POWER CONDUIT
DOWN CONDUCTOR
UG
WITH MOUNTED UTILITY METER
UTILITY COMPANY TRANSFORMER
WITH (2)-12 AWG CONDUCTOR(S) PLUS (1)-12 AWG GROUND
BRANCH CIRCUIT, SURFACE MOUNTED 3/4" RACEWAY,
WHEN MORE THAN 3 IN 3/4" RACEWAY
CROSS MARKS DENOTE NUMBER OF 12 AWG CONDUCTOR(S)
RECESSED CEILING MOUNTED LED LIGHTING FIXTURE
ABOVE GROUND, CONDUCTOR
SYMBOL DESCRIPTION
OH OVERHEAD CONDUCTORS
DESCRIPTIONSYMBOL
120V, 20A, SPECIFICATION GRADE
THREE POLE SWITCH
AC
AIR CONDITIONER CONTROLS / THERMOSTAT
SINGLE POLE SWITCH
DIMMER SWITCHD
DEMOLITION
SINGLE RECEPTACLE
(GFCI)
DUPLEX RECEPTACLE (GFCI)
ETHERNET PORT BOX
TELEPHONE
DISTRIBUTION PANELBOARD
SURFACE-MOUNTED ELECTRICAL
DISTRIBUTION PANELBOARD
RECESSED ELECTRICAL
WRAPAROUND LIGHT
CEILING MOUNTED LED LIGHTING FIXTURE
EXISTING STEPLIGHT FIXTURE
EMERGENCY LIGHT (SINGLE)
EMERGENCY LIGHT (DUAL)
DUPLEX RECEPTACLE
SINGLE RECEPTACLE
QUAD RECEPTACLE
RECEPTACLE
APPLIANCE DESIGNATED
cak-1701251-e006
2023-09-14T12:56:32-0500
DOUGLAS E WEAVER
2022-09-20T17:08:15-0500
RONALD M HUBRICH
PROPOSED 6TH FLOOR POWER & LIGHTING PLAN
CAK-1701251-E007
:5 lo tt e
PROPOSED 6TH FLOOR POWER AND LIGHTING PLAN
SCALE: 1/4" = 1'-0"E007
1 1
C3
C-2, #15
C-2, #16
C-2, #17
C-2, #21
C-2, #22
SINK
PNL C-2
PNL C2-A
PNL A-1
C-2, #15
JBOX
C-2, #20
+78" AFF
A B
A B
C-2, #18
AND #32
C-2, #30
+78" AFF
RECEPTACLE FOR SINK LIGHT MUST BE 18" ABOVE COUNTERTOP.
REPLACE EXISTING LIGHT SWITCH WITH NEW DIMMABLE SWITCH IN THE READY/BREAK ROOM.
BY THE RE.
PROVIDE WALL RECEPTACLES FOR CONFERENCE TABLE. EXACT LOCATIONS TO BE DETERMINED IN THE FIELD
MOVE THE EXISTING AC CONTROLS TO THE NEW SHOWN LOCATION.
SCHEDULE INFORMATION.
EXISTING ELECTRICAL DISTRIBUTION PANEL C2-A. REFER TO DRAWING E004 FOR MORE EXISTING PANEL
MOVE THE EXISTING RECEPTACLE AT DOOR WALL TO THE NEW LOCATION SHOWN.
REPLACE EXISTING LIGHT SWITCH WITH NEW DIMMABLE SWITCH IN THE QUIET ROOM.
MOVE THE EXISTING RECEPTACLE TO THE WEST KITCHEN WALL FOR EASY APPLIANCE ACCESSIBILITY.
MOVE THE EXISTING RECEPTACLE(S) TO THE NEW WALL.
MOVE THE EXISTING RECEPTACLE AS SHOWN.
PROVIDE NEW EMERGENCY EXIT SIGN.
COORDINATE LIGHTING FIXTURE LAYOUT WITH HVAC EQUIPMENT LAYOUT.
PROVIDE A FLOOR MOUNTED QUAD RECEPTACLE AND BOX ON BOTH SIDE OF COUCH.
PER FAA REQUIREMENTS.
PROVIDE A CATV OUTLET AT 72" AFF FOR TV CONNECTIONS AND 1" C FROM JBOX TO 6" ABOVE CEILING AS
EXISTING ELECTRICAL DISTRIBUTION PLANELOAD C-2.
PROVIDE NEW DIMMER SWITCH, IN THE LOCKER ROOM.
SCHEDULE INFORMATION.
EXISTING ELECTRICAL DISTRIBUTION PANEL A-1, REFER TO DRAWING E004 FOR MORE EXISTING PANEL
REPLACE EXISTING LIGHT BULB WITH NEW LED LIGHT BULB.
INFORMATION.
PROVIDE NEW DUPLEX RECEPTACLE. REFER TO GENERAL NOTE 2 FOR MORE VENDING MACHINE RECEPTACLE
PROVIDE NEW LED WRAPAROUND LIGHTING FIXTURES.
REFER TO ARCHITECTURAL DRAWINGS A010 AND A011 FOR MORE INFORMATION.B.
EDITION OF FAA-C-1217.
ENSURE ALL INTERIOR POWER DISTRIBUTION WIRING ARE IN ACCORDANCE WITH THE LATEST A.
LEGEND :
NEW -
EXISTING -
cak-1701251-e007
2023-09-14T12:56:46-0500
DOUGLAS E WEAVER
2022-09-20T17:08:40-0500
RONALD M HUBRICH
LOCAL AREA NETWORK DATA PLAN
PROPOSED 6TH FLOOR
CAK-1701251-E008
:1 lo tt e
PROPOSED 6TH FLOOR LOCAL AREA NETWORK DATA PLAN
SCALE: 1/4" = 1'-0"E008
SYSTEM. THE EXACT LOCATIONS TO BE DETERMINED IN THE FIELD BY RE.
CONNECT NEW TELEPHONE PORT BOX FOR CONFERENCE TABLE TO THE EXISTING TELECOMMUNICATIONS
DETERMINED IN THE FIELD BY RE.
CONNECTIONS TO THE ETHERNET PORT BOXES FOR CONFERENCE TABLE. THE EXACT LOCATIONS TO BE
USE ADDITIONAL LOCKER BREAKROOM NEW ETHERNET BOX PORTS FROM KEYED NOTE 1 TO PROVIDE
CONNECTIONS TO ETHERNET PORT BOX(ES) IN THE LOCATIONS SHOWN.
USE ADDITIONAL LOCKER BREAKROOM NEW ETHERNET BOX PORTS FROM KEYED NOTE 1 TO PROVIDE
PROVIDE NEW TELEPHONE. (GFE) AND CONNECT IT TO THE EXISTING TELECOMMUNICATIONS SYSTEM.
INTERNET ROUTER LOCATED ON THE SECOND FLOOR OF THE ATCT TO THE LOCKER BREAK ROOM.
