These documents are detailed construction drawings for a demolition project at the Perry Point VA Medical Center in Maryland. The project involves the complete demolition of Building 9H, a two-story (with basement) concrete and masonry structure built in 1924, encompassing approximately 54,500 gross square feet. The building has been vacant since 2014 and requires comprehensive hazardous materials abatement before demolition, including removing asbestos-containing materials, lead-based paint, PCBs, mercury, and other potential environmental hazards.
The scope of work extends beyond building demolition to include relocating critical infrastructure like the campus fiber-optic network distribution hub, emergency power systems, and utility services. The project also requires creating a new telecommunications room, installing security access systems, and managing complex utility shutdowns. The contractor must comply with extensive environmental and safety regulations, including obtaining necessary permits from Maryland Department of the Environment and EPA, maintaining strict waste disposal protocols, and ensuring minimal disruption to the medical center's operations. The project is scheduled for 400 calendar days, with a planned Notice to Proceed approximately 30 days after contract award.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT SITE MAPPROJECT LOCATION MAP
CHIEF, ENGINEERING DATE
SIGNATURE BLOCK
DRAWING INDEX
HOSPITAL DIRECTOR DATE
U.S. Department of Veterans Affairs
LOCATION OF
VA MEDICAL CENTER
CAMPUS
LIMITS OF WORK
(502)890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE KY 40218
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
PERRY POINT VA MEDICAL CENTER
DEMOLISH BUILDING 9H
PERRY POINT, MD 21902
PROJECT #512A5-23-311
DEMOLISH BUILDING 9H
GI001
SCMBVG
COVER SHEET
SITE PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BUILDING 9H
SITE REFERENCE PHOTOS
BUILDING 9H - EXTERIOR SOUTH SIDE - EXISTING CONDITIONS
SCALE: NOT TO SCALE
C1
BUILDING 9H - EXTERIOR NORTH SIDE - EXISTING CONDITIONS
SCALE: NOT TO SCALE
F1
N
F9 KEY PLAN
1/64" = 1'-0"
9H-GR901
SCMBVG
BUILDING 9H
SITE REFERENCE PHOTOS 9H
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BUILDING 9H - EXTERIOR EAST SIDE - EXISTING CONDITIONS
SCALE: NOT TO SCALE
D1 BUILDING 9H - EXTERIOR WEST SIDE - EXISTING CONDITIONS
SCALE: NOT TO SCALE
D6
N
F9 KEY PLAN
1/64" = 1'-0"
BUILDING 344
9H-GR902
SCMBVG
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
B1 BUILDING 9H - SOUTH ELEVATION
NOT TO SCALE
D1 BUILDING 9H - EAST ELEVATION
NOT TO SCALE
F1 BUILDING 9H - NORTHEAST ELEVATION
NOT TO SCALE
F5 BUILDING 9H - NORTHWEST ELEVATION
NOT TO SCALE
C5 BUILDING 9H - WEST ELEVATION
NOT TO SCALE
N
F9 KEY PLAN
1/64" = 1'-0"
9H-GR903
SCMBVG
C
070809
17 19 20 21 22 23
D E
C
C F
C
C D EC D EC D EC G
C C D E G
C D E C D E A B C
D E A B C
D E
C D E C D E
F
C D E C D E C D E
C D E A B C D E
A B D E
C D EC
C
C
C D E F
C D E
C I J A B C
D E A B C
D EC F
C F
C F C
F
C
C
C
A B D E
C
K
RH Q
RH Q
RH Q
RH Q
N
N
D
D
D
D
D
E
E E
E
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
5-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BVG NC
9H-HA101
KEY PLAN
NOT TO SCALE
F1
BUILDING 9H - BASEMENT
SCALE: 3/32" = 1'-0"
F1
ASBESTOS CONTAINING MATERIALS DESIGNATION -
A. FLOOR TILE (VARIOUS SIZES AND COLORS)
B. BLACK FLOOR TILE MASTIC
C. WHITE PIPE SEAM SEALANT
D. WINDOW GLAZING
E. EXTERIOR WINDOW CAULKING
F. FIRE DOOR
G. CARDBOARD PIPE INSULATION
H. EXTERIOR STUCCO
I. WHITE DUCT SEAM SEALANT (ON FIBERGLASS INSULATION)
J. CLOTH VIBRATION ISOLATOR
K. WHITE DUCT MASTIC ON METAL
L. YELLOW CARPET MASTIC
M. BROWN CEILING TILE MASTIC DOTS
N. ELEVATOR DOOR AND CAB INSULATION
O. RED FLOOR LEVELING COMPOUND
P. BUILT UP ROOFING
Q. EXTERIOR VENT CAULK
R. EXTERIOR DOOR CAULK
S. GRAY METAL DUCT SEAM SEALANT
T. GRAY LOUVER CAULK
U. ROOF SHINGLES
ASBESTOS CONTAINING MATERIAL NOTES
1. ALL OF THE ACMS DEPICTED ON THE DRAWINGS WILL REQUIRE ABATEMENT. PLEASE REFER TO THE HAZARDOUS MATERIALS REPORT AND ASBESTOS ABATEMENT SPECIFICATION SECTION 02 82 13.41. DEMOLITION MUST OCCUR TO EXPOSE PIPE AND DUCT INSULATION WITHIN WALLS AND ABOVE CEILINGS FOR ABATEMENT.
2.ALL ASBESTOS ABATEMENT WILL BE PERFORMED WITHIN FULL NEGATIVE PRESSURE ENCLOSURES.
3.THE EXTERIOR STUCCO ON THE BUILDING IS ASBESTOS CONTAINING AND WILL NEED TO BE ABATED PRIOR TO
THE DEMOLITION OF THE BUILDING. THE FULL NEGATIVE PRESSURE ENCLOSURES MUST BE CONSTRUCTED IN SUCH A MANNER AS TO WITHSTAND ANY AND ALL POTENTIAL BREACHES FROM OUTDOOR FORCES (WIND, RAIN, SNOW, ICE, VANDALISM, ETC). THIS AREA MUST ALSO BE AIR TIGHT AND BE PLACED UNDER NEGATIVE PRESSURE WITH THE USE OF HEPA FILTERED NEGATIVE AIR MACHINES, CAPABLE OF PROVIDING -0.02 INCHES OF
WATER OF NEGATIVE PRESSURE.
LEAD BASED NOTES
1.THE FOLLOWING SURFACES WERE FOUND TO HAVE LEAD BASED PAINT:
· METAL WINDOW FRAME SYSTEMS
· WOOD TRANSOMS
· TERRACOTTA WALLS
· METAL CORNER GUARDS
· WOOD WINDOW FRAME SYSTEMS
· METAL HANDRAILS
· CONCRETE WINDOW SILLS
· STRUCTURAL STEEL
· METAL CAGE DOORS
· METAL TANK
· METAL VENTS
· METAL DOOR FRAME SYSTEMS
· CONCRETE RISERS
· CERAMIC SLOP SINK
· PLASTER CEILINGS AND WALLS
· METAL STALL DOOR
· METAL LOCKERS
· METAL STAIR SYSTEMS
· WOOD DOOR SYSTEM
· WOOD COLUMNS
2. LEAD ABATEMENT IS NOT REQUIRED FOR THIS PROJECT. HOWEVER, OSHA'S LEAD IN CONSTRUCTION STANDARD APPLIES TO ALL DISTURBANCE OF LEAD BASED PAINT. IN ADDITION, THE CONTRACTOR SHALL USE METHODS TO LIMIT THE AMOUNT OF DUST PRODUCED DURING DEMOLITION OF ANY COMPONENT WITH LEAD PAINT. THE WASTE STREAM (MATERIALS NOT GOING TO BE RECYCLED) WILL REQUIRE TCLP SAMPLES TO DETERMINE IF THE WASTE IS HAZARDOUS FOR DISPOSAL. THIS SAMPLING IS TO BE COMPLETED BY THE
DEMOLITION CONTRACTOR.
OTHER IDENTIFIED HAZARDOUS MATERIALS NOTES
1. APPROXIMATELY 1,105 MERCURY VAPOR LAMPS WERE OBSERVED THROUGHOUT THE BUILDINGS. REMOVAL AND DISPOSAL AS A UNIVERSAL WASTE FOR MERCURY CONTAINING LAMPS UNDER THE RESOURCE CONSERVATION
AND RECOVERY ACT SHALL OCCUR PRIOR TO THE DEMOLITION.
2.RANDOMLY SELECTED LIGHTING BALLASTS WERE CHECKED AND ALL HAD "NO PCBS" LABELS. ALL BALLASTS MUST BE REMOVED AND CHECKED FOR THESE LABELS BY THE DEMOLITION CONTRACTOR AND DISPOSED OF
PROPERLY.
3.THE DEMOLITION CONTRACTOR MUST CHECK ALL EXIST SIGNS FOR BATTERIES OR TRITIUM AND DISPOSE OF
THESE SIGNS AS REQUIRED BY THE EPA.
4.THIRTY THREE WINDOW AIR CONDITIONING UNITS WERE OBSERVED WITHIN BUILDING 9H. THESE UNITS ARE LIKELY TO HAVE REFRIGERANTS THAT WILL NEED TO BE REMOVED PROPERLY UNDER THE EPA REGULATIONS (40
CFR PART 82, SUBPART F) UNDER SECTION 608 OF THE CLEAN AIR ACT.
