570-17-210.OPC.DWG.20221021Part-3.pdf

PDF 10 MB Posted

Attached to
Z2DA--Remodel Emergency Department (ED) Observation Bed Fresno
Solicitation number
36C26123R0008
Issued by

About this file

This federal contract opportunity solicitation seeks proposals to remodel the emergency department observation bed area at the Fresno VA Medical Center. The solicitation number is 36C26123R0008 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21. Offerors are requested to provide all labor, materials, equipment, and supervision to complete the emergency department remodel project. The work includes demolition, construction, and related tasks. The period of performance is 365 calendar days from award. Proposals are due by the date specified in the solicitation and the contract award date will be determined subsequently. Pricing shall be fixed for the period of performance.

View the file

Other files

File Type Posted
Technical Question Tracking Sheet -RFI 1-38 -ED Beds 02212023.pdf PDF
36C26123R0008 0007.docx DOCX document
36C26123R0008 0006.docx DOCX document
WD_CA20230018_02102023.pdf PDF
36C26123R0008 0005.docx DOCX document
Technical Question Tracking Sheet -RFI 1-36 -ED Beds-MRP-020823.pdf PDF
36C26123R0008 0004.docx DOCX document
36C26123R0008 0003.docx DOCX document
Site Visit_01262023 Sign in Sheet.pdf PDF
36C26123R0008 0002.docx DOCX document
36C26123R0008 0001.docx DOCX document
570-17-210.OPC.DWG.20230112Part-1.pdf PDF
Attachment A_Factor 1_Experience_01052023.xlsx XLSX spreadsheet
570-17-210.OPC.Specs.20221024.pdf PDF
ACM Report.pdf PDF
WD_CA29_11042022.pdf PDF
570-17-210.OPC.DWG.20221021Part-2.pdf PDF
Attachment C_Large Business Subcontracting Plan Template_01032023.docx DOCX document
Attachment B_Supplemental Price Breakdown_11222022.xlsx XLSX spreadsheet
36C26123R0008.docx DOCX document
Attachment D_Request for Information (RFI) Form_36C26123R0008.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

V

V

V

F F

1N

F 2 2

TV F

2 21

N

N 2 2 1

N 2 2 1

N 2 2 1

N 2 2 1

N

2 2 2

2 2

TV

F

2 2

F

S S

BA(E)

BB(E)

BE1(E)

BE2(E)

M C

C E

(E

M C

C (E

1-BPH

RF-6

(MCCE)

FACP

M C

C N

B (E

BE3

BESB

BEMD(E)

MSB

RF-5RF-5

RF-6RF-6

SF-3SF-3

SF-4SF-4

BECD(E)

AREAWAY

1 1

1 2

F4/ED100C

IT RACK

NC RACK

F4/ED100B

VAV-1-7

AREAWAY

OBSERVATION/

TREATMENT RM

B1C11

OBSERVATION/

TREATMENT RM

B1C10

OBSERVATION/

TREATMENT RM

B1C13

LOCKER RM

B1C20A

TRANSFORMER RM

B1C17A

STAFF LOUNGE

B1C20

STAIR

B1C21

OBSERVATION/

TREATMENT RM

B1C12

ELECTRIC CLOSET

B1C16

TELEPHONE CLOSET

B1C15

CORRIDOR

B1C-4

ON-CALL RM

B1C18TOILET

B1C19

OBSERVATION/

TREATMENT RM

B1C09

MECHANICAL ROOM

B1C39

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

D

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:0

P

M

ED100D

ELECTRICAL DEMO PLAN - LEVEL B

- AREA D

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

1 ALL EQUIPMENT AND DEVICES INDICATED HALFTONE ARE EXISTING TO REMAIN,

UNO.

2 ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY

BACK TO NEAREST POINT OF SERVICE, UNO.

3 MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.

4 MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

5 CONTRACTOR SHALL FIELD VERIFY BRANCH CIRCUIT INFORMATION NOTATED FOR

RE-USE PRIOR TO ROUGH-IN.

1/4" = 1'-0" F4

ELECTRICAL DEMO PLAN - LEVEL B - AREA D

1 DEMOLISH ELECTRICAL SERVICE INCLUDING CONDUIT, SWITCHES, FEEDERS AND BRANCH CIRCUIT

BREAKER FEEDING THE EQUIPMENT BACK TO THE POINT OF SERVICE.

2 REMOVE MECHANICAL CONTROL PANEL IN IT'S ENTIRETY.

3 REMOVE VFDS SF-3 AND RF-5 IN THEIR ENTIRETY BACK TO THEIR RESPECTIVE DISCONNECT

SWITCHES LOCATED AT THE AH-3.

4 DISCONNECT VFD RF-6 FROM MCCE AND REWIRE TO MCC1. REFER TO SHEET EP101 FOR ADDITIONAL

INFORMATION.

5 DISCONNECT VFD SF-4 AND RELOCATE TO SECTION OF WIREWAY TO REMAIN. REFER TO SHEET

EP101 FOR ADDITIONAL INFORMATION.

6 REMOVE SECTION OF WIREWAY PRESENTLY SERVING VFDS SF-3 AND SF-4.

7 REMOVE TRANSFER SWITCHES FROM ELECTRICAL ROOM. INSTALL NEW TRANSFER SWITCHES IN

THE ADJACENT MECHANICAL ROOM PRIOR TO DEMOLITION. REFER TO SHEET EP100D FOR

ADDITIONAL INFORMATION.

09/11/2022

Revisions: Date:

HVAC DDC (E)

C DDC

HVAC DDC (E)8

VAC DDC

8 EXISTING HVAC DDC CONTROL PANELS SHALL BE REMOVED AND REPLACED WITH DIVISION 23

SCOPE OF WORK. PROVIDE POWER SUPPLIES ON CRITICAL BRANCH FOR NEW EQUIPMENT.

COORDINATE WITH DIVISION 23 CONTROLS SUBCONTRACTOR. COORDINATE NEW LOCATIONS WITH

NEW ELECTRICAL SCOPE. SUBMIT COORDINATION DRAWINGS SHOWING NEW ELECTRICAL ROOM

BUILD-OUT.

9 EXISTING ELECTRICAL PANEL AND MATV CONTROL PANEL SHALL BE REMOVED AND RELOCATED

TO COORDINATE WITH NEW ELECTRICAL SCOPE. COORDINATE NEW LOCATIONS WITH NEW

ELECTRICAL SCOPE. SUBMIT COORDINATION DRAWINGS SHOWING NEW ELECTRICAL ROOM

BUILD-OUT.

ELECTRICAL CLOSET B1C16 - EXISTING CONDITIONS

ELECTRICAL CLOSET B1C16 - EXISTING

MATV CP TO BE RELOCATED

ELECTRICAL CLOSET B1C16 - EXISTING

HVAC DDC PANEL TO BE REPLACED

EXISTING HVAC VFD TO BE REPLACED,

PNEUMATIC CP TO BE REMOVED

MATV CP (E)

V

V

V

F

MCC-2

MCC2-E

PNLAMECHANICAL

PENTHOUSE

RADIO

ROOM

EF1EF1

SF2SF2

RF2RF2

RF1RF1

SF1SF1

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

A B

D C

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/1

/2

:2

:3

P

M

ED102

ELECTRICAL DEMO PLAN - ROOF

LEVEL

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

1 ALL EQUIPMENT AND DEVICES INDICATED HALFTONE ARE EXISTING TO REMAIN,

UNO.

2 ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY

BACK TO NEAREST POINT OF SERVICE, UNO.

