This is a solicitation for a construction project to replace an air handling unit at the James A. Haley VA Medical Center in Tampa, Florida. The solicitation is for project 673-21-151 to replace air handling unit ED-203. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8 is listed as the agency. Responses are due by April 17, 2023. The scope of work includes demolishing the existing air handling unit and associated components, and installing a new unit along with minor associated architectural, structural, mechanical, plumbing, and electrical work. An industrial hygienist study and hazardous material remediation are also included if needed.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs
James A Haley VA Hospital, Tampa, FL
“Replace Air Handling Unit ED-203”
673-21-151
100% Construction Documents Narrative
Contract Number:
36C24819D0022 36C24822N0366
March 29th, 2023
VA Tampa – Replace Air Handling Unit ED-203 Narrative
Department of Veterans Affairs
James A Haley VA Hospital, Tampa, FL
“Replace Air Handling Unit ED-203”
673-21-151
Project Location:
Tampa, FL 33612
Contract Number:
36C24819D0022 36C24822N0366
Contracting Officer (CO):
Cynda (Cindy) Rosa cynda.rosa@va.gov
Contracting Officer’s Representative (COR):
Paul Guerra
Paul.Guerra@va.gov
VA Tampa – Replace Air Handling Unit ED-203 Narrative
Table of Contents
I. Design Schedule
II. Architectural Narrative
III. Mechanical Narrative
a. Appendix C: Equipment Selections
IV. Electrical Narrative
V. Structural Narrative
VI. 95% Design Review Comments
1050 E. Southern Ave, Suite D, Tempe AZ 85282
480.454.2861, info@aesusdesign.com
A Service Disabled Veteran Owned Small Business
AE Replace Air Handling Unit ED‐203
Project Number: 673-21-151
James A. Haley VA Hospital, Tampa, FL 33612
Updated: 3/7/2023
NTP NTP/Kick Off Meeting 0 calendar days Thursday, March 31, 2022
Design Development
DD1 15% Submission
VA to Send Existing Drawings 1 calendar days Friday, April 1, 2022
On Site: Site Investigation 12 calendar days Wednesday, April 13, 2022
As Build Existing Building & Site Utilities
Virtual: DD1 Collaboration Meeting 7 calendar days Wednesday, April 20, 2022
Consultant Drawings Due to AESUS 5 calendar days Monday, April 25, 2022
DD1 Submission Due to VA 3 calendar days Thursday, April 28, 2022
Cost estimate to VA 7 days after submission 15% Submission Due NTP + 28 days
On Site: DD1 VA Review Meeting 13 calendar days Wednesday, May 11, 2022
DD2 30% Submission
Virtual: DD2 Collaboration Meeting 28 calendar days Wednesday, June 8, 2022
Consultant Drawings Due to AESUS 7 calendar days Wednesday, June 15, 2022
DD2 Submission Due to VA 7 calendar days Wednesday, June 22, 2022
Cost estimate to VA 7 days after submission 30% Submission Due NTP + 83 days
On Site: DD2 VA Review Meeting 14 calendar days Wednesday, July 6, 2022
Contract Documents
CD1 60% Submission
Begin Contract Document Stage 1 calendar days Thursday, July 7, 2022
Virtual: CD1 Collaboration Meeting 13 calendar days Wednesday, July 20, 2022
Consultant Drawings Due to AESUS 14 calendar days Wednesday, August 3, 2022
CD1 Submission Due to VA 7 calendar days Wednesday, August 10, 2022
Cost estimate to VA 7 days after submission 60% Submission Due NTP + 132 days
On Site: CD1 VA Review Meeting 14 calendar days Wednesday, August 24, 2022
CD2 90% Submission
Virtual: CD2 Collaboration Meeting 7 calendar days Wednesday, August 31, 2022
Consultant Drawings Due to AESUS 4 calendar days Sunday, September 4, 2022
CD2 Submission Due to VA 3 calendar days Wednesday, September 7, 2022
Cost estimate to VA 7 days after submission 90% Submission Due NTP + 160 days
On Site: CD2 VA Review Meeting 7 calendar days Wednesday, September 14, 2022
CD3 100% Submission
Consultant Drawings Due to AESUS 23 calendar days Friday, October 7, 2022
CD3 Submission Due to VA 8 calendar days Saturday, October 15, 2022
Cost estimate to VA 7 days after submission 100% Submission Due NTP + 198 days
On Site: CD3 Submission Review Meeting 5 calendar days Thursday, October 20, 2022
Contract Modification
CD3 100% Re-Submission
Modification Executed 132 calendar days Wednesday, March 1, 2023
Consultant Drawings Due to AESUS 21 calendar days Wednesday, March 22, 2023
CD3 Submission Due to VA 7 calendar days Wednesday, March 29, 2023
Cost estimate to VA 7 days after submission 100% Submission Due NTP + 356 days
Virtual: CD3 Submission Review Meeting 5 calendar days Monday, April 3, 2023
Bid Documents
Consultant Drawings Due to AESUS 7 calendar days Monday, April 10, 2023
Bid Submission Due to VA 7 calendar days Monday, April 17, 2023
Final Submission Due NTP + 375 days
VA Tampa – Replace Air Handling Unit ED-203 Architectural Narrative
AESUS Design Group A - 1
Architectural Narrative
Introduction
This project scope shall include but not be limited to replacing the Air Handler Unit ED-203 on the roof of Building One at the James A. Haley VA Hospital, located at 13000 Bruce B. Downs Boulevard, Tampa, Florida. This work will also include minor architectural, structural, mechanical, plumbing, and electrical.
In addition, this project shall include an Industrial Hygienist & a hazardous material remediation study.
The presence of hazardous material has been confirmed in the past in the hospital and is part of the scope to verify if hazardous material is present. OHC Environmental Engineering will visited the site and develop a work plans and specifications for this project as required for any hazardous material that is detected.
Demolition The project demolition will include removing the existing AHU, mechanical curbs, associated roofing, and the supply and return ducts will need to be upsized for the increased volume. See mechanical narrative for additional information.
Architectural The architectural scope for this project is limited to removing select ceilings, light fixtures, and mechanical grills to gain access to the bottom of the AHU and duct work located in the ceiling space of the emergency department. The architectural scope also includes coordinating and detailing the roof curbs and associated roof repairs.
The current AHU design intent is to remove the exist AHU and replace with new. The exist duct penetrations below the unit will be reused. The new AHU will be slightly raised up to allow the supply and return ducts to pass below the AHU and connect to the existing roof penetrations. We will provide a walking platform and stair for maintenance as part of the design. The walking platform will be integral with the AHU support. See attached drawings and structural for additional info.