PROVIDE NEW ETHERNET PORT BOX IN THE LOCATIONS SHOWN. ROUTE ETHERNET CABLE FROM THE 1
ENSURE ALL INTERIOR COMMUNICATION WIRING IS IN ACCORDANCE WITH THE LATEST EDITION OF FAA-C-1217.B.
PROVIDE 10 FT STUB UP OF EMT AND PULL ROPE FOR ALL ELECTRICAL/COMMUNCATION DEVICES.A.
-NEW
-EXISTING
cak-1701251-e008
2023-09-14T12:57:17-0500
DOUGLAS E WEAVER
2022-09-20T17:08:53-0500
RONALD M HUBRICH
FACILITY PANEL SCHEDULES
BT
CAK-1701251-E009
lo tt e
1 20
1 15
1 20**
EXISTING ELECTRICAL PANELBOARD C-2
E009
EXISTING ELECTRICAL PANELBOARD A-1
EXISTING ELECTRICAL PANELBOARD C2-A
FED FROM PANEL FROM LOWER ATCT LEVEL
FED FROM PANEL C 2
PANEL A-1FED FROM:
ETVS CONV. BAY-2
C2-A
120/208 VOLTS
BREAKER
POLE
AMP
BUS RATING
MAIN
CKT.
PANEL SCHEDULE*
100 AMPS
LUG ONLY
BUS CONN.
ETVS BAY-2
AMP POLE
LOCATION
MOUNTING
MIN. AIC
CAK TRACON
SURFACE
10 KA
DESCRIPTION
FUTURE BAY-3
SPARE
PANEL
SERVICE VOLTAGE
PHASE
LIGHTS RM. 608
REC. S. WALL RM. 608
LIGHTS RM. 607
LIGHTS RM. 606
LAV LIGHTS & HAND DRYER
A-1
POLE AMP
LIGHTS RM. 602, 603, 604 & HALL (605) 120
REC. RM. 608 N. WALL
REC. W. WALL RM. 607
S.W. CORNER REC. RM. 607
J.S.C. HUMIDITY CONTROL
*ACTUAL CIRCUIT BREAKER INFORMATION MAY BE DIFFERENT THAN SHOWN.
100 AMPS
LUG ONLY
30 1
RECESSED
REC. W. WALL RM. 603
RANGEHOOD
REC. N. WALL RM. 606
REC. S. WALL RM. 603 DRINKING FOUNTAIN
REC. RM. 602
E. WALL RMS. 603 & 606
REC. S. WALL RM. 606 & 607
NIDS D4 1 20 41 42 15 1 ITWS/DMUX B4
***SEE SPECIFIC NOTE 2
**SEE SPECIFIC NOTE 1
225 AMPS
200A CIRCUIT BREAKER
40 15 1
100 3
20**
SURFACE
CONV. OUTLET PARROT D3
STRIP PARROT D3
FDIO BAY-4
NEW WALL FUTURE**
DUPLEX RECEPTACLE IN BREAK ROOM
VENDING MACHINE #2 DUPLEX
SPARE**
LOCKER BREAKROOM LIGHTING
RECEPTACLE(S) SPARE**
KITCHEN AND QUIET ROOM
EFTS E4
EFTS E4
C-2-A SUBPANEL
RM-606 SOUTH UNUSED
CAMERA SYSTEM POWER
ROOM-606 SOUTH WALL
NIDS D4
FDIO A4
DUPLEX RECEPTACLE IN BREAK ROOM
VENDING MACHINE #1 DUPLEX
FUTURE BAY-4
SPARE**
QUIET ROOM AND KITCHEN LIGHTING
FUTURE BAY-4
TOWER-CAB
TOWER-CAB
RM-606 SOUTH UNUSED
RM-606 SOUTH WALL
C-2
40*** 2 OVEN RANGE***
REFER TO DRAWING E007 FOR MORE POWER BRANCH CIRCUIT ROUTING INFORMATION.D.
ELECTRICAL PANELBOARD C-2 SERVES POWER TO THE SUBPANEL ELECTRICAL PANELBOARD C-2-A.C.
ELECTRICAL PANELBOARD A-1 SERVES POWER TO THE SUBPANEL ELECTRICAL PANELBOARD C-2.B.
LOCATED ON A LOWER LEVEL OF THE ATCT.
ELECTRICAL POWER PROVIDED TO THE ELECTRICAL PANELBOARD A-1 COMES FROM ANOTHER ELECTRICAL PANELBOARD A.
-CIRCUIT
NEW BRANCH
-NEW
-EXISTING
SPECIFIC NOTES:
LOCATIONS.
CONDUIT. REFER TO THE PANEL SCHEDULE CLOUDED REGIONS ON THIS DRAWING FOR NEW BRANCH CIRCUIT
REPLACE EXISTING SPARE BREAKERS, WITH NEW, 40A/2, CIRCUIT BREAKER WITH (3)-8 AWG + 10 AWG GND IN 3/4" 2.
REGIONS ON THIS DRAWING FOR NEW BRANCH CIRCUIT LOCATIONS.
REPLACE EXISTING SPARE BREAKERS WITH NEW, 20A, CIRCUIT BREAKER. REFER TO THE PANEL SCHEDULE CLOUDED 1.
cak-1701251-e009
2023-09-14T12:57:02-0500
DOUGLAS E WEAVER
2022-09-20T17:09:09-0500
RONALD M HUBRICH
MOUNTING DETAIL & DEVICE FLOW CHART
CONFERENCE ROOM LUMINAIRE SCHEDULE
BT
CAK-1701251-E010
LIGHTING
HUBBELL
DUAL/LITE
4000K LEDs PROVIDE LUTRON 1% DIMMING DRIVER OPTION.
