These documents are technical HVAC design plans and a state and local contract opportunity for The Gatehouse HVAC and Electrical Upgrades Project located in Mahoning Township, Montour County, Pennsylvania. The project involves installing a new HVAC system at 21 Gatehouse Drive, Danville, PA 17821, with sealed bids to be received via PennBid or in person until 11:00 A.M. on September 24, 2025. The scope includes installing twelve individual wall-mounted units with wireless thermostats across all major rooms, while maintaining the existing heat system as a backup. Three outdoor condenser inverters will be placed along the facility's exterior, with all piping and electrical connections routed underground through the foundation wall and into the basement, then dispersed throughout the building.
The project will utilize Mitsubishi wall-mounted indoor units (MSZ-GL24NA-U1) and exterior units (MUZ-GL24NA-U1), with all infrastructure routed near current radiator pipes and concealed by crown molding. The design preserves the existing building's infrastructure while modernizing the HVAC system, with careful attention to minimizing exterior modifications. The contract documents are prepared by Peters Consultants, Inc., a registered engineering firm, and specify that all work must comply with 2018 International Building Code and 2017 National Electrical Code with state amendments. No specific budget or funding source is explicitly detailed in the provided documents.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAHONING TOWNSHIP - MONTOUR COUNTY - PENNSYLVANIA
2701 Columbia Blvd.
Bloomsburg , Pa. 17815 info1@petersconsultants.com - www.petersconsultants.com
PCI PETERS CONSULTANTS, INC.
CONSULTING ENGINEERS/LAND SURVEYORS
COPYRIGHT PETERS CONSULTANTS, INC. 2025. THESE PLANS ARE INSTRUMENTS OF SERVICE
AND REMAIN THE EXCLUSIVE PROPERTY OF PETERS CONSULTANTS, INC. THE CLIENT IS
GRANTED A NON-EXCLUSIVE LICENSE TO USE THE PLANS SOLELY TO CONSTRUCT THE
PROJECT DEPICTED ON THE PLANS. THE PLANS MAY NOT BE MODIFIED IN ANY WAY AND MAY
NOT BE USED FOR SUBSEQUENT ADDITIONS, RENOVATIONS, MODIFICATIONS, OR
ALTERATIONS TO THE PROJECT WITHOUT THE EXPRESS WRITTEN CONSENT OF PETERS
CONSULTANTS, INC. PETERS CONSULTANTS, INC. ASSUMES NO LIABILITY FOR USE OF THE
PLANS BEYOND THE NON-EXCLUSIVE LICENSE GRANTED HEREIN. Sheet: 1 of 3
File No.: 3697Dwn By: DAV
Ck. By: DRPDate: 08/25/2025
REVISIONS BYDATE
P R
O
JE
C T:
- D
R A
W
IN
G : 3
7.
dw g
- L A
Y O
U T:
C ov er S he et
No.27528-E
P E
N N S Y L V A N
I A
CO
MMONWEA L T H
O F
REGISTERED
DENNIS R. PETERS
ENGINEER
PROFESSIONAL
D en ni s R
. P ete rs HVAC DESIGN
COVER SHEET
FOR
THE GATEHOUSE
LOCATED AT
21 GATEHOUSE DRIVE
DANVILLE, PA 17821
NOTE
SHEETS 1-3 OF 3 MUST BE READ TOGETHER AND ARE TO
BE CONSIDERED ONE INTEGRAL PLAN
NOTES:
ON-SITE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ACTUAL FIELD DIMENSIONS
AND SHALL BE RESPONSIBLE TO MEET ALL APPLICABLE STATE, LOCAL AND
FEDERAL CODES.
ALL CONSTRUCTION SHALL MEET 2018 INTERNATIONAL BUILDING CODE WITH STATE
AMENDMENTS AND 2017 NATIONAL ELECTRICAL CODE WITH STATE AMENDMENTS.
DESIGN DRAWINGS ARE REPRESENTATIVE OF DESIGN INTENT AND
CODE COMPLIANCE. ACTUAL DIMENSIONS AND PHYSICAL LOCATIONS MAY VARY
DUE TO CONSTRUCTION ACTIVITIES.
ALL HEATING WORK SHALL BE THE RESPONSIBILITY OF THE HEATING CONTRACTOR
AND INSTALLED PER THE 2017 NATIONAL ELECTRIC CODE AND THE 2018
INTERNATIONAL MECHANICAL CODE.