3 MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.

4 MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

5 CONTRACTOR SHALL FIELD VERIFY BRANCH CIRCUIT INFORMATION NOTATED FOR

RE-USE PRIOR TO ROUGH-IN.

1 REMOVE POWER ASSOCIATED WITH EXHAUST FAN IN IT'S ENTIRETY BACK TO DISCONNECT SWITCH.

2 REMOVE DISCONNECT SWITCH IN IT'S ENTIRETY BACK SOURCE.

1/8" = 1'-0" F4

ELECTRICAL DEMO PLAN - ROOF LEVEL

Revisions: Date:

09/11/2022

O O O

L L L

D

D

O

L

L

L

L

O

LINEN CLOSET

B1C39

EMS CLOSET

B1C36

FEMALE RR

B1C32

PATIENT COMFORT

ROOM

BC127

LINEN CLOSET

B1C42

LINEN CLOSET

B1C41

INTERVENTION

(SECLUSION) ROOM

B1C28

CRASH CART

ALCOVE

WAITING

B1C-1

CORRIDOR

B1C-6

MALE RR

B1C33

SOILED UTILITY

B1C53

CLEAN UTILITY

B1C52

STF TLT

BC51

NEW OBSERVATION

ROOM

B1C23

NEW OBSERVATION

ROOM

BC24

HAC

BC50

CORRIDOR

B1C-2

OBSERVATION/

TREATMENT RM

B1C14

CORRIDOR

B1C-1

NEW OBSERVATION

ROOM

B1C34K

PAT TLT

B1C34J

HALL

B1C-6A

NEW OBSERVATION

ROOM

B1C34E

CLEAN UTILITY

BC26

PAT TLT

B1C25A

CHIEF OF ER

B1C35

HEAD NURSE

B1C37

ELEVATOR

S-6

ELEVATOR

S-5

ELEVATOR EQUIP RM

B1C40

STAIR NO.4

B1C43

CORRIDOR

B1C-9

G1, G1 G1, L1

L1

F3

M1, M1, M1, M1, L1, M1, j

M1, j

L2, L2, M2, d

D1

D2, L2,L2, c

M1, c M1, c b a j

D2, D2, D2, D2, D2, D2, D2, M2, d

M2, e

M2, e

M2, f

M2, f

M2, g

M2, g d e f g

D2, G3, D2, D2, G1

G1, 12

D2, 12

NEW OBSERVATION

ROOM

B1C34G

NEW OBSERVATION

ROOM

B1C34C

NEW OBSERVATION

ROOM

B1C34A

HALL

B1C-6A

NEW NURSES

STATION

B1C34F

NEW NURSES

STATION

B1C34B

NEW OBSERVATION

ROOM

B1C21

CORRIDOR

B1C-4

3 32

G3, D2, D2, C1, S1, C1, D2, C1, D2, C1, D2, C1, C1, (TYP)

(TYP)

BE1(E)- 4

BE1(E)- 4

BB(E)- 10

BB(E)- 10

BB(E)- 10

BE1(E)- 4

BE1(E)- 4

BB(E)- 12

BB(E)- 12 BB(E)- 12

BB(E)- 2BB(E)- 2BB(E)- 2BB(E)- 2BB(E)- 2BB(E)- 2

BB(E)- 2

BB(E)- 2

BB(E)- 2

BE1(E)- 4

BE1(E)- 4BE1(E)- 4

G1, G1, G1, BE1(E)- 4 BE1(E)- 4 BE1(E)- 4

BE1(E)- 4

BE1(E)- 4

4 4

X1

X1

X1

X1

S1, BB(E)- 10

BB(E)- 10

BB(E)- 10

BB(E)- 10

BB(E)- 10

BB(E)- 10

BB(E)- 10

BB(E)- 10

BE1(E)- 4

BE1(E)- 4

BE1(E)- 4

BE1(E)- 4

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 2

BB(E)- 2

BB(E)- 2

X1, 4

BB(E)- 12

BB(E)- 12

BB(E)- 12

BB(E)- 10

BB(E)- 10

BB(E)- 10

BA(E)- 16

BB(E)- 10

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

B

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:0

P

M

EL100B

ELECTRICAL LIGHTING PLAN -

LEVEL B - AREA B

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

1 PROVIDE A THREE BUTTON, DIGITAL WALL SWITCH FOR CONTROL OF EXAM LIGHTING.

LABEL BUTTONS "OFF", "EXAM" AND "AMBIENT". TYPICAL FOR EACH NEW EXAM SPACE.

2 CONNECT NEW LUMINAIRE TO EXISTING LIGHTING CIRCUITS SHOWN ON THIS SHEET.

3 CONNECT NEW LUMINAIRE TO EXISTING UNSWITCHED LIFE SAFETY BRANCH CIRCUIT

SHOWN ON THIS SHEET.

A ALL LIGHTING IS CONTROLLED BY THE OCCUPANCY SENSOR(S) LOCATED IN THE

ROOM, UNO.

B ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN

UNSWITCHED, 120VAC, LIFE SAFETY BRANCH CIRCUIT.

C ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST

UNSWITCHED, 120VAC, LIFE SAFETY BRANCH CIRCUIT.

D ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST

UNSWITCHES, 120VAC, LIFE SAFETY BRANCH CIRCUIT.

1/4" = 1'-0" F4

LIGHTING PLAN - LEVEL B - AREA B

J

M

J

M

J

M

J

MJ

M

J

M

J

M

J

M

J

MJ

M

J

M

J

J

ELEVATOR

B-19

SOCIAL WORK

OFFICE

B1C01

CLINICAL CHARTING

RM

B1C29

WHEELCH. SCALE

EXAM AREA

B1C04

EXAM AREA

B1C03

INTERVENTION

(SECLUSION) ROOM

B1C28

AOD/ CHECK-IN

B1C30

PROCEDURE RM

B1C05

ENTRANCE

POLICE DISPATCH

B1C02

VESTIBULE

WAITING

B1C-1

TRIAGE RM

B1C31

CHARTING ALCOVE

LINEN CART ALCOVE

CORRIDOR

B1C-1A

ALCOVE,

WHEELCHAIR/

STRETCHER/ LIFT

B1D

VESTIBULE

TOILET

B1C08

X-RAY ALCOVE

TRAUMA RM SMALL

B1C06

TRAUMA RM LARGE

B1C07

CORRIDOR

B1C-5

CORRIDOR

B1C-7

CORRIDOR

B1C-7

NURSE STATION

B1C29A

CORRIDOR

B1C-7

CORRIDOR

B1C-8

TOILET

B1C08

TOILET

B1C08

F /E

P B

F4/EP100D

2 1

2 1

CAV-1-2

DDC-AHU-3- 1

DDC-AHU-3- 2

ZONE 1

ZONE 2

ZONE-1

DDC-AHU-3-1

ZONE-1

DDC-AHU-3-1

ZONE-1

DDC-AHU-3-1

ZONE-1

DDC-AHU-3-1

ZONE-1

DDC-AHU-3-1

ZONE-2

DDC-AHU-3-2

ZONE-2

DDC-AHU-3-2

ZONE-2

DDC-AHU-3-2

ZONE-2

DDC-AHU-3-2 ZONE-2

DDC-AHU-3-2

ZONE-3

DDC-AHU-3-3

CAV-1-7

CAV-1-2

C A

V -1

-8

CAV-1-5

CAV-1-4

VAV-1-1

C A

V -1

-1

VAV-1-2

VAV-1-6

CAV-1-6

C A

V -1

-3

VAV-1-6VAV-1-6

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

A

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:1

P

M

EP100A

ELECTRICAL POWER PLAN - LEVEL

B - AREA A

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.

