6973GH-20-R-00145 Amendment 0001 Revisions

1. Remove “urethane based” from the Specifications, SEC 07 56 00, Part 1, 7.1.0 - Scope, sentence one, and 7.1.1 – Sequence of Operation for VOR Elastomeric Installation item 6.

2. In the specifications, replace SECTION 07 56 00 – FLUID APPLIED ROOFING Part 2 in its entirety with the elastomeric performance spec. listed on pages 2-4 of this document.

3. Contract Drawing ALB-1004541-G005: General note 24: Replace with “The FAA will assist the Contractor in removal and installation of teepee”.

4. Contract Drawing ALB-1004541-G005: General note 25: Replace “250 SQ. FT.” with “500 SQ. FT.”

5. Contract Drawing ALB-1004541-G005: Government Furnished Material note 3: Replace the phrase “Contractor shall” with “FAA will”.

6. Contract Drawing ALB-1004541-D001, Detail A/D001, drawing zone C6, remove “Rosin Paper” from callout note “Contractor to remove: rosin paper, board insulation, and single ply membrane to metal roof.”

7. Contract Drawing ALB-1004541-D001, Detail A/D001, drawing zone B3, Remove callouts “Remove terne roofing (existing)” and “Remove terneplate and hold down clamps from antenna pedestal plate (soldered and screwed)”.

8. Contract Drawing ALB-1004541-A005, Notes 5 and 6, replace “250 SQ.FT.” with “500 SQ.FT.”

9. Contract Drawing ALB-1004541-A005, replace Note 10, with “Not Used”.

10. Contract Drawing ALB-1004541-E001, Detail 3/E001, replace note under title “16 oz. copper sheet .021”thick x 4” wide x 4” long (four required) with “20 oz. copper sheet, (four required)”.

SECTION 07 56 00 – FLUID APPLIED ROOFING

PART 2 – PRODUCTS (REVISED)

7.2.01 Rubber Roof Coating

A. Rubber roof coating products physical specifications and minimum performance criteria shall be in accordance with the following schedules:

1. NEOPRENE FLASHING CEMENT

TESTASTMRESULT
Elongation at 77 deg. F. ASTMD412ASTM D412400%
Recovery from 100% Elongation100%
Tensile Strength ASTM D412ASTM D412600 psi Min.

ADHESIVE BOND Aluminum Q-Panels

Method A D3359-90D3359-905-highest rating
Method B D3359-90D3359-905-highest rating
PLIABILITY @J 0 deg.F.-180 deg. bend
D2823-90D2823-90
1 inch mandrelno cracking or separation
1/4 inch mandrelno cracking or separation
WATER VAPOR PERMEABILITY
E96-80E96-800.15 perms

2. BRUSH GRADE SEAM SEALER

TESTASTMRESULT
Elongation @ 77 deg. F.ASTM D412600%
Elongation @ 32 deg. F.ASTM D412300 %

Recovery from 100% Elongation 100%

Tensile StrengthASTM D4121500 psi
ViscosityASTM D562135-143 K.U.
3.RUBBER COATING
TESTASTMRESULT

Dry film thickness @ 1 gal/100 sq. ft. 6 mils

Elongation @ 77 deg. F.ASTM D412600%
Elongation @ 32 deg. F.ASTM D412300%

Recovery from 100% Elongation 100%

Tensile StrengthASTM D4121500 psi
Shore A HardnessASTM D224070
ViscosityASTM D562105-l 10 K.U.

7.2.02 Rust Remover and Conditioner

A. Rust remover compound shall be a safe, non-toxic, non-flammable formulation which effectively conditions rust. In addition to treating rust and corrosion, product shall remove oil and dirt and prepares the surface for coating.

TYPICAL PROPERTIES

Flash PointNone
Specific Gravity1.10
Weight/Gallon9.3 Ibs.
pH, undiluted1.8
Odor Mild,Not offensive
Freeze/Thaw StabilityThaw at room-temp. and shake or stir
SpillsFlush to sewer
Coverage300-400 sq.ft./gal.

7.2.03 Polyester Membrane

A. Reinforcing membrane shall be composed of warp knit, 100% polyester yarn fibers offering an excellent combination of high strength and elongation to accommodate unusual stress forces from thermal shock or building movement.

TYPICAL PROPERTIES

Tensile StrengthASTM D1682 90 lbs. (41 kg.)
ElongationASTM D1682 45%
Trapezoid Tear StrengthASTM D1117 22 lbs. (10 kg.)
Ball Burst StrengthASTM D3787 180 lbs. (82 kg.)

7.2.04 Manufacturers

A. The following roof coating manufacturers are approved for this project. Substitutions shall be approved after submission showing compliance with the required product technical properties as listed above.

Truco, Inc.

4301 Train Avenue Cleveland, OH 44113

(800) 227-4569

Western Colloid N.C., Inc.

700 71st Ave.

Oakland, CA 94621 510-430-0270

Pacific Polymers 12271 Monarch St.

Garden Grove, CA 92841 714-898-0025

Belzona 2000 N.W. 88th Court Miami, FL 33172 305-594-4994

B. Other manufacturers requesting approval must submit acceptable information certifying that they are the direct manufacturer from raw material into the specified product and meet the performance criteria required.