POWER
PULL BOXES / JUNCTION BOXES
MOTORS
GROUNDING AND LIGHTNING PROTECTION
MISCELLANEOUS
PANELBOARDS AND CABINETS
RACEWAYS
LIGHTING
SIGNAL/TELECOMMUNICATIONS GENERAL NOTES
SINGLE-LINE DIAGRAM
GFM EQUIPMENT
S
GROUND ROD, 10'-0"X3/4" DIA COPPER CLAD STEEL
PB
B
DOOR BELL PUSHBUTTON, MTD 4'-0" AFF
DOOR BELL, MTD 7'-0" AFF
SYMBOL
MOUNTING
+18"
+18"
+48"
AIR TERMINAL (24") (LIGHTNING PROTECTION)
MAIN GROUND PLATE
SUPPLEMENTAL GROUND PLATE
MULTIPOINT GROUND PLATE
MGP
OR
J
G
PC
+60"
+60"
+60"
+18"
HEIGHT, AFF DESCRIPTION SYMBOL DESCRIPTION
SYMBOL
MOUNTING
HEIGHT, AFF DESCRIPTIONSYMBOL
DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
MOUNTING
HEIGHT, AFF
DESCRIPTIONSYMBOL
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
CIRCUIT NUMBERS
HOMERUN CALLOUT INDICATING
(#12 UNLESS INDICATED OTHERWISE)
HOMERUN TO PANEL BOARD
NEUTRAL CONDUCTORS
CONDUCTORS
GROUND PHASE OR SWITCH LEG
T
JUNCTION BOX,
MOTOR
COPPER GROUNDING CONDUCTOR, EXPOSEDG
COMBINATION MOTOR STARTER, NEMA SIZE AS INDICATED
60/3
60/40/3
TRANSFORMER
+60"
P
T
HH
+18"
FAA
FO
BARE COPPER GROUNDING CONDUCTOR UNDERGRADE/IN SLAB
UNFUSED DISCONNECT SWITCH, WHERE 60/3 INDICATES NEMA
FRAME SIZE/NUMBER OF POLES
FUSED DISCONNECT SWITCH, WHERE 60/40/3 INDICATES NEMA
FRAME SIZE/FUSE SIZE/NUMBER OF POLES
3 = 4 = d = k = m =
2P =
OS =
NO TALLIES INDICATE 2 #12 & 1 #12G - 3/4" C, UON
EACH CIRCUIT SHALL HAVE SEPARATE, DEDICATED
NEUTRAL AND GROUND CONDUCTORS.
UNDERGROUND CONDUIT
FAA COMMUNICATION DUCTBANK
POWER DUCTBANK
TELCO DUCTBANK
FIBER OPTIC
CONDUIT TURNING DOWN
CONDUIT TURNING UP
CONDUIT RISER, OR FLOOR SLEEVE
CONDUIT CAPPED
FLEXIBLE CONDUIT
LT = LIQUID TIGHT
CABLE TRAY (NOTED ON DRAWINGS)
ELECTRICAL HANDHOLE
SINGLE GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, WALL MOUNTED
QUADRUPLEX GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, WALL MOUNTED
DUPLEX GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, WALL MOUNTED
DUPLEX GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, FLOOR MOUNTED
SPECIAL PURPOSE OUTLET NEMA RATING INDICATED
LUTRON LIGHTING CONTROL SYSTEM BUTTON WALL STATION , UNO
SUBSCRIPT INDICATES
4" SQUARE DUCT WIREWAY
NOTED ON DRAWINGS
DESCRIPTIONSYMBOL
CONDUIT, CONCEALED IN WALLS &
CEILINGS
TRANSFORMER
GROUND
LUTRON WALL STATION -3-WAY
LUTRON WALL STATION -4-WAY
LUTRON WALL STATION DIMMER CONTROL
LUTRON WALL STATION -KEY OPERATED
MANUAL MOTOR STARTER WITH THERMAL OVERLOADS
& PAD LOCKABLE TOGGLE GUARD.
TWO-POLE MANUAL MOTOR STARTER
OCCUPANT SENSOR, FAIL SAFE TYPE WITH DAYLIGHT HARVESTING SENSOR
ELP1-17,19,21
2' LED WRAPAROUND LIGHTING FIXTURE, SURFACE MOUNTED,
TYPE INDICATED
SEE SPECIFICATIONS FOR GFM EQUIPMENT
GROUND ACCESS WELL
2'X4' RECESSED LED LIGHTING FIXTURE. FIXTURE WHICH
HAS 2 OR MORE LAMPS - UPPER CASE LETTER INDICATES TYPE.
LOWER CASE LETTER (a, b, ETC) INDICATES SWITCH CIRCUIT;
NUMBER (1, 2, ETC) INDICATES BRANCH CIRCUIT NUMBER.
4' LED WRAPAROUND LIGHTING FIXTURE, SURFACE MOUNTED,
TYPE INDICATED
4' LED STRIP LIGHTING FIXTURE, TYPE INDICATED
WALL-MOUNTED LIGHTING FIXTURE, TYPE INDICATED
RECESSED LED LIGHTING FIXTURE,
RECESSED LED, WALL WASHER LIGHTING FIXTURE,
PHOTOCELL
EMERGENCY LIGHTING FIXTURE UNIT ON INVERTER BACKUP, TYPE INDICATED
LED POLE MOUNTED LIGHTING FIXTURE, TYPE INDICATED
LED FLOODLIGHT, TYPE INDICATED
LED BOLLARD LIGHT FIXTURE, TYPE INDICATED
OBSTRUCTION LIGHTING FIXTURE, TYPE INDICATED
LPS NOTES
1. THE COMPLETED GROUNDING AND LIGHTNING PROTECTION SYSTEM SHALL MEET THE
"INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS, AND MATERIALS
PER UL96A- MOST CURRENT EDITION". ALL INSTALLATIONS SHALL BE IN COMPLIANCE
WITH FAA STD 19E.
2. THE LIGHTNING PROTECTION SYSTEM COMPONENTS SHALL COMPLY WITH NFPA 780 CLASS-II
SYSTEM INSTALLATION REQUIREMENTS.
3. ALL METALLIC OBJECTS WITHIN 6' OF ROOF COUNTERPOISE OR DOWN CONDUCTORS SHALL BE
BONDED WITH EXOTHERMIC WELD TO ROOF COUNTERPOISE OR DOWN CONDUCTORS.
MAGNETIC MOTOR STARTER, NEMA SIZE AS INDICATED
1. RECEPTACLES SHALL BE COLOR CODED AS PER SPECIFICATIONS, FAA-STD-1217F.
2. ALL COVER PLATES FOR RECEPTACLES, SWITCHES AND TELCO/LAN SHALL
BE BRUSHED STAINLESS STEEL, UON. ALL RECEPTACLE COVERS SHALL BE
3. PROVIDE SEISMIC RESTRAINTS ON ALL CONDUITS. PROVIDE SEISMIC DESIGN
SUBMITTAL FOR APPROVAL PRIOR TO INSTALLATION. SEE SPECIFICATION 26
05 48 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS FOR
ADDITIONAL REQUIREMENTS.
4. RECESSED/PENDANT/SURFACE-MOUNTED LIGHT FIXTURES SHALL HAVE
A MINIMUM OF TWO SEISMIC BRACING WIRE SUPPORTS (12 GAUGE) PER
FIXTURE. FOR PENDANT LIGHT FIXTURES, PROVIDE TRANSVERSE AND
LONGITUDINAL BRACING. FOR RECESSED LIGHT FIXTURES, FASTEN TO
CEILING GRID W/SHEET METAL SCREWS ON ALL FOUR SIDES.
5. MOUNT ALL PANELBOARDS AND CABINETS ON TYPE A/C PLYWOOD. MOUNT
PLYWOOD TO CONCRETE OR MASONRY WALLS USING SELF-DRILLING MASONRY
ANCHORS, 3/8" DIA. X MIN. 3 3/8" EMBEDMENT (HILTI: HSE 2421). SPACE BETWEEN
ANCHORS NOT TO EXCEED 2'-0". PAINT WITH FIRE RETARDANT PAINT, UON. PAINT
SHALL MATCH SURROUNDING WALL PAINT COLORS. FASTENTERS SHALL BE
6. PROVIDE CONNECTIONS TO ALL MOTORS, TO ALL HVAC AND PLUMBING
EQUIPMENT AND TO ALL OTHER EQUIPMENT PROVIDED UNDER OTHER
DIVISIONS OF WORK FROM DISCONNECT SWITCH, STARTER, J-BOX, ETC.
7. MINIMUM TRADE CONDUIT SIZE SHALL BE 3/4". MINIMUM POWER CONDUCTOR SIZE
8. ALL EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED STEEL.
9. ALL CONDUITS SHALL CONTAIN A GREEN GROUND WIRE SIZE IN ACCORDANCE
WITH THE 2014 EDITION OF THE NEC. CONDUIT SHALL NOT BE USED AS A
10. CRITICAL POWER TRANSFORMERS LOCATED IN THE TOWER AND IN TRANSFORMER
ROOMS IN BASE BUILDING SHALL HAVE ELECTROSTATIC
SHIELDING, LOW TEMPERATURE RISE (115 C DEGREE) WITH 115 DEGREE C
INSULATION AND K13 RATED WITH COPPER WINDINGS.
11. ALL HARDWARE, INCLUDING CLAMPS, BOLTS, NUTS, WASHERS, STRUTS, ANCHOR
BOLTS, ANGLES, ETC. USED TO SUPPORT OR INSTALL ANY EXTERIOR (AND
NON-CONDITIONED LOCATIONS) HANDRAIL, EQUIPMENT, PIPE, CONDUIT, BOX
OR OTHER DEVICE SHALL BE STAINLESS STEEL AISI 316.
2-POSITION TELEPHONE OUTLET. MTD 18" AFF UON,
PROVIDE 1-1"C WITH PULL STRING FROM OUTLET TO CABLE TRAY
4-POSITION TELEPHONE/LAN/ OUTLET W/2 VOICE AND 2 DATA,
MTD 18" AFF UON, PROVIDE 2-1"C WITH PULL STRING FROM OUTLET
TO CABLE TRAY
TELEPHONE/LAN/ OUTLET, FLOOR MOUNTED, PROVIDE 2-1"C
WITH PULL STRING FROM FLOOR OUTLET TO NEAREST WALL, UP
WALL TO CABLE TRAY
4'X8'X3/4" TYPE A/C PLYWOOD (WITH GRADE A ON EXPOSED FACE)
BACKBOARD WITH FIRE RETARDANT PAINT, UON. PAINT SHALL
MATCH SURROUNDING WALL PAINT COLORS. FASTENERS SHALL BE
RECESSED AND HOLES FILLS WITH PUTTY. FIRMLY ATTACH TO WALL
+18" DUPLEX GROUNDED HEAVY DUTY RECEPTACLE, GFCI, 20A, 125V, WALL MOUNTED
PANELBOARD, SURFACE
MOUNTED, ESSENTIAL OR CRITICAL
'PH' ON SINGLE LINE DIAGRAM INDICATES
PHASE
+78" (TOP)
SHALL BE #12 THHN. PREWIRED LIGHT WHIPS SMALLER THAN 3/4" ARE ALLOWED.
