570-17-210.OPC.DWG.20221021Part-3.pdf
PDF 10 MB Posted
- Solicitation number
- 36C26123R0008
About this file
This federal contract opportunity solicitation seeks proposals to remodel the emergency department observation bed area at the Fresno VA Medical Center. The solicitation number is 36C26123R0008 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21. Offerors are requested to provide all labor, materials, equipment, and supervision to complete the emergency department remodel project. The work includes demolition, construction, and related tasks. The period of performance is 365 calendar days from award. Proposals are due by the date specified in the solicitation and the contract award date will be determined subsequently. Pricing shall be fixed for the period of performance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Technical Question Tracking Sheet -RFI 1-38 -ED Beds 02212023.pdf | ||
| 36C26123R0008 0007.docx | DOCX document | |
| 36C26123R0008 0006.docx | DOCX document | |
| WD_CA20230018_02102023.pdf | ||
| 36C26123R0008 0005.docx | DOCX document | |
| Technical Question Tracking Sheet -RFI 1-36 -ED Beds-MRP-020823.pdf | ||
| 36C26123R0008 0004.docx | DOCX document | |
| 36C26123R0008 0003.docx | DOCX document | |
| Site Visit_01262023 Sign in Sheet.pdf | ||
| 36C26123R0008 0002.docx | DOCX document | |
| 36C26123R0008 0001.docx | DOCX document | |
| 570-17-210.OPC.DWG.20230112Part-1.pdf | ||
| Attachment A_Factor 1_Experience_01052023.xlsx | XLSX spreadsheet | |
| 570-17-210.OPC.Specs.20221024.pdf | ||
| ACM Report.pdf | ||
| WD_CA29_11042022.pdf | ||
| 570-17-210.OPC.DWG.20221021Part-2.pdf | ||
| Attachment C_Large Business Subcontracting Plan Template_01032023.docx | DOCX document | |
| Attachment B_Supplemental Price Breakdown_11222022.xlsx | XLSX spreadsheet | |
| 36C26123R0008.docx | DOCX document | |
| Attachment D_Request for Information (RFI) Form_36C26123R0008.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
V
V
V
F F
1N
F 2 2
TV F
2 21
N
N 2 2 1
N 2 2 1
N 2 2 1
N 2 2 1
N
2 2 2
2 2
TV
F
2 2
F
S S
BA(E)
BB(E)
BE1(E)
BE2(E)
M C
C E
(E
M C
C (E
1-BPH
RF-6
(MCCE)
FACP
M C
C N
B (E
BE3
BESB
BEMD(E)
MSB
RF-5RF-5
RF-6RF-6
SF-3SF-3
SF-4SF-4
BECD(E)
AREAWAY
1 1
1 2
F4/ED100C
IT RACK
NC RACK
F4/ED100B
VAV-1-7
AREAWAY
OBSERVATION/
TREATMENT RM
B1C11
OBSERVATION/
TREATMENT RM
B1C10
OBSERVATION/
TREATMENT RM
B1C13
LOCKER RM
B1C20A
TRANSFORMER RM
B1C17A
STAFF LOUNGE
B1C20
STAIR
B1C21
OBSERVATION/
TREATMENT RM
B1C12
ELECTRIC CLOSET
B1C16
TELEPHONE CLOSET
B1C15
CORRIDOR
B1C-4
ON-CALL RM
B1C18TOILET
B1C19
OBSERVATION/
TREATMENT RM
B1C09
MECHANICAL ROOM
B1C39
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
D
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:0
P
M
ED100D
ELECTRICAL DEMO PLAN - LEVEL B
- AREA D
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
1 ALL EQUIPMENT AND DEVICES INDICATED HALFTONE ARE EXISTING TO REMAIN,
UNO.
2 ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY
BACK TO NEAREST POINT OF SERVICE, UNO.
3 MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
4 MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
5 CONTRACTOR SHALL FIELD VERIFY BRANCH CIRCUIT INFORMATION NOTATED FOR
RE-USE PRIOR TO ROUGH-IN.
1/4" = 1'-0" F4
ELECTRICAL DEMO PLAN - LEVEL B - AREA D
1 DEMOLISH ELECTRICAL SERVICE INCLUDING CONDUIT, SWITCHES, FEEDERS AND BRANCH CIRCUIT
BREAKER FEEDING THE EQUIPMENT BACK TO THE POINT OF SERVICE.
2 REMOVE MECHANICAL CONTROL PANEL IN IT'S ENTIRETY.
3 REMOVE VFDS SF-3 AND RF-5 IN THEIR ENTIRETY BACK TO THEIR RESPECTIVE DISCONNECT
SWITCHES LOCATED AT THE AH-3.
4 DISCONNECT VFD RF-6 FROM MCCE AND REWIRE TO MCC1. REFER TO SHEET EP101 FOR ADDITIONAL
INFORMATION.
5 DISCONNECT VFD SF-4 AND RELOCATE TO SECTION OF WIREWAY TO REMAIN. REFER TO SHEET
EP101 FOR ADDITIONAL INFORMATION.
6 REMOVE SECTION OF WIREWAY PRESENTLY SERVING VFDS SF-3 AND SF-4.
7 REMOVE TRANSFER SWITCHES FROM ELECTRICAL ROOM. INSTALL NEW TRANSFER SWITCHES IN
THE ADJACENT MECHANICAL ROOM PRIOR TO DEMOLITION. REFER TO SHEET EP100D FOR
ADDITIONAL INFORMATION.
09/11/2022
Revisions: Date:
HVAC DDC (E)
C DDC
HVAC DDC (E)8
VAC DDC
8 EXISTING HVAC DDC CONTROL PANELS SHALL BE REMOVED AND REPLACED WITH DIVISION 23
SCOPE OF WORK. PROVIDE POWER SUPPLIES ON CRITICAL BRANCH FOR NEW EQUIPMENT.
COORDINATE WITH DIVISION 23 CONTROLS SUBCONTRACTOR. COORDINATE NEW LOCATIONS WITH
NEW ELECTRICAL SCOPE. SUBMIT COORDINATION DRAWINGS SHOWING NEW ELECTRICAL ROOM
BUILD-OUT.
9 EXISTING ELECTRICAL PANEL AND MATV CONTROL PANEL SHALL BE REMOVED AND RELOCATED
TO COORDINATE WITH NEW ELECTRICAL SCOPE. COORDINATE NEW LOCATIONS WITH NEW
ELECTRICAL SCOPE. SUBMIT COORDINATION DRAWINGS SHOWING NEW ELECTRICAL ROOM
BUILD-OUT.
ELECTRICAL CLOSET B1C16 - EXISTING CONDITIONS
ELECTRICAL CLOSET B1C16 - EXISTING
MATV CP TO BE RELOCATED
ELECTRICAL CLOSET B1C16 - EXISTING
HVAC DDC PANEL TO BE REPLACED
EXISTING HVAC VFD TO BE REPLACED,
PNEUMATIC CP TO BE REMOVED
MATV CP (E)
V
V
V
F
MCC-2
MCC2-E
PNLAMECHANICAL
PENTHOUSE
RADIO
ROOM
EF1EF1
SF2SF2
RF2RF2
RF1RF1
SF1SF1
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
A B
D C
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/1
/2
:2
:3
P
M
ED102
ELECTRICAL DEMO PLAN - ROOF
LEVEL
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
1 ALL EQUIPMENT AND DEVICES INDICATED HALFTONE ARE EXISTING TO REMAIN,
UNO.
2 ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR ENTIRETY
BACK TO NEAREST POINT OF SERVICE, UNO.
3 MAINTAIN CIRCUIT CONTINUITY TO DEVICES THAT REMAIN.
4 MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
5 CONTRACTOR SHALL FIELD VERIFY BRANCH CIRCUIT INFORMATION NOTATED FOR
RE-USE PRIOR TO ROUGH-IN.
