5-Scedule II -Montgomery Helioscopes Combined.pdf
PDF 7 MB Posted
- Attached to
- Solar Procurement and Installation for projects identified by the Sustainable Energy Partnership (“SEP”)
- Solicitation number
- 6599
- Issued by
- Montgomery County, Pennsylvania
About this file
This document contains solar system performance reports prepared by the Pennsylvania Solar Center using Aurora Solar simulation software for multiple solar photovoltaic projects identified by the Sustainable Energy Partnership (SEP), a consortium comprising Bucks County, Chester County, Delaware County, and Montgomery County in Pennsylvania. The reports present detailed technical analyses and annual energy production projections for eight distinct solar installations across the Montgomery County region, including systems at the Fire Academy (540 Port Indian Rd, Eagleville, PA), Youth Center (60 Eagleville Rd, Eagleville, PA), Trail Center (75 East Lafayette St., Norristown, PA), and Courthouse Annex (102 N York Rd, Willow Grove, PA). Each project includes comparative analyses between two system configurations: one utilizing Enphase microinverters and one utilizing SolarEdge string inverters with power optimizers. The projects range in scale from 22.82 kW to 1.78 MW DC nameplate capacity, with annual production estimates ranging from approximately 29.3 MWh to 2.375 GWh. The simulation reports employ standardized weather data from the National Renewable Energy Laboratory (NREL) for the region at coordinates 40.15, -75.35, with consistent assumptions regarding soiling rates, albedo, module characteristics, and system losses applied across all analyses.
The reports detail comprehensive system metrics including performance ratios ranging from 75.8 percent to 84.6 percent, module specifications utilizing QCELLS Q.PEAK DUO bifacial solar modules rated at 485 watts or 585 watts, and inverter options from Enphase and SolarEdge manufacturers. Each analysis quantifies system losses across multiple categories including front shading (1.0 to 5.4 percent), reflection (3.0 to 3.6 percent), soiling (4.9 to 5.2 percent), temperature derating (2.0 to 6.8 percent), and inverter losses (1.5 to 3.5 percent). The documents provide detailed field segment layouts specifying racking configurations, tilt angles, azimuth orientations, module counts, and power ratings for each installation. All simulations were conducted using identical meteorological conditions and thermal modeling parameters, establishing a standardized baseline for comparing system performance between different inverter architectures and configurations across the SEP counties' solar procurement initiative.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MontCo - Fire Academy Enphase - Montgomery, 540 Port Indian Rd, Eagleville, PA 19403
Project Name Montgomery
Project
Address
540 Port Indian Rd, Eagleville, PA
19403
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Fire Academy Enphase
Module DC
Nameplate
127.07 kW
Inverter AC
Nameplate
111.87 kW
Load Ratio: 1.14
Annual Production 168.8 MWh
Performance Ratio 83.9% kWh/kWp 1,328.7
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 7cc42bb06c-14b3484bd1-
9cccf5a138-0f50ce10e4
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
10k
20k
30k
Sources of System Loss
Front ShadingFront Shading: 2.2%: 2.2%Front Shading: 2.2%
ReflectionReflection: 3.3%: 3.3%Reflection: 3.3%
SoilingSoiling: 5.0%: 5.0%Soiling: 5.0% IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%
TemperatureTemperature: 2.0%: 2.0%Temperature: 2.0%
ElectricalElectrical MismatchMismatch: 0.1%: 0.1% Electrical Mismatch: 0.1%
WiringWiring: 0.1%: 0.1%Wiring: 0.1%
ClippingClipping: 0.9%: 0.9%Clipping: 0.9%
InvertersInverters: 2.9%: 2.9%Inverters: 2.9%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.1%: 0.1%Bifaciality: 0.1%
Annual Production Report produced by Pennsylvania Solar Center
© 2026 Aurora Solar 1 / 4 April 20, 2026
Description Output
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal
Irradiance 1,476.0
POA Irradiance 1,583.2 7.3%
Shaded Irradiance 1,548.7 -2.2%
Irradiance after Reflection 1,497.7 -3.3%
Irradiance after Soiling 1,422.4 -5.0%
Total Front Collector Irradiance 1,422.4 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on
Surface
437.2 -
Surface Reflected
Irradiance after
Albedo
87.4 -80.0%
Conversion from
Surface Area to
Collector Area
124.3
Surface Irradiance in Collector Plane
5.6 -95.5%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in Collector Plane 5.6
Sky Diffuse 1.6