RECESSED AND HOLES FILLED WITH PUTTY. FIRMLY ANCHOR TO WALL FOR
SEISMIC MOVEMENT.
12. PROVIDE PULLBOX IN ALL CONDUIT RUNS THAT EXCEED FOUR NINETY DEGREE TURNS
FOR POWER AND THREE NINETY DEGREE TURNS FOR TELECOMM SYSTEM. COORDINATE
LOCATION OF PULLBOXES WITH CONDUIT, LIGHTS, DUCTWORK, PIPING, ETC.
13. FOR TOWER CONDUITS-EXPOSED/SURFACE MOUNTED CONDUIT IS ACCEPTABLE IN THE
TOWER WITH THE EXCEPTION OF AREAS WITH SUSPENDED CEILINGS. CONDUIT IN
AREAS OF SUSPENDED CEILINGS SHALL BE RUN ABOVE THE CEILING OR CONCEALED
IN WALLS.
14. PROVIDE GROUNDING BUSHINGS ON ALL FEEDER CIRCUITS (BOTH ENDS AND AT ALL
PULL/JUNCTION BOXES IN BETWEEN).
LABELED SO AS TO IDENTIFY POWER SOURCE (PANEL AND CIRCUIT BREAKER).
2'X2' RECESSED LED LIGHTING FIXTURE, TYPE INDICATED
TYPE INDICATED
TYPE INDICATED
FOR SEISMIC MOVEMENT
TYPICAL FOR ALL LIGHTING FIXTURES
SGP
MPGP
CONTROL MODULE FOR DIMMING SYSTEM
CM1
2'X4' RECESSED LED LIGHTING FIXTURE ON FLS BUS.
FIXTURE WHICH HAS 2 OR MORE LAMPS - UPPER CASE LETTER INDICATES TYPE.
LOWER CASE LETTER (a, b, ETC) INDICATES SWITCH CIRCUIT;
NUMBER (1, 2, ETC) INDICATES BRANCH CIRCUIT NUMBER.
TYPICAL FOR ALL LIGHTING FIXTURES
15. MAINTAIN MINIMUM HEADROOM CLERANCE OF 84".
GROUNDING CONDUCTOR.
16. ALL EXTERIOR RECEPTACLES SHALL BE WEATHER-RESISTANT (WR) WITH
WEATHERPROOF(WP) COVER WHILE ATTACHMENT PLUG IS INSERTED INTO RECEPTACLE.
4' LED STRIP LIGHTING FIXTURE, TYPE INDICATED, ON FLS BUS
17. EACH CIRCUIT SHALL HAVE SEPARATE, DEDICATED NEUTRAL AND GROUND
CONDUCTORS.
2'X2' RECESSED LED LIGHTING FIXTURE ON FLS BUS, TYPE INDICATED
4' LED WRAPAROUND LIGHTING FIXTURE ON INVERTER BACKUP,
SURFACE MOUNTED, TYPE INDICATED
2' LED WRAPAROUND LIGHTING FIXTURE ON FLS BUS,
SURFACE MOUNTED, TYPE INDICATED
OS CEILING MOUNTED OCCUPANCY SENSOR, DUAL TECHNOLOGY TYPE
WITH DAY LIGHT HARVESTING SENSOR
RECESSED LED LIGHTING FIXTURE ON FLS BUS, TYPE INDICATED
WP = WEATHER PROOF SWITCH COVER
EXPOSED CONDUIT
DISTRIBUTION EQUIPMENT NAME LEGEND
BREAKER NAME LEGEND
(EQUIPMENT NAME + FUNCTION)
BREAKER DESIGNATION BY FUNCTION
FB FEEDER BREAKER
GB GENERATOR BREAKER
GM GENERATOR MAIN
GMBB GENERATOR MAINTENANCE BYPASS BREAKER
IB ISOLATION BREAKER
LBB LOAD BANK BREAKER
MB MAIN BREAKER
MBB MAINTENANCE BYPASS BREAKER
MF MAINTENANCE FEEDER
MIB MAINTENANCE ISOLATION BREAKER
MS MAIN SWITCH
NM NORMAL UTILITY POWER MAIN
RIB RECTIFIER INPUT BREAKER
SBB SYSTEM BYPASS BREAKER
TB TIE-BREAKER
KEY INTERLOCK LEGEND
BREAKER ABLE TO BE CLOSED WITH KEY
HELD CAPTIVE
K1
BREAKER LOCKED OPEN AND KEY ABLE
TO BE REMOVED
K1
WR = WATER RESISTANT SWITCH
2-POSITION DATA OUTLET. MTD 18" AFF UON,
PROVIDE 1-1"C WITH PULL STRING FROM OUTLET TO CABLE TRAY
t = TIMER SWITCH
WP = WEATHER PROOF RECEPTACLE COVER
WR = WATER RESISTANT RECEPTACLE
AIR TERMINAL (5'-0")(LIGHTNING PROTECTION)
3t = 3-WAY TIMER SWITCH
4' LED COVE LIGHTING FIXTURE, TYPE INDICATED.
DL CEILING MOUNTED DAYLIGHT HARVESTING SENSOR
P DUAL CHANNEL POWER POLE WITH RECEPTACLES AS NOTED.
2'X4' RECESSED LED LIGHTING FIXTURE ON INVERTER BACKUP.
FIXTURE WHICH HAS 2 OR MORE LAMPS - UPPER CASE LETTER INDICATES TYPE.
LOWER CASE LETTER (a, b, ETC) INDICATES SWITCH CIRCUIT;
NUMBER (1, 2, ETC) INDICATES BRANCH CIRCUIT NUMBER.
TYPICAL FOR ALL LIGHTING FIXTURES
2'X2' RECESSED LED LIGHTING FIXTURE ON INVERTER BACKUP,
TYPE INDICATED
4' LED WRAPAROUND LIGHTING FIXTURE ON FLS BUS,
SURFACE MOUNTED, TYPE INDICATED
2' LED WRAPAROUND LIGHTING FIXTURE ON INVERTER BACKUP,
SURFACE MOUNTED, TYPE INDICATED
4' LED STRIP LIGHTING FIXTURE, TYPE INDICATED, ON INVERTER BACKUP
EXIT SIGN WITH BATTERY BACKUP, SINGLE OR DOUBLE FACE WITH MOUNTING AND
ARROWS AS INDICATED
FIRE PUMP CONTROLLER
W/AUTOMATIC TRANSFER SWITCH
AUTOMATIC TRANSFER SWITCH
WITH ISOLATION BYPASS
DELTA-WYE TRANSFORMER
DESCRIPTIONSYMBOL
MOLDED CASE CIRCUIT BREAKER
DISCONNECT SWITCH
SPD SURGE PROTECIVE DEVICE
BATTERY
ENCLOSED CIRCUIT BREAKER
UNINTERRUPTED POWER SUPPLY
STATIC TRANSFER SWITCH
WITH INTERNAL BYPASS BREAKERS
FEEDER CONTINUATION. REFER TO
KEYED NOTE REFERENCED ON E800
X
(SYSTEM + TYPE + VOLTS + PATH + NUMBER)
SYSTEM DESIGNATION EQUIPMENT TYPE
C CRITICAL POWER H 480 VOLTS
E ESSENTIAL POWER L 208Y/120 VOLTS
G GENERATOR POWER
LB LOAD BANK POWER PATH IDENTIFIER
SE UTILITY SERVICE ENTRANCE
U UPS POWER A PRIMARY BUSS
B ALTERNATE BUSS
EQUIPMENT TYPE M MAINTENANCE
T TEMPORARY
ATS AUTOMATIC TRANSFER SWITCH
D SAFETY SWITCH DISCONNECT NUMBER
DP DISTRIBUTION PANELBOARD (LINE)
GEN GENERATOR 1, 2, ETC.
LB LOAD BANK
P PANELBOARD
S SWITCHBOARD
STS STATIC TRANSFER SWITCH
T TRANSFORMER
UPS UNINTERRUPTIBLE POWER SUPPLY
FEEDER/CONDUIT DESIGNATION.
REFER TO SCHEDULE ON E805
XXX
ST SHUNT TRIP DEVICE
+60" ENCLOSED CIRCUIT BREAKER, NEMA SIZE AS INDICATED
MO MOTOR OPERATOR
18. CONTRACTOR SHALL ALLOCATE SUFFICIENT TIME FOR TESTING AND COMMISSIONING OF
ELECTRICAL SYSTEMS PER SPECIFICATION 26 00 02 SECTION 3.15 IN ORDER TO MEET
THE PROJECT MASTER SCHEDULE .
DOUBLE THROW
DISCONNECT SWITCH
CHECKED
URS project no.
Copyright © 2014 URS Corporation, All Rights Reserved
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
SIGNATURE:
DATE:
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
CLT-D-TRACO-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
TRACON
EASTERN SERVICE AREA ATLANTA, GEORGIA
CHARLOTTE NCCHARLOTTE DOUGLAS INTERNATIONAL AIRPORT (CLT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
400 Northpark Town Center,1000 Abernathy Road, NE.
Suite 900 Tel. No (678)808-8800
Atlanta, Georgia 30328
Fax. (678)808-8400
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
08/31/2015
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
1103700
110370008/31/2015 ISSUED FOR BID
8/
/2
:1 8:
A
M
8/31/2015 10:18:40 AM
15290056
JAW
KCV
E000
KCV
LEGENDS, SYMBOLS, & NOTES
REV
POWER
PULL BOXES / JUNCTION BOXES
MOTORS
GROUNDING AND LIGHTNING PROTECTION
MISCELLANEOUS
PANELBOARDS AND CABINETS
RACEWAYS
SIGNAL/TELECOMMUNICATIONS GENERAL NOTES
SINGLE-LINE DIAGRAM
GFM EQUIPMENT
S
GROUND ROD, 10'-0"X3/4" DIA COPPER CLAD STEEL
PB
B
DOOR BELL PUSHBUTTON, MTD 4'-0" AFF
DOOR BELL, MTD 7'-0" AFF
SYMBOL
MOUNTING
+18"
+18"
+48"
AIR TERMINAL (LIGHTNING PROTECTION)
MAIN GROUND PLATE
SUPPLEMENTAL GROUND PLATE
MULTIPOINT GROUND PLATE
MGP
OR
J
G
RAISED FLOOR PEDESTAL GROUND
+60"
+60"
+60"
+18"
HEIGHT, AFF DESCRIPTION SYMBOL DESCRIPTION
SYMBOL
MOUNTING
HEIGHT, AFF DESCRIPTIONSYMBOL
DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
MOUNTING
HEIGHT, AFF
DESCRIPTIONSYMBOL
SYMBOL DESCRIPTION
CIRCUIT NUMBERS
HOMERUN CALLOUT INDICATING
(#12 UNLESS INDICATED OTHERWISE)
HOMERUN TO PANEL BOARD
NEUTRAL CONDUCTORS
CONDUCTORS
GROUND PHASE OR SWITCH LEG
T
JUNCTION BOX,
MOTOR
COPPER GROUNDING CONDUCTOR, EXPOSEDG
COMBINATION MOTOR STARTER, NEMA SIZE AS INDICATED
60/3
60/40/3
TRANSFORMER
+60"
P
T
HH
+18"
FO
BARE COPPER GROUNDING CONDUCTOR UNDERGRADE/IN SLAB
UNFUSED DISCONNECT SWITCH, WHERE 60/3 INDICATES NEMA
FRAME SIZE/NUMBER OF POLES
FUSED DISCONNECT SWITCH, WHERE 60/40/3 INDICATES NEMA
FRAME SIZE/FUSE SIZE/NUMBER OF POLES
3 = 4 = D = k = m =
2P =
OS =
NO TALLIES INDICATE 2 #12 & 1 #12G - 3/4" C, UON
EACH CIRCUIT SHALL HAVE SEPARATE, DEDICATED
NEUTRAL AND GROUND CONDUCTORS.