Example walking platform and raised AHU:
AESUS Design Group A - 2
Structural The structural scope of work includes analyzing the existing structural capacity. Due to the new AHU requirements, the AHU will likely grow in size and weight. The new AHU will have a larger footprint and steel platform to distribute the additional loads.
Mechanical The mechanical scope is limited to removing and replacing the existing Air Handler Unit ED-203 and supply & return ducts over the emergency department. Therefore, the duct work and grills may be modified to support the new system and layout. See the mechanical narrative for additional information.
Plumbing General plumbing will not be required for this project.
Electrical The electrical scope is limited to disconnecting and reconnecting the existing AHU. Minor modifications to the existing electrical and low voltage may be required to support the new system.
The design intent will be to re-use the existing electrical circuit and reinstall all low voltage systems as required for the new layout.
Design Criteria All aspects of the design shall be in full compliance with VA design criteria as listed in VA design guides and manuals which can be found on the web at the VA Office of Facilities Management technical information library – site address: http://www.cfm.va.gov/TIL/.
The following codes and design criteria shall be utilized to the extent applicable:
VA Directives, Design Manuals, Master Specifications, VA National CAD Standard Application Guide, and other Guidance on the Technical Information Library (TIL) http://www.cfm.va.gov/til/.
International Building Code (IBC) (Only when specifically referenced in VA Design Documents, see notes below)
NFPA 101 Life Safety Code
NFPA National Fire Codes with the exception of NFPA 5000 and NFPA 900
Occupational, Safety and Health Administration (OSHA) Standards.
VA Seismic Design Requirements, H-18-8
National Electrical Code (NEC)
International Plumbing Code (IPC)
ASME Boiler and Pressure Vessel Code
ASME Code for Pressure Piping
Architectural Barriers Act Accessibility Standards (ABAAS) including VA supplement, Barrier Free Design Guide (PG-18-13)
Building Code Requirements for Reinforced Concrete, American Concrete Institute and Commentary (ACI 318)
Manual of Steel Construction, Load and Resistance Factor Design Specifications for Structural Steel Buildings, American Institute of Steel Construction (AISC)
Energy policy Act of 2005 (EPAct)
DOE Interim Final Rule: Energy Conservation Standards for New Federal, Commercial and Multi-Family High-Rise Residential Buildings and New Low-Rise Residential Buildings, 10 CFR Parts 433, 434 and 435.
Federal Leadership in High Performance and Sustainable Buildings: Memorandum of Understanding (MOU) http://www.cfm.va.gov/til/
AESUS Design Group A - 3
Executive Order 13423: Strengthening Federal Environmental, Energy, and Transportation Management.
The Provisions for Construction and Safety Signs. Stated in the General Requirements Section 01010 of the VA Master Construction Specification.
Ventilation for Acceptable Indoor Air Quality – ASHRAE Standard 62.1- 2004.
Safety Standard for Refrigeration Systems – ASHRAE Standard 15 – 2007.
Project Phasing Although this project will not ultimately affect life safety and/or egress, this project will need an in-depth discussion and phasing plan to understand how to keep hospital operations going when AHU ED-203 is offline. This project will include phasing to minimally impact the patient care and existing facility shutdowns. The contractor shall be required to perform construction operations during time frames approved by the hospital. Ultimately, the precise sequence will be determined after a building contractor has been selected and consultations among the hospital staff, facilities personnel, contractor, and architect can be arranged.
The following items shall be considered for this project prior to the start of construction:
Staging for construction materials and access information for contractor.
In-depth site walks with COR
Phasing and safety plans
Coordination drawing
Utilities/Outages
VA Tampa – Replace Air Handling Unit ED-203 Mechanical Narrative
AESUS Design Group MP-1
Introduction
This project scope shall include, but not be limited to the replacement of AHU ED-203 on the roof of
Building One at the James A. Haley VA Hospital, located at 13000 Bruce B. Downs Boulevard, Tampa.
Scope of Work
Replace AHU ED-203. The HVAC Systems need to be evaluated and updated to meet the latest HVAC Design Criteria. The A/E must evaluate the Chilled Water and the Hot Water / Steam System serving the design scope area.
Design Criteria
All aspects of the design shall be in full compliance with VA design criteria as listed in VA design guides and manuals which can be found on the web at the VA Office of Facilities Management technical information library – site address: http://www.cfm.va.gov/TIL/.
VA Directives, Design Manuals, Master Specifications, VA National CAD Standard Application Guide, and other Guidance on the Technical Information Library (TIL) http://www.cfm.va.gov/til/.
International Building Code (IBC) (Only when specifically referenced in VA Design Documents, see notes below)
NFPA 101 Life Safety Code
NFPA National Fire Codes with the exception of NFPA 5000 and NFPA 900
Occupational, Safety and Health Administration (OSHA) Standards.
VA Seismic Design Requirements, H-18-8
International Plumbing Code (IPC)
ASME Boiler and Pressure Vessel Code
ASME Code for Pressure Piping
Energy policy Act of 2005 (EPAct)
Ventilation for Acceptable Indoor Air Quality – ASHRAE Standard 62.1- 2004.
Safety Standard for Refrigeration Systems – ASHRAE Standard 15 – 2007.
Asbestos Containment
A hazardous survey is being conducted. There is likely to be asbestos in this area which potentially includes pipe or duct insulation. Refer to the Architectural/Asbestos narrative.
Demolition The project demolition work will include removing the existing AHU-ED-203 and associated ductwork.
See plans for detail
Mechanical Systems
Custom Outdoor AHU
A new AHU will be provided to serve the Emergency Department:
Total flow of 13,500 CFM
100% Outdoor Air
Pre-filter (MERV8, MERV11) http://www.cfm.va.gov/til/
AESUS Design Group MP-2
Pre-heat coil
Chilled Water o High Humidity and Dehumidification: Coil shall be equipped with electro-deposit coating (E-Coating) of 1-mil thick epoxy lining. Copper coils do not require any additional corrosion protection coatings. Coil velocity shall be maintained below 450 FPM to avoid condensate carry-over.
Humidification section utilizing building steam.