Beam Effective 0.0
Total Unshaded
Irradiance on Rear
Side
7.2
Shaded Irradiance on Rear Side 6.9 -5.0%
Total Rear Collector Irradiance 6.9
Effective Rear Collector
Irradiance
4.8 -30.0%
Total Collector Irradiance 1,427.2
Energy
(kWh)
Nameplate 181,370.9
Output at Irradiance Levels 180,067.7 -0.7%
Output at Cell Temperature Derate 176,499.3 -2.0%
Output after Electrical Mismatch 176,361.6 -0.1%
Output after Rear Mismatch 176,302.5 0.0%
Optimal DC Output 176,239.8 -0.1%
Constrained DC Output 174,710.4 -0.9%
Inverter Output 169,680.8 -2.9%
Energy to Grid 168,832.4 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 22.0 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module Q.PEAK DUO XL-G10.d/BFG
485W (QCELLS)
Spec Sheet
Characterization, PAN True
Inverter
IQ9N-3P-A-US-277 (2026)
(Enphase) Default Characterization N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
© 2026 Aurora Solar 2 / 4 April 20, 2026 https://app.helioscope.com/library/meteo/6111
Component Name Count
Inverters
IQ9N-3P-A-US-277 (2026)
(Enphase)
(111.87 kW)
Strings 10 AWG (Copper) 262 (705.3 ft)
Module
QCELLS, Q.PEAK DUO XL-
G10.d/BFG 485W (485W)
(127.07 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 1-1 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 52 52
25.22 kW
Field
Segment 2
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 67 67
32.50 kW
Field
Segment 3
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 53 53
25.71 kW
Field
Segment 4
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 90 90
43.65 kW
Field Segments
© 2026 Aurora Solar 3 / 4 April 20, 2026
Detailed Layout2
© 2026 Aurora Solar 4 / 4 April 20, 2026
MontCo - Fire Academy String - Montgomery, 540 Port Indian Rd, Eagleville, PA
19403
Project Name Montgomery
Project
Address
540 Port Indian Rd, Eagleville, PA
19403
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Fire Academy String
Module DC
Nameplate
127.07 kW
Inverter AC
Nameplate
133.20 kW
Load Ratio: 0.95
Annual Production 169.1 MWh
Performance Ratio 84.1% kWh/kWp 1,330.7
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 68034364bf-a0135c5470-
972ff57921-bdb00e3c98
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
10k
20k
30k
Sources of System Loss
Front ShadingFront Shading: 2.2%: 2.2%Front Shading: 2.2%
ReflectionReflection: 3.3%: 3.3%Reflection: 3.3%
SoilingSoiling: 5.0%: 5.0%Soiling: 5.0% IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%
TemperatureTemperature: 2.0%: 2.0%Temperature: 2.0%
ElectricalElectrical MismatchMismatch: 0.5%: 0.5% Electrical Mismatch: 0.5%
OptimizersOptimizers: 1.2%: 1.2%Optimizers: 1.2%
WiringWiring: 0.4%: 0.4%Wiring: 0.4%
InvertersInverters: 1.5%: 1.5%Inverters: 1.5%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.1%: 0.1%Bifaciality: 0.1%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal
Irradiance 1,476.0
POA Irradiance 1,583.2 7.3%
Shaded Irradiance 1,548.7 -2.2%
Irradiance after Reflection 1,497.7 -3.3%
Irradiance after Soiling 1,422.4 -5.0%
Total Front Collector Irradiance 1,422.4 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on
Surface
437.2 -
Surface Reflected
Irradiance after
Albedo
87.4 -80.0%
Conversion from
Surface Area to
Collector Area
124.3
Surface Irradiance in Collector Plane
5.6 -95.5%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in Collector Plane 5.6
Sky Diffuse 1.6
Beam Effective 0.0
Total Unshaded
Irradiance on Rear
Side
7.2
Shaded Irradiance on Rear Side 6.9 -5.1%
Total Rear Collector Irradiance 6.9
Effective Rear Collector
Irradiance
4.8 -30.0%
Total Collector Irradiance 1,427.2
Energy
(kWh)
Nameplate 181,363.0
Output at Irradiance Levels 180,059.9 -0.7%
Output at Cell Temperature Derate 176,491.7 -2.0%
Output after Electrical Mismatch 175,691.4 -0.5%
Output after Rear Mismatch 175,632.6 0.0%
Optimizer Output 173,521.1 -1.2%
Optimal DC Output 172,752.1 -0.4%
Constrained DC Output 172,534.5 -0.1%
Inverter Output 169,946.5 -1.5%
Energy to Grid 169,096.8 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 22.0 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module Q.PEAK DUO XL-G10.d/BFG
485W (QCELLS)
Spec Sheet
Characterization, PAN True
Inverter SE66.6KUS (SolarEdge) Spec Sheet N/A
Buck Boost
Optimizer S1200 (SolarEdge) Mfg Spec Sheet N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
Inverters SE66.6KUS (SolarEdge) 2 (133.20 kW)
Strings 10 AWG (Copper) 8 (1,375.7 ft)
Optimizers S1200 (SolarEdge) 134 (160.80 kW)
Module
QCELLS, Q.PEAK DUO XL-
G10.d/BFG 485W (485W)
