697DCK-21-R-00041 Amendment 0005.pdf
PDF 326 KB Posted
- Solicitation number
- 697DCK-21-R-00041
About this file
This solicitation requests proposals for a new building automation system project at the Northern California TRACON facility. Offerors must design and construct a new BACnet building automation system, replacing the existing controls infrastructure. Proposals are due by May 5, 2021. The project involves replacing control panels, sensors, switches and devices, low voltage wiring, air and water meters, and control valves. The new system must provide operator workstations, a laptop, graphics displays, and integrate with the existing fire alarm and notification systems. Site visits are scheduled for April 13-14, 2021, and questions must be submitted by April 23rd. The awarded contractor will be responsible for testing, training, and third party commissioning support.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
5. PROJECT NO. (If applicable)2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ.NO.
PAGE OF PAGES
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6)
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
CODE
9A. AMENDMENT OF SOLICITATION NO.
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
Items 8 and 15, and returning is extended, is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required.)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
(x) A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO THE AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14.
E. IMPORTANT: Contractor is not, is required to sign this document and return
ORDER NO. IN ITEM 10A.
1 10
0005 05/04/2021
FEDERAL AVIATION ADMINISTRATION
AAQ-500 - REGIONAL ACQUISITIONS
1701 COLUMBIA AVENUE
COLLEGE PARK GA 30337
AAQ510ATL-AFN
x
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
separate letter or telegram which includes a reference to the solicitation and amendment number. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By ___________ x x
697DCK-21-R-00041
copies to the issuing office.
03/17/2021
(x)
Amendment 0005 is issued for the following reasons:
1. Respond to questions.
2. Add K SECTION 10270 - ACCESS FLOORING and APPENDIX L - OPS Room VAV Pictures to Section
J.
All other terms and conditions remain unchanged
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. CONTRACT AUTHORITY 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
Katherine Fogle
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
Amendment 0005, 697DCK-21-R-00041
1. Question (Amendment 0001): Response to Question 3 states the following:
Offerors must submit resumes for the Project Manager and the Project Superintendent and submit SF330s for the Designer of Record and Controls Engineer/ Programmer.
Response: Offerors are only required to complete Section E: RESUMES OF KEY PERSONNEL PROPOSED FOR THIS CONTRACT of the SF330 for the Key Personnel identified in Factor 5.
2. Question: Please confirm this is a completely stand-alone system.
Response: The system is a stand-alone system.
3. Question: Please confirm if there may be ATO/accreditation concerns that Offerors should be aware of.
Response: There are no accreditation concerns. System is dedicated to the facility only and will not interact with any other systems.
4. Question: Please confirm the FAA will not require insurance policies to be provided and the Certificate of insurance satisfies the requirement.
Response: Per Section M Volume I Offeror’s must submit their Certificate of Liability Insurance.
5. Question (M.2 Volume I & II): Will the original Bid Bond need to be submitted to a physical address or is it acceptable to include a digital copy in the emailed proposal?
Response: Offerors must include their bid bond electronically with their proposal.
6. Question (Appendix-E-1.1.J Fire Smoke rated HVAC Control System): Appendix-B and Site visit confirms that multiple Fire-Smoke Dampers are controlled via the existing CSI control system. Per NFPA-72 & NFPA-92 code, if these Fire Smoke dampers are controlled via the HVAC Control system, then these systems should be UUKL-864 rated.
However, the specifications section 23 09 23.1.1.J requires the EMCS to be UL-916 certified, which does not meet the project requirements. Please confirm that the proposed system should also comply to UL-864/UUKL and the UL-916 certification. If a UL- 864/UUKL EMCS is not required as part of this replacement project, then please confirm that all Fire Smoke Dampers, Smoke Detectors, Mechanical Fans and the related direct interlocking of Fire Life Safety System (FLSS) components shall not be connected to the new proposed HVAC controls system. Please also confirm that these FLSS components shall be connected / intergated to the Notifier Fire Alarm System and shall be independent of the EMCS.
