ENA ARSR
KENAI ALASKA
BUILDING MATERIALS
3.4 Suspect Asbestos-Containing Materials
The following table contains a list of 28 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Off-White 12" x 12" Floor Tile ARSR, Equipment Room - SE Equipment Area 1 Black Floor Mastic ARSR, Equipment Room - SE Equipment Area 2 Off-White Cove Base Mastic ARSR, Equipment Room - SE Equipment Area 3 Off-White 12" x 12" Floor Tile ARSR, Equipment Room - East Equipment Area 4 Black Floor Mastic ARSR, Equipment Room - East Equipment Area 5 Gray 12" x 12" Floor Tile & Black Mastic ARSR, Equipment Room - Inside cabinet 6 Ceiling Tile ARSR, Equipment Room - Kitchen 7 Black Sink Undercoat ARSR, Equipment Room - Kitchen 8 White Exterior Caulk at Penetrations ARSR, Exterior at Penetrations 9 White Exterior Caulk at Footer Structure ARSR, Exterior SE Corner 10 Gray Duct Sealant (Exterior) Exterior on Chiller (SE ARSR) 11 Gray Duct Sealant (Exterior) Exterior on Chiller (SE ARSR) 12 White Caulk on Conduit ARSR, Exterior NE 13 Gray Duct Sealant on Sheet Metal ARSR, Exterior NE 14 Gray Duct Sealant on Wall ARSR, Exterior NE 15 Brown/White Door Caulk Exterior - Tower 16 Off-White Caulk on Metal Panel Exterior - Tower 17 Gray Duct Sealant Debris on Ground ARSR, Exterior North Side 18 Gray 12" x 12" Floor Tile E/G Building 19 Dark Brown Cove Base Mastic E/G Building 20 Gray Caulk at Floor Seal E/G Building 21 Light Gray Caulk at Penetration Seal E/G Building 22 Brown/Yellow Cove Base Mastic UPS Shelter 23 Gray Rubber Floor & Yellow Mastic UPS Shelter 24 Off-White 12" x 12" Floor Tile UPS Shelter 25 Off-White Epoxy Floor E/G Building 26 Gray Caulk E/G Building 27 White Caulk Tunnel / Walkway 28
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
2 Black Floor Mastic (M)
Remnant Material - Equipment Room - SE Equipment Area
N.F. I >1 SF Good One 6% Chrysotile
5 Black Floor Mastic (M)
Remnant Material - Equipment Room - East Equipment Area
N.F. I >1 SF Good One 6% Chrysotile
6 12" x 12" Floor Tile Mastic (Black)
Equipment Room - Under Cabinet
N.F. II 4 SF Good One Mastic Layer:
6%
Chrysotile Tile Layer:
ND
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
Table 2 No tes: Flooring located in the ARSR equipment area appears abated; however, there are patches of residual floor mastic (samples 2 & 5) near floor penetrations and black mastic under floor tile (sample 6) located under/inside a stationary cabinet.Although the asbestos floor mastic appears largely abated, there is potential for residual asbestos floor mastic to be discovered inother areas of the building including under stationary equipment.
Note: Radome was energized at the time of the site visit and access was not allowed for inspection. Any suspect materials presentat the radome access point or within the radome should be assumed asbestos-containing until sampled and proven to be non-asbestos.
BUILDING SCHEMATICS
ENA Kenai, AK ARSR 3 with generator and storage buildings tim.jacobsen Rectangle tim.jacobsen Typewriter = Positive Sample Location (ACM) tim.jacobsen Typewriter = Locations of ACM. Residual black mastic at floor penetrations and mastic under floor tile in stationary equipment/cabinet.
1 Suspect Asbestos-Containing Materials
The following table contains a list of 61 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number 12" x 12" White Floor Tile with Brown Streaks Main Building FGC-FT-
Yellow Mastic Main Building FGC-FT-
GCK ARSR
GARDEN CITY KANSAS
Material Material Sample Location Sample Number
12" x 12" White Floor Tile with Brown Streaks Main Building FGC-FT-
Yellow Mastic Main Building FGC-FT-
12" x 12"White Floor Tile with Brown Streaks Main Building FGC-FT-
Yellow Mastic Main Building FGC-FT-
Yellow Cove Base Mastic Main Building FGC-CB M-04
Yellow Cove Base Mastic Main Building FGC-CB M-05
Yellow Cove Base Mastic Main Building FGC-CB M-06
2' x 4' White Ceiling Tile with Pinholes Main Building FGC-CT1 -07
2' x 4' White Ceiling Tile with Pinholes Main Building FGC-CT1 -08
2' x 4' White Ceiling Tile with Pinholes Main Building FGC-CT1 -09
2'x4' White Ceiling Tile with Pinholes and Gouges Main Building FGC-CT2 -10
2' x 4' White Ceiling Tile with Pinholes and Gouges
Main Building FGC-CT2 -11
2' x 4' White Ceiling Tile with Pinholes and Gouges
Main Building FGC-CT2 -12
Drywall Main Building FGC-DW
JC-13
12" x 12" Brown Floor Tile Main Building FGC-FT2 -14
Yellow Mastic Main Building FGC-FT2 -14
12" x 12" Brown Floor Tile Main Building FGC-FT2 -15
Yellow Mastic Main Building FGC-FT2 -15
12" x 12" Brown Floor Tile Main Building FGC-FT2 -16
Yellow Mastic Main Building FGC-FT2 -16
9" x 9" Green Floor Tile Main Building FGC-FT2 -17
Black Mastic Main Building FGC-FT2 -17
9" x 9" Green Floor Tile Main Building FGC-FT2 -18
Black Mastic Main Building FGC-FT2 -18
9" x 9" Green Floor Tile Main Building FGC-FT2 -19
Black Mastic Main Building FGC-FT2 -19