262 (127.07 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 13-35 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 52 52
25.22 kW
Field
Segment 2
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 67 67
32.50 kW
Field
Segment 3
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 53 53
25.71 kW
Field
Segment 4
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
154.03525°
1.5 ft 1x1 90 90
43.65 kW
Field Segments
MontCo - Youth Center Enphase - Montgomery, 540 Port Indian Rd, Eagleville, PA 19403
Project Name Montgomery
Project
Address
540 Port Indian Rd, Eagleville, PA
19403
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Youth Center Enphase
Module DC
Nameplate
350.17 kW
Inverter AC
Nameplate
308.29 kW
Load Ratio: 1.14
Annual
Production
436.2 MWh
Performance
Ratio 80.7% kWh/kWp 1,245.6
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 7478cad220-d9da36e9eb-
649e91004b-10da27cc5d
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
20k
40k
60k
Sources of System Loss
Front ShadingFront Shading: 1.0%: 1.0%Front Shading: 1.0%
ReflectionReflection: 3.6%: 3.6%Reflection: 3.6%
SoilingSoiling: 4.9%: 4.9%Soiling: 4.9%
IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%
TemperatureTemperature: 6.8%: 6.8%Temperature: 6.8%
ElectricalElectrical MismatchMismatch: 0.1%: 0.1% Electrical Mismatch: 0.1%
WiringWiring: 0.1%: 0.1%Wiring: 0.1%
ClippingClipping: 0.3%: 0.3%Clipping: 0.3%
InvertersInverters: 2.9%: 2.9%Inverters: 2.9%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.0%: 0.0%Bifaciality: 0.0%
© 2026 Aurora Solar 1 / 4 April 21, 2026
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal
Irradiance 1,476.0
POA Irradiance 1,542.9 4.5%
Shaded Irradiance 1,527.2 -1.0%
Irradiance after Reflection 1,472.0 -3.6%
Irradiance after Soiling 1,399.2 -4.9%
Total Front Collector Irradiance 1,399.1 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on
Surface
20.4 -
Surface Reflected
Irradiance after
Albedo
4.1 -80.0%
Conversion from
Surface Area to
Collector Area
6.0
Surface Irradiance in Collector Plane
0.3 -95.7%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in Collector Plane 0.3
Sky Diffuse 0.1
Beam Effective 0.0
Total Unshaded
Irradiance on Rear
Side
0.4
Shaded Irradiance on Rear Side 0.3 -5.1%
Total Rear Collector Irradiance 0.3
Effective Rear Collector
Irradiance
0.2 -30.0%
Total Collector Irradiance 1,399.4
Energy
(kWh)
Nameplate 490,078.2
Output at Irradiance Levels 486,418.7 -0.7%
Output at Cell Temperature Derate 453,484.8 -6.8%
Output after Electrical Mismatch 453,136.6 -0.1%
Output after Rear Mismatch 453,129.0 0.0%
Optimal DC Output 452,841.6 -0.1%
Constrained DC Output 451,375.5 -0.3%
Inverter Output 438,366.7 -2.9%
Energy to Grid 436,174.9 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 29.2 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module Q.PEAK DUO XL-G10.d/BFG
485W (QCELLS)
Spec Sheet
Characterization, PAN True
Inverter
IQ9N-3P-A-US-277 (2026)
(Enphase) Default Characterization N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
© 2026 Aurora Solar 2 / 4 April 21, 2026
IQ9N-3P-A-US-277 (2026)
(Enphase)
722 (308.29 kW)
Strings 10 AWG (Copper)
(3,272.8 ft)
Module
QCELLS, Q.PEAK DUO XL-
G10.d/BFG 485W (485W)
722 (350.17 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 1-1 Along Racking
Wiring Zone 2 - 1-1 Along Racking
Wiring Zone 3 - 1-1 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Flush
Mount
Landscape
(Horizontal) 12° 69° 0.1 ft 1x1 71 71
34.44 kW
Field
Segment 2
Flush
Mount
Landscape
(Horizontal) 12° 158.1819° 0.1 ft 1x1 58 58
28.13 kW
Field
Segment 3
Flush
Mount
Landscape
(Horizontal) 12° 158.3404° 0.1 ft 1x1 185 185
89.73 kW
Field
Segment 4
Flush
Mount
Landscape
(Horizontal) 12° 68.154594° 0.1 ft 1x1 135 135
65.48 kW
Field
Segment 5
Flush
Mount
Landscape
(Horizontal) 10° 157.8452° 0.1 ft 1x1 61 61
29.59 kW
Field
Segment 6
Flush
Mount
Landscape
(Horizontal) 10° 157.8452° 0.1 ft 1x1 55 55
26.68 kW
Field
Segment 7
Flush
Mount
Landscape
(Horizontal) 10° 158.46954° 0.1 ft 1x1 63 63
30.56 kW
Field
Segment 8
Flush
Mount
Landscape
(Horizontal) 10° 157.84369° 0.1 ft 1x1 63 63
30.56 kW
Field
Segment 9 Fixed Tilt
Landscape
(Horizontal)
Module:
10°
Module:
157.84369°
1.7 ft 1x1 9 9
4.37 kW
Field
Segment 10 Fixed Tilt
Landscape
(Horizontal)
Module:
10°
Module:
157.84369°
1.7 ft 1x1 16 16
7.76 kW
Field
Segment 11 Fixed Tilt
Landscape
(Horizontal)
Module:
10°
Module:
157.84369°
1.7 ft 1x1 6 6
2.91 kW
Field Segments
© 2026 Aurora Solar 3 / 4 April 21, 2026
© 2026 Aurora Solar 4 / 4 April 21, 2026
MontCo - Youth Center String - Montgomery, 540 Port Indian Rd, Eagleville, PA