Response: There is no smoke control system, as defined in NFPA 92, in the facility. The fire/smoke dampers are a passive means of maintaining fire/smoke barriers; therefore, the new EMCS panel does not need to have the UUKL listing.
7. Question (Appendix-E-1.1.J Fire Smoke rated HVAC Control System): For UUKL-
864 rated systems that operate Fire Smoke dampers and related Air Handling Units, then a Firemans Smoke Control Station (FSCS), similar to the picture below is provided in the main entrance area / lobby of the facility. This assists the Firemen control the flow of air but allowing them to manually override operation of individual Air Handling Units and control the Fire Smoke Dampers to meet the project control sequences in emergency cases. Please confirm that a similar customized panel is required as part of this project. If a UL-864/UUKL EMCS is not required as part of this replacement project, then please confirm that all Fire Smoke Dampers, Smoke Detectors, Mechanical Fans and the related direct interlocking of Fire Life Safety System (FLSS) components shall not be connected to the new proposed HVAC controls system. Please also confirm that these FLSS components shall be connected / integrated to the Notifier Fire Alarm System and shall be independent of the proposed EMCS. Please note that this FSCS display / control panel shall still be required for Smoke control operations.
Response: There is no smoke control system in the facility; therefore a FSCS is not required. Non-UUKL EMCS panels are permitted to control fire/smoke dampers as long as the dampers are not associated with a smoke control system.
8. Question (Appendix-E-1.1.J Fire Smoke rated HVAC Control System): Please confirm that the existing Notifier Fire Alarm System is not being upgraded and there is a requirement to integrate this Fire Alarm System to the new proposed EMCS (which shall be UL-864/UUKL & UL-916 rated) to shut down the associated equipment when a fire / smoke alarm is detected in this respective zone / area served by the Mechanical equipment.
Response: There are no immediate plans for a fire alarm panel upgrade. The current interface between the CSI panel and the existing Notifier fire alarm control panel must be maintained with the new EMCS panel.
9. Question (M912 to M914 (Typical) Existing Control Equipment): If compatible with proposed replacement EMCS, please confirm that the following existing controls infrastructure can be utilized:
a. Control Panels and associated infrastructure - Terminals, Panduit, Transformers, Power supplies, Relays and Receptacles
b. Sensors, Switches, and Devices
c. Low Voltage Conduit and Control wire
d. Air Flow and Water Flow Meters / Stations
e. Refrigerant Leak Detection System
f. Fiber optic cables
g. Control Valves
h. Damper Actuators
i. Variable Frequency drives
Response:
a. Control Panels and associated infrastructure - Panel enclosures can be reused, but everything inside (terminals, panduit, transformers, power supplies, relays and receptacles) must be new.
b. Sensors, Switches, and Devices - Space temperature and humidity sensors will be new, but switches and devices can be reused.
c. Low Voltage Conduit and Control wire - Low voltage conduit and control wire can be reused if compatible.
d. Air Flow and Water Flow Meters / Stations - Air flow and water flow meters can be reused if compatible.
e. Refrigerant Leak Detection System - Refrigerant leak detection system can be reused
f. Fiber optic cables - fiber optic cables can be resued if compatible.
g. Control Valves - Existing valves may be reused as they are compatible with new control devices.
h. Damper Actuators - Existing actuators may be reused as they are compatible with new control devices.
i. Variable Frequency drives - Existing drives may be reused as they are compatible with new control devices.
10. Question (M912 Digital output override capability): Digital Output Overrides - For major equipment (AHU, CRAH's, Central Plant, EF's, etc.), please advise which of the below option is acceptable to achieve this functionality:
a. Existing Override switches or
b. Relays with override capability.
Response: Existing manual HOA switches to be integrated and reutilized. All other control boards to have integral manual HOA switches. It is the FAA's intent to keep current functionality.
11. Question (Appendix B): M908 is missing - Please forward copy of the same.
Response: Drawing M908 is provided in APPENDIX B - AS BUILT CONTROL DRAWINGS_Revised.
