671-18-118 Install Generator at PTRP-Bid Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25722B0032
About this file
This solicitation is for the installation of an electrical generator at the Polytrauma Transitional Rehabilitation Program (PTRP) located at the Veterans Affairs Medical Center in San Antonio, Texas. The solicitation number is 36C25722B0032 and the project number is 671-18-118. The work includes installing a new 175kW diesel fueled emergency generator with an enclosed sound attenuated enclosure and integral 510 gallon sub-base fuel tank. Ancillary work involves installing an automatic transfer switch, load center, conduit, and electrical connections to integrate the new generator into the facility's power distribution system. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 17. The response due date is not provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25722B0032 0005.docx | DOCX document | |
| 36C25722B0032 0004.docx | DOCX document | |
| PTRP Irrigation Drawings.pdf | ||
| Clarification Response RFIs 2 16 and 22.pdf | ||
| ICRA-2.0-ICRA.Permit.pdf | ||
| 36C25722B0032 0003.docx | DOCX document | |
| ICRA 2.0 ICRA. Permit.pdf | ||
| PTRP Irrigation Drawing.pdf | ||
| 36C25722B0032 0002.docx | DOCX document | |
| S04 Sign in Sheet PreBid Site Visit Conference AUG 16 2022.pdf | ||
| 36C25722B0032 0001.docx | DOCX document | |
| 671-18-118 Install Generator at PTRP-Bid Specifications.pdf | ||
| 36C25722B0032_1.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019Revisions: Date:
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
CONSULTANTS
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
D S E
L I C E N
S
XET
A
RE
L E NGI
EN
T
OE
T S
A
OR
P
S
NI O
SEF
A
F
ROBERT M. DAWES
92452 engineer is an offense under the Texas Engineering Practice Act.
without proper notification to the responsible
The seal appearing on this document was authorized by Robert M. Dawes, 92452 on
10/11/2019. Alteration of a sealed document GI100
COVER SHEET
AutoCAD SHX Text
INSTALL ELECTRICAL GENERATOR AT PTRP VA PROJECT NUMBER 671-18-118
AutoCAD SHX Text INDEX OF DRAWINGS: DRAWING NUMBER SHEET TITLE SHEET TITLE GENERAL: GI100 COVER SHEET COVER SHEET STRUCTURAL: SS101 GENERAL NOTES AND SPECIAL INSTRUCTIONS GENERAL NOTES AND SPECIAL INSTRUCTIONS SS201 FOUNDATION PLAN FOUNDATION PLAN SS202 SUBGRADE PREPARATION PLAN SUBGRADE PREPARATION PLAN SS301 FOUNDATION SECTIONS FOUNDATION SECTIONS SS302 FOUNDATION TYPICAL DETAILS FOUNDATION TYPICAL DETAILS MEP: MEP100 SITE PLAN: GENERAL REQUIREMENTS, PHASING PLAN AND SW3P PLAN SITE PLAN: GENERAL REQUIREMENTS, PHASING PLAN AND SW3P PLAN MEP101 SITE PLAN: GRADING SITE PLAN: GRADING ELECTRICAL: ES100 NOTES AND SYMBOLS LEGEND NOTES AND SYMBOLS LEGEND ES200 SITE PLAN SITE PLAN ES300 RISERS AND DETAILS RISERS AND DETAILS ES301 DETAILSDETAILS
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS
AutoCAD SHX Text
VETERANS AFFAIRS MEDICAL CENTER, SAN ANTONIO
AutoCAD SHX Text %%uPROJECT LOCATION
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text BUILDING CODES: 2018 NFPA 101 LIFE SAFETY CODE NFPA 101 LIFE SAFETY CODE 2018 NFPA NATIONAL FIRE CODES WITH THE EXCEPTION NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900 2016 NFPA 110 STANDARD FOR EMERGENCY AND NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS 2017 NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE 2018 INTERNATIONAL BUILDING CODE INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL PLUMBING CODE INTERNATIONAL PLUMBING CODE 2018 INTERNATIONAL MECHANICAL CODE INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL FUEL GAS CODE INTERNATIONAL FUEL GAS CODE TEXAS COMMISSION ON ENVIRONMENTAL QUALITY (TCEQ) VA REQUIREMENTS ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABASS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
AutoCAD SHX Text
HUEBNER
AutoCAD SHX Text
WURZBACK
AutoCAD SHX Text
FREDRICKSBURG RD.
AutoCAD SHX Text
HAMILTON-WOLFE RD.
AutoCAD SHX Text
GUS ECKERT RD.
AutoCAD SHX Text
CINNAMON HILL
AutoCAD SHX Text
CINNAMON
AutoCAD SHX Text
CREEK DR.
AutoCAD SHX Text
CINNAMON
AutoCAD SHX Text
TRAIL
AutoCAD SHX Text
USSA
AutoCAD SHX Text
FAWN MEADOWS
AutoCAD SHX Text
VALLY GREEN
AutoCAD SHX Text
BLVD.
AutoCAD SHX Text
RESEARCH
AutoCAD SHX Text
DR.
AutoCAD SHX Text
FLOYD CURL DR.
AutoCAD SHX Text
GOLDEN QUAIL
AutoCAD SHX Text
ENCINO PARK RD.
AutoCAD SHX Text
SOUTHWELL RD.
AutoCAD SHX Text
VERBENA ST.
AutoCAD SHX Text
HOLLYHOCK ST.
AutoCAD SHX Text
LOCKHILL RD.
AutoCAD SHX Text
PRUE RD.
AutoCAD SHX Text
BLUEMEL RD.
AutoCAD SHX Text
GARDENDALE ST.
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text N
STRUCTURAL NOTES
GENERAL
1. The Structural Drawings show the completed structure. They do not show components that may be necessary to support or stabilize the work during construction. The Contractor is solely responsible for ways and means of construction, and for safety on the jobsite during construction.
2. Sections and Details on the Structural Drawings are referenced from the drawings. They apply where referenced, and at all similar locations.
3. Typical Details may not be referenced from the drawings. They apply at the conditions described on the
Typical Detail.
4. See Mechanical Drawings for exact location and sizes of small mechanical openings, sleeves, etc. not shown on the Structural Drawings.
5. Do not use reproductions of the Structural Drawings for shop drawing purposes. CAD files of the Structural
Drawings will not be provided for this purpose.
6. Verify, prior to construction that the new construction will not conflict with existing utilities. If a conflict arises, notify the Architect, and stop the affected work until an appropriate solution to the conflict is found, and the
Architect issues written authorization to proceed with the work.
7. Field verify all dimensions locating existing building elements.
DESIGN LOADS
1. Design loads are based on the 2015 International Building Code.
2. Gravity loads:
a. Design loads are as listed on foundation plan.
FOUNDATION
1. Foundation design is based on the soils report prepared by TTL, Inc., project number 000180902558.00, dated February 15, 2019 and supplemental recommendations in a letter dated March 6, 2019. Perform all foundation work in accordance with the recommendations of the soils report.