B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.

C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.

D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT

REQUIREMENTS.

F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION

26 41 00 REQUIREMENTS.

G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH

SPECIFICATION SECTION 27 15 00.

1/4" = 1'-0" F1

POWER PLAN - LEVEL B - AREA A

1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED

AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.

2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE

MECHCANICAL ROOM.

NN

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

M

J

J

J

N N

N N

N

INTERVENTION

(SECLUSION) ROOM

B1C28

LINEN CLOSET

B1C39

EMS CLOSET

B1C36

FEMALE RR

B1C32

PATIENT COMFORT

ROOM

BC127

LINEN CLOSET

B1C41

CRASH CART

ALCOVE

CORRIDOR

B1C-6

MALE RR

B1C33

NEW OBSERVATION

ROOM

B1C23

NEW OBSERVATION

ROOM

BC24

HAC

BC50

CORRIDOR

B1C-1

NEW OBSERVATION

ROOM

B1C34K

PAT TLT

B1C34J

HALL

B1C-6A

NEW OBSERVATION

ROOM

B1C34E

CLEAN UTILITY

BC26

PAT TLT

B1C25A

CHIEF OF ER

B1C35

HEAD NURSE

B1C37

ELEVATOR

S-6

ELEVATOR

S-5

STAIR NO.4

B1C43

LINEN CLOSET

B1C42

HAC

B1C49

SOILED UTILITY

B1C53

CLEAN UTILITY

B1C52

STF TLT

BC51

CORRIDOR

B1C-2

ELEVATOR EQUIP RM

B1C40

CORRIDOR

B1C-9

OBSERVATION/

TREATMENT RM

B1C14

F1/EP100A

F4/EP100C

F4/EP100D

DDC-AHU-3

DDC-AHU-3- 3

DDC-AHU-3- 4

ZONE 4

ZONE 3

DDC-AHU-3- 5

BELP- 1BELP- 1

BELP- 1BELP- 1BELP- 1

B E

LP

B E

LP

B

E

LP

B A

(E

B A

(E

B A

(E

B A

(E

NEW OBSERVATION

ROOM

B1C21

B E

LP

B E

LP

B E

LP

B E

LP

B A

(E

B A

(E

BA(E)- 14 BA(E)- 14

BA(E)- 14

BA(E)- 14

BB(E)- 8

BB(E)- 8

BB(E)- 8

BB(E)- 8

BB(E)- 7

BB(E)- 7

BB(E)- 9

BB(E)- 9 BB(E)- 9

BB(E)- 9

BE1(E)- 21

BE1(E)- 21

BE1(E)- 21

BE1(E)- 27

BE1(E)- 27

BE1(E)- 27

BE1(E)- 27

BE1(E)- 27

BA(E)- 24

BA(E)- 24

BA(E)- 24

BA(E)- 24

BA(E)- 24

BELP- 9

BELP- 9

BB(E)- 4

BB(E)- 4

BB(E)- 6

BB(E)- 6

BB(E)- 6

BB(E)- 6

BB(E)- 30

BB(E)- 30

BB(E)- 30

BB(E)- 30

BELP- 11

BELP- 11

BELP- 10

NEW OBSERVATION

ROOM

B1C34C

NEW OBSERVATION

ROOM

B1C34A

NEW OBSERVATION

ROOM

B1C34G

BELP- 12

BELP- 13

BELP- 13

BELP- 15

BELP- 15

BELP- 14

BELP- 17

BELP- 16

BELP- 17

ZONE 5

ZONE-3

DDC-AHU-3-3

ZONE-3

DDC-AHU-3-3

ZONE-3

DDC-AHU-3-3

ZONE-3

DDC-AHU-3-3

ZONE-3

DDC-AHU-3-3

ZONE-5

DDC-AHU-3-5

ZONE-4

DDC-AHU-3-4

ZONE-4

DDC-AHU-3-4

ZONE-4

DDC-AHU-3-4

ZONE-4

DDC-AHU-3-4

BELP- 8

ZONE-5

DDC-AHU-3-5

ZONE-5

DDC-AHU-3-5

ZONE-5

DDC-AHU-3-5

ZONE-5

DDC-AHU-3-5

BE1(E)- 21

B E

LP

B E

LP

BB(E)- 7

BB(E)- 9

BA(E)- 24

TS FS

F /E

P D

NEW NURSES

STATION

B1C34B

NEW STORAGE

B1C34D

NEW NURSES

STATION

B1C34F

NEW STORAGE

B1C34H

CORRIDOR

B1C-4

WAITING

B1C-1

VAV-1-2

VAV-1-6

VAV-1-12

VAV-1-15

VAV-1-18

VAV-1-17

V A

V -1

-1

VAV-1-8

VAV-1-13

VAV-1-9

VAV-1-11

VAV-1-14

VAV-1-7

VAV-1-6VAV-1-6

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

B

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:1

P

M

EP100B

ELECTRICAL POWER PLAN - LEVEL

B - AREA B

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.

B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.

C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.

D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT

REQUIREMENTS.

F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION

26 41 00 REQUIREMENTS.

G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH

SPECIFICATION SECTION 27 15 00.

1/4" = 1'-0" F4

POWER PLAN - LEVEL B - AREA B

1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED

AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.

2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE

MECHCANICAL ROOM.

3 PROVIDE CONNECTION TO NURSE CALL DEVICE, INTEGRAL TO THE PREFABRICATED BEDSIDE

PATIENT UNIT (PBPU). TYPICAL FOR ALL NEW EXAM SPACES.

4 PROVIDE TWO, J-BOXES SURFACE MOUNTED, ABOVE CEILING FOR ELECTRICAL SERVICE TO THE PREFABRICATED BEDSIDE PATIENT UNIT (PBPU). ONE J-BOX SHALL CONTAIN TWO CRITICAL BRANCH CIRCUITS; ONE DEDICATED (NO SHARED NETURAL OR GROUND) AND ONE SHARED WITH THE ADJAC

5 NEW TAMPER AND FLOW VALVES POWER FROM THE F.A.C.P. PANEL. COORDINATE WITH

MECHCANICAL CONTRATOR FOR EXACT LOCATION AND POWER REQUIREMENTS

V

J

M

J

J

M

LINEN CLOSET

B1C41

NEW OBSERVATION

ROOM

B1C23

NEW OBSERVATION

ROOM

BC24

HAC

BC50

STAIR NO.4

B1C43

CT SCANNER

B1C46

LINEN CLOSET

B1C42

HAC

B1C49

PAT HOLDING

B1C47

SOILED UTILITY

B1C53

CLEAN UTILITY

B1C52

STF TLT

BC51

EQUIP STOR

B1C44

MECHANICAL ROOM

B1C17

OBSERVATION/

TREATMENT RM

B1C14

MCCNB(E)

IT RACK

DDC-AHU-3

DDC-AHU-3- 5

BELP- 1BELP- 1

BELP- 1BELP- 1BELP- 1

B E

LP

B E

LP

B

E

LP

B A

(E

B A

(E

B A

(E

B A

(E

NEW OBSERVATION

ROOM

B1C21

B E

LP

B E

LP

B E

LP

B E

LP

B A

(E

B A

(E

BA(E)- 14 BA(E)- 14

BA(E)- 14

BA(E)- 14

BB(E)- 8

BB(E)- 8

BB(E)- 8

BB(E)- 8

VFD-1

BEEH- 2

VFD-2

BEEH- 3

BB(E)- 7

BB(E)- 7

ZONE-3

DDC-AHU-3-3

ZONE-5

DDC-AHU-3-5

B E

LP

B E

LP

BB(E)- 7

ZONE-5

DDC-AHU-3-5

TS FS

F4/EP100B

F /E

P D

CORRIDOR

B1C-4

CONTROL ROOM

B1C45

VAV-1-6

VAV-1-15

1-AHU-3

VAV-1-7

1-AHU-3

V A

V -1

-1

1-AHU-4

VAV-1-6VAV-1-6

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

C

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:2

P

M

EP100C

ELECTRICAL POWER PLAN - LEVEL

B - AREA C

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.