12. Question (Appendix B): Please advise if monitoring of Space Carbon Dioxide is required.
Response: Currently there is no Carbon Dioxide monitoring in the spaces and it is not required per Attachment J-1 Scope of Work.
13. Question (Appendix B): During site visit, few critical areas and equipment were discussed which will require access and cutover to be performed during after hours.
Please provide detailed list of the same.
Response: All areas with the exception of the administrative wing/common areas have redundancy. Contractors must keep units operational or provide temporary HVAC while working in the administrative and common areas and work must be scheduled on nights and weekends when the areas are not being utilized. All work in the "operations" areas will have to be done between 11pm-4am. The units are, AHU 101, 102, 201, 202, and 401.
14. Question (Appendix-J 1.1.1 Turnover & 3rd Party Commissioning): Please advise if this project will require the following on a Phased Building-by-Building basis or at the End of the project?
a. System Turnover with closeout package?
b. 3rd Party Commissioning?
Response: The contractor must perform functional testing and fill out "Authority to Operate" forms for each system prior to moving on to the next system during installation.
Both the system turnover with the closeout package and the 3rd party commissioning will be completed at the end of project.
15. Question (M902 Digital Paging System): Please confirm that Specter Digital Paging
System is not to be connected to the proposed new EMCS and also that remote alarm notification via pagers or phones is not required under this replacement project.
Response: Confirmed
16. Question (M915 Space T-Stats): Please confirm that Temperature Display with LCD panel is required for each Space T-Stat
Response: Existing space thermostats with LED display must be replaced with thermostats with LCD/LED displays.
17. Question (M915 Space T-Stats): Please confirm which T-stats need to be relocated to 48 inches to comply with ADA requirements. Of these, how many need to be mounted flush to the wall.
Response: All thermostats requiring accessibility must comply with ADA requirements.
Use As-Built plans to confirm number and locations.
18. Question (M902 Operations Room-301 ECMS Workstation): Please confirm that Operation Room-301 Energy Management System shall have a fully independent and functioning Graphics software package (with necessary Mechanical Equipment Graphics, Alarming, Trending & Scheduling capability) and a new Workstation that shall not be reliant on the new EMCS software installed on the EMCS Room-504 Workstation.
Response: Room 301, and 504 will require a fully functioning workstation. Laptop will also be required to be fully functioning. Room 511 will only require display only functionality.
19. Question (M902 Facilities / Engineers Room Dashboard Display Monitor and ECMS Workstation): Please confirm that the Engineers Officer shall have Dashboard Graphics and Alarming software package (with necessary Mechanical Equipment Graphics) and a new Workstation that shall be reliant on the new EMCS software installed on the EMCS Room-504 Workstation for Data and Graphics database. Please provide dimension details of the Dashboard and installation location for the Display Monitor and associated workstation.
Response: Room 301 and 504 will require a fully functioning workstation. Room 511 will only require display only functionality. Contractor to propose recommended size for room 511 dashboard. Size should be readable from all areas of room.
20. Question (M902 Guard / House & Visitors Area ECMS Workstation): Please confirm the Guard / House & Visitors Area shall have access to all ECMS Graphics and Alarming software packages and a new Workstation that shall be reliant on the EMCS software installed on the EMCS Room-504 Workstation for Data and Graphics database.
Please provide dimension details of the Monitor and exact installation location for the same.
Response: Guard House does not require workstation.
21. Question: Existing Automation System has Uninterrupted Power Supply (UPS) dedicated for each control panel. Please confirm that these need to be replaced with new UPSs that are capable of assisting Facilities in "scheduling Predictive Maintenance by providing Status of UPS connection, UPS Load and Battery Capacity" via communication interface to the proposed EMCS.
Response: The new UPS needs to provide status to new controls system.
22. Question (1.2.G.e Temporary Services): Please confirm Temporary Services are to be provided by Contractor will include self-sufficient trailer, with associated furniture, storage space, Portable Toilets, etc. and this is required regardless of home office.