2. Allowable bearing pressure for foundations is 3 ksf for footings founded a minimum of 3 feet below the existing ground surface.
3. Notify the field representative of the Geotechnical Engineer referenced above, or other pre-approved testing laboratory, at least 48 hours before installing foundations. Begin installation of foundations only in the presence of the field representative. Maintain a log of all foundations, recording the foundation identification mark, size, depth to top of bearing strata, depth to bottom of foundation, reinforcing steel, and concrete quantity.
4. Subgrade preparation under generator pad:
a. Remove the uppermost 6" of soil and any exposed organic materials. Do not use this material for the generator pad.
b. Excavate a minimum of 2 feet below existing site grade. Provide 1% slope at bottom elevation to prevent ponding, and maintain positive drainage or pumping capacity to prevent accumulation of water in the excavation during construction.
c. Excavate an additional one foot below the perimeter strip footing. Excavate with a smooth-mouthed bucket for a neat excavation.
d. Proof-roll the entire area with a 20-ton roller. If any weak yielding zones are present, they should be over excavated, both vertically and horizontally, to expose competent soil.
e. Scarify the exposed subgrade to a depth of at least 6 inches. Uniformly compact soil to a dry density of at least 95% of Standard Proctor (ASTM D-698) maximum dry density. Maintain a soil moisture content at time of compaction between optimum and +4 percentage points of the material's optimum moisture content.
f. Backfill with flowable fill, as shown in 01/S202.
g. Backfill behind the retaining wall with granular backfill, as shown in 01/S202.
h. Generator Foundation h.1. Backfill to 1'-2" below the generator pad finished elevation with select fill. Place in layers of 8 inch maximum loose thickness. Uniformly compact soil to a dry density of at least 95% of
Standard Proctor (ASTM D-698) maximum dry density. Maintain a soil moisture content at time of compaction between -2 and +3. Percentage points above the material's optimum moisture content. Maintain the specified moisture content until the building pad is completed.
h.2. Backfill above the Select Fill with 6 inches of Granular Select Fill. Place Granual Select Fill to the same requirements as the Select Fill listed above.
i. Select Fill shall be a uniformly blended clayey sand having a Liquid Limit less than 30 and a Plasticity
Index (PI) between 4 and 15. Do not use on-site soils for Select Fill.
j. Flowable Fill shall be a self-compacting concrete mix, with a concrete strength of 300 psi or less, and a slump of 8 inches or more.
k. Granual Select Fill shall be a free-draining sand or gravel.
k.1. Sand - 100 percent passing the No. 16 sieve and not more than 5 percent passing the No. 200 sieve.
k.2. Gravel - washed, evenly graded miscture of crushed stone, or crushed or uncrushed gravel with
100 percent passing the 1 inch sieve and not more than 5 percent passing the No. 4 sieve.
5. Where utility trenches enter beneath the foundations, install a plug of low-permeability clay soil. Refer to
Typical Detail. Backfill utility trenches beneath the building using properly compacted select fill, rather than granular material.
6. Provide and maintain positive surface drainage away from the building in accordance with the recommendations of the soils report.
7. The Generator Pad and Strip Footings may be earth-formed on the sides, provided that excavations will safely stand with a vertical cut, and provided that footing sides are located within a tolerance of -0" to +3".
Earth-forming of retaining walls is not acceptable.
REINFORCED CONCRETE
1. Perform concrete work in compliance with "Building Code Requirements for Structural Concrete" (ACI
318-11). Use materials and methods in compliance with "Specification for Structural Concrete for Buildings"
(ACI 301). Structural concrete shall be of normal weight aggregate with specified properties as described below. Use Type I or Type II Portland cement. Do not use fly ash in concrete slabs. Fly ash may be used in other mixes to a maximum of 20% of cementitious materials by weight.
28 day maximum air maximum
Strength slump aggregate content w/c ratio
Structural concrete 4000 psi 4" 1" 4.5% 0.50
Paving See typical details on S302
2. Maximum tolerance for slump is 1". Reject any concrete with non-complying slump, and return to the supplier. Submit the proposed mix for review at least 14 days prior to placing concrete.
3. Reinforcing steel shall conform to ASTM A-615, Grade 60.
4. Do not weld reinforcing steel.
5. All reinforcing shall lap 36 bar diameters at splices unless noted otherwise. Hook continuous bars at discontinuous ends.
6. Detail concrete reinforcing and accessories in accordance with the latest edition of ACI Publication 315.
7. Provide concrete protection for reinforcing as listed below, unless noted otherwise on sections or details.
Beams and walls on earth 2" sides and top, 3" bottom
8. Locate horizontal joints only where shown. Locate vertical joints at or near the center of spans, or as approved in writing by the Structural Engineer.
SITE OBSERVATIONS BY STRUCTURAL STUDIO
1. Structural Studio has been engaged to make periodic site visits during construction to observe the progress of the structural work. Notify the Engineer of Record at least 48 hours in advance of the following tasks:
a. First pour of retaining walls.
b. Final "punch list" visit.
2. A site observation by Structural Studio does not take the place of the Special Inspections listed in the
Contract Documents.
SPECIAL INSPECTIONS
SPECIAL INSPECTIONS: GENERAL
1. The Contractor shall employ and pay for services of an independent testing laboratory to perform the
Special Inspections specified in the Contract Documents or required by the C.O.R..
2. Submit testing lab reports to the C.O.R., with copies to the Mechanical Engineer, the Contractor and the Structural Engineer.
3. Notify the testing laboratory in sufficient time to allow performance of the specified inspections and testing. Cooperate with the laboratory to facilitate execution of required services.
4. Services of a laboratory do not relieve Contractor's obligations to perform the work in accordance with the Contract Documents.
5. Each inspection shall be documented promptly with a written report. Each report shall include:
a. Date issued.
b. Project title and number.
c. Testing laboratory name, address and telephone number.
d. Name and signature of laboratory inspector.
e. Date and time of inspection.
f. Date of test.
g. Identification of product.
h. Location of sample or test in the Project.
i. Type of inspection or test.
j. Results of tests.
k. Statement of compliance or non-compliance with Contract Documents.
l. Interpretation of test results that indicate unsatisfactory conditions.
6. Track all non-complying work in subsequent reports until the work has been corrected and re-inspected.
7. Refer to the Contract Documents and the Building Code for applicable Standards and Criteria.
SPECIAL INSPECTIONS: SUBGRADE DENSITY
1. Obtain samples of imported fill from each proposed source. Test fill for liquid limit, plasticity index and gradation, and verify that materials meet the requirements stated in the Geotechnical Report and on the Contract Documents.
2. Perform in-place density test of completed proof-rolled subgrade in accordance with ASTM D-6938.
3. Perform in-place density test of completed subgrade in accordance with ASTM D-6938, one test for each day's work.
4. Perform in-place density tests of completed backfill in accordance with ASTM D-6938. Perform one test for each lift placed each day.