B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.

C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.

D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT

REQUIREMENTS.

F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION

26 41 00 REQUIREMENTS.

G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH

SPECIFICATION SECTION 27 15 00.

1/4" = 1'-0" F4

POWER PLAN - LEVEL B - AREA C

1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED

AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.

2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE

MECHCANICAL ROOM.

3 REFER TO ONE-LINE DIAGRAM, SEE SHEET E-601 FOR EQUIPMENT ELECTRICAL SERVICE

REQUIREMENTS.

F F

V

J

M

M M

J

M

MM

J

OBSERVATION/

TREATMENT RM

B1C11

OBSERVATION/

TREATMENT RM

B1C10

OBSERVATION/

TREATMENT RM

B1C13

STAIR

B1C21

OBSERVATION/

TREATMENT RM

B1C12

STAIR

B1C21

OBSERVATION/

TREATMENT RM

B1C09

AREAWAY

AREAWAY

TELEPHONE CLOSET

B1C15

CORRIDOR

B1C-4

LOCKER RM

B1C20A

TRANSFORMER RM

B1C17A

STAFF LOUNGE

B1C20

ELECTRIC CLOSET

B1C16

ON-CALL RM

B1C18

TOILET

B1C19

BEMD(E)

BECD(E)

BQHA

BA(E)

BB(E)

BE1(E)

BE2(E)

SF-4SF-4

RF-6RF-6

F4/EP100C

MCCE(E)MCC1(E) MCCNB(E)

BQHAT1

BCHAT

BSHAT

BQHAT2

NC RACK

BEM1

BEEH

BELP T-BELP

BEM1- 9,11,13BEM1- 15,17,19

ZONE 6 DDC-AHU-3- 6

ZONE-6

DDC-AHU-3-6

ZONE-6

DDC-AHU-3-6

ZONE-6

DDC-AHU-3-6

F4/EP100B

MECHANICAL ROOM

B1C17

VAV-1-7

1-AHU-4RF-6

V A

V -1

-5

VAV-1-3 VAV-1-4

EF-1-10EF-1-11

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

D

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:2

P

M

EP100D

ELECTRICAL POWER PLAN - LEVEL

B - AREA D

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.

B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.

C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.

D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT

REQUIREMENTS.

F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION

26 41 00 REQUIREMENTS.

G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH

SPECIFICATION SECTION 27 15 00.

1/4" = 1'-0" F4

POWER PLAN - LEVEL B - AREA D

1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED

AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.

2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE

MECHANICAL ROOM.

F

F

FUTURE

BEM1- 2,4,6

BEM1- 8,10,12

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

A B

D C

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/1

/2

:2

:1

P

M

EP102

ELECTRICAL POWER PLAN - ROOF

LEVEL

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

1/8" = 1'-0" F4

ELECTRICAL POWER PLAN - ROOF LEVEL

1 PROVIDE 480VAC FOR EQUIPMENT. REFER TO ONE-LINE DIAGRAM, SEE SHEET E-601 FOR

ADDITIONAL INFORMATION.

A MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

B CONTRACTOR SHALL COORDINATE FINAL POCs WITH VA COR PRIOR TO ROUGH-IN.

C PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS

D EQUIPMENT CONNECTIONS SHALL BE SIZED PER THE HOMERUN.

E COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH EQUIPMENT

SUPPLIER, PRIOR TO ROUGH-IN.

F ALL EQUIPMENT AND DEVICES ARE EXISTING, UNO.

S

TV

2 2

S

S

F

F

T V

S

F F

N 2 2

CR

F

D

N

D

N W W

C

N

C

N

C

N

C

N

C

N

C

N

E

N

E

N

N

N

N

N

N

N

N

C

N

C

N

C

N

C

N

C

N

C

N

C

N

C

N

C N

C N

P B

P B

A N

N

F

F

F

NNN

LINEN CLOSET

B1C42

LINEN CLOSET

B1C41

SOILED UTILITY

B1C53

CLEAN UTILITY

B1C52

STF TLT

BC51

NEW OBSERVATION

ROOM

B1C23

NEW OBSERVATION

ROOM

BC24

HAC

BC50

CORRIDOR

B1C-2

OBSERVATION/

TREATMENT RM

B1C14

ELEVATOR EQUIP RM

B1C40

STAIR NO.4

B1C43

CORRIDOR

B1C-9

CORRIDOR

B1C-2

ELEVATOR EQUIP RM

B1C40

CORRIDOR

B1C-9

LINEN CLOSET

B1C39

EMS CLOSET

B1C36

FEMALE RR

B1C32

PATIENT COMFORT

ROOM

BC127

CRASH CART

ALCOVE

CORRIDOR

B1C-6

MALE RR

B1C33

OBSERVATION/

TREATMENT RM

B1C14

CORRIDOR

B1C-1

NEW OBSERVATION

ROOM

B1C34K

PAT TLT

B1C34J

HALL

B1C-6A

NEW OBSERVATION

ROOM

B1C34E

CLEAN UTILITY

BC26

PAT TLT

B1C25A

CHIEF OF ER

B1C35

HEAD NURSE

B1C37

ELEVATOR

S-6

ELEVATOR

S-5

STAIR NO.4

B1C43

OBSERVATION/

TREATMENT RM

B1C14

STAIR NO.4

B1C43

WAITING

B1C-1

NEW OBSERVATION

ROOM

B1C21

CORRIDOR

B1C-4

NEW OBSERVATION

ROOM

B1C34A

NEW OBSERVATION

ROOM

B1C34C

NEW OBSERVATION

ROOM

B1C34G

NEW NURSES

STATION

B1C34B

NEW STORAGE

B1C34D

NEW NURSES

STATION

B1C34F

NEW STORAGE

B1C34H

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

B

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/2

/2

:3

:3

P

M

ET100B

ELECTRICAL SYSTEMS PLAN -

LEVEL B - AREA B

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

1/4" = 1'-0" F4

ELECTRICAL SYSTEMS PLAN - LEVEL B - AREA B

1 PROVIDE CONNECTION TO NURSE CALL DEVICE, INTEGRAL TO THE PREFABRICATED

BEDSIDE PATIENT UNIT (PBPU). TYPICAL FOR ALL NEW EXAM SPACES.

A ALL EQUIPMENT AND DEVICES INDICATED HALFTONE ARE EXISTING TO REMAIN, UNO.

B REFER TO SHEET EP100D FOR THE TELECOM ROOM LOCATION AND EQUIPMENT.

C ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH

SPECIFICATION SECTION 27 15 00.

09/11/2022

Revisions: Date:

2 CONTRACTOR SHALL PROVIDE NEW NURSE CALL DEVICES FOR THE RENOVATED

SPACE AND INTEGRATE WITH EXISTING SYSTEM.