Response: Refer to Amendment 0004 and Appendix I Section 01 50 00: Temporary Facilities and Controls.
23. Question: In light of RFP/scope questions clarified at the Site Survey last week, we respectfully request an extension of ten (10) days to incorporate those changes into our Technical Approach and Price Proposal.
Response: The proposal due date was extended to 17:00 PT on June 11, 2021 in Amendment 0004.
24. Question (Uninterrupted Power Supply for Terminal Units - VAV's, Fan Coil Units and Exhaust Fans): During the site visit, attendees were informed all existing HVAC Controllers & Control Panels are powered via Uninterrupted Power Supplies (UPS) installed. We noticed these were installed on all control panels for major equipment in the Environmental wing and Penthouse Area visited. Since attendees were unable to visit the Operations, Commons & Electronics wing, where most of the Terminal Units (like VAV's, Fan Coil Units, etc) are installed, please advise if UPS replacement is also required for all controllers installed on these Terminal Units.
Response: UPS replacement is required on all DDC Panels
25. Question: How long can individual VAV boxes be taken offline for controller changeover?
Response: FAA requires minimal impact to facility. The VAVs changeover duration must be kept to a minimum.
26. Question: For existing controllers and UPS units that are being removed, please confirm that the contractor will turn these items over to the FAA site team.
Response: The FAA reserves the right of first refusal for all C&D waste and materials
27. Question: Would the FAA like us to submit a full SF330 including past performances and corporate information, or is the requirement for a two completed SF330 Section E forms: one for the Designer of Record and one for the Controls Engineer?
Response: Offerors are only required to complete Section E: RESUMES OF KEY PERSONNEL PROPOSED FOR THIS CONTRACT of the SF330 for the Key Personnel identified in Factor 5.
28. Question: Please confirm the following operator workstation quantities: 3 Workstations, 1 Laptop.
Response: The FAA confirms 3 Workstations, 1 Laptop.
29. Question: Please confirm that the successful offeror must carry their own staging, and restroom facilities to be located within the security fence of the Tracon site but outside of the building itself.
Response: The FAA confirms the contractor must carry their own staging, and restroom facilities to be located within the security fence of the Tracon site but outside of the building itself.
30. Question: Please provide weight rating of the raised floor located in the control room so that we may select a man-lift that may be used in this location.
Response: Access flooring weight ratings can be found in APPENDIX K - SECTION 10270 - ACCESS FLOORING under section 1.3 Performance Requirements.
31. Question: Please confirm that the allowable work hours on site (to include survey, point to point, and system installation) are the following:
Operations Wing: between 23:00 and 04:00 Administration Wing and Environmental Wing: Between 17:00 and 09:00 Monday to Friday, or on weekends Outside of Operations, Administration, and Environmental Wings: Work may be performed during normal business hours Monday through Friday
Response: All work must be coordinated with the FAA via a transition plan. In general, the areas that are restricted are: Operations wing 23:00-4:00 and Commons and Admin wing/dining area will be restricted to 17:00-6:00 on weekdays.
32. Question: Please confirm whether the training setup, as shown on Appendix B, Drawing
M996 will also need to be replaced with an identical set up using the new Building Automation System.
Response: Training Setup will not need to be replaced with an identical setup. It is not a requirement of Attachment J-1 Scope of Work for a training setup.
33. Question: Is the VAV box network in conduit in the Operations, Administration and
Commons Wings? If so, what diameter is the conduit?
Response: VAV network is in conduit. Main run is 3/4" EMT. To boxes is 1/2" FMC.
In penthouse is 3/4" rigid conduit. Refer to APPENDIX L - OPS Room VAV Pictures” for samples of VAV wiring and conduit. Refer to FAA requirement 1217H for electrical requirements.
34. Question: Are we to assume these UPSs are to replace the existing UPSs already installed and shall be included in the project cost?
Response: Include the cost to replace and install the new UPSs in the project cost.