5. Perform in-place density tests of completed backfill at retaining walls in accordance with ASTM
D-6938. Perform one test for each lift placed each day.
6. Perform in-place density tests of completed backfill at utility trenches within the new construction in accordance with ASTM D-6938. Perform one test for each lift placed each day.
7. Inspect the subgrade soil beneath each footing. Verify that bearing material is consistent with the
Contract Documents and the geotechnical report.
SPECIAL INSPECTIONS: FLOWABLE FILL
Refer to Specification.
SPECIAL INSPECTIONS: CONCRETE
1. Review and approve concrete mix designs submitted by Contractor.
2. Perform continuous inspection of concrete during placement on site.
3. Inspect plastic concrete at site to verify that concrete is thoroughly and properly mixed. Control consistency of mix to protect against segregation due to excessive water. Adjust amounts of mixing water to assure uniform consistency of each batch.
4. Check mixing time of concrete in trucks.
5. Certify each delivery ticket indicating class of concrete delivered, and record amount of water added, time of mixing, time of discharge, slump and location of placement.
6. Promptly report to C.O.R. details of reasons for rejection of any quantities of concrete. Report locations of concrete pours, quantities, date of pours and other pertinent facts concerning concrete represented by non-complying specimens.
7. Test cylinders: during progress of work, mold, cure and test specimens of each different mix design placed in any one day. For each 50 cubic yards of concrete placed, or part thereof over 10 cubic yards, make compression test cylinders during pour. Mold and cure test cylinders in accordance with
ASTM C-31. Test cylinders in accordance with ASTM C-39. For 6" x 12" cylinders test one at 7 days and 2 at 28 days. For 4" x 8" cylinders test one at 7 days and 3 at 28 days. Make additional sets of cylinders when obvious changes in mix are apparent.
8. Slump tests: make slump tests for each 50 cubic yards of concrete placed, and for each set of cylinders in accordance with ASTM C143.
9. Air content of normal-weight concrete: determine total air content of air entrained concrete for each compressive strength test in accordance with ASTM C231.
10. Temperature of concrete: determine temperature of concrete for each compressive strength test.
11. Curing of concrete: inspect for maintenance of specified curing temperature and protection techniques.
12. Verify in-situ concrete strength prior to removal of shores and forms from beams and structural slabs.
13. Reinforcing steel inspection:
a. Perform visual inspection prior to placement for size, type, and quality of materials.
b. Inspect placement of reinforcement for conformance with Contract Documents and shop drawings, including size, vertical location, horizontal spacing, correctness of bends, splices, clearance between bars and forms, firmness of installation, and security of support and ties.
c. Verify that steel is free of form release oil and other deleterious materials.
14. Perform periodic inspection of formwork for shape, location and dimensions of the concrete member being formed.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019 NB SSRevisions: Date:
CONSULTANTS
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
SSCE PROJECT NO. - 4280.01 S101
GENERAL NOTES &
SPECIAL INSPECTIONS
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text 58443
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text
NIGEL M.H.O. BROWN
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
D
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019 NB SSRevisions: Date:
CONSULTANTS
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
SSCE PROJECT NO. - 4280.01 S201
FOUNDATION PLAN
PLAN NOTES
1. DRAWING REFERENCES: SHEET
FOUNDATION NOTES AND SUBGRADE PREPARATION S101
GENERAL NOTES S101
SPECIAL INSPECTIONS S101
TYPICAL DETAILS S302
2. KEY:
CJ = CONTROL JOINT. SEE SECTIONS ON S302
3. ELEVATIONS NOTED ON PLAN ARE BASED ON
NOMINAL GROUND FLOOR ELEVATION = 100'-0".
SEE SITE PLAN FOR SURVEY ELEVATION.
4. DESIGN LOADS:
UNIFORM LIVE LOAD = 250 PSF
CONCENTRATED LIVE LOADS = 10,000 LB.
CONCENTRATED FLOOR LOAD APPLIED OVER AREA OF 2'-6" X 2'-6"
5. EQUIPMENT:
GENERATOR WEIGHT = 11,000 LBS
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text 58443
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text
NIGEL M.H.O. BROWN
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
FOUNDATION PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 14"=1'-0"
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text 02/S202
AutoCAD SHX Text 03/S301
AutoCAD SHX Text 01/S301
AutoCAD SHX Text 01/S301
AutoCAD SHX Text
GENERATOR FOUNDATION
AutoCAD SHX Text
RETAINING WALL SEE SECTIONS
AutoCAD SHX Text 02/S301
AutoCAD SHX Text 02/S301
AutoCAD SHX Text 14/S302
AutoCAD SHX Text
7" CONCRETE PAVING ON PREPARED SUBGRADE REINF. W/ #3 @ 16" O.C.E.W.
AutoCAD SHX Text
ROLL-OVER CURB
AutoCAD SHX Text 01/S202
AutoCAD SHX Text 01/S301
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text 10 "18"
AutoCAD SHX Text 6 "38"
AutoCAD SHX Text 6 "38"
AutoCAD SHX Text 10 "18"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-1 "78"
AutoCAD SHX Text
AutoCAD SHX Text
FOUNDATION PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 14"=1'-0"
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
ELECTRICAL YARD
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text 13/S301
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text 4'-3"
AutoCAD SHX Text 13/S301
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 3'-9"
LOCATE POST AS REQUIRED
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019 NB SSRevisions: Date:
CONSULTANTS
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
SSCE PROJECT NO. - 4280.01 S202
SUBGRADE PREPARATION
PROFILES
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text 6"
AutoCAD SHX Text FILTER FABRIC GRANULAR SELECT FILL FLOWABLE FILL SELECT FILL PROOF-ROLL, SCARIFY & COMPACT NATIVE SOIL
AutoCAD SHX Text
AutoCAD SHX Text
WEEPHOLES
AutoCAD SHX Text
RETAINING WALL, SEE 01 & 02/S301 SELECT FILL STRIP FOOTING
AutoCAD SHX Text
GENERATOR FOUNDATION, SEE 03/S301 PAVING
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text 58443
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text
NIGEL M.H.O. BROWN
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
SEE S301 FOR FOUNDATION REINFORCING AND DIMENSIONS
AutoCAD SHX Text
SUBGRADE PROFILE
AutoCAD SHX Text
AutoCAD SHX Text
TOP OF WALL NO SLOPE
AutoCAD SHX Text
CONCRETE PAVEMENT - SLOPE 2%
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
GENERATOR FOUNDATION, SEE 03/S301
AutoCAD SHX Text
EXIST. GRADE
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text
SUBGRADE PROFILE
AutoCAD SHX Text
RETAINING WALL, SEE 01/S301 WEEPHOLES SELECT FILL STRIP FOOTING
AutoCAD SHX Text SELECT FILL FILTER FABRIC GRANULAR SELECT FILL FLOWABLE FILL PROOF-ROLL, SCARIFY & COMPACT
AutoCAD SHX Text
6" SELECT FILL FLOWABLE FILL
AutoCAD SHX Text SIMULATED BRICK CLADDING COLOR TO MATCH EXISTING BUILDING - CONTRACTOR TO SUBMIT A SAMPLE.