---LED LAMPS
LIGHTING
PRUDENTIAL
@ H = 8'-0"
RECESSED0
CEILINGCLS-SE3
SINGLE FACE, NO ARROWS
RED LETTERS, BATTERY RUN TIME 90 MINUTES,
CAD BATTERY,
CEILING MOUNTED, LED EXIT LIGHTING UNIT, NI-
SUSPENDED
(TYPICAL)
NEW OR EXISTING
FEET (TYPICAL)
FIXTURE WHIP MAXIMUM LENGTH 6
NEW FLEXIBLE METAL CONDUIT
STRUCTURE
SUPPORT SYSTEM OR BUILDING
EXISTING UNISTRUT-TYPE
NEW RECESSED FIXTURE
EACH END
CORNERS OF FIXTURE WITH 5 TWISTS AT
GALV 12 GA SUSPENSION WIRE AT 2
CONDUIT EMT
NEW OR EXISTING
LBL4 LP840 RFD230716
(TO BE FCC PART 15 CLASS B COMPLIANT)
4'-0" LED WRAPAROUND WITH CLASS B DRIVER
ND-EML
WA-SW-SC-UNV-X1-
P8622-LED4-MO-
NON DIMMING
DIM TO DARK
1204000K LEDs DIM TO DARK
EMERGENCY LIGHT
2' X 2' RECESSED TROFFER W/BATTERY PACK
LUMINAIRE SCHEDULE
LABEL QTY CATALOG NUMBER DESCRIPTION LAMP
MANUFACTURER VOLTS MOUNTING
LITHONIA 120
DRIVER
4000K LEDs 120
LITHONIA LBL4 LP840 RFD230716
(TO BE FCC PART 15 CLASS B COMPLIANT)
4'-0" LED WRAPAROUND WITH CLASS B DRIVER
RECESSED FIXTURE MOUNTING DETAIL
E010
FAN
OR ADA (OPTIONAL)
120 VAC FOR FAN POWER FROM HOOD
(PROVIDED)
PLENUM CABLE
(NOT PROVIDED)
120 VAC 15 AMP CIRCUIT
12/2 MC WIRE WITH RED TAPE
PROVIDED)
(CABLE NOT
SCREEN
TOUCH
HMI
CONTROL BOX
CLOCK BOX
SHUT OFF
ELECTRICAL
131 114
CABLE (PROVIDED)
COMMUNICATION
5 VDC
PLENUM CABLE
BOX
JUNCTION
SWITCHES
THE RED WIRE IS THE FAN
THE BLACK WIRE IS THE LIGHT
THE WHITE WIRE IS CONSTANT HOT
120-220 VAC CIRCUIT 15-50 AMPS
HOOD LIGHT
HOOD OR ADA (OPTIONAL)
120 VAC FOR LIGHT POWER FROM
14/3 MC WIRE
OR CLOCK BOX (OPTIONAL)
VAC (PROVIDED) TO POWER DISCONNECT
14/2 MC WIRE WITH BLACK TAPE 120
DEVICE FLOW CHART
:0 lo tt e
LIGHT FIXTURES.
COMPLETE REQUIREMENTS OF CFR TITLE 47 PART 15 FOR CLASS A AND/OR CLASS B DEVICES FOR LED E.
INSTALLATION OF LIGHTING FIXTURES AND SUPPORTS TO MEET PROJECT SPECIFICATIONS AND SEISMIC D.
LAYOUT AND KEEP FLEXIBLE CONDUIT RUNS TO A MAXIMUM OF 6 FEET.
PROVIDE NEW CONDUIT AND WIRING FROM EXISTING JUNCTION BOXES TO SUPPORT NEW LIGHTING C.
COMPLETE ASSEMBLY.
COMPATIBILITY AND COMPLIANCE WITH LIGHTING CONTROL SYSTEM, PROPER FIT, AND A SECURE AND
MUST BE VERIFIED (CONSULT WITH LIGHTING MANUFACTURER) PRIOR TO INSTALLATION TO ENSURE
MOUNTING BRACKETS AND ACCESSORIES ALL LUMINAIRE BALLASTS, DRIVERS, ROW LENGTH OPTIONS, B.
COR AND WILL BE REVIEWED BY THE ENGINEER OF RECORD FOR COMPLIANCE AND APPROVAL.
EXCEED. SUBSTITUTIONS FOR THE SPECIFIED FIXTURES MUST BE SUBMITTED IN ADVANCE TO THE FAA
OF QUALITY, APPEARANCE, AND PERFORMANCE THAT ANY SUBSTITUTED FIXTURES MUST MATCH OR
ON THIS DRAWINGS ESTABLISH A LEVEL THE FIXTURES SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE A.
cak-1701251-e010
2023-09-14T12:57:47-0500
DOUGLAS E WEAVER
2022-09-20T17:09:21-0500
RONALD M HUBRICH
COVER SHEET AND VICINITY MAP
RDS
CAK-1701251-G006
-g lo tt e
VICINITY MAP
TRANSPO
OF
ST
TES
EN
OF
IC
AVIA
TRAT
SI
NI
AKRON, OHIO
AKRON-CANTON REGIONAL AIRPORT (CAK)
AIR TRAFFIC CONTROL TOWER (ATCT)
cak-1701251-g006
2023-09-14T12:53:43-0500
DOUGLAS E WEAVER
2022-09-20T17:04:21-0500
RONALD M HUBRICH
ABBREVIATIONS
INDEX OF DRAWINGS, LEGEND AND
RDS
CAK-1701251-G007
MAY BE USED ON THIS PROJECT
NOT ALL SYMBOLS AND ABBREVIATIONS°
NORTH ARROW
DEMOLITION
REVISION
REVISION DESIGNATION
NUMBER, POUNDS
CENTERLINE
'FEET OR MINUTES
"INCHES OR SECONDS
DEGREE
@AT
LEGEND
A010
DETAIL MARKER
A012
EXTENDED SECTION CUT
SECTION CUT
ELEVATION SYMBOL
C001
PL
LC
RUNWAY SAFETY AREA
RUNWAY OBJECT FREE AREA
FENCE
PROPERTY LINE
SITE ACCESS ROUTE
STAGING AREA
EXISTING WORK TO BE REMOVED
EXISTING WORK
NEW WORK
REVISED AREA
ENCOMPASS
CLOUD TO
DRAWING NO. DESCRIPTION
INDEX OF DRAWINGS
CAK-1701251-E010
CAK-1701251-E009
CAK-1701251-E008
CAK-1701251-E007
CAK-1701251-E006
CAK-1701251-P003
CAK-1701251-P002
CAK-1701251-P001
CAK-1701251-M003
CAK-1701251-M002
CAK-1701251-A011
CAK-1701251-A010
CAK-1701251-D002
CAK-1701251-D001
CAK-1701251-G008
CAK-1701251-G007
CAK-1701251-G006
LIGHTING FIXTURE & PANEL BOARD SCHEDULE
FACILITY PANEL SCHEDULES
PROPOSED 6TH FLOOR LOCAL AREA NETWORK DATA PLAN
PROPOSED 6TH FLOOR POWER AND LIGHTING PLAN
ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS
NEW CONSTRUCTION
PLUMBING AND FIRE PROTECTION PARTIAL SIXTH FLOOR DEMO &
PLUMBING PARTIAL FIFTH FLOOR PLAN - DEMO & NEW CONSTRUCTION
PLUMBING AND FIRE PROTECTION COVER SHEET
MECHANICAL PARTIAL SIXTH FLOOR PLAN - DEMO & NEW CONSTRUCTION
MECHANICAL COVER SHEET