ALL REPAIRS WHETHER INDICATED OR NOT SHALL COMPLY WITH ALL APPLICABLE
BUILDING CODES INCLUDING BUT NOT LIMITED TO IBC, ICC, ETC.
MOUNT HARDWARE TO COMPLY WITH INDUSTRY STANDARDS AND CODE
COMPLIANCE.
FIELD VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING CONDITIONS AT THE
SITE PRIOR TO THE START OF WORK.
SAFEGUARD THE OWNER'S PROPERTY DURING CONSTRUCTION AND REPLACE
DAMAGED PROPERTY OF THE OWNER'S PROPERTY TO THE ORIGINAL CONDITION.
ALL ELECTRICAL TYPES AND METHODS SHALL CONFORM WITH ALL CURRENT "IBC"
AND "NEC" CODES.
ALL THERMOSTATS 48" MAXIMUM HEIGHT.
BUILDING CONTRACTOR TO VERIFY ALL DIMENSIONS BEFORE PROCEEDING.
DIMENSIONS ALWAYS TAKE PRECEDENT OVER SCALE MEASUREMENTS.
ALL WORKMANSHIP TO BE OF A STANDARD EQUAL TO GOOD BUILDING PRACTICE, IN
ALL RESPECTS.
NOTHING TO BE INSTALLED OR ATTACHED TO THE EXTERIOR OF THE BUILDING.
EXISTING HEATING SYSTEM TO REMAIN.
ALL NEW LINES SHALL BE RUN ON THE INTERIOR OF THE BUILDING ALONG THE SIDE
OF THE EXISTING HEAT PIPING OR AS NOTED.
ALL NEW HVAC LINES WILL ORIGINATE FROM THE NEW EXTERIOR UNITS AND ROUTE
INTO THE BASEMENT, AND WILL BE DISTRIBUTED THROUGHOUT THE BUILDING.
ALL NEW LINES TO RUN NEAR EXISTING LINES. NEW HOLES WILL BE REQUIRED
THROUGH INTERIOR FLOORS AND INTERIORS WALLS AS NEEDED. NEW HOLES
SHOULD BE MADE ONLY TO THE SIZE THAT IS NECESSARY FOR PIPING AND
ELECTRICAL CONNECTION.
ALL CONDENSATE LINES FROM THE UNITS TO BE RUN TO NEAREST SANITARY
SEWER LINE WITH INSTALLATION BY GOOSE NECK AND CUT INTO NEAREST
SANITARY SEWER LINES
HVAC DESIGN
FOR
THE GATEHOUSE
LOCATED AT
21 GATEHOUSE DRIVE, DANVILLE, PA 17821
SHEET INDEX
SHEET
1 COVER SHEET
2 FIRST & SECOND FLOOR PLANS
3 THIRD FLOOR PLAN
LEGEND
New Wall Unit
Existing Wall
Electrical Box
Existing Radiator
Existing Vertical Pipe
FRONT PERSPECTIVE RIGHT PERSPECTIVE
BACK PERSPECTIVE
LEFT PERSPECTIVE
Not to Scale
New Wireless Thermostat
New Horizontal Piping
New Exterior Unit
Slanted Ceiling
New Concrete Pad
First Floor Plan
SCALE: 1/4" = 1'
Office #1
Office #2
9' 5 58" Finished Ceiling Height
Entrance 7' 2 18" Finished Ceiling Height
Bedroom #7 9' 6" Finished Ceiling Height
Laundry Room 8' Unfinished Ceiling Height
Bathroom #1 7' 9 34" Finished Ceiling Height
Hallway
Hallway
7' 10 13" Unfinished Ceiling Height
8' 1" Unfinished Ceiling Height
Bedroom #2 9' 9 38" Finished Ceiling Height
UP
UP
UP
Common Room 9' 10 14" Finished Ceiling Height
Bedroom #1 9' 10 38" Finished Ceiling Height
Kitchen 8' 9 58" Unfinished Higher Ceiling Height 8' 6 12" Finished Lower Ceiling Height
FrontFront
Bathroom #2
Second Floor Plan
SCALE: 1/4" = 1'
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator: 1' 7" Height
New Wall Unit
N ew
W al l U ni t
N ew
W al l U ni t
New Wall Unit
New Wall Unit
New Wall Unit
N ew
W al l U ni t
New Wall Unit
Locked
Locked Locked
Locked
Locked
Locked
New Exterior UnitNew Exterior Unit
Enters through foundation wall
NOTES:
NEW WALL UNITS SHALL CONSIST OF MITSUBISHI MSZ-GL24NA-U1 WALL-MOUNTED INDOOR UNITS OR APPROVED EQUAL. SEE APPENDIX J OF THE CONTRACT DOCUMENTS.