AutoCAD SHX Text
NOTE: INSTALL FILTER FABRIC ALL SIDES OF GRANULAR SELECT FILL.
NOTE: INSTALL FILTER FABRIC ALL SIDES OF GRANULAR SELECT FILL.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019 NB SSRevisions: Date:
CONSULTANTS
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
SSCE PROJECT NO. - 4280.01 S301
FOUNDATION SECTIONS
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text 58443
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text
NIGEL M.H.O. BROWN
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text
3" CL.
AutoCAD SHX Text 8"
AutoCAD SHX Text #4 @ 18" O.C.
AutoCAD SHX Text
1-#4 CONT.
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text
3" CL.
AutoCAD SHX Text 5'-2"
AutoCAD SHX Text 2'-2"
AutoCAD SHX Text #4 x 3'-8" @ 16" O.C.
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text 6"
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text
OR LESS
AutoCAD SHX Text
WALL HEIGHT 7'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text
#5 VERT. @ 12"
AutoCAD SHX Text
#4 HORIZ. @ 12"
AutoCAD SHX Text
#4 VERT. @ 12"
AutoCAD SHX Text
#4 HORIZ. @ 12"
AutoCAD SHX Text
1 " WEEP HOLES 12" WEEP HOLES@ 5'-0" O.C.
AutoCAD SHX Text
#4 DOWELS @ 12" LAP 1'-6"
AutoCAD SHX Text
#4 @ 12" O.C. TOP & BOTT.
AutoCAD SHX Text #4 @ 16" O.C.
AutoCAD SHX Text
GUARDRAIL- SEE M2.0
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-8"
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text
PAVING
AutoCAD SHX Text
CORE SLEEVES AS REQ'D.
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-5"
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text
34" CHAMFER, BOTH SIDES
AutoCAD SHX Text 2-#5 x CONT. #4 STIRR. @ 12" O.C. 2-#5 x CONT., EA. FACE 3-#6 x CONT.
AutoCAD SHX Text
8" SLAB REINF. W/ #5 @ 12" E.W., T. & B.
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text
34" CHAMFER, ALL AROUND
AutoCAD SHX Text 3'-8"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-4"
AutoCAD SHX Text
3" CL.
AutoCAD SHX Text 8"
AutoCAD SHX Text 1'-4"
AutoCAD SHX Text
CONCRETE FOR WALL FOOTING & KEY MUST BE PLACED AGAINST UNDISTURBED SOIL (TYP.)
AutoCAD SHX Text
3" CL.
AutoCAD SHX Text
SECTION
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
CORE SLEEVES AS REQ'D.
AutoCAD SHX Text
PAVING
AutoCAD SHX Text
GUARDRAIL- SEE M2.0
AutoCAD SHX Text
#4 VERT. @ 12"
AutoCAD SHX Text
#4 HORIZ. @ 12"
AutoCAD SHX Text
#4 VERT. @ 12"
AutoCAD SHX Text
#4 HORIZ. @ 12"
AutoCAD SHX Text
OR LESS
AutoCAD SHX Text
#4 DOWELS @ 12" LAP 1'-6"
AutoCAD SHX Text
WALL HEIGHT 5'-0"
AutoCAD SHX Text
1 " WEEP HOLES 12" WEEP HOLES@ 5'-0" O.C.
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text
#4 @ 12" O.C. TOP & BOTT.
AutoCAD SHX Text 10"
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text 1'-8"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text #4 x 2'-8" @ 12" O.C.
AutoCAD SHX Text #4 @ 18" O.C.
AutoCAD SHX Text
1-#4 CONT.
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text #4 @ 16" O.C.
AutoCAD SHX Text
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text 6"
AutoCAD SHX Text
2" CL.
AutoCAD SHX Text
CONCRETE FOR WALL FOOTING & KEY MUST BE PLACED AGAINST UNDISTURBED SOIL (TYP.)
AutoCAD SHX Text EXIST. CONDUIT ROUTED TO ELEC. RM. 137. REFER TO ELEC PLAN. FIELD VERIFY DEPTH AND ROUTING
AutoCAD SHX Text
EXISTING ELEC. (HATCHED) REFER ELEC.
AutoCAD SHX Text
CONDUIT - REFER ELEC.
AutoCAD SHX Text
2" GALV. STEELPIPE POST
AutoCAD SHX Text
12/S301 TYP.
AutoCAD SHX Text
NOTE: COORDINATE ALL WORK WITH ELECTRICAL.
AutoCAD SHX Text CONDUITS FOR GENERATOR CONTROLS, CONVENIENCE RECEPTACLES, BATTERY CHARGER AND JACKET HEATER.
AutoCAD SHX Text 13/S301
AutoCAD SHX Text
EXIST. SIDEWALK
AutoCAD SHX Text
CHECK FOR EXISTING UTILITIES PRIOR TO AUGURING FOUNDATIONS
AutoCAD SHX Text 2" GALV. STEEL POST34" FLEXIBLE JOINT FILLER AT PAVING 12" ISOLATION JOINT AT PAVING
AutoCAD SHX Text
POST AT ELECTRICAL YARD
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
12" SONOTUBE AT PAVING12" CONCRETE
AutoCAD SHX Text
PAVING
AutoCAD SHX Text
GALV. METAL CAP
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 12"=1'-0"
AutoCAD SHX Text
2'-0" ABOVE EXIST. SWITCH GEAR
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text 6"
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text SEGREGATE EXCAVATED SOIL & REPLACE IN LAYERS TO MATCH EXISTING. COMPACT TO 95% STANDARD PROCTOR DENSITY.
AutoCAD SHX Text
TRENCHING EXISTING SIDE WALK
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text
AS REQUIRED
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text
#3 @ 18" EACH WAY
AutoCAD SHX Text
EXISTING SIDEWALK
AutoCAD SHX Text #3 x 2'-0" DOWELS. @ 18". DRILL & EPOXY INTO EXISTING CONCRETE.
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
SIMULATED BRICK CLADDING
AutoCAD SHX Text
SIMULATED BRICK CLADDING
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
ATS EQUIPMENT PAD & PULL-BOX FOUNDATION
AutoCAD SHX Text
AutoCAD SHX Text FOR SLEEVES, ANCHOR BOLTS AND OTHER EMBEDDED MATERIAL, REFER TO MANUFACTURER'S EQUIPMENT DRAWINGS.
AutoCAD SHX Text 34" x 45° CHAMFER AT ALL EDGES
AutoCAD SHX Text 6"
AutoCAD SHX Text
1 " CLR.12" CLR.