Supply Fans (6-total) with VFD, 30 HP Total, 480V-3Ph
Return Fans (6-total) with VFD, 18 HP Total, 480V-3Ph
Final filter (MERV17)
Air Changes
All rooms were verified for air changes and all either met or exceeded the minimum ACH per the VA Design Guide except for a corridor. See Below:
Room Number Room Name Area Volume ACH
Minimum
CFM
Actual CFM Check
1A-200 Entry 64 576 2 19.2 100 TRUE
1A-201 Waiting 414 3726 12 745.2 1800 TRUE
1A-203 Pre-Triage 93 837 6 83.7 150 TRUE
1A-206 Conf/Training 275 2475 6 247.5 540 TRUE
1A-207 RN Manager 117 1053 4 70.2 210 TRUE
1A-208 On Call 95 855 4 57 105 TRUE
1A-211 Staff Locker/Break 337 3033 4 202.2 510 TRUE
1A-213 Bereav/Counsel 78 702 4 46.8 100 TRUE
1A-214 EKG 80 720 6 72 85 TRUE
1A-215 Emergency Director 114 1026 4 68.4 115 TRUE
1A-217 Triage 3 117 1053 6 105.3 215 TRUE
1A-218 Triage 2 122 1098 6 109.8 215 TRUE
1A-219 Nurse Station 288 2592 6 259.2 415 TRUE
1A-220 Triage 1 117 1053 6 105.3 215 TRUE
1A-221 Unit Clerk 179 1611 6 161.1 345 TRUE
1A-222 Clean Linen 29 261 4 17.4 50 TRUE
1A-223 Secure Exam 122 1098 6 109.8 110 TRUE
1A-224 Clean Utility Equipment 220 1980 4 132 480 TRUE
1A-225 Mon Exam 15 129 1161 6 116.1 235 TRUE
1A-226 Mon Exam 14 130 1170 6 117 235 TRUE
1A-227 Mon Exam 13 125 1125 6 112.5 165 TRUE
1A-229 Mon Exam 12 125 1125 6 112.5 220 TRUE
1A-230 Mon Exam 11 126 1134 6 113.4 220 TRUE
1A-232 Mon Exam 10 126 1134 6 113.4 220 TRUE
1A-235 Mon Exam 9 126 1134 6 113.4 220 TRUE
1A-236 Procedure/Cast 227 2043 6 204.3 540 TRUE
1A-237 Mon Exam 8 127 1143 6 114.3 235 TRUE
1A-238 Clean Linen 20 180 4 12 50 TRUE
1A-239 Mon Exam 7 127 1143 6 114.3 235 TRUE
1A-241 Mon Exam 6 128 1152 6 115.2 195 TRUE
1A-242 EMT 64 576 6 57.6 110 TRUE
AESUS Design Group MP-3
1A-242a Meds 100 900 6 89.5 90 TRUE
1A-243 Mon Exam 5 128 1152 6 115.2 195 TRUE
1A-244 Mon Exam 4 128 1152 6 115.2 195 TRUE
1A-245 Radiography 279 2511 6 251.1 440 TRUE
1A-247 Mon Exam 3 129 1161 6 116.1 130 TRUE
1A-248 Vestibule 127 1143 2 38.1 100 TRUE
1A-249 Mon Exam 2 132 1188 6 118.8 120 TRUE
1A-250 Mon Exam 1 131 1179 6 117.9 120 TRUE
1A-253 PACS/Consult 75 675 6 67.5 155 TRUE
1A-254 Ambulance Storage 109 981 0 0 50 TRUE
1A-255 Decon 124 1116 0 0 90 TRUE
1A-256 Electrical 109 981 0 0 95 TRUE
C1-51-01 Corridor 396 3564 2 118.8 540 TRUE
C1-52-01 Corridor 545 4905 2 163.5 375 TRUE
C1-53-01 Corridor 363 3267 2 108.9 200 TRUE
C1-54-01 Corridor 370 3330 2 111 100 FALSE
C1-55-01 Corridor 131 1179 2 39.3 170 TRUE
C1-56-01 Corridor 206 1854 2 61.8 100 TRUE
C1-57-01 Corridor 669 6021 2 200.7 335 TRUE
Chilled water pumps – the chilled water pumps were analyzed will be replaced due to the Epidemic AHU requirements of 100% OA.
o Existing Pump Characteristics
200 GPM
50 feet of head o New Pump Characteristics
243 GPM
55 feet of head
Heating hot water pumps – the heating hot water pumps were analyzed will be replaced due to the Epidemic AHU requirements of 100% OA.
o Existing Pump Characteristics
40 GPM
50 feet of head o New Pump Characteristics
47.5 GPM
50 feet of head
Supply air main – Velocities were evaluated in the existing supply air duct system and the SA was verified to be undersized and will be replaced along with ancillary ductwork found to be undersized. Below is a figure of showing the velocity of the mains
AESUS Design Group MP-4
Return air main - Velocities were evaluated in the existing return air duct system and the RA was verified to be properly sized. Below is a figure of showing the velocity of the main.
AESUS Design Group MP-5
Exhaust system o The dedicated exhaust system is existing to remain. The exhaust rates of each room are not being changed, therefore, there is no need to replace the exhaust fans.
o The new AHU has a dedicated return/exhaust fan that is capable of exhausting the air when the unit converts to 100% OA in the event of a pandemic.
Chilled water system – The chilled water system was analyzed and determined to be sized appropriately for the new 100% OA requirement.
Heating hot water system – The heating hot water system was analyzed and determined to be sized appropriately for the new 100% OA requirement. We reached out to the manufacturer and it was indicated that the existing heat exchangers have the capacity to perform at the new levels without any modifications. The existing heat exchanger are existing to remain.
Humidification – The humidification will be provided by campus steam.
Plumbing
Condensate drains will be routed from new AHU to existing roof drain.
AESUS Design Group MP-6
Appendix D: Equipment Selections
Job Information Technical Data Sheet
Job Name VA Tampa
Date March 09 2023
Submitted By JS
Software Version 13.04
Unit Tag AHU-1
Unit Overview
Model Number
Supply Return/Exhaust
Air
Volume cfm
Static Pressure External Dimensions Air
Volume cfm
Static Pressure External Dimensions
External inWc
Total inWc
Height in
Width in
Length in
External inWc
Total inWc
Height in
Width in
Length in
CAH039GDCM 13500 2.00 5.29 102* 72* 404** 7000 2.00 2.06 102* 72* 404**
*Not including base rails, coil connectors, drain connectors and control boxes.