UNDERGROUND CONDUIT
FAA COMMUNICATION DUCTBANK
POWER DUCTBANK
TELCO DUCTBANK
FIBER OPTIC
CONDUIT TURNING DOWN
CONDUIT TURNING UP
CONDUIT RISER, OR FLOOR SLEEVE
CONDUIT CAPPED
FLEXIBLE CONDUIT
LT = LIQUID TIGHT
CABLE TRAY (NOTED ON DRAWINGS)
ELECTRICAL HANDHOLE
SINGLE GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, WALL MOUNTED
QUADRUPLEX GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, WALL MOUNTED
DUPLEX GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, WALL MOUNTED
DUPLEX GROUNDED HEAVY DUTY RECEPTACLE, 20A, 125V, FLOOR MOUNTED
SPECIAL PURPOSE OUTLET NEMA RATING INDICATED
LUTRON LIGHTING CONTROL SYSTEM BUTTON WALL STATION, UON
SUBSCRIPT INDICATES
4" OR 6" SQUARE DUCT WIREWAY
NOTED ON DRAWINGS
DESCRIPTIONSYMBOL
CONDUIT, CONCEALED IN WALLS & CEILINGS
TRANSFORMER
MOLDED CASE CIRCUIT
BREAKER
GROUND
3-WAY (LUTRON LIGHTING CONTROL WALL STATION)
4-WAY (LUTRON LIGHTING CONTROL STATION)
DIMMER SWITCH (LUTRON LIGHTING CONTROL WALL STATION)
KEY OPERATED
MANUAL MOTOR STARTER WITH THERMAL OVERLOADS
& PAD LOCKABLE TOGGLE GUARD.
TWO-POLE MANUAL MOTOR STARTER
OCCUPANT SENSOR, FAIL SAFE TYPE
ELP1-17,19,21
SEE SPECIFICATIONS FOR GFM EQUIPMENT
GROUND ACCESS WELL
LPS NOTES
1. THE COMPLETED GROUNDING AND LIGHTNING PROTECTION SYSTEM SHALL MEET THE "INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS, AND MATERIALS PER UL96A- MOST CURRENT
EDITION". ALL INSTALLATIONS SHALL BE IN COMPLIANCE WITH FAA STD 19E.
2. THE LIGHTNING PROTECTION SYSTEM COMPONENTS SHALL COMPLY WITH NFPA 780 CLASS-II SYSTEM
INSTALLATION REQUIREMENTS.
3. ALL METALLIC OBJECTS WITHIN 6' OF ROOF COUNTERPOISE OR DOWN CONDUCTORS SHALL BE BONDED WITH
EXOTHERMIC WELD TO ROOF COUNTERPOISE OR DOWN CONDUCTORS.
MAGNETIC MOTOR STARTER, NEMA SIZE AS INDICATED
1. RECEPTACLES SHALL BE COLOR CODED AS PER SPECIFICATION FAA-STD-1217F.
2. PROVIDE IESNA COMPLIANT LIGHTING FIXTURES IN ALL AREAS.
3. ALL COVER PLATES FOR RECEPTACLES, SWITCHES AND TELCO/LAN SHALL
BE BRUSHED STAINLESS STEEL, UON. ALL RECEPTACLE COVERS SHALL BE
5. RECESSED/PENDANT/SURFACE-MOUNTED LIGHT FIXTURES SHALL HAVE
A MINIMUM OF TWO SEISMIC BRACING WIRE SUPPORTS (12 GAUGE) PER
FIXTURE. FOR PENDANT LIGHT FIXTURES, PROVIDE TRANSVERSE AND
LONGITUDINAL BRACING. FOR RECESSED LIGHT FIXTURES, FASTEN TO
CEILING GRID W/SHEET METAL SCREWS ON ALL FOUR SIDES.
6. MOUNT ALL PANELBOARDS AND CABINETS ON TYPE A-B PLYWOOD. MOUNT PLYWOOD
TO CONCRETE OR MASONRY WALLS USING SELF-DRILLING MASONRY
ANCHORS, 3/8" DIA. X MIN. 3 3/8" EMBEDMENT (HILTI: HSE 2421). SPACE
BETWEEN ANCHORS NOT TO EXCEED 2'-0". PAINT WITH FIRE RETARDANT
PAINT, UON. PAINT SHALL MATCH SURROUNDING WALL PAINT COLORS.
7. PROVIDE CONNECTIONS TO ALL MOTORS, TO ALL HVAC AND PLUMBING
EQUIPMENT AND TO ALL OTHER EQUIPMENT PROVIDED UNDER OTHER
DIVISIONS OF WORK FROM DISCONNECT SWITCH, STARTER, J-BOX, ETC.
8. MINIMUM TRADE CONDUIT SIZE SHALL BE 3/4". MINIMUM POWER CONDUCTOR
9. ALL EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED STEEL.
10. ALL CONDUITS SHALL CONTAIN A GREEN GROUND WIRE SIZE IN ACCORDANCE
WITH THE 2014 EDITION OF THE NEC. CONDUIT SHALL NOT BE USED AS A
11. ALL HARDWARE, INCLUDING CLAMPS, BOLTS, NUTS, WASHERS, STRUTS, ANCHOR
BOLTS, ANGLES, ETC. USED TO SUPPORT OR INSTALL ANY EXTERIOR (AND
NON-CONDITIONED LOCATIONS) HANDRAIL, EQUIPMENT, PIPE, CONDUIT, BOX
OR OTHER DEVICE SHALL BE STAINLESS STEEL AISI 316.
2-POSITION TELEPHONE OUTLET. MTD 18" AFF UON,
PROVIDE 1-1"C FROM OUTLET TO CABLE TRAY
4-POSITION TELEPHONE/LAN/ OUTLET W/2 VOICE AND 2 DATA,
MTD 18" AFF UON, PROVIDE 2-1"C FROM OUTLET TO CABLE TRAY
TELEPHONE/LAN/ OUTLET, FLOOR MOUNTED, PROVIDE 2-1"C
FROM FLOOR OUTLET TO NEAREST WALL, UP WALL TO CABLE TRAY
4'X8'X3/4" TYPE A/B PLYWOOD (WITH GRADE A ON EXPOSED FACE)
BACKBOARD WITH FIRE RETARDANT PAINT, UON. PAINT SHALL
MATCH SURROUNDING WALL PAINT COLORS. FASTENERS SHALL BE
RECESSED AND HOLES FILLS WITH PUTTY. FIRMLY ATTACH TO WALL
+18" DUPLEX GROUNDED HEAVY DUTY RECEPTACLE, GFCI, 20A, 125V, WALL MOUNTED
PANELBOARD, SURFACE
MOUNTED, ESSENTIAL OR CRITICAL
'PH' ON SINGLE LINE DIAGRAM
INDICATES PHASE
+78" (TOP)
FAA
SIZE SHALL BE #12 THHN. PREWIRED LIGHT WHIPS SMALLER THAN 3/4" ARE ALLOWED.
FASTENERS SHALL BE RECESSED AND HOLES FILLED WITH PUTTY. FIRMLY
ANCHOR TO WALL FOR SEISMIC MOVEMENT.
12. PROVIDE PULLBOX IN ALL CIRCUITS THAT EXCEED TWO NINETY DEGREE
TURNS. COORDINATE LOCATION OF PULLBOXES WITH CONDUIT, LIGHTS
DUCTWORK, PIPING, ETC.
13. FOR TOWER CONDUITS-EXPOSED/SURFACE MOUNTED CONDUIT IS
ACCEPTABLE IN THE TOWER WITH THE EXCEPTION OF AREAS WITH SUSPENDED
CEILINGS. CONDUIT IN AREAS OF SUSPENDED CEILINGS SHALL BE RUN ABOVE
THE CEILING OR CONCEALED IN WALLS.
14. PROVIDE GROUNDING BUSHINGS ON ALL FEEDER CIRCUITS (BOTH ENDS AND
AT ALL PULL/JUNCTION BOXES IN BETWEEN).
LABELED SO AS TO IDENTIFY POWER SOURCE (PANEL AND CIRCUIT BREAKER).
FOR SEISMIC MOVEMENT
SGP
MPGP
15. MAINTAIN MINIMUM HEADROOM CLEARANCE OF 84".
GROUNDING CONDUCTOR.
16. ALL EXTERIOR RECEPTACLES SHALL BE WEATHER-RESISTANT (WR) WITH WEATHER PROOF
(WP) COVER WHILE ATTACHMENT PLUG IS INSERTED INTO RECEPTACLE.
17. EACH CIRCUIT SHALL HAVE SEPARATE, DEDICATED NEUTRAL AND GROUND CONDUCTORS.
OS CEILING MOUNTED OCCUPANCY SENSOR, DUAL TECHNOLOGY TYPE
WP = WEATHER PROOF SWITCH COVER/RECEPTACLE COVER
EXPOSED CONDUIT
DISTRIBUTION EQUIPMENT NAME LEGEND
(SYSTEM + TYPE + VOLTS + PATH + NUMBER)
SYSTEM DESIGNATION
C CRITICAL POWER
E ESSENTIAL POWER
G GENERATOR POWER
LB LOAD BANK
SE UTILITY SERVICE ENTRANCE
U UPS POWER
EQUIPMENT TYPE
ATS AUTOMATIC TRANSFER SWITCH
D SAFETY SWITCH DISCONNECT
DP DISTRIBUTION PANELBOARD (I LINE)
GEN GENERATOR
LB LOAD BANK
P BRANCH CIRCUIT PANELBOARD
S SWITCHBOARD
STS STATIC TRANSFER SWITCH
T TRANSFORMER
UPS UNINTERRUPTIBLE POWER SUPPLY
VOLTAGE LEVEL
H 480 VOLTS
L 208Y/120 VOLTS
POWER PATH IDENTIFIER
A PRIMARY BUSS
B ALTERNATE BUSS
M MAINTENANCE
T TEMPORARY
NUMBER
1, 2, ETC.
