This document is a product specification sheet for Allied Commercial's K-Series™ Packaged Electric Rooftop HVAC Units, covering 15 to 25 ton cooling capacity models. The units are ASHRAE 90.1 compliant, feature R-410A refrigerant, scroll compressors, and are available in standard efficiency configurations with multiple voltage options (208/230V, 460V, 575V). Key features include an Eco-Last™ coil system, thermal expansion valves, single zone VAV supply fans, optional electric heat (15-90 kW), and optional accessories like economizers, smoke detectors, and various roof curbs.
The specification details comprehensive technical information including electrical data, blower performance, unit dimensions, sound ratings, and weight specifications. Models range from 15 ton (KCC180S4M) to 25 ton (KCC300S4M), with net cooling capacities from 172,000 to 270,000 Btuh. The units offer flexible configuration options, including different blower motor horsepower, drive kits, and electrical configurations. Warranty coverage includes five years for compressors, three years for the Eco-Last™ coil system, and one year for other covered components. The document is part of a August 2023 product bulletin (No. 310991) that supersedes the June 2023 version.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| QandA Sheet 6973GH-25-Q-00094.pdf | ||
| Maintenance Schedule.pdf | ||
| SOW MAST Site C STT ASR HVAC Installation.pdf | ||
| 6973GH-25-Q-00094.pdf | ||
| Contractors Release Form DOT F 4220.4.doc | DOC document | |
| Offeror Organizational Experience Form.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KCC
K-Series™ Rooftop Units
Standard Efficiency - 60 Hz Bulletin No. 310991
August 2023 Supersedes June 2023
15 to 25 Tons Net Cooling Capacity − 172,000 to 270,000 Btuh
Optional Electric Heat - 15 to 90 kW
ASHRAE 90.1
COMPLIANT
K C C 240 S 4 M N 1 Y Brand/Family K = K-Series™
Unit Type C = Packaged Electric Cooling w/ optional Electric Heat
Major Design Sequence C = 3rd Generation
Nominal Cooling Capacity - Tons 180 = 15 Tons
210 = 17.5 Tons 240 = 20 Tons 300 = 25 Tons
Cooling Efficiency S = Standard Efficiency
Refrigerant Type 4 = R-410A
Factory Installed Electric Heat N = No Heat
Minor Design Sequence 1 = 1st Revision
Voltage Y = 208/230V-3 phase-60Hz G = 460V-3 phase-60Hz J = 575V-3 phase-60Hz
Blower Type M = Single Zone VAV Supply Fan, Belt Drive
KCC 15-25 TON ROOFTOP UNITS
PA C K A G E D E L E C T R I C / E L E C T R I C
MODEL NUMBER IDENTIFICATION
C O M M E R C I A L
P R O D U C T S P E C I F I C AT I O N S
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 2
FEATURE HIGHLIGHTS
1. Scroll Compressors
2. Thermal Expansion Valves
3. Filter/Driers
4. Eco-Last™ Coil System
5. Outdoor Coil Fan Motors
6. Cabinet Construction
7. Single Zone VAV
Air Volume Blower
8. Unit Control
9. Disconnect Switch (option)
10. Electric Heat (option)
11. Air Filters
12. Economizer (option)
13. Downflow Barometric Relief Dampers
(option)
14. Power Exhaust Fans (option)
CONTENTS
BB
CC
OO NN
MM LL
KK
JJ
IIHH
GG
FF
EE
DD
K-Series rooftop units are engineered with the right technologies and options to meet standard efficiency requirements while delivering reliable performance and year-round comfort.
Approvals And Warranty Blower Data Dimensions - Unit
- KCC180 | KCC210
- KCC240
- KCC300
- Optional Accessories
Electrical Accessories - Disconnects Electrical/Electric Heat Data
- 15 Ton
- 17.5 Ton
- 20 Ton
- 25 Ton
Electric Heat Capacities Features And Benefits Dehumidification System Option Dehumidification System Ratings Model Number Identification Optional Conventional Temperature Control Systems Options / Accessories Outdoor Sound Data Ratings Specifications Unit Clearances Weight Data
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 3
COOLING SYSTEM
• Designed to maximize sensible and latent cooling performance at design conditions
• System can operate from 45°F to 125°F without any additional controls
R-410A Refrigerant
• Non-chlorine based
• Ozone-friendly
Scroll Compressors
• Scroll compressors on all models for high performance, reliability, and quiet operation
• Resiliently mounted on rubber grommets for quiet operation
Compressor Crankcase Heaters
• Protects against refrigerant migration that can occur during low ambient operation or during extended off cycles
Thermal Expansion Valves Ensures optimal performance throughout the application range
• Removable element head
Filter/Driers
• High capacity filter/drier protects the system from dirt and moisture
High Pressure Switches
• Protects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow or loss of outdoor fan operation
BB
CC
DD
APPROVALS AND WARRANTY
Indoor Coil Freeze Protection
• Protects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow or low refrigerant charge
Condenser Coil - Eco-Last™ Coil System
• Lightweight, all aluminum brazed fin construction
• Constructed of three components
• A flat extrusion tube
• Fins in-between the flat extrusion tube
• Two refrigerant manifolds
Eco-Last™ Coil System Features:
• Improved heat transfer performance due to high primary surface area (flat tubes) versus secondary surface (fins)
• Smaller internal volume (reduced refrigerant charge)
• High durability
• All aluminum construction
• Fewer brazed joints
• Compact design
• Reduced unit weight
• Easy maintenance/cleaning
• Mounting brackets with rubber inserts secure coil to unit providing vibration dampening and corrosion protection
• Angled cabinet design protects coil from damage
EE
APPROVALS
• AHRI Standard 340/360 certified
• ETL and CSA listed
• CSA certified energy ratings
• Unit and components are ETL, NEC, and CEC bonded for grounding to meet safety standards for servicing
• All models are ASHRAE 90.1 energy efficiency compliant and meet or exceed requirements of Section 6.8
• All models meet DOE 2023 energy efficiency standards
• All models meet California Code of Regulations, Title 24 and ASHRAE 90.1 Section 6.4.3.10 requirements for staged airflow
• ISO 9001 Registered Manufacturing Quality System
WARRANTY
• Compressors - Limited five years
• Eco-Last™ Coil System - Limited three years
• Variable-Frequency Drive (VFD)- Limited five years
• High Performance Economizers (optional) - Limited five years
• All other covered components - Limited one year
FEATURES AND BENEFITS
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 4
COOLING SYSTEM (continued)
Evaporator Coil
• Copper tube construction
• Enhanced rippled-edge aluminum fins
• Flared shoulder tubing connections
• Silver soldered construction
• Factory leak tested
• Cross-row circuiting with rifled tubing
Antimicrobial Condensate Drain Pan
• Composite pan, sloped to meet drainage requirements of ASHRAE 62.1
• Antimicrobial additive resists growth of mold and mildew on drain pan, which improves indoor air quality and reduces drain line blockage
• Side or bottom drain connections
Outdoor Coil Fan Motors
• Thermal overload protected
• Totally enclosed
• Permanently lubricated ball bearings
• Shaft up
• Wire basket mount
Outdoor Coil Fans
• PVC coated fan guard furnished
Required Selections
Cooling Capacity
• Specify nominal cooling capacity
Options/Accessories
Factory Installed Conventional Fin/Tube Condenser Coil (replaces Eco- Last™ Coil System)
• Copper tube construction
• Enhanced rippled-edge aluminum fins
• Flared shoulder tubing connections
• Silver soldered construction NOTE - Required if Dehumidification System is ordered
(180, 210, and 240 models only).