BASIS OF DESIGN:

TELLIGENTS C600 SYSTEM

VENDOR: INTEGRATED ELECTRONICS

-HC-PSTN1, STANDARD SGL. PATIENT STATION

-HC-PP2-LAV-3K, 2-BTN PUSH/PULL LAV. STA. 3K

-NUDL4S-H, DOME LIGHT 4 SECTIONS, SPEECH AND BUZZER

-NUDUTY-HU, DUTY STATION

-NGTDSPA-H, NURSE STATION CONSOLE

-HP-IPSWITCH8, PPOWER SWITCH

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

E

N

L

ATS "D"

150A/3P

BYPASS E

N

L

BQHAT2

480Y/277V

150A-4P

BYPASS

M M

M M 7.5 7.5

E

N

L

ATS "A"

150A/3P

BYPASS

E

N

L

BQHAT1

480Y/277V

150A-4P

BYPASS

E

N

L

ATS "B"

150A/3P

BYPASS

E

N

L

BSHAT

480Y/277V

150A-4P

BYPASS

E

N

L

ATS "C"

150A/3P

BYPASS

E

N

L

BCHAT

480Y/277V

150A-4P

BYPASS

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

A

/3 P

BE2

208Y/120V

100A

MLO

2ECLA

208Y/120V

225A

MLO

3ECLA

208Y/120V

225A

MLO

/3

P

MCCB-N

100A

2EHLA

225A

2EHLA

225A

BE1

100A

MCC2-E

480V

SECT.

MCC2-E

208Y/120V

SECT.

MCC2

480V

SECT.

MCC2

208Y/120V

SECT.

2NHA

225A

/3

P

/3

P

/3

P

/3

P

/3

P

/3

P

7.5 20

BA

208Y/120V

100A

MLO

BA

208Y/120V

100A

MLO

1A 208Y/120V

100A

MLO

1B 208Y/120V

100A

MLO

40 40

TRAILER

/3

P

2NLA

100A

2NLB

225A

2NLC

225A

2NLD

225A

3NLA

225A

3NLB

225A

3NLB1

225A

/3

P

PNLA

100A

BEM1

480/277V

100A

MLO

BELP

208Y/120V

100A

MCB

0/

3P

MCCE

208V, 3P, 3W 600A

BECD

208V, 3P, 4W 400A

BEMD

480Y/277V, 3P, 4W 800A

BEEH(NEW)

480Y/277V 3P, 3W 600A

BPH

480Y/277V 3P, 4W 800A

MSB

480Y/277V 3P, 4W 1200A

NLDP

208Y/120V 3P, 4W 600A

MCC1

208V, 3P, 3W 200A

SEE SHEET E-602

FOR CONTINUATION

FIRST FLOOR

BASEMENT

SECOND FLOOR

THIRD FLOOR

ROOF/PENTHOUSE

T-BELP

480V

30KVA

208/120V

4 5

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/1

/2

:2

:2

P

M

E-601

PARTIAL ONE LINE DIAGRAM

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 K. LUKE J. HALPIN

ISSUED FOR

CONSTRUCTION

NTS

F1

PARTIAL ONE LINE DIAGRAM

1 INSTALL NEW EQUIPMENT PER THE 'ESSENTIAL SYSTEM RENOVATION SEQUENCE' SCHEDULE, TYPICAL.

2 CUT OVER FEEDERS INTO THE EXISTING SYSTEMS PER THE 'ESSENTIAL SYSTEM RENOVATION

SEQUENCE' SCHEDULE, TYPICAL.

3 REMOVE EXISTING AUTOMATIC TRANSFER SWITCHES PER THE 'ESSENTIAL SYSTEM RENOVATION

SEQUENCE' SCHEDULE, TYPICAL.

4 REMOVE VFD SF3 AND SF5 IN THEIR ENTIRETY BACK TO AH-3.

5 DISCONNECT VFD RF6 AND RELOCATE TO GUTTER SERVING VFD SF4. REWIRE VFD SF6 TO MCC1.

6 REMOVE GUTTER IN ITS ENTIRETY BACK TO MCCE.

7 GENERAL CONTRACTOR SHALL PROVIDE 30-DAY LOAD MEASUREMENT PER NEC 220.87 OF EQUIPMENT

INDICATED AND PROVIDE THE RESULTS TO THE ENGINEER OF RECORD (EEOR) TO VERIFY THE

EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD PRIOR TO COMMENCEMENT OF ELECTRICAL

WORK.

A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.

B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR

ENTIRETY BACK TO NEAREST POINT OF SERVICE, UNO.

C PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.

D PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.

E COORDINATE FINAL EQUIPMENT CONNECTIONS REQUIREMENTS WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

G NEW PANELBOARDS RATED LESS THAN 100A SHALL HAVE A MINIMUM 10,000 AIC

BRACING.

H NEW PANELBOARDS RATED LESS THAN 400A SHALL HAVE A MINIMUM 22,000 AIC

BRACING.

I NEW PANELBOARDS RATED 400A SHALL HAVE A MINIMUM 35,000 AIC BRACING.

J NEW DISTRIBUTION PANELBOARDS RATED OVER 400A SHALL BE SWITCHBOARDS

AND HAVE A MINIMUM 65,000 AIC BRACING.

FEEDER SCHEDULE

AMP CONDUCTORS - 3W+G (Suffix -3) CONDUCTORS - 4W+G (Suffix -4) CONDUCTORS - 3W,200%N,G (Suffix -N)

20 3#12, 1#12 G, 3/4"C 3#12, 1#12 N, 1#12 G, 3/4"C 3#12, 1#8 N, 1#12 G, 3/4"C

25 3#10, 1#10 G, 3/4"C 3#10, 1#10 N, 1#10 G, 3/4"C 3#10, 1#6 N, 1#10 G, 3/4"C

30 3#10, 1#10 G, 3/4"C 3#10, 1#10 N, 1#10 G, 3/4"C 3#10, 1#6 N, 1#10 G, 3/4"C

35 3#8, 1#10 G, 3/4"C 3#8, 1#8 N, 1#10 G, 3/4"C 3#8, 1#4 N, 1#10 G, 1"C

40 3#8, 1#10 G, 3/4"C 3#8, 1#8 N, 1#10 G, 3/4"C 3#8, 1#3 N, 1#10 G, 1"C

45 3#6, 1#10 G, 3/4"C 3#6, 1#6 N, 1#10 G, 1"C 3#6, 1#2 N, 1#10 G, 1"C

50 3#6, 1#10 G, 3/4"C 3#6, 1#6 N, 1#10 G, 1"C 3#6, 1#2 N, 1#10 G, 1"C

60 3#4, 1#10 G, 1"C 3#4, 1#4 N, 1#10 G, 1-1/4"C 3#4, 1#1 N, 1#10 G, 1-1/4"C

70 3#4, 1#8 G, 1"C 3#4, 1#4 N, 1#8 G, 1-1/4"C 3#4, 1#2/0 N, 1#8 G, 1-1/4"C

80 3#3, 1#8 G, 1-1/4"C 3#3, 1#3 N, 1#8 G, 1-1/4"C 3#3, 1#3/0 N, 1#8 G, 1-1/2"C

90 3#2, 1#8 G, 1-1/4"C 3#2, 1#2 N, 1#8 G, 1-1/4"C 3#2, 1#3/0 N, 1#8 G, 1-1/2"C

100 3#1, 1#8 G, 1-1/4"C 3#1, 1#1 N, 1#8 G, 1-1/2"C 3#1, 1#4/0 N, 1#8 G, 2"C

110 3#1, 1#6 G, 1-1/4"C 3#1, 1#1 N, 1#6 G, 1-1/2"C 3#1, 1-250kcmil N, 1#6 G, 2"C

125 3#1, 1#6 G, 1-1/4"C 3#1, 1#1 N, 1#6 G, 1-1/2"C 3#1/0, 1-300kcmil N, 1#4 G, 2"C