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 1'-4"
AutoCAD SHX Text
SEE PLAN
AutoCAD SHX Text
SLOPE DOWN
AutoCAD SHX Text
SLOPE DOWN
AutoCAD SHX Text #4 @ 12"
AutoCAD SHX Text
#4 CONT. ALL AROUND
AutoCAD SHX Text
PREPARE SUBGRADE AS FOR PAVING
PROVIDE POST BEHIND EXISTING ELECTRICAL EQUIPMENT TO SUPPORT CONDUIT AS REQUIRED
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019 NB SSRevisions: Date:
CONSULTANTS
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
SSCE PROJECT NO. - 4280.01 S302
FOUNDATION TYPICAL
DETAILS
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text 58443
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text
NIGEL M.H.O. BROWN
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
RUN REINF. CONTINUOUS THRU JOINT
AutoCAD SHX Text PROVIDE "SYNCO-FLEX" WATER STOP (OR APPROVED EQUAL) AT BACKFILLED SIDE OF RETAINING WALL
AutoCAD SHX Text
SEE
AutoCAD SHX Text
SECTIONS
AutoCAD SHX Text
EQ.
AutoCAD SHX Text 2 "12"
AutoCAD SHX Text Ld
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
34" MITER EA. SIDE OF WALL AT CONSTRUCTION JOINT
AutoCAD SHX Text
STOP EVERY OTHER BAR 2" SHORT OF CONTRACTION JOINT
AutoCAD SHX Text NOTE: LOCATE CONTRACTION JOINTS AT 20'-0" O.C. MAX. AT CONTRACTOR'S OPTION EITHER A CONSTRUCTION OR A CONTRACTION JOINT COULD BE USED.
AutoCAD SHX Text 0"
AutoCAD SHX Text 0"
AutoCAD SHX Text
SEE
AutoCAD SHX Text
SECTIONS
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
34" MITER EA. SIDE OF WALL AT CONTRACTION JOINT. TYP.
AutoCAD SHX Text PROVIDE "SYNCO-FLEX" WATER STOP (OR APPROVED EQUAL) AT BACKFILLED SIDE OF RETAINING WALL
AutoCAD SHX Text 1 "12"
AutoCAD SHX Text
CONT. REINF.
AutoCAD SHX Text
CONTRACTION JOINT
AutoCAD SHX Text
CONSTRUCTION JOINT
AutoCAD SHX Text
WALL JOINTS
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
NOTES: 1. ALL BARS CONTINUOUS, U.N.O.
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text PROVIDE STANDARD HOOKS FOR ALL TOP BARS AT DISCONTINUOUS ENDS BOTTOM CONTINUOUS BARS - SEE SECTIONS
AutoCAD SHX Text
TOP CONTINUOUS BARS - SEE SECTIONS
AutoCAD SHX Text
STIRRUP SPACING
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
2" CLEAR
AutoCAD SHX Text
BEAM WIDTH SEE SECTIONS
AutoCAD SHX Text
1 " CLEAR 12" CLEAR TO STIRRUPS TYP.
AutoCAD SHX Text
2 " CLEAR 12" CLEAR TO STIRRUPS
AutoCAD SHX Text
BEAM DEPTH SEE SECTIONS
AutoCAD SHX Text
BAR BENDING DIAGRAM
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
(2'-6" MIN.)
AutoCAD SHX Text
30 BAR DIA.
AutoCAD SHX Text
CORNER BAR - MATCH SIZE AND SPACING OF WALL AND BEAM REINFORCING
AutoCAD SHX Text
(2'-6" MIN.)
AutoCAD SHX Text
30 BAR DIA.
AutoCAD SHX Text
CORNER BARS AT WALLS AND BEAMS
AutoCAD SHX Text
AutoCAD SHX Text
FOR BEAMS DEEPER THAN 24" ADD ONE KEY FOR EACH 12" ADDED DEPTH.
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text 1 " x 5 " KEY x 12" x 5 " KEY x 12" KEY x FULL WIDTH OF BEAM
AutoCAD SHX Text
EQ.
AutoCAD SHX Text 1 "12"
AutoCAD SHX Text 5 "12"
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
EXTEND ALL REINFORCING BARS THROUGH JOINT STIRRUPS
AutoCAD SHX Text 1 "12"
AutoCAD SHX Text
D = DEPTH
AutoCAD SHX Text
OF BEAM
AutoCAD SHX Text
CONSTRUCTION JOINT IN CONCRETE BEAM
AutoCAD SHX Text
ELEVATION
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
12" EXP. JT. MAT'L. FULL DEPTH
AutoCAD SHX Text
PAVING ISOLATION JOINT
AutoCAD SHX Text
18" R. TOOLED EDGE CONCRETE PAVEMENT - REF. DWGS.
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
JOINT SEALANT 34" DEEP (FILL FLUSH TO SURFACE) BUILDING STRUCTURE
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL DETAIL
AutoCAD SHX Text 1 "=1'-0"12"=1'-0"=1'-0"
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AutoCAD SHX Text
CONCRETE WATERSTOP
AutoCAD SHX Text
EQ.
AutoCAD SHX Text 3 "12"
AutoCAD SHX Text
EQ.
AutoCAD SHX Text 1 "12"
AutoCAD SHX Text
2 " 12" MIN.
AutoCAD SHX Text
SEE SECTIONS
AutoCAD SHX Text
SYNKO-FLEX SF302 WATERSTOP, CONT. IN KEYWAY
AutoCAD SHX Text 3 "12"
AutoCAD SHX Text 7"
AutoCAD SHX Text
#3 BARS ON 16" CTRS. BOTH WAYS
AutoCAD SHX Text
CLASS "A" - TYPE "IA" CONCRETE 3000 PSI CONCRETE AT 28 DAYS
AutoCAD SHX Text
*ALL CONCRETE TO HAVE 4.5% ±1.5% ENTRAINED AIRWITH A MAXIMUM SLUMP = 5"
AutoCAD SHX Text FLY ASH OR SLAG CEMENT (GROUND GRANULATED BLAST-FURNACE SLAG) MAY BE SUBSTITUTED FOR UP TO A MAX. OF 20% OF THE REQUIRED PORTLAND CEMENT IN CONCRETE. (PER ASTM C 989 & C 595) SEPARATE CEMENTITIOUS MATERIAL AT A CONCRETE BATCH PLANT AS GOVERNED BY ASTM C 989 STANDARD SPECIFICATION FOR GROUND GRANULATED BLAST FURNACE-SLAG FOR USE IN CONCRETE AND MORTARS. BLENDED CEMENTS BY THE PORTLAND CEMENT SUPPLIER TO ADD SLAG CEMENT TO CONCRETE AS GOVERNED BY ASTM C 595 STANDARD SPECIFICATIONS FOR BLENDED HYDRAULIC CEMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text 3"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 6"
AutoCAD SHX Text 3"
AutoCAD SHX Text 3"
AutoCAD SHX Text 7"
AutoCAD SHX Text
SAWCUT SHALL EXTEND THROUGH CURB
AutoCAD SHX Text
#3 @ 18" O.C. BOTH WAYS
AutoCAD SHX Text R 1 "12"
AutoCAD SHX Text R 3"
AutoCAD SHX Text
38" RADIUS 2-#3 BAR CONT.