19403
Project Name Montgomery
Project
Address
540 Port Indian Rd, Eagleville, PA
19403
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Youth Center String
Module DC
Nameplate
350.17 kW
Inverter AC
Nameplate
399.60 kW
Load Ratio: 0.88
Annual
Production
435.8 MWh
Performance
Ratio 80.7% kWh/kWp 1,244.6
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 7478cad220-d9da36e9eb-
649e91004b-10da27cc5d
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
20k
40k
60k
Sources of System Loss
Front ShadingFront Shading: 1.0%: 1.0%Front Shading: 1.0%
ReflectionReflection: 3.6%: 3.6%Reflection: 3.6%
SoilingSoiling: 4.9%: 4.9%Soiling: 4.9%
IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%
TemperatureTemperature: 6.8%: 6.8%Temperature: 6.8%
ElectricalElectrical MismatchMismatch: 0.3%: 0.3% Electrical Mismatch: 0.3%
OptimizersOptimizers: 1.2%: 1.2%Optimizers: 1.2%
WiringWiring: 0.3%: 0.3%Wiring: 0.3%
ClippingClipping: 0.1%: 0.1%Clipping: 0.1%
InvertersInverters: 1.5%: 1.5%Inverters: 1.5%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal
Irradiance 1,476.0
POA Irradiance 1,542.9 4.5%
Shaded Irradiance 1,527.2 -1.0%
Irradiance after Reflection 1,472.0 -3.6%
Irradiance after Soiling 1,399.2 -4.9%
Total Front Collector Irradiance 1,399.1 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on
Surface
20.4 -
Surface Reflected
Irradiance after
Albedo
4.1 -80.0%
Conversion from
Surface Area to
Collector Area
6.0
Surface Irradiance in Collector Plane
0.3 -95.7%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in Collector Plane 0.3
Sky Diffuse 0.1
Beam Effective 0.0
Total Unshaded
Irradiance on Rear
Side
0.4
Shaded Irradiance on Rear Side 0.3 -10.0%
Total Rear Collector Irradiance 0.3
Effective Rear Collector
Irradiance
0.2 -30.0%
Total Collector Irradiance 1,399.3
Energy
(kWh)
Nameplate 490,070.5
Output at Irradiance Levels 486,411.1 -0.7%
Output at Cell Temperature Derate 453,384.5 -6.8%
Output after Electrical Mismatch 452,029.0 -0.3%
Output after Rear Mismatch 452,021.7 0.0%
Optimizer Output 446,586.8 -1.2%
Optimal DC Output 445,051.8 -0.3%
Constrained DC Output 444,679.5 -0.1%
Inverter Output 438,009.3 -1.5%
Energy to Grid 435,819.3 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 29.2 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module Q.PEAK DUO XL-G10.d/BFG
485W (QCELLS)
Spec Sheet
Characterization, PAN True
Inverter SE66.6KUS (SolarEdge) Spec Sheet N/A
Buck Boost
Optimizer S1200 (SolarEdge) Mfg Spec Sheet N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
Inverters SE66.6KUS (SolarEdge) 6 (399.60 kW)
Strings 10 AWG (Copper) 23 (2,807.1 ft)
Optimizers S1200 (SolarEdge) 368 (441.60 kW)
Module
QCELLS, Q.PEAK DUO XL-
G10.d/BFG 485W (485W)
722 (350.17 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 13-35 Along Racking
Wiring Zone 2 - 13-35 Along Racking
Wiring Zone 3 - 13-35 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Flush
Mount
Landscape
(Horizontal) 12° 69° 0.1 ft 1x1 71 71
34.44 kW
Field
Segment 2
Flush
Mount
Landscape
(Horizontal) 12° 158.1819° 0.1 ft 1x1 58 58
28.13 kW
Field
Segment 3
Flush
Mount
Landscape
(Horizontal) 12° 158.3404° 0.1 ft 1x1 185 185
89.73 kW
Field
Segment 4
Flush
Mount
Landscape
(Horizontal) 12° 68.154594° 0.1 ft 1x1 135 135
65.48 kW
Field
Segment 5
Flush
Mount
Landscape
(Horizontal) 10° 157.8452° 0.1 ft 1x1 61 61
29.59 kW
Field
Segment 6
Flush
Mount
Landscape
(Horizontal) 10° 157.8452° 0.1 ft 1x1 55 55
26.68 kW
Field
Segment 7
Flush
Mount
Landscape
(Horizontal) 10° 158.46954° 0.1 ft 1x1 63 63
30.56 kW
Field
Segment 8
Flush
Mount
Landscape
(Horizontal) 10° 157.84369° 0.1 ft 1x1 63 63
30.56 kW
Field
Segment 9 Fixed Tilt
Landscape
(Horizontal)
Module:
10°
Module:
157.84369°
1.7 ft 1x1 9 9
4.37 kW
Field
Segment 10 Fixed Tilt
Landscape
(Horizontal)
Module:
10°
Module:
157.84369°
1.7 ft 1x1 16 16
7.76 kW
Field
Segment 11 Fixed Tilt
Landscape
(Horizontal)
Module:
10°
Module:
157.84369°
1.7 ft 1x1 6 6
2.91 kW
Field Segments
MontCo - Trail Center Enphase IQ8 - Montgomery, 75 East Lafayette St., Norristown, PA
Project Name Montgomery
Project Address 75 East Lafayette St., Norristown, PA
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Trail Center Enphase IQ8
Module DC
Nameplate
22.82 kW
Inverter AC
Nameplate
18.53 kW
Load Ratio: 1.23
Annual Production 30.67 MWh
Performance Ratio 85.0% kWh/kWp 1,344.2
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version d41bb4f217-702647e35c-
25cbfbd28d-1d4a14f0cf
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
1k
2k
3k