Window Glazing Main Building FGC-WG-
Black Caulk Radar Tower FGC-CLK 1-21
Black Caulk Radar Tower FGC-CLK 1-22
Black Caulk Radar Tower FGC-CLK 1-23
Soft White Caulk Radar Tower FGC-CLK 2-24
Soft White Caulk Radar Tower FGC-CLK 2-25
Soft White Caulk Radar Tower FGC-CLK 2-26
Hard White Caulk Radar Tower FGC-CLK 3-27
Hard White Caulk Radar Tower FGC-CLK 3-28
Hard White Caulk Radar Tower FGC-CLK 3-29
Drywall Ceiling HVAC Building FGC-DW C-30
Joint Compound HVAC Building FGC-DW C-30
Drywall Ceiling HVAC Building FGC-DW C-31
Joint Compound HVAC Building FGC-DW C-31
Drywall Ceiling HVAC Building FGC-DW C-32
Joint Compound HVAC Building FGC-DW C-32
Drywall HVAC Building FGC-DW
JC2-33
Drywall HVAC Building FGC-DW
JC2-34
Joint Compound HVAC Building FGC-DW
JC2-34
Drywall HVAC Building FGC-DW
JC2-35
Joint Compound HVAC Building FGC-DW
JC2-35
White Cove Base HVAC Building FGC-CB M2-36
Yellow Mastic HVAC Building FGC-CB M2-36
White Cove Base HVAC Building FGC-CB M2-37
Yellow Mastic HVAC Building FGC-CB M2-37
White Cove Base HVAC Building FGC-CB M2-38
Yellow Mastic HVAC Building FGC-CB M2-38
Roof Shingle Wood Shed FGC-RS-
Roof Shingle Wood Shed FGC-RS-
Roof Shingle Wood Shed FGC-RS-
Clear Caulk Metal Shed FGC-CLK 4-42
Clear Caulk Metal Shed FGC-CLK 4-43
Clear Caulk Metal Shed FGC-CLK 4-44
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
FGC-FT2
-17,18,19
Floor Tile - 9" x 9" Green (M)
Main Building - Underneath Cabinets
N.F. I 50 SF Good 1 4-5% Chrysotile
FGC-FT2
-17,18,19
Black Mastic (M) for Green 9" x 9" Floor Tile
Main Building - Underneath Cabinets
N.F. I 50 SF Good 1 3% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM PACM= Presumed asbestos containing material
GCK Garden City, KS
ARSR ½ with storage buildings
8246 Marshall Drive Lenexa, Kansas 66214
SITE SKETCH
DESIGNED BY: ATC SCALE: NTS
DRAWN BY: MM DATE: 5/16/18 FILE: SKETCH
REVIEWED BY: TJ
ASBESTOS SURVEY
PROJECT NO: 204BS01749 Air Route Surveillance Radar (ARSR) Shelter Site – GCK 37.497694, -100.871833
Garden City, Kansas 66054
26 25
39,40,41
05,06
03 = Negative Asbestos Sample Locations 05 = Positive or Assumed Asbestos Sample Locations
= Asbestos Containing Material Locations
12 13
17,18
15, 16
34 35
42,43,44
The following table contains a list of 90 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number 12" x 12" Vinyl Floor Tile (VFT), Tan w/Gray Streaks/Mastic
PCS Building, PCS Area, Storage 001, 002, 2' x 4' Ceiling Tile PCS Building, PCS Area 004, 005, IRK ARSR
KIRKSVILLE MISSOURI
Brown Vinyl Cove Base (VCB) & Adhesive PCS Building, PCS Area, Storage 007, 008, Drywall System PCS Building, PCS Area, Storage 010, 011, Gray Sealant PCS Building, PCS Area 013, 014, Yellow Insulation PCS Building, PCS Area 016, 017, Gray Exterior Sealant Exterior PCS Building-South, Exterior PCS Building-North
019, 020, Red Fireproof Sealant Generator Room 022, 023, Brown Exterior Sealant Exterior Generator Room-South, Exterior Generator Room-East, Exterior Generator Room-North
025, 026, Gray Exterior Sealant Exterior Generator Room-South, Exterior Generator Room-East, Exterior Generator Room-North
028, 029, White Exterior Sealant PCS Exterior 031, 032, Gray Exterior Sealant PCS Exterior 034, 035, 12" x 12" VFT, Tan w/Brown Streaks/Mastic ARSR Office/Kitchen, ARSR Electronics Room, ARSR Transmitter Room
037, 038, 2' x 4' White Ceiling Tile ARSR Restroom, ARSR Office/Kitchen 040, 041, Gray Caulk ARSR Transmitter Room 043, 044, 12" x 12" VFT, Lt. Tan w/Mastic ARSR Electronics Room, Under ATCBI-6 Cabinet 046, 047,048
Yellow Insulation ARSR Electronics Room 049, 050, Gray Sink Insulation ARSR Office Kitchen 052, 053, White Caulk ARSR Exterior-East, ARSR Exterior-South, ARSR Exterior-West
055, 056, Clear Caulk ARSR Exterior-East 058, 059, Yellow HVAC Foam Insulation ARSR Exterior-West, ARSR Exterior-North 061, 062, White Sealant ARSR Exterior-West 064, 065, White HVAC Sealant ARSR Exterior-West 067, 068, Red Fireproof Sealant ARSR Electronics Room 070, 071, 9" x 9" VFT, Black w/Mastic FAA Storage 073, 074, White Door Caulk FAA Storage 076, 077, Clear Sealant Exterior FAA Storage 079, 080, White Caulk Exterior FAA Storage 082, 083, White Caulk ARSR Tower 085, 086, Gray Caulk ARSR Tower 088, 089, The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
46 12" x 12" Vinyl Floor Tile (VFT), Lt. Tan (M)
ARSR Electronics Room, Under ATCBI-6 Cabinet
N.F. I 30 SF Good 1 10% Chrysotile
46 Black Mastic Associated with Lt.
Tan 12" x 12" VFT (M)
ARSR Electronics Room, Under ATCBI-6 Cabinet
N.F. I 30 SF Good 1 15% Chrysotile
73 9" x 9" VFT, Black (M)
FAA Storage N.F. I 50 SF Fair 5 15% Chrysotile
73 Black Mastic Associated with 9" x 9" Black VFT (M)
FAA Storage N.F. I 50 SF Fair 5 15% Chrysotile
76 Door Caulk, Off White (M)
FAA Storage N.F. I 30 LF Good 1 3% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
IRK Kirksville MO ARSR 3 with generator, UPS and large storage buildings.