**The supply and return lengths display total unit length (not including hoods).
Unit
Model Number: CAH039GDCM
Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label)
Outer Panel: Painted 24 gauge G60 Galvanized Steel
Liner: 24 gauge Galvanized Steel (unless noted per section)
Insulation: R-13 Injected Foam
Unit Configuration: Inline horizontal Drive (Handling) Location: Left
Base: 10" formed channel Wall Thickness: 2 in
Altitude: 0 ft Parts Warranty: Standard One Year
Exhaust Air Stream
Plenum Section Component: 1 Length: 52 in Shipping Section: 1
Air Pressure Drop
0.02 inWc
Custom Openings
Custom Opening Location Width Height Rainhood w/Screen
1 Bottom 68 in 24 in None
Door
Location Width Opening
Drive side 30 in Outward
Return/Exhaust Fan Array Component: 2 Length: 24 in Shipping Section: 1
Fan Performance
Air
Volume*
Static Pressure Fan Energy
Index(FEI)
Total Input
Power
Fan Shaft
Power*
Speed Redundancy(N-1) Fan Circuit
External Total Cabinet Operating Maximum MOP MCA
2333 cfm 2.00 inWc 2.06 inWc 0.00 inWc 1.72 2.7 kW 1.10 BHP 2229 rpm 3300 rpm 100.0 % 15.0 A 14.6 A
Fan Data
Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location
ECM / 2x2 : 3 Airfoil / N/A 3 13.98 in 5 Axial Behind Fan
Motor Data
Power* Electrical Supply Speed Control Signal Full Load Current*
4.4 HP 460/60/3 V/Hz/Phase 3300 rpm 0-10V 4.50 A
Fan Options
Piezometer Ring: 1 ring per array Piezometer Delta P: 2.89
Transducer:
Output signal = 4-20 mA Input power = 10-35 VDC or 16-26
VAC
Isolator Type: Rigid
Control Data
Selection Type: Integrated Drive Vendor: Daikin Applied
Auxiliary Control: Disconnect w/ motor starter Voltage: 460 V
Disconnect Type: Fused Height x Width x Depth: 23.60 in x 15.75 in x 10.76 in
Mounting: Drive Side Enclosure: NEMA 3R
Control box: Basic controls, unit mounted power box, drive side
Panel
Location Width Opening
Removable panels - in Outward
Notes
* after a unit label denotes the data for an individual fan.
Access Section Component: 3 Length: 30 in Shipping Section: 1
Air Pressure Drop
0.00 inWc
Door
Location Width Opening
Drive side 26 in Outward
Special Options
Tread Plate Floor Liner Sound Baffle
Tread plate installed (As casing details)
Economizer Component: 4 Length: 40 in Shipping Section: 2
Portion Damper Blade Action Rated CFM Air Pressure
Drop
Quantity
Size (length x width) Location Type Actuation
Overall Opening
Outside Air 36 in x 92 in 32 in x 82 in Right UltraSeal
Low Leak NA Parallel 13500 cfm 0.04 inWc 1
Return Air 18 in x 92 in 14 in x 82 in Internal UltraSeal
Low Leak NA Parallel 7000 cfm 0.06 inWc 1
Exhaust Air 22 in x 92 in 18 in x 82 in Left UltraSeal
Low Leak NA Parallel 7000 cfm 0.03 inWc 1
VXTZ56 VA Tampa 2 3/9/2023
Supply Air Stream
Access Section Component: 1 Length: 24 in Shipping Section: 2
Air Pressure Drop
0.00 inWc
Door
Location Width Opening
Drive side 20 in Outward
Combination Filter Component: 2 Length: 16 in Shipping Section: 2
Access Face Velocity Face Area Air Volume
Side 314 ft/min 42.9 13500 cfm
Portion Type Efficiency Air Pressure Drop Number of
Filters
Height Width Depth
Clean Air Mean Air Dirty Air User Spec
Pre-Filter Pleated MERV 8 0.12 inWc 0.56 inWc 1.00 inWc N/A 8 24 in 24 in 2 in
4 24 in 20 in 2 in
Filter Pre Pleat MERV 13 0.12 inWc 0.56 inWc 1.00 inWc N/A 8 24 in 24 in 4 in
4 24 in 20 in 4 in
Door
Location Width Opening
Drive side 12 in Outward
Special Options
Sound Baffle Pre-Filter Gauge Final-Filter Gauge
(As casing details) Magnehelic Magnehelic
Future Chilled Water Coil Component: 3 Length: 42 in Shipping Section: 2
Number of Coils Number of Rows
2 2 Coil Air Pressure Drop Finned Height Finned Width Face Area Face Velocity
0.05 inWc 45 in 59 in 36.88 366 ft/min
Connection Location Connection Material
Drive side Carbon steel Coil Model Drain Pan Drain Pan Side
Future Coil (Not Supplied) Stainless steel Opp drive side
AHRI 410 Certification
Coil is NOT certified by AHRI
Door
Location Width Opening
Drive side 26 in Outward
Special Options
Liner Sound Baffle
24 gauge Stainless Steel (As casing details)
VXTZ56 VA Tampa 3 3/9/2023
Hot Water Coil Component: 4 Length: 12 in Shipping Section: 2
Coil Model Total Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing
(Face x Row)
5WQ0801C 435870 Btu/hr 2 1 8 0.625 in 1.50 in x 1.299 in
Air Volume Air Temperature Coil Air Pressure
Drop
Finned Height Finned Length Face Area Face Velocity
Entering Leaving
Dry Bulb Dry Bulb
13500 cfm 34.8 64.3 0.10 inWc 42 in 56 in 32.67 413 ft/min
Water Flow Rate Pressure Drop Velocity Volume Weight
Entering Leaving
150.0 119.4 28.40 gpm 2.80 ftHd 2.20 ft/s 8.0 gal 70.00 lb
Connection [Data Per Coil] Min. Fin Surface
Temp.
Min. Tube Wall
Surface Temp.
Fouling Factor
Type Size Location Material
Threaded 1.50 in Drive side Carbon steel 119.4 119.4 0.000
Material Drain Pan Drain Side Electro-Fin Coat
Fin Tube Header Case
Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Opp drive side With coating
AHRI 410 Certification
Coil is NOT certified by AHRI
Chilled Water Coil Component: 5 Length: 54 in Shipping Section: 3
Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing
(Face x Row)
5WS1106C 1244568 Btu/hr 622439 Btu/hr 2 6 11 0.625 in 1.50 in x 1.299 in
Air Volume Air Temperature Coil Air
Pressure
Drop
Finned
Height
Finned
Length
Face Area Face
VelocityEntering Leaving
Dry Bulb Wet Bulb Dry Bulb Wet Bulb
13500 cfm 92.4 77.4 50.2 50.0 0.80 inWc 45 in 59 in 36.88 366 ft/min
Water Flow Rate Pressure Drop Velocity Volume Weight
Entering Leaving
42.0 52.0 247.80 gpm 11.70 ftHd 4.40 ft/s 31.0 gal 263.00 lb
Connection [Data Per Coil] Min. Fin Surface
Temp.