Field Installed Condensate Drain Trap
• Available in copper or PVC
Drain Pan Overflow Switch
• Monitors condensate level in drain pan, shuts down unit if drain becomes clogged
FF
FEATURES AND BENEFITS
Low Ambient Controls (0°F)
• Units operate satisfactorily down to 45°F outdoor air temperature without any additional controls
• Allows unit operation down to 0°F without evaporator coil icing
• Head pressure speed control reduces outdoor fan operation during low ambient conditions until head pressure rises to the setpoint
• Pressure transducers are mounted on the liquid lines
• Liquid line pressure switches and temperature switches are provided for field installation
• Wiring harnesses are furnished for simple plug-in wiring to fans and controller
CABINET
Construction
• Heavy-gauge steel panels
• Full perimeter heavy-gauge galvanized steel base rail
• Base rails have rigging holes
• Three sides of the base rail have forklift slots
• Raised edges around duct and power entry openings in the bottom of the unit for water protection
Airflow Choice
• Units are shipped in downflow (vertical) return air flow configuration NOTE - Units can be field converted to horizontal air flow with optional Horizontal Return Air Panel Kit and Horizontal Roof Curb.
Power Entry
• Electrical lines can be routed through the unit base or through horizontal access knock-outs
Exterior Panels
• Constructed of heavy-gauge, galvanized steel
• Textured pre-paint with polyurethane finish
• Cyclic salt fog and UV exposure up to 1,680 hours per
ASTM D5894
Insulation
• Fully insulated with non-hygroscopic fiberglass insulation (conditioned areas)
• Unit base is fully insulated
• Base insulation serves as an air seal to the roof curb, eliminating the need to add a seal during installation
Access Panels
• Economizer/Filter section
• Heating/Blower section
• Compressor/Controls section
GG
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 5
CABINET (continued)
Options/Accessories
Hinged Access Panels
• Tool-less access
• Filter section
• Heating/Blower section
• Compressor/Controls section
• Panel seals and quarter-turn latching handles provide a tight air and water seal
Field Installed Combination Coil/Hail Guards
• Heavy gauge steel frame
• Painted to match cabinet
• Expanded metal mesh protects outdoor coil
Field Installed Horizontal Return Air Panel Kit
• Required for horizontal applications with Horizontal Roof
Curb
• Contains panel with return air opening for field replacement of existing unit panel and panel to cover bottom return air opening in unit
• See dimension drawings
FEATURES AND BENEFITS
BLOWER
A wide selection of supply air blower options are available to meet a variety of airflow requirements
Blower Motor
• Overload protected
• Ball bearings
Supply Air Blower
• Forward curved blades
• Double inlet
• Blower wheel statically and dynamically balanced
• Ball bearings
• Adjustable pulley (allows speed change)
• Blower assembly slides out of unit for servicing
Single Zone VAV Supply Fan Operation
• Single Zone VAV stages the amount of airflow according to compressor stages, heating demand and ventilation demand
• Units utilize a Variable Frequency Drive (VFD) to stage the supply air blower airflow
• VFD alters the frequency and voltage of the power supply to the blower to control blower speed
• The supply air blower has two speeds:
1. Low speed for part-load cooling operation.
Note - Low speed is 60% of high speed.
2. High speed for full load cooling and all heat modes.
• Full speed blower operation is set by adjusting the motor pulley to deliver the desired air volume
• Ventilation speed is selectable between high and low speed NOTE - Part load airflow in cooling mode should not be set below 220 cfm/nominal full load ton to reduce the risk of evaporator coil freeze-up.
• VFD has an operational range of -40 to 125° F outdoor air ambient temperature
NOTE - Lower operating costs are obtained when the blower is operated on lower speeds.
HH
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 6
BLOWER (continued)
Single Zone VAV Air Volume Sequence of Operation
• Ventilation speed is determined by the VENT SPEED switch setting on VFD control board (LO or HI)
• Blower operates in low speed for mechanical cooling
(Y1)
• Blower operates in high speed for any other mode (free cooling, mechanical cooling Y1+Y2, and heating)
• Economizer damper minimum position is fully closed in unoccupied mode
• In occupied mode, the economizer damper minimum position is determined by the setting of the two potentiometers on VFD control board:
• LO SPD MIN POS potentiometer sets the minimum position when blower is operating at low speed
• HI SPD MIN POS potentiometer sets the minimum position when blower is operating at high speed
Ordering Information
• Specify blower motor, motor horsepower and drive kit number when base unit is ordered NOTE - Units equipped a Variable Frequency Drive (VFD) are designed to operate on balanced, three-phase power. Operating units on unbalanced three-phase power will reduce the reliability of all electrical components in the unit. Unbalanced power is a result of the power delivery system supplied by the local utility company. Factory-installed inverters are sized to drive blower motors with an equivalent current rating using balanced three-phase power. If unbalanced three-phase power is supplied; the installer must replace the existing factory-installed inverter with an inverter that has a higher current rating to allow for the imbalance.
Refer to the installation instructions for additional information and replacement information.
Options/Accessories
Field Installed Blower Belt Auto-Tensioner
• Provides proper tension to belt drive blower belt without the need for regular adjustments
• Maintains airflow and proper performance
VFD Manual Bypass Kit
• Bypass Kit can be used to operate the unit in single speed (CAV) blower mode if the inverter needs to be serviced or replaced
• VFD Manual Bypass Control is a manual bypass and is enabled by re-configuring the wiring on the unit
FEATURES AND BENEFITS
CONTROLS
Unit Control
• All control voltage is provided via a 24V (secondary) transformer with built-in circuit breaker protection
• Up to 2 heat / 2 cool staging with a third party DDC control system or thermostat
• Low voltage terminal block provides screw terminal connections for thermostat or controller wiring
Options/Accessories
Field Installed Smoke Detector
• Photoelectric type
• Installed in supply air section, return air section or both sections
• Available with power board and single sensor (supply or return) or power board and two sensors (supply and return)
• Power board located in unit control compartment
Commercial Control Systems Thermostats
• Control system and thermostat options see page 11
ELECTRICAL
All units include terminal block and fuse block in power entry junction box for single power entry application
Marked & Color-Coded Wiring
• All electrical wiring is color-coded and marked to identify which components it is connecting
Electrical Plugs
• Positive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation
Phase Monitor
• Located in the control compartment
• Detects the phasing of incoming power
• If the incoming power is out of phase or if any of the three phases are lost, an indicator LED on the phase monitor will turn red and the unit will not start
• In normal operation with correct incoming power phasing, indicator LED will be green
Required Selections
Voltage Choice
• Specify when ordering base unit
II
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 7
ELECTRICAL (continued)
Options/Accessories
Factory or Field Installed Disconnect Switch
• Accessible from outside of unit
• Spring loaded weatherproof cover furnished
GFI Service Outlets (2)
• 115V ground fault circuit interrupter (GFCI) type options:
• Field installed, non-powered, field wired
Field Installed Electric Heat
• Helix wound nichrome elements
• Individual element limit controls
• Wiring harness
• Unit fuse block
• See Options / Accessories tables for ordering information
GFI Weatherproof Cover
• Single-gang cover
• Heavy-duty UV-resistant polycarbonate case construction
• Hinged base cover with gasket
INDOOR AIR QUALITY
Air Filters
• Disposable 2 inch MERV 4 filters furnished as standard
Options/Accessories
Field Installed High Efficiency Air Filters
• Disposable MERV 8, MERV 13 (Minimum Efficiency
Reporting Value based on ASHRAE 52.2) efficiency
• 2 inch pleated filters
Replacement Filter Media Kit With Frame
• Replaces existing pleated filter media
• Includes washable metal mesh screen and metal frame with clip for holding replaceable non-pleated filter
Indoor Air Quality (CO2) Sensors
• Monitors CO2 levels
• Reports to the Unit Controller which adjusts economizer dampers as needed
JJ
KK
LL
FEATURES AND BENEFITS
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 8
ECONOMIZER
Economizer (Standard and High Performance Common Features)
• Outdoor Air Hood with mist elimination filter furnished
• Mixed Air Sensor furnished for field installation in the rooftop unit NOTE - Sensor is factory installed when Economizer is factory installed.