BREAKER NAME LEGEND
(EQUIPMENT NAME + FUNCTION)
BREAKER DESIGNATION BY FUNCTION
FB FEEDER BREAKER
GB GENERATOR BREAKER
GM GENERATOR MAIN
GMBB GENERATOR MAINTENANCE BYPASS BREAKER
IB ISOLATION BREAKER
LBB LOAD BANK BREAKER
MB MAIN BREAKER
MBB MAINTENANCE BYPASS BREAKER
MF MAINTENANCE FEEDER
MIB MAINTENANCE ISOLATION BREAKER
MS MAIN SWITCH
NM NORMAL UTILITY POWER MAIN
RIB RECTIFIER INPUT BREAKER
SBB SYSTEM BYPASS BREAKER
TB TIE-BREAKER
KEY INTERLOCK LEGEND
BREAKER ABLE TO BE CLOSED WITH KEY
HELD CAPTIVE
K1
BREAKER LOCKED OPEN AND KEY ABLE
TO BE REMOVED
K1
WR = WATER RESISTANT SWITCH/RECEPTACLE
2-POSITION DATA OUTLET. MTD 18" AFF UON,
PROVIDE 1-1"C FROM OUTLET TO CABLE TRAY
t = TIMER SWITCH
4. PROVIDE SEISMIC RESTRAINTS ON ALL CONDUITS. PROVIDE SEISMIC DESIGN
SUBMITTAL FOR APPROVAL PRIOR TO INSTALLATION. SEE SPECIFICATION 26
05 48 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS FOR
ADDITIONAL REQUIREMENTS.
LIGHTING
PC
SYMBOL DESCRIPTION
EXIT SIGN WITH BATTERY BACKUP, SINGLE OR DOUBLE FACE WITH MOUNTING AND
ARROWS AS INDICATED
2' LED WRAPAROUND LIGHTING FIXTURE, SURFACE MOUNTED,
TYPE INDICATED
2'X4' RECESSED LED LIGHTING FIXTURE. FIXTURE WHICH
HAS 2 OR MORE LAMPS - UPPER CASE LETTER INDICATES TYPE.
LOWER CASE LETTER (a, b, ETC) INDICATES SWITCH CIRCUIT;
NUMBER (1, 2, ETC) INDICATES BRANCH CIRCUIT NUMBER.
4' LED WRAPAROUND LIGHTING FIXTURE, SURFACE MOUNTED,
TYPE INDICATED
4' LED STRIP LIGHTING FIXTURE, TYPE INDICATED
WALL-MOUNTED LIGHTING FIXTURE, TYPE INDICATED
RECESSED LED LIGHTING FIXTURE,
RECESSED LED, WALL WASHER LIGHTING FIXTURE,
PHOTOCELL
OBSTRUCTION LIGHTING FIXTURE, TYPE INDICATED
2'X2' RECESSED LED LIGHTING FIXTURE, TYPE INDICATED
TYPE INDICATED
TYPE INDICATED
TYPICAL FOR ALL LIGHTING FIXTURES
CONTROL MODULE FOR DIMMING SYSTEM
CM1
2'X4' RECESSED LED LIGHTING FIXTURE ON FLS BUS.
FIXTURE WHICH HAS 2 OR MORE LAMPS - UPPER CASE LETTER INDICATES TYPE.
LOWER CASE LETTER (a, b, ETC) INDICATES SWITCH CIRCUIT;
NUMBER (1, 2, ETC) INDICATES BRANCH CIRCUIT NUMBER.
TYPICAL FOR ALL LIGHTING FIXTURES
4' LED STRIP LIGHTING FIXTURE, TYPE INDICATED, ON FLS BUS
2'X2' RECESSED LED LIGHTING FIXTURE ON FLS BUS, TYPE INDICATED
4' LED WRAPAROUND LIGHTING FIXTURE ON INVERTER BACKUP,
SURFACE MOUNTED, TYPE INDICATED
2' LED WRAPAROUND LIGHTING FIXTURE ON FLS BUS,
SURFACE MOUNTED, TYPE INDICATED
RECESSED LED LIGHTING FIXTURE ON FLS BUS, TYPE INDICATED
2'X4' RECESSED LED LIGHTING FIXTURE ON INVERTER BACKUP.
FIXTURE WHICH HAS 2 OR MORE LAMPS - UPPER CASE LETTER INDICATES TYPE.
LOWER CASE LETTER (a, b, ETC) INDICATES SWITCH CIRCUIT;
NUMBER (1, 2, ETC) INDICATES BRANCH CIRCUIT NUMBER.
TYPICAL FOR ALL LIGHTING FIXTURES
2'X2' RECESSED LED LIGHTING FIXTURE ON INVERTER BACKUP, TYPE INDICATED
4' LED WRAPAROUND LIGHTING FIXTURE ON FLS BUS,
SURFACE MOUNTED, TYPE INDICATED
2' LED WRAPAROUND LIGHTING FIXTURE ON INVERTER BACKUP,
SURFACE MOUNTED, TYPE INDICATED
4' LED STRIP LIGHTING FIXTURE, TYPE INDICATED, ON INVERTER BACKUP
CENTRAL CONTROL UNIT FOR DIMMING SYSTEM
CCU
18. CONTRACTOR SHALL ALLOCATE SUFFICIENT TIME FOR TESTING AND COMMISSIONING OF
ELECTRICAL SYSTEMS PER SPECIFICATION 26 00 02 SECTION 3.15 IN ORDER TO MEET THE
PROJECT MASTER SCHEDULE .
DOUBLE THROW
DISCONNECT SWITCH
DESCRIPTIONSYMBOL
CHECKED
URS project no.
Copyright © 2013 URS Corporation, All Rights Reserved
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
SIGNATURE:
DATE:
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
CLT-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATCT
EASTERN SERVICE AREA ATLANTA, GEORGIA
CHARLOTTE NCCHARLOTTE DOUGLAS INTERNATIONAL AIRPORT (CLT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
400 Northpark Town Center,1000 Abernathy Road, NE.
Suite 900 Tel. No (678)808-8800
Atlanta, Georgia 30328
Fax. (678)808-8400
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
08/31/2015 1103700
0 110370008/31/2015 ISSUED FOR BID
8/
/2
2:
:0
PM
8/26/2015 2:10:09 PM
15290056
JAW
KCV
E000
KCV
LEGENDS, SYMBOLS, & NOTES
GENERAL NOTES (FOR SHEETS E801, E802, & E803)
REFER TO SHEETS E500 SERIES FOR PANEL SCHEDULES FOR SIZES AND QUANTITY OF SPARE
BREAKERS AND ADDITIONAL PREPARED SPACES FOR ALL EQUIPMENT.
PROVIDE FINAL ADJUSTMENTS OF RATINGS AND SETTINGS FOR ALL EQUIPMENT PER SHORT
CIRCUIT, ARC FLASH, AND COORDINATION CALCULATIONS. BEFORE ENERGIZING CONTRACTOR
TO FIELD VERIFY CABLE LENGTH AND SUBMIT TO FAA, AND ADJUST FEEDER CONDUCTOR AND
CONDUIT SIZES AS NECESSARY TO ACCOMMODATE FIELD CONDITIONS FOR VOLTAGE DROPS,
AND DERATING FOR BELOW SLAB, ETC. ADJUST FEEDER AND CONDUIT SIZES TO MATCH LUG
SIZE ON PANELBOARDS, SWITCHBOARDS AND SWITCHGEAR. PROVIDE ARC FLASH LABELING
FOR EQUIPMENT. SEE SHORT CIRCUIT COORDINATION STUDY TO BE PERFORMED BY SQUARE
D.
ALL BREAKERS AND SWITCHES SHALL BE IN NORMALLY CLOSED POSITION UNLESS OTHERWISE
NOTED.
FIRE PUMP CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH ALL APPLICABLE CODES
AND AS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
BREAKERS FOR SERVICES ABOVE 1000A SHALL BE GROUND FAULT PROTECTION (GFP) TYPE
BREAKERS, EXCEPT FOR BREAKERS ON THE FLS BUS, WHICH WILL HAVE GROUND FAULT
INDICATION (GFI).
TRANSFORMER DISCONNECTS SHALL BE LOCATED WITHIN 50 FEET OF TRANSFORMER.
LOCATE SPD AS CLOSE TO THE EQUIPMENT MAIN BREAKER AS POSSIBLE.
FOR CONDUCTOR AND CONDUIT SIZE, SEE DRAWING E805.
ALL SWITCHBOARDS, PANELBOARDS, AND CIRCUIT BREAKERS ARE GFE SQUARE D.
PROVIDE AND AFFIX PERMANENT LABELS TO EACH PIECE EQUIPMENT PER THE REQUIREMENTS
OF 26 05 53 -IDENTIFICATION OF ELECTRICAL SYSTEMS.
ALL CIRCUIT BREAKERS SHALL HAVE PERMANENTLY INSTALLED PADLOCKING ATTACHMENTS.
ALL CONDUITS, CONDUCTORS, AND CONTROL SIGNAL CABLES SHALL BE PROVIDED BY THE
CONTRACTOR.
THE NEUTRAL TERMINAL OF THE SPD SHALL NOT BE LEFT UNCONNECTED. CONNECT NEUTRAL
TERMINAL PER MANUFACTURER'S REQUIREMENTS.
REFER TO E807 AND E807 FOR BREAKER SCHEDULES.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
KEYED NOTES (FOR SHEETS E801, E802, & E803)
TRIP UNIT POWER FROM LINE SIDE OF BREAKER. VOLTAGE SENSING ON LINE SIDE OF BREAKER. PROVIDE TRIP UNIT WITH
VOLTAGE/CURRENT DISPLAY.
REMOTELY CONTROLLED BREAKER WITH RECLOSER.
SESHA-MB AND SESHB-MB REMOTE CONTROL SWITCH (GFE) - SELECTOR SWITCH, 3-POSITION MOMENTARY-MAINTAINED- MOMENTARY SPRING RETURN TO CENTER, 600V, 10A, 2NO-2NC CONTACTS; CODE B, WITH ONE RED AND ONE GREEN LIGHT.
INSTALLED INSIDE A NEMA 4X S.S. BOX WITH WINDOW. INSTALL OUTSIDE CIRCUIT BREAKER ARC FLASH BOUNDARY.
UNDERGROUND CONDUIT. CONDUIT SHALL BE CAPPED AT EACH END WITH FIRE STOPPING PUTTY AFTER INSTALLATION OF
CONDUCTORS OR PULL STRINGS.
INCOMING MAIN LUGS ONLY.
ATS-FP-CB-A AND ATS-FP-CB-B (GFE) - FIRE PUMP MAIN NORMAL FEED BREAKER IN NEMA 4X S.S. ENCLOSURE WITH WINDOW.