4k
Sources of System Loss
Front ShadingFront Shading: 1.1%: 1.1%Front Shading: 1.1%
ReflectionReflection: 3.5%: 3.5%Reflection: 3.5%
SoilingSoiling: 5.0%: 5.0%Soiling: 5.0%IrradianceIrradiance: 0.8%: 0.8%Irradiance: 0.8%
TemperatureTemperature: 2.0%: 2.0%Temperature: 2.0%
ElectricalElectrical MismatchMismatch: 0.1%: 0.1% Electrical Mismatch: 0.1%
WiringWiring: 0.1%: 0.1%Wiring: 0.1%
ClippingClipping: 0.6%: 0.6%Clipping: 0.6%
InvertersInverters: 2.7%: 2.7%Inverters: 2.7%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.1%: 0.1%Bifaciality: 0.1%
Rear MismatchRear Mismatch: 0.0%: 0.0%Rear Mismatch: 0.0%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal Irradiance 1,476.0
POA Irradiance 1,581.2 7.1%
Shaded Irradiance 1,564.5 -1.1%
Irradiance after Reflection 1,510.0 -3.5%
Irradiance after Soiling 1,433.8 -5.0%
Total Front Collector Irradiance 1,433.8 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on Surface
510.3 -
Surface Reflected
Irradiance after
Albedo
102.1 -80.0%
Conversion from
Surface Area to
Collector Area
141.6
Surface Irradiance in Collector Plane
5.4 -96.2%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in
Collector Plane 5.4
Sky Diffuse 1.7
Beam Effective 0.0
Total Unshaded
Irradiance on Rear
Side
7.1
Shaded Irradiance on Rear Side 6.7 -5.0%
Total Rear Collector Irradiance 6.7
Effective Rear Collector
Irradiance
4.7 -30.0%
Total Collector Irradiance 1,438.5
Energy
(kWh)
Nameplate 32,812.9
Output at Irradiance Levels 32,561.2 -0.8%
Output at Cell Temperature Derate 31,907.2 -2.0%
Output after Electrical Mismatch 31,886.4 -0.1%
Output after Rear Mismatch 31,875.9 0.0%
Optimal DC Output 31,861.6 -0.1%
Constrained DC Output 31,685.4 -0.6%
Inverter Output 30,822.0 -2.7%
Energy to Grid 30,667.9 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 22.0 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module
Q.PEAK DUO XL-G11S 585W
(QCells)
Spec Sheet Characterization, PAN
True
Inverter
IQ8P-3P-72-E-US-208 (2026)
(Enphase) Default Characterization N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
IQ8P-3P-72-E-US-208 (2026)
(Enphase)
39 (18.53 kW)
Strings 10 AWG (Copper) 39 (110.2 ft)
Module QCells, Q.PEAK DUO XL-G11S
585W (585W)
39 (22.82 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 1-1 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
206.01668°
1.5 ft 1x1 39 39
22.82 kW
Field Segments
MontCo - Trail Center String - Montgomery, 75 East Lafayette St., Norristown, PA
Project Name Montgomery
Project Address 75 East Lafayette St., Norristown, PA
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Trail Center String
Module DC
Nameplate
22.82 kW
Inverter AC
Nameplate
25.00 kW
Load Ratio: 0.91
Annual Production 29.29 MWh
Performance Ratio 81.2% kWh/kWp 1,283.8
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 68034364bf-a0135c5470-
972ff57921-bdb00e3c98
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
1k
2k
3k
4k
Sources of System Loss
Front ShadingFront Shading: 1.1%: 1.1%Front Shading: 1.1%
ReflectionReflection: 3.5%: 3.5%Reflection: 3.5%
SoilingSoiling: 5.0%: 5.0%Soiling: 5.0%
IrradianceIrradiance: 0.8%: 0.8%Irradiance: 0.8%TemperatureTemperature: 2.0%: 2.0%Temperature: 2.0%
ElectricalElectrical MismatchMismatch: 4.0%: 4.0% Electrical Mismatch: 4.0%
WiringWiring: 0.4%: 0.4%Wiring: 0.4%
ClippingClipping: 0.0%: 0.0%Clipping: 0.0%
InvertersInverters: 3.5%: 3.5%Inverters: 3.5%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.1%: 0.1%Bifaciality: 0.1%
Rear MismatchRear Mismatch: 0.0%: 0.0%Rear Mismatch: 0.0%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal Irradiance 1,476.0
POA Irradiance 1,581.2 7.1%
Shaded Irradiance 1,564.5 -1.1%
Irradiance after Reflection 1,510.0 -3.5%
Irradiance after Soiling 1,433.8 -5.0%
Total Front Collector Irradiance 1,433.9 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on Surface
510.3 -
Surface Reflected
Irradiance after
Albedo
102.1 -80.0%
Conversion from
Surface Area to
Collector Area
141.6
Surface Irradiance in Collector Plane
5.4 -96.2%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in
Collector Plane 5.4
Sky Diffuse 1.7
Beam Effective 0.0
Total Unshaded
Irradiance on Rear
Side
7.1
Shaded Irradiance on Rear Side 6.7 -5.2%
Total Rear Collector Irradiance 6.7
Effective Rear Collector
Irradiance
4.7 -30.0%
Total Collector Irradiance 1,438.6
Energy
(kWh)
Nameplate 32,822.3
Output at Irradiance Levels 32,570.4 -0.8%
Output at Cell Temperature Derate 31,915.9 -2.0%
Output after Electrical Mismatch 30,630.8 -4.0%
Output after Rear Mismatch 30,620.8 0.0%