KITCHEN ROOM ELEVATIONS AND DETAILS
NEW CONSTRUCTION AND RCP PLAN
DEMOLITION FLOOR PLAN
GENERAL NOTES
INDEX OF DRAWINGS, LEGEND AND ABBREVIATIONS
COVER SHEET AND VICINITY MAP
ABBREVIATIONS
- TRANSMITTERXMTR
- TRANSFORMERXFMR
- WELDED WIRE FABRICWWF
- WATERWTR
- WATER CLOSETWC
- WASTEW
- VISUAL APPROACH SLOPE INDICATORVASI
- VENTV
- UNINTERRUPTIBLE POWER SOURCE/SUPPLYUPS
- TYPICALTYP
- TRANSIENT VOLTAGE SURGE SUPPRESSORTVSS
- TAXIWAY SAFETY AREATSA
- TOP OF STEELTOS
- TAXIWAY OBJECT FREE AREATOFA
- TOP OF CONCRETETOC
- TELEPHONE COMPANYTELCO
- TAXIWAYT/W
- TO BE DETERMINEDTBD
- STATIONSTA
- SYSTEM SUPPORT CENTER (FAA)SSC
WITH RUNWAY ALIGNMENT INDICATOR LIGHTS
- SIMPLIFIED SHORT APPROACH LIGHTING SYSTEMSSALR
- SYSTEM MANAGEMENT OFFICE (FAA)SMO
- SURGE ARRESTORSA
- RUNWAY VISUAL RANGERVR
- REMOTE TRANSMITTER/RECEIVERRTR
- RIGID STEEL CONDUIT/RIGID GALVANIZED STEELRSC/RGS
- RUNWAY SAFETY AREARSA
- REMOTE RADIO CONTROL SYSTEMRRCS
- RUNWAY PROTECTION ZONERPZ
- RIGHT-OF-WAYROW
- RUNWAY OBJECT FREE AREAROFA
- RADIO FREQUENCYRF
- REVISIONREV
- RUNWAY EDGE LIGHTSREL
- RUNWAY END IDENTIFIER LIGHTSREIL
- REFERENCEREF
- RECONNECTRECONN
- RESIDENT ENGINEER (FAA/TSSC)RE
- RECEIVERRCVR
- REINFORCED CONCRETE PIPERCP
- RUNWAY ALIGNMENT INDICATOR LIGHTSRAIL
- RUNWAYR/W
- POLYVINYL CHLORIDE CONDUITPVC
- POUNDS PER SQUARE INCHPSI
- POUNDS PER SQUARE FOOTPSF
- PAIRPR
- POWER POLE/UTILITY POLEPP
- POINT OF STARTPOS
- POINT OF BEGINNINGPOB
- POINT OF INTERCEPTPOI
- PANELPNL
- PROPERTY LINE, PLATEPL
- POWER AND CONTROL UNITPCU
- PRECISION APPROACH PATH INDICATOR LIGHTSPAPI
- OUTER MARKEROM
- OBJECT FREE AREAOFA
- OUTSIDE DIAMETER/OVERFLOW DRAINOD
- NATIONAL WEATHER SERVICENWS
- NOTICE TO AIRMENNOTAM
- NATIONAL GEODETIC VERTICAL DATUMNGVD
- NATIONAL ELECTRIC CODENEC
- NON-DIRECTIONAL BEACONNDB
- NORTH AMERICAN VERTICAL DATUMNAVD
- NORTH AMERICAN DATUMNAD
- NOT APPLICABLEN/A
- MEAN SEA LEVELMSL
- MULTI-POINT (GROUND)MP
- MINIMUMMIN
- MEGAHERTZMHZ
- MANHOLEMH
- MAXIMUMMAX
WITH RUNWAY ALIGNMENT INDICATOR LIGHTS (RAIL)
- MEDIUM INTENSITY APPROACH LIGHTING SYSTEM (MALS)MALSR
WITH SEQUENCED FLASHERS
- MEDIUM INTENSITY APPROACH LIGHTING SYSTEMMALSF
- LOCATOR - OUTER MARKERLOM
- LOCALIZERLOC
- LOW IMPACT RESISTANTLIR
- LAMP HOUSING ASSEMBLYLHA
- LAVATORYLAV
- KILO-WATTKW
- KILO-VOLT AMPEREKVA
- KILO-VOLTKV
- KILO-HERTZKHZ
- INNER MARKERIM
- INSTRUMENT LANDING SYSTEMILS
- INDIVIDUAL CONTROL CABINETICC
- HERTZHZ
- HOT WATERHW
- HIGH VOLTAGEHV
- HEATERHTR
- HEIGHTHT
- HANDHOLEHH
- HIGH DENSITY POLYETHYLENEHDPE
- GLIDE SLOPEGS
- GALVANIZED RIGID STEEL CONDUITGRSC
- GEOGRAPHICAL REFERENCE POINTGRP
- GROUNDGND
- GOVERNMENT FURNISHED MATERIALGFM
- GROUND FAULT CIRCUIT INTERRUPTERGFCI
- GROUNDING ELECTRODE CONDUCTORGEC
- GALVANIZEDGALV
- FOOT/FEETFT
- FOREIGN OBJECT DEBRISFOD
- FAR FIELD MONITORFFM
- FINISH FLOORFF
- FIBER DISTRIBUTION PANELFDP
- FOUNDATIONFDN
- FIBER OPTICF/O
- EXTERIOR, EXTERNALEX/EXT
- EXISTINGEXIST
- EQUIPMENTEQUIP
- ELECTRIC METALLIC TUBINGEMT
- EMERGENCYEMERG
- ELECTRICELEC
- ELECTRICAL LINE DISTRIBUTIONELD
- ELEVATION (HEIGHT)EL
- EXPANSION JOINTEJ
- END-FIRE GLIDE SLOPEEFGS
- EARTH ELECTRODE SYSTEM (COUNTERPOISE)EES
- ENGINE-GENERATORE/G
- EXISTING TO BE REMOVED(ETBR)
- EXISTING TO REMAIN(ETR)
- EXISTING(E)
- DISTRIBUTION UNIT DU
- DISTANCE MEASURING EQUIPMENTDME
- DISCONNECTDISC
- DIMENSIONDIM
- DIRECT EARTH BURIALDEB
- COLD WATERCW
- CONTRACTING OFFICER'S REPRESENTATIVECOR
- CONTINUE, CONTINUATION, CONTINUOUSCONT
- CONNECTCONN
- CONCRETECONC
- COMMUNICATIONSCOMM
- CEILINGCLG
- CONTROL JOINTCJ
- CUBIC FEET PER MINUTECFM
- CONCRETE CABLE MARKERCCM
- BARE SOLID COPPERBSCU
- BARE STRANDED COPPERBSC
- BOTTOMBOT
- BELOWBLW
- BUILDINGBLDG
- BELOW GROUND/GRADE LEVELBGL
- AMERICAN WIRE GAUGEAWG
- AIRPORT TRAFFIC CONTROL TOWERATCT
- AIRPORT SURVEILLANCE RADARASR
- AUTOMATED SURFACE OBSERVATION SYSTEM (NWS)ASOS
- AIRPORT SURFACE DETECTION EQUIPMENTASDE
- AIRPORT REFERENCE POINTARP
- APPROXIMATELYAPPROX
- AIR OPERATIONS AREAAOA
- HIGH INTENSITY APPROACH LIGHTING SYSTEM WITH SEQUENCED FLASHERSALSF
- AMBIENT LIGHT SENSORALS
- ABOVE GROUND/GRADE LEVELAGL
- AMPERESA
lo tt e cak-1701251-g007
2023-09-14T12:53:57-0500
DOUGLAS E WEAVER
2022-09-20T17:04:44-0500
RONALD M HUBRICH
GENERAL NOTES
SKM
CAK-1701251-G008
lo tt e
GENERAL ARCHITECTURAL NOTES:
MATERIALS AND EQUIPMENT.
