511/22046. JBB; Marquette Armory - Replace Boiler
Solicitation number
RFQ - 171 - 220000000415
Issued by
Alger County, Menominee City, Michigan

About this file

This document contains plans and specifications for the Marquette Armory Boiler Replacement project in Alger County and Menominee City, Michigan. The project involves demolition and replacement of the existing boiler system at the Marquette Armory facility. The bid attachments must be uploaded to the SIGMA VSS system, and questions should be emailed to Deana Paoli-Wuori at OHM Advisors. The bid deadline is 2:00 p.m., and emailed submissions may be accepted on a case-by-case basis with prior approval. COVID-19 precautions such as mask requirements may be in place for meetings and site visits.

The project drawings and details provide specifications for the new concrete equipment pad, floor slab infill, and reinstallation of the existing acoustic ceiling system. The general notes indicate coordination is required with the owner's abatement contractor. Temporary barriers, shoring, and protection of the means of egress are also specified. Pricing, funding, and incumbent contractor details are not provided in the document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

DN

DN

DN

STAIR

BREAK RM

PASSAGE

E.M. TOILET

DRYING

SHOWER

UTILITY RM

STRONG RM

SIGNAL RM

UNIT STORAGE

FEMALE DRYING ROOM

121B

FEMALE LOUNGE

BOILER RM

FEMALE LATRINE

CORRIDOR

ASSEMBLY HALL

LOBBY.

FEMALE SHOWERS

121C

H.C. FEMALE LATRINE

121A

3'-0"

3' -0

2'-0"

4' -2

6'-10"

2' -0

1. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN

CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO

CONTINUATION OF WORK

2. REFER TO A-001 FOR MATERIAL / REFERENCE SYMBOLS AND ABBREVIATIONS

3. REFER TO LIFE SAFETY DRAWINGS (G-SERIES) FOR LOCATIONS AND EXTENTS OF RATED

ASSEMBLIES, AS WELL AS FIRE EXTINGUISHER LOCATIONS. IF PARTITION DESIGNATION

DISCREPANCY OCCURS BETWEEN THE CODE DRAWINGS AND FLOOR PLANS, PROVIDE THE

PARTITION TYPE INDICATED WITH THE MOST STRINGENT REQUIREMENTS

4. REFER TO A-900 SERIES FOR FURNITURE, FIXTURE, & EQUIPMENT PLANS

5. REFER TO A-800 SERIES FOR ROOM FINISH PLANS

6. REFER TO A-011 FOR ALL ASSEMBLY TYPES

7. REFER TO A-002 FOR ACCESSORY MOUNTING DIAGRAMS AND TYPICAL TOILET ROOM TYPES

8. REFER TO A-600 SERIES FOR DOOR, WINDOW, AND STOREFRONT INFORMATION AND DETAILS

9. REFER TO A-600 SERIES FOR ROOM FINISH SCHEDULE

10. ALL MASONRY DIMENSIONS ARE NOMINAL, UNO

11. ALL DIMENSIONS ARE FROM COLUMN REFERENCE LINE TO FACE OF STUD, UNO

12. PARTITION TYPE 'J' TO BE APPLIED TO ALL INTERIOR EXISTING WALL CONDITIONS TO REMAIN, UNO

13. ALL INTERIOR COLUMN WRAPS TO BE PARTITION TYPE 'K', UNO

14. ALL DOORS TO BE BE 4" FROM FINISH FACE OF WALL TO HINGE, UNO

GENERAL NOTES - PLANS

BREAK RM

STAIR

ASSEMBLY HALL

STRONG RM

SIGNAL RM

UTILITY RM

E.M. TOILET

PASSAGE

DRYING

SHOWER

UNIT STORAGE

BOILER RM

FEMALE LATRINE

FEMALE LOUNGE

FEMALE DRYING ROOM

121B

LOBBY.