Optimal DC Output 30,520.6 -0.4%
Constrained DC Output 30,512.1 0.0%
Inverter Output 29,436.7 -3.6%
Energy to Grid 29,289.5 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 22.0 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module
Q.PEAK DUO XL-G11S 585W
(QCells)
Spec Sheet
Characterization, PAN True
Inverter CPS SCA25KTL-DO/US-208 (Chint
Power Systems) Default Characterization N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
CPS SCA25KTL-DO/US-208
(Chint Power Systems)
1 (25.00 kW)
Strings 10 AWG (Copper) 3 (219.7 ft)
Module QCells, Q.PEAK DUO XL-G11S
585W (585W)
39 (22.82 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 5-16 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
206.01668°
1.5 ft 1x1 39 39
22.82 kW
Field Segments
MontCo - Courthouse Annex Enphase IQ8 - Montgomery, 102 N York Rd, Willow Grove, PA 19090
Project Name Montgomery
Project
Address
102 N York Rd, Willow Grove, PA
19090
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Courthouse Annex
Enphase IQ8
Module DC
Nameplate
39.29 kW
Inverter AC
Nameplate
38.48 kW
Load Ratio: 1.02
Annual Production 52.19 MWh
Performance Ratio 84.6% kWh/kWp 1,328.5
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version d41bb4f217-702647e35c-
25cbfbd28d-1d4a14f0cf
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
2.5k
5k
7.5k
Sources of System Loss
Front ShadingFront Shading: 2.3%: 2.3%Front Shading: 2.3%
ReflectionReflection: 3.4%: 3.4%Reflection: 3.4%
SoilingSoiling: 5.0%: 5.0%Soiling: 5.0% IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%
TemperatureTemperature: 2.0%: 2.0%Temperature: 2.0%
ElectricalElectrical MismatchMismatch: 0.1%: 0.1% Electrical Mismatch: 0.1%
WiringWiring: 0.1%: 0.1%Wiring: 0.1%
InvertersInverters: 2.7%: 2.7%Inverters: 2.7%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.2%: 0.2%Bifaciality: 0.2%
Rear MismatchRear Mismatch: 0.0%: 0.0%Rear Mismatch: 0.0%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal Irradiance 1,476.0
POA Irradiance 1,570.2 6.4%
Shaded Irradiance 1,534.5 -2.3%
Irradiance after Reflection 1,482.5 -3.4%
Irradiance after Soiling 1,408.3 -5.0%
Total Front Collector Irradiance 1,408.3 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on Surface
447.5 -
Surface Reflected
Irradiance after
Albedo
89.5 -80.0%
Conversion from
Surface Area to
Collector Area
127.3
Surface Irradiance in Collector Plane
5.8 -95.4%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in
Collector Plane 5.8
Sky Diffuse 1.6
Beam Effective 0.1
Total Unshaded
Irradiance on Rear
Side
7.5
Shaded Irradiance on Rear Side 7.1 -5.0%
Total Rear Collector Irradiance 7.1
Effective Rear Collector
Irradiance
5.0 -30.0%
Total Collector Irradiance 1,413.3
Energy
(kWh)
Nameplate 55,527.0
Output at Irradiance Levels 55,119.5 -0.7%
Output at Cell Temperature Derate 54,007.3 -2.0%
Output after Electrical Mismatch 53,964.7 -0.1%
Output after Rear Mismatch 53,945.8 0.0%
Optimal DC Output 53,915.5 -0.1%
Constrained DC Output 53,908.9 0.0%
Inverter Output 52,451.3 -2.7%
Energy to Grid 52,189.0 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 21.9 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module Q.PEAK DUO XL-G10.d/BFG
485W (QCELLS)
Spec Sheet
Characterization, PAN True
Inverter
IQ8P-3P-72-E-US-208 (2026)
(Enphase) Default Characterization N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
IQ8P-3P-72-E-US-208 (2026)
(Enphase)
81 (38.48 kW)
Strings 10 AWG (Copper) 81 (352.8 ft)
Module
QCELLS, Q.PEAK DUO XL-
G10.d/BFG 485W (485W)
81 (39.29 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 1-1 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
215.55°
1.5 ft 1x1 81 81
39.29 kW
Field Segments
MontCo - Courthouse Annex String - Montgomery, 102 N York Rd, Willow
Grove, PA 19090
Project Name Montgomery
Project
Address
102 N York Rd, Willow Grove, PA
19090
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design MontCo - Courthouse Annex String
Module DC
Nameplate
39.29 kW
Inverter AC
Nameplate
36.00 kW
Load Ratio: 1.09
Annual
Production
49.08 MWh
Performance
Ratio 79.6% kWh/kWp 1,249.3
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 7478cad220-d9da36e9eb-
649e91004b-10da27cc5d
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
2.5k
5k
7.5k
Sources of System Loss
Front ShadingFront Shading: 2.3%: 2.3%Front Shading: 2.3%
ReflectionReflection: 3.4%: 3.4%Reflection: 3.4%
SoilingSoiling: 5.0%: 5.0%Soiling: 5.0%
IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%TemperatureTemperature: 2.0%: 2.0%Temperature: 2.0%