SIZE OVER LOCKED ROTOR. INSTALL REMOTE OPERATOR OUTSIDE OF ARC FLASH BOUNDARY. CONNECT LINE SIDE OF BREAKER DIRECTLY TO THE SECONDARY OF THE UTILITY TRANSFORMER. PROVIDE ADEQUATE LUGS AT THE SECONDARY OF THE UTILITY
TRANSFORMER TO COMPLETE THIS CONNECTION. COORDINATE WORK WITH DUKE ENERGY.
PROVIDE AS 84 CIRCUIT VERTICAL PANELBOARD.
3 POLE, DOUBLE THROW DISCONNECT SWITCH IS CFE.
PROVIDE CONNECTION BETWEEN BUSS A AND BUSS B PAIRED TRANSFORMER GROUND. SEE TRANSFORMER PAIRED
GROUNDING DETAIL 2 ON SHEET E-622.
SPD: RAYVOSS 277-3Y-N1-3-06-C, CLIN 1004 (GFE) MOUNT EXTERNALLY AND AS CLOSE AS POSSIBLE TO MINIMIZE LENGTH
(12") OF CONDUCTORS AND BENDS IN THE CONDUCTORS.
SPD: RAYVOSS 277-3Y-M3-3-06-C, CLIN 1010 (GFE) MOUNT EXTERNALLY AND AS CLOSE AS POSSIBLE TO MINIMIZE LENGTH
(12") OF CONDUCTORS AND BENDS IN THE CONDUCTORS.
SPD: RAYVOSS 120-3Y-M3-4-06-A, CLIN 1003 (GFE) MOUNT EXTERNALLY AND AS CLOSE AS POSSIBLE TO MINIMIZE LENGTH
(12") OF CONDUCTORS AND BENDS IN THE CONDUCTORS.
PROVIDE LOCKABLE CIRCUIT BREAKERS.
PROVIDE SHUNT TRIP CIRCUIT TO E/G CONTROLLER FOR ENGINE GENERATOR LOAD BANK LOAD SHEDDING.
PROVIDE POWER METER. CT'S AND VOLTAGE SENSING SHALL BE PLACED IN A LOCATION TO READ CURRENT AND VOLTAGE FROM THE INCOMING CABLE FROM SESHA. PROVIDE CONTROL POWER FROM DEDICATED 120VAC CRITICAL POWER CIRCUIT.
POSITION CT'S AND VOLTAGE SENSING ON INCOMING LUGS FROM SESHA. METER TO INCLUDE ETHERNET AND DIGITAL INPUT
OPTIONS. LABEL THE DISPLAY "UTILITY FEED" ON EXTERIOR OF THE GEAR.
PROVIDE TEMPORARY ENGINE GENERATOR CONNECTION BOX, 36" X 24" X 12" NEMA 4X S.S. BOX, BERTHOLD ELECTRIC: W16-5S-
M OR APPROVED EQUAL.
PROVIDE 60/60/3, DISCONNECT SWITCH. PROVIDE CONNECTION FROM DISCONNECT SWITCH TO ELEVATOR CONTROLLER.
SEE E/G CONTROLLER INTERCONNECTIONS DETAIL ON DETAIL 1 DRAWING E619 FOR E/G CONTROLLER START SIGNAL, SHUNT TRIPS, REMOTE BREAKER OPERATORS, ATS START SIGNAL, AND ALL OTHER I/O AND CONTROL FUNCTIONS.
SEE SINGLE TRANSFORMER GROUNDING DETAIL 1 ON SHEET E-622.
BOND NEUTRAL TO GROUND WITH 4/0 AWG CONDUCTOR INSIDE ENGINE GENERATOR.
FOR CONTINUATION, SEE SHEET E801.
FOR CONTINUATION, SEE SHEET E802.
FOR CONTINUATION, SEE SHEET E803.
FOR CONTINUATION, SEE SHEET CLT-D-ATCT-E800.
PROVIDE AS 84 CIRCUIT VERTICAL PANELBOARD. FULLY POPULATE EMPTY SPACES WITH SPARE 20A-1P BREAKERS.
PROVIDE KEY TRANSFER BLOCKS.
PROVIDE LOAD SIDE FIRE PUMP MOTOR WIRING PER MANUFACTURER'S RECOMMENDATIONS.
PANEL IS DUAL FED. PROVIDE MB AND MBB AS AUTOMATIC SWITCHES.
SPD: RAYVOSS 277-3Y-M3-4-06-C, CLIN 1011 (GFE) MOUNT EXTERNALLY AND AS CLOSE AS POSSIBLE TO MINIMIZE LENGTH
(12") OF CONDUCTORS AND BENDS IN THE CONDUCTORS.
BOND NEUTRAL TO GROUND INSIDE TEMPORARY GENERATOR CONNECTION BOX. PROVIDE LABEL ON OUTSIDE OF BOX STATING
'DO NOT MAKE NEUTRAL/GROUND BOND AT TEMPORARY GENERATOR'.
ATS-FP-CB-A-PB / ATS-FP-CB-B-PB REMOTE CONTROL SWITCH (GFE) - SELECTOR SWITCH, 3-POSITION MOMENTARY- MAINTAINED-MOMENTARY SPRING RETURN TO CENTER, 600V, 10A, 2NO-2NC CONTACTS; CODE B, WITH ONE RED AND ONE GREEN LIGHT. INSTALLED INSIDE A NEMA 4X S.S. BOX WITH WINDOW. INSTALL OUTSIDE CIRCUIT BREAKER ARC FLASH
BOUNDARY.
PROVIDE ONE EMERGENCY LIGHTING INVERTER SYSTEM WITH (6) 20A-1P OUTPUT DISTRIBUTION BREAKERS AND BATTERY CAPACITY FOR 90 MINUTES OF RUN TIME. CONTROLLED POWER COMPANY #ELU-DJX-5-1S10 OR APROVED EQUAL. CFE.
PROVIDE GROUND FAULT INDICATION AT GENERATOR AND AT REMOTE MONITORS IN THE CAB AND FIRE CONTROL ROOM.
FOR CONTINUATION, SEE SHEET CLT-D-ATCT-E801.
PROVIDE JJ200 THERMAL MAGNETIC BREAKER.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
CHECKED
URS project no.
Copyright © 2014 URS Corporation, All Rights Reserved
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
SIGNATURE:
DATE:
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
CLT-D-TRACO-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
TRACON
EASTERN SERVICE AREA ATLANTA, GEORGIA
CHARLOTTE NCCHARLOTTE DOUGLAS INTERNATIONAL AIRPORT (CLT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
400 Northpark Town Center,1000 Abernathy Road, NE.
Suite 900 Tel. No (678)808-8800
Atlanta, Georgia 30328
Fax. (678)808-8400
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
08/31/2015
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
1103700
110370008/31/2015 ISSUED FOR BID
8/
/2
:2 2:
A
M
8/31/2015 10:22:25 AM
15290056
JAW
KCV
E800
KCV
SINGLE LINE DIAGRAM - TRACON - NOTES
DUKE ENERGY
1000KVA MAIN UTILITY
TRANSFORMER
23.9/13.8KV - 480V,
Z=5.75%, AVAILABLE FAULT
CURRENT=20,918A
GEN-B1
480V, 3PH, 3W
800KW, GFE
(ROOM 187) N G
GEN-B1-
IB
1600AF
1600AT
LSIA, RG
GENERATOR
CONTROLLER
ATS-ELEV-B-
GM-FB LSI
GSHB
1600A, 480V, 3PH,3W
GFE, 18,000 AIR
(ROOM 185)
QED 2
SPD
GFE
NOTE 10
1600AF
1600AT
3P
GEN-B1
GB, LSIA
ATSB-
GM-FB
LSI
ATS-FP-2-
GM-FB
032026
GEN-B1-LB-DS
1200AF
480V, 3P, 3W, NF,
GFE, NEMA 4X S.S.
GEN-B1-LB
750KW,480V,
3P, 3W, GFE
NEMA 4X S.S.
USHB-
GMBB-FB
LSI
100AF
60AT
3P
1600AF
1600AT
3P
250AS
150AT
3P
GSHB-SPD-FB
200AF/200AT
3P
400AF
90AT
3P
SECTION PARTITION
ATS-B,
1600A, 480V, 3P, 3W
GFE, 25,000 WCR
(ROOM 185)
UPS-B
100KVA, 480V
3P, 3W
GFE (ROOM 184)
UPS-B-BATT-CB
400AF/400AT
ATS-B-
FB LSI
SEDSHB
1600A, 480V, 3PH,3W
GFE, 25,000 AIR
(ROOM 185)
QED 2
SPD
GFE
NOTE 10
SEDSHB-SPD-FB
200AF/200AT
3P
ATS-ELEV-
B-FB LSI
100AF
60AT
3P
1600AF
1600AT
3P
SECTION
PARTITION
NOTE 4
NOTE 5
EPMS SECTION
NOTE 15
T-EDPLB
150KVA
480V- 208Y/120V, GFE
(ROOM 185)
M
NOTE 18
NOTE 20
ATS-FP-CB-A
480V, 3P, 3W
600AF/500AT
GFE, NOTE 2,6
NEMA 4X S.S.
GEN-A1
480V, 3PH, 3W
800KW, GFE
(ROOM 182) N G
GEN-A1-
IB
1600AF
1600AT
LSIA, RG
SESHA-MB-PB
REMOTE CONTROL
SWITCH NOTE 3
GENERATOR
CONTROLLER
FP-1 FIRE PUMP
CONTROLLER
WITH ATS
50HP
NOTE 27
ATS-ELEV-A-
GM-FB LSI
GSHA
1600A, 480V, 3PH,3W
GFE, 18,000 AIR
(ROOM 179)
QED 2
018 019
ATS-FLS-
GM-FB LSI
SPD
GFE
NOTE 10
1600AF
1600AT
3P G1
GEN-A1-
GB, LSIA
ATSA-
GM-FB
LSI
ATS-FP-1-
GM-FB
020015
GEN-A1-LB-DS
1200AF, 480V,
3P, 3W, NF, GFE
NEMA 4X S.S.
GEN-A1-LB
750KW,480V, 3P, 3W
GFE, NEMA 4X S.S.