NEW EXTERIOR UNITS SHALL CONSIST OF MITSUBISHI MUZ-GL24NA-U1 OR APPROVED EQUAL. SEE APPENDIX J OF THE CONTRACT DOCUMENTS.
New Exterior Unit
MAHONING TOWNSHIP - MONTOUR COUNTY - PENNSYLVANIA
2701Columbia Blvd.
Bloomsburg , Pa. 17815 info1@petersconsultants.com - www.petersconsultants.com
PCI PETERS CONSULTANTS, INC.
CONSULTING ENGINEERS/LAND SURVEYORS
COPYRIGHT PETERS CONSULTANTS, INC. 2025. THESE PLANS ARE INSTRUMENTS OF SERVICE
AND REMAIN THE EXCLUSIVE PROPERTY OF PETERS CONSULTANTS, INC. THE CLIENT IS
GRANTED A NON-EXCLUSIVE LICENSE TO USE THE PLANS SOLELY TO CONSTRUCT THE
PROJECT DEPICTED ON THE PLANS. THE PLANS MAY NOT BE MODIFIED IN ANY WAY AND MAY
NOT BE USED FOR SUBSEQUENT ADDITIONS, RENOVATIONS, MODIFICATIONS, OR
ALTERATIONS TO THE PROJECT WITHOUT THE EXPRESS WRITTEN CONSENT OF PETERS
CONSULTANTS, INC. PETERS CONSULTANTS, INC. ASSUMES NO LIABILITY FOR USE OF THE
PLANS BEYOND THE NON-EXCLUSIVE LICENSE GRANTED HEREIN. Sheet 2 of 3
File No.: 3697Dwn By: DAV
Ck. By: DRPDate: 08/25/2025
REVISIONS BYDATE
P R
O
JE
C T:
- D
R A
W
IN
G : 3
7.
dw g
- L A
Y O
U T:
No.27528-E
P E
N N S Y L V A N
I A
CO
MMONWEA L T H
O F
REGISTERED
DENNIS R. PETERS
ENGINEER
PROFESSIONAL
D en ni s R
. P ete rs HVAC DESIGN
FIRST & SECOND FLOOR PLANS
FOR
THE GATEHOUSE
LOCATED AT
21 GATEHOUSE DRIVE
DANVILLE, PA 17821
NOTE
SHEETS 1-3 OF 3 MUST BE READ TOGETHER AND ARE TO
BE CONSIDERED ONE INTEGRAL PLAN
Scale: 1/4" = 1'
1/4 INCH = 1 FEET
04 2 4 8 123 1
AutoCAD SHX Text 17'-10 "34"
AutoCAD SHX Text 32'-3"
AutoCAD SHX Text 14'-11 "34"
AutoCAD SHX Text 37'-4"
AutoCAD SHX Text 17'-11"
AutoCAD SHX Text 14'-11 "38"
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text 17'-10 "34"
AutoCAD SHX Text 32'-3"
AutoCAD SHX Text 14'-11 "34"
AutoCAD SHX Text 37'-4"
AutoCAD SHX Text 7'-5"
AutoCAD SHX Text 14'-11 "38"
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text Top of window to ceiling: 11"
AutoCAD SHX Text Top of window to ceiling: 1'
AutoCAD SHX Text Pipe
AutoCAD SHX Text Electrical Box
AutoCAD SHX Text Pipes
AutoCAD SHX Text Pipe
AutoCAD SHX Text Floor to bottom of window: 3' 3" Window opening: 4' 9 " 14"
AutoCAD SHX Text Pipes
AutoCAD SHX Text Floor to bottom of window: 3' 4" Top of window to ceiling: 1'
AutoCAD SHX Text Electrical Box
AutoCAD SHX Text Floor to bottom of window: 2' 2" Top of window to ceiling: 1' 6 " 34"
AutoCAD SHX Text Floor to bottom of window: 2' 2" Top of window to ceiling: 1' 6 "14"
AutoCAD SHX Text Pipes
AutoCAD SHX Text Floor to bottom of window: 2' 2" Top of window to ceiling: 1' 6"
AutoCAD SHX Text Floor to bottom of window: 2' 2" Top of window to ceiling: 1' 6"