Field Installed Standard Economizer Features (Not for Title 24)
• Gear-driven action
• 24-volt, fully-modulating spring return motor
• Return air and outdoor air dampers
• Plug-in connections to unit
• Nylon bearings
• Neoprene seals
Standard Economizer Control Module (Not for Title 24)
• Standard Economizer Control Module operation is based on outdoor air temperatures Economizer Controls:
• Damper Minimum Position - Can be set lower than traditional minimum air requirements resulting in cost savings
• IAQ Sensor - Signals dampers to modulate and maintain 55°F when CO2 is higher than the CO2 setpoint
• Demand Control Ventilation (DCV) LED - A steady green Demand Control Ventilation LED indicates the IAQ reading is higher than setpoint and requires more fresh air
• Free Cool LED - A steady green LED indicates outdoor air is suitable for free cooling
• Free Cooling runs when outdoor air temperature is lower than the set temperature on the economizer control
NOTE: The Free Cooling default setting for outdoor air temperature sensor is 55°F.
MM
OPTIONS/ACCESSORIES
Factory or Field Installed High Performance Economizer Features
• Approved for California Title 24 building standards
• Low leakage dampers are Air Movement and Control
Association International (AMCA) Class 1A Certified - Maximum 3 CFM per sq. ft. leakage at 1 in. w.g.
• ASHRAE 90.1-2010 compliant
• Linked damper action
• High torque 24-volt fully-modulating spring return damper motor
• Return air and outdoor air dampers
• Plug-in connections to unit NOTE - High Performance Economizers are not approved for use with differential enthalpy controls in Title 24 applications.
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 9
OPTIONS/ACCESSORIES
ECONOMIZER (continued)
High Performance Economizer Control Module
• Provides inputs and outputs to control economizer based on parameter settings
• Free cooling based on single dry bulb temperature, or combination temperature + humidity sensors
• Automatic switchover for different control modes
• Parameter settings based on climate zone, using GPS functionality in the Climatix Mobile application
• LED indication for free cooling operation, sensor operation and damper operation
• Quick installation and easy commissioning with the Climatix Mobile App on a mobile device
NOTE - WLAN Stick is required for App connection to module(s).
• Module displays any alarm messages (fault detection and diagnostics) as an aid in troubleshooting
• RS485 port for BACnet MSTP or Modbus RTU communication
• USB port for firmware updates and WLAN connection for setup and commissioning
• QR codes on module for quick access to download
Climatix Mobile App and user documentation
• User Interface for normal operation, parameter setup, and alarm notifications with an LCD display and three operation buttons:
1. Up Button - Move to the previous value, step or category
2. Down Button - Move to the next value, step or category
3. Enter Button -
• Press to edit the current value or option
• Press to confirm a newly selected value or option
• Press Enter + Up to jump up one category
• Press Enter + Down to jump down one category
NOTE - The Free Cooling setpoint for Title 24 applications must be set based on the Climate Zone where the system is installed. See Section 140.4 “Prescriptive Requirements for Space Conditioning Systems” of the California Energy Commission’s 2013 Building Energy Efficiency Standards.
NOTE - Refer to Installation Instructions for complete setup information and menu parameters available.
Factory or Field Installed
Single Enthalpy Temperature Control
• Outdoor air enthalpy sensor enables economizer if the outdoor enthalpy is less than the setpoint of the control
NOTE - The factory installed economizer option comes preset for Single Enthalpy control but can be field converted to Single Sensible Temperature control by changing a parameter on the economizer control module.
Field Installed
Differential Enthalpy Control (Not for Title 24)
• Order one for factory installed economizer
• Order two for field installed economizer
• One is field installed in the return air section
• One in the outdoor air section
• Allows the economizer control board to select between outdoor air or return air, whichever has lower enthalpy
WLAN Stick
• Required for Climatix Mobile App usage
• Plugs into USB port on Module to provide a temporary
WLAN connection for setup, commissioning, and servicing
NOTE - Only one WLAN Stick is required and can be used on multiple modules.
EXHAUST
Factory or Field Installed Downflow Barometric Relief Dampers With Exhaust Hood
• Allow relief of excess air
• Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle
• Exhaust hood with bird screen is furnished
Field Installed Horizontal Barometric Relief Dampers With Exhaust Hood
• For use when unit is configured for horizontal applications requiring an economizer
• Allows relief of excess air
• Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle
• Field installed in return air duct
• Exhaust hood with bird screen is furnished
Power Exhaust Fans
• Installs internal to unit for downflow applications only with economizer option
• Provides exhaust air pressure relief
• Interlocked to run when supply air blower is operating, fans run when outdoor air dampers are 50% open (adjustable)
• Motor is overload protected
• Dual fans
• 20 in. diameter
• 5 blades
• Two 1/3 hp motors
• SCCR rated NOTE - Requires Economizer with Outdoor Air Hood and
Downflow Barometric Relief Dampers
NN
OO
https://apps.apple.com/us/app/climatix/id1527230319 https://play.google.com/store/apps/details?id=com.siemens.climatixmobile&hl=en_US&gl=US
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 10
OPTIONS/ACCESSORIES
OUTDOOR AIR
Field Installed Outdoor Air Damper
• Downflow or Horizontal
• Linked mechanical dampers
• 0 to 25% (fixed) outdoor air adjustable
• Installs in unit
• Includes outdoor air hood
• Motorized model features fully modulating spring return damper motor with plug-in connection
• Manual model features parallel blade, gear-driven dampers with adjustable fixed position
ROOF CURBS
• Nailer strip furnished (downflow only)
• Mates to unit
• US National Roofing Contractors Approved
• Shipped knocked down
Downflow
Hybrid Roof Curbs
• Interlocking tabs fasten corners together
• No tools required for assembly
• Can also be fastened together with furnished hardware
• Available in 8, 14, 18, and 24 inch heights
Adjustable Pitch Curb
• Fully adjustable pitch curbs (3/4 in. per foot in any direction) provide a level platform for rooftop units allowing flexible installations on roofs with uneven or sloped angles
• Uses interlocking tabs to fasten corners together
• No tools required for assembly
• Hardware is furnished to connect upper curb with lower curb
• Available in 14 inch height
Horizontal
• Meet National Roofing Code requirements
• Converts unit from downflow to horizontal (side) air flow
• Return air is on unit
• Supply air is on curb
• See dimension drawings
• Available in 26, 30, 37, and 41 inch heights NOTE - Requires Horizontal Return Air Panel Kit.