HAZARDOUS MATERIALS
BUILDING 9H - BASEMENT
9H
42 43
98 82
109111
223 222
C E
A B D E
D E
B D E F
K K
B D E
B D E F
D E
B D E F
C
C
D E
IB C CA B
B D E F
D E
B D E F
C
B H
C
I
E B D
IF
B H
C E
A D F
D E
EB D
E B
DB
LD E
EB C
L
L B C
D E
C I
B B
B C
EC D
F
I
B C
D E
D
EE
B D L
A B D E
D E
B C
B CB C
A
E B
D
D E
C
D E D E
CA B
B A B
D E
D E
A B D E
C
C D E
D E
E A B
D
C
E B
D F
E A B
D
D E
D E B
C
C
B L
B I
B
D B C
E
IB C
C
EC D
B B
B
E A B D
CA B
D
I B
G
B I
DA B E ED
C CA
C D
E C
A C
A C
B
C
BA
C C
B
AA
F
C A
C
CA
C
A
A I
C
BA
C
A B D E
C
C
F I
D E C
D E C
C C
C
A
A
A
A
A C
E
I
IC
A C
A C
E A B D
C E
A B D
C A C A C F
A C
P
I
A
A C
A
G B C B C
C
C
A C
A
A C
C
C
C
B A
C C
C
A B
CA
A
C
CA
A C
RH Q
RH Q
RH Q
RH Q
L O
N
N
229 ED P
C
E B C
D A
C
D
D
D
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
5-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BVG NC
9H-HA102
KEY PLAN
NOT TO SCALE
F1
BUILDING 9H - FIRST FLOOR
SCALE: 3/32" = 1'-0"
F1
HAZARDOUS MATERIALS
BUILDING 9H - FIRST FLOOR
9H
ASBESTOS CONTAINING MATERIALS DESIGNATION -
A. FLOOR TILE (VARIOUS SIZES AND COLORS)
B. BLACK FLOOR TILE MASTIC
C. WHITE PIPE SEAM SEALANT
D. WINDOW GLAZING
E. EXTERIOR WINDOW CAULKING
F. FIRE DOOR
G. CARDBOARD PIPE INSULATION
H. EXTERIOR STUCCO
I. WHITE DUCT SEAM SEALANT (ON FIBERGLASS INSULATION)
J. CLOTH VIBRATION ISOLATOR
K. WHITE DUCT MASTIC ON METAL
L. YELLOW CARPET MASTIC
M. BROWN CEILING TILE MASTIC DOTS
N. ELEVATOR DOOR AND CAB INSULATION
O. RED FLOOR LEVELING COMPOUND
P. BUILT UP ROOFING
Q. EXTERIOR VENT CAULK
R. EXTERIOR DOOR CAULK
S. GRAY METAL DUCT SEAM SEALANT
T. GRAY LOUVER CAULK
U. ROOF SHINGLES
ASBESTOS CONTAINING MATERIAL NOTES
1. ALL OF THE ACMS DEPICTED ON THE DRAWINGS WILL REQUIRE ABATEMENT. PLEASE REFER TO THE HAZARDOUS MATERIALS REPORT AND ASBESTOS ABATEMENT SPECIFICATION SECTION 02 82 13.41. DEMOLITION MUST OCCUR TO EXPOSE PIPE AND DUCT INSULATION WITHIN WALLS AND ABOVE CEILINGS FOR ABATEMENT.
2.ALL ASBESTOS ABATEMENT WILL BE PERFORMED WITHIN FULL NEGATIVE PRESSURE ENCLOSURES.
3.THE EXTERIOR STUCCO ON THE BUILDING IS ASBESTOS CONTAINING AND WILL NEED TO BE ABATED PRIOR TO
THE DEMOLITION OF THE BUILDING. THE FULL NEGATIVE PRESSURE ENCLOSURES MUST BE CONSTRUCTED IN SUCH A MANNER AS TO WITHSTAND ANY AND ALL POTENTIAL BREACHES FROM OUTDOOR FORCES (WIND, RAIN, SNOW, ICE, VANDALISM, ETC). THIS AREA MUST ALSO BE AIR TIGHT AND BE PLACED UNDER NEGATIVE PRESSURE WITH THE USE OF HEPA FILTERED NEGATIVE AIR MACHINES, CAPABLE OF PROVIDING -0.02 INCHES OF
WATER OF NEGATIVE PRESSURE.
LEAD BASED NOTES
1.THE FOLLOWING SURFACES WERE FOUND TO HAVE LEAD BASED PAINT:
· METAL WINDOW FRAME SYSTEMS
· WOOD TRANSOMS
· TERRACOTTA WALLS
· METAL CORNER GUARDS
· WOOD WINDOW FRAME SYSTEMS
· METAL HANDRAILS
· CONCRETE WINDOW SILLS
· STRUCTURAL STEEL
· METAL CAGE DOORS
· METAL TANK
· METAL VENTS
· METAL DOOR FRAME SYSTEMS
· CONCRETE RISERS
· CERAMIC SLOP SINK
· PLASTER CEILINGS AND WALLS
· METAL STALL DOOR
· METAL LOCKERS
· METAL STAIR SYSTEMS
· WOOD DOOR SYSTEM
· WOOD COLUMNS
2. LEAD ABATEMENT IS NOT REQUIRED FOR THIS PROJECT. HOWEVER, OSHA'S LEAD IN CONSTRUCTION STANDARD APPLIES TO ALL DISTURBANCE OF LEAD BASED PAINT. IN ADDITION, THE CONTRACTOR SHALL USE METHODS TO LIMIT THE AMOUNT OF DUST PRODUCED DURING DEMOLITION OF ANY COMPONENT WITH LEAD PAINT. THE WASTE STREAM (MATERIALS NOT GOING TO BE RECYCLED) WILL REQUIRE TCLP SAMPLES TO DETERMINE IF THE WASTE IS HAZARDOUS FOR DISPOSAL. THIS SAMPLING IS TO BE COMPLETED BY THE
DEMOLITION CONTRACTOR.
OTHER IDENTIFIED HAZARDOUS MATERIALS NOTES
1. APPROXIMATELY 1,105 MERCURY VAPOR LAMPS WERE OBSERVED THROUGHOUT THE BUILDINGS. REMOVAL AND DISPOSAL AS A UNIVERSAL WASTE FOR MERCURY CONTAINING LAMPS UNDER THE RESOURCE CONSERVATION
AND RECOVERY ACT SHALL OCCUR PRIOR TO THE DEMOLITION.
2.RANDOMLY SELECTED LIGHTING BALLASTS WERE CHECKED AND ALL HAD "NO PCBS" LABELS. ALL BALLASTS MUST BE REMOVED AND CHECKED FOR THESE LABELS BY THE DEMOLITION CONTRACTOR AND DISPOSED OF
PROPERLY.
3.THE DEMOLITION CONTRACTOR MUST CHECK ALL EXIST SIGNS FOR BATTERIES OR TRITIUM AND DISPOSE OF
THESE SIGNS AS REQUIRED BY THE EPA.
4.THIRTY THREE WINDOW AIR CONDITIONING UNITS WERE OBSERVED WITHIN BUILDING 9H. THESE UNITS ARE LIKELY TO HAVE REFRIGERANTS THAT WILL NEED TO BE REMOVED PROPERLY UNDER THE EPA REGULATIONS (40
CFR PART 82, SUBPART F) UNDER SECTION 608 OF THE CLEAN AIR ACT.
124 125 126
127 133
148 146
145 143
139 137
136134
156157
192191
182 180
179177
209 210
B
E B D
LD E EB D D E
DA B
E
C
DA B
E
C
EB D
B
B
EB D
D E
LB E
EB DBL
B
E
ED
DA B
E
DA B
E
D E
E B D
EB D
D E
DA B
E
D E
L
ED
C
CB
L I
MD E
EB D
L M
E A
D B
EB D
D E
D E
B
B C
C L
EB D
B
DA B
E
ND E
EB D
C
B L
E D
DA B
E
C
E B
D
C D E
EB D
C
EC D
E B D
B
B
A B
EA D
EB D
L
EB D
L
C
B
D A B
E I
C A B
D E I
CA B
D E I
B D E F
EB D
F I
EB D
F I
EB D F
D E L M
D E I M
B M
B D E M
B D E
D E
D E M
EB D
I M
ED
B D E M
C I
B I M
E
C
D
193A
A
RH Q
A
C D E
A
C
A F
A
BA
A C
A
A
D EC
A
F
BA
B
A
D EC
A
F B
D A
A
C
C
M
B
A B F M
A
A
A
A
A
A
A F
A
A
A A
A
C
A
A
A C A A
A
CC
A
A
RH Q
RH Q
N
N
E B
D A
CA B
D E I
D
D
D D
EE
E
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
5-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BVG NC
9H-HA103
KEY PLAN
NOT TO SCALE
F1
BUILDING 9H - SECOND FLOOR
SCALE: 3/32" = 1'-0"
F1
HAZARDOUS MATERIALS
BUILDING 9H - SECOND FLOOR
9H
ASBESTOS CONTAINING MATERIALS DESIGNATION -
A. FLOOR TILE (VARIOUS SIZES AND COLORS)
B. BLACK FLOOR TILE MASTIC
C. WHITE PIPE SEAM SEALANT
D. WINDOW GLAZING
E. EXTERIOR WINDOW CAULKING
F. FIRE DOOR
G. CARDBOARD PIPE INSULATION
H. EXTERIOR STUCCO
I. WHITE DUCT SEAM SEALANT (ON FIBERGLASS INSULATION)
J. CLOTH VIBRATION ISOLATOR
K. WHITE DUCT MASTIC ON METAL
L. YELLOW CARPET MASTIC
M. BROWN CEILING TILE MASTIC DOTS
N. ELEVATOR DOOR AND CAB INSULATION
O. RED FLOOR LEVELING COMPOUND
P. BUILT UP ROOFING
Q. EXTERIOR VENT CAULK
R. EXTERIOR DOOR CAULK
S. GRAY METAL DUCT SEAM SEALANT
T. GRAY LOUVER CAULK
U. ROOF SHINGLES
ASBESTOS CONTAINING MATERIAL NOTES
1. ALL OF THE ACMS DEPICTED ON THE DRAWINGS WILL REQUIRE ABATEMENT. PLEASE REFER TO THE HAZARDOUS MATERIALS REPORT AND ASBESTOS ABATEMENT SPECIFICATION SECTION 02 82 13.41. DEMOLITION MUST OCCUR TO EXPOSE PIPE AND DUCT INSULATION WITHIN WALLS AND ABOVE CEILINGS FOR ABATEMENT.
2.ALL ASBESTOS ABATEMENT WILL BE PERFORMED WITHIN FULL NEGATIVE PRESSURE ENCLOSURES.
3.THE EXTERIOR STUCCO ON THE BUILDING IS ASBESTOS CONTAINING AND WILL NEED TO BE ABATED PRIOR TO
THE DEMOLITION OF THE BUILDING. THE FULL NEGATIVE PRESSURE ENCLOSURES MUST BE CONSTRUCTED IN SUCH A MANNER AS TO WITHSTAND ANY AND ALL POTENTIAL BREACHES FROM OUTDOOR FORCES (WIND, RAIN, SNOW, ICE, VANDALISM, ETC). THIS AREA MUST ALSO BE AIR TIGHT AND BE PLACED UNDER NEGATIVE PRESSURE WITH THE USE OF HEPA FILTERED NEGATIVE AIR MACHINES, CAPABLE OF PROVIDING -0.02 INCHES OF
WATER OF NEGATIVE PRESSURE.
LEAD BASED NOTES
1.THE FOLLOWING SURFACES WERE FOUND TO HAVE LEAD BASED PAINT:
· METAL WINDOW FRAME SYSTEMS
· WOOD TRANSOMS
· TERRACOTTA WALLS
· METAL CORNER GUARDS
· WOOD WINDOW FRAME SYSTEMS
· METAL HANDRAILS
· CONCRETE WINDOW SILLS
· STRUCTURAL STEEL
· METAL CAGE DOORS
· METAL TANK
· METAL VENTS
· METAL DOOR FRAME SYSTEMS
· CONCRETE RISERS
· CERAMIC SLOP SINK
· PLASTER CEILINGS AND WALLS
· METAL STALL DOOR
· METAL LOCKERS
· METAL STAIR SYSTEMS
· WOOD DOOR SYSTEM
· WOOD COLUMNS
2. LEAD ABATEMENT IS NOT REQUIRED FOR THIS PROJECT. HOWEVER, OSHA'S LEAD IN CONSTRUCTION STANDARD APPLIES TO ALL DISTURBANCE OF LEAD BASED PAINT. IN ADDITION, THE CONTRACTOR SHALL USE METHODS TO LIMIT THE AMOUNT OF DUST PRODUCED DURING DEMOLITION OF ANY COMPONENT WITH LEAD PAINT. THE WASTE STREAM (MATERIALS NOT GOING TO BE RECYCLED) WILL REQUIRE TCLP SAMPLES TO DETERMINE IF THE WASTE IS HAZARDOUS FOR DISPOSAL. THIS SAMPLING IS TO BE COMPLETED BY THE
DEMOLITION CONTRACTOR.
OTHER IDENTIFIED HAZARDOUS MATERIALS NOTES
1. APPROXIMATELY 1,105 MERCURY VAPOR LAMPS WERE OBSERVED THROUGHOUT THE BUILDINGS. REMOVAL AND DISPOSAL AS A UNIVERSAL WASTE FOR MERCURY CONTAINING LAMPS UNDER THE RESOURCE CONSERVATION
AND RECOVERY ACT SHALL OCCUR PRIOR TO THE DEMOLITION.
2.RANDOMLY SELECTED LIGHTING BALLASTS WERE CHECKED AND ALL HAD "NO PCBS" LABELS. ALL BALLASTS MUST BE REMOVED AND CHECKED FOR THESE LABELS BY THE DEMOLITION CONTRACTOR AND DISPOSED OF
PROPERLY.
3.THE DEMOLITION CONTRACTOR MUST CHECK ALL EXIST SIGNS FOR BATTERIES OR TRITIUM AND DISPOSE OF
THESE SIGNS AS REQUIRED BY THE EPA.
4.THIRTY THREE WINDOW AIR CONDITIONING UNITS WERE OBSERVED WITHIN BUILDING 9H. THESE UNITS ARE LIKELY TO HAVE REFRIGERANTS THAT WILL NEED TO BE REMOVED PROPERLY UNDER THE EPA REGULATIONS (40
CFR PART 82, SUBPART F) UNDER SECTION 608 OF THE CLEAN AIR ACT.
C I
C I
C I
C I
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
5-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BVG NC
9H-HA104
KEY PLAN
NOT TO SCALE
F1
BUILDING 9H - ATTIC
SCALE: 3/32" = 1'-0"
F1
HAZARDOUS MATERIALS
BUILDING 9H - ATTIC
9H
ASBESTOS CONTAINING MATERIALS DESIGNATION -
A. FLOOR TILE (VARIOUS SIZES AND COLORS)
B. BLACK FLOOR TILE MASTIC
C. WHITE PIPE SEAM SEALANT
D. WINDOW GLAZING
E. EXTERIOR WINDOW CAULKING
F. FIRE DOOR
G. CARDBOARD PIPE INSULATION
H. EXTERIOR STUCCO
I. WHITE DUCT SEAM SEALANT (ON FIBERGLASS INSULATION)
J. CLOTH VIBRATION ISOLATOR
K. WHITE DUCT MASTIC ON METAL
L. YELLOW CARPET MASTIC
M. BROWN CEILING TILE MASTIC DOTS
N. ELEVATOR DOOR AND CAB INSULATION
O. RED FLOOR LEVELING COMPOUND
P. BUILT UP ROOFING
Q. EXTERIOR VENT CAULK
R. EXTERIOR DOOR CAULK
S. GRAY METAL DUCT SEAM SEALANT
T. GRAY LOUVER CAULK
U. ROOF SHINGLES
ASBESTOS CONTAINING MATERIAL NOTES
1. ALL OF THE ACMS DEPICTED ON THE DRAWINGS WILL REQUIRE ABATEMENT. PLEASE REFER TO THE HAZARDOUS MATERIALS REPORT AND ASBESTOS ABATEMENT SPECIFICATION SECTION 02 82 13.41. DEMOLITION MUST OCCUR TO EXPOSE PIPE AND DUCT INSULATION WITHIN WALLS AND ABOVE CEILINGS FOR ABATEMENT.
2.ALL ASBESTOS ABATEMENT WILL BE PERFORMED WITHIN FULL NEGATIVE PRESSURE ENCLOSURES.
3.THE EXTERIOR STUCCO ON THE BUILDING IS ASBESTOS CONTAINING AND WILL NEED TO BE ABATED PRIOR TO
THE DEMOLITION OF THE BUILDING. THE FULL NEGATIVE PRESSURE ENCLOSURES MUST BE CONSTRUCTED IN SUCH A MANNER AS TO WITHSTAND ANY AND ALL POTENTIAL BREACHES FROM OUTDOOR FORCES (WIND, RAIN, SNOW, ICE, VANDALISM, ETC). THIS AREA MUST ALSO BE AIR TIGHT AND BE PLACED UNDER NEGATIVE PRESSURE WITH THE USE OF HEPA FILTERED NEGATIVE AIR MACHINES, CAPABLE OF PROVIDING -0.02 INCHES OF
WATER OF NEGATIVE PRESSURE.
LEAD BASED NOTES
1.THE FOLLOWING SURFACES WERE FOUND TO HAVE LEAD BASED PAINT:
· METAL WINDOW FRAME SYSTEMS
· WOOD TRANSOMS
· TERRACOTTA WALLS
· METAL CORNER GUARDS
· WOOD WINDOW FRAME SYSTEMS
· METAL HANDRAILS
· CONCRETE WINDOW SILLS
· STRUCTURAL STEEL
· METAL CAGE DOORS
· METAL TANK
· METAL VENTS
· METAL DOOR FRAME SYSTEMS
· CONCRETE RISERS
· CERAMIC SLOP SINK
· PLASTER CEILINGS AND WALLS
· METAL STALL DOOR
· METAL LOCKERS
· METAL STAIR SYSTEMS
· WOOD DOOR SYSTEM
· WOOD COLUMNS
2. LEAD ABATEMENT IS NOT REQUIRED FOR THIS PROJECT. HOWEVER, OSHA'S LEAD IN CONSTRUCTION STANDARD APPLIES TO ALL DISTURBANCE OF LEAD BASED PAINT. IN ADDITION, THE CONTRACTOR SHALL USE METHODS TO LIMIT THE AMOUNT OF DUST PRODUCED DURING DEMOLITION OF ANY COMPONENT WITH LEAD PAINT. THE WASTE STREAM (MATERIALS NOT GOING TO BE RECYCLED) WILL REQUIRE TCLP SAMPLES TO DETERMINE IF THE WASTE IS HAZARDOUS FOR DISPOSAL. THIS SAMPLING IS TO BE COMPLETED BY THE
DEMOLITION CONTRACTOR.
PANEL "GB 344"
GEN.
200KW/
250KVA.
AT 0.8PF.
GEN. SWGR. 6
EMERGENCY POWER DISCONNECT TO BLDG 9H
CABLE TRAY FOR
EMERGENCY POWER
DIESEL DAY TANK
CONTROL PANEL
PRIMARY POWER SWITCH FOR BLDG 9H
500KVA TRANSFORMER SUBSTATION "SS-6"
NORMAL POWER
DISCONNECT TO BLDG 9H
FIRE ALARM
CONTROL PANEL
MUFFLER
DUAL 3ɸ FEEDERS (NORMAL)
TO 12-DUCT BANK TO BLDG 9H
SOUND
CASING
DUAL 3ɸ FEEDERS (EMERGENCY)
TO 12-DUCT BANK TO BLDG 9H
4160V PRIMARY FEEDER
FROM MANHOLE E45
EXHAUST
S T U
S T U
S T U S T
U
S T U
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
5-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
BVG NC
344-HA105
KEY PLAN
NOT TO SCALE
F1
BUILDING 344
SCALE: 1/4" = 1'-0"
F1
HAZARDOUS MATERIALS
BUILDING 344
ASBESTOS CONTAINING MATERIALS DESIGNATION -
A. FLOOR TILE (VARIOUS SIZES AND COLORS)
B. BLACK FLOOR TILE MASTIC
C. WHITE PIPE SEAM SEALANT
D. WINDOW GLAZING
E. EXTERIOR WINDOW CAULKING
F. FIRE DOOR
G. CARDBOARD PIPE INSULATION
H. EXTERIOR STUCCO
I. WHITE DUCT SEAM SEALANT (ON FIBERGLASS INSULATION)
J. CLOTH VIBRATION ISOLATOR
K. WHITE DUCT MASTIC ON METAL
L. YELLOW CARPET MASTIC
M. BROWN CEILING TILE MASTIC DOTS
N. ELEVATOR DOOR AND CAB INSULATION
O. RED FLOOR LEVELING COMPOUND
P. BUILT UP ROOFING
Q. EXTERIOR VENT CAULK
R. EXTERIOR DOOR CAULK
S. GRAY METAL DUCT SEAM SEALANT
T. GRAY LOUVER CAULK
U. ROOF SHINGLES
ASBESTOS CONTAINING MATERIAL NOTES
1. ALL OF THE ACMS DEPICTED ON THE DRAWINGS WILL REQUIRE ABATEMENT. PLEASE REFER TO THE HAZARDOUS MATERIALS REPORT AND ASBESTOS ABATEMENT SPECIFICATION SECTION 02 82 13.41. DEMOLITION MUST OCCUR TO EXPOSE PIPE AND DUCT INSULATION WITHIN WALLS AND ABOVE CEILINGS FOR ABATEMENT.
2.ALL ASBESTOS ABATEMENT WILL BE PERFORMED WITHIN FULL NEGATIVE PRESSURE ENCLOSURES.
3.THE EXTERIOR STUCCO ON THE BUILDING IS ASBESTOS CONTAINING AND WILL NEED TO BE ABATED PRIOR TO
THE DEMOLITION OF THE BUILDING. THE FULL NEGATIVE PRESSURE ENCLOSURES MUST BE CONSTRUCTED IN SUCH A MANNER AS TO WITHSTAND ANY AND ALL POTENTIAL BREACHES FROM OUTDOOR FORCES (WIND, RAIN, SNOW, ICE, VANDALISM, ETC). THIS AREA MUST ALSO BE AIR TIGHT AND BE PLACED UNDER NEGATIVE PRESSURE WITH THE USE OF HEPA FILTERED NEGATIVE AIR MACHINES, CAPABLE OF PROVIDING -0.02 INCHES OF
WATER OF NEGATIVE PRESSURE.
OTHER IDENTIFIED HAZARDOUS MATERIALS NOTES
1. AN ABOVE GROUND STORAGE TANK WITH FUEL OIL EXISTS WITHIN BUILDING 344. CONTRACTOR MUST FOLLOW ALL EPA, MDE, AND LOCAL REGULATIONS FOR THE CONTAINMENT, REMOVAL, AND DISPOSAL OF THE FUEL OIL.
DECIDUOUS TREE FIRE HYDRANT
WATER VALVE WATER METER
SD INLET
UNKNOWN MANHOLE
HANDICAPPED PARKING
UTILITY PEDESTAL
SPOT GRADE
CORNER FOUND
ANGLE BREAK
SANITARY SEWER
STORMDRAIN
METAL FENCE
WOOD FENCE
GUARDRAIL
OVERHEAD LINES
WOODS LINE
BLDG HEIGHT= VERTICAL HEIGHT OF WALL ABOVE ADJACENT GROUND
INLET TOP ELEVATION: 25.57'
6" STEEL: 22.32'
12" RCP: 21.92'
INLET TOP ELEVATION: 25.90'
12"RCP: 18.90'
4" PVC: 19.15'
10" TERRA: 18.88'
INLET TOP ELEVATION: 27.05'
12" RCP: 22.95'
8" TERRA: 21.90'
INLET TOP ELEVATION: 27.19'
8" TERRA: 21.69'
8" TERRA: 21.64'
INLET TOP ELEVATION: 24.51'
12" TERRA: 18.56'
12" TERRA: 15.91'
MANHOLE TOP ELEVATION: 24.27'
DROP 12" TERRA: 18.30'
15" TERRA/STEEL: 14.24'
12" TERRA: 13.3'
15"TERRA/STEEL: 13.29'
15" TERRA/STEEL: 13.24'
MANHOLE TOP ELEVATION: 24.62'
24" TERRA: 18.97'
12" TERRA: 18.90'
MANHOLE TOP ELEVATION: 24.67'
24" TERRA: 19.15'
INLET TOP ELEVATION: 24.21'
10" RCP: 21.71'
INLET TOP ELEVATION: 24.21'
10" RCP: 21.46'
INLET TOP ELEVATION: 25.24'
FILLED WITH DEBRIS
INLET TOP ELEVATION: 25.34'
15" STEEL: 20.39'
15" RCP: 20.34'
MANHOLE TOP ELEVATION: 25.90'
12" RCP: 22.10'
12" RCP: 21.99'
MANHOLE TOP ELEVATION: 26.25'
10" TERRA: 22.30'
8" TERRA: 21.95'
20" TERRA: 21.25'
20" TERRA: 21.25'
SANITARY MANHOLE TOP ELEVATION: 26.38'
DROP INVERT: 18.36'
DROP INVERT: 17.94'
8" PVC: 14.72'
12" PVC: 14.70'
12" PVC: 14.65'
12" PVC: 14.53'
SANITARY MANHOLE TOP ELEVATION: 26.97'
8" PVC: 16.58'
8" PVC: 16.56'
SANITARY MANHOLE TOP ELEVATION: 25.79'
15" TERRA: 17.04'
INV: 16.81'
15" TERRA: 16.68'
15" TERRA: 16.67'
MANHOLE TOP ELEVATION: 27.33'
INACCESSIBLE AT TIME OF SURVEY
MANHOLE TOP ELEVATION: 26.18'
BOLTED SHUT
SANITARY MANHOLE TOP ELEVATION: 26.81'
WATER IN BOTTOM WITH NO PIPES VISIBLE
MANHOLE TOP ELEVATION: 26.15'
BOLTED SHUT
INLET TOP ELEVATION: 27.17'
INV: 18.52'
INV: 18.47'
RAMP
PORTICO
CONCRETE SIDEWALK
EXISTINGPAVING
SHED
UTILITY MANHOLE (TYP.)
STAIRCASE
RAM
P
CONCRETE SIDEWALK
CONCRETEPAD
SU
NROOM
EN
CLO
SE
D
PE
DWAY
CONCRETE
EXISTING
PAVING
AS
PH
AL
T
LO
T CO (T
YP
EMERGENCY
TELEPHONE
RAIS
ED
PA
TIO
: 4
AG
L
SL
IT
GRAT
E
DRAIN
FF ELEV: 27.95'
FF ELEV: 21.28'
FF ELEV: 21.68'
FF ELEV: 27.88'
RAIS
ED
PA
TIO
: 5
AG
L
AVENUE D
EIGHTH
STREET
FWA TRAVERSE POINT 29003
N: 687169.1395 E: 1577015.6747
FWA TRAVERSE POINT 29002
N: 686887.4332 E: 1577020.9905
FWA TRAVERSE POINT 29001
N: 686918.0160 E: 1577453.3463
FWA TRAVERSE POINT 29000
N: 686724.3410 E: 1577306.9380
INLET TOP ELEVATION: 26.10'
6" PVC: 22.8'
MANHOLE TOP ELEVATION: 27.82'
DROP 8" TERRA: 18.07'
12" PVC: 17.67'
12" PVC: 17.62'
INLET TOP ELEVATION: 23.79'
DROP 8" TERRA: 19.19'
15" TERRA/STEEL: 12.74'
15" TERRA/STEEL: 12.74'
INLET TOP ELEVATION: 27.07'
12" RCP: 23.65'
SANITARY MANHOLE TOP ELEVATION: 28.13'
6" TERRA: 23.58'
6" TERRA: 23.32'
SIDEWALK
BU
ILD
ING
OVE
RHAN
G
MET
AL
FE
NCE
LIN
E BL
DG 31
4C
2x2 INLET
2x2 INLET
2x2 INLET
2x2
INLET
2x2 INLET
2x2 INLET
2x2 INLET
2x2 INLET ROUND
NV WEIR
NV WEIR
2x2 INLET 2x2 INLET 2x2 INLET
BLDG 9H
BL
DG 34
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
TOPOGRAPHICAL SURVEY
SCALE: 1/32" = 1'
F1
NOTE:
1. THIS DOCUMENT IS AN INSTRUMENT OF SERVICE OF FREDERICK WARD ASSOCIATES. IT IS ISSUED TO WEST POINT
ENGINEERS FOR PURPOSES RELATED DIRECTLY AND SOLELY TO FREDERICK WARD ASSOCIATES'S SCOPE OF SERVICES UNDER CONTRACT WITH WEST POINT ENGINEERS FOR EXISTING CONDITIONS OF PERRY POINT VA MEDICAL CENTER, BUILDINGS 9H AREA. ANY USE OR REUSE OF THIS DOCUMENT FOR ANY REASON BY ANY PARTY FOR PURPOSES UNRELATED DIRECTLY AND SOLELY TO SAID CONTRACT AND PROJECT SHALL BE AT THE USER'S SOLE AND EXCLUSIVE RISK AND LIABILITY, INCLUDING LIABILITY FOR VIOLATION OF COPYRIGHT LAWS, UNLESS WRITTEN AUTHORIZATION IS GIVEN THEREFOR BY
FREDERICK WARD ASSOCIATES.
2. THE PURPOSE OF THIS PLAN IS TO SHOW EXISTING CONDITIONS AS THE RESULT OF AN ON-THE-GROUND INSTRUMENT
SURVEY WHICH OCCURRED JULY, 2023 AND AUGUST, 2023.
3. HORIZONTAL BEARINGS REFER TO MARYLAND STATE PLANE COORDINATE SYSTEM (NAD83) BASED ON GPS OBSERVATIONS.
4. ELEVATION REFERS TO NORTH AMERICAN VERTICAL DATUM (NAVD88) VERTICAL BASED ON GPS OBSERVATIONS.
UTILITY INFORMATION STATEMENT
1. THE SUB-SURFACE UTILITY INFORMATION SHOWN HEREON IS COMPILED
BASED ON FIELD SURVEY INFORMATION, RECORD INFORMATION AS
SUPPLIED BY THE APPROPRIATE UTILITY COMPANIES, AND PLAN
INFORMATION SUPPLIED BY THE CLIENT, IF ANY; THEREFORE WE CANNOT
GUARANTEE THE ACCURACY OF SAID COMPILED SUB-SURFACE
INFORMATION TO ANY CERTAIN DEGREE OF STATED TOLERANCE. ONLY
PHYSICALLY LOCATED SUB-SURFACE UTILITY FEATURES FALL WITHIN
NORMAL STANDARD OF CARE ACCURACIES.
2. THE LOCATIONS OF UNDERGROUND PIPES, CONDUITS, AND STRUCTURES
HAVE BEEN DETERMINED FROM SAID INFORMATION, AND ARE APPROXIMATE
ONLY. COMPILED LOCATIONS OF ANY UNDERGROUND STRUCTURES, NOT
VISIBLY OBSERVED AND LOCATED, CAN VARY FROM THEIR ACTUAL
LOCATIONS.
3. ADDITIONAL BURIED UTILITIES/STRUCTURES MAY BE ENCOUNTERED.
4. THE STATUS OF UTILITIES, WHETHER ACTIVE, ABANDONED, OR REMOVED,
IS AN UNKNOWN CONDITION AS FAR AS OUR COMPILATION OF THIS
INFORMATION.
5. IT IS INCUMBENT UPON INDIVIDUALS USING THIS INFORMATION TO
UNDERSTAND THAT COMPILING UTILITY INFORMATION IS NOT EXACT, AND IS
SUBJECT TO CHANGE BASED UPON VARYING PLAN INFORMATION RECEIVED
AND ACTUAL LOCATIONS.
6. THE ACCURACY OF MEASURED UTILITY INVERTS AND PIPE SIZES IS
SUBJECT TO FIELD CONDITIONS, THE ABILITY TO MAKE VISUAL
OBSERVATIONS, DIRECT ACCESS TO THE VARIOUS ELEMENTS AND OTHER
MATTERS.
7. THE PROPER UTILITY ENGINEERING/COMPANY SHOULD BE CONSULTED
AND THE ACTUAL LOCATIONS OF SUBSURFACE STRUCTURES SHOULD BE
VERIFIED IN THE FIELD (V.I.F.) BEFORE PLANNING FUTURE CONNECTIONS.
CONTACT THE DIG SAFE CALL CENTER AT 1-888-344-7233, SEVENTY-TWO
HOURS PRIOR TO EXCAVATION, BLASTING, GRADING, AND/OR PAVING.
TOPOGRAPHICAL SURVEY PERFORMED BY FREDERICK WARD ASSOCIATES, DATED 25-OCT-2023.
THIS SURVEY WAS NOT PREFORMED BY WEST POINT ENGINEERS. THIS SURVEY WAS PROVIDED
TO WEST POINT ENGINEERS FOR BACKGROUND INFORMATION PURPOSES FOR THIS PROJECT
BY THE DEPARTMENT OF VETERANS AFFAIRS. WEST POINT ENGINEERS IS NOT A LICENSED
SURVEY COMPANY.
N
VU101
SCMBVG
SITE PLAN - TOPOGRAPHICAL SURVEY
DECIDUOUS TREE FIRE HYDRANT
WATER VALVE WATER METER
SD INLET
UNKNOWN MANHOLE
HANDICAPPED PARKING
UTILITY PEDESTAL
SPOT GRADE
CORNER FOUND
ANGLE BREAK
SANITARY SEWER
STORMDRAIN
METAL FENCE
WOOD FENCE
GUARDRAIL
OVERHEAD LINES
WOODS LINE
BLDG HEIGHT= VERTICAL HEIGHT OF WALL ABOVE ADJACENT GROUND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
GENERAL CIVIL NOTES
A. REFER TO CIVIL EXISTING, DEMOLITION, EROSION CONTROL, NEW WORK, GRADING, AND UTILITIES PLANS AND DETAILS FOR
LOCATIONS OF INFORMATION ON THIS SHEET.
B. COORDINATE ALL WORK WITH EXISTING CONDITIONS, ALL OTHER TRADES, AND IN ACCORDANCE WITH ALL STATE, LOCAL AND
NATIONAL CODES, AS WELL AS WITH ALL FEDERAL HEALTHCARE REGULATIONS.
C. CONTRACTOR IS RESPONSIBLE FOR ALL FEES, PERMITS AND LICENSES FOR THE COMPLETE INSTALLATION OF THEIR WORK.
D. BEFORE ANY WORK IS STARTED, MAKE A THOROUGH SURVEY WITH THE COR IN WHICH ALTERATIONS OCCUR AND AREAS WHICH ARE ANTICIPATED ROUTES OF ACCESS, AND FURNISH A REPORT. REPORT WILL BE SIGNED BY BOTH COR AND CONTRACTOR, AND WILL BE
PROVIDED TO THE CONTRACTING OFFICER.
E. CARE SHOULD BE TAKEN BY ALL CONTRACTORS TO AVOID DAMAGING OR DISTURBING EXISTING CONSTRUCTION WHICH IS TO REMAIN.
CONTRACTOR IS RESPONSIBLE FOR MAKING ANY REPAIRS NECESSARY TO RECTIFY DAMAGES AND RESTORE EXISTING
CONSTRUCTION TO UNDAMAGED STATE UPON COMPLETION OF WORK AT NO EXPENSE TO OWNER.
F. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL ASBESTOS ABATEMENT ASSOCIATED WITH NEW AND DEMOLITION WORK.
G. ALL EXISTING UNDERGROUND UTILITIES TO REMAIN BUT EXPOSED TO CONSTRUCTION/DEMOLITION ACTIVITIES ON ADJACENT
UTILITIES ARE TO BE PROTECTED FROM DAMAGE DURING ADJACENT WORK.
H. DOCUMENTATION:
PROVIDE ELECTRONIC COPIES OF TECHNICAL MANUALS, AS-BUILT DRAWINGS, AND MANUFACTURER'S OPERATION AND MAINTENANCE
MANUALS TO THE COR.