Min. Tube Wall
Surface Temp.
Fouling Factor
Type Size Location Material
Threaded 3.00 in Drive side Carbon steel 42.0 42.0 0.000
Material Drain Pan Drain Side Electro-Fin Coat
Fin Tube Header Case
Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Opp drive side With coating
AHRI 410 Certification
Coil is NOT certified by AHRI
Door
Location Width Opening
Drive side 30 in Outward
VXTZ56 VA Tampa 4 3/9/2023
Supply Fan Array Component: 6 Length: 24 in Shipping Section: 3
Fan Performance
Air
Volume*
Static Pressure Fan Energy
Index(FEI)
Total Input
Power
Fan Shaft
Power*
Speed Redundancy(N-1) Fan Circuit
External Total Cabinet Operating Maximum MOP MCA
2700 cfm 2.00 inWc 5.29 inWc 0.00 inWc 1.46 13.3 kW 3.23 BHP 3162 rpm 3300 rpm 96.4 % 25.0 A 23.6 A
Fan Data
Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location
ECM / 3x2 : 5 Airfoil / N/A 5 13.98 in 5 Axial Behind Fan
Motor Data
Power* Electrical Supply Speed Control Signal Full Load Current*
4.4 HP 460/60/3 V/Hz/Phase 3300 rpm 0-10V 4.50 A
Fan Options
Piezometer Ring: 1 ring per array Piezometer Delta P: 3.88
Transducer:
Output signal = 4-20 mA Input power = 10-35 VDC or 16-26
VAC
Isolator Type: Rigid
Control Data
Selection Type: Integrated Drive Vendor: Daikin Applied
Auxiliary Control: Disconnect w/ motor starter Voltage: 460 V
Disconnect Type: Fused Height x Width x Depth: 23.60 in x 15.75 in x 10.76 in
Mounting: Drive Side Enclosure: NEMA 3R
Control box: Basic controls, unit mounted power box, drive side
Panel
Location Width Opening
Removable panels - in Outward
Notes
* after a unit label denotes the data for an individual fan.
Access Section Component: 7 Length: 30 in Shipping Section: 3
Air Pressure Drop
0.00 inWc
Door
Location Width Opening
Drive side 26 in Outward
Special Options
Tread Plate Floor Liner Sound Baffle
Tread plate installed (As casing details)
Combination Filter Component: 8 Length: 20 in Shipping Section: 3
Access Face Velocity Face Area Air Volume
Front 397 ft/min 34.0 13500 cfm
Portion Type Efficiency Air Pressure Drop Number of
Filters
Height Width Depth
Clean Air Mean Air Dirty Air User Spec
Filter HEPA
MERV 17
(99.97%)
1.07 inWc 1.93 inWc 2.80 inWc N/A
6 24 in 24 in 12 in
3 24 in 12 in 12 in
2 12 in 24 in 12 in
Special Options
Sound Baffle Filter Gauge
(As casing details) Magnehelic 0-5"
VXTZ56 VA Tampa 5 3/9/2023
Plenum Section Component: 9 Length: 36 in Shipping Section: 4
Air Pressure Drop
0.09 inWc
Custom Openings
Custom Opening Location Width Height Rainhood w/Screen
1 Bottom 68 in 24 in None
Door
Location Width Opening
Drive side 28 in Outward
Unit Sound Power (dB)
Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
Radiated: 69 63 73 60 58 50 46 51
Unit Discharge: 70 65 80 69 67 63 56 51
Unit Return: 69 63 73 60 58 55 56 55
Shipping Section Details
Section Length in
Weight lb
Corner Weights (lb) Center of Gravity (in)
P1 P2 P3 P4 XX YY ZZ
1 106 1822 424 443 487 468 56 37 48
2 134 2268 489 496 645 638 76 36 50
3 128 3548 1082 1144 692 630 48 37 51
4 36 566 142 142 142 142 18 36 49
Entire Unit 404 8204 1888 1977 2214 2125 214 37 50
NOTE: Special components aren't included in the corner weights and center of gravity data.
Supply Static Pressure Drop
Component Option Static Pressure Drop
Economizer Damper 0.06 insWg
Access Section Access Section
Panel and Bag Filter Panel and Bag Filter 1.12 insWg
Chilled Water coil Chilled Water coil 0.05 insWg
Hot Water Coil Hot Water Coil 0.10 insWg
Chilled Water coil Chilled Water coil 0.80 insWg
Supply Fan Cabinet
Access Section Access Section
Panel and Bag Filter Panel and Bag Filter 1.07 insWg
Plenum Section Plenum Section 0.09 insWg
External Static External Static 2.00 insWg
Total Supply Fan Static 5.29 insWg
VXTZ56 VA Tampa 6 3/9/2023
Exhaust Static Pressure Drop
Component Option Static Pressure Drop
Plenum Section Plenum Section 0.02 insWg
Return Fan Cabinet
Access Section Access Section
Economizer Damper 0.03 insWg
External Static External Static 2.00 insWg
Total Return/Exhaust Fan Static 2.06 insWg
Minimum Recommended Drain Pan Trap Dimensions
Shipping Section Component H
2 Chilled Water coil 2.46
2 Hot Water Coil 2.66
3 Chilled Water coil 4.26
Dimensions provided as a courtesy and are recommended minimums only. Daikin is not responsible for supplying or designing drain pan traps and is not responsible for any damage caused by incorrect trap heights. The dimensions listed above should be reviewed and approved by a licensed plumbing professional.
AHRI Certification
The air-handler is selected outside of the scope of AHRI Standard 430/431
Notes
Standard
1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2007. The approving authority is responsible for compliance of multi - component building systems.