NOTE - Optional Insulation Kit is available to help prevent sweating.
Adaptor Curbs (not shown)
• Curbs are regionally sourced
• Dimensions vary based upon the source NOTE - Contact your local sales representative for a detailed cut sheet with applicable dimensions.
CEILING DIFFUSERS
Field Installed Ceiling Diffusers (Flush or Step-Down)
• White powder coat finish on diffuser face and grilles
• Insulated UL listed duct liner
• Diffuser box has collars for duct connection
• Step-down diffusers have double deflection blades
• Flush diffusers have fixed blades
• Provisions for suspending
• Internally sealed to prevent recirculation
• Removable return air grille
• Adapts to T-bar ceiling grids or plaster ceilings
Transitions (Supply and Return)
• Used with diffusers
• Installs in roof curb
• Galvanized steel construction
• Flanges furnished for duct connection to diffusers
• Fully insulated
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 11
CS7500 Commercial 7-Day Programmable Thermostat
• Premium Universal Thermostat
• Full Color Touchscreen Interface
• Up To 4 Heat / 3 Cool
• Built-In Sensors For Temperature and Humidity
• Remote Sensors Options For Temperature, Discharge
Air, Outdoor Air
• 5-2 or 7-Day Scheduling
• Smooth Setback Recovery
• Heat/Cool Auto-Changeover
• FDD, ASHRAE, IECC Compliant
CS3000 Commercial 5-2 Day Programmable Thermostat
MAINT
Commercial
• Conventional Multi-Stage Thermostat
• Intuitive Display
• Push-Button Operation
• Up To 2 Heat / 2 Cool
• Built-In Temperature Sensor
• Remote Temperature Sensing
• Up to 5-2 Day Scheduling
• Smooth Setback Recovery
• Heat/Cool Auto-changeover
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS
Description Catalog No.
CS7500 Commercial 7-Day Programmable Thermostat CS7500 7-Day Thermostat 24K41 Sensors/ Accessories
¹ Remote non-adjustable wall-mount 20k 47W36 ¹ Remote non-adjustable wall-mount 10k 47W37
Remote non-adjustable discharge air (duct mount) 19L22 Outdoor temperature sensor X2658
CS3000 5-2 Day Programmable Thermostat CS3000 5-2 Day Thermostat 11Y05 Sensor/ Accessories
Remote non-adjustable wall mount 10k averaging 47W37 Thermostat wall mounting plate X2659
BACnet 7-Day Programmable Thermostat BACnet Controls
² 7-Day BACnet Thermostat 24C57 ³ BACnet Module 16X72
⁴���BACnet Room Sensors
With Display 97W23 Without Display 97W24
Universal Thermostat Guard with Lock (clear) Inside Dimensions (H x W x D) 5-7/8 x 8-3/8 x 3 in. 39P21
1 R emote wall-mount sensors can be applied in any of the following combinations:
One Sensor - (1) 47W36, Two Sensors - (2) 47W37, Three Sensors - (2) 47W36 and (1) 47W37 Four Sensors - (4) 47W36, Five Sensors - (3) 47W36 and (2) 47W37
2 BACnet Thermostat (24C57) will control units with and without the dehumidification option.
If there is a mix of units equipped with and without dehumidification on the same site, this thermostat can be used for all units if suitable.
3 Not compatible with units equipped with dehumidification option.
4 Only compatible with BACnet Module (16X70).
BACnet Compatible Thermostat With Reheat
• 7-Day Programmable
• For units with or without Humiditrol®
• BTL listed MS/TP ensures compatibility with any
BACnet system
• Built-in control programs for conventional and heat pump applications
• Conventional systems up to 3-stage heat and
3-stage cool
• Heat pumps with 1 or 2 compressors and up to
2-stage auxiliary heat
• On-board temperature and humidity sensor
• Multiple configurable inputs and outputs enable advanced control strategies
• Set-up Wizard enables rapid system configuration
• No special tools required for installation or commissioning
• Seven-day (2, 4 or 6 event) occupancy scheduling per day
• Backlit 5-inch LCD touchscreen
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 12
OVERVIEW
NOTE - Not available with Eco-Last™ Coil System (180, 210 and 240 models only).
Conventional Fin/Tube condenser coil must be ordered as a factory option.
• Factory installed option designed to control humidity
• Provides dehumidification on demand using ASHRAE
90.1 recommended method for comfort conditioning humidity control
• Unit comes equipped with one row reheat coil, solenoid valve and humidity controller
• A thermostat with a dehumidification output, a dehumidistat, or a DDC controller with an isolated output is required to control humidity and must be located in the occupied space
BENEFITS
• Improves indoor air quality
• Helps prevent damage due to high humidity levels
• Improves comfort levels by reducing space humidity levels
OPERATION
No Dehumidification Demand
• The unit will operate conventionally whenever there is a demand for cooling or heating and no dehumidification demand
• Free cooling is only permitted when there is no demand for dehumidification
Dehumidification Demand Only
• Dehumidification is initiated by an output from a dehumidistat (furnished), an optional thermostat with a dehumidification output or an optional DDC controller with an isolated output to control humidity
• Reheat operation will initiate on a dehumidification demand and does not require a cooling demand
• The unit will operate in the dehumidification mode until the relative humidity of the conditioned space is below the setpoint
• This reduces sensible cooling capacity and extends compressor run time to control humidity when the cooling load is low
• A solenoid valve diverts hot gas from the compressor to the reheat coil
• The cooled and dehumidified air from the evaporator is reheated as it passes through the reheat coil
• The de-superheated and partially condensed refrigerant continues to the outdoor condenser coil where condensing is completed
• The unit will continue to operate in this mode until the dehumidification demand is satisfied
DEHUMIDIFICATION SYSTEM OPTION
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 13
DEHUMIDIFICATION SYSTEM OPTION
REFRIGERANT SCHEMATIC (180, 210 AND 240 MODELS ONLY)
3 3
NOTE - Two refrigerant circuits operate during reheat.