1 REMOVE POWER ASSOCIATED WITH EXHAUST FAN IN IT'S ENTIRETY BACK TO DISCONNECT SWITCH.
2 REMOVE DISCONNECT SWITCH IN IT'S ENTIRETY BACK SOURCE.
1/8" = 1'-0" F4
ELECTRICAL DEMO PLAN - ROOF LEVEL
Revisions: Date:
09/11/2022
O O O
L L L
D
D
O
L
L
L
L
O
LINEN CLOSET
B1C39
EMS CLOSET
B1C36
FEMALE RR
B1C32
PATIENT COMFORT
ROOM
BC127
LINEN CLOSET
B1C42
LINEN CLOSET
B1C41
INTERVENTION
(SECLUSION) ROOM
B1C28
CRASH CART
ALCOVE
WAITING
B1C-1
CORRIDOR
B1C-6
MALE RR
B1C33
SOILED UTILITY
B1C53
CLEAN UTILITY
B1C52
STF TLT
BC51
NEW OBSERVATION
ROOM
B1C23
NEW OBSERVATION
ROOM
BC24
HAC
BC50
CORRIDOR
B1C-2
OBSERVATION/
TREATMENT RM
B1C14
CORRIDOR
B1C-1
NEW OBSERVATION
ROOM
B1C34K
PAT TLT
B1C34J
HALL
B1C-6A
NEW OBSERVATION
ROOM
B1C34E
CLEAN UTILITY
BC26
PAT TLT
B1C25A
CHIEF OF ER
B1C35
HEAD NURSE
B1C37
ELEVATOR
S-6
ELEVATOR
S-5
ELEVATOR EQUIP RM
B1C40
STAIR NO.4
B1C43
CORRIDOR
B1C-9
G1, G1 G1, L1
L1
F3
M1, M1, M1, M1, L1, M1, j
M1, j
L2, L2, M2, d
D1
D2, L2,L2, c
M1, c M1, c b a j
D2, D2, D2, D2, D2, D2, D2, M2, d
M2, e
M2, e
M2, f
M2, f
M2, g
M2, g d e f g
D2, G3, D2, D2, G1
G1, 12
D2, 12
NEW OBSERVATION
ROOM
B1C34G
NEW OBSERVATION
ROOM
B1C34C
NEW OBSERVATION
ROOM
B1C34A
HALL
B1C-6A
NEW NURSES
STATION
B1C34F
NEW NURSES
STATION
B1C34B
NEW OBSERVATION
ROOM
B1C21
CORRIDOR
B1C-4
3 32
G3, D2, D2, C1, S1, C1, D2, C1, D2, C1, D2, C1, C1, (TYP)
(TYP)
BE1(E)- 4
BE1(E)- 4
BB(E)- 10
BB(E)- 10
BB(E)- 10
BE1(E)- 4
BE1(E)- 4
BB(E)- 12
BB(E)- 12 BB(E)- 12
BB(E)- 2BB(E)- 2BB(E)- 2BB(E)- 2BB(E)- 2BB(E)- 2
BB(E)- 2
BB(E)- 2
BB(E)- 2
BE1(E)- 4
BE1(E)- 4BE1(E)- 4
G1, G1, G1, BE1(E)- 4 BE1(E)- 4 BE1(E)- 4
BE1(E)- 4
BE1(E)- 4
4 4
X1
X1
X1
X1
S1, BB(E)- 10
BB(E)- 10
BB(E)- 10
BB(E)- 10
BB(E)- 10
BB(E)- 10
BB(E)- 10
BB(E)- 10
BE1(E)- 4
BE1(E)- 4
BE1(E)- 4
BE1(E)- 4
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 2
BB(E)- 2
BB(E)- 2
X1, 4
BB(E)- 12
BB(E)- 12
BB(E)- 12
BB(E)- 10
BB(E)- 10
BB(E)- 10
BA(E)- 16
BB(E)- 10
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
B
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:0
P
M
EL100B
ELECTRICAL LIGHTING PLAN -
LEVEL B - AREA B
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
1 PROVIDE A THREE BUTTON, DIGITAL WALL SWITCH FOR CONTROL OF EXAM LIGHTING.
LABEL BUTTONS "OFF", "EXAM" AND "AMBIENT". TYPICAL FOR EACH NEW EXAM SPACE.
2 CONNECT NEW LUMINAIRE TO EXISTING LIGHTING CIRCUITS SHOWN ON THIS SHEET.
3 CONNECT NEW LUMINAIRE TO EXISTING UNSWITCHED LIFE SAFETY BRANCH CIRCUIT
SHOWN ON THIS SHEET.
A ALL LIGHTING IS CONTROLLED BY THE OCCUPANCY SENSOR(S) LOCATED IN THE
ROOM, UNO.
B ALL LUMINAIRES NOTATED AS 'NL' ARE UNSWITCHED NIGHT LIGHTS, WIRED TO AN
UNSWITCHED, 120VAC, LIFE SAFETY BRANCH CIRCUIT.
C ALL SINGLE FACE EXIT SIGNS ARE TYPE 'X1' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHED, 120VAC, LIFE SAFETY BRANCH CIRCUIT.
D ALL DOUBLE FACED EXIT SIGNS ARE TYPE 'X2' AND SHALL BE WIRED TO THE NEAREST
UNSWITCHES, 120VAC, LIFE SAFETY BRANCH CIRCUIT.
1/4" = 1'-0" F4
LIGHTING PLAN - LEVEL B - AREA B
J
M
J
M
J
M
J
MJ
M
J
M
J
M
J
M
J
MJ
M
J
M
J
J
ELEVATOR
B-19
SOCIAL WORK
OFFICE
B1C01
CLINICAL CHARTING
RM
B1C29
WHEELCH. SCALE
EXAM AREA
B1C04
EXAM AREA
B1C03
INTERVENTION
(SECLUSION) ROOM
B1C28
AOD/ CHECK-IN
B1C30
PROCEDURE RM
B1C05
ENTRANCE
POLICE DISPATCH
B1C02
VESTIBULE
WAITING
B1C-1
TRIAGE RM
B1C31
CHARTING ALCOVE
LINEN CART ALCOVE
CORRIDOR
B1C-1A
ALCOVE,
WHEELCHAIR/
STRETCHER/ LIFT
B1D
VESTIBULE
TOILET
B1C08
X-RAY ALCOVE
TRAUMA RM SMALL
B1C06
TRAUMA RM LARGE
B1C07
CORRIDOR
B1C-5
CORRIDOR
B1C-7
CORRIDOR
B1C-7
NURSE STATION
B1C29A
CORRIDOR
B1C-7
CORRIDOR
B1C-8
TOILET
B1C08
TOILET
B1C08
F /E
P B
F4/EP100D
2 1
2 1
CAV-1-2
DDC-AHU-3- 1
DDC-AHU-3- 2
ZONE 1
ZONE 2
ZONE-1
DDC-AHU-3-1
ZONE-1
DDC-AHU-3-1
ZONE-1
DDC-AHU-3-1
ZONE-1
DDC-AHU-3-1
ZONE-1
DDC-AHU-3-1
ZONE-2
DDC-AHU-3-2
ZONE-2
DDC-AHU-3-2
ZONE-2
DDC-AHU-3-2
ZONE-2
DDC-AHU-3-2 ZONE-2
DDC-AHU-3-2
ZONE-3
DDC-AHU-3-3
CAV-1-7
CAV-1-2
C A
V -1
-8
CAV-1-5
CAV-1-4
VAV-1-1
C A
V -1
-1
VAV-1-2
VAV-1-6
CAV-1-6
C A
V -1
-3
VAV-1-6VAV-1-6
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
A
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:1
P
M
EP100A
ELECTRICAL POWER PLAN - LEVEL
B - AREA A
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.
C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.
D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN.
E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT
REQUIREMENTS.
F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION
26 41 00 REQUIREMENTS.
G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH
SPECIFICATION SECTION 27 15 00.
1/4" = 1'-0" F1
POWER PLAN - LEVEL B - AREA A
1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED
AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.
2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE
MECHCANICAL ROOM.
NN
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
M
J
J
J
N N
N N
N
INTERVENTION
(SECLUSION) ROOM
B1C28
LINEN CLOSET
B1C39
EMS CLOSET
B1C36
FEMALE RR
B1C32
PATIENT COMFORT
ROOM
BC127
LINEN CLOSET
B1C41
CRASH CART
ALCOVE
CORRIDOR
B1C-6
MALE RR
B1C33
NEW OBSERVATION
ROOM
B1C23
NEW OBSERVATION
ROOM
BC24
HAC
BC50
CORRIDOR
B1C-1
NEW OBSERVATION
ROOM
B1C34K
PAT TLT
B1C34J
HALL
B1C-6A
NEW OBSERVATION
ROOM
B1C34E
CLEAN UTILITY
BC26
PAT TLT
B1C25A
CHIEF OF ER
B1C35
HEAD NURSE
B1C37
ELEVATOR
S-6
ELEVATOR
S-5
STAIR NO.4
B1C43
LINEN CLOSET
B1C42
HAC
B1C49
SOILED UTILITY
B1C53
CLEAN UTILITY
B1C52
STF TLT
BC51
CORRIDOR
B1C-2
ELEVATOR EQUIP RM
B1C40
CORRIDOR
B1C-9
OBSERVATION/
TREATMENT RM
B1C14
F1/EP100A
F4/EP100C
F4/EP100D
DDC-AHU-3
DDC-AHU-3- 3
DDC-AHU-3- 4
ZONE 4
ZONE 3
DDC-AHU-3- 5
BELP- 1BELP- 1
BELP- 1BELP- 1BELP- 1
B E
LP
B E
LP
B
E
LP
B A
(E
B A
(E
B A
(E
B A
(E
NEW OBSERVATION
ROOM
B1C21
B E
LP
B E
LP
B E
LP
B E
LP
B A
(E
B A
(E
BA(E)- 14 BA(E)- 14
BA(E)- 14
BA(E)- 14
BB(E)- 8
BB(E)- 8
BB(E)- 8
BB(E)- 8
BB(E)- 7
BB(E)- 7
BB(E)- 9
BB(E)- 9 BB(E)- 9
BB(E)- 9
BE1(E)- 21
BE1(E)- 21
BE1(E)- 21
BE1(E)- 27
BE1(E)- 27
BE1(E)- 27
BE1(E)- 27
BE1(E)- 27
BA(E)- 24
BA(E)- 24
BA(E)- 24
BA(E)- 24
BA(E)- 24
BELP- 9
BELP- 9
BB(E)- 4
BB(E)- 4
BB(E)- 6
BB(E)- 6
BB(E)- 6
BB(E)- 6
BB(E)- 30
BB(E)- 30
BB(E)- 30
BB(E)- 30
BELP- 11
BELP- 11
BELP- 10
NEW OBSERVATION
ROOM
B1C34C
NEW OBSERVATION
ROOM
B1C34A
NEW OBSERVATION
ROOM
B1C34G
BELP- 12
BELP- 13
BELP- 13
BELP- 15
BELP- 15
BELP- 14
BELP- 17
BELP- 16
BELP- 17
ZONE 5
ZONE-3
DDC-AHU-3-3
ZONE-3
DDC-AHU-3-3
ZONE-3
DDC-AHU-3-3
ZONE-3
DDC-AHU-3-3
ZONE-3
DDC-AHU-3-3
ZONE-5
DDC-AHU-3-5
ZONE-4
DDC-AHU-3-4
ZONE-4
DDC-AHU-3-4
ZONE-4
DDC-AHU-3-4
ZONE-4
DDC-AHU-3-4
BELP- 8
ZONE-5
DDC-AHU-3-5
ZONE-5
DDC-AHU-3-5
ZONE-5
DDC-AHU-3-5
ZONE-5
DDC-AHU-3-5
BE1(E)- 21
B E
LP
B E
LP
BB(E)- 7
BB(E)- 9
BA(E)- 24
TS FS
F /E
P D
NEW NURSES
STATION
B1C34B
NEW STORAGE
B1C34D
NEW NURSES
STATION
B1C34F
NEW STORAGE
B1C34H
CORRIDOR
B1C-4
WAITING
B1C-1
VAV-1-2
VAV-1-6
VAV-1-12
VAV-1-15
VAV-1-18
VAV-1-17
V A
V -1
-1
VAV-1-8
VAV-1-13
VAV-1-9
VAV-1-11
VAV-1-14
VAV-1-7
VAV-1-6VAV-1-6
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
B
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:1
P
M
EP100B
ELECTRICAL POWER PLAN - LEVEL
B - AREA B
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.
C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.
D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN.
E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT
REQUIREMENTS.
F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION
26 41 00 REQUIREMENTS.
G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH
SPECIFICATION SECTION 27 15 00.
1/4" = 1'-0" F4
POWER PLAN - LEVEL B - AREA B
1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED
AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.
2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE
MECHCANICAL ROOM.
3 PROVIDE CONNECTION TO NURSE CALL DEVICE, INTEGRAL TO THE PREFABRICATED BEDSIDE
PATIENT UNIT (PBPU). TYPICAL FOR ALL NEW EXAM SPACES.
4 PROVIDE TWO, J-BOXES SURFACE MOUNTED, ABOVE CEILING FOR ELECTRICAL SERVICE TO THE PREFABRICATED BEDSIDE PATIENT UNIT (PBPU). ONE J-BOX SHALL CONTAIN TWO CRITICAL BRANCH CIRCUITS; ONE DEDICATED (NO SHARED NETURAL OR GROUND) AND ONE SHARED WITH THE ADJAC
5 NEW TAMPER AND FLOW VALVES POWER FROM THE F.A.C.P. PANEL. COORDINATE WITH
MECHCANICAL CONTRATOR FOR EXACT LOCATION AND POWER REQUIREMENTS
V
J
M
J
J
M
LINEN CLOSET
B1C41
NEW OBSERVATION
ROOM
B1C23
NEW OBSERVATION
ROOM
BC24
HAC
BC50
STAIR NO.4
B1C43
CT SCANNER
B1C46
LINEN CLOSET
B1C42
HAC
B1C49
PAT HOLDING
B1C47
SOILED UTILITY
B1C53
CLEAN UTILITY
B1C52
STF TLT
BC51
EQUIP STOR
B1C44
MECHANICAL ROOM
B1C17
OBSERVATION/
TREATMENT RM
B1C14
MCCNB(E)
IT RACK
DDC-AHU-3
DDC-AHU-3- 5
BELP- 1BELP- 1
BELP- 1BELP- 1BELP- 1
B E
LP
B E
LP
B
E
LP
B A
(E
B A
(E
B A
(E
B A
(E
NEW OBSERVATION
ROOM
B1C21
B E
LP
B E
LP
B E
LP
B E
LP
B A
(E
B A
(E
BA(E)- 14 BA(E)- 14
BA(E)- 14
BA(E)- 14
BB(E)- 8
BB(E)- 8
BB(E)- 8
BB(E)- 8
VFD-1
BEEH- 2
VFD-2
BEEH- 3
BB(E)- 7
BB(E)- 7
ZONE-3
DDC-AHU-3-3
ZONE-5
DDC-AHU-3-5
B E
LP
B E
LP
BB(E)- 7
ZONE-5
DDC-AHU-3-5
TS FS
F4/EP100B
F /E
P D
CORRIDOR
B1C-4
CONTROL ROOM
B1C45
VAV-1-6
VAV-1-15
1-AHU-3
VAV-1-7
1-AHU-3
V A
V -1
-1
1-AHU-4
VAV-1-6VAV-1-6
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
C
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:2
P
M
EP100C
ELECTRICAL POWER PLAN - LEVEL
B - AREA C
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.
C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.
D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN.
E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT
REQUIREMENTS.
F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION
26 41 00 REQUIREMENTS.
G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH
SPECIFICATION SECTION 27 15 00.
1/4" = 1'-0" F4
POWER PLAN - LEVEL B - AREA C
1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED
AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.
2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE
MECHCANICAL ROOM.
3 REFER TO ONE-LINE DIAGRAM, SEE SHEET E-601 FOR EQUIPMENT ELECTRICAL SERVICE
REQUIREMENTS.
F F
V
J
M
M M
J
M
MM
J
OBSERVATION/
TREATMENT RM
B1C11
OBSERVATION/
TREATMENT RM
B1C10
OBSERVATION/
TREATMENT RM
B1C13
STAIR
B1C21
OBSERVATION/
TREATMENT RM
B1C12
STAIR
B1C21
OBSERVATION/
TREATMENT RM
B1C09
AREAWAY
AREAWAY
TELEPHONE CLOSET
B1C15
CORRIDOR
B1C-4
LOCKER RM
B1C20A
TRANSFORMER RM
B1C17A
STAFF LOUNGE
B1C20
ELECTRIC CLOSET
B1C16
ON-CALL RM
B1C18
TOILET
B1C19
BEMD(E)
BECD(E)
BQHA
BA(E)
BB(E)
BE1(E)
BE2(E)
SF-4SF-4
RF-6RF-6
F4/EP100C
MCCE(E)MCC1(E) MCCNB(E)
BQHAT1
BCHAT
BSHAT
BQHAT2
NC RACK
BEM1
BEEH
BELP T-BELP
BEM1- 9,11,13BEM1- 15,17,19
ZONE 6 DDC-AHU-3- 6
ZONE-6
DDC-AHU-3-6
ZONE-6
DDC-AHU-3-6
ZONE-6
DDC-AHU-3-6
F4/EP100B
MECHANICAL ROOM
B1C17
VAV-1-7
1-AHU-4RF-6
V A
V -1
-5
VAV-1-3 VAV-1-4
EF-1-10EF-1-11
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
D
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:2
P
M
EP100D
ELECTRICAL POWER PLAN - LEVEL
B - AREA D
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.
C PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.
D COORDINATE FINAL EQUIPMENT CONNECTION REQUIREMENTS WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN.
E REFER TO SPECIFICATION 13 05 41 FOR EQUIPMENT SEISMIC RESTRAINT
REQUIREMENTS.
F PROVIDE LIGHTNING PROTECTION FOR ROOF TOP EQUIPMENT PER SPECIFICATION
26 41 00 REQUIREMENTS.
G ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH
SPECIFICATION SECTION 27 15 00.
1/4" = 1'-0" F4
POWER PLAN - LEVEL B - AREA D
1 PROVIDE A MOTOR RATED SWITCH AT EACH TERMINAL UNIT FOR DDC CONTROL POWER. PROVIDE A 277V SINGLE PHASE BRANCH CIRCUIT TO THE DDC CONTROL PANEL LOCATED AT THE ASSOCIATED
AHU. TYPICAL FOR ALL TERMINAL UNITS ON THIS LEVEL.
2 UNIT CONTROLS SHALL BE 24VDC SUPPLIED FROM THE 'DDC' CONTROL PANEL LOCATED IN THE
MECHANICAL ROOM.
F
F
FUTURE
BEM1- 2,4,6
BEM1- 8,10,12
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
A B
D C
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/1
/2
:2
:1
P
M
EP102
ELECTRICAL POWER PLAN - ROOF
LEVEL
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
1/8" = 1'-0" F4
ELECTRICAL POWER PLAN - ROOF LEVEL
1 PROVIDE 480VAC FOR EQUIPMENT. REFER TO ONE-LINE DIAGRAM, SEE SHEET E-601 FOR
ADDITIONAL INFORMATION.
A MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
B CONTRACTOR SHALL COORDINATE FINAL POCs WITH VA COR PRIOR TO ROUGH-IN.
C PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS
D EQUIPMENT CONNECTIONS SHALL BE SIZED PER THE HOMERUN.
E COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH EQUIPMENT
SUPPLIER, PRIOR TO ROUGH-IN.
F ALL EQUIPMENT AND DEVICES ARE EXISTING, UNO.
S
TV
2 2
S
S
F
F
T V
S
F F
N 2 2
CR
F
D
N
D
N W W
C
N
C
N
C
N
C
N
C
N
C
N
E
N
E
N
N
N
N
N
N
N
N
C
N
C
N
C
N
C
N
C
N
C
N
C
N
C
N
C N
C N
P B
P B
A N
N
F
F
F
NNN
LINEN CLOSET
B1C42
LINEN CLOSET
B1C41
SOILED UTILITY
B1C53
CLEAN UTILITY
B1C52
STF TLT
BC51
NEW OBSERVATION
ROOM
B1C23
NEW OBSERVATION
ROOM
BC24
HAC
BC50
CORRIDOR
B1C-2
OBSERVATION/
TREATMENT RM
B1C14
ELEVATOR EQUIP RM
B1C40
STAIR NO.4
B1C43
CORRIDOR
B1C-9
CORRIDOR
B1C-2
ELEVATOR EQUIP RM
B1C40
CORRIDOR
B1C-9
LINEN CLOSET
B1C39
EMS CLOSET
B1C36
FEMALE RR
B1C32
PATIENT COMFORT
ROOM
BC127
CRASH CART
ALCOVE
CORRIDOR
B1C-6
MALE RR
B1C33
OBSERVATION/
TREATMENT RM
B1C14
CORRIDOR
B1C-1
NEW OBSERVATION
ROOM
B1C34K
PAT TLT
B1C34J
HALL
B1C-6A
NEW OBSERVATION
ROOM
B1C34E
CLEAN UTILITY
BC26
PAT TLT
B1C25A
CHIEF OF ER
B1C35
HEAD NURSE
B1C37
ELEVATOR
S-6
ELEVATOR
S-5
STAIR NO.4
B1C43
OBSERVATION/
TREATMENT RM
B1C14
STAIR NO.4
B1C43
WAITING
B1C-1
NEW OBSERVATION
ROOM
B1C21
CORRIDOR
B1C-4
NEW OBSERVATION
ROOM
B1C34A
NEW OBSERVATION
ROOM
B1C34C
NEW OBSERVATION
ROOM
B1C34G
NEW NURSES
STATION
B1C34B
NEW STORAGE
B1C34D
NEW NURSES
STATION
B1C34F
NEW STORAGE
B1C34H
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
B
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/2
/2
:3
:3
P
M
ET100B
ELECTRICAL SYSTEMS PLAN -
LEVEL B - AREA B
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
GENERAL SHEET NOTES
KEYNOTES
1/4" = 1'-0" F4
ELECTRICAL SYSTEMS PLAN - LEVEL B - AREA B
1 PROVIDE CONNECTION TO NURSE CALL DEVICE, INTEGRAL TO THE PREFABRICATED
BEDSIDE PATIENT UNIT (PBPU). TYPICAL FOR ALL NEW EXAM SPACES.
A ALL EQUIPMENT AND DEVICES INDICATED HALFTONE ARE EXISTING TO REMAIN, UNO.
B REFER TO SHEET EP100D FOR THE TELECOM ROOM LOCATION AND EQUIPMENT.
C ALL COMMUNICATIONS CABLING SHALL BE CAT 6A INACCORDANCE WITH
SPECIFICATION SECTION 27 15 00.
09/11/2022
Revisions: Date:
2 CONTRACTOR SHALL PROVIDE NEW NURSE CALL DEVICES FOR THE RENOVATED
SPACE AND INTEGRATE WITH EXISTING SYSTEM.
BASIS OF DESIGN:
TELLIGENTS C600 SYSTEM
VENDOR: INTEGRATED ELECTRONICS
-HC-PSTN1, STANDARD SGL. PATIENT STATION
-HC-PP2-LAV-3K, 2-BTN PUSH/PULL LAV. STA. 3K
-NUDL4S-H, DOME LIGHT 4 SECTIONS, SPEECH AND BUZZER
-NUDUTY-HU, DUTY STATION
-NGTDSPA-H, NURSE STATION CONSOLE
-HP-IPSWITCH8, PPOWER SWITCH
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
E
N
L
ATS "D"
150A/3P
BYPASS E
N
L
BQHAT2
480Y/277V
150A-4P
BYPASS
M M
M M 7.5 7.5
E
N
L
ATS "A"
150A/3P
BYPASS
E
N
L
BQHAT1
480Y/277V
150A-4P
BYPASS
E
N
L
ATS "B"
150A/3P
BYPASS
E
N
L
BSHAT
480Y/277V
150A-4P
BYPASS
E
N
L
ATS "C"
150A/3P
BYPASS
E
N
L
BCHAT
480Y/277V
150A-4P
BYPASS
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
A
/3 P
BE2
208Y/120V
100A
MLO
2ECLA
208Y/120V
225A
MLO
3ECLA
208Y/120V
225A
MLO
/3
P
MCCB-N
100A
2EHLA
225A
2EHLA
225A
BE1
100A
MCC2-E
480V
SECT.
MCC2-E
208Y/120V
SECT.
MCC2
480V
SECT.
MCC2
208Y/120V
SECT.
2NHA
225A
/3
P
/3
P
/3
P
/3
P
/3
P
/3
P
7.5 20
BA
208Y/120V
100A
MLO
BA
208Y/120V
100A
MLO
1A 208Y/120V
100A
MLO
1B 208Y/120V
100A
MLO
40 40
TRAILER
/3
P
2NLA
100A
2NLB
225A
2NLC
225A
2NLD
225A
3NLA
225A
3NLB
225A
3NLB1
225A
/3
P
PNLA
100A
BEM1
480/277V
100A
MLO
BELP
208Y/120V
100A
MCB
0/
3P
MCCE
208V, 3P, 3W 600A
BECD
208V, 3P, 4W 400A
BEMD
480Y/277V, 3P, 4W 800A
BEEH(NEW)
480Y/277V 3P, 3W 600A
BPH
480Y/277V 3P, 4W 800A
MSB
480Y/277V 3P, 4W 1200A
NLDP
208Y/120V 3P, 4W 600A
MCC1
208V, 3P, 3W 200A
SEE SHEET E-602
FOR CONTINUATION
FIRST FLOOR
BASEMENT
SECOND FLOOR
THIRD FLOOR
ROOF/PENTHOUSE
T-BELP
480V
30KVA
208/120V
4 5
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
KEY PLAN
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/1
/2
:2
:2
P
M
E-601
PARTIAL ONE LINE DIAGRAM
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 K. LUKE J. HALPIN
ISSUED FOR
CONSTRUCTION
NTS
F1
PARTIAL ONE LINE DIAGRAM
1 INSTALL NEW EQUIPMENT PER THE 'ESSENTIAL SYSTEM RENOVATION SEQUENCE' SCHEDULE, TYPICAL.
2 CUT OVER FEEDERS INTO THE EXISTING SYSTEMS PER THE 'ESSENTIAL SYSTEM RENOVATION
SEQUENCE' SCHEDULE, TYPICAL.
3 REMOVE EXISTING AUTOMATIC TRANSFER SWITCHES PER THE 'ESSENTIAL SYSTEM RENOVATION
SEQUENCE' SCHEDULE, TYPICAL.
4 REMOVE VFD SF3 AND SF5 IN THEIR ENTIRETY BACK TO AH-3.
5 DISCONNECT VFD RF6 AND RELOCATE TO GUTTER SERVING VFD SF4. REWIRE VFD SF6 TO MCC1.
6 REMOVE GUTTER IN ITS ENTIRETY BACK TO MCCE.
7 GENERAL CONTRACTOR SHALL PROVIDE 30-DAY LOAD MEASUREMENT PER NEC 220.87 OF EQUIPMENT
INDICATED AND PROVIDE THE RESULTS TO THE ENGINEER OF RECORD (EEOR) TO VERIFY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD PRIOR TO COMMENCEMENT OF ELECTRICAL
WORK.
A ALL EQUIPMENT INDICATED HALFTONE IS EXISTING TO REMAIN, UNO.
B ALL EQUIPMENT SHOWN DASHED AND BOLD SHALL BE REMOVED IN THEIR
ENTIRETY BACK TO NEAREST POINT OF SERVICE, UNO.
C PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED OUTDOORS.
D PROVIDE EQUIPMENT CONNECTIONS SIZED PER THE HOMERUN.
E COORDINATE FINAL EQUIPMENT CONNECTIONS REQUIREMENTS WITH EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN.
G NEW PANELBOARDS RATED LESS THAN 100A SHALL HAVE A MINIMUM 10,000 AIC
BRACING.
H NEW PANELBOARDS RATED LESS THAN 400A SHALL HAVE A MINIMUM 22,000 AIC
BRACING.
I NEW PANELBOARDS RATED 400A SHALL HAVE A MINIMUM 35,000 AIC BRACING.
J NEW DISTRIBUTION PANELBOARDS RATED OVER 400A SHALL BE SWITCHBOARDS
AND HAVE A MINIMUM 65,000 AIC BRACING.
FEEDER SCHEDULE
AMP CONDUCTORS - 3W+G (Suffix -3) CONDUCTORS - 4W+G (Suffix -4) CONDUCTORS - 3W,200%N,G (Suffix -N)
20 3#12, 1#12 G, 3/4"C 3#12, 1#12 N, 1#12 G, 3/4"C 3#12, 1#8 N, 1#12 G, 3/4"C
25 3#10, 1#10 G, 3/4"C 3#10, 1#10 N, 1#10 G, 3/4"C 3#10, 1#6 N, 1#10 G, 3/4"C
30 3#10, 1#10 G, 3/4"C 3#10, 1#10 N, 1#10 G, 3/4"C 3#10, 1#6 N, 1#10 G, 3/4"C
35 3#8, 1#10 G, 3/4"C 3#8, 1#8 N, 1#10 G, 3/4"C 3#8, 1#4 N, 1#10 G, 1"C
40 3#8, 1#10 G, 3/4"C 3#8, 1#8 N, 1#10 G, 3/4"C 3#8, 1#3 N, 1#10 G, 1"C
45 3#6, 1#10 G, 3/4"C 3#6, 1#6 N, 1#10 G, 1"C 3#6, 1#2 N, 1#10 G, 1"C
50 3#6, 1#10 G, 3/4"C 3#6, 1#6 N, 1#10 G, 1"C 3#6, 1#2 N, 1#10 G, 1"C
60 3#4, 1#10 G, 1"C 3#4, 1#4 N, 1#10 G, 1-1/4"C 3#4, 1#1 N, 1#10 G, 1-1/4"C
70 3#4, 1#8 G, 1"C 3#4, 1#4 N, 1#8 G, 1-1/4"C 3#4, 1#2/0 N, 1#8 G, 1-1/4"C
80 3#3, 1#8 G, 1-1/4"C 3#3, 1#3 N, 1#8 G, 1-1/4"C 3#3, 1#3/0 N, 1#8 G, 1-1/2"C
90 3#2, 1#8 G, 1-1/4"C 3#2, 1#2 N, 1#8 G, 1-1/4"C 3#2, 1#3/0 N, 1#8 G, 1-1/2"C
100 3#1, 1#8 G, 1-1/4"C 3#1, 1#1 N, 1#8 G, 1-1/2"C 3#1, 1#4/0 N, 1#8 G, 2"C
110 3#1, 1#6 G, 1-1/4"C 3#1, 1#1 N, 1#6 G, 1-1/2"C 3#1, 1-250kcmil N, 1#6 G, 2"C
125 3#1, 1#6 G, 1-1/4"C 3#1, 1#1 N, 1#6 G, 1-1/2"C 3#1/0, 1-300kcmil N, 1#4 G, 2"C
150 3#1/0, 1#6 G, 1-1/2"C 3#1/0, 1#1/0 N, 1#6 G, 2"C 3#2/0, 2#2/0 N, 1#4 G, 2"C
175 3#2/0, 1#6 G, 1-1/2"C 3#2/0, 1#2/0 N, 1#6 G, 2"C 3#3/0, 2#3/0 N, 1#4 G, 2-1/2"C
200 3#3/0, 1#6 G, 2"C 3#3/0, 1#3/0 N, 1#6 G, 2"C 3#4/0, 2#4/0 N, 1#4 G, 2-1/2"C
225 3#4/0, 1#4 G, 2"C 3#4/0, 1#4/0 N, 1#4 G, 2-1/2"C 3-250kcmil, 2-250kcmil N, 1#3 G, 3"C
250 3-250kcmil, 1#4 G, 2"C 3-250kcmil, 1-250kcmil N, 1#4 G, 2-1/2"C 3-300kcmil, 2-300kcmil N, 1#3 G, 3"C
300 3-350kcmil, 1#4 G, 2-1/2"C 3-350kcmil, 1-350kcmil N, 1#4 G, 3"C 3-400kcmil, 2-400kcmil N, 1#3 G, 3-1/2"C
350 3-500kcmil, 1#3 G, 3"C 3-500kcmil, 1-500kcmil N, 1#3 G, 3-1/2"C [2 SETS] 3#3/0, 2#3/0 N, 1#3 G, 2-1/2"C
400 [2 SETS] 3#3/0, 1#3 G, 2"C [2 SETS] 3#3/0, 1#3/0 N, 1#3 G, 2"C [2 SETS] 3#4/0, 2#4/0 N, 1#2 G, 2-1/2"C
450 [2 SETS] 3#4/0, 1#2 G, 2"C [2 SETS] 3#4/0, 1#4/0 N, 1#2 G, 2-1/2"C [2 SETS] 3-250kcmil, 2-250kcmil N, 1#1 G, 3"C
500 [2 SETS] 3-250kcmil, 1#2 G, 2"C [2 SETS] 3-250kcmil, 1-250kcmil N, 1#2 G, 2-1/2"C [2 SETS] 3-300kcmil, 2-300kcmil N, 1#1 G, 3"C
600 [2 SETS] 3-350kcmil, 1#1 G, 2-1/2"C [2 SETS] 3-350kcmil, 1-350kcmil N, 1#1 G, 3"C [2 SETS] 3-400kcmil, 2-400kcmil N, 1#1/0 G, 3-1/2"C
700 [2 SETS] 3-500kcmil, 1#1/0 G, 3"C [2 SETS] 3-500kcmil, 1-500kcmil N, 1#1/0 G, 3-1/2"C
[3 SETS] 3-300kcmil, 2-300kcmil N, 1#1/0 G, 3"C
750 [2 SETS] 3-500kcmil, 1#1/0 G, 3"C [2 SETS] 3-500kcmil, 1-500kcmil N, 1#1/0 G, 3-1/2"C
[3 SETS] 3-300kcmil, 2-300kcmil N, 1#1/0 G, 3"C
800 [3 SETS] 3-300kcmil, 1#1/0 G, 2-1/2"C [3 SETS] 3-300kcmil, 1-300kcmil N, 1#1/0 G, 3"C [3 SETS] 3-350kcmil, 2-350kcmil N, 1#2/0 G, 3"C
900 [3 SETS] 3-350kcmil, 1#2/0 G, 2-1/2"C [3 SETS] 3-350kcmil, 1-350kcmil N, 1#2/0 G, 3"C [3 SETS] 3-400kcmil, 2-400kcmil N1#3/0 G, 3-1/2"C
1000 [3 SETS] 3-400kcmil, 1#2/0 G, 3"C [3 SETS] 3-400kcmil, 1-400kcmil N, 1#2/0 G, 3"C [3 SETS] 3-500kcmil, 2-500kcmil N, 1#3/0 G, 3-1/2"C
1200 [4 SETS] 3-350kcmil, 1#3/0 G, 2-1/2"C [4 SETS] 3-350kcmil, 1-350kcmil N, 1#3/0 G, 3"C [4 SETS] 3-400kcmil, 2-400kcmil N, 1#4/0 G, 3-1/2"C
1600 [5 SETS] 3-400kcmil, 1#4/0 G, 3"C [5 SETS] 3-400kcmil, 1-400kcmil N, 1#4/0 G, 3"C [5 SETS] 3-500kcmil, 2-500kcmil N, 1-300kcmil G, 4"C
2000 [6 SETS] 3-400kcmil, 1-250kcmil G, 3"C [6 SETS] 3-400kcmil, 1-400kcmil N, 1-250kcmil G, 3"C
[6 SETS] 3-500kcmil, 2-500kcmil N, 1-350kcmil G, 4"C
2500 [7 SETS] 3-500kcmil, 1-350kcmil G, 3"C [7 SETS] 3-500kcmil, 1-500kcmil N, 1-350kcmil G, 3-1/2"C
[8 SETS] 3-500kcmil, 2-500kcmil N, 1-400kcmil G, 4"C
3000 [8 SETS] 3-500kcmil, 1-400kcmil G, 3"C [8 SETS] 3-500kcmil, 1-500kcmil N, 1-400kcmil G, 3-1/2"C
[9 SETS] 3-500kcmil, 2-500kcmil N, 1-500kcmil G, 4"C
4000 [11 SETS] 3-500kcmil, 1-500kcmil G, 3"C [11 SETS] 3-500kcmil, 1-500kcmil N, 1-500kcmil G, 3-1/2"C
[12 SETS] 3-500kcmil, 2-500kcmil N, 2-300kcmil G, 4"C
5000 [14 SETS] 3-500kcmil, 2-350kcmil G, 3-1/2"C [14 SETS] 3-500kcmil, 1-500kcmil N, 2-350kcmil G, 3-1/2"C
[15 SETS] 3-500kcmil, 2-500kcmil N, 2-400kcmil G, 4"C
TAG CONDUCTORS, 4W + GEC
9TX 3#8, 1#8 N, 1#8 GEC, 1"C
15TX 3#6, 1#6 N, 1#8 GEC, 1"C
30TX 3#1, 1#1 N, 1#6 GEC, 1-1/2"C
45TX 3#1/0, 1#1/0 N, 1#6 GEC, 2"C
75TX 3-250kcmil, 1-250kcmil N, 1#2 GEC, 2-1/2"C
112.5TX [2 SETS] 3#3/0, 1#3/0 N, 1#1/0 GEC, 2"C
150TX [2 SETS] 3-250kcmil, 1-250kcmil N, 1#1/0 GEC, 2-1/2"C
225TX [3 SETS] 3-300kcmil, 1-300kcmil N, 1#1/0 GEC, 3"C
300TX [3 SETS] 3-400kcmil, 1-400kcmil N, 1#1/0 GEC, 3"C
500TX [5 SETS] 3-400kcmil, 1-400ckmil N, 1#1/0 GEC, 3"C
ESSENTIAL SYSTEM RENOVATION SEQUENCE
1 INSTALL THE NEW AUTOMATIC TRANSFER SWITCHES AND EQUIPMENT BRANCH
PANEL 'BEEH'.
2 INSTALL FEEDERS FROM THE NEW EQUIPMENT TO THE TERMINATION POINTS. DO
NOT CUTOVER THE FEEDERS INTO THE EXISTING SYSTEMS.
3 SCHEDULE THE FEEDER CUTOVERS WITH THE VA COR. ATS 'BEHA1' AND PANEL
'BEHA1' SHALL BE PRIORITY. TEMPORARY POWER SHALL BE PROVIDED, AFTERHOUR
WORK IS REQUIRED DURING THE CUTOVER TO TEMPORARY POWER. SEE
SPECIFICATION 01 00 00 PART 1.6.J. FOR ADDITIONAL INFORMATION.
4 REMOVE THE OLD AUTOMATIC TRANSFER SWITCHES.
5 REMOVE THE VFDs AND REWIRE VFDs ASSOCIATED WITH AHUs.
6 INSTALL FEEDERS FROM PANEL 'BEH1' TO MECHANICAL EQUIPMENT.
GENERAL SHEET NOTES
KEYNOTES
TRENCH
GRADE
WARNING TAPE
COPPER GROUND CONDUCTOR
P
12" MINIMUM
6"
COMPACTED
BACKFILL
CONDUIT, REFER
TO DRAWINGS FOR
ADDITIONAL
INFORMATION
3"
(TYP)
36" MINIMUM
XQ350
RATING (KW)
MODEL
GENERATOR SCHEDULE
CATERPILLAR
MFG RATING (KVA)
437.5
VOLT.
277/480
POWER FACTOR
0.8 LAGGING
APPLICATION
STAND-ALONE
FUEL
DIESEL
PHASE
3 WYE
NOTE:
1. REFER TO SPECIFICATION SECTION 26 32 13 FOR ADDITIONAL INFORMATION.
2. PROVIDE A FACTORY ASSEMBLED, WIRED (EXCEPT FOR FIELD CONNECTIONS), COMPLETE, FULLY AUTOMATIC ENGINE GENERATOR SYSTEM, AS WELL AS
ALL ASSOCIATED EQUIPMENT AND DEVICES INTENDED FOR THE OPERATING, CONTROL, MONITORING, AND REMOTE MANUAL STOP FUNCTIONS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/1
/2
:2
:3
P
M
E-701
ELECTRICAL SCHEDULES AND
DETAILS
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 J. LOHL J. HALPIN
ISSUED FOR
CONSTRUCTION
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING VOLTS LAMPS DRIVER LOAD MANUFACTURER AND MODEL NO.
C1 COVE MOUNTED, LED STRIP, ASYMMETRIC
DISTRIBUTION, LENGTH AS INDICATED ON
PLANS, COMPLETE WITH CONNECTORS
(STRAIGHT AND 90). 3VA/FT LOAD
COVE MVOLT 3500k, 300lm/ft, 80CRI
0-10V
DIMMABLE
<varies> AXIS LIGHTING #CL SERIES FOR ARMSTRONG
AXION COVE
D1 6" APERTURE, LED SHOWER DOWNLIGHT,
FLAT CLEAR LENS, IP66 RATED
FLUSH MVOLT 1000LM
3500K
80CRI
LED (FIXED) 12 VA GOTHAM #EVO6SH SERIES OR APPROVED EQUAL
D2 6" APERTURE, ENCLOSED GLASS, WET
LOCATION, LED DOWNLIGHT, CLEAR
REFLECTOR
FLUSH MVOLT 1000LM
3500K
80CRI
0-10V
DIMMABLE
12 VA GOTHAM #EVO SERIES OR APPROVED EQUAL
F3 2X2 RECESSED, FLUSH MOUNT, A12.125,
FLAT ACRYLIC LENSED TROFFER, FLUSH
STEEL DOOR, 4 1/4" DEEP.
FLUSH
(FLANGED)
MVOLT 2500LM
3500K
80CRI
0-10V
DIMMABLE
26 VA COLUMBIA #LLT22 SERIES OR APPROVED EQUAL
G1 2X4 RECESSED DIRECT-INDIRECT TROFFER,
3 1/2" DEEP, SNAP-IN FROSTED ACRYLIC
DIFFUSER
FLUSH MVOLT 4500LM
3500K
80CRI
0-10V
DIMMABLE
43 VA FOCAL POINT #FARL SERIES OR APPROVED EQUAL
G3 2X2 RECESSED, FLUSH MOUNT, A12.125,
FLAT ACRYLIC LENSED TROFFER, FLUSH
STEEL DOOR, 4 1/4" DEEP.
FLUSH MVOLT 2500LM
3500K
80CRI
0-10V
DIMMABLE
26 VA COLUMBIA #LLT22 SERIES OR APPROVED EQUAL
L1 1X4, RECESSED STATIC TROFFER, FLAT
STEEL DOOR, A12.125 ACRYLIC LENS
FLUSH
(FLANGED)
MVOLT 3800LM
3500K
80CRI
0-10V
DIMMABLE
45 VA COLUMBIAL #LLT14 SERIES OR APPROVED EQUAL
L2 6"X4', LINEAR RECESSED, SYMMETRIC
DISTRIBUTION, FLAT LENS,LED
FLUSH MVOLT 1300LM
3500K
80CRI
0-10V
DIMMABLE
14 VA MARK LIGHTING #SL6L SERIES OR APPROVED
EQUAL
M1 9.5"X4, LINEAR, FLUSH, ASSYMETRIC
DISTRIBUTION TOWARDS PATIENT, TWO
FUNCTION, AMBIENT/EXAM
(FLANGED) MVOLT 6500LM
3500K
90CRI
0-10V
DIMMABLE
91 VA KENALL #MAEC SERIES OR APPROVED EQUAL
M2 9.5"X4, LINEAR, FLUSH, ASSYMETRIC
DISTRIBUTION TOWARDS PATIENT, TWO
FUNCTION, AMBIENT/EXAM
FLUSH MVOLT 6500LM
3500K
90CRI
0-10V
DIMMABLE
91 VA KENALL #MAEC SERIES OR APPROVED EQUAL
S1 24" x 24" x 5" LED FIXTURE, LUMINOUS LENS
WITH PATTERN PER ARCHITECT
REQUIREMENTS. PROVIDE WITH ONE #LSC
24PS, 277VAC-24VD POWER SUPPLY FOR
THE PROJECT. SEE LIGHTING PLANS FOR
WIRING REQUIREMENTS
FLUSH 24VDC LED 6500k 0-10V
DIMMABLE
25 VA SKYFACTORY #ES22-CLA SERIES
X1 CEILING MOUNTED EXIT SIGNS LED 7 VA COOPER
N.T.S.
B9
CONCRETE RADIAL DUCTBANK SECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical and Plumbing:
A u to d e s k D o c s /5
-1
-2
E x p a n d
E D
B e d s
/5
-1
-2
.O
P C
.M E
.r v t
/1
/2
:2
:4
P
M
E-702
ELECTRICAL SCHEDULES
TRIPLE C - THE A-E GROUP
4401 Atlantic Avenue, Suite 200
Long Beach, CA 90807
562.452.7175
MAT PERKINS
REMODEL ED BEDS FOR
OBSERVATION BEDS
2615 E. CLINTON AVENUE, FRESNO, CA 93703
570-17-210
OPC
09/11/2022 J. LOHL J. HALPIN
ISSUED FOR
CONSTRUCTION
Total Est. Demand: 68 A
Mechanical Equipment 57160 VA 80.00% 45728 VA Total Conn.: 82 A
NC 2520 VA 100.00% 2520 VA Total Est. Demand (kVA): 56 kVA
REC 900 VA 100.00% 900 VA Total Conn. (kVA): 68 kVA
Receptacle 7200 VA 100.00% 7200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 82 A
Total Conn. Load: 67780 VA
3 AHU-3 VFD-2 3 400 A 50 A 18643 VA
2 AHU-3 VFD-1 3 400 A 100 A 27098 VA
1 BEM1 3 400 A 100 A 22040 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Enclosure: Type 1
Mounting: Surface Mains Rating: 600 A
Supply From: Wiring: 3P,4 OCP Device Type: MLO
Location: ELECTRIC CLOSET B1C16 Volts: 480/277 Wye A.I.C. Rating:
Switchboard: BEEH
PER NEC 700.1 ONLY LIFE SAFTY LOADS CAN BE USED ON THIS PANEL
Notes:
Total Est. Demand Current: 29 A
Total Conn. Current: 29 A
REC 900 VA 100.00% 900 VA Total Est. Demand: 10620 VA
NC 2520 VA 100.00% 2520 VA Total Conn. Load: 10620 VA
Receptacle 7200 VA 100.00% 7200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 33 A 38 A 21 A
Total Load: 3780 VA 4320 VA 2520 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 OBSERVATION RM B1C34A 20 A 1 360 VA 0 VA 1 20 A Spare 18
15 OBSERVATION RM B1C34C 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34A... 16
13 OBSERVATION RM B1C34E 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34C... 14
11 OBSERVATION RM B1C34G 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34E... 12
9 OBSERVATION RM B1C34K 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34G... 10
7 OBSERVATION RM BC24 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C34K... 8
5 OBSERVATION RM B1C23 20 A 1 360 VA 720 VA 1 20 A OBSERVATION RM B1C24 DEDICATED 6
3 OBSERVATION RM B1C21 20 A 1 1440... 720 VA 1 20 A OBSERVATION RM B1C23 DEDICATED 4
1 REC Room B1C53, B1C52 20 A 1 900 VA 720 VA 1 20 A OBSERVATION RM B1C21 DEDICATED 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Indoor Spaces: 42 MCB Rating: 125 A
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: T-BELP Phases: 3 Mains Type: MCB
Location: Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study
Branch Panel: BELP
Notes: (1) EXISTING PANEL, LOAD SHOWN ARE RE-USED DEMO LOADS. ALL LOADS ARE LESS THEN THE ORIGINAL LOADS
Total Est. Demand Current: 8 A
Total Conn. Current: 8 A
REC 1800 VA 100.00% 1800 VA Total Est. Demand: 2954 VA
NC 1080 VA 100.00% 1080 VA Total Conn. Load: 2954 VA
Other 74 VA 100.00% 74 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 16 A 1 A 10 A
Total Load: 1800 VA 74 VA 1080 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 1080... 1 20 A 1 REC B1C34J, B1C34F, B1C34B,... 24
21 22
19 20
17 18
15 74 VA 1 20 A 1 SKYLIGHTS NEW OBSERVATION 16
13 720 VA 1 20 A 1 REC Room BC50, B1C23, B1C21, B1C-9 14
11 12
9 10
7 NEW OBSERVATION RM BB1C23 AND... 1 20 A 1 720 VA 360 VA 1 20 A 1 NEW OBSERVATION RM BC24 8
5 6
3 4
1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Indoor Spaces: 42 MCB Rating: 125 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELECTRIC CLOSET B1C16 Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study
Branch Panel: BA(E)
Notes: (1) EXISTING PANEL, LOAD SHOWN ARE RE-USED DEMO LOADS. ALL LOADS ARE LESS THEN THE ORIGINAL LOADS
Total Est. Demand Current: 6 A
Total Conn. Current: 6 A
LTG 359 VA 125.00% 448 VA Total Est. Demand: 2126 VA
REC 1620 VA 100.00% 1620 VA Total Conn. Load: 2025 VA
Lighting 47 VA 125.00% 59 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 17 A 0 A
Total Load: 0 VA 2025 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 REC Room B1C34H, B1C34F 1 20 A 1 900 VA 28
25 26
23 24
21 REC Room B1C34D, B1C34B 1 20 A 1 720 VA 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 406 VA 1 20 A 1 LS LIGHTING NEW OBSERVATION 4
1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Indoor Spaces: 42 MCB Rating: 125 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELECTRIC CLOSET B1C16 Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study
Branch Panel: BE1(E)
PER NEC 701.1 ONLY LEGALLY REQUIRED STANDBY LOADS CAN BE USED ON THIS PANEL
Notes:
Total Est. Demand Current: 24 A
Mechanical Equipment 11420 VA 80.00% 9136 VA Total Conn. Current: 27 A
REC 900 VA 100.00% 900 VA Total Est. Demand: 19756 VA
NC 2520 VA 100.00% 2520 VA Total Conn. Load: 22040 VA
Receptacle 7200 VA 100.00% 7200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 38 A 20 A 22 A
Total Load: 10327 VA 5587 VA 6127 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Spare 20 A 1 0 VA -- 1 -- Space 26
23 Spare 20 A 1 0 VA -- 1 -- Space 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 -- -- -- 903 VA 0 VA 1 20 A Spare 20
17 -- -- -- 903 VA 0 VA 1 20 A Spare 18
15 EF-1-11 20 A 3 903 VA 0 VA 1 20 A Spare 16
13 -- -- -- 903 VA 0 VA 1 20 A Spare 14
11 -- -- -- 903 VA 0 VA -- -- -- 12
9 EF-1-10 20 A 3 903 VA 0 VA -- -- -- 10
7 -- -- -- 2520... 0 VA 3 30 A 1-EF-ED 8
5 -- -- -- 4320... 0 VA -- -- -- 6
3 T-BELP 20 A 3 3780... 0 VA -- -- -- 4
1 DDC-AHU-3 20 A 1 6000... 0 VA 3 30 A EF-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Indoor Spaces: 42 MCB Rating: 125 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: BEEH Phases: 3 Mains Type: MLO
Location: ELECTRIC CLOSET B1C16 Volts: 480/277 Wye A.I.C. Rating: Per Arc Flash Study
Branch Panel: BEM1
Notes: (1) EXISTING PANEL, LOAD SHOWN ARE RE-USED DEMO LOADS. ALL LOADS ARE LESS THEN THE ORIGINAL LOADS
LTG 1917 VA 125.00% 2396 VA Total Est. Demand Current: 18 A
REC 2160 VA 100.00% 2160 VA Total Conn. Current: 17 A
NC 1800 VA 100.00% 1800 VA Total Est. Demand: 6600 VA
Other 74 VA 100.00% 74 VA Total Conn. Load: 6086 VA
Lighting 136 VA 125.00% 171 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 17 A 17 A 17 A
Total Load: 2070 VA 2011 VA 2006 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 720 VA 1 20 A 1 OBSERVATION RM B1C34E 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 566 VA 1 20 A 1 LTG NEW OBSERVATION ROOM 12
9 REC Room B1C-6, B1C-9 1 20 A 1 900 VA 751 VA 1 20 A 1 LTG NEW OBSERVATION ROOM 10
7 REC Room B1C53, B1C52, BC51 1 20 A 1 540 VA 720 VA 1 20 A 1 REC Room BC24, B1C23, B1C21 8
5 720 VA 1 20 A 1 OBSERVATION RM B1C34E 6
3 360 VA 1 20 A 1 OBSERVATION RM B1C34K 4
1 810 VA 1 20 A 1 LTG NEW OBSERVATION ROOM BC24 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Indoor Spaces: 42 MCB Rating: 125 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELECTRIC CLOSET B1C16 Volts: 120/208 Wye A.I.C. Rating: Per Arc Flash Study
Branch Panel: BB(E)
THIS PANEL IS FOR LIFE SAFE LOADS ONLY
THIS PANEL IS FOR EMERGENCY LOADS ONLY
File details come from the government source that posted it. Updated .