VXTZ56 VA Tampa 7 3/9/2023
VXTZ56 VA Tampa 8 3/9/2023
VXTZ56 VA Tampa 9 3/9/2023
V X
TZ5
V A Tam p a
/9 /2
TZ5
V A Tam p a
/9 /2
TZ5
V A Tam p a
/9 /2
TZ5
V A Tam p a
/9 /2
TZ5
V A Tam p a
/9 /2
TZ5
V A Tam p a
/9 /2
TZ5
V A Tam p a
/9 /2
PART 1: GENERAL
1.01 SECTION INCLUDES
A. Indoor Air Handling Units.
1.02 REFERENCES
A. AFBMA 9 - Load Ratings and Fatigue Life for Ball Bearings.
B. AMCA 99 - Standards Handbook.
C. AMCA 210 - Laboratory Methods of Testing Fans for Rating Purposes.
D. AMCA 300 - Test Code for Sound Rating Air Moving Devices.
E. AMCA 500 - Test Methods for Louver, Dampers, and Shutters.
F. AHRI 410 - Forced-Circulation Air-Cooling and Air-Heating Coils.
G. AHRI 430 - Central-Station Air-Handling Units.
H. AHRI 435 - Application of Central-Station Air-Handling Units.
I. ASTMB117 - Standard Practice for Operating Salt Spray Apparatus.
J. NEMA MG1 - Motors and Generators.
K. NFPA 70 - National Electrical Code.
L. SMACNA - HVAC Duct Construction Standards - Metal and Flexible.
M. UL 723 - Test for Surface Burning Characteristics of Building Materials.
N. UL 900 - Test Performance of Air Filter Units.
O. UL 1995 - Standard for Heating and Cooling Equipment.
P. UL 94 - Test for Flammability of Plastic Materials for Parts in Devices and Appliances.
Q. IBC 2000, 2003 - International Building Code.
R. NFPA 90A - Standard for the Installation of Air Conditioning and Ventilating Systems.
S. NFPA 5000 - Building Construction and Safety Code.
T. ASHRAE 90.1 Energy Code.
U. AHRI Standard 1060 - Rating Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment.
V. GSA 2003 Facilities Standard - 5.9 HVAC Systems and Components.
1.03 SUBMITTALS
A. Shop Drawings: Indicate assembly, unit dimensions, weight loading, required clearances, construction details, field connection details, and electrical characteristics and connection requirements. Computer generated fan curves for each air handling unit shall be submitted with specific design operating point noted. A computer generated psychometric chart shall be submitted for each cooling coil with design points and final operating point clearly noted. Sound data for discharge, radiated and return positions shall be submitted by octave band for each unit. Calculations for required baserail heights to satisfy condensate trapping requirements of cooling coil shall be included.
B. Product Data:
1. Provide literature that indicates dimensions, weights, capacities, ratings, fan performance, finishes of materials, electrical characteristics, and connection requirements.
2. Provide data of filter media, filter performance data, filter assembly, and filter frames.
3. Provide manufacturer's installation instructions.
1.04 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing Air Handler products specified in this section must show a minimum five years documented experience and complete catalog data on total product.
1.05 SAFETY AGENCY LISTED & CERTIFICATION
VXTZ56 VA Tampa 17 3/9/2023
A. Air Handling units shall be cETLus safety listed to conform with UL Standard 1995 and CAN/CSA Standard
C22.2 No. 236. Units shall be accepted for use in New York City by the Department of Building, MEA 342-99-E.
B. Air handler furnished with double width, double inlet (DWDI) fans and/or plenum fans where applicable, shall be certified in accordance with the central station air handling units certification program, which is based on AHRI Standard 430. (NOTE: Above does not apply to fan array)
C. Air handling unit water heating & cooling coils shall be certified in accordance with the forced circulation air cooling and air heating coils certification program, which is based on AHRI Standard 410.
1.06 DELIVERY, STORAGE, AND HANDLING
A. Deliver, store, protect and handle products to site.
B. Accept products on site on factory-furnished shipping skids. Inspect for damage.
C. Store in clean dry place and protect from construction traffic. Handle carefully to avoid damage to components, enclosures, and finish.
PART 2: PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. The following manufacturers are approved for use. No substitutions will be permitted.
1. Daikin Applied 'Vision' Air Handler shall be the basis of design.
2. Miller-Picking
3. Temtrol
4. Scott-Springfield
5. Racan-Carrier Company
2.02 GENERAL DESCRIPTION
A. Configuration: Fabricate as detailed on drawings.
B. Performance: Conform to AHRI 430. See schedules on prints. (NOTE: above does not apply to fan array)
C. Acoustics: Sound power levels (dB) for the unit shall not exceed the specified levels shown on the unit schedule. The manufacturer shall provide the necessary sound treatment to meet these levels if required.
2.03 UNIT CONSTRUCTION
A. Fabricate unit with heavy gauge channel posts and panels secured with mechanical fasteners. All panels, access doors, and ship sections shall be sealed with permanently applied bulb-type gasket. Shipped loose gasketing is not allowed.
B. Panels and access doors shall be constructed as a 2-inch nominal thick; thermal broke double wall assembly, injected with foam insulation with an R-value of not less than R-13.
1. The inner liner shall be constructed of G90 galvanized steel.
2. Exterior surfaces shall be constructed of painted galvanized steel, for aesthetics and long-term durability.
Paint finish will include a base primer with a high-quality polyester resin topcoat. Finished, unabraded panel surfaces shall be exposed to an ASTM B117 salt spray environment and exhibit no visible red rust at a minimum of 3,000 hours exposure. Finished, abraded surfaces shall be tested per ASTM D1654, having a environment. Measurements of results shall be quantified using ASTM D1654 in conjunction with ASTM
D610 and ASTM D714 to evaluate blister and rust ratings.
3. The floor plate shall be constructed as specified for the inner liner.
4. Unit will be furnished with solid inner liners.
C. Panel deflection shall not exceed L/240 ratio at 125% of design static pressure, maximum 5 inches of positive or 6 inches of negative static pressure. Deflection shall be measured at the panel midpoint.
VXTZ56 VA Tampa 18 3/9/2023
D. The casing leakage rate shall not exceed 0.50 cfm per square foot of casing surface area at design static
(.0025 m3/s per square meter of cabinet area at 1.24 kPa static pressure)
E. Module to module field assembly shall be accomplished with an overlapping, full perimeter internal splice joint that is sealed with bulb type gasketing on both mating modules to minimize on-site labor and meet indoor air quality standards.
F. Access doors shall be flush mounted to cabinetry, with minimum of two six inch long stainless steel piano-type hinges, latch and full size handle assembly. Access doors shall swing outward for unit sections under negative pressure. Access doors on positive pressure sections, shall have a secondary latch to relieve pressure and prevent injury upon access.
G. A 10-inch formed G60 galvanized steel base rail shall be provided by the unit manufacturer for structural rigidity and condensate trapping.. The base rail shall be constructed with 12-gauge nominal for unit sizes 003 -
035 and 10-gauge nominal for unit sizes 040 - 090. The following calculation shall determine the required height of the baserail to allow for adequate drainage. Use the largest pressure to determine base rail height.
factory supplied at this height, the contractor is required to supply a concrete housekeeping pad to make up the difference.
H. Construct drain pans from stainless steel with cross break and double sloping pitch to drain connection.
base rail to aid in proper condensate trapping. Drain connections that protrude from the base rail are not
2.04 FAN ASSEMBLIES
A. Provide ECM, motorized impeller fan(s). Fan assembly shall include fan, fan base, and a motor and shall be dynamically balanced by the fan manufacturer.