USHA-
GMBB-FB
LSI
100AF
60AT
3P
400AS
125AT
3P
1600AF
1600AT
3P
250AS
150AT
3P
GSHA-SPD-FB
200AF/200AT
3P
400AF
100AT
3P
SECTION PARTITION
ATS-A,
1600A, 480V, 3P, 3W
GFE, 25,000 WCR
(ROOM 179)
UPS-A
100KVA, 480V
3PH, 3W
GFE (ROOM 180)
UPS-A-BATT-CB
400AF/400AT
023 ELEV-DS-A
480V, 3P, 3W
60AF/60A
CFE (ROOM 173)
NOTE 17024
ELEVATOR A
CONTROLLER
ATS-ELEV-A,
150A,3P,3W
480V, GFE
18,000 WCR
(ROOM 173)
ATS-A-
FB LSI
SEDSHA
1600A, 480V
3PH, 3W
GFE
25,000 AIR
(ROOM 179)
QED 2
SPD
GFE
NOTE 10
SEDSHA-SPD-FB
200AF/200AT
3P
008009006
ATS-FLS-
FB LSI
ATS-ELEV-
A-FB LSI
100AF
60AT
3P
1600AF
1600AT
3P
400AS
125AT
3P
SECTION
PARTITION
NOTE 4
NOTE 5
EPMS
SECTION
NOTE 15
T-EDPLA
150KVA
480V-208Y/120V, GFE(ROOM 179)
1600AF
1600AT
3P G1
GEN-T-GB
N.O., LSIA
NOTE 18
NOTE 9
NOTE 20
DUKE ENERGY
1000KVA MAIN UTILITY
TRANSFORMER
23.9/13.8KV - 480V,
Z=5.75%, AVAILABLE FAULT
CURRENT=20,918A
M
SESHA-MB
480V, 1600AF/1600AT
3P, 3W, NW LSIG
NOTES 1, 2
SESHA
1600A, 480V
3PH, 4W, GFE
25,000 AIR
(ROOM 181)
QED 2
ST
N G
SESHB-MB-PB
REMOTE CONTROL
SWITCH NOTE 3
SESHB-MB
480V, 1600AF/1600AT
3P, 3W, NW LSIG
NOTES 1, 2
SESHB
1600A, 480V
3PH,4W,
GFE
25,000 AIR
(ROOM 186)
QED 2
ST
N G
049048 055
EDPHA1-
CAB-FB
LSI
USHA-
MBB-FB
LSI
UPSA-
SBB-FB
LSI
UPSA-RIB-
FB LSI
T-EDPLA-
FB LSI
NOTE 13
EDPHA1-
FB LSI
ESHA-MB
LSI
ESHA-SPD-FB
100AF,100AT,3P
ESHA
1600A, 480V
3PH, 3W, 25,000 AIR,
GFE, (ROOM 179)
QED 2
SPD
GFE NOTE 11
1600AF
1600AT
3P
800AF
400AT
3P
400AS
400AT
3P
250AS
150AT
3P
250AS
150AT
3P
250AS
150AT
3P
400AS
225AT
3P
CH-1-FB
LSI
400AS
350AT
3P 051
B-CH-1
ESHA-TB, N.O.
LSI
K1
059058 063 064
EDPHB1-
CAB-FB
LSI
USHB-MBB-
FB LSI
UPSB-SBB-
FB LSI
UPSB-RIB-
FB LSI
T-EDPLB-
FB LSI
NOTE 13
EDPHB1-
FB LSI
ESHB-MB
LSI
ESHB-SPD-FB
100AF,100AT,3P
ESHB
1600A, 480V
3PH,3W
25,000 AIR
GFE
(ROOM 185)
QED 2
SPD
GFE NOTE 11
1600AF
1600AT
3P
800AS
400AT
3P
400AS
400AT
3P
250AS
150AT
3P
250AS
150AT
3P
250AS
150AT
3P
400AS
225AT
3P
CH-2-FB
LSI
400AF
350AT
3P 061
B-CH-2
K1
ESHB-TB, N.O.
LSI K1
EDPHA2
225A, 480/277V
3PH, 4W, GFE
18,000 AIR
(ROOM 179)
I LINE
EDPHA2-MB
LI
T-EDPHA2
150KVA
480V-480Y/277V, GFE, (ROOM 179)
NOTE 19
T-EDPHA2-
FB LI
NOTE 13
EDPHA1-
MB LSI
EDPHA1
400A, 480V, 3PH,3W, GFE,
25,000 AIR
(ROOM 179)
I LINE
800AS
400AT
3P
400AF
225AT
3P
400AF
225AT
3P
SPARE
LSI
100AF
50AT
3P
SPD
EDPHA2-
SPD-FB
70AT
GFE
NOTE 29
075 EDPHB2
400A, 480/277V
3PH, 4W, GFE
18,000 AIR
(ROOM 185)
I LINE
EDPHB2-MB
LI
T-EDPHB2
150KVA
480V-480Y/277V, GFE, (ROOM 185)
NOTE 19
T-EDPHB2-
FB LI
NOTE 13
EDPHB1-
MB LSI
EDPHB1
400A, 480V, 3PH, 3W, GFE,
25,000 AIR
(ROOM 185) I LINE
800AS
400AT
3P
400AF
225AT
3P
400AF
225AT
3P
SPARE
LSI
100AF
50AT
3P
SPD
EDPHB2-
SPD-FB
70AT
GFE
NOTE 29
ATS-FLS
150A, 4P, 3W
480V, GFE
18,000 WCR
(ROOM 173)
FLSDPH1
200A, 480V, 3PH, 4W
GFE 18,000 AIR
(ROOM 173)
I LINE 045
SPD GFE
T-FLSPL-
FB
NOTE 13
FLSDPH1-
CAB-
FB LSI
100AF
20AT
2P
INV1-FB
LSI
NOTE 13
100AF
25AT
3P
FLSDPH1-SPD-FB
100AF/100AT
FLSDPH1-
MB LSI
100AS
60AT
3P
250AS
125AT
3P
NOTE 22
NOTE 22
NOTE 34
NOTE 23
NOTE 24
NOTE 22
NOTE 22
NOTE 23
NOTE 24
NOTE 22
NOTE 22
FROM COFFEE CREEK SUBSTATION
PRIMARY CIRCUIT (CIRCUIT 2406)
FROM COFFEE CREEK SUBSTATION
ALTERNATE CIRCUIT (CIRCUIT XXXX)
042 ELEV-DS-B
480V, 3P, 3W
60AF/60AT
CFE (ROOM 173)
NOTE 17043
ATS-ELEV-B,
150A,3P,3W
480V, GFE
18,000 WCR
(ROOM 173)
ELEVATOR B
CONTROLLER
NPH-
A-FB
LSIG
400AS
200AT
3P
NOTE 23
NPH-
B-FB
LSIG
250AS
200AT
3P
35 NOTE 23
ATS-FP-CB-B
480V, 3P, 3W
400AF/400AT
GFE, NOTE 2, 6
NEMA 4X S.S.
FP-2 FIRE PUMP
CONTROLLER WITH ATS
40HP, NOTE 27
1600AS, 1600AT, 3P1600AS, 1600AT, 3P
NOTE 11
FLSPL
60A, 208Y/120V
3PH, 4W, GFE
10,000 AIR
(ROOM 173)
NQOD
FLSPL-MB
LSI
T-FLSPL
15KVA
480V-208Y/120V, GFE, (ROOM 173)
NOTE 19
60AF
50AT
3P
T-FLSDPH1
75KVA
480V-480Y/277V, GFE, (ROOM 173)
NOTE 19
ATS-FP-CB-A-PB
REMOTE CONTROL
SWITCH NOTE 31
ST
ATS-FP-CB-B-PB REMOTE
CONTROL SWITCH NOTE 31
INV1
480/277V, 1PH,3W, 5KW
10,000 AIR
(ROOM 173)
NOTE 32
NOTE 33 NOTE 33
100AF
20AT
2P
BATT.
N E
N E N E N EN E
GEN-A1-
LBB
1200AF
1200AT
LSIA, PG
GEN-B1-
LBB
1200AF
1200AT
LSIA, PG
T-EPLA6
-A-FB
LSI
100AF
50AT
3P
T-EPLA6
30KVA
480V-208Y/120V, GFE, (GUARD
BOOTH) NOTE 19
T-EPLA6-DS
480V, 3P, 3W
60AF, CFE
(GUARD BOOTH)
NEMA 4X S.S.
EPLA6
100A, 208/120V
3PH, 4W, GFE
10,000 AIR
(GUARD BOOTH)
NQOD
EPLA6-MB
LSI
250AF
100AT
3P
SPD
EPLA6-
SPD-FB
100AT
GFE
NOTE 12
ATS PRIORITY SEQUENCE
UPON LOSS OF NORMAL UTILITY POWER THE ATS'S SHALL SWITCH FROM THE
NORMAL UTILITY POWER TO GENERATOR POWER WITH THE FOLLOWING PRIORITY:
1. FP-1 AND FP-2
2. ATS-FLS
3. ATS-ELEV-A, ATS-ELEV-B
4. ATS-A, ATS-B
IN THE EVENT OF A GENERATOR OVERLOAD CONDITION, THE LOADS SHOULD BE
DISCONNECTED FROM GENERATOR POWER IN REVERSE ORDER (4,3,2).
FP-2
ROOM 175
FP-1
ROOM 175
T-EPLA6-DT-DS
480V, 3P, 3W
60AF, GFE
(ROOM 179)
NOTE 8, CFE
B-AHU-1
-B-FB
LSI
400AS
200AT
3P
B-AHU-1
-A-FB
LSI
400AS
200AT
3P
B-AHU-1
B-AHU-1-DS
480V, 3P, 3W
200AF, CFE
(ROOM 177)
NOTE 8
194193
T-EPLA6
-B-FB
LSI
100AF
50AT
3P
MO
ST
MO MOMO
K1
T-FLSDPH1-DS
480V, 3P, 3W
200AF, CFE
(ROOM 173)196
CHECKED
URS project no.
Copyright © 2014 URS Corporation, All Rights Reserved
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
SIGNATURE:
DATE:
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
CLT-D-TRACO-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
TRACON
EASTERN SERVICE AREA ATLANTA, GEORGIA
CHARLOTTE NCCHARLOTTE DOUGLAS INTERNATIONAL AIRPORT (CLT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
400 Northpark Town Center,1000 Abernathy Road, NE.
Suite 900 Tel. No (678)808-8800
Atlanta, Georgia 30328
Fax. (678)808-8400
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
08/31/2015
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
1103700
110370008/31/2015 ISSUED FOR BID
8/
/2
:2 2:
A
M
8/31/2015 10:22:27 AM
15290056
JAW
KCV
E801
KCV
SINGLE LINE DIAGRAM - TRACON - CPDS TYPE 2A & 2B - 1
OF 3
085 086
T-UDPLB-FB
LSI
NOTE 13
UDPHB-CAB-FB
LSI
NOTE 13
UPSB-LBB
(N.O.)
UPSB-MIB LSI
USHB-SPD-FB, 100AF,100AT,3P
USHB-MBB
(N.O.) LSI
USHB-GMBB
(N.O.) LSI
GFE
SPD
069250AS
150AT
3P LSI
250AF
125AT
3P
250AF
150AT
3P
USHB
200A, 480V, 3PH, 3W, GFE
25,000 AIR
(ROOM 184)
QED 2
250AS
150AT
3P
250AS
150AT
3P
250AS
150AT
3PB1
B2 B1 B1
NOTE 11
STS1-FB-B
LSI
UDPLB-MB LSI
UDPLB-SPD-FB, 100AF,100AT,3P
GFE
SPD
250AF
250AT
3P
UDPLB
250A, 208V, 3PH, 4W
GFE, 10,000 AIR
(ROOM 184)
I LINE
400AS
250AT
3P
A3
NOTE 12
STS2-FB-A
LSI
250AF
250AT
3P
UDPLB-TB LSI
400AS/250AT
N.O. A3
STS2
250A, 208V, 3P, GFE,
10,000 WCR
(ROOM 184)
CPL6-FB
LSI
GFESPD
CDPL2
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 184)
I LINE
CDPL2-SPD-FB
100AF/100AT
3P
250AF
150AT
3P
CPL7-FB
LSI
250AF
150AT
3P
CPL8-FB
LSI
250AF
150AT
3P
CPL6-
MBB, N.O.