ENVIRONMENTAL CONDITIONS WHICH ARE REQUIRED TO MAINTAIN THE ORIGINAL QUALITY OF
MANUFACTURER'S INSTRUCTIONS REGARDING TEMPERATURE LIMITATIONS AND OTHER
OF FOREIGN MATTER OR MOISTURE FROM ANY SOURCE. COMPLY WITH MATERIAL AND EQUIPMENT
MANNER AS TO PREVENT DAMAGE, INCLUDING DAMAGE WHICH MIGHT RESULT FROM INTRUSIONS
TRANSPORT, DELIVER, HANDLE AND STORE MATERIALS AND EQUIPMENT AT THE JOBSITE IN SUCH A16.
ALL WORK SHALL BE PLUMB, SQUARE, LEVEL, IN PROPER ALIGNMENT, AND SECURELY FASTENED.15.
SYSTEM.
DO NOT ALLOW ADHESIVE ODOR AND OTHER FUMES FROM CONSTRUCTION ACTIVITY TO ENTER HVAC14.
CONTRACTOR'S EXPENSE AND TO THE SATISFACTION OF THE RESIDENT ENGINEER.
NOT INCLUDED IN THE SCOPE OF THIS PROJECT, SHALL BE REPAIRED AND CORRECTED AT
ELEMENTS AND FIRE RATED ASSEMBLIES. ANY DAMAGE TO THE EXISTING BUILDING AND/OR SITE, EXTEND PATCH TO THE NEAREST NATURAL BREAK POINT. REPAIR FIREPROOFING ON STRUCTURAL
OCCURS. PATCH AND FINISH DISTURBED AREAS TO MATCH ADJACENT MATERIALS AND FINISHES.
PROVIDE PROTECTION FOR ALL EXISTING FINISHES TO REMAIN, AND REPAIR ANY DAMAGE THAT13.
FURNISHED TO THE RESIDENT ENGINEER PRIOR TO THE COMMENCEMENT OF ANY WORK.
DEMOLITION AND CONSTRUCTION PHASES. A COPY OF SUCH INSURANCE COVERAGE SHALL BE
COPIES OF ALL APPLICABLE PERMITS SHALL BE MAINTAINED ON-SITE AND ADHERED TO DURING THE
NATIONAL BUILDING REGULATIONS OR CODES TO ADEQUATELY PROTECT PERSONS AND PROPERTY.
COSTS SHALL INCLUDE THE COST OF PROPER INSURANCE AS REQUIRED BY STATE AND LOCAL LAWS, THE CONTRACTOR SHALL APPLY FOR AND OBTAIN ALL PERMITS REQUIRED BY REGULATORY AGENCIES.12.
IN FINISHED AREAS CONCEAL PIPING, DUCTWORK WIRING AND CONDUITS.
DUCTWORK AND CONDUITS ALLOW FOR MAXIMUM ACCESSIBILITY FOR MAINTENANCE AND REPAIRS.
PLUMBING, MECHANICAL AND SECURITY SYSTEMS AS REQUIRED SO THAT PIPING, WIRING,
CONSTRUCTION TO REMAIN. ESTABLISH ROUTING FOR ELECTRICAL, TELECOMMUNICATION,
THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF NEW CONSTRUCTION WITH EXISTING11.
FOR SERVICE INTERRUPTIONS A MINIMUM OF 14 BUSINESS DAYS PRIOR TO PLANNED INTERRUPTION.
THE SYSTEM. SERVICE OR UTILITY IN QUESTION. THE CONTRACTOR WILL MAKE REQUESTS IN WRITING
ACCEPTABLE SCHEDULE FOR THE INTERRUPTION, SWITCH OVER OR OTHER CHANGE IN OPERATION TO
CONTRACT TO PERFORM THE WORK, CONSULT RESIDENT ENGINEER TO ARRIVE AT A MUTUALLY
PRIOR TO ANY TEMPORARY INTERRUPTION OF SERVICES DEEMED ABSOLUTELY NECESSARY BY THE10.
ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED.9.
CONSTRUCTION.
RESIDENT ENGINEER OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING NEW
ALL DIMENSIONS ARE FROM FINISHED WALL TO FINISHED WALL, UNLESS OTHERWISE NOTED. NOTIFY8.
ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.
PROVIDE AND INSTALL ALL MANUFACTURED ITEMS, MATERIALS AND EQUIPMENT IN STRICT7.
IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL CODES AND REGULATIONS.
UNSATISFACTORY MATERIALS MUST BE REMOVED FROM THE PROJECT PROPERTY AND DISPOSED OF
LAWFULLY REMOVED ON A REGULAR BASIS. ALL WASTE, DEBRIS, UNUSED MATERIALS AND OTHER
THE WORK AREA IS TO BE KEPT CLEAN AND ORDERLY AT ALL TIMES. REFUSE AND DEBRIS SHALL BE6.
SCOPE OF THE CONTRACT DOCUMENTS.
FEES AND PERMITS REQUIRED AND ASSOCIATED WITH ALL PHASES OF THE WORK AND WITHIN THE
CODES, ORDINANCES, AND REGULATIONS. CONTRACTOR WILL OBTAIN AND BE RESPONSIBLE FOR ALL
ALL WORK PERFORMED BY THE CONTRACTOR SHALL BE DONE IN ACCORDANCE WITH APPLICABLE5.
SHALL BE FURNISHED.
THE GREATER QUANTITY AND THE HIGHER QUALITY (AS DETERMINED BY THE CONTRACTING OFFICER)
STRINGENT REQUIREMENTS (AS DETERMINED BY THE CONTRACTING OFFICER) SHALL GOVERN, AND
IN CASE OF CONFLICT BETWEEN OR WITHIN THE VARIOUS CONTRACT DOCUMENTS, THE MORE4.
AREAS OF CONSTRUCTION.