150 3#1/0, 1#6 G, 1-1/2"C 3#1/0, 1#1/0 N, 1#6 G, 2"C 3#2/0, 2#2/0 N, 1#4 G, 2"C

175 3#2/0, 1#6 G, 1-1/2"C 3#2/0, 1#2/0 N, 1#6 G, 2"C 3#3/0, 2#3/0 N, 1#4 G, 2-1/2"C

200 3#3/0, 1#6 G, 2"C 3#3/0, 1#3/0 N, 1#6 G, 2"C 3#4/0, 2#4/0 N, 1#4 G, 2-1/2"C

225 3#4/0, 1#4 G, 2"C 3#4/0, 1#4/0 N, 1#4 G, 2-1/2"C 3-250kcmil, 2-250kcmil N, 1#3 G, 3"C

250 3-250kcmil, 1#4 G, 2"C 3-250kcmil, 1-250kcmil N, 1#4 G, 2-1/2"C 3-300kcmil, 2-300kcmil N, 1#3 G, 3"C

300 3-350kcmil, 1#4 G, 2-1/2"C 3-350kcmil, 1-350kcmil N, 1#4 G, 3"C 3-400kcmil, 2-400kcmil N, 1#3 G, 3-1/2"C

350 3-500kcmil, 1#3 G, 3"C 3-500kcmil, 1-500kcmil N, 1#3 G, 3-1/2"C [2 SETS] 3#3/0, 2#3/0 N, 1#3 G, 2-1/2"C

400 [2 SETS] 3#3/0, 1#3 G, 2"C [2 SETS] 3#3/0, 1#3/0 N, 1#3 G, 2"C [2 SETS] 3#4/0, 2#4/0 N, 1#2 G, 2-1/2"C

450 [2 SETS] 3#4/0, 1#2 G, 2"C [2 SETS] 3#4/0, 1#4/0 N, 1#2 G, 2-1/2"C [2 SETS] 3-250kcmil, 2-250kcmil N, 1#1 G, 3"C

500 [2 SETS] 3-250kcmil, 1#2 G, 2"C [2 SETS] 3-250kcmil, 1-250kcmil N, 1#2 G, 2-1/2"C [2 SETS] 3-300kcmil, 2-300kcmil N, 1#1 G, 3"C

600 [2 SETS] 3-350kcmil, 1#1 G, 2-1/2"C [2 SETS] 3-350kcmil, 1-350kcmil N, 1#1 G, 3"C [2 SETS] 3-400kcmil, 2-400kcmil N, 1#1/0 G, 3-1/2"C

700 [2 SETS] 3-500kcmil, 1#1/0 G, 3"C [2 SETS] 3-500kcmil, 1-500kcmil N, 1#1/0 G, 3-1/2"C

[3 SETS] 3-300kcmil, 2-300kcmil N, 1#1/0 G, 3"C

750 [2 SETS] 3-500kcmil, 1#1/0 G, 3"C [2 SETS] 3-500kcmil, 1-500kcmil N, 1#1/0 G, 3-1/2"C

[3 SETS] 3-300kcmil, 2-300kcmil N, 1#1/0 G, 3"C

800 [3 SETS] 3-300kcmil, 1#1/0 G, 2-1/2"C [3 SETS] 3-300kcmil, 1-300kcmil N, 1#1/0 G, 3"C [3 SETS] 3-350kcmil, 2-350kcmil N, 1#2/0 G, 3"C

900 [3 SETS] 3-350kcmil, 1#2/0 G, 2-1/2"C [3 SETS] 3-350kcmil, 1-350kcmil N, 1#2/0 G, 3"C [3 SETS] 3-400kcmil, 2-400kcmil N1#3/0 G, 3-1/2"C

1000 [3 SETS] 3-400kcmil, 1#2/0 G, 3"C [3 SETS] 3-400kcmil, 1-400kcmil N, 1#2/0 G, 3"C [3 SETS] 3-500kcmil, 2-500kcmil N, 1#3/0 G, 3-1/2"C

1200 [4 SETS] 3-350kcmil, 1#3/0 G, 2-1/2"C [4 SETS] 3-350kcmil, 1-350kcmil N, 1#3/0 G, 3"C [4 SETS] 3-400kcmil, 2-400kcmil N, 1#4/0 G, 3-1/2"C

1600 [5 SETS] 3-400kcmil, 1#4/0 G, 3"C [5 SETS] 3-400kcmil, 1-400kcmil N, 1#4/0 G, 3"C [5 SETS] 3-500kcmil, 2-500kcmil N, 1-300kcmil G, 4"C

2000 [6 SETS] 3-400kcmil, 1-250kcmil G, 3"C [6 SETS] 3-400kcmil, 1-400kcmil N, 1-250kcmil G, 3"C

[6 SETS] 3-500kcmil, 2-500kcmil N, 1-350kcmil G, 4"C

2500 [7 SETS] 3-500kcmil, 1-350kcmil G, 3"C [7 SETS] 3-500kcmil, 1-500kcmil N, 1-350kcmil G, 3-1/2"C

[8 SETS] 3-500kcmil, 2-500kcmil N, 1-400kcmil G, 4"C

3000 [8 SETS] 3-500kcmil, 1-400kcmil G, 3"C [8 SETS] 3-500kcmil, 1-500kcmil N, 1-400kcmil G, 3-1/2"C

[9 SETS] 3-500kcmil, 2-500kcmil N, 1-500kcmil G, 4"C

4000 [11 SETS] 3-500kcmil, 1-500kcmil G, 3"C [11 SETS] 3-500kcmil, 1-500kcmil N, 1-500kcmil G, 3-1/2"C

[12 SETS] 3-500kcmil, 2-500kcmil N, 2-300kcmil G, 4"C

5000 [14 SETS] 3-500kcmil, 2-350kcmil G, 3-1/2"C [14 SETS] 3-500kcmil, 1-500kcmil N, 2-350kcmil G, 3-1/2"C

[15 SETS] 3-500kcmil, 2-500kcmil N, 2-400kcmil G, 4"C

TAG CONDUCTORS, 4W + GEC

9TX 3#8, 1#8 N, 1#8 GEC, 1"C

15TX 3#6, 1#6 N, 1#8 GEC, 1"C

30TX 3#1, 1#1 N, 1#6 GEC, 1-1/2"C

45TX 3#1/0, 1#1/0 N, 1#6 GEC, 2"C

75TX 3-250kcmil, 1-250kcmil N, 1#2 GEC, 2-1/2"C

112.5TX [2 SETS] 3#3/0, 1#3/0 N, 1#1/0 GEC, 2"C

150TX [2 SETS] 3-250kcmil, 1-250kcmil N, 1#1/0 GEC, 2-1/2"C

225TX [3 SETS] 3-300kcmil, 1-300kcmil N, 1#1/0 GEC, 3"C

300TX [3 SETS] 3-400kcmil, 1-400kcmil N, 1#1/0 GEC, 3"C

500TX [5 SETS] 3-400kcmil, 1-400ckmil N, 1#1/0 GEC, 3"C

ESSENTIAL SYSTEM RENOVATION SEQUENCE

1 INSTALL THE NEW AUTOMATIC TRANSFER SWITCHES AND EQUIPMENT BRANCH

PANEL 'BEEH'.