tim.jacobsen Typewriter Not Part of Inspection tim.jacobsen
LEGEND
- Negative Sample Number/Location
- Positive Sample Number/Location
019020
011 015
001 008 010
016 017 018
PCS AREASTORAGE
034 035 036031032033
- Positive Sample Number/Location
Generator Building
AutoCAD SHX Text SAMPLE LOCATION DRAWING - Generator Building
AutoCAD SHX Text N40 17 51.7 W92 34 33.9, Kirksville, MO 63546
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
204BS01749
AutoCAD SHX Text
GTW
AutoCAD SHX Text 7/9/18
AutoCAD SHX Text Fed Aviation Admin (FAA) - IRK ARSR
AutoCAD SHX Text Reviewed By:
AutoCAD SHX Text
KD
- Positive Sample Number/Location
043 044
066 067 068
061 064 065
070 071 072
046 047 048
Asbestos Containing Material Locations:
- Asbestos 12"x12" Lt. Tan Vinyl Floor
Tile and Asbestos Black Mastic
AutoCAD SHX Text SAMPLE LOCATION DRAWING - CARSR Equipment Room
AutoCAD SHX Text N40 17 51.7 W92 34 33.9, Kirksville, MO 63546
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
204BS01749
AutoCAD SHX Text
GTW
AutoCAD SHX Text 7/9/18
AutoCAD SHX Text Fed Aviation Admin (FAA) - IRK ARSR
AutoCAD SHX Text Reviewed By:
AutoCAD SHX Text
KD
N
- Positive Sample Number/Location
082 083
Asbestos Containing Material Locations:
- Asbestos 9"x9" Black Vinyl Floor Tile and
Asbestos Black Mastic
- Asbestos Door Caulk
AutoCAD SHX Text SAMPLE LOCATION DRAWING - FAA Storage
AutoCAD SHX Text N40 17 51.7 W92 34 33.9, Kirksville, MO 63546
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
204BS01749
AutoCAD SHX Text
GTW
AutoCAD SHX Text 7/9/18
AutoCAD SHX Text Fed Aviation Admin (FAA) - IRK ARSR
AutoCAD SHX Text Reviewed By:
KD
001 - Negative Sample Number/Location
001 - Positive Sample Number/Location
AutoCAD SHX Text SAMPLE LOCATION DRAWING - Radome Stairs
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
204BS01749
AutoCAD SHX Text
GTW
AutoCAD SHX Text 7/9/18
AutoCAD SHX Text Reviewed By:
AutoCAD SHX Text
KD
AutoCAD SHX Text N40 17 51.7 W92 34 33.9, Kirksville, MO 63546
Fed Aviation Admin (FAA) - IRK ARSR
The following table contains a list of 25 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Caulking Exterior (white) Exterior of the Radome panels LBF-01 Sealant (gray) Exterior HVAC units Equipment Building LBF-02 Caulking Exterior (white) Penatrations Equipment Building LBF-03 Caulking Exterior (gray/white) Equipment Building around all windows and Doors LBF-04 Wall System EFIS (white) Exterior of the Equipment Building LBF-05-0
Sealant Roof (black) Roof penatrations Equipment Building LBF-08 Adhesive (tan) Equipment Building Roof on Granding system LBF-09 Sealant (gray) Equipment Building on TSI for Fuel Lines LBF-10 TSI (thermal System Insulation) (tan) Equipment Building on Genorator Exhaust LBF-11-1
LBF ARSR
NORTH PLATTE NEBRASKA
Floor Coating (gray) Equipment Building Genorator room LBF-14 Cove Base (tan) Adhesive (yellow)
Equipment Builiding LBF-15
Floor Tile 12" x 12" (white mottled) Adhesive (yellow)
Equipment Building LBF-16
Floor Tile 9" x 9" (green) Mastic (black)
Equipment Building under equipment that cannot be moved
LBF-17
Ceiling Tile 2' x 4' (pinholes/fissures) Equipment Building LBF-18 Caulking Exterior (tan) Storage Shed (wooden) LBF-19 Asphalt Roof Shingle (brown) Storage Shed (wooden) LBF-20 Caulking Exterior (clear) White storage shed (metal) LBF-21 Caulking Exterior (gray) White storage shed (metal) LBF-22 Caulking (white) Small Storage Shed (metal) LBF-23 Floor TIle 9" x 9" (tan) Mastic (black)
Equipment Building Under Equipemnt that cannot be moved
LBF-24
Concrete/StyroFoam (gray/blue) Equipment Building Roof LBF-25
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
LBF-04 Exterior Caulk (gray/white) (M)
Equipment Building around all windows and Doors
N.F. II 500 LF Good 1 2% Chrysotile
LBF-17 Floor Tile (green 9"x 9") (M)
Equipment Room Under Equipment
N.F. II 100 SF Good 1 10% Chrysotile
LBF-17 Black Mastic (on green floor tile) (M)
Equipment Room Under Equipment
N.F. II 100 SF Good 1 5% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
LBF North Platte, NE
ARSR ½ with small storage buildings tony.colby tony.colby Rectangle tony.colby Textbox LBF-04, ACM caulking around all doors and windows.
tony.colby Textbox LBF-17, ACM floor Tile & Mastic located under equipment.
tony.colby tony.colby Textbox LBF-04, ACM caulking around all doors and windows.
