Questions and Responses_March 23 2022.pdf
PDF 102 KB Posted
- Attached to
- Farmingdale HVAC Replacement Federal contract opportunity
- Solicitation number
- 697DCK-22-R-00045
About this file
This document contains questions and responses related to a solicitation for HVAC replacement services at the Farmingdale Republic Airport in Farmingdale, New York. The Federal Aviation Administration is seeking to replace the HVAC system at the Airport Traffic Control Tower facility and base building. Key details include: Johnson Controls is the incumbent controls vendor and NY Fire Service Inc. handles fire alarm panel maintenance. A site visit was scheduled for March 15th and all questions must be received by March 22nd. Proposals are due by March 29th at 5:00 PM ET and must include all required documents outlined in Sections L and M. The contract will be a small business set-aside awarded as a single award in accordance with FAA acquisition regulations. The Davis-Bacon Act and attached wage determination apply.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 697DCK-22-R-00045 Amendment 0001.pdf | ||
| Questions and Responses_March 29 2022.pdf | ||
| Site Visit Attendee Log_Redacted.pdf | ||
| Attachment J-1a FRG HVAC Drawings.pdf | ||
| Attachment J-1a FRG HVAC Drawings.pdf | ||
| 697DCK-22-R-00045.pdf | ||
| Attachment J-1a FRG HVAC Drawings.pdf | ||
| Attachment J-1 FRG HVAC Specifications.pdf | ||
| PAST PERFORMANCE QUESTIONNAIRE.pdf | ||
| Attachment J-2 Wage Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
QUESTIONS & RESPONES
697DCK‐22‐R‐00045
March 23, 2022
No. Question Response
Can you please advise what the weight of the existing rooftop unit is?
As per the data furnished from the manufacturer, the unit is approximately
8666 LBS.
Who is the current front‐end vendor in the existing building?
Johnson Controls is the controls vendor. The Johnson Controls Point of Contact is Chris who can be reached at 866‐854‐4724.
Who is the current fire alarm vendor?
Fire Alarm Panel Maintenance is handled by NY Fire Service Inc., 1230 Port Washington Blvd, Port Washington, NY 11050, 516‐883‐3900.
Who holds the roofing warranty? See General Note 3, D003 for roofer.
Confirm that no bid bond/security is required to be submitted with our bid package for the Farmingdale Republic Airport HVAC Project.
A bid guarantee is not required for this procurement.
Will temporary air conditioning be required? What method/equipment should be used?
Temporary air conditioning will not be required. See demolition staging notes on D003.
What length of run should be carried for the electrical wiring for the ionization system to panel NPA Circuit #42?
Load is 10 watt as per the cut sheet.
Approximately 350 ft for electrical wiring.
This project is a negotiated bid and not a sealed bid as per section #2 on the “Solicitation, Offer and
Award” form. Can you confirm if this indicates that bids should be submitted electronically?
Offerors proposals must be submitted electronically to Katie Fogle at katherine.fogle@faa.gov.
File details come from the government source that posted it. Updated .