1. Fan array shall be equipped with a piezometer point to measure airflow. One piezometer point shall be supplied on one fan in the fan array.
2. Motor control panel shall come with a low voltage terminal strip and shall include terminals for Fan
ON/OFF, 0-10V signal, and fan fault.
3. Motor control panel shall come equipped with a fused disconnect.
4. Fan section shall come equipped with a motor control panel mounted on the fan section. Both line voltage and low voltage wiring shall be done by the factory. Each fan shall have an isolation switch.
5. Motor shall be brushless DC type with a permanent magnet rotor.
6. Inverter shall be integral to the motor and come as an assembly from the fan manufacturer.
2.05 BEARINGS, SHAFTS, AND DRIVES
A. Shafts shall be solid, hot rolled steel, ground and polished, keyed to shaft, and protectively coated with lubricating oil. Hollow shafts are not acceptable.
2.06 ELECTRICAL
A. The air handler(s) shall be ETL and ETL-Canada listed by Intertek Testing Services, Inc. Units shall conform to bi-national standard ANSI/UL Standard 1995/CSA Standard C22.2 No. 236.
B. Wiring Termination: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclosed terminal lugs in terminal box sized to NFPA 70.
C. Manufacturer shall provide ASHRAE 90.1 Energy Efficiency equation details for individual equipment to assist Building Engineer for calculating system compliance.
D. Installing contractor shall provide GFI receptacle within 25 feet of unit to satisfy National Electrical Code requirements.
VXTZ56 VA Tampa 19 3/9/2023
2.07 COOLING AND HEATING COILS
A. Certification: Acceptable water cooling, water heating, steam, and refrigerant coils shall be certified in manufacturer is a current member of the AHRI Forced Circulation Air-Cooling and Air-Heating Coils certification programs and that the coils have been rated in accordance with AHRI Standard 410. Manufacturer must be
ISO 9002 certified.
B. Water cooling coil shall be provided. Provide access to coil(s) for service and cleaning. Enclose coil headers and return bends fully within unit casing. Unit shall be provided with coil connections that extend a minimum casing. Coil connections must be factory sealed with grommets on interior and exterior panel liners to minimize air leakage and condensation inside panel assembly. If not factory packaged, Contractor must supply all coil connection grommets and sleeves. Coils shall be removable through side and/or top panels of unit without the need to remove and disassemble the entire section from the unit.
1. Headers shall consist of seamless copper tubing to assure compatibility with primary surface. Headers to have intruded tube holes to provide maximum brazing surface for tube to header joint, strength, and inherent flexibility. Header diameter should vary with fluid flow requirements.
2. Fins shall have a minimum thickness of 0.0075 inch aluminum plate construction. Fins shall have full drawn collars to provide a continuous surface cover over the entire tube for maximum heat transfer. Tubes shall be mechanically expanded into the fins to provide a continuous primary to secondary compression bond over the entire finned length for maximum heat transfer rates. Bare copper tubes shall not be visible between fins.
3. Coil tubes shall be 5/8 inch OD seamless copper, 0.020 inch nominal tube wall thickness, expanded into fins, brazed at joints.
4. Coil connections shall be carbon steel, NPT threaded connection. Connection size to be determined by manufacturer based upon the most efficient coil circuiting. Vent and drain fittings shall be furnished on the connections, exterior to the air handler. Vent connections provided at the highest point to assure proper venting. Drain connections shall be provided at the lowest point to insure complete drainage and prevent freeze-up.
5. Coil casing shall be a formed channel frame of galvanized steel.
C. Water heating coil shall be provided. Provide access to coil(s) for service and cleaning. Enclose coil headers and return bends fully within unit casing. Unit shall be provided with coil connections that extend a minimum casing. Coil connections must be factory sealed with grommets on interior and exterior panel liners to minimize air leakage and condensation inside panel assembly. If not factory packaged, Contractor must supply all coil connection grommets and sleeves. Coils shall be removable through side and/or top panels of unit without the need to remove and disassemble the entire section from the unit.
1. Headers shall consist of seamless copper tubing to assure compatibility with primary surface. Headers to have intruded tube holes to provide maximum brazing surface for tube to header joint, strength, and inherent flexibility. Header diameter should vary with fluid flow requirements.
2. Fins shall have a minimum thickness of 0.0075 inch aluminum plate construction. Fins shall have full drawn collars to provide a continuous surface cover over the entire tube for maximum heat transfer. Tubes shall be mechanically expanded into the fins to provide a continuous primary to secondary compression bond over the entire finned length for maximum heat transfer rates. Bare copper tubes shall not be visible between fins.
3. Coil tubes shall be 5/8 inch OD seamless copper, 0.020 inch nominal tube wall thickness, expanded into fins, brazed at joints.
VXTZ56 VA Tampa 20 3/9/2023
4. Coil connections shall be carbon steel, threaded connection. Connection size to be determined by manufacturer based upon the most efficient coil circuiting. Vent and drain fittings shall be furnished on the connections, exterior to the air handler. Vent connections provided at the highest point to assure proper venting. Drain connections shall be provided at the lowest point to insure complete drainage and prevent freeze-up.
5. Coil shall be furnished as an uncased galvanized steel to allow for thermal movement and slide into a pitched track for fluid drainage.
2.08 FILTERS
A. Furnish combination filter section with 2-inch pleated MERV 8 flat pre-filter and 4-inch final filter. Provide side loading and removal of filters.
B. Furnish combination filter section with flat pre-filter and 12-inch HEPA final filter. Provide front loading and removal of filters.
C. Filter media shall be UL 900 listed, Class I or Class II.
D. Filter Magnehelic gauge(s) shall be furnished and mounted by equipment manufacturer.
2.09 ADDITIONAL SECTIONS
A. Plenum section shall be provided and properly sized for inlet and/or discharge air flow (between 600 and
1500 feet per minute). The plenum shall provide single or multiple openings as shown on drawings and project schedule.
B. Access section shall be provided for access between components.
C. Economizer section shall be provided with right side outside air opening and end return air opening and left side exhaust air opening with or without parallel low leak airfoil damper blades. Dampers shall be hollow core galvanized steel airfoil blades, fully gasketed and have continuous vinyl seals between damper blades in a galvanized steel frame. Dampers shall have stainless steel jamb seals along end of dampers. Linkage and ABS plastic end caps shall be provided when return and outside air dampers sized for full airflow. Return and outside air dampers of different sizes or very large dampers and exhaust dampers must be driven separately.