ElectricalElectrical MismatchMismatch: 5.5%: 5.5% Electrical Mismatch: 5.5%
WiringWiring: 0.3%: 0.3%Wiring: 0.3%
ClippingClipping: 0.1%: 0.1%Clipping: 0.1%
InvertersInverters: 2.9%: 2.9%Inverters: 2.9%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.2%: 0.2%Bifaciality: 0.2%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal Irradiance 1,476.0
POA Irradiance 1,570.2 6.4%
Shaded Irradiance 1,534.6 -2.3%
Irradiance after Reflection 1,482.5 -3.4%
Irradiance after Soiling 1,408.3 -5.0%
Total Front Collector Irradiance 1,408.3 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on Surface
447.5 -
Surface Reflected
Irradiance after
Albedo
89.5 -80.0%
Conversion from
Surface Area to
Collector Area
127.3
Surface Irradiance in Collector Plane
5.8 -95.4%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in
Collector Plane 5.8
Sky Diffuse 1.6
Beam Effective 0.1
Total Unshaded
Irradiance on Rear
Side
7.5
Shaded Irradiance on Rear Side 7.1 -5.1%
Total Rear Collector Irradiance 7.1
Effective Rear Collector
Irradiance
5.0 -30.0%
Total Collector Irradiance 1,413.3
Energy
(kWh)
Nameplate 55,526.2
Output at Irradiance Levels 55,118.6 -0.7%
Output at Cell Temperature Derate 54,006.7 -2.0%
Output after Electrical Mismatch 51,034.0 -5.5%
Output after Rear Mismatch 51,016.2 0.0%
Optimal DC Output 50,873.7 -0.3%
Constrained DC Output 50,803.9 -0.1%
Inverter Output 49,324.5 -2.9%
Energy to Grid 49,077.9 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 21.9 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature
Model Sandia Model
Temperature
Model Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation
Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module Q.PEAK DUO XL-G10.d/BFG
485W (QCELLS)
Spec Sheet
Characterization, PAN True
Inverter CPS SCA 36KTL-DO (US) (Chint) Manufacturer N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
Inverters CPS SCA 36KTL-DO (US) (Chint) 1 (36.00 kW)
Strings 10 AWG (Copper) 6 (598.2 ft)
Module
QCELLS, Q.PEAK DUO XL-
G10.d/BFG 485W (485W)
81 (39.29 kW)
Components
Description Combiner Poles String Size Stringing Strategy
Wiring Zone - 13-16 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 1
Fixed
Tilt
Landscape
(Horizontal)
Module:
10°
Module:
215.55°
1.5 ft 1x1 81 81
39.29 kW
Field Segments
Montco- Eagleville Campus- Enphase_04212026 - Montgomery, 60
Eagleville Rd, Eagleville, PA 19403
Project Name Montgomery
Project Address 60 Eagleville Rd, Eagleville, PA 19403
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design Montco- Eagleville Campus-
Enphase_04212026
Module DC
Nameplate
1.78 MW
Inverter AC
Nameplate
1.30 MW
Load Ratio: 1.37
Annual
Production
2.375 GWh
Performance
Ratio 79.8% kWh/kWp 1,332.3
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 8e3cf736c4-9e4df94b8e-
35ab2d83df-34f6b04b77
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
100k
200k
300k
Sources of System Loss
Front ShadingFront Shading: 5.3%: 5.3%Front Shading: 5.3%
ReflectionReflection: 3.0%: 3.0%Reflection: 3.0%
SoilingSoiling: 5.2%: 5.2%Soiling: 5.2%IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%
TemperatureTemperature: 2.6%: 2.6%Temperature: 2.6%
WiringWiring: 0.2%: 0.2%Wiring: 0.2%
ClippingClipping: 3.4%: 3.4%Clipping: 3.4%
InvertersInverters: 3.0%: 3.0%Inverters: 3.0%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.8%: 0.8%Bifaciality: 0.8%
Rear MismatchRear Mismatch: 0.2%: 0.2%Rear Mismatch: 0.2%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal
Irradiance 1,476.0
POA Irradiance 1,669.2 13.1%
Shaded Irradiance 1,580.7 -5.3%
Irradiance after Reflection 1,533.6 -3.0%
Irradiance after Soiling 1,453.9 -5.2%
Total Front Collector
Irradiance 1,453.9 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on
Surface
476.5 -
Surface Reflected
Irradiance after
Albedo
95.3 -80.0%
Conversion from
Surface Area to
Collector Area
157.2
Surface
Irradiance in
Collector Plane
30.8 -80.4%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in Collector Plane 30.8
Sky Diffuse 11.8
Beam Effective 0.2
Total Unshaded
Irradiance on
Rear Side
42.8
Shaded Irradiance on Rear Side 40.7 -5.0%
Total Rear Collector Irradiance 40.7
Effective Rear Collector
Irradiance
28.5 -30.0%
Total Collector Irradiance 1,482.3
Energy
(kWh)
Nameplate 2,641,601.2
Output at Irradiance Levels 2,622,220.7 -0.7%
Output at Cell Temperature
Derate 2,554,845.4 -2.6%
Output after Electrical Mismatch 2,553,213.6 -0.1%
Output after Rear Mismatch 2,548,327.0 -0.2%
Optimal DC Output 2,547,769.8 -0.2%
Constrained DC Output 2,459,987.5 -3.4%
Inverter Output 2,386,701.8 -3.0%