TENANTS AND GENERAL PUBLIC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE THE
BARRICADES, DANGER SIGNALS AND SIGNS IN AREAS OF WORK FOR PROTECTION AND SAFETY OF
NOT BLOCK EXISTS. PROVIDE, ERECT AND MAINTAIN BARRICADES, DANGER SIGNALS AND MAINTAIN
MAINTAIN ALL BUILDING LIFE SAFETY, FIRE PROTECTION AND SECURITY SYSTEMS AT ALL TIMES. DO3.
DURING CONSTRUCTION.
OF THE PROJECT SITE TO EMERGENCY AND SECURITY VEHICLES AT ALL TIMES AND WITHOUT DELAY
AND HAUL ROUTES IN A MANNER THAT ALLOWS UNOBSTRUCTED EMERGENCY ACCESS TO ALL AREAS
CONSTRUCTION PHASES OF THIS PROJECT, IN ADDITION, THE CONTRACTOR MUST MAINTAIN ACCESS
RESIDENT ENGINEER. LOCAL TRAFFIC ACCESS SHALL BE MAINTAINED DURING THE DEMOLITION AND
THE CONTRACTOR SHALL VERIFY AND COORDINATE ALL SITE AND BUILDING ACCESS WITH THE2.
PROBLEM RESOLUTION WITHOUT DELAYING THE WORK.
AND DRAWINGS PRIOR TO PROCEEDING WITH ANY PORTION OF THE WORK. ALLOW TIME FOR
BUILDING CONDITIONS. NOTIFY RESIDENT ENGINEER OF ANY CONFLICTS BETWEEN FIELD CONDITIONS
THE CONTRACTOR SHALL VERIFY AND COORDINATE THE SCOPE OF WORK WITH EXISTING SITE AND1.
EXISTING WALLS TO PROVIDE A SMOOTH AND FLUSH TRANSITION.
PREP EXISTING WALLS TO RECEIVE NEW FINISHES AS REQUIRED AND ALIGN ALL NEW WALLS TO6.
WORK.
ITEMS SALVAGED FOR RE-USE SHALL BE CLEANED, STORED AND RE-INSTALLED AS REQUIRED BY NEW5.
BROUGHT IMMEDIATELY TO THE RESIDENT ENGINEER ATTENTION.
ANY EVIDENCE OF HAZARDOUS MATERIALS (I.E ACM'S) PRIOR TO OR DURING CONSTRUCTION SHALL BE4.
DEMOLITION.
NOTIFY RESIDENT ENGINEER OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING
DEMOLITION REQUIRED TO ACCOMMODATE NEW WORK. REFER TO NEW CONSTRUCTION PLANS.
ALL DIMENSION ON DEMOLITION PLANS ARE FOR ROUGH OPENINGS TO DETERMINE THE EXTENT OF3.
THE OWNER.
NEW" CONDITIONED WILL MATCH EXISTING ADJACENT CONSTRUCTION AT NO ADDITIONAL COST TO
ACTIVITIES. ANY AREA DAMAGED AND NOT INDICATED TO BE REMOVED WILL BE REPAIRED TO "LIKE
PROTECT ALL EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE DURING CONSTRUCTION2.
THE OWNER OR DISCARDED.
COORDINATE WITH RESIDENT ENGINEER ALL ITEMS THAT ARE TO BE REMOVED AND RETURNED TO1.
GENERAL DEMOLITION NOTES:
cak-1701251-g008
2023-09-14T12:54:09-0500
DOUGLAS E WEAVER
2022-09-20T17:04:59-0500
RONALD M HUBRICH
MECHANICAL COVER SHEET
AK
UR
CAK-1701251-M002
-m lo tt e
MECHANICAL GENERAL NOTES MECHANICAL DEMOLITION NOTES
ANY AND ALL UTILITY/SYSTEM SHUTDOWNS.
THE RESIDENT ENGINEER, IN WRITING, 10 WORKING DAYS IN ADVANCE OF
COORDINATE WITH SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY AND 4.
RESIDENT ENGINEER PRIOR TO PROCEEDING WITH DEMOLITION.
BUILDING, THE SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY THE
INTEGRITY OF THE WHERE DEMOLITION WOULD AFFECT THE STRUCTURAL 3.
DAMAGE ADJOINING SURFACES OR EQUIPMENT INDICATED TO REMAIN.
MANNER THAT WILL NOT DEMOLITION SHALL BE PERFORMED IN SUCH A 2.
WORK.
REPORTED TO THE RESIDENT ENGINEER PRIOR TO STARTING DEMOLITION
CONSTRUCTION DOCUMENTS AND VERIFIED FIELD CONDITIONS SHALL BE
ROUTING OF EXISTING PIPING, ETC. ANY DISCREPANCIES BETWEEN THE
SIZES AND ROUTING OF EXISTING DUCTWORK, THE EXACT SIZES AND
SHALL VERIFY THE CONDITION OF ALL EXISTING EQUIPMENT, THE EXACT
SUBCONTRACTOR/CONTRACTOR BEFORE DEMOLITION WORK BEGINS THE 1.
ALL WORK SHALL MEET THE REQUIREMENTS OF THE 2017 OHIO MECHANICAL AND PLUMBING CODES.19.
SHALL BE PROVIDED TO THE ENGINEER OF RECORD FOR REVIEW.
SYSTEMS WITHIN THE SCOPE OF WORK. UPON COMPLETION OF WORK, A WRITTEN TEST & BALANCE AND OPERATION OF CONTROLS REPORT
AND BALANCE ALL MECHANICAL UPON COMPLETION OF WORK AN INDEPENDENT AND CERTIFIED TEST & BALANCE COMPANY SHALL TEST 18.
MECHANICAL SYSTEMS.INSTALL ALL BALANCING DEVICES NEEDED TO ACHIEVE PROPER ADJUSTING AND BALANCING OF 17.
DUCTWORK AND PIPING SHALL NOT RUN OVER ELECTRIC PANELS OR ELECTRIC EQUIPMENT.16.
ACCEPTANCE.UNLESS OTHERWISE NOTED, GUARANTEE ALL PARTS AND LABOR FOR ONE YEAR FROM DATE OF FINAL 15.
THIS SHALL INCLUDE PROVIDING SUFFICIENT SPACE TO MEET ALL OTHER TRADE CLEARANCE REQUIREMENTS.
INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, PLUMBING, FIRE PROTECTION, TELECOM, STRUCTURAL, CIVIL, AND GENERAL ARCHITECTURE.
WORK WITH THAT OF ALL OTHER TRADES IT SHALL BE THE RESPONSIBILITY OF THIS SUBCONTRACTOR/CONTRACTOR TO COORDINATE THEIR 14.
OTHERWISE, THE REUSE OF EXISTING DEVICES, MATERIALS, EQUIPMENT AND ASSOCIATED COMPONENTS AND ACCESSORIES IS PROHIBITED.
