FURNISH AND INSTALL COMMUNICATIONS TOWER AT 358 SOUTH MAIN STREET
Solicitation number
24/25-25
Issued by
Hartford County, Connecticut

About this file

This document is a Unit Base Foundation Summary for a communications tower project for the Manchester Police Department in Connecticut, prepared by Whitestone Project No. GM2421632.000 on April 10, 2024. The preliminary design document details the technical specifications for a H-22' x 180' tower foundation, including specific dimensions, soil parameters, reinforcement design, and anchor steel selection. The design conforms to International Building Code (IBC), ANSI TIA-222-H standards, and Building Code Requirements for Reinforced Concrete (ACI 318-14), with a Seismic Design Category of B.

The foundation summary provides comprehensive technical details, including a 28.50 ft pad width, 6 ft depth, and 3 ft pier diameter. Material properties are specified with steel tensile strength at 60,000 psi and concrete compressive strength at 4,500 psi. The design includes 37 pad rebar bars (size 8), 12 pier vertical bars per pier (size 8), and 14 pier ties per pier (size 4). Foundation loading calculations are provided, with shear, moment, compression, and uplift values. The design notes include requirements for concrete placement, on-site geotechnical engineer confirmation of soil strengths, site grading, and a recommended crushed stone layer under the foundation.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

nd716431 PRELIMINARY DESIGN. NOT FOR CONSTRUCTION.

Manchester Police H 22.0 180 V 5.0

H-22' x 180' - Manchester Police Department, CT Quote-

Foundation Dimensions Soil Information Per: Material Properties Pad width, W: 28.50 ft Steel tensile str, Fy: 60000 psi

Depth, D: 6.00 ft Conc. Comp. str, F'c: 4500 psi

Ext. above grade, E: 0.50 ft Conc. Density, δ: 150 pcf

Pier diameter, di: 3.00 ft Clear cover, cc: 3.00 in

Pad thickness, T: 1.50 ft Soil Parameters Depth neglected, N: 6.00 ft Soil unit weight, γ: 110 pcf Backfill Compaction

Volume, Vo: 49.05 cy Ultimate Bearing, Bc: 10.000 ksf Lift thickness: 12 in

Cohesion, Co: 1.000 ksf Compaction: 95 %

Reinforcement Design Friction angle, f: 0.0 degrees ASTM D698 pad rebar qty., m_p: 37 bars * Ult. Passive P., Pp: 0.443 pcf size, s_p: 8 Base sliding, μ: 0.40 Tower design conforms to the following:

pier vertical qty, m_c: 12 verticals/pier Seismic Design Cat.: B

* International Building Code (IBC) size, s_c: 8 2.5' cage Water at: none ft * ANSI TIA-222-H

Anchor Steel Selection pier tie qty., m_t: 14 ties/pier Part Number, P/N: 103183 size, s_t: 4 default hook Note:

* Use standees to support top rebar above bottom rebar in mat

Foundation Loading Views of Foundation (not to scale) stress ratio: 95.9% mark up: 4.3%

Shear (Per Leg), Sl: 37.00 kips x 1.04 = 38.59 kips

Shear (total), S: 58.00 kips x 1.04 = 60.49 kips

Moment, M: 6130.00 ft-kips x 1.04 = 6393.59 ft-kips

Compression/Leg, C: 338.00 kips x 1.04 = 352.53 kips

Uplift/Leg, U: 301.00 kips x 1.04 = 313.94 kips

48.00 kips = 48.00 kips

Additional Notes:

* No foundation modifications listed.

* See attached "Foundation Notes" for further information.

The centroid of the tower is offset from the centroid of the foundation

* Building Code Requirements for Reinforced Concrete (ACI 318-

14)

* Rebar to be equally spaced, both ways, top & bottom, for a total of 148 bars

Tower Weight, Wt:

(4) 1.25'' Dia. x 60'' Anchor

Bolts Per Leg Grade 105

UNIT BASE FOUNDATION SUMMARY

615709-01

WHITESTONE PROJECT NO.:

GM2421632.000, April 10, 2024

Standard Proctor:

Horizontal Rebar in top 6in of pier for temp. & shrinkage?:

no per TIA-222-H 9.6

615709-01umrp Summary 4/22/2024 4:47 PM

FOUNDATION NOTES

1 CONCRETE IS TO BE PLACED THE SAME DAY THAT THE EXCAVATION IS COMPLETED.

2 THE ON-SITE GEOTECHNICAL ENGINEER SHALL CONFIRM THAT THE INSITU SOIL STRENGTHS MEET OR

EXCEED THOSE PARAMETERS GIVEN IN THE SOIL REPORT.

3 GRADE THE SITE TO DRAIN AWAY FROM FOUNDATION.

4 RECOMMEND THE FOUNDATION BEAR ON A LAYER OF CRUSHED STONE PLACED OVER THE BEDROCK. WHERE

FOUNDATION SUBGRADE IS BEDROCK, FOOTING SHOULD BE UNDERLAIN BY A MINIMUM EIGHT-INCH THICK

LAYER OF MINUS 0.375-INCH CRUSHED STONE

615709-01umrp Notes 4/22/2024 4:47 PM