AutoCAD SHX Text
OPTIONAL CONSTRUCTION JOINT (SEE DETAIL)
AutoCAD SHX Text
COMPACTED SUBGRADE SEE NOTES
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text 3 "12"
AutoCAD SHX Text 7"
AutoCAD SHX Text
VERTICAL SAW CUT 18" TO " WIDE 316" WIDE (CARRY THROUGH ADJACENT CURB)
AutoCAD SHX Text SELF LEVELING SILICONE JOINT SEALANT OR HOT POURED RUBBER JOINT SEALING COMPOUND PER ASTM D3406
AutoCAD SHX Text 1 "34"
AutoCAD SHX Text
BARS EQUAL SIZE AND SPACING AS SPECIFIED IN PAVEMENT SECTION
AutoCAD SHX Text NOTES: 1. MAX. JOINT SPACING 15'-0" C-C EACH WAY. 2. CONSTRUCTION JOINT PATTERNS SHOULD DIVIDE PAVEMENTS INTO APPROXIMATELY SQUARE PANELS. 3. THE LENGTH OF THE PANEL (LONGITUDINAL) SHOULD NOT BE MORE THAN 25% GREATER THAN ITS WIDTH (TRANSVERSE). 4. JOINT PATTERNS ACROSS LANES SHOULD BE CONTINUOUS.
AutoCAD SHX Text
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 34"=1'-0"
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text 2"
AutoCAD SHX Text 3"
AutoCAD SHX Text 9 "58"
AutoCAD SHX Text 1'-2 "38"
AutoCAD SHX Text 1"
AutoCAD SHX Text 1"
AutoCAD SHX Text
NEW HEAVY PAVEMENT, REFER TO PLANS AND GEOTECHNICAL REPORT.
AutoCAD SHX Text
2% MAX.
AutoCAD SHX Text
#4 BARS AS SHOWN WITH #3 TIES @ 24" O.C.
AutoCAD SHX Text
DOWEL INTO CURB, REFER TO GEOTECH REPORT
AutoCAD SHX Text
EXIST. PAVEMENT AS SHOWN ON PLANS. FIELD VERIFY.
AutoCAD SHX Text 7"
AutoCAD SHX Text 11 "12"
AutoCAD SHX Text SELF LEVELING SILICONE JOINT SEALANT OR HOT POURED RUBBER JOINT SEALING COMPOUND PER ASTM D 3406 FORMED GROOVE ( " WIDE x 1" DP.) 12" WIDE x 1" DP.) EDGES ROUNDED TO " RADIUS14" RADIUS
AutoCAD SHX Text #4 BARS EQUAL SPACING AS SPECIFIED IN PAVEMENT SECTION. DOWEL SQUARE BARS INTO EXIST. PAVEMENT AND SECURE WITH EPOXY.
AutoCAD SHX Text
#4 (TYP.)
AutoCAD SHX Text BOND BREAKER SHALL BE APPLIED TO EXISTING PAVEMENT FACE IMMEDIATELY PRIOR TO PROPOSED CONCRETE PLACEMENT.
AutoCAD SHX Text
DOWELS TO BE MACHINE DRILLED. NO HAND DRILLING ALLOWED.
AutoCAD SHX Text
PAVEMENT SECTION
AutoCAD SHX Text
CONCRETE CURB
AutoCAD SHX Text
SAWED DUMMY JOINT
MOUNTABLE CURB
SYMBOLS LEGENDSYMBOLS LEGENDSYMBOLS LEGEND
GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019Revisions: Date:
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
CONSULTANTS
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
D S E
L I C E N
S
XET
A
RE
L E NGI
EN
T
OE
T S
A
OR
P
S
NI O
SEF
A
F
STANLEY RAY CURTIS
87974 engineer is an offense under the Texas Engineering Practice Act.
without proper notification to the responsible
The seal appearing on this document was authorized by Stanley R. Curtis, 87974 on
10/11/2019. Alteration of a sealed document ES100
NOTES AND SYMBOLS LEGEND
AutoCAD SHX Text
PROVIDE 1"C. WITH PULL STRING TO ACCESSIBLE LOCATION ABOVE CEILING
AutoCAD SHX Text S
AutoCAD SHX Text
MT
AutoCAD SHX Text
SELF-CONTAINED EMERGENCY BATTERY BACKUP DRIVER
AutoCAD SHX Text
LED LIGHT FIXTURE EQUIPPED WITH 2-LAMP
AutoCAD SHX Text
FLUORESCENT LIGHT FIXTURE - CEILING MOUNTED
AutoCAD SHX Text
FLUORESCENT LIGHT FIXTURE - CEILING MOUNTED
AutoCAD SHX Text
LED LIGHT FIXTURE - CEILING MOUNTED
AutoCAD SHX Text
EM
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
EMERGENCY POWER OFF BUTTON (DISCONNECTS POWER TO GENERATOR)
AutoCAD SHX Text
TC
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text
OR
AutoCAD SHX Text
EPO
AutoCAD SHX Text
EPO
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text S
AutoCAD SHX Text
IR
AutoCAD SHX Text S
AutoCAD SHX Text K
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
DISCONNECT SWITCH
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
MOTOR STARTER
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
CONTACTOR
AutoCAD SHX Text
TIME CLOCK
AutoCAD SHX Text
COMBINATION MOTOR STARTER / DISCONNECT SWITCH
AutoCAD SHX Text
SURFACE MOUNTED PANELBOARD - SEE SCHEDULE
AutoCAD SHX Text
FLUSH MOUNTED PANELBOARD - SEE SCHEDULE
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
LED LIGHT FIXTURE - WALL MOUNTED
AutoCAD SHX Text
SELF-CONTAINED EMERGENCY BATTERY BACKUP DRIVER
AutoCAD SHX Text
SELF-CONTAINED EMERGENCY BATTERY BACKUP DRIVER
AutoCAD SHX Text
LED STRIP LIGHT - WALL MOUNTED
AutoCAD SHX Text
EMERGENCY LIGHT FIXTURE