BE FIRST QUALITY. UNLESS INDICATED ALL EQUIPMENT, DUCTWORK, DEVICES, DAMPERS, CONTROLS, VALVES, PIPING, INSULATION, ETC SHALL 13.
CONTRACT DOCUMENTS SHALL BE IDENTIFIED AND BROUGHT THE RESIDENT ENGINEER'S ATTENTION PRIOR TO COMMENCING WORK.
THE CONTRACT DOCUMENTS PRIOR TO STARTING CONSTRUCTION. ANY DISCREPANCIES NOTED BETWEEN EQUIPMENT VENDOR PLANS AND
DRAWINGS AND COORDINATE THESE PLANS WITH THIS SUBCONTRACTOR/CONTRACTOR SHALL OBTAIN A FULL SET OF ALL EQUIPMENT VENDOR 12.
STARTING WORK.
DOCUMENTS AND MANUFACTURER'S REQUIREMENTS, THIS SUBCONTRACTOR/CONTRACTOR SHALL NOTIFY THE RESIDENT ENGINEER PRIOR TO
WORK SHALL ADHERE TO THE MANUFACTURERS' RECOMMENDATIONS/REQUIREMENTS. IF A CONFLICT EXISTS BETWEEN THE DESIGN
DOCUMENTS/REQUIREMENTS PRIOR TO STARTING WORK. ALL REVIEW ALL APPLICABLE MANUFACTURERS' INSTALLATION AND MAINTENANCE 11.
SUBMIT LITERATURE FOR ALL EQUIPMENT AND MATERIALS TO THE ENGINEER OF RECORD FOR APPROVAL.
FOR PERFORMANCE AND MATERIALS. MANUFACTURER'S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY 10.
A COMPLETE INSTALLATION.FURNISH ANY MISCELLANEOUS ITEMS NORMALLY USED, SPECIFICALLY MENTIONED OR NOT, TO RENDER 9.
APPROVAL.
STRUCTURAL ENGINEER'S REVIEW AND STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY MANNER WITHOUT A 8.
VERIFY SIZES, LOCATIONS, INVERTS AND ELEVATIONS PRIOR TO RUNNING ANY DUCTWORK/PIPING.7.
ACCEPTANCE.
DISCREPANCIES BETWEEN THE DELIVERY AND CONSTRUCTION DOCUMENTS SHALL BE REPORTED TO RESIDENT ENGINEER PRIOR TO
PRIOR TO ACCEPTING DELIVERY. ANY SUBCONTRACTOR/CONTRACTOR SHALL FIELD INSPECT ALL GOVERNMENT FURNISHED MATERIALS 6.
OTHER TRADES.
SHALL INCLUDE, BUT NOT BE LIMITED TO, OFFSETTING EXISTING PIPING AND MODIFICATIONS REQUIRED FOR COORDINATION WITH ALL
NOT SHOWN ON DRAWINGS. MAKE ALL NECESSARY MODIFICATIONS TO EXISTING CONDITIONS TO PERFORM WORK OF THIS SECTION. THIS
LOCATIONS SHOWN ON DRAWINGS IS GUARANTEED. DETERMINE EXACT LOCATIONS OF EXISTING SYSTEMS/UTILITIES IN FIELD, WHETHER OR
NEITHER ACCURACY NOR COMPLETION OF ALL EXISTING CONDITIONS SHOWN ARE TAKEN FROM EXISTING DRAWINGS AND FIELD SURVEYS. 5.
THE WORK INVOLVED.
IN VIOLATION SHALL BE BROUGHT TO THE ATTENTION OF THE RESIDENT ENGINEER AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF
SHOWN ON THE DRAWINGS WHICH IS NO WORK SHALL BE INSTALLED IN VIOLATION OF ANY GOVERNING STANDARDS AND CODES. ANY WORK 4.
REGULATIONS. IN CASE OF DIFFERENCES THE MOST STRINGENT SHALL GOVERN.
AND LOCAL CODES, RULES AND ALL MECHANICAL WORK SHALL BE IN ACCORDANCE WITH FAA STANDARDS AND ALL APPLICABLE STATE 3.
GETTING THE EQUIPMENT INTO PLACE, AND BECOME THOROUGHLY FAMILIAR WITH ALL OF THE REQUIREMENTS OF THE CONTRACT.
WORK. DETERMINE, IN ADVANCE, THE METHODS OF INSTALLING AND CONNECTING THE APPARATUS, THE MEANS TO BE PROVIDED FOR
THE PREMISES AND ANY EXISTING BEFORE SUBMITTING A BID CAREFULLY STUDY THE CONSTRUCTION DOCUMENTS. CAREFULLY EXAMINE 2.
NOT SCALE THESE DRAWINGS.
MECHANICAL SYSTEM COMPONENTS. DO THESE DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO DEPICT THE GENERAL LOCATION OF 1.
MECHANICAL LEGEND
POINT OF CONNECTION (POC)
POINT OF DISCONNECT (POD)
THERMOSTAT
CONTROLLER
HUMIDISTAT
SA
8"Ø
FLEX DUCT
MANUAL VOLUME DAMPER
2'x2' SUPPLY DIFFUSER
2'x2' RETURN GRILLE
ROOF ABOVE
SUPPLY DUCT UP TO FLOOR ABOVE/THRU
ROOF ABOVE
RETURN DUCT UP TO FLOOR ABOVE/THRU
45 DEGREE ENTRY
EXISTING TO REMAIN
EXISTING TO BE REMOVED
REGISTER/GRILLE: DEVICE TYPE/AIRFLOW/OPENING SIZE
DIFFUSER: DEVICE TYPE/AIRFLOW/NECK SIZE
FLEX DUCT MAX. 6' - 0"
MATCH NECK SIZE
FLEX DUCT SIZE SHALL
AIR DEVICE SCHEDULE
SYMBOLS TYPE MATERIAL FINISH
S-1 SUPPLY DIFFUSER STEEL WHITE
1,2,3
& MODEL #
MANUFACTURER
SIZE
R-1 STEEL WHITE24x24
CEILING MOUNT3.
NC VALUE SHALL NOT EXCEED 30.2.
4-WAY ADJUSTABLE1.
RETURN GRILLE
PRICE #SCD
PRICE #PDDR
24X24
2,3
PROJECT DESIGN CONDITIONS
COOLING PER ASHRAE 0.4%
DRY BULB WET BULB ASHRAE 99.6%
HEATING PER
75 DEG F
COOLING HEATING
DESIGN SETPOINTS
72.6 DEG F 3.1 DEG F 70 DEG F88.6 DEG FCANTON, OH
(SIDE OF DUCT CONNECTION)
TYPICAL DIFFUSER CONNECTION
NOT TO SCALEM002
CEILING DIFFUSERCEILING
HAND DAMPER
SILICONE SEALER
DRAW BAND WITH
SUPPLY DUCT
COLLAR
DAMPER
BLADE
OPPOSED
RTU AIR BALANCE TABLE
EXISTING ROOM
(SPACE BY SPACE) AND OUTSIDE AIR FLOWS AND PROVIDE A REPORT TO PARSONS FOR REVIEW.
SURVEY EXISTING AIRSIDE SYSTEM PRIOR TO CONSTRUCTION, RECORD EXISTING SUPPLY AIR (SPACE BY SPACE), RETURN AIR5.
RELIEF DEVICES AS NEEDED TO PROVIDE A FULLY FUNCTIONAL SYSTEM.
FIELD CONFIRM ROOFTOP UNIT OUSTIDE AIR INTAKE AND EXTERIOR RELIEF DAMPER ARE FUNCTIONAL. REPAIR INTAKE AND4.
REVISED MINIMUM OUTSIDE AIRFLOW.
UTILIZE OUTSIDE AIR INTAKE AT ROOFTOP UNIT AND EXTERIOR RELIEF DAMPER IN RETURN AIR DUCTWORK TO ACCOMODATE3.
SUBCONTRACTOR SHALL ADJUST EXISTING ROOFTOP UNIT TO ACCOMODATE REVISED AIRFLOWS.2.
EXISTING UNIT AIRFLOWS ARE BASED ON EXISTING CONDITION DRAWINGS.1.
NOTES:
LOCKER ROOM
TOTAL
EXISTING AIRFLOW (CFM)
RETURN
2,200
3,200
SUPPLY
2,200
3,200
EXHAUST
MIN OUTSIDE AIR
NEW ROOM
QUIET ROOM
MIN OUTSIDE AIR
EXHAUST
RETURN
1,500
2,500
SUPPLY
1,500
2,500
REVISED AIRFLOW (CFM)
RECTANGLE TO ROUND TRANSITION
ECCENTRIC TRANSITION
LINEAR RETURN GRILLE
LINEAR SUPPLY DIFFUSER
TOTAL
cak-1701251-m002
2023-09-14T12:55:18-0500
DOUGLAS E WEAVER
2022-09-20T17:06:21-0500
RONALD M HUBRICH
DEMO & NEW CONSTRUCTION
MECHANICAL PARTIAL SIXTH FLOOR PLAN -
CAK-1701251-M003
lo tt e
BREAKROOM
READY/BREAK TOILET
R-1
12"Ø
S-1
14"Ø
(TYP)
6"
8"
14x10 14"
14x10
6"Ø
6"Ø
14"Ø
(TYP.6)
12"Ø
14"
10"Ø (TYP)
DIFFUSER (TYP)
(ETBR) 10" CLG
DIFFUSER (TYP.)
(ETBR) 8" CLG
T T
ETR
X
8"Ø (ETR)
6"Ø (ETR)
18X14 (UP)
18X14 (UP)18X14 (UP)
18X14 (UP)
MECHANICAL PARTIAL SIXTH FLOOR PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"M003
1 MECHANICAL PARTIAL SIXTH FLOOR PLAN - NEW WORK
SCALE: 1/4" = 1'-0"M003
K
SHEET NOTES
PARSONS HAS PROVIDED A LOAD CALCULATION TO THE FAA FOR RTU SIZING.
IN A SEPERATE FUTURE PROJECT, THE FAA WILL BE REPLACING THE RTU.
AS PART OF THIS PROJECT THE EXISTING ROOFTOP UNIT IS TO REMAIN.11.
INSTALL MANUAL VOLUME DAMPER AND REBALANCE THE AIRFLOW. 10.
AIRFLOW. TIE IN NEW 12" FLEX DUCT TO THE RETURN MAIN.
INSTALL NEW RETURN DIFFUSER IN THE EXISTING CEILING GRID. REBALANCE THE9.
AIRFLOW. TIE INTO EXISTING FLEX CONNECTION.
INSTALL NEW RETURN DIFFUSER IN THE EXISTING CEILING GRID. REBALANCE THE8.
ON EACH TAKE OFF.
AIRFLOW. TIE INTO EXISTING FLEX CONNECTION. INSTALL MANUAL VOLUME DAMPER
INSTALL NEW SUPPLY DIFFUSER IN THE EXISTING CEILING GRID. REBALANCE THE7.
SEAL THE OPENING ON THE MAIN DUCT.
DEMOLISH EXISTING RETURN DIFFUSER, FLEXIBLE DUCT, AND ASSOCIATED BRANCH.6.
SEAL THE OPENING ON THE MAIN DUCT.
DEMOLISH EXISTING SUPPLY DIFFUSER, FLEXIBLE DUCT, AND ASSOCIATED BRANCH.5.
ON THE SLAB AS REQUIRED TO MATCH EXISTING.
WATER PIPING DOWN TO LEVEL 5 AND CAPP. PATCH THE EXISTING PENETRATIONS
DEMOLISH EXISTING BASEBOARD HEATER. DISCONNECT AND DEMOLISH THE HOT4.
DEMOLISH EXISTING RETURN DIFFUSER AND FLEXIBLE DUCT. 3.
DISCONNECT AND DEMOLISH EXISTING RETURN GRILLE. 2.
DISCONNECT AND DEMOLISH EXISTING SUPPLY DIFFUSER. 1.
NEW CONSTRUCTION LEGEND
CONNECT TO EXISTING
DEMOLITION LEGEND
DEMO TO THIS POINT
cak-1701251-m003
2023-09-14T12:55:35-0500
DOUGLAS E WEAVER
2022-09-20T17:06:37-0500
RONALD M HUBRICH
PLUMBING AND FIRE PROTECTION COVER SHEET
CAK-1701251-P001
-p
:0 lo tt e
FIRE PROTECTION/PLUMBING GENERAL NOTES
MODIFYING HAZARD OCCUPANCY, DESIGN DENSITY, AND AREA OF PROTECTIOND.
MODIFYING EXISTING MAIN SPRINKLER SUPPLY AND BRANCH PIPE CONFIGURATIONC.
MODIFYING EXISTING PIPE SIZESB.
ADDING SQUARE FOOTAGE TO THE SYSTEM'S PROTECTED AREAA.
NOT AFFECT THE EXISTING SYSTEM WITH ANY OF THE FOLLOWING CHANGES.
HYDRAULIC CALCULATIONS HAVE NOT BEEN PROVIDED FOR THIS PROJECT AS ITS ASSOCIATED SCOPE OF WORK WILL 34.
INSTALL HANGERS AND SUPPORTS FOR SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13.33.
SPACES SHALL BE PROTECTED WITH STANDARD RESPONSE SPRINKLER HEADS.
ALL LIGHT HAZARD SPACES SHALL BE PROTECTED WITH QUICK RESPONSE SPRINKLER HEADS. ALL ORDINARY HAZARD 32.
CENTER ALL SPRINKLER HEADS IN CEILING TILES.31.
THE SYSTEM SHALL…