Damper Leakage: Leakage rate shall be less than two tenths of one percent leakage at 2 inches static pressure differential. Leakage rate tested in accordance with AMCA Standard 500.
PART 3: EXECUTION
3.01 INSTALLATION
A.
3.02 ENVIRONMENTAL REQUIREMENTS
A. Do not operate units for any purpose, temporary or permanent, until ductwork is clean, filters are in place, bearings lubricated, and fan has been test run under observation.
3.03 EXTRA MATERIALS
A. Provide [one, two, etc.] extra set(s) [fan belts, filters, etc.] for each unit as shown on project schedule.
VXTZ56 VA Tampa 21 3/9/2023
VA Tampa – Replace Air Handling Unit ED-203 Electrical Narrative
AESUS Design Group E - 1
Electrical Narrative
Introduction
This project scope shall include, but not be limited to the replacement of AHU ED-203 and associated pumps of Building One at the James A. Haley VA Hospital, located at 13000 Bruce B.
Downs Boulevard, Tampa.
General Design Guidelines
The following guidelines shall establish the basic standards of construction for the work associated with this project.
All work described herein shall conform to the National Electric Code (NEC) – NFPA 70, The International Building Code, The Health Care Facilities Code, NFPA 99, The Life Safety Code, NFPA 101, The International Energy Conservation Code, and VA design guidelines.
Project Scope
The electrical portion of this work shall include, but not be limited to the following:
Coordinate electrical load study as necessary to verify the existing electrical load demand on the existing electrical distribution system.
Demolish the following:
o Air handling unit AHU-ED-203.
o Hot water pumps HWP-1 & HWP-2 and starters.
o Chilled water pumps CWP-9 & CWP-10 and starters.
Provide new variable frequency drives to serve new hot and chilled water pumps.
Utilize existing circuit breaker in distribution board “EQER1” to feed new AHU-ED-203, HWP-1, HWP-2, CWP-9 & CWP-10.
Utilize existing circuit breaker in panelboard “EQERL1” to feed 120V circuit for AHU lighting & maintenance receptacle.
Relocate existing VAV box per mechanical plans.
The replacement of AHU ED-203 and associated pumps shall add 39.1 amperes of electrical load to the associated electrical distribution system. Existing electrical loads shown on plans are per existing drawings, project #673-318, dated 2004.08.05.
Furthermore, the following shall apply to the areas in scope:
Electrical Service and Distribution:
All existing electrical service and distribution are to remain “as-is” unless noted otherwise.
Additions or modification to any panel or service will be documented.
No additional backup, standby or emergency power will be required. Existing egress or emergency lighting will be reconnected or modified as needed.
VA Tampa – Replace Air Handling Unit ED-203 Electrical Narrative
AESUS Design Group E - 2
Branch Wiring:
Branch wiring system will be installed in accordance with 2020 NEC. Each branch circuit will utilize a dedicated neutral conductor. All branch circuits shall utilize an equipment grounding conductor in each conduit. The conduit will not be allowed to be used as the sole grounding path.
All branch circuiting will be copper conductors in conduit. Minimum conduit size will be 3/4”.
MC Cable will be allowed to be used for normal power circuits from a junction box in the ceiling space in a room to devices located in the walls. The MC cable is to be concealed in the walls.
MC is not to be used for homeruns or for emergency circuits.
Typical branch circuit wiring will be minimum #12 AWG CU, installed in EMT conduit for power and lighting systems. Rigid conduits shall be used for all exposed conduit runs where EMT would be subject to physical damage as defined by the National Electrical Code (NEC). Conduits to be installed concealed, except where installed in electrical rooms, mechanical rooms or other unfinished areas.
All empty conduits shall have a pull string installed in them.
All panelboard feeders shall be copper conductors installed in conduits.
All electrical equipment shall be bonded with a dedicated equipment grounding conductor.
Power for Mechanical Equipment:
Power for Mechanical Equipment wiring systems will be installed in accordance with 2020 NEC.
Each branch circuit will utilize a dedicated neutral conductor as needed. All branch circuits shall utilize an equipment grounding conductor in each conduit. The conduit will not be allowed to be used as the sole grounding path.
All branch circuiting will be copper conductors in conduit. Minimum conduit size will be 3/4”.
Wiring Devices:
Wiring Devices shall be duplex receptacles rated for 120V with 5-20 NEMA configuration, nylon type, with finishes determined by architect. Device faceplates shall be thermoplastic.
Interior receptacles located within 6 feet of a water source shall be provided with GFCI.
Wiring devices to be mounted in 4” square x 2-1/8” deep minimum boxes with appropriate gang mud ring.
Where wiring devices are surface mounted or in unfinished areas, devices to be mounted in a 4” square outlet box with matching industrial raised cover plates.
Device wall plates to have extra strength laminated adhesive tape labels indicating the source panel and circuit number. Tape to be clear with back letters.
Receptacles shall have the following finish:
o Normal = White o Life Safety / Emergency = Red
Receptacle cover plate to match color of receptacle
Receptacles to be installed in accordance with the electrical drawings.
VA Tampa – Replace Air Handling Unit ED-203 Structural Narrative
AESUS Design Group S - 1
Structural Narrative
Introduction
The scope of work will involve replacing the existing Air Handler Unit ED-203 that is located on the roof of Building One at the James A. Haley VA Hospital in Tampa, Florida. The structural scope includes an analysis of the existing roof structure to determine whether the existing roof structure can adequately support the larger AHU (increased size in both weight and dimensionally).
Structural Scope
In order to offset the increase of unit weight, the intent of the design is to remove the existing concrete housekeeping pad (6” of normal-weight concrete placed directly on the 1-1/2” x 20 gage steel roof deck ~90 psf) while leaving the roof penetrations as-is to accommodate the currently in-use ductwork. The mechanical unit will be placed on a pre-manufactured roof curb and fastened to the roof structure per the manufacturer installation instructions.
The structural analysis of the existing roof members supporting the new mechanical unit utilized existing structural drawings prepared by Allan and Conrad, Inc. dated 1/28/2005. The existing drawings indicate the existing unit and housekeeping pad is supported on W16x40 wide flange roof members spanning to a W24x55 wide flange girder to the north and a W18x35 wide flange girder and masonry bearing wall to the south. The new mechanical unit weight is 18,024 lbs or 89 psf. By comparison, the new unit weight is less than the existing concrete pad weight which is being removed. However, an analysis of the steel beams and girders was also performed to validate the structural member adequacy.
With the existing concrete pad being cast directly on the existing 1-1/2” x 20 gage steel roof deck, it is presumed that…