CPL6
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 197) NQOD, NOTE 28
250AF
175AT
3P
SPD
CPL6-
SPD-FB
100AT
GFE
NOTE 12
CPL6-
MB
CPL7-
MBB, N.O.
CPL7
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 193) NQOD, NOTE 25, 28
250AF
175AT
3P
SPD
CPL7-
SPD-FB
100AT
GFE
NOTE 12
CPL7-
MB
T-UDPLB
75KVA, K13
480V-208Y/120V, GFE (ROOM 184)
S2
CPL8-
MBB, N.O.
CPL8
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 196) NQOD, NOTE 25, 28
250AF
175AT
3P
SPD
CPL8-
SPD-FB
100AT
GFE
NOTE 12
CPL8-
MBP6 P7 P8
P6 P7 P8
CPL9-FB
LSI
250AF
150AT
3P
CPL9-
MBB, N.O.
CPL9
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 194) NQOD, NOTE 25, 28
250AF
175AT
3P
SPD
CPL9-
SPD-FB
100AT
GFE
NOTE 12
CPL9-
MB P9
P9
UPS-LB
100KVA
480V, 3PH, 3W
GFE, NEMA 4X S.S.
UPS-LB-DS
200A, 480V, 3P, 3W, NF,GFE
NEMA 4X S.S.
T-UDPLA-FB
LSI
NOTE 13
UDPHA-CAB-FB
LSI
UPSA-LBB
(N.O.)
UPSA-MIB LSI
USHA-SPD-FB, 100AF,100AT,3P
USHA-MBB
(N.O.) LSI
USHA-GMBB
(N.O.) LSI
GFE
SPD
080250AS
150AT
3P LSI
250AF
125AT
3P
250AF
150AT
3P
USHA
200A, 480V, 3PH, 3W, GFE
25,000 AIR
(ROOM 180)
QED 2
250AS
150AT
3P
250AS
150AT
3P
250AS
150AT
3P
A2 A1 A1
NOTE 11
UPS-A-LB-IB
LSI
LBDPH
200A, 480V, 3PH, 3W
GFE, 18,000 AIR
(ROOM 180)
I LINE
250AS
150AT
3P
KL UPS-B-LB-IB
LSI
250AS
150AT
3P
KL
LBH-FB
LSI
NOTE 35
250AS
150AT
3P
T-UDPLA
75KVA, K13
480V-208Y/120V, GFE (ROOM 180)
STS1-FB-A
LSI
UDPLA-MB LSI
UDPLA-SPD-FB, 100AF,100AT,3P
GFE
SPD
250AF
250AT
3P
UDPLA
250A, 208V, 3PH, 4W
GFE, 10,000 AIR
(ROOM 180) I LINE
400AS
250AT
3P
A3
NOTE 12
STS2-FB-B
LSI
250AF
250AT
3P
S1
UDPLA-TB LSI
400AS/250AT, N.O.
A3
CPL1-
MBB-
FB
LSI
250AF
150AT
3P
UDPLM
250A, 208V, 3PH, 4W
GFE, 10,000 AIR
(ROOM 180) I LINE
UDPLM-TB-A, LSI
400AS/250AT
CPL2-
MBB-
FB
LSI
250AF
150AT
3P
CPL3-
MBB-
FB
LSI
250AF
150AT
3P
CPL4-
MBB-
FB
LSI
250AF
150AT
3P
CPL5-
MBB-
FB
LSI
250AF
150AT
3P
CPL6-
MBB-
FB
LSI
250AF
150AT
3P
CPL7-
MBB-
FB
LSI
250AF
150AT
3P
UDPLM-TB-B, LSI
400AS/250AT
STS1
250A, 208V, 3P, GFE,
10,000 WCR
(ROOM 180)
CPL1-FB
LSI
CDPL1
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 180)
I LINE250AF
150AT
3P
CPL2-FB
LSI
250AF
150AT
3P
CPL3-FB
LSI
250AF
150AT
3P
CPL1-
MBB, N.O.
CPL1
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 197) NQOD
NOTE 28
250AF
175AT
3P
SPD
CPL1-
SPD-FB
100AT
GFE
NOTE 12
CPL1-
MB
CPL2-
MBB, N.O.
CPL2
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 190) NQOD
NOTE 25, 28
250AF
175AT
3P
SPD
CPL2-
SPD-FB
100AT
GFE
NOTE 12
CPL2-
MB
CPL3-
MBB, N.O.
CPL3
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 190) NQOD
NOTE 25, 28
250AF
175AT
3P
SPD
CPL3-
SPD-FB
100AT
GFE
NOTE 12
CPL3-
MB
CPL4-
MBB, N.O.
CPL4
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 194) NQOD, NOTE 25, 28
250AF
175AT
3P
SPD
CPL4-
SPD-FB
100AT
GFE
NOTE 12
CPL4-
MBP1 P2 P3 P4
P1 P2 P4P3
GFE
SPD
NOTE 12
UDPLM-SPD-FB, 100AF,100AT,3P
CPL8-
MBB-
FB
LSI
250AF
150AT
3P
CPL9-
MBB-
FB
LSI
250AF
150AT
3P
CPL4-FB
LSI
250AF
150AT
3P
CPL5-FB
LSI
250AF
150AT
3P
CPL5-
MBB, N.O.
CPL5
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 180) NQOD, NOTE 28
250AF
175AT
3P
SPD
CPL5-
SPD-FB
100AT
GFE
NOTE 12
CPL5-
MB P5
P5
NOTE 9
6 7 1
12 13
210 11
NOTE 21 NOTE 21 NOTE 21 NOTE 21 NOTE 21 NOTE 21
NOTE 24NOTE 24
P1
P2
P3
P4
P5
S1
S2
P7
P8
P9
P6
NOTE 26 NOTE 26
056 017
064 029
123 124
NOTE 28 NOTE 28 NOTE 28 NOTE 28 NOTE 28
NOTE 28 NOTE 28 NOTE 28 NOTE 28
A2
NOTE 12
A1
B2
GFESPD
CDPL1-SPD-FB
100AF/100AT
3P
NOTE 12
SOURCE 1 SOURCE 2 SOURCE 1 SOURCE 2
CHECKED
URS project no.
Copyright © 2014 URS Corporation, All Rights Reserved
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
SIGNATURE:
DATE:
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
CLT-D-TRACO-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
TRACON
EASTERN SERVICE AREA ATLANTA, GEORGIA
CHARLOTTE NCCHARLOTTE DOUGLAS INTERNATIONAL AIRPORT (CLT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
400 Northpark Town Center,1000 Abernathy Road, NE.
Suite 900 Tel. No (678)808-8800
Atlanta, Georgia 30328
Fax. (678)808-8400
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
08/31/2015
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
1103700
110370008/31/2015 ISSUED FOR BID
8/
/2
:2 2:
A
M
8/31/2015 10:22:29 AM
15290056
JAW
KCV
E802
KCV
SINGLE LINE DIAGRAM - TRACON - CPDS TYPE 2A & 2B - 2
EPLB1-
MB
EPLB1
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 194) NQOD, NOTE 7
250AF
150AT
3P
SPD
EPLB1-
SPD-FB
100AT
GFE
NOTE 12
EPLB1-
MBB,N.O.
EPLB2-
MB
EPLB2
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 185) NQOD
250AF
150AT
3P
SPD
EPLB2-
SPD-FB
100AT
GFE
NOTE 12
EPLB2-
MBB,N.O.
EPLB3-
MB
EPLB3
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 188) NQOD
250AF
150AT
3P
SPD
EPLB3-
SPD-FB
100AT
GFE
NOTE 12
EPLB3-
MBB,N.O.
EPLB4-
MB
EPLB4
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 140) NQOD
250AF
150AT
3P
SPD
EPLB4-
SPD-FB
100AT
GFE
NOTE 12
EPLB4-
MBB,N.O.E6
E6
E7
E7
E8
E8EPLA1-
MBB, N.O.
EPLA1
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 197) NQOD
250AF
150AT
3P
SPD
EPL1-
SPD-FB
100AT
GFE
NOTE 12
EPLA1-
MB
EPLA2-
MBB, N.O.
EPLA2
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 179) NQOD
250AF
150AT
3P
SPD
EPL2-
SPD-FB
100AT
GFE
NOTE 12
EPLA2-
MB
EPLA3-
MBB, N.O.
EPLA3
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 188) NQOD, NOTE 7
250AF
150AT
3P
SPD
EPL3-
SPD-FB
100AT
GFE
NOTE 12
EPLA3-
MB
EPLA4-
MBB, N.O.
EPLA4
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 194) NQOD
250AF
150AT
3P
SPD
EPL4-
SPD-FB
100AT
GFE
NOTE 12
EPLA4-
MBE1
E1 E2
E2 E3
E3 E4
E4
14 24 15 25 16 26 17 27 29 19 30 20 31 21 32 22NOTE 23NOTE 23
NPL-A
250A, 208/120V
3PH, 4W, GFE
10,000 AIR
(ROOM 177)
I LINE
NPL-A-MB
LSI
T-NPLA
45KVA
480V-208Y/120V, GFE, (ROOM 140)
NOTE 19
T-NPLA-
FB LSI
NOTE 13
NPH-A-
MB LSI
NPH-A
250A, 480V, 3PH, 3W, GFE,
18,000 AIR
(ROOM 177)
I LINE
200AF
200AT
3P
250AF
150AT
3P
100AF
70AT
3P
SPD
NPL-A-
SPD-FB
100AT
GFE
NOTE 12
34 NOTE 21
NPL-B
250A, 208/120V
3PH, 4W, GFE
10,000 AIR
(ROOM 140)
I LINE
NPL-B-MB
LSI
T-NPLB
45KVA
480V-208Y/120V, GFE, (ROOM 177)
NOTE 19
T-NPLB-
FB LSI
NOTE 13
NPH-B-
MB LSI
NPH-B
250A, 480V, 3PH, 3W, GFE,
18,000 AIR
(ROOM 140)
I LINE
200AF
200AT
3P
250AF
150AT
3P
100AF
70AT
3P
SPD
NPL-B-
SPD-FB
100AT
GFE
NOTE 12
35 NOTE 21
007 039
EPLA1-
FB
EPLA2-
FB
EPLA3-
FB
EPLA4-
FB
EDPLA
800A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 179)
I LINE
EDPLA-SPD-FB
100AF,100AT,3P
EDPLA-
MB LSI
GFESPD
EPLB1-
MBB-
FB
800AF
500AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
EPLB2-
MBB-
FB
250AF
150AT
3P
EPLB3-
MBB-
FB
250AF
150AT
3P
EPLB4-
MBB-
FB
250AF
150AT
3P
14 15 16 17 19 20 21
NOTE 21
NOTE 23NOTE 23NOTE 23NOTE 23NOTE 23NOTE 23NOTE 23NOTE 23
089 090 091 092 093 094 095 096
NOTE 12
EPLA1-
MBB-FB
EPLA2-
MBB-FB
EPLA3-
MBB-FB
EPLA4-
MBB-FB
EDPLB
800A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 185)
I LINE
EDPLB-SPD-FB
100AF,100AT,3P
EDPLB-
MB LSI
GFESPD
EPLB1-
FB
800AF
500AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
EPLB2-
FB
250AF
150AT
3P
EPLB3-
FB
250AF
150AT
3P
EPLB4-
FB
250AF
150AT
3P
24 25 26 27 28 29
NOTE 21
NOTE 23 NOTE 23 NOTE 23 NOTE 23 NOTE 23 NOTE 23 NOTE 23 NOTE 23
101 102 103 104 105 106 107 108
NOTE 12
EPLB5-
MB
EPLB5
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 187) NQOD
250AF
150AT
3P
SPD
EPLB5-
SPD-FB
100AT
GFE
NOTE 12EPLB5-
MBB,N.O.E9
E9EPLA5-
MBB, N.O.