ALL THREE
EVAPORATOR
CIRCUITS ARE
INTERLACED
REHEAT
COIL
L14
REHEAT
VALVE
L30
REHEAT
VALVE
CHECK
VALVES
EXPANSION
VALVES
REFRIGERANT SCHEMATIC (300S MODELS ONLY)
4 2
3 4
REHEAT
COIL
ALL FOUR
EVAPORATOR
CIRCUITS ARE
INTERLACED
EXPANSION
VALVES
CHECK
VALVES
L14
REHEAT
VALVE L30
REHEAT
VALVE
NOTE - Two refrigerant circuits operate during reheat.
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 14
OPTIONS / ACCESSORIES
Item Description Catalog Number 180 210 240 300
COOLING SYSTEM
Condensate Drain Trap PVC 22H54 X X X X
Copper 76W27 X X X X Conventional Fin/Tube Condenser Coil (replaces Eco-Last™ Coil System) (Required for Dehumidification option on 180, 210 and 240 models)
Factory O O O O
Drain�Pan�Overflow�Switch 10C24 X X X X Low Ambient Kits (0°F) 23V24 X X
23V25 X 23V26 X
BLOWER - SUPPLY AIR
Blower Motors Belt Drive - 3 hp Factory O O
Belt Drive - 5 hp Factory O O O O Belt Drive 7.5 hp Factory O O O O Belt Drive 10 hp Factory O O
VFD Manual Bypass Kit 3, 5 hp (208/230V) 3, 5, 7.5, 10 hp (460V and 575V)
90W52 X X X X
7.5, 10 hp (208/230V) 90W51 X X X X Drive Kits See Blower Data Tables for usage and selection
Kit #1 535-725 rpm Factory O O Kit #2 710-965 rpm Factory O O Kit #3 685-856 rpm Factory O O O O
Kit #4 850-1045 rpm Factory O O O O Kit #5 945-1185 rpm Factory O O O O Kit #6 850-1045 rpm Factory O O O O Kit #7 945-1185 rpm Factory O O O O
Kit #8 1045-1285 rpm Factory O O O O Kit #10 1045-1285 rpm Factory O O Kit #11 1135-1365 rpm Factory O O
Blower Belt Auto-Tensioner 24B80 X X X X
CABINET
Combination Coil/Hail Guards 23U69 X X
23U71 X X Hinged Access Panels Factory O O O O
CONTROLS
NOTE - Also see Conventional Thermostat Control Systems on page 11 for additional control options.
Smoke Detector - Supply or Return (Power board and one sensor) 22H56 X X X X Smoke Detector - Supply and Return (Power board and two sensors) 22H57 X X X X NOTE�-�Catalog�numbers�shown�are�for�ordering�field�installed�accessories.
OX�-�Configure�To�Order�(Factory�Installed)�or�Field�Installed O�=�Configure�To�Order�(Factory�Installed) X = Field Installed
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 15
Item Description Catalog Number 180 210 240 300
ELECTRICAL
Voltage 60 Hz 208/230V - 3 phase Factory O O O O
460V - 3 phase Factory O O O O 575V - 3 phase Factory O O O O
Disconnect Switch (see Electric Heat Tables for usage)
80 amp 54W85 OX OX OX OX 150 amp 54W86 OX OX OX OX 250 amp 54W87 OX OX OX OX
GFI Service Outlets
15�amp�non-powered,�field-wired�(208/230V,�460V�only) 74M70 X X X X ¹�20�amp�non-powered,�field-wired�(208/230V,�460V,�575V) 67E01 X X X X
Weatherproof Cover for GFI 10C89 X X X X
ELECTRIC HEAT
15 kW 208/240V-3ph 22H66 X X X X
460V-3ph 22H67 X X X X 575V-3ph 22V35 X X X X
30 kW 208/240V-3ph 22H68 X X X X 460V-3ph 22H69 X X X X 575V-3ph 22V36 X X X X
45 kW 208/240V-3ph 22H72 X X X X 460V-3ph 22H73 X X X X 575V-3ph 22V38 X X X X
60 kW 208/240V-3ph 22H76 X X X X 460V-3ph 22H77 X X X X 575V-3ph 22V40 X X X X
90 kW 208/240V-3ph 22H80 X X X 460V-3ph 22H81 X X X 575V-3ph 22V42 X X X
DEHUMIDIFICATION REHEAT OPTION
Dehumidification�Option Factory O O O O 1�Canada�requires�a�minimum�20�amp�circuit.�Select�20�amp,�non-powered,�field�wired�GFI.
NOTE�-�Catalog�numbers�shown�are�for�ordering�field�installed�accessories.
OX�-�Configure�To�Order�(Factory�Installed)�or�Field�Installed
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 16
Item Description Catalog Number 180 210 240 300
INDOOR AIR QUALITY
Air Filters High�Efficiency�Air�Filters 24 x 24 x 2 in. (Order 6 per unit)
MERV 8 54W67 X X X X
MERV 13 52W40 X X X X
Replacement Media Filter With Metal Mesh Frame (includes non-pleated�filter�media)
44N61 X X X X
Indoor Air Quality (CO2) Sensors Sensor�-�Wall-mount,�off-white�plastic�cover�with�LCD�display 77N39 X X X X Sensor�-�Wall-mount,�off-white�plastic�cover,�no�display 23V86 X X X X Sensor - Black plastic case with LCD display, rated for plenum mounting 87N52 X X X X Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting 87N54 X X X X CO2�Sensor�Duct�Mounting�Kit�-�for�downflow�applications 85L43 X X X X Aspiration Box - for duct mounting non-plenum rated CO2 sensors (77N39) 90N43 X X X X
ECONOMIZER
Standard Economizer With Outdoor Air Hood (Not for Title 24) Standard Economizer Downflow�or�Horizontal�Applications�-�Includes�Outdoor�Air�Hood,�order�Downflow�or� Horizontal Barometric Relief Dampers separately
13U48 X X X X
Standard Economizer Controls (Not for Title 24) Single Enthalpy Control 21Z09 X X X X Differential�Enthalpy�Control�(order�2) 21Z09 X X X X High Performance Economizer With Outdoor Air Hood (For Title 24) / AMCA Class 1A Certified High Performance Economizer Downflow�or�Horizontal�Applications�-�Includes�Outdoor�Air�Hood,�order�Downflow�or� Horizontal Barometric Relief Dampers separately Factory Installed Economizer - Enthalpy control is furnished as standard. Field programmable for Sensible Control without additional hardware Field Installed Economizer - Sensible Sensible Sensor is furnished as standard
23G24 OX OX OX OX
High Performance Economizer Controls Single Enthalpy Control (Not for Title 24) 23G26 X X X X Differential�Enthalpy�Control�(order�1�for�factory.�order�2�for�field)�(Not�for�Title�24) 23G26 X X X X Economizer Accessories WLAN Stick (For High Performance Economizer only) 23K58 X X X X Barometric Relief Dampers With Exhaust Hood Downflow�Barometric�Relief�Dampers 54W78 OX OX OX OX Horizontal Barometric Relief Dampers 16K99 X X X X
NOTE�-�Catalog�numbers�shown�are�for�ordering�field�installed�accessories.