AutoCAD SHX Text Electrical Box
AutoCAD SHX Text Top of cabinet to ceiling: 1' 3 "14"
AutoCAD SHX Text Top of window to ceiling: 8"
AutoCAD SHX Text Floor to bottom of window: 1' 1" Top of window to ceiling: 7"
AutoCAD SHX Text Top of cabinet to ceiling: 1' 7"
AutoCAD SHX Text Pipe
AutoCAD SHX Text Pipes
AutoCAD SHX Text Floor to bottom of window: 2' 2" Top of window to ceiling: 1'
AutoCAD SHX Text Floor to bottom of window: 2' 2" Top of window to ceiling: 1' 5"
AutoCAD SHX Text Floor to bottom of window: 2' 1" Top of window to ceiling: 1' 6"
AutoCAD SHX Text Pipes
AutoCAD SHX Text 2'-7"
AutoCAD SHX Text 2'-7"
AutoCAD SHX Text Existing Box Out
AutoCAD SHX Text First Floor Data
AutoCAD SHX Text Office #1
AutoCAD SHX Text 17X17
AutoCAD SHX Text
290 SF
AutoCAD SHX Text
5,800 BTU
AutoCAD SHX Text Office #2
AutoCAD SHX Text 17X17
AutoCAD SHX Text
290 SF
AutoCAD SHX Text
5,800 BTU
AutoCAD SHX Text Laundry Room
AutoCAD SHX Text 17X17
AutoCAD SHX Text
290 SF
AutoCAD SHX Text
5,800 BTU
AutoCAD SHX Text Bedroom #7
AutoCAD SHX Text 14X10
AutoCAD SHX Text
140 SF
AutoCAD SHX Text
2,800 BTU
AutoCAD SHX Text Second Floor Data
AutoCAD SHX Text Common Room
AutoCAD SHX Text 15X13
AutoCAD SHX Text
195 SF
AutoCAD SHX Text
3,900 BTU
AutoCAD SHX Text Bedroom #1
AutoCAD SHX Text
100 SF
AutoCAD SHX Text
2,000 BTU
AutoCAD SHX Text Kitchen
AutoCAD SHX Text 12X13
AutoCAD SHX Text
156 SF
AutoCAD SHX Text
3,120 BTU
AutoCAD SHX Text Bedroom #2
AutoCAD SHX Text 13X15
AutoCAD SHX Text
195 SF
AutoCAD SHX Text
3,900 BTU
UP
Bathroom #3 8' Finished Ceiling Height
Landing 7' 7 38" Unfinished Ceiling Height
Bedroom #3 7' 7" Unfinished Ceiling Height
Slanted Ceiling
Slanted Ceiling
Bedroom #4 7' 7" Unfinished Ceiling Height
Bedroom #5 7' 6" Unfinished Ceiling Height
Slanted Ceiling
Slanted Ceiling
Bedroom #6 7' 6 12" Unfinished Ceiling Height
Slanted Ceiling
Slanted Ceiling
Front
Third Floor Plan
SCALE: 1/4" = 1'
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
Existing Radiator
New Wall Unit
New Wall Unit
New Wall Unit
Locked
Locked
Locked
Locked
CROWN MOLDING DETAIL
NOT TO SCALE1
BOX OUT DETAIL
NOT TO SCALE2
N ew
W al l U ni t
NOTES:
NEW WALL UNITS SHALL CONSIST OF MITSUBISHI MSZ-GL24NA-U1 WALL-MOUNTED INDOOR UNITS OR APPROVED EQUAL. SEE APPENDIX J OF THE CONTRACT DOCUMENTS.
NEW EXTERIOR UNITS SHALL CONSIST OF MITSUBISHI MUZ-GL24NA-U1 OR APPROVED EQUAL. SEE APPENDIX J OF THE CONTRACT DOCUMENTS.
MAHONING TOWNSHIP - MONTOUR COUNTY - PENNSYLVANIA
2701Columbia Blvd.
Bloomsburg, Pa. 17815 info1@petersconsultants.com - www.petersconsultants.com
PCI PETERS CONSULTANTS, INC.