EPLA5
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 182) NQOD
250AF
150AT
3P
SPD
EPL5-
SPD-FB
100AT
GFE
NOTE 12EPLA5-
MBE5
E5
EPLA5-
MBB-FB
250AF
150AT
3P
NOTE 23
EPLB5-
FB
250AF
150AT
3P
NOTE 23
33 2318 28
EPLA5-
FB
250AF
150AT
3P
18 NOTE 23
EPLB5-
MBB-
FB
250AF
150AT
3P
23 NOTE 2322 30 31 32
NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23 NOTE 23NOTE 23
175 176E10
E10
CHECKED
URS project no.
Copyright © 2014 URS Corporation, All Rights Reserved
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
SIGNATURE:
DATE:
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
CLT-D-TRACO-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
TRACON
EASTERN SERVICE AREA ATLANTA, GEORGIA
CHARLOTTE NCCHARLOTTE DOUGLAS INTERNATIONAL AIRPORT (CLT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
400 Northpark Town Center,1000 Abernathy Road, NE.
Suite 900 Tel. No (678)808-8800
Atlanta, Georgia 30328
Fax. (678)808-8400
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
08/31/2015
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
DISCIPLINE: ELECTRICAL
NAME: KUNG C. VEN
NORTH CAROLINA REG. #: 036451
ELECTRICAL
1103700
110370008/31/2015 ISSUED FOR BID
8/
/2
:2 2:
A
M
8/31/2015 10:22:31 AM
15290056
JAW
KCV
E803
KCV
SINGLE LINE DIAGRAM - TRACON - CPDS TYPE 2A & 2B - 3
T-EDPHA2-
CAB-FB
LSI, NOTE 1
EDPHA1-CAB-MB
LSI
EDPHA1-CAB-SPD-FB
100AF/100AT
3P
GFESPD
EDPHA1-CAB
400A, 480V, 3PH,3W,
GFE
18,000 AIR
(ROOM 1209)
I LINE 400AF
175AT
3P
250AF
125AT
3P
T-EDPLA-
CAB-FB
LSI, NOTE 1
400AS
400AT
3P
SPARE-
FB
003 006
T-UDPLA-
CAB-FB, LSI
NOTE 1
UDPHA-CAB-MB
LSI
UDPHA-CAB-SPD-FB
100AF/100AT
3P
GFESPD
UDPHA-CAB
250A, 480V, 3PH,3W,
GFE
18,000 AIR
(ROOM 1208)
I LINE 250AF
125AT
3P
SPARE-
FB
400AS
150AT
3P
SPARE-
FB
T-UDPLB-
CAB-FB, LSI
NOTE 1
UDPHB-CAB-MB
LSI
UDPHB-CAB-SPD-FB
100AF/100AT
3P
GFESPD
UDPHB-CAB
250A, 480V, 3PH, 3W,
GFE
18,000 AIR
(ROOM 1208)
I LINE 250AF
125AT
3P
SPARE-
FB
400AS
150AT
3P
SPARE-
FB
T-EDPHB2-
CAB-FB
LSI,NOTE 1
EDPHB1-CAB-MB
LSI
EDPHB1-CAB-SPD-FB
100AF/100AT
3P
GFESPD
EDPHB1-CAB
400A, 480V, 3PH, 3W, GFE
18,000 AIR
(ROOM 1209)
I LINE 400AF
175AT
3P
250AF
125AT
3P
T-EDPLB-
CAB-FB
LSI,NOTE 1
400AS
400AT
3P
SPARE-
FB
T-EDPHA2-CAB
112.5KVA
480V-480Y/277V, GFE (ROOM 1209)
T-EDPHB2-CAB
112.5KVA
480V-480Y/277V, GFE (ROOM 1209)
T-EDPLA-CAB
75KVA
480V-208Y/120V, GFE (ROOM 1209)
T-UDPLA-CAB
75KVA
480V-208Y/120V, GFE (ROOM 1208)
T-UDPLB-CAB
75KVA
480V-208Y/120V, GFE (ROOM 1208)
T-EDPLB-CAB
75KVA
480V-208Y/120V, GFE (ROOM 1209)
GENERAL NOTES
KEYED NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
EDPHA2-CAB
-MB LSI
EDPHA2-CAB,
200A, 480/277V, 3PH, 4W, GFE,
18,000 AIR
(ROOM 1209)
I LINE
250AF
175AT
3P
EDPHA2-CAB-
SPD-FB
100AF, 70AT, 3P
GFE SPD
045 047
EPLA1-
CAB-
FB
EDPLA-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000AIR
(ROOM 1209) I LINE
250AF
150AT
3P
EPLA2-
CAB-
FB
EPLA3-
CAB-
FB
250AF
150AT
3P
250AF
150AT
3P
EDPLA-CAB-MB LSI
400AF/250AT, 3P
EDPHB2-
CAB-MB
LSI
EDPHB2-CAB,
200A, 480/277V, 3PH, 4W, GFE,
18,000 AIR
(ROOM 1209)
I LINE
250AF
175AT
3P
EDPHB2-CAB-
SPD-FB
100AF, 70AT, 3P
GFE SPD
035 036 037
EPLA1-
CAB-MBB-
FB
EDPLB-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000AIR
(ROOM 1209)
I LINE
250AF
150AT
3P
EPLA2-
CAB-MBB-
FB
EPLA3-
CAB-MBB-
FB
250AF
150AT
3P
250AF
150AT
3P
EDPLB-CAB-MB LSI
400AF/250AT, 3P
UDPLA-CAB
-MB LSI
UDPLA-CAB,
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1208)
I LINE
250AF
250AT
3P
UDPLA-CAB-
SPD-FB
100AF, 70AT, 3P
SPD
STS1-
CAB-
FB-A
LSI
UDPLM-CAB,250A, 208/120V, 3PH, 4W,
GFE,10,000 AIR (ROOM 1208)
I LINE
UDPLM-CAB-
SPD-FB
100AF, 70AT, 3P
SPD
CPL1-
CAB
MBB-FB
250AF
150AT
3P,LSI
020 022 STS1-CAB
150A,208V, 3P, GFE
10,000 AIR
(ROOM 1208)
NOTE15
250AF
150AT
3P
S3
CPL1-
CAB-
FB LSI
250AF
150AT
3P
CDPL1-CAB
250A, 208/120V, 3PH,
4W, GFE,
10,000AIR
(ROOM 1208) I LINE
CPL8-CAB-
MBB, N.O.
CPL8-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1109) NQOD, NOTE 14
250AF
175AT
3P
SPD
CPL8-
CAB-
SPD-FB
100AT
GFE
NOTE 2
CPL8-
CAB-
MB P17
P17
CPL5-CAB-
MBB, N.O.
CPL5-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1405) NQOD, NOTE 14
250AF
175AT
3P
SPD
CPL5-
CAB-
SPD-FB
100AT
GFE
NOTE 2
CPL5-
CAB-
MB P14
P14
CPL6-CAB-
MBB, N.O.
CPL6-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1405) NQOD, NOTE 14
250AF
175AT
3P CPL6-
CAB-
SPD-FB
100AT
CPL6-
CAB-
MB P15
P15
EPLA1-CAB-
MBB, N.O.
EPLA1-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1209)
NQOD
250AF
150AT
3P
SPD
EPLA1-CAB-
SPD-FB
100AT
GFE
NOTE 2
EPLA1-
CAB-
MB E11
E11
EPLA2-CAB-
MBB, N.O.
EPLA2-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1109) NQOD
250AF
150AT
3P
SPD
EPLA2-
CAB-
SPD-FB
100AT
GFE
NOTE 2
EPLA2-
CAB-
MB E12
E12
EPLA3-CAB-
MBB, N.O.
EPLA3-CAB
250A, 208/120V, 3PH, 4W, GFE,
10,000 AIR
(ROOM 1403) NQOD
250AF
150AT
3P
SPD
EPLA3-
CAB-
SPD-FB
100AT
GFE
NOTE 2
EPLA3-
CAB-
MB E13
E13
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
REFER TO SHEETS E500 SERIES FOR PANEL SCHEDULES FOR SIZES AND QUANTITY OF SPARE
BREAKERS AND ADDITIONAL PREPARED SPACES FOR ALL EQUIPMENT.
PROVIDE FINAL ADJUSTMENTS OF RATINGS AND SETTINGS FOR ALL EQUIPMENT PER SHORT
CIRCUIT, ARC FLASH, AND COORDINATION CALCULATIONS. CONTRACTOR TO FIELD VERIFY
CABLE LENGTH AND SUBMIT TO FAA, AND ADJUST FEEDER CONDUCTOR AND CONDUIT SIZES AS
NECESSARY TO ACCOMMODATE FIELD CONDITIONS FOR VOLTAGE DROPS, AND DERATING FOR
BELOW SLAB, ETC. ADJUST FEEDER AND CONDUIT SIZES TO MATCH LUG SIZE ON
PANELBOARDS, SWITCHBOARDS AND SWITCHGEAR. PROVIDE ARC FLASH LABELING FOR
EQUIPMENT. SEE SHORT CIRCUIT COORDINATION STUDY TO BE PERFORMED BY SQUARE D.
ALL BREAKERS AND SWITCHES SHALL BE IN NORMALLY CLOSED POSITION UNLESS OTHERWISE
NOTED.
TRANSFORMER DISCONNECTS SHALL BE LOCATED WITHIN 50 FEET OF TRANSFORMER.
LOCATE SPD…