OX�-�Configure�To�Order�(Factory�Installed)�or�Field�Installed
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 17
Item Description Catalog Number 180 210 240 300
OUTDOOR AIR
Outdoor Air Dampers With Outdoor Air Hood Motorized 22J27 X X X X Manual 13U05 X X X X
¹ POWER EXHAUST (DOWNFLOW APPLICATIONS ONLY)
Standard Static, SCCR Rated 208/230V 22H90 X X X X
460V 22H91 X X X X 575V 22V34 X X X X
ROOF CURBS
Hybrid Roof Curbs, Downflow 8 in. height 11F58 X X X X 14 in. height 11F59 X X X X 18 in. height 11F60 X X X X 24 in. height 11F61 X X X X Adjustable Pitch Curb 14 in. height 43W26 X X X X Standard Roof Curbs, Horizontal - Requires Horizontal Return Air Panel Kit 26 in. height - slab applications 11T89 X X X 30 in. height - slab applications 11T90 X 37 in. height - rooftop applications 11T96 X X X 41 in. height - rooftop applications 11T97 X Insulation Kit For Standard Horizontal Curbs For 26 in. Curb 73K32 X X X For 30 in. Curb 73K33 X For 37 in. Curb 73K34 X X X For 41 in. Curb 73K35 X Horizontal Return Air Panel Kit Required for Horizontal Applications with Roof Curb 87M00 X X X X
CEILING DIFFUSERS
Step-Down - Order one RTD11-185S 13K63 X
RTD11-275S 13K64 X X X
Flush - Order one FD11-185S 13K58 X
FD11-275S 13K59 X X X
Transitions (Supply and Return) - Order one C1DIFF33C-1 12X68 X
C1DIFF34C-1 12X70 X X X
1 Field installed Power Exhaust requires Economizer with Outdoor Air Hood and�Downflow�Barometric�Relief�Dampers�with�Exhaust�Hood.�Must�be�ordered�separately.
NOTE�-�Catalog�numbers�shown�are�for�ordering�field�installed�accessories.
OX�-�Configure�To�Order�(Factory�Installed)�or�Field�Installed
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 18
SPECIFICATIONS
General Data Nominal Tonnage 15 Ton 17.5 Ton 20 Ton 25 Ton
Model Number KCC180S4M KCC210S4M KCC240S4M KCC300S4M Efficiency Type Standard Standard Standard Standard
Blower Type Single Zone VAV Supply Fan
Single Zone VAV Supply Fan
Single Zone VAV Supply Fan
Single Zone VAV Supply Fan
Cooling Performance
Gross Cooling Capacity - Btuh 178,000 206,000 236,000 282,000 1 Net Cooling Capacity - Btuh 172,000 200,000 228,000 270,000
1 AHRI Rated Air Flow - cfm 7200 6125 7000 7500 Total Unit Power - kW 15.6 18.2 20.7 27
1 IEER (Btuh/Watt) 14.2 14.2 14.2 13.2 ¹ EER (Btuh/Watt) 11.0 11.0 11.0 10.0
Refrigerant Charge
Refrigerant Type R-410A R-410A R-410A R-410A Eco-Last™ Coil System Circuit 1 7 lbs. 3 oz. 8 lbs. 0 oz. 8 lbs. 12 oz. 7 lbs. 13 oz.
Circuit 2 6 lbs. 10 oz. 7 lbs. 2 oz. 8 lbs. 7 oz. 6 lbs. 8 oz.
Circuit 3 6 lbs. 3 oz. 7 lbs. 6 oz. 8 lbs. 10 oz. 5 lbs. 13 oz.
Circuit 4 - - - - - - - - - 5 lbs. 13 oz.
Conventional Fin Tube Coil Option
Circuit 1 11 lbs. 8 oz. 12 lbs. 12 oz. 13 lbs. 10 oz. 10 lbs. 8 oz.
Circuit 2 9 lbs. 14 oz. 12 lbs. 0 oz. 14 lbs. 8 oz. 10 lbs. 0 oz.
Circuit 3 8 lbs. 15 oz. 11 lbs. 2 oz. 13 lbs. 4 oz. 9 lbs. 12 oz.
Circuit 4 - - - - - - - - - 9 lbs. 12 oz.
Conventional Fin/Tube with Reheat Option
Circuit 1 15 lbs. 4 oz. 14 lbs. 8 oz. 14 lbs. 12 oz. - - - Circuit 2 13 lbs. 0 oz. 13 lbs. 9 oz. 15 lbs. 4 oz. - - - Circuit 3 8 lbs. 15 oz. 11 lbs. 2 oz. 13 lbs. 4 oz. - - - Circuit 4 - - - - - - - - - - - -
Coil System with Reheat Option
Circuit 1 - - - - - - - - - 7 lbs. 7 oz.
Circuit 2 - - - - - - - - - 7 lbs. 2 oz.
Circuit 3 - - - - - - - - - 5 lbs. 15 oz.
Circuit 4 - - - - - - - - - 6 lbs. 1 oz.
Electric Heat Available, see page 15 15-30-45-60 kW 15-30-45-60-90 kW Compressor Type (number) Scroll (3) Scroll (3) Scroll (3) Scroll (4) Outdoor Coils Eco-Last™ (Fin/Tube)
Net face area (total) - sq. ft. 41.1 41.1 55.0 55.0 Number of rows 1 (2) 1 (2) 1 (2) 1 (2)
Fins per inch 23 (20) 23 (20) 23 (20) 23 (20) Outdoor Coil Fans
No. and type (3) PSC (3) PSC (4) PSC (6) PSC Motor - horsepower 1/3 1/3 1/3 1/3
Motor rpm 1075 1075 1075 1075 Total Motor watts 1100 1100 1665 1950
Diameter - (No.) in. / No. of blades (3) 24 / 3 (3) 24 / 3 (4) 24 / 3 (6) 24 / 3 Total Air volume - cfm 12,000 12,000 16,000 20,000
Indoor Coils Net face area (total) - sq. ft. 21.4 21.4 21.4 21.4 Tube diameter - in. / No. of rows 3/8 / 3 3/8 / 4 3/8 / 4 3/8 / 4
Fins per inch 14 14 14 14 Drain connection - No. and size (1) 1 in. FPT (1) 1 in. FPT (1) 1 in. FPT (1) 1 in. FPT
Expansion device type Balanced Port Thermostatic Expansion Valve, removable element head 2 Indoor
Blower and Drive Selection
Nominal motor output 3 hp, 5 hp, 7.5 hp 5 hp, 7.5 hp, 10 hp Maximum usable motor output (US) 3.45 hp, 5.75 hp, 8.62 hp 5.75 hp, 8.62 hp, 11.5 hp
Motor - Drive kit number 3 hp Kit 1 535-725 rpm Kit 2 710-965 rpm
5 hp Kit 3 685-856 rpm
Kit 4 850-1045 rpm Kit 5 945-1185 rpm
7.5 hp Kit 6 850-1045 rpm Kit 7 945-1185 rpm
Kit 8 1045-1285 rpm
5 hp Kit 3 685-856 rpm
Kit 4 850-1045 rpm Kit 5 945-1185 rpm
7.5 hp Kit 6 850-1045 rpm Kit 7 945-1185 rpm
Kit 8 1045-1285 rpm 10 hp
Kit 7 945-1185 rpm Kit 10 1045-1285 rpm Kit 11 1135-1365 rpm
Blower wheel nominal diameter x width - in. (2) 15 x 15 Filters Type�of�filter�/�No.�and�size�(in.) MERV 4, Disposable / (6) 24 x 24 x 2 Electrical characteristics 208/230V, 460V or 575V - 60 hertz - 3 phase NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1�AHRI�Certified�to�AHRI�Standard�340/360;�95°F�outdoor�air�temperature�and�80°F�db/67°F�wb�entering�evaporator�air;�minimum�external�duct�static�pressure.