AutoCAD SHX Text
LED LIGHT FIXTURE EQUIPPED WITH 2-LAMP
AutoCAD SHX Text
LED LIGHT FIXTURE - CEILING MOUNTED
AutoCAD SHX Text
LED STRIP LIGHT - CEILING MOUNTED OR CHAIN HUNG
AutoCAD SHX Text
LED STRIP LIGHT - EQUIPPED WITH 2-LAMP
AutoCAD SHX Text
ON EMERGENCY POWER CIRCUIT OR EQUIPPED WITH BATTERY PACK
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DIRECTIONAL ARROWS SHALL BE AS SHOWN ON PLANS
AutoCAD SHX Text
THREE-WAY TOGGLE SWITCH (K3-KEYED 3-WAY)
AutoCAD SHX Text
TWO-POLE TOGGLE SWITCH
AutoCAD SHX Text
SINGLE-POLE TOGGLE SWITCH
AutoCAD SHX Text
FOUR-WAY TOGGLE SWITCH (K4-KEYED 4-WAY)
AutoCAD SHX Text
MANUAL MOTOR STARTER WITH OVERLOADS, TOGGLE OPERATED
AutoCAD SHX Text
ULTRASONIC/PIR SWITCH MOUNTED OCCUPANCY SENSOR
AutoCAD SHX Text
INFRA RED SWITCH MOUNTED OCCUPANCY SENSOR
AutoCAD SHX Text
SINGLE-POLE TOGGLE SWITCH - KEY OPERATED
AutoCAD SHX Text
DIMMER CONTROL SWITCH OR STATION (AS SPECIFIED ON PLANS AND/OR RISER)
AutoCAD SHX Text
INCANDESCENT, LED OR FLUORESCENT DOWNLIGHT FIXTURE - CEILING MOUNTED
AutoCAD SHX Text
EXIT LIGHTS - WALL MT. & CEILING MT. SHOWN - SHADING INDICATES FACE(S),
AutoCAD SHX Text
INCANDESCENT, LED, OR FLUORESCENT DOWNLIGHT FIXTURE - CEILING MOUNTED
AutoCAD SHX Text
INCANDESCENT, FLUORESCENT, OR LED LIGHT FIXTURE - WALL MOUNTED
AutoCAD SHX Text
ABOVE COUNTER
AutoCAD SHX Text
AC
AutoCAD SHX Text
BELOW FINISH CEILING
AutoCAD SHX Text
ABOVE FINISH FLOOR
AutoCAD SHX Text
ABOVE FINISH GRADE
AutoCAD SHX Text
EXPLOSION PROOF
AutoCAD SHX Text
AFG
AutoCAD SHX Text
BFC
AutoCAD SHX Text
EP
AutoCAD SHX Text
GFI
AutoCAD SHX Text
EPO
AutoCAD SHX Text
AFF
AutoCAD SHX Text
EMERGENCY POWER OFF
AutoCAD SHX Text
GROUND FAULT INTERRUPTING
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
GRD
AutoCAD SHX Text
DATA OUTLET: # INDICATES RJ45 DATA MODULES IN 2 GANG, 3 1/2" DEEP BACKBOX.
AutoCAD SHX Text
EXISTING CONDUIT
AutoCAD SHX Text
GROUND, AND EQUIPMENT GROUND INDICATED
AutoCAD SHX Text
JUNCTION BOX - SIZED TO ACCOMODATE CONNECTION
AutoCAD SHX Text
CONDUIT CONCEALED IN OR BELOW FLOOR SLAB OR BELOW GRADE
AutoCAD SHX Text
"POWER RISER DIAGRAM"
AutoCAD SHX Text
EMERGENCY CIRCUIT(S) (SHOWN WITH NON-ARCHED LINES)
AutoCAD SHX Text
FLEXIBLE CONDUIT
AutoCAD SHX Text
BRANCH CIRCUIT IN CONDUIT - SWITCH LEG, PHASE LEG, NEUTRAL, ISOLATED
AutoCAD SHX Text
EMERGENCY POWER OFF STATION (REMOTE SHUNT TRIP) - REFER TO
AutoCAD SHX Text
BRANCH CIRCUIT HOMERUN - PANEL AND CIRCUIT NUMBER INDICATED
AutoCAD SHX Text 10-30R
AutoCAD SHX Text
ISOLATED GROUNDING
AutoCAD SHX Text
OVERHEAD ELECTRIC
AutoCAD SHX Text
MOUNTED
AutoCAD SHX Text
IG
AutoCAD SHX Text
NFDS
AutoCAD SHX Text
OHE
AutoCAD SHX Text
MTD
AutoCAD SHX Text
SURGE PROTECTION
AutoCAD SHX Text
TIME CLOCK
AutoCAD SHX Text
SDBC
AutoCAD SHX Text
TC
AutoCAD SHX Text
SP
AutoCAD SHX Text
UGE
AutoCAD SHX Text
UON
AutoCAD SHX Text
UNDERGROUND ELECTRIC
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
NON-FUSED DISCONNECT SWITCH
AutoCAD SHX Text
SOFT-DRAWN BARE COPPER
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
WP
AutoCAD SHX Text %%uNOTE:
AutoCAD SHX Text
FIXTURES, EQUIPMENT, ETC.
AutoCAD SHX Text
2. SYMBOLS SHOWN DASHED ON PLANS INDICATES EXISTING DEVICES,
AutoCAD SHX Text
1. NOT ALL SYMBOLS MAY APPLY TO THIS PROJECT.
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
AS NOTED ON DRAWINGS
AutoCAD SHX Text
SPECIAL PURPOSE OUTLET - NEMA CONFIGURATION (VOLTAGE, AMPACITY)
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text
SWITCH MOUNTED DIGITAL TIMER - INTERMATIC OR HWD
AutoCAD SHX Text
US2
AutoCAD SHX Text
PP
AutoCAD SHX Text
CEILING MOUNTED BIDIRECTIONAL ULTRASONIC ONLY OCCUPANCY SENSOR
AutoCAD SHX Text
POWER PACK FOR OCCUPANCY SENSORS (MAX OF 1 PER 3 SENSORS)
AutoCAD SHX Text S
AutoCAD SHX Text K3
AutoCAD SHX Text S
AutoCAD SHX Text K4
AutoCAD SHX Text
RATED FOR LOAD AND LOAD TYPE.
AutoCAD SHX Text
CEILING MOUNTED BIDIRECTIONAL DUAL TECHNOLOGY OCCUPANCY SENSOR
AutoCAD SHX Text
PROVIDE CONDUIT BUSHING AND COVERPLATE.
AutoCAD SHX Text
PROVIDE 1"C. WITH PULL STRING TO ACCESSIBLE LOCATION ABOVE CEILING
AutoCAD SHX Text
TELE OUTLET: # INDICATES RJ45 MODULES IN 2 GANG, 3 1/2" DEEP BACKBOX.
AutoCAD SHX Text
PROVIDE CONDUIT BUSHING AND COVERPLATE.