EXISTING BOLLARD GUARD POST
TEMPORARY FENCING AND BARRICADES FOR SITE PROTECTION AND STAGING
DURING CONSTRUCTION
SAMP SAMPLE
SAN SANITARY
SB SPLASH BLOCK
SCHED SCHEDULE
SCP SCUPPER
SD STORM DRAIN
SDL SADDLE
SDMH STORM DRAIN MANHOLE
SECT SECTION
SEG SEGMENT
SEL SELECT
SEP SEPARATE
SEP TNK SEPTIC TANK
SF SQUARE FOOT (FEET)
SHLDR SHOULDER
SJ SCORED JOINT
SLV SLEEVE
SMH STEAM MANHOLE
SMP SUMP PUMP
SP STANDPIPE OR SUMP PIT
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SPKLR SPRINKLER
SPLY SUPPLY
SPR SPRINKLER LINE
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SR STEAM RETURN
SS SANITARY SEWER, STEAM SUPPLY, OR STORM
SEWER
SSP STAINLESS STEEL PIPE
SST STAINLESS STEEL
ST STREET
ST W STORM WATER
STA STATION
STD STANDARD
STIR STIRRUP
STM STEAM
SUCT SUCTION
SUPT SUPPORT
SURF SURFACE
SURV SURVEY
SUTK SUMP TANK
SW SIDEWALK
SWG SEWAGE
SWR SEWER
SYM SYMBOL
T&M TIME AND MATERIALS
TAN TANGENT
TBM TEMPORARY BENCHMARK
TB-XX TEST BORING-XX (E.G., TB-01)
TC TOP OF CURB
TCP TRAFFIC CONTROL PLAN
TD TRENCH DRAIN
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPORARY
TG TOP OF GRATE
THK THICKNESS
THRU THROUGH
TMH TOP OF MANHOLE
TN TRUE NORTH
TNL TUNNEL
TO FDN TOP OF FOUNDATION
TOB TOP OF BEAM
TOC TOP OF CONCRETE OR TOP OF CURB
TOF TOP OF FOOTING
TOP TOP OF PAVEMENT
TOPO TOPOGRAPHY
TOS TOP OF STEP
TOW TOP OF WALL
TP TELEPHONE POLE
TR TOP OF RIM
TWR TREATED WATER RETURN
TWS TREATED WATER SUPPLY
TYP TYPICAL
UFC UNIFORM FIRE CODE
U/G UNDERGROUND
UGE UNDERGROUND ELECTRICAL
UGND UNDERGROUND
UNFIN UNFINISH
UNPV RD UNPAVED ROAD
UON UNLESS OTHERWISE NOTED
UP UTILITY POLE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
VA VETERANS AFFAIRS
VAR VARIES
VB VALVE BOX
VC VERTICAL CURVE
VCT VITRIFIED CLAY TILE VINYL COMPOSITION TILE
VERT VERTICAL
VIC VICINITY
VID VIDEO
VIF VERIFY IN FIELD
VOL VOLUME
W WASTE, WEST, OR WATER LINE
W/ WITH
W/O WITHOUT
WALK WALKWAY OR SIDEWALK
WI WROUGHT IRON
WL WATER LINE
WLD WELDED
WM WATER METER WIRE MESH
WM WIRE MESH WATER METER
WO WORK ORDER
WP WATER PUMP
WT WATER TABLE
WT EL WATER ELEVATION
WTR WATER
WW WASTE WATER
WW WASTE WATER WARM WHITE; WIREWAY
XFMR TRANSFORMER
YD YARD DRAIN
(D) EXISTING ITEM TO BE DEMOLISHED AND/OR
REMOVED
D PENNY (NAIL)
DA DRAINAGE AREA
DAT DATUM
D-B DESIGN-BUILD
DBA UNIT OF SOUND LEVEL
DBL DOUBLE
DC DEPRESSED CURB
DEG DEGREE
DEL DELETE
DEMO DEMOLITION
DEPT DEPARTMENT
DESCR DESCRIPTION
DET DETAIL
DEV DEVELOPMENT
DHW DOMESTIC HOT WATER
DI DROP INLET
DIA DIAMETER
DIAG DIAGONAL DIAGRAM
DIAG DIAGRAM DIAGONAL
DIFF DIFFERENCE OR DIFFERENTIAL
DIM DIMENSION
DIP DUCTILE IRON PIPE
DIR DIRECTION
DIST DISTANCE
DIV DIVISION
DOC DOCUMENT
DOM DOMESTIC
DOUG FIR DOUGLAS FIR
DOZ DOZEN
DR DRAIN OR DRIVE
DS DOWNSPOUT
DSBL DISABLE
DSGN DESIGN
DW DOMESTIC WATER
DWG DRAWING
DWR DOMESTIC WATER RETURN OR DRAWER
DWS DOMESTIC WATER SUPPLY
(E) EXISTING ITEM TO REMAIN
E EAST
EA EACH
EC EDGE OF CURB
EJ EXPANSION JOINT
EL EASEMENT LINE OR ELEVATION
ELEV ELEVATION
ENGR ENGINEER
ENTR ENTRANCE
EOS EDGE OF SLAB
EP EDGE OF PAVEMENT (PAVING)
EPA ENVIRONMENTAL PROTECTION AGENCY
EPT EXTERNAL PIPE THREAD
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ERD EXISTING ROOF DRAIN
ES EDGE OF SHOULDER
ESMT EASEMENT
EST ESTIMATE
EW EACH WAY
EXCL EXCLUDE
EXIST EXISTING
EXP EXPANSION
EXST GR EXISTING GRADE
EXT EXTERIOR
EXT GR EXTERIOR GRADE
F FIRE LINE
F METER FLOWMETER
F/F FACE TO FACE
FACIL FACILITY
FD FLOOR DRAIN
FFE FINISH FLOOR ELEVATION
FH FIRE HYDRANT
FIG FIGURE
FIL FILLET
FIN FINISH
FLL FLOW LINE
FLR FLOOR
FLRD FLARED
FLTR FILTER
FLUOR FLUORESCENT
FN FENCE
FOC FACE OF CURB
FP FIRE PROTECTION OR FLAGPOLE
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPW FIRE PROTECTION WATER SUPPLY
FSP FIRE STANDPIPE
FSS FLOW SENSING SWITCH
FT FEET OR FOOT
FTG FOOTING
FW FLOOD WALL
G GROUND OR NATURAL GAS
G LN GAS LINE
GA GAGE
GAL GALLON
GC GENERAL CONTRACTOR
GCO GRADE CLEANOUT
GDR GUARD RAIL
GEN GENERATOR
GI GALVANIZED IRON
GIP GALVANIZED IRON PIPE
GL GROUND LEVEL
GOVT GOVERNMENT
GPD GALLONS PER DAY
GR BM GRADE BEAM
GT GREASE TRAP
GUT GUTTER
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HANDICAP
HCP HANDICAPPED
HDPE HIGH DENSITY POLYETHYLENE
HDR HEADER
HDWL HEADWALL
HEX HEXAGON
HH HAND HOLE
HNDRL HANDRAIL
HORIZ HORIZONTAL
HP HIGH PRESSURE
HT HEIGHT
HWT HOT WATER TANK
HWY HIGHWAY
HYD HYDRANT
HYDR HYDRAULIC
ICV IRRIGATION CONTROL VALVE
ID INSIDE DIAMETER OR INSIDE DIMENSION
IMH INLET MANHOLE
INCL INCLUDED
INCR INCREMENT
INFO INFORMATION
INSTL INSTALL
INSTR INSTRUMENT
INV INVERT
INV EL INVERT ELEVATION
IP IRON PIPE
IPS IRON PIPE SIZE
IPT IRON PIPE THREADED
IRREG IRREGULAR
ISO ISOMETRIC
IW IRRIGATION WATER
KWY KEYWAY
L ANGLE
LAT LATITUDE
LF LINEAR FEET (FOOT)
LIN LINEAR
LNG LONGITUDE
LOC LOCATION
LONG LONGITUDINAL
LOS LINE OF SIGHT
LPT LOW POINT
LS LUMP SUM
LT LIGHT
LTG LIGHTING
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MAIL BOX
MED MEDIUM
MEMO MEMORANDUM
MER MERIDIAN
MFD MANUFACTURED
MFG MANUFACTURING
MGT MANAGEMENT
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML MATERIALS LIST
MN MAGNETIC NORTH
MOD MODEL OR MODIFY
MON MONUMENT
MTG MEETING
MULT MULTIPLE
MUNIC MUNICIPAL
N NORTH
NA NOT APPLICABLE
NAT NATURAL
NATL NATIONAL
NBC NATIONAL BUILDING CODE
NE NOT EXCEEDING
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NORM NORMAL
NRCP NON-REINFORCED CONCRETE PIPE
NTP NOTICE TO PROCEED
NTS NOT TO SCALE
OC ON CENTER
OFD OVERFLOW DRAIN
OPNG OPENING
OZ OUNCE
P PUMP
PAR PARALLEL
PAT PATTERN
PB PULL BOX
PC POINT OF CURVE
PCA PORTLAND CEMENT ASSOCIATION
PCC PRECAST CONCRETE
PCCP CONCRETE PAVEMENT
PCT PERCENT
PED PEDESTAL
PEN PENETRATE
PERF PERFORATED
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PG PRESSURE GAGE OR PROFILE GRADE
PH PHASE
PHOTO PHOTOGRAPH
PHWR PRIMARY HOT WATER RETURN
PHWS PRIMARY HOT WATER SUPPLY
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PK GAR PARKING GARAGE
PK LOT PARKING LOT
PL PROPERTY LINE
PLAS PLASTIC PLASTER
PN PART NUMBER
PNEU PNEUMATIC
PO POST OFFICE OR PURCHASE ORDER
POLY POLYETHYLENE (PLASTIC)
PORT PORTABLE
POTW POTABLE WATER
POW LN POWER LINE
PP POLYPROPYLENE (PLASTIC)
PR PUMPED RETURN
PRCST PRECAST
PREFMD PREFORMED
PRELIM PRELIMINARY
PREP PREPARATION
PREV PREVIOUS
PRKG PARKING
PROJ PROJECT
PROP PROPERTY
PS CONC PRESTRESSED CONCRETE
PSI POUNDS PER SQUARE INCH
PSL PIPE SLEEVE
PT POST TENSIONED
PT CONC POST-TENSIONED CONCRETE
PV PAVED
PV RD PAVED ROAD
PVC POLYVINYL CHLORIDE (PLASTIC)
QTR QUARTER
QTY QUANTITY
QUAD QUADRANT
QUAL QUALITY
R RADIUS OR RANGE
RAD RADIAN
RC REINFORCED CONCRETE
RCB REINFORCED CONCRETE BOX
RCCP REINFORCED CONCRETE CULVERT PIPE
RCP REINFORCED CONCRETE PIPE
RD ROAD OR ROOF DRAIN
REBAR REINFORCING STEEL BARS
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
ROW RIGHT OF WAY
RST REINFORCING STEEL
RT RIGHT
RW ROADWAY
RWL RAIN WATER LEADER
RWR RECESSED WASTE RECEPTACLE
PHOTO INDICATORCD901
A1
POINT OF CONNECTION FOR NEW WORK
DETAIL INDICATOR
LIMITS OF DISTURBANCE AND CONSTRUCTION FENCE
END OF DEMOLITION
NEW SPOT ELEVATION
NEW DRAINAGE ARROW
NEW CONTOUR ELEVATION
ADA ACCESSIBLE AREA (2.0% MAX. CROSS SLOPE)
SF SF SF SF SILT FENCE
STONE BAG INLET PROTECTION
TREE PROTECTION FENCE
EXISTING ITEMS TO BE REMOVED
CONCRETE SURFACE
GRAVEL SURFACE (EXTERIOR ENCLOSURE AREA)
CONCRETE SIDEWALK
HEAVY-DUTY ASPHALT PAVEMENT SURFACE
TACTILE WARNING SURFACE
BREAK, ROUND (USER DEFINES SIZE)
DIMENSION (CIVIL ONLY)
GENERAL TOPOGRAPHICAL SURVEY NOTES
A. EXISTING TOPOGRAPHICAL SURVEY INFORMATION OBTAINED FROM "FREDERICK WARD ASSOCIATES" DATED 10-25-2023
TEMPORARY CONSTRUCTION ENTRANCE
NEW SOD AREA
EXISTING TOP OF BANK
EXISTING TOE OF SLOPE/DITCH
EXISTING STREET SIGN
EXISTING FENCE
EXISTING HEADWALL W/ PIPE
EXISTING CATCH BASIN & YARD DRAIN W/ PIPE
EXISTING TREE
EXISTING CONTOUR
EXISTING DOUBLE CATCH BASIN W/ PIPE
EXISTING SANITARY MANHOLE W/PIPE
EXISTING STORM MANHOLE W/ PIPE
EXISTING SPOT ELEVATION
EXISTING UTILITY POLE
EXISTING WATER LINE W/ SIZE
EXISTING OVERHEAD UTILITIES
EXISTING WATER VALVE
EXISTING DOWN GUY
EXISTING FIRE HYDRANT
EXISTING TRANSFORMER
EXISTING LIGHT POLE
EXISTING GAS METER
EXISTING ELECTRIC SPLICE BOX
EXISTING ELECTRIC MANHOLE
EXISTING OVERHEAD TELEPHONE
EXISTING TELEPHONE SPLICE BOX
EXISTING WATER METER
EXISTING TELEPHONE PEDESTAL
EXISTING GAS W/ SIZE
EXISTING UNDERGROUND ELECTRIC
EXISTING TELEPHONE MANHOLE
EXISTING GAS VALVE
EXISTING OVERHEAD ELECTRIC
EXISTING UNDERGROUND TELEPHONE
EXISTING UNDERGROUND UTILITIES
EXISTING GUY UTILITY POLE
EXISTING SIGNAL POLE
EXISTING ELECTRIC BOX
EXISTING FLOOD LIGHT
NEW GAS LINE
REMOVE EXISTING GAS LINE
REMOVE EXISTING UNDERGROUND ELECTRIC
REMOVE EXISTING UNDERGROUND UTILITY
REMOVE EXISTING UNDERGROUND TELEPHONE
REMOVE EXISTING STORM MANHOLE W/ PIPE
REMOVE EXISTING SANITARY MANHOLE W/PIPE
REMOVE EXISTING WATER LINE
GENERAL NOTES
A. REPAIR ANY DAMAGED EXISTING GROUND, ASPHALT, SIDEWALKS, CURB AND GUTTER, ETC. SHOWN TO REMAIN, TO MATCH
EXISTING CONDITION BEFORE DAMAGE.
B. ALL EXISTING UNDERGROUND UTILITIES TO REMAIN BUT EXPOSED TO CONSTRUCTION OR DEMOLITION ACTIVITIES ON ADJACENT
UTILITIES ARE TO BE PROTECTED FROM DAMAGE DURING ADJACENT WORK.
C. REFER TO THE SPECIFICATIONS FOR ANY FURTHER CIVIL SITE DETAILS AND REQUIREMENTS.
D. CHANGES TO EXISTING PAVEMENT GRADES TO MATCH EXISTING UNLESS OTHERWISE NOTED.
E. REFER TO SHEETS CD401, C-002 & C-003 FOR EXISTING CONDITIONS, EROSION CONTROL, AND DEMOLITION SITE PLAN AND
RELATED DETAILS.
F. REFER TO SHEET CD501 & CD502 FOR SITE PLAN AND RELATED DETAILS.
G. REFER TO SHEETS CG401 FOR FINISH GRADE PLANS, AND RELATED DETAILS.
H. REFER TO SHEETS CU401 THRU CU405 FOR EXISTING CONDITIONS AND DEMOLITION UTILITY PLANS AND RELATED DETAILS (STORM, SANITARY, WATER, GAS, AND ELECTRICAL).
ABBREVIATIONS
(NOT ALL ABBREVIATIONS WILL APPLY TO THIS WORK)
CIVIL UTILITY SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
CIVIL GENERAL SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
CIVIL EROSION CONTROL SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
CIVIL SITE AMENITIES SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
CIVIL HATCH SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
CIVIL GRADING SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
CIVIL LANDSCAPE SYMBOLS
(NOT ALL SYMBOLS WILL APPLY TO THIS WORK)
AB ANCHOR BOLT
ABAN ABANDON
ABBRV ABBREVIATION
ABC AGGREGATE BASE COURSE
AC ASPHALTIC CONCRETE
ACP ASPHALTIC CONCRETE PAVING
ADA AMERICANS WITH DISABILITIES ACT
ADDM ADDENDUM
AGGR AGGREGATE
ALLOW ALLOWANCE
ALNMT ALIGNMENT
ALT ALTERNATE OR ALTITUDE
ALUM ALUMINUM
AMT AMOUNT
APPD APPROVED
APPROX APPROXIMATE
APPX APPENDIX
ASB ASBESTOS
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION
ASPH ASPHALT
ASSY ASSEMBLY
AVE AVENUE
AWG AMERICAN WIRE GAUGE
AWWA AMERICAN WATER WORKS ASSOCIATION
B BOLLARD
BAL BALANCE
BC BACK OF CURB
BDRY BOUNDARY
BITUM BITUMINOUS
BKGD BACKGROUND
BL BASE LINE
BLDG BUILDING
BLT BUILT
BLVD BOULEVARD
BM BEAM OR BENCHMARK
BMP BEST MANAGEMENT PRACTICES
BN BULLNOSE
BOC BOTTOM OF CURB
BOW BOTTOM OF WALL
BRG BEARING
BSTR BOOSTER
BW BOTH WAYS
C TO C CENTER TO CENTER
CALC CALCULATE
CAP CAPACITY
CB CATCH BASIN OR CEMENT BASE
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS OR CONTRACT
DOCUMENTS
CE CONSTRUCTION ENTRANCE
CF CONTRACTOR FURNISHED
CFS CUBIC FEET PER SECOND
CG CENTER OF GRAVITY
CH CHANNEL OR CHILLER
CHFR CHAMFER
CI CAST IRON OR CURB INLET
CIP CAST-IN-PLACE OR CAST IRON PIPE
CIR CIRCLE
CJ CONSTRUCTION JOINT OR CONTROL JOINT
CL CENTER LINE, CLASS, OR CLOSE
CLASS CLASSIFICATION
CLL CONTRACT LIMIT LINE
CLOS CLOSURE
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CNCL CONCEALED
CND CONDUIT
CNDS CONDENSATE
CNR CORNER
CNTOR CONTACTOR
CO CLEANOUT, COMPANY, OR CUTOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCENTRIC OR CONCRETE
CONC FLR CONCRETE FLOOR
COND CONDENSER OR CONDITION
CONDN CONDENSATION
CONF CONFERENCE
CONSTR CONSTRUCTION
CONSULT CONSULTANT
CONT CONTINUE
CONTR CONTRACT OR CONTRACTOR
COORD COORDINATE
COR CHANGE ORDER REQUEST
CORR CORRIDOR
COTG CLEANOUT TO GRADE
COV COVER OR CUT OFF VALVE
COV PL COVER PLATE
CP CONCRETE PIPE OR CONTROL PANEL
CPLG COUPLING
CPM CRITICAL PATH METHOD
CRCMF CIRCUMFERENCE
CRN CROWN
CRP CONDENSATE RETURN PUMP
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CRT YD COURTYARD
CSB CONCRETE SPLASH BLOCK
CSI CONSTRUCTION SPECIFICATIONS INSTITUTE
CSP CONCRETE SEWER PIPE
CSTL CAST STEEL
CTR CENTER, CONTOUR, OR COOLING TOWER RETURN
CTRL CONTROL
CTS COOLING TOWER SUPPLY
CTV CABLE TELEVISION
CU COPPER OR CUBIC
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
AREA TO BE DEMOLISHED
C-001
SCMBVG
CIVIL ABBREVIATIONS, SYMBOLS, AND GENERAL
NOTES SITE PLAN
SURVEY CONTROL
COORDINATES SHOWN HEREON ARE DERIVED FROM VIRTUAL REFERENCE SYSTEM
OBSERVATION CALIBRATED TO THE MARYLAND COORDINATE SYSTEM (NAD83/2011) ON
THE KEYNET VRS NETWORK ON OCTOBER 25, 2023.
VERTICAL DATUM IS NAVD88.
UTILITY NOTE
UTILITIES AND OTHER OBSTRUCTIONS AS SHOWN HEREON HAVE BEEN LOCATED BY
ACTUAL FIELD MEASUREMENT, SUPPLEMENTED BY INFORMATION OBTAINED FROM
THE VARIOUS AGENCIES INVOLVED. HOWEVER, WE DO NOT GUARANTEE THE
ACCURACY NOR THE COMPLETENESS OF THE INFORMATION RECEIVED. IN
CONSTRUCTION ON THIS SITE TAKES PLACE THE CONTRACTOR MUST VERIFY ALL
SUCH INFORMATION TO HIS OWN SATISFACTION AND MUST NOTIFY THE COMPANIES
INVOLVED PRIOR TO THE START OF CONSTRUCTION.
LOCATIONS OF INDIVIDUAL ELECTRIC, TELEPHONE, GAS, WATER, AND SANITARY
SEWER SERVICE CONNECTIONS, AS SHOWN HEREON, ARE UNCERTAIN. THE
LOCATIONS OF SAID CONNECTIONS SHOWN ARE BASED ON PROPOSED SITE PLANS OR
AN ESTIMATION OF THE POSSIBLE LOCATION. SHOULD EXCAVATION BECOME
NECESSARY FOR MAINTENANCE OR REPAIR OF THESE LINES, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO ACCURATELY DETERMINE THE LOCATION OF THESE LINES BEFORE
COMMENCING WORK.
UTILITIES NOT MARKED BY THE APPROPRIATE UTILITY PROVIDERS IN A TIMELY
MANNER MAY NOT BE SHOWN HEREON.
FLOOD NOTE
THE SUBJECT PROPERTY SHOWN HEREON APPEARS ON THE FEDERAL EMERGENCY
MANAGEMENT AGENCY (FEMA) FLOOD INSURANCE RATE MAP (FIRM) MAP NUMBER
24015C0137E (EFFECTIVE DATE MAY, 4, 2015) & 24015C0141E (EFFECTIVE DATE MAY 4,
2015). ACCORDING TO THESE MAPS, THE SUBJECT PROPERTY LIES IN ZONE X (AREAS
DETERMINED TO BE OUTSIDE OF THE 0.2% ANNUAL CHANCE FLOODPLAIN).
FF ELEV: 27.95'
FF ELEV: 21.28'
FF ELEV: 21.68'
FF ELEV: 27.88'
AVENUE D
EIGHTH
STREET
BL
DG 31
4C
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSFSFSF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
TG
CE
BLDG 9H
BL
DG 34
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
PERRY POINT VAMC - PERRY POINT, MD
NOTES
1. REFER TO C-001 FOR CIVIL ABBREVIATIONS, SYMBOLS, AND GENERAL NOTES.
2. THE EXISTING TOPOGRAPHIC AND SITE UTILITY INFORMATION SHOWN HAS BEEN PROVIDED TO THE VA AND IS AVAILABLE AS A FULL ELECTRONIC FILE AVAILABLE BY REQUEST FROM THE COR. THIS INFORMATION IS PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR. THE VA IS NOT RESPONSIBLE FOR THE ACCURACY OF THE INFORMATION SHOWN THEREON. CONTRACTOR WILL VERIFY ALL INFORMATION SHOWN; THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE TO UTILITIES SHOWN ON THE SURVEY AND
DRAWINGS TO REMAIN.
3. THE CONTRACT DRAWINGS SHOW THE APPROXIMATE LOCATION OF EXISTING UTILITY LINES. THESE LINES HAVE BEEN IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE USING AVAILABLE INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING UTILITY LOCATIONS ON THE SURVEY WITH LOCATIONS IN THE FIELD, AND COORDINATING WITH ANY ASSOCIATED UTILITY COMPANIES FOR DEMOLITION OF UTILITIES
INDICATED.
4. THE TOTAL AREA OF DISTURBANCE IS APPROXIMATELY 97,965 SQ. FT.
TOPOGRAPHICAL SURVEY NOTE
THE EXISTING TOPOGRAPHIC AND SITE INFORMATION SHOWN HAS BEEN PROVIDED BY FREDERICK WARD ASSOCIATES. DATED 10-25-2023. THIS INFORMATION IS PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR.
THE CONTRACTOR IS REQUIRED TO PROVIDE THEIR OWN SURVEYING AND UTILITY LOCATING SERVICES TO VERIFY ALL INFORMATION SHOWN PRIOR TO THE START OF CONSTRUCTION AND TO IMMEDIATELY NOTIFY THE COR OF DISCREPANCIES BETWEEN THE CONTRACTORS SURVEY AND THE INFORMATION SHOWN ON THESE DRAWINGS, OTHERWISE THE CONTRACTOR ACCEPTS LIABILITY FOR ACCURACY OF THE INFORMATION SHOWN;
THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE (RESULTANT OF WORK PERFORMED ACCORDING TO THESE DOCUMENTS) TO UTILITIES SHOWN ON THE DRAWINGS THAT ARE TO REMAIN.
SITE PLAN - EROSION AND SEDIMENT CONTROL PLAN
SCALE: 3/64" = 1'
F1
CD501
D4
CD502
C3
CIVIL UTILITY SYMBOLS
EXISTING STORMWATER DRAINAGE LINE
EXISTING SANITARY SEWER LINE
SILT FENCESF SF SF
TEMPORARY TREE PROTECTION FENCE
TEMPORARY CONSTRUCTION FENCE
TGCE TEMPORARY CONSTRUCTION ENTRANCE
EXISTING SANITARY SEWER MANHOLE
EXISTING STORM DRAIN MANHOLE
CD501
D4
CD502
C1
CD502
C1
CD501
D4
CD502
C1
N
CD503
F1
CD503
F1
CD503
F1
AT GRADE INLET PROTECTION (AGIP)
CD502
F6
CD503
F1
CD503
F1
CD503
F1
CD503
F1
C-002
SCMBVG
SITE PLAN - EROSION AND SEDIMENT CONTROL
PLAN SITE PLAN
OBSERVATION CALIBRATED TO THE MARYLAND COORDINATE SYSTEM (NAD83/2011) ON
THE KEYNET VRS NETWORK ON OCTOBER 25, 2023.
VERTICAL DATUM IS NAVD88.
UTILITY NOTE
UTILITIES AND OTHER OBSTRUCTIONS AS SHOWN HEREON HAVE BEEN LOCATED BY
ACTUAL FIELD MEASUREMENT, SUPPLEMENTED BY INFORMATION OBTAINED FROM
THE VARIOUS AGENCIES INVOLVED. HOWEVER, WE DO NOT GUARANTEE THE
ACCURACY NOR THE COMPLETENESS OF THE INFORMATION RECEIVED. IN
CONSTRUCTION ON THIS SITE TAKES PLACE THE CONTRACTOR MUST VERIFY ALL
SUCH INFORMATION TO HIS OWN SATISFACTION AND MUST NOTIFY THE COMPANIES
INVOLVED PRIOR TO THE START OF CONSTRUCTION.
LOCATIONS OF INDIVIDUAL ELECTRIC, TELEPHONE, GAS, WATER, AND SANITARY
SEWER SERVICE CONNECTIONS, AS SHOWN HEREON, ARE UNCERTAIN. THE
LOCATIONS OF SAID CONNECTIONS SHOWN ARE BASED ON PROPOSED SITE PLANS OR
AN ESTIMATION OF THE POSSIBLE LOCATION. SHOULD EXCAVATION BECOME
NECESSARY FOR MAINTENANCE OR REPAIR OF THESE LINES, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO ACCURATELY DETERMINE THE LOCATION OF THESE LINES BEFORE
COMMENCING WORK.
UTILITIES NOT MARKED BY THE APPROPRIATE UTILITY PROVIDERS IN A TIMELY
MANNER MAY NOT BE SHOWN HEREON.
FLOOD NOTE
THE SUBJECT PROPERTY SHOWN HEREON APPEARS ON THE FEDERAL EMERGENCY
MANAGEMENT AGENCY (FEMA) FLOOD INSURANCE RATE MAP (FIRM) MAP NUMBER
24015C0137E (EFFECTIVE DATE MAY, 4, 2015) & 24015C0141E (EFFECTIVE DATE MAY 4,
2015). ACCORDING TO THESE MAPS, THE SUBJECT PROPERTY LIES IN ZONE X (AREAS
DETERMINED TO BE OUTSIDE OF THE 0.2% ANNUAL CHANCE FLOODPLAIN).
FF ELEV: 27.95'
FF ELEV: 21.28'
FF ELEV: 21.68'
FF ELEV: 27.88'
BL
DG 31
4C
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSFSFSF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
TG
CE
BLDG 9H
BL
DG 34
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
PERRY POINT VA
MEDICAL CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% BID DOCUMENTS DEMOLISH BUILDING 9H
512A5-23-311
05-NOV-2024
VA MARYLAND HEALTHCARE SYSTEM
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE.