F
SD
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR-COOLED CONDENSER
ACCH AIR-COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND
REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELCIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHWP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CMO CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CHWCC CHILLED WATER COOLING COIL
D DAMPER - AUTOMATIC
dB DECIBELS Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DHX DOMESTIC WATER HEAT EXCHANGER
DIA DIAMETER
DIW DEIONIZED WATER
DOAS DEDICATED OUTSIDE AIR SYSTEM
DP DEW POINT TEMPERATURE
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
ETR EXISTING TO REMAIN
EX. EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCW FORWARD CURVED WHEEL (FAN)
FDR FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H HUMIDIFER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HHW HEATING HOT WATER
HHWC HEATING HOT WATER COIL
HHWP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HOA HAND/OFF/AUTOMATIC
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPM HEAT PUMP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
Hz HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LH LATENT HEAT
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPS LOW PRESSURE SUPPLY (STEAM)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL
PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/s METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT
AMPACITY
MD MANUAL BALANCING DAMPER
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MOD MOTOR OPERATED DAMPER
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE SUPPLY (STEAM)
MTD MEAN TEMPERATURE DIFFERENCE
MD or MVD MANUAL VOLUME DAMPER
NA NOT APPLICABLE
NC NOISE CRITERIA
NCL NORMALLY CLOSED
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OSA OUTSIDE SUPPLY AIR
(CONDITIONED)
P PUMP
PA PRESSURIZED AIR
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SDT SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSR SOLID SEPARATOR
ST STEAM TRAP
SV STEAM SAFETY VALVE
SVR STEAM VACUUM RETURN
SVS STEAM VENT SILENCER
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL
OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
Wb WET-BULB (TEMPERATURE)
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
XT EXPANSION TANK
YR YEAR
MECHANICAL ABBREVIATIONS
1. WORK SHALL CONFORM TO LOCAL, STATE, AND NATIONAL CODES AND VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.
4. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE
REQUIRED.
5. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
6. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
7. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.
8. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.
9. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF ALL OTHER TRADES.
10. PROVIDE SUPPORTS FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH ALL CONTRACTORS PRIOR TO INSTALLATION.
11. COORDINATE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT WITH THE ELECTRICAL CONTRACTOR.
12. CONTROL WIRING FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED BY CONTROLS CONTRACTOR.
13. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND
PIPING IN THE FIELD.
14. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT BEFORE ANY WORK OR EQUIPMENT RELEASE TAKES PLACE.
15. NOTIFY COR REGARDING DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS OR DIMENSIONS BEFORE PERFORMING WORK. FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE CONTRACTOR'S ACCEPTANCE OF EXISTING CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THE WORK.
16. SEE ARCHITECTURAL DRAWINGS FOR FINAL LOCATION OF CEILING INSTALLED EQUIPMENT.
17. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE AND AS CLOSE AS POSSIBLE TO BUILDING WALLS, CEILING AND FLOOR AND ROOF STRUCTURE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.
18. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
19. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.
20. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION. CAULK FULLY AROUND THE ESCUTCHEON.
21. MAKE A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. PROVIDE WRITTEN RFI TO COR.
22. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL CLOSETS/ROOMS.
23. PREPARE DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY THE GOVERNMENT.
A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.
B. DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO, ALL DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, CEILING GRID AND HEIGHT, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER AND OTHER CEILING MOUNT DEVICES OR EQUIPMENT THAT PROTRUDE INTO THE CEILING CAVITY.
C. IF THERE ARE OUTSTANDING ISSUES THAT CANNOT BE RESOLVED, ISSUE RFI TO COR FOR GUIDANCE AND MAKE CORRECTIONS IN ACCORDANCE WITH DIRECTIONS
GIVEN.
D. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.
24. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK LACKING
COORDINATION AT NO ADDITIONAL COST
25. ALL EXISTING DUCTWORK THAT IS REUSED AS PART OF THIS PROJECT, AND EXISTING DUCTWORK THAT IS TIED INTO WITH NEW DUCTWORK, SHALL BE PROFESSIONALLY CLEANED AND SANITIZED PRIOR TO BEING RETURNED TO SERVICE. DUCT CLEANING AND SANITIZING SHALL BE PERFORMED BY A PROFESSIONAL DUCT CLEANING COMPANY CERTIFIED BY NADCA (NATIONAL AIR DUCT CLEANERS ASSOCIATION). CLEANING AND SANITIZING SHALL BE PERFORMED ACCORDING TO THE LATEST NADCA STANDARDS.
26. CLEAR SPACE ABOVE CEILINGS IS LIMITED. THERE IS EXISTING CABLE TRAY, SPRINKLER PIPING, CONDUIT, AND OTHER SERVICES ABOVE THE FIRST FLOOR CEILING THAT WILL NOT BE REMOVED. CAREFULLY COORDINATE THE INSTALLATION OF MECHANICAL SYSTEMS WITH THEMSELVES AND ALL OTHER TRADES, BOTH NEW AND EXISTING.
GENERALLY, SYSTEMS REQUIRING SLOPE (SUCH AS CONDENSATE PIPING) TAKE PRECEDENCE OVER OTHER SYSTEMS. NO CHANGE ORDERS WILL BE PERMITTED FOR
ISSUES ARISING DUE TO FAILURE TO COORDINATE ON THE PART OF THE CONTRACTOR.
27. THE ATTIC IS A VERY TIGHT SPACE. SYSTEMS THAT WILL BE REMOVED WILL NEED TO BE BROKEN DOWN INTO PIECES IN ORDER TO REMOVE THEM. INSTALL NEW SYSTEMS IN SUCH A WAY THAT EGRESS OUT OF THE ATTIC IS MAINTAINED. INSTALL EQUIPMENT TO MAINTAIN MANUFACTURER-REQUIRED CLEARANCES.
28. AIR HANDLING UNIT 2-AH-1 WILL NEED TO BE SHIPPED IN MODULES, BROUGHT IN THROUGH AN EXISTING GABLE LOUVER, AND ASSEMBLED IN THE ATTIC. THE GABLE LOUVERS ARE APPROXIMATELY 36"x48". PRIOR TO RELEASING THE UNIT FOR FABRICATION, CONFIRM GABLE LOUVER SIZE AND THE MAXIMUM SIZE OF A MODULE THAT CAN BE BROUGHT INTO THE ATTIC. PROVIDE AS MANY MODULES AS REQUIRED TO BRING UNIT INTO THE ATTIC.
29. FULLY DRAIN THE CHILLED WATER SYSTEM AND RE-FILL PER SPECIFICATIONS. COORDINATE TIME OF SYSTEM DRAINING AND REFILLING WITH COR.
30. SIZE, ROUTE AND INSTALL REFRIGERANT PIPING IN STRICT ACCORDANCE WITH EQUIPMENT MANUFACTURER'S INSTRUCTIONS.
31. IT IS THE INTENT OF THE FIRST FLOOR DEMOLITION DRAWINGS TO REMOVE ALL HVAC EQUIPMENT, INCLUDING, BUT NOT LIMITED TO, FAN COIL UNITS, INDUCTION UNITS, SPLIT SYSTEMS, WINDOW AIR CONDITIONING UNITS, EXHAUST FANS, UNIT HEATERS AND RADIATORS. REMOVE ALL EQUIPMENT EVEN IF NOT SHOWN ON THE DRAWINGS, EXCEPT HEATING EQUIPMENT IN THE STAIRWELLS AND ELECTRICAL ROOM 110 SHALL REMAIN. REMOVE ALL EXISTING DUCTWORK, PIPING, AND AIR DEVICES ON THE FIRST FLOOR EVEN IF NOT SHOWN ON THE DRAWINGS, EXCEPT WHERE SPECIFICALLY SHOWN AS EXISTING TO REMAIN. EXISTING SUPPLY DUCT VERTICAL RISERS ON THE NORTH AND SOUTH SIDE SHALL BE REMOVED BACK TO THE POINT WHERE IT PENETRATES THE SECOND FLOOR SLAB. THE EXISTING MAIN EXHAUST DUCT VERTICAL RISER ON THE NORTH SIDE SHALL BE REMOVED ENTIRELY, INCLUDING THE DUCTWORK IN THE ROOFTOP PENTHOUSE.
MECHANICAL GENERAL NOTES
T
CO2 CARBON DIOXIDE
THERMOSTAT
SUPPLY DIFFUSER
RETURN DIFFUSER/GRILLE
EXHAUST GRILLE
ROUND FLEX DUCT
EG-88 2000 AIR DEVICE TAG | AIR DEVICE CFM
BALANCING DAMPER
(RECTANGULAR)
BALANCING DAMPER
(ROUND)
FIRE DAMPER
SMOKE DAMPER
D
R INCLINED RISE, IN
DIRECTION OF AIRFLOW
INCLINED DROP, IN DIRECTION
OF AIRFLOW
CONNECT NEW DUCT
TO EXISTING
LIMIT OF DEMOLITION
VANED ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR
ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
STANDARD RADIUS ELBOW
(LONG RADIUS)
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
DUCT TRANSITION
SIDE MOUNTED GRILLE
SUPPLY
RETURN45°
45°
DN
DN
UP
UP
DNUP
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
MECHANICAL LEGEND
HPS
LPS
LPR
CHS
CHR
HIGH PRESSURE STEAM
PIPING (60 PSI)
LOW PRESSURE STEAM PIPING
(15 PSI AND BELOW)
LOW PRESSURE STEAM
CONDENSATE RETURN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
PIPE UP
PIPE DOWN
BOTTOM CONNECTION
TOP CONNECTION
CAPPED OUTLET
GLOBE VALVE
GATE VALVE
BALL VALVE
STEAM SAFETY VALVE
PRESSURE REGULATING VALVE
WYE STRAINER VALVE
BALANCING VALVE
MOTORIZED CONTROL VALVE
STEAM TRAP
D CONDENSATE DRAIN LINE
HPR HIGH PRESSURE STEAM
CONDENSATE RETURN
HWS
HWR
HEATING HOT WATER SUPPLY
PIPING
HEATING HOT WATER RETURN PIPING
RLS REFRIGERANT LINE SET (LIQUID
AND SUCTION)
CONNECT TO EXISTING PIPE
LIMITS OF DEMOLITION
INLINE CENTRIFUGAL PUMP
TANGENTIAL AIR SEPARATOR
EXPANSION TANK
WALL-MOUNTED INDOOR
SPLIT-SYSTEM
SPLIT-SYSTEM CONDENSING UNIT
UTILITY SET EXHAUST FAN
STEAM PRESSURE
REDUCING STATION
DRAIN VALVE
TEST PLUG
SUPPLY
TERMINAL UNIT SUPPLY
DUCT BRANCH (CONICAL
TAP)
TERMINAL UNIT
CHECK VALVE
MPS
MPR
MEDIUM PRESSURE STEAM
PIPING (30 PSI)
MEDIUM PRESSURE STEAM
CONDENSATE RETURN
PIPE FLOW ARROW
(EXISTING PIPE)
PIPE FLOW ARROW
(NEW PIPE)
FLAT OVAL ELBOW
SECTION LETTER
DRAWING NUMBER WHERE SHOWN
M-105
A
M-105
DRAWING SYMBOLS
2 SECTION LETTER
DRAWING NUMBER WHERE SHOWN
NEW WORK KEYED NOTE
DEMOLITION KEYED NOTE
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
/8
/2
:5
:3
A M
M-001
GENERAL NOTES, LEGEND, AND
ABBREVIATIONS
01 21
TAMEKA J. TAYLOR
SWR
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
Exterior Stairs NA NA NA 50 NA NA NA
Corridors 75 65.3 55 70 50.0 30 32
Electrical Room 86 NA NA 40 NA NA NA
IT Room 86 NA NA 40 NA NA NA
Staff Breakroom/Conference 75 65.3 55 70 50.0 30 32
Storage 75 65.3 55 70 50.0 30 32
Toilet NA NA NA 68 NA NA 32
Library 75 65.3 55 70 50.0 30 32
Offices 75 65.3 55 70 50.0 30 32
OUTDOOR DESIGN CONDITIONS 97.2 77.1 41.2 27.4 9.0 50 13
F F % F F %
DB WB RH DB WB RH ANNUAL DEWPOINT
AREA ROOM NUMBERS SUMMER WINTER LOWEST AVERAGE
HVAC DESIGN DATA
DocuSign Envelope ID: B9D4F131-B263-4860-8434-0C5CADDF2C68
1/8/2020
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
(EX) HX 2-3
(EX) HX 2-4
(EX) HWP2-10
(EX) HWP 2-9
(EX) HX 2-1
(EX) HWP 2-7
(EX) HWP 2-8
(EX) ET-2
(EX) ET-1
(EX) DHX
(EX) DHX
EX. 3" S-30EX. 3" S-30
EX. 2" PCR
2" PCR
2" HPR
EX. 3" HPS
3" LPR
4" LPS
2 1/2" SVR
4" HPR
(EX) ET-4
(EX) ET-3
4" LPS
3" LPR
4" LPS
3" LPR
4" LPR
6" LPS
6" LPS
L P
S
6" LPS
4" MPR
6" LPS
4" MPR
6" LPS
4" LPR
6" LPS
6" LPS
4" LPR
4" LPR
6" LPS
4" LPR
2" HPR
4" LPS
3" LPR
4" LPS
3" LPR
L P
S
L P
R
3" LPR
4" LPS
EX. 3" PCR
EX. 4" HPS
4" LPS
3" LPR
2" MPR
2" MPC
2" MPR
EX. 2" LPR
EX. 2" LPR
L P
S
EX. 8" CHR
EX. 6" CHS
EX. 4" CHR
EX. 4" CHS
4" LPS
3" LPR
4" LPS
3" LPR
EX. 3" HPS
EX. 2 1/2" SVR
3" HPR
2 1/2" SVR
(EX) HWP 2-6
(EX) HWP 2-5
(EX) HWP 2-1
(EX) HWP 2-2
1 1/4'' LPS/R UP TO
PERIMETER STEAM
RADIATORS. TYPICAL.
1 1/4'' LPS/R UP TO
PERIMETER STEAM
RADIATORS
1 1/4'' LPS/R UP TO
PERIMETER STEAM
RADIATORS
ETR 4'' HWS/R UP
ETR 4'' CHS/R UP
ETR 4'' CHS/R UP
ETR 3 1/2'' CHS/R UP
ETR 5'' CHS/R UP
ETR 4'' CHS/R UP
(EX) CHP 2-6
(EX) CHP 2-4
(EX) CHP 2-3ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
(EX) CWP 2-5
(EX) CWP 2-2
(EX) CWP 2-1
ETR
ETR
ETR
2" HWS
2" HWR
2" HWS
2" HWR
2" HWR
2" HWS
(EX) ET
(EX) HX
(EX) ET
(EX) HX
(EX) HX 2-2 ETR
EX. 2 1/2" SVR
EX. 4" HPR
EX. 6" HPS EX. 8" CHSEX. 8" CHR
EX. 3" HPS
EX. 4"
EX. 6" HPS
EX. 4" HWR
EX. 4" HWS
(TYP)
EX. 6" HPS
E X
C H
S
E X
C H
R
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
MAIN STEAM LINE TO BOILER PLANT.
EX. 2" D EX. 2" D
EX. 2" D
EX. 2" D
EX. 2" D
(EX) PRS
ETR
ETR
(EX) PRS
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
SCALE: 1/8" = 1'-0"1
BASEMENT MECHANICAL DEMOLITION PLAN PHASE 1 0 4 8 16
N O
R
TH
TRUE
01 DEMOLISH LOW PRESSURE STEAM, LOW
PRESSURE STEAM CONDENSATE PIPING
AND INSULATION COMPLETELY. DO NOT
ABANDON PIPING IN FLOOR. PATCH, PAINT,
INFILL AND REFINISH WALL AND/OR FLOOR
TO MATCH EXISTING.
02 DEMOLISH MEDIUM PRESSURE STEAM
CONDENSATE PIPING AS REQUIRED TO
INSTALL NEW STEAM PUMP TRAP FOR THE
EXISTING HEAT EXCHANGERS IN THE
LOCATION SHOWN. SEE SHEET MP101 FOR
RELATED WORK.
03 VERIFY STEAM PRESSURE REDUCING
VALVE STATION REMAINS OPERATIONAL TO
SERVE THE DOMESTIC HOT WATER SYSTEM
DURING CONSTRUCTION. COORDINATE ANY
REQUIRED SHUTDOWNS WITH THE
OWNERS REPRESENTATIVE.
04 DEMOLISH SHELL AND TUBE HEAT
EXCHANGER, SUPPORTS, AND INSULATION
COMPLETE.
05 DEMOLISH HOT WATER EXPANSION TANK,
MOUNTINGS, AND INSULATION COMPLETE.
06 DEMOLISH HOT WATER PUMP, MOUNTINGS,
AND INSULATION COMPLETE.
07 DEMOLISH STEAM CONDENSATE PIPING
MAIN AS SHOWN AND PREPARE FOR
CONNECTION TO NEW STEAM
CONDENSATE PUMP. SEE SHEET MP101
FOR RELATED WORK.
08 CAP AT WALL PENETRATION.
09 REMOVE EXISTING STEAM CONDENSATE
GRAVITY AND VACUUM RETURN LINES.
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:4
A M
MD101
BASEMENT MECHANICAL DEMOLITION
PHASE 1
02 21
TAMEKA J. TAYLOR
SWR
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
ETR 3'' HWR UP
ETR 3'' HWS UP
ETR 2 1/2'' CHS UP
ETR 2 1/2'' CHR UP
A BASEMENT PHASE 1 AND PHASE 2 DOES NOT
RELATE TO THE GENERAL PHASING PLAN.
THE PHASES SHOWN ON MD101, MD102,
MP101, AND MP102 ARE TO PHASE THE
WORK OF THE BASEMENT INDEPENDENTLY.
B EXTEND TEMPORARY STEAM CONDENSATE
LINE TO DRAIN WHERE NECESSARY.
C ASBESTOS IS PRESENT IN THE BUILDING
(PIPING MASTIC, DUCT MASTIC, INSULATION,
ETC.). ABATE ALL ASBESTOS THAT IS
DISTURBED AS A RESULT OF WORK.
SERVICE ROOM
TRANSFORMER ROOM
BATTERY ROOM
PIT
ELEV.
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
2-CP-2
(EX) HX 2-1
(EX) HWP 2-7
(EX) HWP 2-8
2-ST-2 2-ST-1
(EX) HX 2-2
EX. 3" PCR
EX. 3" PCR
3" PCR
EX. 4" PCR
EX. 2" LPR
EX. 2 1/2" SVR
EX. 3" HPR
EX. 2" LPR
EX. 2" LPR
EX. 2" PCREX. 2" PCR
2" PCR
EX. 2" PCR
2-ST-42-ST-3
2-ST-5
EX. 2 1/2" MPR
EX. 4" PCR
EX. 4" PCR
2-CP-1
(EX) CWP 2-5
(EX) CWP 2-2
(EX) CWP 2-1
(EX) CHP 2-6
(EX) CHP 2-4
(EX) CHP 2-36" PCR EX. 4" PCR
EX. 4" PCR
EX. 6" CHS
EX. 6" CHS
6" CHS
2-CWP-2
2-CWP-1
(EX) 2-CWP-4
(EX) 2-CWP-3
EX. 4" CHS
EX. 4" CHS
EX. 4" CHS
(EX) ET-1
(EX) ET-2
(EX) ET-3
(EX) ET-4
4"
4"
4"
(EX) HX 2-4(EX) HX 2-3
(EX) DHX
(EX) DHX
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
4"
4"
4"
C H
R
03 (TYP)
03 (TYP)
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
EX. 6" V
EX. 2" D
E X
V
E X
D
EX. 2" D
E X
D
EX. 2" D
EX. 6" V
EX. 2" D
E X
H P
S
(EX) PRS ETR
(EX) PRS ETR
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
01 DEMOLISH CHILLED WATER PIPING AS
SHOWN AND PROVIDE CAP AT
DEMARCATION POINT(S).
02 REMOVE CHILLED WATER PUMP AND
ASSOCIATED PIPING, CONTROLS, AND
ACCESSORIES AS SHOWN. PROVIDE
TEMPORARY CAP TO PREPARE FOR NEW
CONNECTION. SEE SHEET MP102 FOR
RELATED WORK.
03 DEMOLISH VALVE AS SHOWN AND PROVIDE
CAP AT DEMARCATION POINT(S). ALLOW
ADEQUATE ROOM TO INSTALL NEW VALVE,
REFER TO MP102 FOR LOCATION OF NEW
VALVES.
SCALE: 1/8" = 1'-0"1
BASEMENT MECHANICAL DEMOLITION PLAN PHASE 2 0 4 8 16
N O
R
TH
TRUE
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:4
A M
MD102
BASEMENT MECHANICAL DEMOLITION
PHASE 2
03 21
TAMEKA J. TAYLOR
SWR
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
A BASEMENT PHASE 1 AND PHASE 2 DOES
NOT RELATE TO THE GENERAL PHASING
PLAN. THE PHASES SHOWN ON MD101,
MD102, MP101, AND MP102 ARE TO PHASE
THE WORK OF THE BASEMENT
INDEPENDENTLY.
B COORDINATE SHUTDOWN OF CHILLED
WATER SYSTEM WITH ARCHITECTURAL
PHASES.
C ASBESTOS IS PRESENT IN THE BUILDING
(PIPING MASTIC, DUCT MASTIC,
INSULATION, ETC.). ABATE ALL ASBESTOS
THAT IS DISTURBED AS A RESULT OF
WORK.
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8 x
24x14
16x12 x
14x8 ø ø ø
C H
R
3" CHR
3" CHS
C H
S
C H
R
D
1 1/2" CHS
1 1/2" CHR
1 1/2" D
1 1/2" CHR
1 1/2" CHS
/2
C H
S
/2
C H
R
D
HWS
HWR
/2
D
/2
C H
R
/2
C H
S
H W
SH
W
R
D
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
15ø
102A
123A
104A
117K
117J
117H
114G
117A 117B
117C 117D
117L
117E
117F
138A STAIRS
126A
127A
127B
126E
126B 126D
128B
128E
128A
128C
128D
128F
128G
128H
126C
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:5
A M
MD103
FIRST FLOOR MECHANICAL
DEMOLITION PLAN
04 21
TAMEKA J. TAYLOR
SM
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
0 4 8 16
N O R
TH
TRUE
Scale: 1/8" = 1'-0"
FIRST FLOOR MECHANICAL DEMOLITION PLAN
01 DEMOLISH FLOOR MOUNTED RADIATOR
AND ASSOCIATED STEAM AND STEAM
CONDENSATE PIPING COMPLETELY.
COMPLETELY REMOVE PIPING AND PIPE
INSULATION. DO NOT ABANDON PIPING IN
FLOOR. PATCH, PAINT, INFILL AND
REFINISH WALL AND/OR FLOOR TO MATCH
EXISTING.
02 DEMOLISH INDUCTION UNIT AND
ASSOCIATED PIPING, SUPPORTS,
CONTROLS, AND ACCESSORIES. PROVIDE
CAP AT BRANCH TAKEOFF FROM MAIN.
03 DEMOLISH WINDOW AIR CONDITIONING
UNIT AND BLANKOFFS IN THE LOCATION
SHOWN COMPLETE. RESTORE WINDOW TO
WORKING CONDITION.
04 DEMOLISH FAN COIL UNIT, ASSOCIATED
DUCTWORK, PIPING, SUPPORTS, AND
CONTROLS COMPLETE.
05 EXISTING 4'' HOT WATER SUPPLY/RETURN
DOWN TO BASEMENT TO REMAIN.
06 EXISTING 4'' CHILLED WATER
SUPPLY/RETURN DOWN TO BASEMENT TO
REMAIN.
07 DEMOLISH CHILLED WATER, HOT WATER,
AND CONDENSATE DRAIN PIPING,
SUPPORTS, HANGERS, AND INSULATION
COMPLETE.
08 DEMOLISH DUCTWORK, HANGERS, AND
INSULATION COMPLETE.
09 DEMOLISH 16''X19'' EXHAUST DUCT AND
ASSOCIATED DUCTWORK COMPLETE.
10 THIS ROOM IS IN PHASE 3, SEE SHEET
GC101 FOR FURTHER INFORMATION.
11 THIS ELEVATOR LOBBY IS IN PHASE 3, SEE
SHEET GC101 FOR FURTHER
INFORMATION.
12 EXISTING DRAIN PIPING DOWN TO
BASEMENT TO REMAIN.
13 REMOVE DUCTLESS SPLIT SYSTEM INDOOR
UNIT AND OUTDOOR UNIT, AND TURN OVER
TO THE COR. REMOVE REFRIGERANT
PIPING AND PIPING AND EQUIPMENT
SUPPORTS. REFRIGERANT PIPING IS
ROUTED IN THE CRAWLSPACE.
01 01
01 01
03 03 03
04 (TYP.)
ETR 2 1/2'' CHR UP TO 2ND FLR
ETR 2 1/2'' CHS UP TO 2ND FLR
ETR 3'' HWR UP TO 2ND FLR
ETR 3'' HWS UP TO 2ND FLR
ETR 26''X14'' OUTSIDE AIR DUCT UP
02 02 02
02 02 02
04 (TYP.)
A. ASBESTOS IS PRESENT IN THE BUILDING
(PIPING MASTIC, DUCT MASTIC,
INSULATION, ETC.). ABATE ALL ASBESTOS
THAT IS DISTURBED AS A RESULT OF
WORK.
04(TYP.)
ETR 2'' DRAIN DN TO BASEMENT
ETR 4'' CHS UP TO 2ND FLOOR
ETR 4'' CHR UP TO 2ND FLOOR
ETR 3 1/2 '' CHS
ETR 3 1/2'' CHR
ETR HWS DN TO BASEMENT
ETR HWR DT TO BASEMENT
ETR 2'' DRAIN DN TO BASEMENT
ETR 5'' CHS DN TO BASEMENT
ETR 4'' CHR DN TO BASEMENT
ETR 4'' CHS DN TO BASEMENT
ETR 5'' CHR DN TO BASEMENT
ETR 4'' HWS DN TO BASEMENT
ETR 4'' HWR DN TO BASEMENT
ETR 4'' CHR DN TO BASEMENT
ETR 4'' CHS DN TO BASEMENT
ETR 2 1/2'' HWS
ETR 2 1/2'' HWR
ETR 3'' HWR UP TO2ND FLR
ETR 3'' HWS UP TO 2ND FLR
ETR 2 1/2'' CHS UP TO 2ND FLR
ETR 2 1/2'' CHR UP TO 2ND FLR
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
EX. RAD EX. RAD EX. RAD
EX. RAD
EX. RAD EX. RAD01 01
01 01 01
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:5
A M
MD104
FOURTH FLOOR MECHANICAL
DEMOLITION PLAN
05 21
TAMEKA J. TAYLOR
SWR
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
Scale: 1/8" = 1'-0"
FOURTH FLOOR MECHANICAL DEMOLITION PLAN 0 4 8 16
N O
R
TH
TRUE
01 DEMOLISH RADIATOR, ASSOCIATED PIPING,
SUPPORTS AND INSULATION COMPLETELY.
DO NOT ABANDON PIPING IN FLOOR. SEE
ARCHITECTURAL AD104 FOR WORK IN THIS
AREA.
A. ASBESTOS IS PRESENT IN THE BUILDING
(PIPING MASTIC, DUCT MASTIC,
INSULATION, ETC.). ABATE ALL ASBESTOS
THAT IS DISTURBED AS A RESULT OF
WORK.
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
14x8 x
10x12
16x12
8x8 x
24x2018x1610x8 x
18x12
18x1216x1214x1212x12 x x
CHR
CHS
MPS
CHR
CHS
HWS
HWR
MPS MPR
ETR1 1/2'' CHS/R DOWN
ETR 1 1/4'' HWS/R DOWN
CHR
CHS
EX. 20X16 EXHAUST
DUCT FROM BELOW
EX. 12X10 EXHAUST
DUCT FROM BELOW
EX. 16X10 RETURN
DUCT FROM
BELOW
EX. 10X10
EXHAUST DUCT
FROM BELOW
10x10 8x6 x x x
(EX) DOAS-1, ETR
(EX) AHU-1, ETR
MPR
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
DISCONNECT FROM
EXISTING GABLE
LOUVER, LOUVER TO
REMAIN
DISCONNECT FROM
EXISTING GABLE
LOUVER, LOUVER TO
REMAIN
DISCONNECT FROM
EXISTING GABLE
LOUVER, LOUVER
TO REMAIN
REMOVE HOT
WATER COIL AND
CONNECTED PIPING
10x30 x x
REMOVE
EXISTING RETURN
FAN AND
CONNECTED
DUCTWORK
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:5
A M
MD105
ROOF AND ATTIC MECHANICAL
DEMOLITION PLAN
06 21
TAMEKA J. TAYLOR
SM
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
Scale: 1/8" = 1'-0"
ROOF AND ATTIC MECHANICAL DEMOLITION PLAN 0 4 8 16
N O
R
TH
TRUE
01 DEMOLISH AIR HANDLING UNIT,
ASSOCIATED DUCTWORK, PIPING,
SUPPORTS, AND CONTROLS. UNIT WILL
NEED TO BE CUT UP INTO SMALL
COMPONENTS IN ORDER TO BE REMOVED.
02 DEMOLISH EXHAUST FAN AND ASSOCIATED
DUCTWORK, CONTROLS AND ACCESSORIES
AS SHOWN. COORDINATE PATCH AND
REPAIR OF THE EXTERIOR WALL WITH THE
ARCHITECTURAL CONTRACTOR.
03 REMOVE STEAM WATER PIPING, HANGERS,
AND SUPPORTS.
04 DEMOLISH EXISTING CHILLED WATER
PIPING FROM AIR HANDLING UNIT TO
IMMEDIATELY ABOVE FLOOR.
05 DEMOLISH EXISTING STEAM AND STEAM
CONDENSATE PIPING BACK TO
IMMEDIATELY ABOVE THE FLOOR
PENETRATION.
06 DEMOLISH EXISTING UTILITY VENT SET
RETURN FAN, CONTROLS AND DUCTWORK.
07 DEMOLISH RETURN DUCT AND FIRE
DAMPER BACK TO SLAB PENETRATION.
08 DEMOLISH SUPPLY DUCTWORK AND FIRE
DAMPER BACK TO SLAB PENETRATION.
09 DEMOLISH ALL CHILLED WATER, STEAM
AND STEAM CONDENSATE PIPING IN
PENTHOUSE BACK TO SLAB PENETRATION.
A. ASBESTOS IS PRESENT IN THE BUILDING
(PIPING MASTIC, DUCT MASTIC, INSULATION,
ETC.). ABATE ALL ASBESTOS THAT IS
DISTURBED AS A RESULT OF WORK.
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
2-FCU-13A 14x10 x
0 2-FCU-02
2-FCU-04
2-FCU-06
2-FCU-08
2-FCU-07B
2-FCU-07A
8x8
2-FCU-09
2-FCU-10B
2-FCU-10C
2-FCU-11B
2-FCU-11C
8x8
8x8
2-FCU-11D
6ø
2-FCU-11E
6ø
6x6
6ø6ø
6x6 6x6
8x8
2-FCU-11F
6ø
2-FCU-11G
8x8
6ø
6ø
6x8
4ø
8x6
12x8
2-FCU-11
8x8
2-FCU-11A
6ø
2-FCU-13B
2-FCU-14
2-FCU-15
2-FCU-17
2-FCU-18
2-FCU-20
2-FCU-16
2-FCU-19
2-FCU-21
2-FCU-22
2-FCU-23
2-FCU-25
2-FCU-24
2-FCU-26
2-FCU-28
2-FCU-27
2-FCU-30
2-FCU-29
2-FCU-31
2-FCU-36
2-FCU-35
2-FCU-34
2-FCU-38
2-FCU-332-FCU-32
2-FCU-39
2-FCU-37
2-FCU-48
2-FCU-47
4ø
8ø
2-FCU-42
2-FCU-44
6x6
6x6
8x8
6x6
2-FCU-41
2-FCU-40
2-FCU-43
x x
6x6
6x6
6x6
6ø
8x68x6
6ø
10ø
2-FCU-45
10x8
2-FCU-11H
6ø
2-FCU-46
24x12
12x8 x
10x8
8x6
20x12 x x x
10x10 x ø
14x10 12x8 x
10x8 8x8
8x10 8x8 x x x x x
12x8 10x8 x
8x6
8x8
8x6 x x x x x
12x8
8x8
16x8
10x8 x x
10x8 8x812x88x88x66x6
26x14 x x x
16x6 x
12x6 8x8 8x8
10x616x1216x1014x1014x8 ø
8ø 10x8 x
10x88ø
8ø x x ø
102A
123A
104A
117K
117J
117H
114G
117A
117B
117C 117D
117L
117E 117F
122 126
138A
STAIRS
126A
127A
127B
126E
126B 126D
128B
128E
128A
128C
128D
128F128G
128H
122121
126C
DAC-1
ACCU-1
DAC-2
ACCU-2
ACCU-3
x
MH105
MH105
2-FCU-01
x x
10x6 x
8x6
10x8
6x6 x x
8x8
DAC-3
2-FCU-05
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
8x8
20x16 x x
6x6
6x612x8 x x
6x6 x x
10x8 x
6x66 x x x x
10x88x6 x 66x6
2-EF-BIO
10x6
8x6
12x12
2-EF-ELEC
T
2-FCU-10A
x
6x6
8x6
6x6
2-FCU-03
6x6
8x8
6x6 6x6
8x6
2-FCU-49
x
14x10 x x
10x108ø
22x8 12x8
10x10
6x6 6x6
30x8 x
6x6
30x8
13 14
20x16
10x8
20x8
8ø
6x6
8x6
10x8
TRANSFER
DUCT
12x10 6x610x6
6x6
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:5
A M
MH101
FIRST FLOOR HVAC PLAN
07 21
TAMEKA J. TAYLOR
SM
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
Scale: 1/8" = 1'-0"
FIRST FLOOR HVAC PLAN
01 DUCT FULL SIZE OF FCU RETURN
CONNECTION.
02 PROVIDE DUCT TRANSITION FROM FAN COIL
UNIT OUTLET TO THE SIZE SHOWN.
COORDINATE WITH FCU SELECTION INLET
CONNECTION SIZE.
03 PROVIDE RETURN GRILLE AND SUPPORTS
COMPLETE.
04 PROVIDE SUPPLY DIFFUSER AND SUPPORTS
COMPLETE.
05 PROVIDE 4-PIPE FAN COIL UNIT, SUPPORTS,
AND CONTROLS COMPLETE.
06 NEW 20''X16'' EXHAUST DUCT FROM SHAFT
ABOVE. PROVIDE FIRE DAMPER AT SHAFT
PENETRATION. SEE ARCHITECTURAL FOR
EXACT SHAFT LOCATION.
07 NEW 20"x16'' EXHAUST DUCT FROM SHAFT
ABOVE. PROVIDE FIRE DAMPER AT SHAFT
PENETRATION. SEE ARCHITECTURAL FOR
EXACT SHAFT LOCATION.
08 DUCT FULL SIZE OF EXHAUST/SUPPLY GRILLE
CONNECTION.
09 FIRE DAMPER SHALL BE OUT-OF-THE-WALL,
"GRILLE ACCESS" TYPE.
10 NEW 12"x12" LOUVER CENTERED OVER DOOR
WITH FULL SIZE PLENUM BOX.
11 NEW 14"x14" LOUVER CENTERED OVER DOOR
WITH FULL SIZE PLENUM BOX.
12 NEW 16"x12" LOUVER CENTERED OVER DOOR
WITH FULL SIZE INSULATED PLENUM BOX.
13 NEW SIEMENS DDC FLOOR-LEVEL
CONTROLLER FOR HVAC EQUIPMENT ON
SOUTH SIDE OF FIRST FLOOR. CONTRACTOR
SHALL DETERMINE FINAL LOCATION BASED
ON COORDINATION WITH THE COR AND ALL
OTHER TRADES. FULLY INTEGRATE WITH
CAMPUS-WIDE SIEMENS DDC SYSTEM.
14 NEW SIEMENS DDC FLOOR-LEVEL
CONTROLLER FOR HVAC EQUIPMENT ON
NORTH SIDE OF FIRST FLOOR. CONTRACTOR
SHALL DETERMINE FINAL LOCATION BASED
ON COORDINATION WITH THE COR AND ALL
OTHER TRADES. FULLY INTEGRATE WITH
CAMPUS-WIDE SIEMENS DDC SYSTEM.
0 4 8 16
N O
R
TH
TRUE
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
08 (TYP.)
08 (TYP.)
A. WHERE A DUCT SIZE TO AN AIR DEVICE IS
NOT SHOWN, ASSUME DUCT IS THE SIZE
OF AIR DEVICE CONNECTION SIZE.
B. ALL ROUND DUCT TAKE-OFFS SHALL BE
MADE WITH SPIN-IN FITTINGS WITH
BALANCING DAMPER.
PROVIDE FAN INLET GUARD
FD
MOD
FD
FD
MOD
PROVIDE FAN
INLET GUARD
MOD
MD IN
VERTICAL
MD IN VERTICAL
MD IN
VERTICAL FD
10X6
TRANSFER
DUCT
PROVIDE MD IN
VERTICAL DUCT TO
GRILLE
MANUAL
BALANCING
DAMPER (TYP.)
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
RG-1 625 SD-3 160
SD-3 155
SD-3 155
SD-3 155
RG-1 115
SD-1 115
RG-1 180
SD-3 180
RG-1 180
SD-3 180
RG-1 120
SD-1 120
SD-1 110
SD-1 110
SD-1 105 SD-1 105
SD-1 105SD-1 105
RG-1 420
SD-1 120
RG-1 120
SD-1 80
SD-1 85
SD-2 25
RG-1 120
SD-1 120
RG-1 625
SD-3 160 SD-3 155SD-3 155SD-3 155
SD-3 170 SD-3 170
RG-1 340
SD-3 170 SD-3 170
RG-1 340
SD-3 155
SD-3 155
SD-2 30
RG-1 340
RG-1 625
SD-1 105
SD-1 105
SD-1 105
SD-1 105SD-1 105
SD-1 100
RG-1 185
SD-3 185
SD-1 110
SD-1 110
RG-1 220
RG-1 625
SD-1 105
SD-1 100
SD-1 105
SD-1 85
SD-1 85
SD-1 85
SD-1 85SD-4 270
RG-1 270
SD-1 85SD-1 80
SD-1 135
SD-1 135
RG-1 270
SD-1 105
RG-1 220
RG-1 340
EG-1 50
EG-5 100
EG-1 30
EG-2 50
EG-1 40
SG-3 50
SG-1 40
SG-1 30
SG-2 115
SG-1 60
SG-1 15
EG-1 25
SG-1 50
SG-1 25
EG-5 75
EG-1 30
EG-1 50
EG-1 60
EG-2 70
EG-2 40
EG-2 35
EG-2 35
EG-2 35
EG-4 200
EG-4 160
EG-1 50
EG-2 50
EG-2 35
EG-2 45
EG-2 30 EG-2 70
EG-3 105
SD-3 200
SG-1 35
SG-3 70
SG-3 40
SG-3 35
SG-3 35
SG-3 35
SG-4 165
SD-3 200
SG-3 35 SG-3 40
SG-5 105
SG-3 35
SG-3 45
SG-3 30
SG-3 70
SG-3 30
SG-1 35
SG-1 30
SG-2 100
EG-1 50
EG-5 120
EG-1 65
EG-6 440
EG-2 70
EG-1 35
EG-1 30
SG-3 70
EG-2 40
EG-2 30
SG-3 30
SG-3 35
SG-3 65
EG-2 65
EG-1 60
EG-1 30
EG-5 95
EG-1 30
EG-3 160
EG-4 175
EG-2 35
EG-2 40
EG-2 60
EG-1 55
EG-2 70
SG-3 70
SG-3 35
SG-3 70
SG-3 40
SG-4 160
SG-1 70
SG-2 125
SG-3 50
SG-3 70
SG-3 35
SG-1 25
SG-3 40
SG-3 60
SG-3 85
SG-6 245
SG-1 55
SG-1 65
SG-1 50
SG-2 120
SG-6 245
102A
123A
104A
117K
117J
117H
114G
117A 117B
117C 117D
117L
117E 117F
138A
STAIRS
126A
127A
127B
126E
126B 126D
128B
128E
128A
128C
128D
128F 128G
128H
122121
126C
EG-2 25
SG-2 140
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
EG-5 165
EG-2 40
SD-1 105
SD-1 105
SG-1 35
SD-1 120
RG-1 120
SD-3 200 SD-3 200
RG-1 120
SD-1 120
RG-1 375
EG-1 30
EG-1 40
SG-40 40
EG-7 100
SG-8 140
EG-2 80
SG-5 80
EG-4 200
EG-4 200
EG-4 160
EG-4 160
EG-1 50
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:0
A M
MH102
FIRST FLOOR AIR DEVICES PLAN
08 21
TAMEKA J. TAYLOR
SM
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
Scale: 1/8" = 1'-0"
FIRST FLOOR HVAC PLAN 0 4 8 16
N O
R
TH
TRUE
2'-2"
2'-2"
5'-1
2'-10"
1'-6"
NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
EX. SD 30
EX. SD 45
EX. SD 30
EX. SD 40
EX. SD 20
EX. SD 30
EX. SD 45 EX. SD 40
EX. SD 20
EX. SD 40
EX. SD 30
EX. SD 50
EX. SD 40
EX. SD 90
EX. SD 90
EX. SD 30
EX. SD 45
EX. SD 40
EX. SD 40EX. SD 40
EX. SD 30
EX. SD 30
EX. SD 30
EX. SD 45
EX. SD 45
EX. SD 25
EX. SD 30
EX. SD 20
EX. SD 30
EX. SD 30
EX. SD 20
EX. SD 40
EX. SD 50
EX. SD 20
EX. SD 30
EX. SD 40 EX. SD 40
EX. SD 120
EX. SD 50
EX. SD 65
EX. SD 80
EX. SD 60
EX. SD 80
EX. SD 35
EX. SD 30
EX. SD 20
EX. SD 20
EX. SD 40
EX. SD 55
EX. SD 40
EX. SD 40
EX. SD 40
EX. SD 30
EX. SD 45
EX. SD 90
EX. SD 90
EX. ED 290
EX. ED 70
EX. ED 70
EX. ED 70
EX. ED 65
EX. ED 65
EX. ED 60
EX. ED 155
EX. ED 15
EX. ED 15
EX. SD 30
EX. ED 15
EX. ED 20
EX. ED 15
EX. ED 15
EX. ED 20
EX. ED 25
EX. ED 20
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 25
EX. ED 20
EX. ED 35
EX. ED 35
EX. ED 50
EX. ED 35
EX. ED 35
EX. ED 35
EX. ED 50
EX. ED 60
EX. ED 65
55 80
EX. ED 55
EX. ED 25
EX. ED 40
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 30
EX. ED 65
EX. ED 35
EX. ED 45
EX. ED 60
EX. ED 50
EX. ED 35
EX. ED 85
EX. ED 30
EX. ED 35
EX. ED 25
EX. ED 80
(TYP.)
(TYP.)
10x8
EX. FCU
(TYP.)
EX. FCU
(TYP.)
01 NEW EXHAUST SHAFT WITH NEW 18"X18"
EXHAUST DUCT, SEE ARCHITECTURAL FOR
MORE INFORMATION.
02 REPLACE EXISTING 16"X19" EXHAUST DUCT
WITH NEW 20"X16" EXHAUST DUCT IN SHAFT.
03 BALANCE EXISTING EXHAUST GRILLE(S) IN
ROOM TO QUANTITY INDICATED.
04 BALANCE SUPPLY OUTDOOR AIRFLOW INTO
EXISTING FAN COIL UNIT TO QUANTITY
INDICATED. FOR ROOMS WITH MULTIPLE FAN
COIL UNITS, THE OUTSIDE AIR TO EACH UNIT
SHALL BE BALANCED TO THE QUANTITY
INDICATED. PERMANENTLY OPEN MOTORIZED
OUTSIDE AIR DAMPER TO EACH FAN COIL
UNIT.
05 PROVIDE NEW FIRE DAMPER AT FLOOR SLAB
PENETRATION.
06 RECONNECT EXISTING HORIZONTAL DUCT
LEAVING THE SHAFT INTO NEW DUCT RISER.
PROVIDE FIRE DAMPER AT SHAFT
PENETRATION. FIELD CONFIRM THE SIZE OF
THE EXISTING HORIZONTAL SHAFT PRIOR TO
ORDERING THE FIRE DAMPER.
07 PROVIDE 2" HPS AND 1
" LPR PIPING FROM
BASEMENT TO ROOF. REFER TO MH105 FOR
CONTINUATION.
A FOR ALL FAN COIL UNITS ON THIS FLOOR
REFER TO DETAIL 12 / M-501 FOR NEW
COMBINATION SHUT-OFF / STRAINER /
BALANCING VALVES TO BE ADDED TO BOTH
THE CHILLED WATER AND HEATING WATER
LINES. CONTROL VALVES TO REMAIN.
SECOND FLOOR MECHANICAL PLAN
Scale: 1/8" = 1'-0"
SECOND FLOOR MECHANICAL PLAN
0 4 8 16
N
O
R
T
H
TRUE
WALL RATING LEGEND
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
AREA OF WORK
KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
# 2
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
502-16-104
TAMEKA J. TAYLOR
1-9-2020
100% SUBMISSION
17-108
2495 SHREVEPORT HWY. PINEVILLE, LA 71360
REPLACE HVAC SYSTEM
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
S S S S
SWRPLH
MH103
09 21
N
N
EI
A
F
P
I
S
O
H
A
I
L
A
N
L
E
R
47721
E
N
G
O
N
T
R
SEAL
R
O
O
S
E
RC
P
A
U
L
H
O
L
L
O
W
A
Y
NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
EX. SD 40
EX. SD 60
EX. SD 60
EX. SD 20
EX. SD 20
EX. SD 65
EX. SD 90
EX. SD 90
EX. SD 35
EX. SD 45
EX. SD 50
EX. SD 65
EX. SD 45
EX. SD 40
EX. SD 20
EX. SD 40
EX. SD 30
EX. SD 60
EX. SD 90
EX. SD 35 EX. SD 35
EX. SD 240
EX. SD 35
EX. SD 50
EX. SD 80
EX. SD 70
EX. SD 25
EX. SD 25
EX. SD 45
EX. SD 80
EX. SD 80
EX. ED 285
EX. ED 75
EX. ED 65
EX. ED 65
EX. ED 80
EX. ED 40
EX. SD 20
EX. ED 25
EX. ED 15
EX. ED 15
EX. ED 15
EX. ED 30
EX. ED 70
EX. ED 45
EX. ED 55
EX. ED 55
EX. ED 55
EX. ED 15
EX. ED 30
EX. ED 35
EX. ED 65
EX. ED 50
EX. ED 35
EX. ED 215
EX. ED 80
EX. ED 80
EX. ED 40
EX. ED 100
EX. ED 35
EX. ED 60
EX. ED 40
EX. ED 55
EX. ED 190
(TYP)
(TYP)
EX. SD 45
EX. ED 35
EX. SD 50
EX. ED 80
EX. SD 20
EX. ED 15
EX. SD 50
EX. ED 80
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 30
EX. SD 45
EX. ED 35
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 25
EX. SD 30
EX. ED 30
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
EX. SD 45
EX. ED 35
10x8
EX. FCU
(TYP.)
EX. FCU
(TYP.)
01 REPLACE EXISTING 22"x18" EXHAUST DUCT IN
SHAFT WITH 36"x18" NEW EXHAUST DUCT.
02 DEMOLISH EXISTING JOHNSON CONTROLS
THREE WAY CONTROL VALVE AND PROVIDE
SIEMENS THREE WAY CONTROL VALVE IN IT'S
PLACE.
03 NEW EXHAUST SHAFT WITH 22"x22" EXHAUST
DUCT, SEE ARCHITECTURAL FOR MORE
INFORMATION.
04 BALANCE EXISTING EXHAUST GRILLE OR
REGISTER IN ROOM TO QUANTITY INDICATED.
05 BALANCE SUPPLY OUTDOOR AIRFLOW INTO
EXISTING FAN COIL UNIT TO QUANTITY
INDICATED. FOR ROOMS WITH MULTIPLE FAN
COIL UNITS, THE OUTSIDE AIR TO EACH UNIT
SHALL BE BALANCED TO THE QUANTITY
INDICATED. PERMANENTLY OPEN MOTORIZED
OUTSIDE AIR DAMPER TO EACH FAN COIL
UNIT.
06 RECONNECT EXISTING HORIZONTAL DUCT
LEAVING THE SHAFT INTO NEW DUCT RISER.
PROVIDE FIRE DAMPER AT SHAFT
PENETRATION. FIELD CONFIRM THE SIZE OF
THE EXISTING HORIZONTAL SHAFT PRIOR TO
ORDERING THE FIRE DAMPER.
07 PROVIDE 2" HPS AND 1
" LPR PIPING FROM
BASEMENT TO ROOF. REFER TO MH105 FOR
CONTINUATION.
THIRD FLOOR MECHANICAL PLAN
Scale: 1/8" = 1'-0"
THIRD FLOOR MECHANICAL PLAN
0 4 8 16
N
O
R
T
H
TRUE
A FOR ALL FAN COIL UNITS ON THIS FLOOR
REFER TO DETAIL 12 / M-501 FOR NEW
COMBINATION SHUT-OFF / STRAINER /
BALANCING VALVES TO BE ADDED TO BOTH
THE CHILLED WATER AND HEATING WATER
LINES. CONTROL VALVES TO REMAIN UNLESS
NOTED OTHERWISE TO BE REPLACED.
WALL RATING LEGEND
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
AREA OF WORK
KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
# 2
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
502-16-104
TAMEKA J. TAYLOR
1-9-2020
100% SUBMISSION
17-108
2495 SHREVEPORT HWY. PINEVILLE, LA 71360
REPLACE HVAC SYSTEM
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
S S S S
SWRPLH
MH104
10 21
N
N
EI
A
F
P
I
S
O
H
A
I
L
A
N
L
E
R
47721
E
N
G
O
N
T
R
SEAL
R
O
O
S
E
RC
P
A
H
O
L
L
O
W
A
Y
17'-10" 12'-9" 9'-0" 12'-9" 18'-6" 18'-6" 18'-3" 10'-6" 1'-2" 14'-9" 10'-8" 18'-4" 18'-3" 18'-3" 12'-7" 9'-3" 12'-8" 17'-9"
I RQP0NMLKJI.1HGFEDCBA
3.7
7.5
3.8
6.2
4.5
2.8
3.7
7.5
3.8
6.2
4.5
2.8
26x26 x
14x8 x
12x12 x
10x8 18x16 24x20 x
18x1216x1214x1212x12
16x1216x12
8x8
16x12
10x8 x x
36x18 x x
10x10 8x6 x x
18x12
CHS
CHR
CHR
CHS
HWS
HWR
C H
S
C H
R
CHR
CHS
EX. 1 1/4''
HWS/R
DOWN
12x10
(TYP.)
NEW 36''X18'' EXHAUST
DUCT DOWN INTO IN
EXISTING SHAFT.PROVIDE
NEW FIRE DAMPER AT
FLOOR SLAB
CONNECT TO EXISTING 26x14 FLAT
OVAL OUTSIDE AIR DUCT IN EXISTING
SHAFT. PROVIDE NEW FIRE DAMPER IN
FLOOR SLAB IN 26x14 FLAT OVAL DUCT
(CONFIRM DUCT SIZE IN FIELD).
CONNECT TO
EXIST. CHS/CHR
FR. BEL.
x
26x26
20x16
2 1/2" LPS
2" LPS 2"
1" LPR
3/4"
3/4" LPR
09 10
36x20
2-ERV-1
26x26
2-ERV-2
L P
R
2 1/2" LPS
2 1/2" LPS
1" LPR
C H
S
C H
R
TURN UP 26x26
26''X26'' NEW EXHAUST
DUCT DOWN THROUGH
ROOF.
MH105
MH105
MH105
MH105
P H
A S
E
S
E E
S H
E E
T G
C
P H
A S
E
S
E E
S H
E E
T G
C
16x12
SDT
SDT
SDT
S D T
2-EF-ATTIC
NEW PLENUM BOX FULL
SIZE OF GABLE LOUVER,
FIELD CONFIRM SIZE OF
LOUVER (APPOX. 40"x48")
MOD
26x20
NEW PLENUM BOX FULL SIZE
OF GABLE LOUVER, FIELD
CONFIRM SIZE OF LOUVER
(APPROX. 40"x48")
MOD
2-EF-ATTIC
26x20
NEW INSULATED PLENUM
BOX FULL SIZE OF GABLE
LOUVER, FIELD CONFIRM SIZE
OF LOUVER (APPOX. 40"x48")
MOD
T
2-EF-SLEEP
12x10
REMOVE EXISTING SHEET
METAL OVER ON GABLE
LOUVER AND INSTALL NEW
PLENUM BOX FULL SIZE OF
GABLE LOUVER, FIELD
CONFIRM SIZE OF LOUVER
(APPROX. 40"x48")
8x8
MOD
10x30 x
20x16
10x12
10x8
10x8
12x10
18x8
2-AH-1
3" CHR
3" CHS
x
26x26
2-AH-2
(TYP.)
SUPPORT ALL ROOFTOP PIPING 8' ON CENTER
WITH nVENT CADDY PYRAMID RL ADJUSTABLE
ROLLER SUPPORT (OR EQUAL). SIZE OF SUPPORT
AS REQUIRED BY PIPE SIZE. ADJUST HEIGHTS AS
NECESSARY. INSTALL PER MANUFACTURER'S
INSTRUCTIONS. SECURE FEET TO ROOF WITH
ROOFING MASTIC. MAINTAIN ROOF WARRANTY.
2" HPS
/2
L P
S
2-PRS-2 17
17 2-PRS-1
2" HPS
1 1/4" LPR
2-FT-1
2" HPS
192-FT-2
2"
1"
201"
2" 20
1 1/4" LPR
3/4" LPR
3/4" LPR
3/4" HPR
BOTTOM OF OUTSIDE
AIR INTAKE OPENING
SHALL BE MINIMUM
36" ABOVE THE ROOF
BOTTOM OF OUTSIDE
AIR INTAKE OPENING
SHALL BE MINIMUM
36" ABOVE THE ROOF
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
LINE TYPE LEGEND
NEW PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE DEMOLISHED
ROOF LEVEL
36' - 0"
20x36
26x26
12x16
3" CHS
3" CHR
3" CHS
EX. 1 1/4" HWR
2" LPS
3/4" LPR
2" LPS
3/4" LPR1" LPR
2 1/2" LPS
26x26
26x26
20x36
10x8
19x26Φ
EX.
EX.
SECOND FLOOR
14' - 0"
THIRD FLOOR
24' - 0"
ROOF LEVEL
36' - 0"
20x16
22x22
26x26 26x26
16x20
FIRE DAMPER IN
SECOND FLOOR SLAB FIRE DAMPER
ACCESS DOOR
(SIZE PER
SPECIFICATIONS)
16x20
16x20
16x32
18x36
18x36
FIRE DAMPER IN
ROOFTOP
PENTHOUSE
FLOOR SLAB
FIRE DAMPER IN
SECOND FLOOR SLAB
FIRE DAMPER
ACCESS DOOR
(SIZE PER
SPECIFICATIONS)
FIRE DAMPER ACCESS
DOOR (SIZE PER
SPECIFICATIONS)
ROOF LEVEL
36' - 0"
16x20
26x26
8x10 26x26
26x26
26x19Φ
1" LPR2 1/2" LPS
3" CHS
1 1/4" HWS 1 1/4" HWR
/2
C H
R
3" CHR
3" CHS
20x16 EX.
EX.
EX.
8x10
N
RN
47721
E
ENIG
O
NA
TR
F
SEAL
RP
OO ISS OE
H RCA
IL
A N
L
E
P A
U
L L . H O L L O
W A
Y
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
N
KEY PLAN
SCALE: NO SCALE
BUILDING 2
TRUE
SCOPE OF WORK
FULLY SPRINKLERED
100% CONSTRUCTION
DOCUMENTS
S S S S
/8
/2
:5
:0
A M
MH105
ROOF AND ATTIC MECHANICAL PLAN
11 21
TAMEKA J. TAYLOR
SM
REPLACE HVAC SYSTEM
2495 SHREVEPORT HWY. PINEVILLE,
LA 71360
1-9-2020
502-16-10417-108
PLH
Scale: 1/8" = 1'-0"
ROOF AND ATTIC MECHANICAL PLAN 0 4 8 16
N O
R
TH
TRUE
01 INSTALL NEW AIR HANDLING UNIT ON NEW 4''
CONCRETE PAD. UNIT SHALL HAVE 6'' INTEGRAL BASE
RAILS.
02 INSTALL ON INSULATED ROOF CURB. FLASH CURB
INTO EXISTING ROOFING SYSTEM. MAINTAIN EXISTING
ROOF WARRANTY.
03 MOUNT DUCTWORK ON nVENT CADDY PYRAMID
H-FRAME SUPPORTS (OR EQUAL), COMPLETE WITH
RUBBER "FEET", HORIZONTAL AND VERTICAL STEEL
MEMBERS, AND REQUIRED HARDWARE. WIDTH AS
REQUIRED BY DUCT SIZE. MAINTAIN EXISTING ROOF
WARRANTY. MAXIMUM DISTANCE BETWEEN
SUPPORTS SHALL BE 8 FEET OR AS RECOMMENDED
BY SUPPORT MANUFACTURER, WHICHEVER REQUIRES
MORE SUPPORTS.
04 CONNECT 26x26 TO EXISTING 26x19…