35. Question: Is it the intent of this project to replace these controllers with new controllers with onboard HOA switches and keep the existing remote HOA switches as well?
Response: The FAA's intent to keep current functionality of the controllers. The existing manual HOA switches are to be integrated and reutilized. All other control boards must have integral manual HOA switches.
36. Question: To ensure we are including all the latest point data, is it possible to obtain a copy of the INET database files from each of the existing active site controllers?
Response: The INET files cannot be released as an attachment to this solicitation.
37. Question: To ensure we are including all the latest point data, is it possible to obtain a copy of the INET database files from each of the existing active site controllers?
Response: The INET files cannot be released as an attachment to this solicitation.
38. Question: Assuming a single man‐lift maybe required (and or scaffolding) to access these VAV’s, is there anything else we need to include in our offering? ie: (furniture moving, static free plastic covering for equipment, etc…)
Response: It is contractor's responsibility to assess site conditions and propose the means and methods to keep work areas clean and ready for FAA’s use daily.
39. Question: It appears there are VAV’s in areas that are typically 24/7 operation where
BMS technicians are expected to work around air traffic controllers. Can these areas be defined and is productivity efficiency expected to be impacted in these areas?
Response: All areas with the exception of the administrative wing/common areas have redundancy. Contractors must keep units operational or provide temporary HVAC while working in the administrative and common areas and work must be scheduled on nights and weekends when the areas are not being utilized. All work in the "operations" areas will have to be done between 11pm-4am. The units are, AHU 101, 102, 201, 202, and 401.
40. Question: It is our understanding the FAA will hire a third party CXa (commissioning) contractor directly and our scope of work is to provide pre‐functional testing and support th CXa effort with a bundle of “Support Hours”. Please confirm this is an accurate understanding and if possible clarify the amount of anticipated hours.
Response: Third party commissioning agent will provide all forms and procedures to complete commissioning during design of project. Third party will also provide "Authority to Operate" (ATO) forms for functional testing that must be completed for each system prior to working on another system. The contractor must complete the ATO forms and assist the third party for final commissioning. The FAA cannot provide an estimation of hours.
41. Question: Please confirm the CXa will be providing all functional testing for the BMS contractor to perform prior to CXa commissioning effort AND demonstration to the CXa
/ FAA?
Response: The third party commissioning agent will provide all forms and procedures to complete commissioning during design of project. The rhird party will also provide "Authority to Operate" (ATO) forms for functional testing that must be completed for each system prior to working on another system.
42. Question (Appendix D 23 09 23‐25): Is it the responsibility of the Contractor to provide Test and Balance?
Response: It is the responsibility of the contractor to calibrate all sensors.
43. Question (Appendix I 01 50 00 – 2 / 2.1): This section appears to be extensive for a
(more than likely) single trade project where personal and meetings are unlikely to have as many participants as mentioned in this section. It is our experience that a contained and controlled yet methodical approach where there will be only enough manpower to retrofit a single system at any one time. Given this approach, is this section requirement left up to the contractor to provide adequate facilities for our personal only?
Response: The contractor is expected to provide facilities for their own personnel.
44. Question: Please indicate if existing pneumatic system is to be replaced or abandoned in place or reused. If it is going to be replaced, please provide the quantity of actuators that must be replaced and provide existing actuators model number. If actuators are to be replaced, please confirm that all transducers are located in the actuator and not in the BAS enclosure.
Response: It is the intent of the FAA to keep the existing pneumatic system. However, if contractor sees value in replacing the pneumatic system or if the pneumatic system is incompatible with new system, the contractor must include their technical approach and cost to install the new pneumatic system.
45. Question: Please indicate if software maintenance agreements are required for supervisory devices and server.
Response: No software will be installed that requires a software maintenance agreement to maintain functionality after the warranty period.
46. Question: Please provide drawings page M908.
Response: Drawing M908 is provided in APPENDIX B - AS BUILT CONTROL DRAWINGS_Revised.