2 INSTALL FEEDERS FROM THE NEW EQUIPMENT TO THE TERMINATION POINTS. DO

NOT CUTOVER THE FEEDERS INTO THE EXISTING SYSTEMS.

3 SCHEDULE THE FEEDER CUTOVERS WITH THE VA COR. ATS 'BEHA1' AND PANEL

'BEHA1' SHALL BE PRIORITY. TEMPORARY POWER SHALL BE PROVIDED, AFTERHOUR

WORK IS REQUIRED DURING THE CUTOVER TO TEMPORARY POWER. SEE

SPECIFICATION 01 00 00 PART 1.6.J. FOR ADDITIONAL INFORMATION.

4 REMOVE THE OLD AUTOMATIC TRANSFER SWITCHES.

5 REMOVE THE VFDs AND REWIRE VFDs ASSOCIATED WITH AHUs.

6 INSTALL FEEDERS FROM PANEL 'BEH1' TO MECHANICAL EQUIPMENT.

GENERAL SHEET NOTES

KEYNOTES

TRENCH

GRADE

WARNING TAPE

COPPER GROUND CONDUCTOR

P

12" MINIMUM

6"

COMPACTED

BACKFILL

CONDUIT, REFER

TO DRAWINGS FOR

ADDITIONAL

INFORMATION

3"

(TYP)

36" MINIMUM

XQ350

RATING (KW)

MODEL

GENERATOR SCHEDULE

CATERPILLAR

MFG RATING (KVA)

437.5

VOLT.

277/480

POWER FACTOR

0.8 LAGGING

APPLICATION

STAND-ALONE

FUEL

DIESEL

PHASE

3 WYE

NOTE:

1. REFER TO SPECIFICATION SECTION 26 32 13 FOR ADDITIONAL INFORMATION.

2. PROVIDE A FACTORY ASSEMBLED, WIRED (EXCEPT FOR FIELD CONNECTIONS), COMPLETE, FULLY AUTOMATIC ENGINE GENERATOR SYSTEM, AS WELL AS

ALL ASSOCIATED EQUIPMENT AND DEVICES INTENDED FOR THE OPERATING, CONTROL, MONITORING, AND REMOTE MANUAL STOP FUNCTIONS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/1

/2

:2

:3

P

M

E-701

ELECTRICAL SCHEDULES AND

DETAILS

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 J. LOHL J. HALPIN

ISSUED FOR

CONSTRUCTION

LUMINAIRE SCHEDULE

TYPE DESCRIPTION MOUNTING VOLTS LAMPS DRIVER LOAD MANUFACTURER AND MODEL NO.

C1 COVE MOUNTED, LED STRIP, ASYMMETRIC

DISTRIBUTION, LENGTH AS INDICATED ON

PLANS, COMPLETE WITH CONNECTORS

(STRAIGHT AND 90). 3VA/FT LOAD

COVE MVOLT 3500k, 300lm/ft, 80CRI

0-10V

DIMMABLE

<varies> AXIS LIGHTING #CL SERIES FOR ARMSTRONG

AXION COVE

D1 6" APERTURE, LED SHOWER DOWNLIGHT,

FLAT CLEAR LENS, IP66 RATED

FLUSH MVOLT 1000LM

3500K

80CRI

LED (FIXED) 12 VA GOTHAM #EVO6SH SERIES OR APPROVED EQUAL

D2 6" APERTURE, ENCLOSED GLASS, WET

LOCATION, LED DOWNLIGHT, CLEAR

REFLECTOR

FLUSH MVOLT 1000LM

3500K

80CRI

0-10V

DIMMABLE

12 VA GOTHAM #EVO SERIES OR APPROVED EQUAL

F3 2X2 RECESSED, FLUSH MOUNT, A12.125,

FLAT ACRYLIC LENSED TROFFER, FLUSH

STEEL DOOR, 4 1/4" DEEP.

FLUSH

(FLANGED)

MVOLT 2500LM

3500K

80CRI

0-10V

DIMMABLE

26 VA COLUMBIA #LLT22 SERIES OR APPROVED EQUAL

G1 2X4 RECESSED DIRECT-INDIRECT TROFFER,

3 1/2" DEEP, SNAP-IN FROSTED ACRYLIC

DIFFUSER

FLUSH MVOLT 4500LM

3500K

80CRI

0-10V

DIMMABLE

43 VA FOCAL POINT #FARL SERIES OR APPROVED EQUAL

G3 2X2 RECESSED, FLUSH MOUNT, A12.125,

FLAT ACRYLIC LENSED TROFFER, FLUSH

STEEL DOOR, 4 1/4" DEEP.

FLUSH MVOLT 2500LM

3500K

80CRI

0-10V

DIMMABLE

26 VA COLUMBIA #LLT22 SERIES OR APPROVED EQUAL

L1 1X4, RECESSED STATIC TROFFER, FLAT

STEEL DOOR, A12.125 ACRYLIC LENS

FLUSH

(FLANGED)

MVOLT 3800LM

3500K

80CRI

0-10V

DIMMABLE

45 VA COLUMBIAL #LLT14 SERIES OR APPROVED EQUAL

L2 6"X4', LINEAR RECESSED, SYMMETRIC

DISTRIBUTION, FLAT LENS,LED

FLUSH MVOLT 1300LM

3500K

80CRI

0-10V

DIMMABLE

14 VA MARK LIGHTING #SL6L SERIES OR APPROVED

EQUAL

M1 9.5"X4, LINEAR, FLUSH, ASSYMETRIC

DISTRIBUTION TOWARDS PATIENT, TWO

FUNCTION, AMBIENT/EXAM

(FLANGED) MVOLT 6500LM

3500K

90CRI

0-10V

DIMMABLE

91 VA KENALL #MAEC SERIES OR APPROVED EQUAL

M2 9.5"X4, LINEAR, FLUSH, ASSYMETRIC

DISTRIBUTION TOWARDS PATIENT, TWO

FUNCTION, AMBIENT/EXAM

FLUSH MVOLT 6500LM

3500K

90CRI

0-10V

DIMMABLE

91 VA KENALL #MAEC SERIES OR APPROVED EQUAL

S1 24" x 24" x 5" LED FIXTURE, LUMINOUS LENS

WITH PATTERN PER ARCHITECT

REQUIREMENTS. PROVIDE WITH ONE #LSC

24PS, 277VAC-24VD POWER SUPPLY FOR

THE PROJECT. SEE LIGHTING PLANS FOR

WIRING REQUIREMENTS

FLUSH 24VDC LED 6500k 0-10V

DIMMABLE

25 VA SKYFACTORY #ES22-CLA SERIES

X1 CEILING MOUNTED EXIT SIGNS LED 7 VA COOPER

N.T.S.