CONSULTING ENGINEERS/LAND SURVEYORS
COPYRIGHT PETERS CONSULTANTS, INC. 2025. THESE PLANS ARE INSTRUMENTS OF SERVICE
AND REMAIN THE EXCLUSIVE PROPERTY OF PETERS CONSULTANTS, INC. THE CLIENT IS
GRANTED A NON-EXCLUSIVE LICENSE TO USE THE PLANS SOLELY TO CONSTRUCT THE
PROJECT DEPICTED ON THE PLANS. THE PLANS MAY NOT BE MODIFIED IN ANY WAY AND MAY
NOT BE USED FOR SUBSEQUENT ADDITIONS, RENOVATIONS, MODIFICATIONS, OR
ALTERATIONS TO THE PROJECT WITHOUT THE EXPRESS WRITTEN CONSENT OF PETERS
CONSULTANTS, INC. PETERS CONSULTANTS, INC. ASSUMES NO LIABILITY FOR USE OF THE
PLANS BEYOND THE NON-EXCLUSIVE LICENSE GRANTED HEREIN. Sheet 3 of 3
File No.: 3697Dwn By: DAV
Ck. By: DRPDate: 08/25/2025
REVISIONS BYDATE
P R
O
JE
C T:
- D
R A
W
IN
G : 3
7.
dw g
- L A
Y O
U T:
No.27528-E
P E
N N S Y L V A N
I A
CO
MMONWEA L T H
O F
REGISTERED
DENNIS R. PETERS
ENGINEER
PROFESSIONAL
D en ni s R
. P ete rs HVAC DESIGN
THIRD FLOOR PLAN
FOR
THE GATEHOUSE
LOCATED AT
21 GATEHOUSE DRIVE
DANVILLE, PA 17821
NOTE
SHEETS 1-3 OF 3 MUST BE READ TOGETHER AND ARE TO
BE CONSIDERED ONE INTEGRAL PLAN
Scale: 1/4" = 1'
1/4 INCH = 1 FEET
013 128424
AutoCAD SHX Text 37'-4"
AutoCAD SHX Text 2'-7"
AutoCAD SHX Text 17'-10 "34"
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text 17'-11"
AutoCAD SHX Text 14'-11 "34"
AutoCAD SHX Text 14'-11 "38"
AutoCAD SHX Text 32'-3"
AutoCAD SHX Text Floor to bottom of window: 2' 7 " 12" Top of window to ceiling: 6 "12"
AutoCAD SHX Text Electrical Box
AutoCAD SHX Text Floor to bottom of window: 2' 8" Top of window to ceiling: 1'
AutoCAD SHX Text Floor to bottom of window: 2' 11" Top of window to ceiling: 5 "12"
AutoCAD SHX Text NOTE: 1. COULD VARY BASED ON HOW MANY LINES ARE REQUIRED. 2. NOTHING IS TO BE INSTALLED ONTO THE EXTERIOR OF THE BUILDING.
AutoCAD SHX Text Electrical Line
AutoCAD SHX Text Liquid Supply Line
AutoCAD SHX Text Gas Return Line
AutoCAD SHX Text Trim
AutoCAD SHX Text Wall
AutoCAD SHX Text Ceiling
AutoCAD SHX Text NOTE: 1. COULD VARY BASED ON HOW MANY LINES ARE REQUIRED. 2. NOTHING IS TO BE INSTALLED ONTO THE EXTERIOR OF THE BUILDING.
AutoCAD SHX Text Line Set Cover
AutoCAD SHX Text Wall
AutoCAD SHX Text Condensation Line
AutoCAD SHX Text Third Floor Data
AutoCAD SHX Text Bedroom #3
AutoCAD SHX Text 13X15
AutoCAD SHX Text
195 SF
AutoCAD SHX Text
3,900 BTU
AutoCAD SHX Text Bedroom #6
AutoCAD SHX Text 14X11
AutoCAD SHX Text
154 SF
AutoCAD SHX Text
3,100 BTU
AutoCAD SHX Text Bedroom #5
AutoCAD SHX Text 14X11
AutoCAD SHX Text
154 SF
AutoCAD SHX Text
3,100 BTU
AutoCAD SHX Text Bedroom #4
AutoCAD SHX Text 14X13
AutoCAD SHX Text
182 SF
AutoCAD SHX Text
3,100 BTU