The following table contains a list of twenty-eight (28) sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number White Exterior Caulk Radome BH-AB01, BH-AB02
Gray Floor Caulk Radome BH-AB03 Clear Silicone Caulk Radome Stair, North BH-AB04 Tan Caulk Radome Stair, North BH-AB05 Gray Caulk Radome Stair, North BH-AB06 Gray Exterior Window Caulk Radome Stair, South BH-AB07 Gray Exterior Door Caulk Radome Stair, South BH-AB08 Tan Vinyl Floor Tile and Black Mastic ARSR Facility Building BH-AB09 Red Caulk on Conduit Penetration ARSR Facility Building BH-AB10 White Caulk on Conduit Penetration ARSR Facility Building BH-AB11 Duct Seal ARSR Facility Building BH-AB12 Tan Floor Mastic ARSR Facility Building - Klystron Room BH-AB13 2'x4' White Fissured Ceiling Tile ARSR Facility Building - Office BH-AB14
QBN ARSR
BINNS HALL VIRGINIA
Gray Sink Mastic ARSR Facility Building - Office BH-AB15 Tan Exterior Door Caulk ARSR Facility Building BH-AB16 White Roof Caulk ARSR Facility Building BH-AB17 Black Roof Insulation ARSR Facility Building BH-AB18 White Exterior Concrete/Wall Caulk ARSR Facility Building BH-AB19 Gray Caulk and Fabric Insulation Exterior HVAC ARSR Facility Building BH-AB20 White Door Caulk Garage BH-AB21 Black Roof Shingle East Shed BH-AB22 Black Roof Shingle West Shed BH-AB23 12"x12" White Vinyl Floor Tile and White Mastic E.G. Building BH-AB24 Black Cove Base and Mastic E.G. Building BH-AB25 Red Caulk on Conduit Penetration E.G. Building BH-AB26 Duct Seal E.G. Building BH-AB27 Gray Exterior Caulk on Conduit Penetration E.G. Building - North Wall BH-AB28
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
BH-AB05 Tan interior caulk (M)
Radome Stair North (patches, interior corner of stairwell)
N.F. II 20 SF Good 1 5% Chrysotile
BH-AB09
layer 1
Tan vinyl floor tile (M)
ARSR Facility Building
N.F. I 80 SF Good 1 3% Chrysotile
BH-AB09
layer 2
Black mastic (M) ARSR Facility Building
N.F. II 80 SF Good 1 8% Chrysotile
BH-AB24 12" x 12" white vinyl floor tile (M)
E.G. Building N.F. I 300 SF Fair 5 3% Chrysotile
BH-AB28 Gray exterior caulk (M)
E.G. Building - North Wall
N.F. II 3 LF Fair 4 8% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
BUILDING SCHEMATIC
QBN Binns Hall, VA
ARSR 3 ~1500 sf with generator and several storage buildings
211 Expressway Court Virginia Beach, VA 23462
(757) 467-2100
PROJECT NO: 204BS01749
REVIEWED BY:ML SCALE: NTS DATE: 05-2018
SAMPLE LOCATION DRAWING
QBN ARSR
N37 22 58.4 W76 59 55.5
BINNS HALL, VIRGINIA 23140
Sample Locations
Positive Sample Locations
Main Building
Tower
E.G. Building Garage
BH-AB01
BH-AB02
BH-AB03
BH-AB04
BH-AB05
BH-AB06
BH-AB14
BH-AB09
BH-AB07
BH-AB08
BH-AB10 BH-AB11
BH-AB20
BH-AB12
BH-AB13
BH-AB15
BH-AB16
BH-AB17
BH-AB18
BH-AB19
East Shed West Shed
BH-AB22 BH-AB23
BH-AB21
BH-AB24 BH-AB26 BH-AB27BH-AB28 BH-AB25
211 Expressway Court Virginia Beach, VA 23462
(757) 467-2100
PROJECT NO: 204BS01749
REVIEWED BY:ML SCALE: NTS DATE: 05-2018
ACM LOCATION DRAWING
QBN ARSR
N37 22 58.4 W76 59 55.5
BINNS HALL, VIRGINIA 23140
Tan caulk
Tan vinyl floor tile and black mastic
Main Building
Tower
E.G. Building Garage East Shed West Shed
12”x12” white vinyl floor tile
Gray exterior caulk
The following table contains a list of sixty-nine (69) sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number 2" x 4" White Ceiling Tile Equipment Room - Kitchen 01-A 2" x 4" White Ceiling Tile Equipment Room - Kitchen 01-B 2" x 4" White Ceiling Tile Equipment Room - Kitchen 01-C White Caulk Radome Platform Deck 02-A White Caulk Radome Platform Deck 02-B White Caulk Radome Platform Deck 02-C 12" x 12" White Speckled Vinyl Floor Tile (VFT) Equipment Room - Transmitter Area 03-A 12" x 12" White Speckled VFT Equipment Room - Restroom 03-B 12" x 12" White Speckled VFT Equipment Room - Work Bench 03-C Mastic for 12" x 12" White Speckled VFT Equipment Room - Transmitter Area 04-A Mastic for 12" x 12" White Speckled VFT Equipment Room - Restroom 04-B Mastic for 12" x 12" White Speckled VFT Equipment Room - Work Bench 04-C 4" Black Covebase Covered Walkway/Storage 05-A 4" Black Covebase Covered Walkway/Storage 05-B
QCF ARSR
CLEARFIELD
PENSYLVANNIA
4" Black Covebase Covered Walkway/Storage 05-C Mastic for 4" Black Covebase Covered Walkway/Storage 06-A Mastic for 4" Black Covebase Covered Walkway/Storage 06-B Mastic for 4" Black Covebase Covered Walkway/Storage 06-C Gypsum Board Covered Walkway/Storage 07-A Gypsum Board Covered Walkway/Storage 07-B Gypsum Board Covered Walkway/Storage 07-C Joint Compound Covered Walkway/Storage 08-A Joint Compound Covered Walkway/Storage 08-B Joint Compound Covered Walkway/Storage 08-C Gray Caulk Covered Walkway/Storage 09-A Gray Caulk Covered Walkway/Storage 09-B Gray Caulk Covered Walkway/Storage 09-C White Caulk Exterior 10-A White Caulk Exterior 10-B White Caulk Exterior 10-C Black Expansion Caulk E/G Room 11-A Black Expansion Caulk E/G Room 11-B Black Expansion Caulk E/G Room 11-C White Caulk Radome Exterior 12 Brown Caulk AC Ductowork 13-A Brown Caulk AC Ductwork 13-B Brown Caulk AC Ductwork 13-C White Window Caulk Exterior 14-A White Window Caulk Exterior 14-B White Window Caulk Exterior 14-C Tan Caulk Radome Base 15-A Tan Caulk Radome Base 15-B Tan Caulk Radome Base 15-C Gray Caulk Radome Base 16-A Gray Caulk Radome Base 16-B Gray Caulk Radome Base 16-C Gray Sealant Exterior 17-A Gray Sealant Exterior 17-B Gray Sealant Exterior 17-C White Sealant Exterior 18-A White Sealant Exterior 18-B White Sealant Exterior 18-C Lightning Rod Adhesive (Brown/Yellow) Roof 19-A Lightning Rod Adhesive (Brown/Yellow) Roof 19-B Lightning Rod Adhesive (Brown/Yellow) Roof 19-C 12" x 12" White Speckled VFT E/G Room 20-A 12" x 12" White Speckled VFT E/G Room 20-B 12" x 12" White Speckled VFT E/G Room 20-C Mastic for 12" x 12" White Speckled VFT E/G Room 21-A Mastic for 12" x 12" White Speckled VFT E/G Room 21-B Mastic for 12" x 12" White Speckled VFT E/G Room 21-C Black Sealant E/G Room 22-A Black Sealant E/G Room 22-B Black Sealant E/G Room 22-C Brown Caulk E/G Room 23-A Brown Caulk E/G Room 23-B Brown Caulk E/G Room 23-C Lightning Rod Adhesive (Gray) Roof 24-A Lightning Rod Adhesive (Gray) Roof 24-B Lightning Rod Adhesive (Gray) Roof 24-C
None of the samples collected and analyzed through laboratory analysis were determined to be asbestos-containing materials.