B9

CONCRETE RADIAL DUCTBANK SECTION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

A u to d e s k D o c s /5

-1

-2

E x p a n d

E D

B e d s

/5

-1

-2

.O

P C

.M E

.r v t

/1

/2

:2

:4

P

M

E-702

ELECTRICAL SCHEDULES

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

09/11/2022 J. LOHL J. HALPIN

ISSUED FOR

CONSTRUCTION

Total Est. Demand: 68 A

Mechanical Equipment 57160 VA 80.00% 45728 VA Total Conn.: 82 A

NC 2520 VA 100.00% 2520 VA Total Est. Demand (kVA): 56 kVA

REC 900 VA 100.00% 900 VA Total Conn. (kVA): 68 kVA

Receptacle 7200 VA 100.00% 7200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 82 A

Total Conn. Load: 67780 VA

3 AHU-3 VFD-2 3 400 A 50 A 18643 VA

2 AHU-3 VFD-1 3 400 A 100 A 27098 VA

1 BEM1 3 400 A 100 A 22040 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Enclosure: Type 1

Mounting: Surface Mains Rating: 600 A

Supply From: Wiring: 3P,4 OCP Device Type: MLO

Location: ELECTRIC CLOSET B1C16 Volts: 480/277 Wye A.I.C. Rating:

Switchboard: BEEH

PER NEC 700.1 ONLY LIFE SAFTY LOADS CAN BE USED ON THIS PANEL

Notes:

Total Est. Demand Current: 29 A

Total Conn. Current: 29 A

REC 900 VA 100.00% 900 VA Total Est. Demand: 10620 VA

NC 2520 VA 100.00% 2520 VA Total Conn. Load: 10620 VA

Receptacle 7200 VA 100.00% 7200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 33 A 38 A 21 A

Total Load: 3780 VA 4320 VA 2520 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 OBSERVATION RM B1C34A 20 A 1 360 VA 0 VA 1 20 A Spare 18

15 OBSERVATION RM B1C34C 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34A... 16

13 OBSERVATION RM B1C34E 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34C... 14

11 OBSERVATION RM B1C34G 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34E... 12

9 OBSERVATION RM B1C34K 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34G... 10

7 OBSERVATION RM BC24 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34K... 8

5 OBSERVATION RM B1C23 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C24 DEDICATED 6

3 OBSERVATION RM B1C21 20 A 1 1440... 720 VA 1 20 A OBSERVATION RM B1C23 DEDICATED 4

1 REC Room B1C53, B1C52 20 A 1 900 VA 720 VA 1 20 A OBSERVATION RM B1C21 DEDICATED 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Indoor Spaces: 42 MCB Rating: 125 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: T-BELP Phases: 3 Mains Type: MCB

Location: Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study

Branch Panel: BELP

Notes: (1) EXISTING PANEL, LOAD SHOWN ARE RE-USED DEMO LOADS. ALL LOADS ARE LESS THEN THE ORIGINAL LOADS

Total Est. Demand Current: 8 A

Total Conn. Current: 8 A

REC 1800 VA 100.00% 1800 VA Total Est. Demand: 2954 VA

NC 1080 VA 100.00% 1080 VA Total Conn. Load: 2954 VA

Other 74 VA 100.00% 74 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 16 A 1 A 10 A

Total Load: 1800 VA 74 VA 1080 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 1080... 1 20 A 1 REC B1C34J, B1C34F, B1C34B,... 24

21 22

19 20

17 18

15 74 VA 1 20 A 1 SKYLIGHTS NEW OBSERVATION 16

13 720 VA 1 20 A 1 REC Room BC50, B1C23, B1C21, B1C-9 14

11 12

9 10

7 NEW OBSERVATION RM BB1C23 AND... 1 20 A 1 720 VA 360 VA 1 20 A 1 NEW OBSERVATION RM BC24 8

5 6

3 4

1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Indoor Spaces: 42 MCB Rating: 125 A

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELECTRIC CLOSET B1C16 Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study

Branch Panel: BA(E)

Notes: (1) EXISTING PANEL, LOAD SHOWN ARE RE-USED DEMO LOADS. ALL LOADS ARE LESS THEN THE ORIGINAL LOADS

Total Est. Demand Current: 6 A

Total Conn. Current: 6 A

LTG 359 VA 125.00% 448 VA Total Est. Demand: 2126 VA

REC 1620 VA 100.00% 1620 VA Total Conn. Load: 2025 VA

Lighting 47 VA 125.00% 59 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 17 A 0 A

Total Load: 0 VA 2025 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 REC Room B1C34H, B1C34F 1 20 A 1 900 VA 28

25 26

23 24

21 REC Room B1C34D, B1C34B 1 20 A 1 720 VA 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 406 VA 1 20 A 1 LS LIGHTING NEW OBSERVATION 4

1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Indoor Spaces: 42 MCB Rating: 125 A

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELECTRIC CLOSET B1C16 Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study

Branch Panel: BE1(E)

PER NEC 701.1 ONLY LEGALLY REQUIRED STANDBY LOADS CAN BE USED ON THIS PANEL

Notes:

Total Est. Demand Current: 24 A

Mechanical Equipment 11420 VA 80.00% 9136 VA Total Conn. Current: 27 A

REC 900 VA 100.00% 900 VA Total Est. Demand: 19756 VA

NC 2520 VA 100.00% 2520 VA Total Conn. Load: 22040 VA

Receptacle 7200 VA 100.00% 7200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 38 A 20 A 22 A

Total Load: 10327 VA 5587 VA 6127 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Spare 20 A 1 0 VA -- 1 -- Space 26

23 Spare 20 A 1 0 VA -- 1 -- Space 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 -- -- -- 903 VA 0 VA 1 20 A Spare 20

17 -- -- -- 903 VA 0 VA 1 20 A Spare 18

15 EF-1-11 20 A 3 903 VA 0 VA 1 20 A Spare 16

13 -- -- -- 903 VA 0 VA 1 20 A Spare 14

11 -- -- -- 903 VA 0 VA -- -- -- 12

9 EF-1-10 20 A 3 903 VA 0 VA -- -- -- 10

7 -- -- -- 2520... 0 VA 3 30 A 1-EF-ED 8

5 -- -- -- 4320... 0 VA -- -- -- 6

3 T-BELP 20 A 3 3780... 0 VA -- -- -- 4

1 DDC-AHU-3 20 A 1 6000... 0 VA 3 30 A EF-1 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Indoor Spaces: 42 MCB Rating: 125 A

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: BEEH Phases: 3 Mains Type: MLO

Location: ELECTRIC CLOSET B1C16 Volts: 480/277 Wye A.I.C. Rating: Per Arc Flash Study

Branch Panel: BEM1

Notes: (1) EXISTING PANEL, LOAD SHOWN ARE RE-USED DEMO LOADS. ALL LOADS ARE LESS THEN THE ORIGINAL LOADS

LTG 1917 VA 125.00% 2396 VA Total Est. Demand Current: 18 A

REC 2160 VA 100.00% 2160 VA Total Conn. Current: 17 A

NC 1800 VA 100.00% 1800 VA Total Est. Demand: 6600 VA

Other 74 VA 100.00% 74 VA Total Conn. Load: 6086 VA

Lighting 136 VA 125.00% 171 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 17 A 17 A 17 A

Total Load: 2070 VA 2011 VA 2006 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 720 VA 1 20 A 1 OBSERVATION RM B1C34E 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 566 VA 1 20 A 1 LTG NEW OBSERVATION ROOM 12

9 REC Room B1C-6, B1C-9 1 20 A 1 900 VA 751 VA 1 20 A 1 LTG NEW OBSERVATION ROOM 10

7 REC Room B1C53, B1C52, BC51 1 20 A 1 540 VA 720 VA 1 20 A 1 REC Room BC24, B1C23, B1C21 8

5 720 VA 1 20 A 1 OBSERVATION RM B1C34E 6

3 360 VA 1 20 A 1 OBSERVATION RM B1C34K 4

1 810 VA 1 20 A 1 LTG NEW OBSERVATION ROOM BC24 2

CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT

Notes:

Enclosure: Indoor Spaces: 42 MCB Rating: 125 A

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELECTRIC CLOSET B1C16 Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study

Branch Panel: BB(E)

THIS PANEL IS FOR LIFE SAFE LOADS ONLY

THIS PANEL IS FOR EMERGENCY LOADS ONLY