AutoCAD SHX Text
DT2
AutoCAD SHX Text
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
AutoCAD SHX Text
US1
AutoCAD SHX Text
DT1
AutoCAD SHX Text
CEILING MOUNTED ULTRASONIC ONLY OCCUPANCY SENSOR
AutoCAD SHX Text
AutoCAD SHX Text CONTRACTOR SHALL VISIT SITE PRIOR TO BID AND SECURE A FULL SET OF CONTRACT DOCUMENTS TO ENSURE COMPLETE ELECTRICAL BID PACKAGE. PROVIDE ENGRAVED NAMEPLATES ON ALL OF THE FOLLOWING EQUIPMENT: AUTOMATIC STARTERS, GENERATOR, GENERATOR ANNUNCIATOR PANEL, ETC... LABELLING TO COMPLY WITH VA STANDARDS. REFERENCE SPECIFICATIONS. ALL ELECTRICAL EQUIPMENT (CONDUIT, BOXES, SUPPORTS, ETC.) INSTALLED IN EXPOSED CEILING AREAS OR ON BUILDING EXTERIOR SHALL BE PAINTED AS DIRECTED BY THE ARCHITECT. MC CABLE SHALL NOT BE USED ON THIS PROJECT IN LENGTHS EXCEEDING 6' AND ONLY FOR CONNECTING RECEPTACLES IN WALLS OR LIGHT FIXTURE WHIPS. GENERATOR MANUFACTURER SHALL DELIVER EQUIPMENT COMPLETE INCLUDING BATTERIES, CHARGERS, BLOCK HEATERS, REMOTE CONTROL PANEL, STATUS INDICATOR AND OTHER ACCESSORIES AS NECESSARY TO ENSURE A COMPLETE WORKING SYSTEM.
AutoCAD SHX Text ALL WORK SHALL COMPLY WITH THE 2017 EDITION OF THE NATIONAL ELECTRIC CODE (N.E.C.) AND VA ELECTRICAL DESIGN STANDARDS (LATEST EDITION) AS WELL AS ALL CURRENT STATE AND LOCAL CODES. THE SPECIFICATIONS ARE AS BINDING ON THE CONTRACTOR AS THE DRAWINGS. THE CONTRACTOR SHALL READ THE SPECIFICATIONS AND SHALL INCLUDE ALL ITEMS REQUIRED BY THE SPECIFICATIONS BEFORE SUBMITTING A BID. MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE NOTED. ALL CONDUIT SHALL BE CONCEALED UNLESS OTHERWISE NOTED. ALL CONDUIT IN OR BELOW FLOOR SLABS AND BELOW GRADE SHALL BE 1" MINIMUM UNLESS OTHERWISE NOTED. EACH CIRCUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR. MULTI-WIRE CIRCUITS FOR SINGLE PHASE LOADS SHALL NOT SHARE NEUTRALS. EACH SINGLE PHASE 120V OR 277V CIRCUIT SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR PER PHASE. MINIMUM EQUIPMENT GROUND AND NEUTRAL SHALL BE #12AWG COPPER. ALL CONDUCTORS #10 AND SMALLER SHALL BE SOLID COPPER, EXCEPT WHERE FLEXIBILITY IS REQUIRED, AND ALL CONDUCTORS #8 AND LARGER SHALL BE STRANDED COPPER USING BOLTED LUGS AT TERMINALS. ALL ELECTRICAL EQUIPMENT (CONDUIT, BOXES, SUPPORTS, ETC.) INSTALLED IN EXPOSED CEILING AREAS SHALL BE PAINTED AS DIRECTED BY THE ARCHITECT. PVC CONDUIT IS NOT ALLOWED EXCEPT FOR UNDERGROUND FEEDERS ENTRENCHED IN 24" OF BACKFILL WITH MARKER TAPE. ELBOWS AND RISERS TO 6" ABOVE FLOOR TO BE RGS.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text 8.
AutoCAD SHX Text 9.
AutoCAD SHX Text 10.
AutoCAD SHX Text 11.
AutoCAD SHX Text 12.
AutoCAD SHX Text
BRANCH TO CONNECTION
AutoCAD SHX Text ns
AutoCAD SHX Text
NON-SWITCHED
AutoCAD SHX Text
WP
AutoCAD SHX Text
DUPLEX RECEPTACLE - HUBBELL WIRING DEVICE #CR20WHITR W/ COVERPLATE
AutoCAD SHX Text
MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS AND MILLWORK DETAILS.
AutoCAD SHX Text
DUPLEX RECEPTACLE MOUNTED HORIZONTALLY ABOVE COUNTER TOP - VERIFY
AutoCAD SHX Text
MOUNT WITH GROUND TERMINAL UP 18" TO BOTTOM OF BOX (UNO).
AutoCAD SHX Text
QUADRAPLEX RECEPTACLE - (2) HUBBELL WIRING DEVICE #CR20WHITR W/
AutoCAD SHX Text
COVERPLATE. MOUNT WITH GROUND TERMINAL UP 18" TO BOTTOM OF BOX (UNO).
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
GROUND FAULT RECEPTACLE - HUBBELL WIRING DEVICE #GFTR20W W/
AutoCAD SHX Text
COVERPLATE.
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
WEATHERPROOF HOUSING. MOUNT AT 18" TO BOTTOM OF BOX (UNO).
AutoCAD SHX Text
WEATHERPROOF IN USE TYPE RECEPTACLE - HWD #GRFT20W W/RW57500 IN USE
AutoCAD SHX Text
USB
AutoCAD SHX Text
DUPLEX CONVENIENCE RECEPTACLE WITH DUAL USB PORTS - HUBBELL WIRING
AutoCAD SHX Text
DEVICE #USB20X2W WITH COVERPLATE.
AutoCAD SHX Text
CIRCUIT BREAKER
C.B.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
INSTALL ELECTRICAL
GENERATOR
VAMC SAN ANTONIO, TX
671-18-118
Project Director
10/11/2019Revisions: Date:
A/E:
RMDC ENGINEERING, INC.
2815 VALLEY VIEW LANE, SUITE 214
DALLAS, TEXAS 75234
P: 972-488-8077
MIKE DAWES, PE
TEXAS REGISTERED ENGINEERING FIRM: F-15386
CONSULTANTS
STRUCTURAL:
STRUCTURAL STUDIO CONSULTING ENGINEERS
1506 GRIFFIN STREET WEST
DALLAS, TEXAS 75215
214-273-0300
NIGEL BROWN, PE
TEXAS REGISTERED ENGINEERING FIRM: F-11469
D S E
L I C E N
S
XET
A
RE
L E NGI
EN
T
OE
T S
A
OR
P
S
NI O
SEF
A
F
ROBERT M. DAWES
92452 engineer is an offense under the Texas Engineering Practice Act.
without proper notification to the responsible
The seal appearing on this document was authorized by Robert M. Dawes, 92452 on
10/11/2019. Alteration of a sealed document MEP100
SITE PLAN: GENERAL REQUIREMENTS,
PHASING PLAN AND SW3P PLAN
AutoCAD SHX Text
POLYTRAUMA TRANSITIONAL HOUSING FF 978.00
AutoCAD SHX Text
ELEV EQUIP 136
AutoCAD SHX Text
ELEC RM 137
AutoCAD SHX Text
51.96' (5 SPACES)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX…