2'-2"
2'-2"
5'-1
2'-10"
1'-6"
NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
EX. SD 30
EX. SD 45
EX. SD 30
EX. SD 40
EX. SD 20
EX. SD 30
EX. SD 45 EX. SD 40
EX. SD 20
EX. SD 40
EX. SD 30
EX. SD 50
EX. SD 40
EX. SD 90
EX. SD 90
EX. SD 30
EX. SD 45
EX. SD 40
EX. SD 40EX. SD 40
EX. SD 30
EX. SD 30
EX. SD 30
EX. SD 45
EX. SD 45
EX. SD 25
EX. SD 30
EX. SD 20
EX. SD 30
EX. SD 30
EX. SD 20
EX. SD 40
EX. SD 50
EX. SD 20
EX. SD 30
EX. SD 40 EX. SD 40
EX. SD 120
EX. SD 50
EX. SD 65
EX. SD 80
EX. SD 60
EX. SD 80
EX. SD 35
EX. SD 30
EX. SD 20
EX. SD 20
EX. SD 40
EX. SD 55
EX. SD 40
EX. SD 40
EX. SD 40
EX. SD 30
EX. SD 45
EX. SD 90
EX. SD 90
EX. ED 290
EX. ED 70
EX. ED 70
EX. ED 70
EX. ED 65
EX. ED 65
EX. ED 60
EX. ED 155
EX. ED 15
EX. ED 15
EX. SD 30
EX. ED 15
EX. ED 20
EX. ED 15
EX. ED 15
EX. ED 20
EX. ED 25
EX. ED 20
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 20
EX. ED 35
EX. ED 35
EX. ED 50
EX. ED 35
EX. ED 35
EX. ED 35
EX. ED 50
EX. ED 60
EX. ED 65
EX. ED 80EX. ED 55
EX. ED 25
EX. ED 40
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 65
EX. ED 35
EX. ED 45
EX. ED 60
EX. ED 50
EX. ED 35
EX. ED 85
EX. ED 30
EX. ED 35
EX. ED 25
EX. ED 80
(TYP.)
(TYP.)
10x8
EX. FCU
(TYP.)
EX. FCU
(TYP.)
01 NEW EXHAUST SHAFT WITH NEW 18"X18"
EXHAUST DUCT, SEE ARCHITECTURAL FOR
MORE INFORMATION.
02 REPLACE EXISTING 16"X19" EXHAUST DUCT
WITH NEW 20"X16" EXHAUST DUCT IN SHAFT.
03 BALANCE EXISTING EXHAUST GRILLE(S) IN
ROOM TO QUANTITY INDICATED.
04 BALANCE SUPPLY OUTDOOR AIRFLOW INTO
EXISTING FAN COIL UNIT TO QUANTITY
INDICATED. FOR ROOMS WITH MULTIPLE FAN
COIL UNITS, THE OUTSIDE AIR TO EACH UNIT
SHALL BE BALANCED TO THE QUANTITY
INDICATED. PERMANENTLY OPEN MOTORIZED
OUTSIDE AIR DAMPER TO EACH FAN COIL
UNIT.
05 PROVIDE NEW FIRE DAMPER AT FLOOR SLAB
PENETRATION.
06 RECONNECT EXISTING HORIZONTAL DUCT
LEAVING THE SHAFT INTO NEW DUCT RISER.
PROVIDE FIRE DAMPER AT SHAFT
PENETRATION. FIELD CONFIRM THE SIZE OF
THE EXISTING HORIZONTAL SHAFT PRIOR TO
ORDERING THE FIRE DAMPER.
07 PROVIDE 2" HPS AND 1
" LPR PIPING FROM
BASEMENT TO ROOF. REFER TO MH105 FOR
CONTINUATION.
A FOR ALL FAN COIL UNITS ON THIS FLOOR
REFER TO DETAIL 12 / M-501 FOR NEW
COMBINATION SHUT-OFF / STRAINER /
BALANCING VALVES TO BE ADDED TO BOTH
THE CHILLED WATER AND HEATING WATER
LINES. CONTROL VALVES TO REMAIN.
SECOND FLOOR MECHANICAL PLAN
Scale: 1/8" = 1'-0"
SECOND FLOOR MECHANICAL PLAN
0 4 8 16
N
O
R
T
H
TRUE
WALL RATING LEGEND
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
AREA OF WORK
KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
# 2
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
502-16-104
TAMEKA J. TAYLOR
5-15-2020
100% SUBMISSION
17-108
2495 SHREVEPORT HWY. PINEVILLE, LA 71360
REPLACE HVAC SYSTEM
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
S S S S
SWRPLH
MH103
09 21
VA COMMENTS 5/15/20201
DocuSign Envelope ID: FC52A366-4C33-40F9-8CAE-C17A7D694A8F
5/15/2020
NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
EX. SD 40
EX. SD 60
EX. SD 60
EX. SD 20
EX. SD 20
EX. SD 65
EX. SD 90
EX. SD 90
EX. SD 35
EX. SD 45
EX. SD 50
EX. SD 65
EX. SD 45
EX. SD 40
EX. SD 20
EX. SD 40
EX. SD 30
EX. SD 60
EX. SD 90
EX. SD 35 EX. SD 35
EX. SD 240
EX. SD 35
EX. SD 50
EX. SD 80
EX. SD 70
EX. SD 25
EX. SD 25
EX. SD 45
EX. SD 80
EX. SD 80
EX. ED 285
EX. ED 75
EX. ED 65
EX. ED 65
EX. ED 80
EX. ED 40
EX. SD 20
EX. ED 25
EX. ED 15
EX. ED 15
EX. ED 15
EX. ED 30
EX. ED 70
EX. ED 45
EX. ED 55
EX. ED 55
EX. ED 55
EX. ED 15
EX. ED 30
EX. ED 35
EX. ED 65
EX. ED 50
EX. ED 35
EX. ED 215
EX. ED 80EX. ED 80
EX. ED 40
EX. ED 100
EX. ED 35
EX. ED 60
EX. ED 40
EX. ED 55
EX. ED 190
(TYP)
(TYP)
EX. SD 45
EX. ED 35
EX. SD 50
EX. ED 80
EX. SD 20
EX. ED 15
EX. SD 50
EX. ED 80
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 30
EX. SD 45
EX. ED 35
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 30
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
10x8
EX. FCU
(TYP.)
EX. FCU
(TYP.)
01 REPLACE EXISTING 22"x18" EXHAUST DUCT IN
SHAFT WITH 36"x18" NEW EXHAUST DUCT.
02 DEMOLISH EXISTING JOHNSON CONTROLS
THREE WAY CONTROL VALVE AND PROVIDE
SIEMENS THREE WAY CONTROL VALVE IN IT'S
PLACE.
03 NEW EXHAUST SHAFT WITH 22"x22" EXHAUST
DUCT, SEE ARCHITECTURAL FOR MORE
INFORMATION.
04 BALANCE EXISTING EXHAUST GRILLE OR
REGISTER IN ROOM TO QUANTITY INDICATED.
05 BALANCE SUPPLY OUTDOOR AIRFLOW INTO
EXISTING FAN COIL UNIT TO QUANTITY
INDICATED. FOR ROOMS WITH MULTIPLE FAN
COIL UNITS, THE OUTSIDE AIR TO EACH UNIT
SHALL BE BALANCED TO THE QUANTITY
INDICATED. PERMANENTLY OPEN MOTORIZED
OUTSIDE AIR DAMPER TO EACH FAN COIL
UNIT.
06 RECONNECT EXISTING HORIZONTAL DUCT
LEAVING THE SHAFT INTO NEW DUCT RISER.
PROVIDE FIRE DAMPER AT SHAFT
PENETRATION. FIELD CONFIRM THE SIZE OF
THE EXISTING HORIZONTAL SHAFT PRIOR TO
ORDERING THE FIRE DAMPER.
07 PROVIDE 2" HPS AND 1
" LPR PIPING FROM
BASEMENT TO ROOF. REFER TO MH105 FOR
CONTINUATION.
THIRD FLOOR MECHANICAL PLAN
Scale: 1/8" = 1'-0"
THIRD FLOOR MECHANICAL PLAN
0 4 8 16
N
O
R
T
H
TRUE
A FOR ALL FAN COIL UNITS ON THIS FLOOR
REFER TO DETAIL 12 / M-501 FOR NEW
COMBINATION SHUT-OFF / STRAINER /
BALANCING VALVES TO BE ADDED TO BOTH
THE CHILLED WATER AND HEATING WATER
LINES. CONTROL VALVES TO REMAIN UNLESS
NOTED OTHERWISE TO BE REPLACED.
WALL RATING LEGEND
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
AREA OF WORK
KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
# 2
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
502-16-104
TAMEKA J. TAYLOR
5-15-2020
100% SUBMISSION
17-108
2495 SHREVEPORT HWY. PINEVILLE, LA 71360
REPLACE HVAC SYSTEM
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
S S S S
SWRPLH
MH104
10 21
VA COMMENTS 5/15/20201
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
# 2
502-16-104
TAMEKA J. TAYLOR
1-9-2020
100% CONSTRUCTION DOCUMENTS
17-108
2495 SHREVEPORT HWY. PINEVILLE, LA 71360
REPLACE HVAC SYSTEM
COOLING COIL
RA
HWS
HWR
V-1
HEATING COIL
CHS
CHR
V-2
T-1
DDC ROOM TEMPERATURE SENSOR/THERMOSTAT, ADJUSTABLE, WALL MOUNTED 48" AFF.
SENSOR SHALL HAVE FAN SPEED ADJUSTMENT CAPABILITIES. PROVIDE BY DDC CONTRACTOR.
T
PC
FILTER
FAN COIL SEQUENCE OF OPERATION
FAN COIL SHALL OPERATE ON A SCHEDULE AS SET BY ECC. FAN SHALL RUN CONTINUOUSLY
IN OCCUPIED MODE. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE
GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70°-75° SPACE
TEMPERATURE BOTH V-1 & V-2 SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 75°
V-2 SHALL MODULATE OPEN TO MAINTAIN 75° F. UPON FALL IN TEMPERATURE BELOW 70° F.
HEATING VALVE V-1 SHALL MODULATE TO OPEN TO MAINTAIN 70° F.
AN OVERFLOW SWITCH SHALL MONITOR THE LEVEL OF WATER IN THE DRAIN PAN. UPON
DETECTION OF HIGH WATER LEVEL, THE SUPPLY FAN SHALL SHUT DOWN, THE COOLING COIL
VALVE SHALL CLOSE, AND AN ALARM SHALL BE ENUNCIATED AT THE ECC.
FAN
CS
TT
HS
SST
PROGRAMMABLE CONTROLLER, PROVIDED BY DDC CONTRACTOR.
POINT NAME:
ZONE TEMPERATURE
ZONE TEMPERATURE SETPOINT
FAN START/STOP
DISCHARGE AIR TEMPERATURE
FAN STATUS
HEATING COIL VALVE
COOLING COIL VALVE
HEATING MODE
SETPOINT TEMPERATURE
HIGH ZONE TEMPERATURE
LOW ZONE TEMPERATURE
HIGH DISCHARGE TEMPERATURE
HARDWARE POINTS
AI AO
X
X
X
X
BI BO
SOFTWARE POINTS
AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TOTAL HARDWARE (7) TOTAL SOFTWARE (17)
2 2 3
X
X
9 4 10
X
X
X
X
X
X
MINIMUM OCCUPIED AIR FLOW SETPOINT
MINIMUM UNOCCUPIED AIRFLOW SETPOINT
X
X
X
X
X
X
SST
ERW
OUTSIDE AIR
ZC D-1
D-1
E R
V
P
R E
F
I L T
E R
DPT
DPT-1
TT
T-2
HT
H-2
OUTSIDE AIR TEMPERATURE AND
HUMIDITY SENSORS
TT
T-3
ERV INTAKE
DAMPER
ZC D-2
D-2
AHU INTAKE
DAMPER
FIELD-INSTALLED
DUCTWORK BETWEEN
ERV AND AHU
A F
M D
FT
AF-1
SST
SF1
HS
CS
IT-1
SPD
ALA
VFD
SF1
SF1
ERV SUPPLY FAN
VARIABLE FREQUENCY
DRIVE (TYP.)
PH
PH-1
TT
T-4
H
HUMIDIFIER
ZC
HC-1
V-2
C O
O L I N
G
CHS
V-3
CHR
TT
T-6
RH
RH-1
LPC
LPS
V-1
P R
E H
E A
T
SST
SF2
HS
CS
IT-2
SPD
ALA
VFD
SF2
SF2
AHU SUPPLY FAN
ARRAY
ONE (1) VFD FOR EACH
FAN IN THE ARRAY
P R
E F
I L T
E R
DPT
DPT-2
P R
E F
I L T
DPT
DPT-3
TT
T-5
TT
T-7
HT
H-3
SD
INSTALL IN DUCTWORK
DOWNSTREAM OF AHU
SUPPLY AIR
PSH
PRESSURE SWITCH HIGH TO DISABLE
SUPPLY FANS IN AHU AND ERV WHEN
HIGH PRESSURE LIMIT SETPOINT IS
REACHED
TT
T-1
HT
H-1
PSL
A F
M D
FT
AF-2
PRESSURE SWITCH LOW TO DISABLE
EXHAUST FAN IN ERV WHEN LOW
PRESSURE LIMIT SETPOINT IS
REACHED
INSTALL IN EHAUST
DUCTWORK
UPSTREAM OF ERV
EXHAUST AIR
(FROM
BUILDING)
E X
H A
U S
T
F
I L T
E R
DPT
DPT-4
DPT
DPT-5
EXHAUST
FAN
SST
EF1
HS
CS
IT-3
SPD
ALA
VFD
EF1
EF1
ZC D-3
D-3
ERV EXHAUST
(DISCHARGE)
DAMPER
CS
IT-4
CURRENT
TRANSMITTER FOR
FAN STATUS (TYP. 3)
CURRENT TRANSMITTER FOR
ENERGY WHEEL STATUS
SYSTEM: 2-ERV-1 WITH 2-AH-1; 2-ERV-2
WITH 2-AH-2
POINT LEGEND
SYSTEM
OUTPUTS
BINARY
ANA-
LOG
BINARY ANALOG
SYSTEM INPUTS SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
ALARM
PROCESSING
REMARKS:
SYSTEM COMPONENT:
EXHAUST AIRFLOW (CFM)
EXHAUST FILTER DIFFERENTIAL PRESSURE
ENERGY WHEEL DIFFERENTIAL PRESSURE
EXHAUST AIR DISCHARGE TEMPERATURE
EXHAUST AIR TEMPERATURE
ENERGY WHEEL STATUS
AHU SUPPLY FAN STATUS (PER FAN)
ERV SUPPLY FAN VSMC
OUTSIDE AIR DAMPER OPEN/CLOSE
AI-3
AI-4
AI-5
AI-6
BI-1
BI-4
AO-1
BO-1
AF-2
DPT-4
DPT-5
T-8
T-1
IT-4
IT-2
SPD-SF1
D-1
P
O
I
N
T
I
D
A
B
B
R
E
V
I
A
T
I
O
N
P
R
I
O
R
I
T
Y
A
A
L
T
E
E
L
E
C
T
R
C
V
I
C
E
S
T
A
R
T
S
T
O
P
O
P
E
N
C
L
O
S
E
S
P
E
O
M
M
A
N
D
V
A
L
V
P
S
I
T
I
O
N
D
A
M
P
S
I
T
I
O
N
S
T
A
T
U
S
A
L
A
R
M
P
R
E
S
S
U
R
E
H
I
G
H
U
M
I
D
I
T
Y
H
I
S
A
T
E
S
S
U
R
E
L
W
M
P
E
R
A
T
U
R
E
T
E
M
P
E
R
A
T
U
I
P
R
E
S
S
U
R
E
P
O
S
I
T
I
O
N
F
L
O
W
P
E
R
C
E
N
T
S
T
A
T
E
S
S
U
R
E
C
A
R
B
M
N
O
X
I
D
E
H
U
M
I
D
I
T
Y
V
A
C
U
U
M
L
O
C
L
A
N
E
L
A
R
A
N
E
L
M
A
S
T
A
N
E
L
H
I
M
I
T
L
W
M
I
T
S
C
H
E
D
U
S
A
R
T
S
T
O
P
F
U
N
C
T
I
O
N
D
U
Y
C
L
E
T
E
M
O
N
O
M
I
Z
E
R
E
N
T
H
A
L
O
N
O
M
I
Z
E
R
T
E
M
P
E
R
A
T
U
S
E
T
D
E
M
A
M
I
T
I
N
G
T
E
M
P
E
R
A
T
U
V
E
R
R
I
D
E
S
T
A
T
E
S
S
U
S
E
T
P
R
E
S
S
U
R
E
V
O
N
T
R
O
L
F
A
I
L
U
D
E
S
P
A
M
N
T
R
O
L
F
U
M
M
I
U
N
I
C
A
T
I
O
N
T
R
E
N
D
I
N
G
REMARKS
FULL COMMUNICATION
AI-1
ENERGY WHEEL SUPPLY HUMIDITY AI-9 H-4
ERV PRE-FILTER DIFFERENTIAL PRESSURE DPT-1AI-7
EXHAUST FAN VSMC ALARM BI-6 ALA-EF1
ERV SUPPLY FAN START/STOP BO-5 SST-SF1
ENERGY WHEEL SUPPLY TEMPERATURE
T-3AI-8
SUPPLY AIRFLOW (CFM)
AI-10
AF-1
PRE-FILTER 1 DIFFERENTIAL PRESSURE
AI-11 DPT-2
PRE-FILTER 2 DIFFERENTIAL PRESSURE
AI-12 DPT-3
EXHAUST FAN STATUS BI-2 IT-3
ERV SUPPLY FAN STATUS BI-3 IT-1
DUCT SMOKE DETECTOR
BI-5 SD
EXHAUST FAN VSMC AO-2 SPD-EF1 FULL COMMUNICATION
EXHAUST AIR HUMIDITY H-1AI-2
ERV SUPPLY FAN VSMC ALARM
BI-7 ALA-SF1
PREHEAT VALVE BO-8 V-1
HUMIDIFIER VALVE
AO-4
V-2
EXHAUST FAN START/STOP BO-6 SST-EF1
AHU SUPPLY FAN START/STOP (EACH FAN)
BO-7 SST-SF2
COOLING VALVE AO-5 V-3
TT
T-8
HT
H-4
PREHEAT TEMPERATURE
AI-13 T-4
PSL
HT
H-5
HUMIDIFIER TEMPERATURE
AI-14 T-5
HUMIDIFIER HUMIDITY
AI-15 H-5
REHEAT TEMPERATURE
AI-16 T-6
DISCHARGE AIR TEMPERATURE
AI-17 T-7
DISCHARGE AIR HUMIDITY
AI-18 H-3
AHU SUPPLY FAN VSMC ALARM (PER FAN)
BI-8 ALA-SF2
OUTSIDE AIR DAMPER END SWITCH
BI-9 D-1
AHU DAMPER END SWITCH
BI-10 D-2
EXHAUST AIR DAMPER END SWITCH
BI-11 D-3
REHEAT VALVE (EACH) AO-6 V-4 AND V-5
AHU SUPPLY FAN VSMC (EACH FAN) AO-7 SPD-SF2
FULL COMMUNICATION
SUPPLY AIR DAMPER OPEN/CLOSE BO-2 D-2
EXHAUST AIR DAMPER OPEN/CLOSE BO-3 D-3
ENERGY WHEEL START/STOP BO-4 SST-ERW
1. 2-ERV-1 WITH 2-AH-1 AND 2-ERV-2 WITH 2-AH-2 CONTROL SEQUENCE
1.1. FAN OPERATION: ERV SUPPLY FAN, AHU SUPPLY FANS, AND ERV EXHAUST FAN SHALL
OPERATE CONTINUOUSLY DURING BUILDING OCCUPIED HOURS. FANS SHALL BE
DE-ENERGIZED DURING BUILDING UNOCCUPIED HOURS. PRIOR TO FANS ENERGIZING,
THE OUTSIDE AIR DAMPER (D-1), SUPPLY AIR DAMPER (D-2), AND EXHAUST AIR DAMPER
(D-3) SHALL FULLY OPEN, AND SHALL BE PROVEN OPEN BY THEIR RESPECTIVE END
SWITCHES. DAMPERS SHALL CLOSE AFTER THE STATUS OF ALL FANS IS "OFF" FOR A
MINIMUM TIME OF 15 SECONDS (ADJUSTABLE. OCCUPIED AND UNOCCUPIED MODES
SHALL BE DETERMINED BY THE ECC.
1.2. COOLING/HEATING MODES AND ENERGY WHEEL OPERATION:
1.2.1. THE ENERGY WHEEL SHALL ROTATE AT FULL SPEED WHENEVER THE FANS ARE
OPERATIONAL. IF THE WHEEL FAILS TO ROTATE UPON A COMMAND TO ENERGIZE,
AN ALARM SHALL ANNUNCIATE AT THE ECC.
1.2.2. THE SUPPLY AIR TEMPERATURE SETPOINT (T-7) SHALL BE 55°F (ADJUSTABLE)
WHEN THE OUTSIDE AIR TEMPERATURE AS MEASURED BY T-2 IS GREATER THAN
OR EQUAL TO 80°F (ADJUSTABLE), 70°F (ADJUSTABLE) WHEN THE OUTSIDE AIR
TEMPERATURE IS LESS THAN OR EQUAL TO 52°F (ADJUSTABLE), AND SHALL RESET
LINEARLY BETWEEN 52°F AND 80°F OUTSIDE AIR TEMPERATURE (ADJUSTABLE).
WHEN THE TEMPERATURE ENTERING THE CHILLED WATER COIL, MEASURED BY
T-5, IS GREATER THAN THE SETPOINT, THE CHILLED WATER CONTROL VALVE (V-3)
SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT. WHEN
THE TEMPERATURE ENTERING THE PREHEAT COIL, AS MEASURED BY T-4, IS LESS
THAN THE SETPOINT, THE PREHEAT COIL CONTROL VALVE (V-1) SHALL OPEN
FULLY, AND THE FACE AND BYPASS DAMPERS (D-4) SHALL MODULATE TO MAINTAIN
DISCHARGE AIR TEMPERATURE SETPOINT.
1.3. HUMIDITY CONTROL MODES:
1.3.1. DEHUMIDIFICATION: WHEN THE RELATIVE HUMIDITY OF THE EXHAUST AIR COMING
FROM THE BUILDING, AS MEASURED BY H-1, RISES ABOVE 60% (ADJUSTABLE),
SUPPLY AIR TEMPERATURE CONTROL SHALL BE OVERRIDDEN. COOLING COIL
CONTROL VALVE V-3 SHALL MODULATE OPEN TO MAINTAIN TEMPERATURE T-6 AT
A SETPOINT OF 50°F (ADJUSTABLE), AND THE REHEAT COIL CONTROL VALVES (V-4
AND V-5) SHALL MODULATE TO MAINTAIN DISCHARGE HUMIDITY (H-3) SETPOINT OF
50% (ADJUSTABLE). THIS SHALL CONTINUE UNTIL EXHAUST AIR RELATIVE
HUMIDITY FALLS BELOW 55% (ADJUSTABLE).
1.3.2. HUMIDIFICATION: WHEN THE RELATIVE HUMIDITY OF THE EXHAUST AIR COMING
FROM THE BUILDING, AS MEASURED BY H-1, FALLS BELOW 20% (ADJUSTABLE),
HUMIDIFIER STEAM CONTROL VALVE (V-2) SHALL MODULATE TO MAINTAIN
DISCHARGE AIR HUMIDITY (H-3) OF 35% (ADJUSTABLE). THIS SHALL CONTINUE
UNTIL EXHAUST AIR RELATIVE HUMIDITY RISES ABOVE 25% (ADJUSTABLE).
1.4. ECONOMIZER OPERATION:
1.4.1. WHEN THE OUTDOOR AIR ENTHALPY, AS MEASURE BY T-2 AND H-2, IS LESS THAN
OR EQUAL TO THE INDOOR AIR ENTHALPY, AS MEASURED BY T-1 AND H-1, THE
ENERGY WHEEL SHALL STOP AND ALL VALVES SHALL CLOSE.
1.4.2. ECONOMIZER OPERATION SHALL BE DISABLED WHEN:
1.4.2.1. OUTDOOR AIR ENTHALPY EXCEEDS INDOOR AIR ENTHALPY, OR
1.4.2.2. OUTDOOR AIR TEMPERATURE (T-2) EXCEEDS 75°F (ADJUSTABLE), OR
1.4.2.3. OUTDOOR AIR TEMPERATURE (T-2) IS LESS THAN 55°F
1.5. SAFETY CONTROL/PROTECTION:
1.5.1. FREEZE PROTECTION: AVERAGING TEMPERATURE SENSOR T-5 SHALL
DE-ENERGIZE ALL SUPPLY FANS, CLOSE THE OUTSIDE AIR AND SUPPLY AIR
DAMPER, CLOSE THE CHILLED WATER COOLING COIL VALVE (V-4), AND FULLY
OPEN THE PREHEAT COIL VALVE (V-1) IF ANY PART OF THE SENSOR MEASURES
36°F (ADJUSTABLE) OR BELOW.
1.5.2. UPON DETECTION OF PRODUCTS OF COMBUSTION BY THE SMOKE DETECTOR, ALL
SUPPLY FANS SHALL DE-ENERGIZE, VALVES SHALL CLOSE, AND AND ALARM SHALL
BE ANNUNCIATED TO THE FIRE ALARM SYSTEM AND AT THE ECC.
1.6. OTHER ALARMS:
1.6.1. AN ALARM SHALL ANNUNCIATE AT THE ECC WHEN PRESSURE DROP ACROSS ANY
FILTER OR THE ENERGY WHEEL EXCEEDS THE INITIAL PRESSURE DROP BY 0.5"
W.G. (ADJUSTABLE)
1.6.2. AN ALARM SHALL ANNUNCIATE AT THE ECC WHEN DISCHARGE AIR TEMPERATURE
EXCEEDS 60°F (ADJUSTABLE) OR FALLS BELOW 45°F (ADJUSTABLE).
1.6.3. AN ALARM SHALL ANNUNCIATE AT THE ECC WHEN ANY SUPPLY OR EXHAUST FAN
FAILS TO START OR FAILS DURING OPERATION.
1.6.4. AN ALARM SHALL ANNUNCIATE AT THE ECC WHEN DISCHARGE AIR HUMIDITY
RISES ABOVE 60% (ADJUSTABLE) OR FALLS BELOW 20% (ADJUSTABLE).
1.7. GRAPHICS AND MONITORING: ADD SYSTEMS TO THE EXISTING BUILDING DDC SYSTEM,
SHOWING ALARMS AND OTHER POINTS SHOWN ON THE DRAWINGS AND INCLUDED IN
THE SPECIFICATIONS AND IN ACCORDANCE WITH VA REQUIREMENTS. THE DDC SHALL
MONITOR VFD OPERATIONS AND ALARM CONDITIONS.
1.8. ALL ALARM SETPOINTS SHALL BE ADJUSTABLE. ALL ALARMS SHALL BE ABLE TO BE
SILENCED AND RESET REMOTELY AT THE ECC AND DDC WORKSTATION.
TOTAL ENERGY
RECOVERY WHEEL
CONTROLS DIAGRAMS
SCALE: N.T.S.
FOUR PIPE FAN COIL UNIT CONTROLS
SCALE: N.T.S.
100% OUTSIDE AIR ENERGY RECOVERY UNIT AND AIR HANDLING UNIT CONTROLS
NOTE: PROVIDE AN ANALOG OUTPUT POINT FOR EACH
NEW SIEMENS CONTROL VALVE ON THE THIRD FLOOR.
PLHPLH
M-504
18 21
LPC
LPS
V-5 (1/3)V-4 (2/3)
P R
E H
E A
T
STEAM TO
HUMIDIFIER
DISPERSION
RACKS IN AHU
FCU
FCU
FCU
STEAM CONTROL VALVE CAPACITIES:
1. V-1: 411 LBS/HR (2-AH-1), 372 LBS/HR (2-AH-2)
2. V-2: 127 LBS/HR (2-AH-1), 119 LBS/HR (2-AH-2)
3. V-4: 135 LBS/HR (2-AH-1), 129 LBS/HR (2-AH-2)
4. V-5: 67 LBS/HR (2-AH-1), 65 LBS/HR (2-AH-2)
VALVE V-1 SHALL BE 2-POSITION WITH 24 VOLT ACTUATOR.
ALL OTHER VALVES SHALL BE MODULATING AND HAVE 24
VOLT ACTUATORS.
SST
EF1
HS
CS
IT-3
MOTOR
STARTER
EXHAUST
FAN
SCALE: N.T.S.
MISCELLANEOUS EXHAUST FAN CONTROLS
1. 2-EF-ATTIC (2 FANS) - FANS SHALL BE CONTROLLED BY A SINGLE COOLING THERMOSTAT IN
THE ATTIC. WHEN THE TEMPERATURE IN THE ATTIC RISES ABOVE SETPOINT (ADJUSTABLE
AT THERMOSTAT), THE OUTSIDE AIR INTAKE MOTORIZED DAMPERS AND EXHAUST
MOTORIZED DAMPERS SHALL OPEN, AND THE FANS SHALL ENERGIZE AFTER THE DAMPERS
ARE PROVEN OPEN BY AN END SWITCH. THE ECC SHALL MONITOR THE STATUS OF THE
FANS.
2. 2-EF-BIO AND 2-EF-SLEEP: FAN SHALL BE ENERGIZED WHENEVER THE BUILDING IS
OCCUPIED, AS SCHEDULED BY THE ECC. PRIOR TO THE FAN ENERGIZING, THE EXHAUST
AIR MOTORIZED DAMPER SHALL OPEN AND BY PROVEN OPEN BY AND END SWITCH.
3. 2-EF-ELEC: FAN SHALL BE CONTROLLED BY A COOLING THERMOSTAT IN THE ELECTRICAL
ROOM. WHEN THE TEMPERATURE IN THE ROOM RISES ABOVE SETPOINT (ADJUSTABLE AT
THERMOSTAT), THE OUTSIDE AIR INTAKE MOTORIZED DAMPER AND EXHAUST MOTORIZED
DAMPER SHALL OPEN, AND THE FAN SHALL ENERGIZE AFTER THE DAMPERS ARE PROVEN
OPEN BY AN END SWITCH. THE ECC SHALL MONITOR THE STATUS OF THE FAN.
POINT NAME:
FAN START/STOP (QTY. 2)
FAN STATUS (QTY. 5)
MOTORIZED DAMPER OPEN/CLOSE (QTY. 7)
HARDWARE POINTS
AI AO
X
X
X
BI BO
SOFTWARE POINTS
AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
X
X
X
X
TOTAL HARDWARE (14) TOTAL SOFTWARE (5)
5 5 149
ZC
D-4
FACE AND BYPASS
DAMPERS
FACE AND BYPASS DAMPER AO-3 D-4
CONDENSATE OVERFLOW SWITCH
X X X
2 1
D-4
NOTE: DIAGRAM, SEQUENCE AND POINTS LIST ARE TYPICAL FOR (2) ENERGY
RECOVERY UNITS AND (2) AIR HANDLING UNITS.
NOTE: TYPICAL FOR EACH FAN COIL UNIT.
D U
I G
H
H
H
STEAM
CONDENSATE
RETURN
TEMPERATURE SWITCH
SCALE POCKET
HUMIDIFIER
CONTROL VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE
AHU HUMIDIFER SECTION
M
I N m m
INVERTED BUCKET
TRAP
ASSEMBLY
SEE MANUFACTURER'S
PIPING RECOMMENDATIONS
FOR FINAL LAYOUT
SCALE: N.T.S.
AHU STEAM HUMIDIFIER - PIPING CONNECTIONS
(MULTIPLE DISPERSION TUBES)
VA COMMENTS 5/15/20201