CORRIDOR

H.C. FEMALE LATRINE

121A

FEMALE SHOWERS

121C

1. ALL DEMOLITION WORK IS TO BE COORDINATED WITH ABATEMENT WORK BY OWNER. REFER TO

MECHANICAL, ELECTRICAL, & PLUMBING DEMOLITION PLANS FOR ADDITIONAL INFORMATION.

COORDINATE DEMOLITION WORK WITH EXISTING SECURITY AND TECHNOLOGY BY OTHERS

2. PROVIDE DUST-PROOF CONSTRUCTION BARRIERS TO SEPARATE AND SECURE THE CONSTRUCTION

AREA FROM THE REMAINDER OF THE BUILDING. PROVIDE TEMPORARY FILTERS AT RETURN AIR

DUCTWORK AS REQUIRED TO MINIMIZE THE SPREAD OF DUST THROUGHOUT THE BUILDING

3. KEEP MEANS OF EGRESS OPEN, PROPERLY ILLUMINATED, AND FREE OF OBSTRUCTIONS AT ALL

TIMES

4. PROVIDE TEMPORARY SHORING AS REQUIRED TO MAINTAIN THE STRUCTURAL STABILITY OF

BUILDING ELEMENTS TO REMAIN DURING DEMOLITION THROUGH COMPLETION OF WORK

GENERAL NOTES - DEMOLITION PLANS

EXIST. CONC. FLOOR

3/4" CHAMFER

TYP

4" THICK CONC. EQUIPMENT PAD W/ #4 @ 8" E.W.

SCARIFY EXIST. CONC.

FLOOR AS REQUIRED

APPLY EPOXY BONDING

AGENT

CONCRETE: 3,000 P.S.I

@ 28 DAYS

SECTION

4"

SEE PLAN FOR DIMENSIONS

NEW FLOOR SLAB TO MATCH

DEPTH OF EXISTING REINF W/

6x6 W2.9xW2.9 WWF & 10 MIL VB

DRILL & EPOXY GROUT #5

DOWELS x 10" LONG W/ EPOXY

COATED 5" EMBED INTO EX

FLOOR SLAB @ 24" OC TPY

EX CONCRETE FLOOR SLAB

EX FILL

VERIFY IN FIELD

V E

R

IF

Y

IN

F

IE

LD

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

P L

U R

I B

U

E

S U

N U

M

C I

R C

U M

S P

I C

E

S I

Q U

E R

E I

S P

E N

I N

S U

L A

M A

M O E

N A

M

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

424 Hancock Street Hancock, MI 49930

PH 906.482.0535 | F 906.482.6453

F

IL

E P

A T

H

S H

E E

T

ID

E N

T

IF

IC

A

T

IO

N N o.

IS

S U

E D

F O

R D

A T

E

OHM PROJECT No.

P R

E

LI

M

IN

A R

Y

C O

N S

T R

U C

T

IO

N

F

IN

A L

R E

C O

R D

D T

M B

F

IL

E N

U M

B E

R

COPYRIGHT 2022 OHM ALL DRAWINGS AND WRITTEN MATERIALS APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF OHM AND THE SAME MAY NOT BE DUPLICATED, DISTRIBUTED, OR DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF OHM

D E

S

IG

N E

D

D R

A W

N

C H

E C

K E

D

A P

P R

O V

E D

A C

C O

U N

T

IN

G T

E M

P

B

IM

-2

2-

M ar qu et te

A rm or y

B oi le r

R ep la ce m en t/7

0_

A _M ar qu et te

A rm or y_

B oi le rR ep la ce m en t_

_C E

N .r vt 6/

/2

:2

3:

A M

C he ck er

A pp ro ve r

D E

P A

R T

M E

N T

O F

M

IL

IT

A

R Y

V

E T

E R

A N

S A

F F

A

IR

S

M ar qu et te A rm or y R ep la ce B oi le r A

-1

7136-22-0060

1/

6.

JB

B

1S T

F

LO

O R

P

LA

N

D es ig ne r

/0 6/

/0 6/ xx xx

/x x/ xx

/0 6/

P

LA

N

R E

V

IE

W

N

1/8" = 1'-0"1

1ST FLOOR PLAN

SHEET KEYNOTES - PLAN

01 INFILL DEMOLISHED SLAB. REFER TO DETAIL 3/A-101

02 NEW HOUSEKEEPING PAD. REFER TO DETAIL 4/A-101

N

1/8" = 1'-0"2

1ST FLOOR DEMOLITION PLAN

SHEET KEYNOTES - DEMO. PLAN

01 DEMO EXSTING PAD. PREP FOR INFILL.

1" = 1'-0"4

EQUIPMENT PAD DETAIL

3/4" = 1'-0"3

FLOOR SLAB INFILL DETAIL

STAIR

BREAK RM

PASSAGE

E.M. TOILET

DRYING

UTILITY RM

ASSEMBLY HALL

STRONG RM

SIGNAL RM

SHOWER

UNIT STORAGE

BOILER RM

FEMALE LATRINE

FEMALE LOUNGE

FEMALE DRYING ROOM

121B

LOBBY.

CORRIDOR

10'-0"

ACT-1

10'-0"

GPBD-1

10'-0"

GPBD-1

H.C. FEMALE LATRINE

121AFEMALE SHOWERS

121C

1. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN

CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO

CONTINUATION OF WORK

2. REFER TO PROJECT INFORMATION SHEET FOR MATERIAL / REFERENCE SYMBOLS AND

ABBREVIATIONS

3. REFER TO MECHANICAL, ELECTRICAL, FIRE SUPPRESSION & TECHNOLOGY DRAWINGS FOR

QUANTITY AND TYPE OF CEILING MOUNTED FIXTURES / DEVICES

4. ALL CEILING MOUNTED FIXTURES, DEVICES, ETC. ARE TO BE CENTERED WITHIN THE CEILING TILE, UNO

5. PROVIDE CONTROL JOINTS @ 30'-0" OC MAX AT ALL GYPSUM BOARD BULKHEADS. LOCATE TO BE

EVENLY SPACED OR TO ALIGN WITH COLUMN CENTERLINES, ADJACENT WALLS, OR OTHER

ARCHITECTURAL ELEMENTS. REVIEW PROPOSED LOCATIONS WITH ARCHITECT PRIOR TO

INSTALLATION

6. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR MOUNTING LOCATIONS OF ITEMS

WHERE NO CEILINGS ARE REQUIRED OR INDICATED

7. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE SCHEDULE

8. REFER TO MECHANICAL DRAWINGS FOR DIFFUSER FIXTURE SCHEDULE

GENERAL NOTES - REF. CEILING PLANS

STAIR

ASSEMBLY HALL

STRONG RM

SIGNAL RM

UTILITY RM

DRYING

SHOWER

E.M. TOILET

BREAK RM

UNIT STORAGE

FEMALE DRYING ROOM

121B

FEMALE LOUNGE

FEMALE LATRINE

BOILER RM

CORRIDOR

LOBBY.

H.C. FEMALE LATRINE

121A

FEMALE SHOWERS

121C

CEILING INDICATION

EXISTING CEILING SYSTEM TO BE REMOVED.

DEMOLITION RCP LEGEND

EXISTING CEILING SYSTEM TO BE REMOVED.

NEW GRID TO REFLECT EXISTING GRID LAYOUT & HEIGHT WITHIN

SPACE, UNO

1. ALL DEMOLITION WORK IS TO BE COORDINATED WITH ABATEMENT WORK BY OWNER. REFER TO

MECHANICAL, ELECTRICAL, & PLUMBING DEMOLITION PLANS FOR ADDITIONAL INFORMATION.

COORDINATE DEMOLITION WORK WITH EXISTING SECURITY AND TECHNOLOGY BY OTHERS

2. PROVIDE DUST-PROOF CONSTRUCTION BARRIERS TO SEPARATE AND SECURE THE CONSTRUCTION

AREA FROM THE REMAINDER OF THE BUILDING. PROVIDE TEMPORARY FILTERS AT RETURN AIR

DUCTWORK AS REQUIRED TO MINIMIZE THE SPREAD OF DUST THROUGHOUT THE BUILDING

3. KEEP MEANS OF EGRESS OPEN, PROPERLY ILLUMINATED, AND FREE OF OBSTRUCTIONS AT ALL

TIMES

4. PROVIDE TEMPORARY SHORING AS REQUIRED TO MAINTAIN THE STRUCTURAL STABILITY OF

BUILDING ELEMENTS TO REMAIN DURING DEMOLITION THROUGH COMPLETION OF WORK

GENERAL NOTES - DEMOLITION PLANS

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

P L

U R

I B

U

E

S U

N U

M

C I

R C

U M

S P

I C

E

S I

Q U

E R

E I

S P

E N

I N

S U

L A

M A

M O

E N

A M

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

424 Hancock Street Hancock, MI 49930

PH 906.482.0535 | F 906.482.6453

F

IL

E P

A T

H

S H

E E

T

ID

E N

T

IF

IC

A

T

IO

N N o.

IS

S U

E D

F O

R D

A T

E

OHM PROJECT No.

P R

E

LI

M

IN

A R

Y

C O

N S

T R

U C

T

IO

N

F

IN

A L

R E

C O

R D

D T

M B

F

IL

E N

U M

B E

R

COPYRIGHT 2022 OHM ALL DRAWINGS AND WRITTEN MATERIALS APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF OHM AND THE SAME MAY NOT BE DUPLICATED, DISTRIBUTED, OR DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF OHM

D E

S

IG

N E

D

D R

A W

N

C H

E C

K E

D

A P

P R

O V

E D

A C

C O

U N

T

IN

G T

E M

P

B

IM

-2

2-

M ar qu et te

A rm or y

B oi le r

R ep la ce m en t/7

0_

A _M ar qu et te

A rm or y_

B oi le rR ep la ce m en t_

_C E

N .r vt 6/

/2

:2

3:

A M

C he ck er

A pp ro ve r

D E

P A

R T

M E

N T

O F

M

IL

IT

A

R Y

V

E T

E R

A N

S A

F F

A

IR

S

M ar qu et te A rm or y R ep la ce B oi le r A

-7

7136-22-0060

1/

6.

JB

B

1S T

F

LO

O R

R E

F

LE

C T

E D

C E

IL

IN

G P

LA

N

D es ig ne r

/0 6/

/0 6/ xx xx

/x x/ xx

/0 6/

P

LA

N

R E

V

IE

W

N

1/8" = 1'-0"2

1ST FLOOR REFLECTED CEILING PLAN

SHEET KEYNOTES - RCP

01 REINSTALL ORIGINAL ACT SUSPENDED SYSTEM AND TILES

02 PROVIDE 5/8" GYP BOARD ON METAL FURRING ON EX. METAL JOISTS

N

1/8" = 1'-0"1

1ST FLOOR DEMOLITION REFLECTED CEILING PLAN

SHEET KEYNOTES - DEMO. RCP

01 REMOVE EXISTING ACT SUSPENDED SYSTEM AND TILES.

02 REMOVE AND SAVE EXISTING ACT SUSPENDED SYSTEM AND TILES FOR REINSTALLATION.

03 REMOVE EXISTING PLASTER CEILING AND FRAMING. COORDINATE WITH ABATEMENT CONTRACTOR.

03 REMOVE EXISTING PLASTER CEILING AND FRAMING. PROVIDE ABATEMENT IN THESE AREAS. REFER TO

ENVIRONMENTAL REPORT IN SPECIFICATION APPENDIX II

04 REMOVE EXISTING PLASTER CEILING AND FRAMING.

Sheets
A-101 - 1ST FLOOR PLAN
A-701 - 1ST FLOOR REFLECTED CEILING PLAN

File details come from the government source that posted it. Updated .