None of the samples collected and analyzed through laboratory analysis were determined to be asbestos-containing materials.
NOTE: There are asbestos tiles located under several pieces of permanently mounted equipment that were not sampled at this facility
QCF Clearfield, PA
ARSR 3 with generator and
The following table contains a list of ten (10) sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Radome Caulking, White Exterior of Radome - Hatch Entryway RD-0419-
01A Radome Caulking, White Interior of Radome - East Wall RD-0419-
01B Radome Caulking, White Interior of Radome - West Wall RD-0419-
01C Seam Caulking, Grey Radome - Staircase - Antenna Deck RD-0419-
02A Seam Caulking, Grey Radome - Entry Door Casing - Mezzanine Level RD-0419-
02B Seam Caulking, Grey Radome - Lower Staircase - Mezzanine Level RD-0419-
02C 4' x 2' White Fissured Ceiling Panels Equipment Room - Restroom ER-0419-
03A
QNK ARSR
LINCOLNTON GEORGIA
4' x 2' White Fissured Ceiling Panels Equipment Room - UPS Room ER-0419- 03B
4' x 2' White Fissured Ceiling Panels Equipment Room - UPS Room ER-0419- 03C
Beige Vinyl Cove Base (VCB) with Yellow Mastic Equipment Room - UPS Room - South Wall ER-0419- 04A
Beige VCB with Yellow Mastic Equipment Room - UPS Room - North Wall ER-0419- 04B
Beige VCB with Yellow Mastic Equipment Room - UPS Room - West Wall ER-0419- 04C
Off-White & Beige Vinyl Floor Tile (VFT) with Clear Mastic
Restroom ER-0419- 05A
Off-White & Beige VFT with Clear Mastic South Section of Equipment Room ER-0419- 05B
Penetration Caulk, White Exterior - West Side of Building - Duct Work MB-0419- 06A
Penetration Caulk, White Exterior - West Side of Building - Duct Work MB-0419- 06A
Penetration Caulk, White Exterior - West Side of Building - Duct Work MB-0419- 06A
Duct Sealant, White Exterior - North Side Of Building - Duct Work MB-0419- 07A
Duct Sealant, White Exterior - North Side Of Building - Duct Work MB-0419- 07B
Duct Sealant, White Exterior - North Side Of Building - Duct Work MB-0419- 07C
12" x 12" Grey VFT with Clear Mastic Generator Building - West GB-0419- 08A
12" x 12" Grey VFT with Clear Mastic Generator Building - East GB-0419- 08B
Grey VCB with Black and Beige Mastic Generator Building GB-0419- 09A
Grey VCB with Black and Beige Mastic Generator Building GB-0419- 09B
Grey VCB with Black and Beige Mastic Generator Building GB-0419- 09C
Exhaust Duct Insulation, White Exhaust Duct GB-0419- 10A
Exhaust Duct Insulation, White Exhaust Tank GB-0419- 10B
Exhaust Duct Insulation, White Exhaust Tank GB-0419- 10C
None of the samples collected and analyzed through laboratory analysis were determined to be asbestos-containing materials.
NOTE: There are asbestos tiles located under several pieces of permanently mounted equipment that were not sampled at this facility
BUILDING SCHEMATIC
QNK Lincolnton, GA
ARSR3 with generator and
QNM ARSR
NEWPORT MISSISSIPPI
The following table contains a list of 43 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Caulk - White Radome Walls QNM-CK
1-01 Caulk - White Radome Walls QNM-CK
1-02 Caulk - White Radome Walls QNM-CK
1-03 Metal Floor Panel Mastic - Grey/Silver Radome Floor QNM-CK
2-04 Metal Floor Panel Mastic - Grey/Silver Radome Floor QNM-CK
2-05 Metal Floor Panel Mastic - Grey/Silver Radome Floor QNM-CK
2-06 Expansion Caulk - Grey Radome Floor QNM-CK
3-07 Expansion Caulk - Grey Radome Floor QNM-CK
3-08 Caulk - White Radome Exterior Wall - Replacement Panel QNM-CK
4-09 Caulk - White Radome Exterior Wall - Replacement Panel QNM-CK
4-10 Corrugated Panel Coating - Silver Radar Tower QNM-CP
C1-11 Corrugated Panel Coating - Silver Radar Tower QNM-CP
C1-12 Corrugated Panel Coating - Silver Radar Tower QNM-CP
C1-13 Caulk - Grey/Silver Base of Radar Tower QNM-CK
5-14 Caulk - Grey/Silver Base of Radar Tower QNM-CK
5-15 Caulk - Grey/Silver Base of Radar Tower QNM-CK
5-16 Duct Sealant - Black Base of Radar Tower QNM-DS
1-17 Duct Sealant - Black Base of Radar Tower QNM-DS
1-18 Duct Sealant - Black Base of Radar Tower QNM-DS
1-19 Caulk - Grey Exterior Ductwork QNM-CK
6-20 Caulk - Grey Exterior Ductwork QNM-CK
6-21 Caulk - Off-White Exterior Base of Main Building QNM-CK
7-22 Caulk - Off-White Exterior Base of Main Building QNM-CK
7-23 Ceiling Tile - 2' x 4' Pinholes & Gouges Main Building Restroom QNM-CT
1-24 Ceiling Tile - 2' x 4' Pinholes & Gouges Main Building Office QNM-CT
1-25 Ceiling Tile - 2' x 4' Pinholes & Gouges Main Building Office QNM-CT
1-26 Cove Base Adhesive - Yellow Main Building Electronics Room QNM-CB
A1-27
Cove Base Adhesive - Yellow Main Building Transmitter Room QNM-CB A1-28
Floor Tile - 12" x 12" Cream w/ Beige Streaks Main Building Telecom Room QNM-FT1 -29
Floor Tile Mastic - Yellow Under FT1 QNM-FT1 -29
Floor Tile - 12" x 12" Cream w/ Beige Streaks Main Building Entry Way QNM-FT1 -30
Floor Tile Mastic - Yellow Under FT1 QNM-FT1 -30
Floor Tile - 12" x 12" Beige Main Building Electronics Room Under Equipment QNM-FT2 -31
Floor Tile Mastic - Black Under FT2 QNM-FT2 -31
Floor Tile - 12" x 12" Beige Main Building Electronics Room Under Equipment QNM-FT2 -32
Floor Tile Mastic - Black Under FT2 QNM-FT2 -32
Floor Tile - 12" x 12" Beige Main Building Electronics Room Under Equipment QNM-FT2 -33
Floor Tile Mastic - Black Under FT2 QNM-FT2 -33
Caulk - Brown Diesel Shop QNM-CK 8-34
Caulk - Brown Diesel Shop QNM-CK 8-35
Stucco - Brown Diesel Shop QNM-ST C1-36
Stucco - Brown Diesel Shop QNM-ST C1-37
Stucco - Brown Diesel Shop QNM-ST C1-38
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
QNM-CK
2-04,05,0
Metal Floor Panel Mastic - Grey/Silver (M)
Radome Floor N.F. I 425 SF Good 1 5-8% Chrysotile
QNM-DS
1-17,18,1
Duct Sealant - Black (M)
Base of Radar Tower
N.F. II 1 SF Good 1 20-25% Chrysotile
QNM-CK
7-23
Caulk - Off-White (M)
Exterior Base of Main Building
N.F. II 156 LF Good 1 3% Chrysotile
QNM-FT2
-31,32,33
Floor Tile - 12" Beige (M)
Main Building Electronics Room Under Equipment
N.F. I 75 SF Good 1 3-5% Chrysotile
QNM-FT2
-31,32,33
Floor Tile Mastic - Black (M)
Main Building Electronics Room Under Equipment
N.F. I 75 SF Good 1 5-10% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
QNM Newport, MS
ARSR 3 building ~1500 sf additional generator and storage
SITE SKETCH
DESIGNED BY: ATC SCALE: NTS
DRAWN BY: DG DATE: 5/11/18 FILE: SKETCH
REVIEWED BY: TJ
ASBESTOS SURVEY
PROJECT NO: 204BS01749 Air Route Surveillance Radar Shelter (ARSR) Site - QNM 32.947583, -89.844694
Newport, Mississippi 39079
Legend
East Shed
Generator Room
Radar Tower
03 = Negative Asbestos Sample Locations
05 = Positive or Assumed Asbestos Sample Locations
= Asbestos Containing Material Locations
17,18,19
14,15
Main Building
North Shed
36,37 34,35
SITE SKETCH
DESIGNED BY: ATC SCALE: NTS
DRAWN BY: DG DATE: 5/11/18 FILE: SKETCH
REVIEWED BY: TJ
ASBESTOS SURVEY
PROJECT NO: 204BS01749 Air Route Surveillance Radar Shelter (ARSR) Site - QNM 32.947583, -89.844694
Newport, Mississippi 39079
Legend
Stairwell
Radome
03 = Negative Asbestos Sample Locations
05 = Positive or Assumed Asbestos Sample Locations
= Asbestos Containing Material Locations
05 = Positive or Assumed Asbestos Sample Locations
03 = Negative Asbestos Sample Locations
8246 Marshall Drive Lenexa, Kansas 66214
SITE SKETCH
DESIGNED BY: ATC SCALE: NTS
DRAWN BY: DG DATE: 5/11/18 FILE: SKETCH
REVIEWED BY: TJ
ASBESTOS SURVEY
PROJECT NO: 204BS01749 Air Route Surveillance Radar Shelter (ARSR) Site - QNM 32.947583, -89.844694
Newport, Mississippi 39079
Legend
= Asbestos Containing Material Locations
23 20 21 22
The following table contains a list of 25 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Green 9" x 9" Floor Tile with Black Mastic Equipment Building, Beneath Limited Equipment and Kitchen Cabinets 01-01
Tan Cove Base with Yellow Mastic Equipment Building 02-02 Wallboard Equipment Building Kitchenette 03-03 Restroom Wall Covering and Mastic Equipment Building Restroom 04-04 12" x 12" Beige Vinyl Floor Tile with Yellow Mastic Equipment Building 05-05 1' x 1' Ceiling Tile Equipment Building Kitchenette 06-06 Joint Compound Equipment Building Closet 07-07 Grey HVAC Putty Equipment Building Interior 08-08 Tan HVAC Putty Equipment Building Interior 09-09 White Caulk Radome 10-10
QOJ ARSR
JOELTON TENNESEE
Black Tar Radome Radio Motor Box 12-12 Grey Cement Fire Stop Equipment Building Pipe Chase Filler 13-13 White/Red Fire Stop Equipment Building Pipe Chase Filler 14-14 White Window Glaze Equipment Building Windows 15-15 White/Tan Ceiling Panel Equipment Building Restroom 16-16 2'x4' White/Brown Ceiling Panel Equipment Building Office 17-17 2' x 4' White/Yellow Ceiling Panel Equipment Building Above Kitchenette 18-18 Light Grey HVAC Caulk Equipment Building Exterior 19-19 Dark Grey HVAC Caulk Equipment Building Exterior 20-20 Textured Paint Equipment Building Exterior 21-21, 21-22, 21-23
Shingle Flashing Equipment Building Roof 22-24 Tar Flashing Equipment Building Roof 23-25 Asphaltic Tar Pebble Roof Equipment Building Roof 24-26
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
01-01 Green 9" x 9" Floor Tile with Black Mastic (M)
Equipment Building, Beneath Limited Equipment and Kitchen Cabinets
N.F. I 91 s.f. Good 1 Tile-2% Chrysotile Mastic-2% Chrysotile
12-12 Radio Antenna Black Tar (M)
Radome - Radio Motor Box
N.F. II 10 s.f. Good 2 2% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
QOJ Joelton, TN ARSR ½ with small storage
The following table contains a list of 18 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number White 2' x 4' ceiling tile Over main equipment room floor near main entry door 01-01
Tan mastic associate w/tan covebase Wall next to UPS Room door 02-02 Beige 12" x 12" floor tile Behind east HVAC unit 03-03
(layer 1) Yellow mastic associated w/beige 12" x 12" floor tile
Behind east HVAC unit 03-03 (layer 2)
Green 9" x 9" floor tile Under legacy racks/cabinets and battery rack in UPS Room
04-04
Drywall system (Drywall & Joint Compound) Restroom wall near kitchen door 05-05 Yellowish-brown insulation Restroom adjacent to kitchen and UPS room 06-06 Blue/gray 12" x 12" floor tile Under ATCB1-6 cabinets and battery rack in UPS room 07-07
QRI ARSR
LYNCH KENTUCKY
Yellow mastic associated with blue/gray 12" x 12" floor tile
Under ATCB1-6 cabinets and battery rack in UPS room
07-07
Gray 12" x 12" floor tile Under battery rack in UPS room (middle layer) 08-08 Gray HVAC seam sealant On east HVAC unit in equipment building - south wall 09-09
Gray/pink sink undercoating Kitchen sink - bottom side 10-10 Gray/clear caulking On plumbing cover adjacent to restroom exterior 11-11 Green/black asphalt shingle roofing material On utility cover box - south exterior wall adjacent to restroom 12-12
White caulk On exterior wall penetration - south side middle 13-13 Black coating/paint Base of radome tower frame 14-14 CMU scratch coating Exterior wall - northeast corner 15-15 CMU scratch coating Exterior wall - near northwest corner 15-16 CMU scratch coating Exterior wall - southwest corner 15-17
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
04-04 Green 9" x 9" Floor Tile (M)
Under equipment cabinets and battery rack in UPS room
N.F. I 85 sq.ft. Good 1 5.1% Chrysotile
10-10 Gray/Pink Sink Undercoating (M)
Kitchen sink N.F. I 1 unit Good 1 1.8% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
QRI Lynch, KY ARSR ½ building with office addition
N
ATC GROUP SERVICES LLC
2724 River Green Circle
Louisville, KY 40206
DATE: May 8, 2018
PROJECT No.: 204BS01749
DRAWN BY: JC
APPROVED BY: JC
APPROXIMATE SCALE: NOT TO SCALE
SOURCE: FAA
Sampling and ACM Location Plan
Asbestos Survey
QRI ARSR
N36 54 58.0 W82 53 28.0
Lynch, KY
01-01
02-02
03-03
04-04
05-05
06-06
07-07 08-08
09-09
10-10
11-11 12-1213-13
LEGEND
01-01 Bulk Sample Location
Located Under Battery Rack
ACM – Green 9”x9” Floor Tile
ACM – Sink Undercoating
15-15 15-16
15-17 14-14 – on base of tower support
The following table contains a list of 79 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Radome panel caulk Radome panel seam QWC-1 Radome panel caulk Radome panel seam QWC-2 Radome panel caulk Radome panel seam QWC-3 Black sealant Radome steel support base QWC-4 Black sealant Radome steel support base QWC-5
QWC ARSR
MESA RICA
NEW MEXICO
Gray seam sealant Radome concrete pad seams QWC-6 Gray seam sealant Radome concrete pad seams QWC-7 Textured paint Equipment building office wall QWC-8 Textured paint Equipment building office wall QWC-9 Textured paint Equipment building office wall QWC-10 Drywall and joint compound Equipment building office QWC-11 Drywall and joint compound Equipment building office QWC-12 Drywall and joint compound Equipment building office QWC-13 12 x 12" Tan mottled floor tile and mastic Equipment building office QWC-14 12 x 12" Tan mottled floor tile and mastic Equipment building equipment room QWC-15 12 x 12" Tan mottled floor tile and mastic Equipment building equipment room QWC-16 Tan cove base and mastic Equipment building equipment room QWC-17 Tan cove base and mastic Equipment building equipment room QWC-18 Tan cove base and mastic Equipment building rest room QWC-19 2' x 4' Perforated ceiling tile Equipment building equipment room QWC-20 2' x 4' Perforated ceiling tile Equipment building equipment room QWC-21 2' x 4' Fissured ceiling tile Equipment building equipment room QWC-22 2' x 4' Fissured ceiling tile Equipment building equipment room QWC-23 9" x 9" Green floor tile and mastic Equipment building equipment room QWC-24 Stucco Equipment building exterior wall QWC-25 Stucco Equipment building exterior wall QWC-26 Stucco Equipment building exterior wall QWC-27 Stucco Equipment building exterior wall QWC-28 Stucco Equipment building exterior wall QWC-29 Stucco Equipment building exterior wall QWC-30 Stucco Equipment building exterior wall QWC-31 Vent frame caulk Equipment building E/G room QWC-32 Vent frame caulk Equipment building E/G room QWC-33 White caulk Equipment building at lightening ground wire conduit
QWC-34
Door frame caulk Equipment building exterior at main front door QWC-35 Paint on CMU Equipment building exterior under stucco QWC-36 Paint on CMU Equipment building exterior under stucco QWC-37 Paint on CMU Equipment building exterior under stucco QWC-38 Vent frame caulk Equipment building exterior at E/G air vent QWC-39 Adhesive Equipment building roof at lightening cable bracket QWC-40 Adhesive Equipment building roof at lightening cable bracket QWC-41 Conduit caulk Exterior at radome tower QWC-42 Roofing materials Garage roof QWC-43 Roofing materials Garage roof QWC-44 Roofing materials Garage roof QWC-45 Stucco Garage exterior wall QWC-46 Stucco Garage exterior wall QWC-47 Stucco Garage exterior wall QWC-48 Caulking Garage exterior at soffit and fascia board QWC-49 12" x 12" White floor tile and mastic House/office entryway closet QWC-50 12" x 12" White floor tile and mastic House/office kitchen behind door QWC-51 Carpet mastic House/office, office area northeast corner QWC-52 Carpet mastic House/office hallway QWC-53 12" x 12" ceiling tile House/office entryway closet QWC-54 12" x 12" ceiling tile House/office, office closet QWC-55 Gray cove base and mastic House/office kitchen southwest at door QWC-56 Gray cove base and mastic House/office kitchen and hallway corner QWC-57 Brown cove base and mastic House/office bathroom southwest by door QWC-58 Brown cove base and mastic House/office bathroom behind bathroom door QWC-59 12" x 12" Brown streaked floor tile and mastic House/office bathroom closet under heater QWC-60 12" x 12" Brown streaked floor tile and mastic House/office bathroom closet under heater QWC-61 Square pattern sheet flooring and mastic House/office bathroom QWC-62 Square pattern sheet flooring and mastic House/office bathroom QWC-63 Drywall and joint compound House/office, office area northeast corner QWC-64