2 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
NOTE – Motor service factor limit - 1.0.
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 19
RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
15 TON - KCC180S4M (FULL LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 85°F 95°F 105°F 115°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 4800 167.2 10.03 0.73 0.87 1 156.2 11.19 0.74 0.89 1 143 12.44 0.75 0.92 1 132.3 13.9 0.77 0.94 1 6000 176.2 10.11 0.78 0.94 1 163.7 11.26 0.8 0.97 1 151.4 12.53 0.81 0.99 1 141.1 13.99 0.84 1 1 7200 183.5 10.19 0.83 0.99 1 171 11.32 0.85 1 1 158.7 12.59 0.88 1 1 148.6 14.07 0.91 1 1
67°F 4800 178.6 10.13 0.57 0.7 0.83 166.6 11.28 0.57 0.72 0.85 153.5 12.54 0.57 0.73 0.88 143.1 14.02 0.58 0.75 0.9 6000 188.2 10.23 0.6 0.76 0.91 174.7 11.36 0.61 0.78 0.93 161.3 12.62 0.62 0.8 0.97 149.6 14.07 0.63 0.82 0.99 7200 194.9 10.3 0.64 0.81 0.97 180.3 11.41 0.65 0.83 0.99 166.3 12.66 0.66 0.86 1 154.6 14.13 0.67 0.89 1
71°F 4800 189.7 10.24 0.43 0.56 0.68 176.6 11.37 0.42 0.56 0.69 163.5 12.64 0.42 0.57 0.71 152.5 14.1 0.41 0.57 0.72 6000 198.9 10.33 0.44 0.59 0.74 185.1 11.46 0.44 0.6 0.75 171.3 12.71 0.44 0.61 0.78 159.8 14.17 0.43 0.62 0.79 7200 205.8 10.4 0.46 0.63 0.79 191.9 11.53 0.46 0.64 0.81 176.3 12.76 0.45 0.65 0.84 164.5 14.22 0.46 0.66 0.86
15 TON - KCC180S4M (PART LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 65°F 75°F 85°F 95°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 3500 125.9 5.32 0.73 0.84 0.94 119.3 6.01 0.73 0.85 0.95 112.4 6.75 0.74 0.86 0.97 105.1 7.57 0.74 0.88 0.98 4000 130.8 5.35 0.75 0.86 0.97 123.9 6.04 0.75 0.88 0.98 116.7 6.79 0.76 0.89 0.98 109 7.6 0.77 0.92 1 4500 134.9 5.38 0.77 0.89 0.98 127.7 6.07 0.78 0.91 0.99 120.1 6.81 0.79 0.93 1 112.3 7.63 0.8 0.95 1
67°F 3500 132.1 5.36 0.6 0.71 0.81 125.5 6.06 0.6 0.71 0.82 118.3 6.8 0.6 0.72 0.83 110.8 7.62 0.6 0.73 0.85 4000 137.4 5.39 0.62 0.73 0.84 130.3 6.1 0.62 0.73 0.85 122.9 6.84 0.62 0.74 0.87 115 7.65 0.62 0.75 0.88 4500 141.7 5.42 0.63 0.75 0.87 134.4 6.13 0.63 0.76 0.88 126.5 6.87 0.63 0.77 0.9 118.5 7.68 0.64 0.78 0.92
71°F 3500 137.9 5.4 0.49 0.59 0.69 131.2 6.1 0.48 0.59 0.69 123.8 6.85 0.48 0.59 0.7 116.2 7.66 0.47 0.59 0.71 4000 143.4 5.43 0.49 0.61 0.71 136.2 6.15 0.49 0.61 0.71 128.7 6.88 0.49 0.61 0.72 120.5 7.7 0.48 0.61 0.73 4500 148 5.46 0.5 0.62 0.73 140.3 6.18 0.5 0.62 0.74 132.4 6.92 0.5 0.63 0.75 124.2 7.73 0.49 0.63 0.76
17.5 TON - KCC210S4M (FULL LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 85°F 95°F 105°F 115°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 5600 201.9 12.89 0.71 0.86 0.99 188.9 14.4 0.72 0.87 1 173.9 16.1 0.73 0.9 1 158.3 17.99 0.74 0.93 1 7000 214.1 13.09 0.77 0.93 1 198.7 14.55 0.78 0.96 1 184.2 16.26 0.8 0.98 1 168.1 18.13 0.82 1 1 8400 223.7 13.24 0.82 0.99 1 208.5 14.7 0.84 1 1 194.6 16.44 0.87 1 1 178.9 18.32 0.9 1 1
67°F 5600 217.9 13.14 0.55 0.69 0.82 202.6 14.61 0.55 0.7 0.84 187.7 16.32 0.55 0.71 0.86 170.8 18.17 0.55 0.72 0.89 7000 229.8 13.33 0.59 0.74 0.9 212.6 14.77 0.59 0.76 0.92 196.9 16.47 0.59 0.78 0.96 179.8 18.33 0.6 0.8 0.99 8400 237.8 13.46 0.62 0.8 0.97 219.9 14.88 0.63 0.82 0.99 203.9 16.59 0.63 0.84 1 186 18.44 0.65 0.88 1
71°F 5600 234.1 13.39 0.41 0.54 0.66 217.2 14.83 0.4 0.54 0.67 201.8 16.54 0.39 0.54 0.68 184.8 18.42 0.38 0.54 0.7 7000 245.4 13.57 0.42 0.57 0.72 227.5 15 0.41 0.58 0.74 211.5 16.71 0.41 0.59 0.76 193.4 18.57 0.4 0.59 0.78 8400 253.4 13.69 0.44 0.61 0.78 235.3 15.15 0.43 0.62 0.8 218.4 16.83 0.43 0.63 0.83 199.8 18.68 0.43 0.65 0.86
17.5 TON - KCC210S4M (PART LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 65°F 75°F 85°F 95°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 4000 154.1 6.87 0.71 0.82 0.93 146.7 7.73 0.71 0.83 0.95 138.8 8.64 0.72 0.84 0.97 130.5 9.69 0.72 0.86 0.98 4750 161.8 6.94 0.73 0.86 0.98 153.9 7.81 0.74 0.87 0.98 145.5 8.74 0.75 0.89 0.99 136.1 9.78 0.76 0.92 1 5500 167.8 7.01 0.76 0.9 0.99 159.6 7.88 0.77 0.92 1 150.1 8.81 0.78 0.95 1 141.5 9.86 0.8 0.96 1
67°F 4000 162.3 6.95 0.58 0.68 0.79 154.6 7.82 0.58 0.69 0.8 146.4 8.76 0.58 0.7 0.81 137.6 9.81 0.58 0.7 0.83 4750 170.2 7.04 0.6 0.71 0.83 162 7.91 0.6 0.72 0.84 153.3 8.86 0.6 0.73 0.86 144.1 9.91 0.6 0.74 0.88 5500 176.4 7.1 0.61 0.74 0.87 167.8 7.98 0.62 0.75 0.89 158.8 8.94 0.62 0.76 0.91 149.1 9.99 0.62 0.78 0.93
