This document provides an amendment to a solicitation for replacing air handling units at an air traffic control center in Palmdale, California. The Federal Aviation Administration is seeking to replace two air handling units in room 110A of the Los Angeles Air Route Traffic Control Center. The project is set aside exclusively for small businesses with a NAICS code of 238290 and size standard of $22 million. A mandatory site visit will be held on January 8, 2024 and all questions must be submitted by January 9th. An amendment answering questions will be issued on January 11th. Offerors must register in the System for Award Management and faxed submissions will not be accepted. The solicitation requires adherence to requirements in sections L and M of the solicitation document. This amendment provides clarification on drawings and answers questions on ductwork, valve sizing, and condensate drain routing.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
5. PROJECT NO. (If applicable)2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ.NO.
PAGE OF PAGES
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6)
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
CODE
9A. AMENDMENT OF SOLICITATION NO.
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
Items 8 and 15, and returning is extended, is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required.)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
(x) A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO THE AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14.
E. IMPORTANT: Contractor is not, is required to sign this document and return
ORDER NO. IN ITEM 10A.
1 1
0004 01/23/2024
FEDERAL AVIATION ADMINISTRATION
AAQ-500 - REGIONAL ACQUISITIONS
1701 COLUMBIA AVENUE
COLLEGE PARK GA 30337
AAQ510ATL-AFN
x
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
separate letter or telegram which includes a reference to the solicitation and amendment number. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By ___________ 1 x x
697DCK-24-R-00113
1 copies to the issuing office.
12/27/2023
(x)
Amendment 0004 is being issued to incorporate the below Questions and Answers including drawing clarifications into the Request For Offer (RFO).
The RFO close date remains Wednesday, January 31, 2024, by 5:00pm EST.
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. CONTRACT AUTHORITY 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
Jacqueline T. Jones
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
Question 1) Detail A on sheet M246 Shows Supply ductwork to the new AHU-4, however the drawing do not show supply air. Please confirm if SA is required for this project.
Response 1) The above ceiling ductwork depicted for the typical AHU section on M246 is the fresh air supply above the return air plenum. See picture below:
I believe the question being asked is if the fresh air supply duct is to be replaced or reworked. The answer is no the fresh air supply duct does not need to be replaced or reworked if the return air plenum that goes above the T-Bar ceiling is installed with in 2 inches of the duct per the drawing above. RA Plenum height should be coordinated with fresh air return duct. Fresh air return duct may need to be reworked for new AHU if it does not fit or work with new Return Air Plenum, field verify when ordering new unit with return air plenum. On M242 AHU Note 6 states: “Provide with Factory Lined return Air Plenum Mounted on top of the unit. Return Air Plenum to be provided with standard and optional side grilles. Paint to match.”
Question 2) Sheet M244 calls for new ISO valves. However, sizing is not provided for HHW valves. Please confirm of the new valves.
Response 2) The existing hot water piping is depicted as 1 inch. See drawing M243. The isolation valves for hot water piping generally match pipe size being 1 inch, contractor to field verify. General note 3 on M244 states: “Physical sizes and locations of equipment and associated piping are approximate, verify sizes and dimensions affecting work.” This means contractor to field verify the size, also see General Note E and I on M242.
Question 3) Detail #4 on 246 calls for new CD drains from AHUs. However, sheet M244 does not show the CD routing and size. Please confirm where CD drains will be routing to and provide update plans if possible.
Response 3) New AHU Units are different from existing AHU Unit. Per Detail 4/M246 contractor shall connect condensate drain to existing condensate drain line. General note 3 on M244 states: “Physical sizes and locations of equipment and associated piping are approximate, verify sizes and dimensions affecting work.” This means contractor to field verify the location, placement and tie in point that make sense for condensate drain, also see General Note E on I on M242. Detail 3/M246 specifies the condensate drain detail that needs to come off the new AHU before it is connected to the existing condensate drain. Coordinate with COR the placement and connection point of the new condensate drain with the existing condensate drain.
| 697DCK-24-R-00113_Amendment 0004 |
| Q and A w-Drawings Amend 0004 |