Drywall and joint compound House/office, office closet QWC-65 Drywall and joint compound House/office bathroom behind door QWC-66 Paint on CMU House/office entryway closet QWC-67 Paint on CMU House/office bathroom closet QWC-68 Paint on CMU House/office, office closet QWC-69 Stucco House/office exterior south side by storage/pump room
QWC-70
Stucco House/office exterior south side QWC-71 Stucco House/office vestibule QWC-72 Roofing materials House/office roof QWC-73 Roofing materials House/office roof QWC-74 Roofing materials House/office roof QWC-75 Brown floor tile and mastic House/office hallway under carpet QWC-76 Exterior CMU paint House/office storage/pump room QWC-77 Exterior CMU paint House/office storage/pump room QWC-78 Exterior CMU paint House/office storage/pump room QWC-79
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
QWC-24 9" x 9" Green floor tile and black mastic (M)
Equipment room, under equipment racks
N.F. I Approxim ately 110
SF
Good 1 Floor Tile 15%
Chrysotile Mastic 10% Chrysotile
QWC-32 Vent frame caulk, gray (M)
Equipment building E/G room
N.F. I Approxim ately 24
LF
Good 1 5% Chrysotile
QWC-33 Vent frame caulk, gray (M)
Equipment building E/G room
N.F. I Quantity reflected above
Good 1 2% Chrysotile
QWC-60 12" x 12" Brown streaked floor tile and mastic (M)
House/office bathroom closet, under heater
N.F. I Approxim ately 25
SF
Good 1 Floor Tile 2% Chrysotile
QWC-61 12" x 12" Brown streaked floor tile and mastic (M)
House/office bathroom closet, under heater
N.F. I Quantity reflected above
Good 1 Floor Tile 2% Chrysotile
QWC-76 Brown floor tile and mastic (M)
House/office hallway under carpet
N.F. I Approxim ately 750
SF
Good 1 Floor Tile 15%
Chrysotile;
Mastic 10% Chrysotile
QWC-77 Exterior CMU paint (S)
House/office storage/pump room
N.F. II Approxim ately
1,500 SF
Good 1 3% Chrysotile
QWC-78 Exterior CMU paint (S)
House/office storage/pump room
N.F. II Quantity reflected above
Good 1 2% Chrysotile
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM
QWC Mesa Rica, NM
ARSR ½ with additional office and garage buildings.
(mastic is <1% asbestos)
CMU paint is <1% asbestos
The following table contains a list of 46 sampled accessible building materials suspected of containing asbestos:
TABLE 1: SUSPECT BUILDING MATERIALS
Material Material Sample Location Sample
Number Seal Tab Roofing and Tar Living Quarters Roof 1-5 Drywall Garage 6-8 White Caulk Garage Exterior 9 Exterior Caulk Type 1 Exterior Window 10 Exterior Caulk Type 2 Exterior Window 11 Firestop Caulk Exterior East 12 Ladder Tread Exterior AST 13 CMU Wall Patch CMU Wall 14 Block Filler Exterior Wall 15-19 Radome Caulk Radome 20 Caulk Paint Exterior Radome Base 21
RKS ARSR
ROCK SPRINGS
WYOMING
BUILDING MATERIALS
#HAZARDASSESSMENTMATRIX
#HAZARDASSESSMENTMATRIX
Caulk Radome Structure 22 Caulk Radome Superstructure 23 White Caulk Building Exterior 24 HVAC Caulk HVAC System 25 2' x 4' Ceiling Tile - Fissures Ceiling of Equipment Room 26 Beige Cove Base and Mastic Equipment Room 27 12" x 12" Resilient Floor Tile - White/Brown Equipment Room 28 12" x 12" Resilient Floor Tile - Green Living Quarters 29 Brown Cove Base Living Quarters 30 Ceiling Tile Living Quarters 31 Wall System Living Quarters 32-34 Sink Undercoat Living Quarters 35-41 White Paint Exterior 42 Firestop Caulk Generator Room 43 9" x 9" Green Resilient Tile and Mastic Equipment Room 44 Lightning Rod Caulk Membrane Roof 45 Foundation Tar Exterior 46
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
TABLE 2: ASBESTOS CONTAINING MATERIALS
Sample Number
Material Description & Type (T, S, M)
Location Friability Quantity Condition Hazard Rank
Asbestos Content
9 White Caulk (M) Garage Exterior N.F. I 75 LF Good 1 10% 44 9" x 9" Green
Resilient Tile and Mastic (M)
Equipment Room (under equipment)
N.F. I 72 SF Good 1 55% Tile 15% Mastic
*N/A Membrane Roof Equipment Room N.F. I 3,000 Good 1 PACM
SF = square feet, LF= linear feet, ND = Non Detected, N/A= Not Applicable S = Surfacing, M= Miscellaneous, T= Thermal System Insulation Cat. I= Category I Non-friable ACM, Cat. II= Category II Non-friable ACM PACM= Presumed asbestos containing material
*Membrane roof not sampled to prevent damage and voiding warranties on the roof.
RKS Rock Springs, WY ARSR ½ with additional living quarters and garage.
Asbestos Sampling Locations
& Asbestos Material Locations
Living Quarters & Garage
Rock Springs, Wyoming
= Approximate location of white exterior asbestos caulk.
Asbestos Sampling & Asbestos
Material Locations
Equipment Room
Rock Springs, Wyoming
9”x 9” ACM Floor Tile Locations
Rock Springs RKS Tower
Rock Springs, Wyoming
Tower Shown
Vertically
No N-S
Orientation
Emergency Generator Room
Rock Springs, Wyoming
17 11