71°F 4000 169.9 7.03 0.46 0.57 0.66 162.1 7.92 0.46 0.57 0.67 153.7 8.86 0.46 0.57 0.68 144.7 9.92 0.45 0.57 0.68 4750 178.4 7.13 0.47 0.59 0.69 170 8.01 0.47 0.59 0.7 160.9 8.98 0.47 0.59 0.71 151.5 10.03 0.46 0.6 0.72 5500 184.7 7.2 0.48 0.6 0.72 176.2 8.09 0.48 0.61 0.73 166.7 9.07 0.48 0.61 0.74 156.8 10.12 0.48 0.62 0.76
K-Series™ Packaged Electric / Electric 15 to 25 Ton / Page 20
RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
20 TON - KCC240S4M (PART LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 65°F 75°F 85°F 95°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 4500 179.6 7.37 0.71 0.83 0.95 171.3 8.41 0.71 0.84 0.96 162.3 9.53 0.72 0.86 0.97 152.6 10.78 0.73 0.88 0.98 5500 189.3 7.42 0.74 0.88 0.98 180.4 8.47 0.75 0.9 0.99 169.6 9.6 0.76 0.93 1 160 10.85 0.78 0.95 1 6500 195.2 7.46 0.78 0.95 1 186.6 8.51 0.79 0.96 1 177 9.65 0.81 0.96 1 166.9 10.91 0.82 0.97 1
67°F 4500 189 7.43 0.57 0.68 0.79 180.7 8.48 0.58 0.69 0.81 171.3 9.62 0.58 0.7 0.82 161.3 10.87 0.58 0.71 0.84 5500 199.2 7.48 0.6 0.72 0.85 189.8 8.54 0.6 0.73 0.87 180 9.68 0.6 0.74 0.9 169.5 10.95 0.61 0.76 0.92 6500 206.6 7.53 0.62 0.76 0.92 196.9 8.59 0.62 0.77 0.94 186.7 9.74 0.63 0.78 0.95 175.4 10.99 0.64 0.8 0.97
71°F 4500 198 7.48 0.45 0.56 0.66 189.3 8.54 0.45 0.56 0.67 179.8 9.69 0.45 0.57 0.68 169.6 10.94 0.44 0.57 0.69 5500 208.5 7.54 0.46 0.58 0.7 199.1 8.61 0.46 0.59 0.71 189 9.76 0.46 0.59 0.72 178.2 11.02 0.46 0.6 0.74 6500 216.5 7.59 0.48 0.61 0.74 206.7 8.67 0.48 0.61 0.75 195.9 9.81 0.48 0.62 0.76 184.8 11.09 0.48 0.63 0.78
20 TON - KCC240S4M (FULL LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 85°F 95°F 105°F 115°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 6400 238.4 15.16 0.67 0.84 0.99 218.9 17.01 0.68 0.86 1 198.1 19.1 0.69 0.89 1 176.7 21.46 0.7 0.93 1 8000 252.9 15.3 0.74 0.93 1 232.6 17.16 0.75 0.96 1 211.9 19.27 0.77 0.99 1 190.6 21.65 0.8 1 1 9600 264.9 15.43 0.8 1 1 245.3 17.3 0.83 1 1 225 19.43 0.85 1 1 204.1 21.84 0.89 1 1
67°F 6400 257.9 15.35 0.5 0.65 0.8 237.7 17.22 0.49 0.65 0.82 216 19.32 0.49 0.67 0.85 193.5 21.69 0.48 0.68 0.88 8000 271.7 15.5 0.54 0.72 0.9 250.6 17.37 0.54 0.73 0.92 228.2 19.47 0.54 0.75 0.96 204.1 21.85 0.54 0.78 0.99 9600 282.1 15.61 0.58 0.78 0.98 260 17.49 0.58 0.8 1 236.5 19.57 0.59 0.83 1 211.7 21.92 0.6 0.87 1
71°F 6400 277.4 15.56 0.36 0.49 0.63 256.4 17.43 0.34 0.49 0.63 234.4 19.55 0.32 0.48 0.64 210.8 21.92 0.3 0.48 0.66 8000 291.9 15.71 0.37 0.53 0.69 269.8 17.6 0.36 0.53 0.71 246.6 19.7 0.35 0.54 0.73 221.7 22.08 0.33 0.54 0.75 9600 302.1 15.83 0.39 0.57 0.76 279.2 17.71 0.38 0.58 0.78 254.7 19.81 0.37 0.59 0.81 229.1 22.18 0.36 0.6 0.84
25 TON - KCC300S4M (PART LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 65°F 75°F 85°F 95°F
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Total Cool Cap.
Comp.
Motor Input
Sensible To Total Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F
63°F 5750 159.2 6.52 0.79 0.93 1 152.7 7.37 0.8 0.95 1 146.1 8.33 0.81 0.96 1 139.4 9.43 0.83 0.98 1 6750 164.1 6.57 0.82 0.97 1 157.8 7.43 0.83 0.99 1 151.2 8.4 0.85 0.99 1 144.3 9.49 0.87 1 1 7750 168.8 6.61 0.85 0.99 1 162.4 7.48 0.87 1 1 155.6 8.45 0.89 1 1 148.7 9.55 0.91 1 1
67°F 5750 168 6.61 0.62 0.76 0.9 161.1 7.47 0.63 0.78 0.92 153.9 8.43 0.64 0.79 0.94 146.3 9.52 0.65 0.81 0.96 6750 172.6 6.66 0.64 0.8 0.95 165.5 7.52 0.65 0.82 0.97 157.9 8.48 0.66 0.83 0.98 149.7 9.56 0.67 0.85 0.99 7750 176.2 6.69 0.66 0.84 0.99 168.7 7.56 0.66 0.85 0.99 160.8 8.52 0.68 0.87 1 152.4 9.6 0.7 0.89 1
71°F 5750 175.5 6.68 0.46 0.61 0.74 168.6 7.56 0.47 0.62 0.76 161.2 8.52 0.47 0.63 0.77 153.3 9.61 0.47 0.64 0.79 6750 180.7 6.74 0.47 0.63 0.78 173.3 7.61 0.48 0.64 0.8 165.6 8.58 0.48 0.65 0.81 152.2 9.76 0.48 0.65 0.83 7750 184.6 6.78 0.49 0.65 0.82 176.9 7.66 0.49 0.67 0.83 168.9 8.63 0.49 0.68 0.85 160.2 9.71 0.47 0.69 0.88
25 TON - KCC300S4M (FULL LOAD)
Entering
Wet Bulb Tem-perature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil 85°F 95°F 105°F 115°F
Total Cool Cap.
Comp.
Motor Input
Sensible To…