Energy to Grid 2,374,768.4 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 23.0 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature Model Sandia Model
Temperature Model
Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module
Q.PEAK DUO XL-G11S 585W
(QCells)
Spec Sheet Characterization, PAN
True
Inverter
IQ9N-3P-A-US-277 (2026)
(Enphase) Default Characterization N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
IQ9N-3P-A-US-277 (2026)
(Enphase)
3,047 (1.30
MW)
Strings 10 AWG (Copper) 3,047
(3,990.4 ft)
Module QCells, Q.PEAK DUO XL-
G11S 585W (585W)
3,047 (1.78
MW)
Components
Description Combiner Poles String Size Stringing Strategy
Emergnecy Ops N - 1-1 Along Racking
Archives - 1-1 Along Racking
Emergency Ops S - 1-1 Along Racking
Coroners - 1-1 Along Racking
Garage - 1-1 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field Segment
Flush
Mount
Landscape
(Horizontal) 10° 325.20993° 0.0 ft 1x1 307 307
179.60 kW
Field Segment
Fixed Tilt
Portrait
(Vertical)
Module:
25°
Module:
165.68896°
12.0 ft 2x1 229 458
267.93 kW
Field Segment
5 (copy) Fixed Tilt
Portrait
(Vertical)
Module:
25° Module: 180° 12.0 ft 2x1 385 770
450.45 kW
Field Segment
8 (copy) Fixed Tilt
Portrait
(Vertical)
Module:
25° Module: 180° 12.0 ft 2x1 548 1,096
641.16 kW
Field Segment
7 (copy) Fixed Tilt
Portrait
(Vertical)
Module:
25° Module: 180° 12.0 ft 2x1 208 416
243.36 kW
Field Segments
Montco- Eagleville Campus- String_04212026 - Montgomery, 60 Eagleville
Rd, Eagleville, PA 19403
Project Name Montgomery
Project Address 60 Eagleville Rd, Eagleville, PA 19403
Prepared By Pennsylvania Solar Center info@pasolarcenter.org
Report
Design Montco- Eagleville Campus-
String_04212026
Module DC
Nameplate
1.78 MW
Inverter AC
Nameplate
1.26 MW
Load Ratio: 1.41
Annual
Production
2.252 GWh
Performance
Ratio 75.8% kWh/kWp 1,265.2
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Simulator Version 3d95575071-500033d1a3-
7a70f8553e-2e9c31aff5
System Metrics Project Location
Monthly Production kW h
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
100k
200k
300k
Sources of System Loss
Front ShadingFront Shading: 5.4%: 5.4%Front Shading: 5.4%
ReflectionReflection: 3.0%: 3.0%Reflection: 3.0%
SoilingSoiling: 5.2%: 5.2%Soiling: 5.2%
IrradianceIrradiance: 0.7%: 0.7%Irradiance: 0.7%TemperatureTemperature: 2.6%: 2.6%Temperature: 2.6%
ElectricalElectrical MismatchMismatch: 4.7%: 4.7% Electrical Mismatch: 4.7%
WiringWiring: 0.6%: 0.6%Wiring: 0.6%
ClippingClipping: 3.5%: 3.5%Clipping: 3.5%
InvertersInverters: 2.8%: 2.8%Inverters: 2.8%
AC SystemAC System: 0.5%: 0.5%AC System: 0.5%
BifacialityBifaciality: 0.8%: 0.8%Bifaciality: 0.8%
Rear MismatchRear Mismatch: 0.2%: 0.2%Rear Mismatch: 0.2%
Delta
Front
Irradiance
(kWh/m )
Annual Global Horizontal
Irradiance 1,476.0
POA Irradiance 1,669.2 13.1%
Shaded Irradiance 1,578.7 -5.4%
Irradiance after Reflection 1,531.7 -3.0%
Irradiance after Soiling 1,452.1 -5.2%
Total Front Collector
Irradiance 1,451.9 0.0%
Rear Irradiance
(kWh/m )
Supported only for fixed tilt racking
Surface
Irradiance in
Collector
Plane
Global Incident
Irradiance on
Surface
476.2 -
Surface Reflected
Irradiance after
Albedo
95.2 -80.0%
Conversion from
Surface Area to
Collector Area
157.0
Surface
Irradiance in
Collector Plane
30.7 -80.4%
Unshaded
Irradiance on
Rear Side
Surface Irradiance in Collector Plane 30.7
Sky Diffuse 11.7
Beam Effective 0.2
Total Unshaded
Irradiance on
Rear Side
42.7
Shaded Irradiance on Rear Side 40.5 -5.2%
Total Rear Collector Irradiance 40.5
Effective Rear Collector
Irradiance
28.3 -30.0%
Total Collector Irradiance 1,480.2
Energy
(kWh)
Nameplate 2,634,626.1
Output at Irradiance Levels 2,615,247.0 -0.7%
Output at Cell Temperature
Derate 2,548,119.8 -2.6%
Output after Electrical Mismatch 2,427,147.0 -4.7%
Output after Rear Mismatch 2,422,505.0 -0.2%
Optimal DC Output 2,413,224.4 -0.6%
Constrained DC Output 2,329,819.5 -3.5%
Inverter Output 2,263,520.3 -2.8%
Energy to Grid 2,252,202.8 -0.5%
Temperature Metrics
Avg. Operating Ambient Temp 14.6 °C
Avg. Operating Cell Temp 22.9 °C
Simulation Metrics
Operating Hours 4684
Solved Hours 4684
Annual Production
Description Condition Set 1
Weather Dataset TMY, 10km grid (40.15,-75.35), NREL (prospector)
Solar Angle
Location Meteo Lat/Lng
Transposition
Model Perez Model
Temperature Model Sandia Model
Temperature Model
Parameters
Rack Type a b Temperature Delta
Fixed Tilt -3.56 -0.075 3°C
Flush Mount -2.81 -0.0455 0°C
East-West -3.56 -0.075 3°C
Carport -3.56 -0.075 3°C
Soiling (%) J F M A M J J A S O N D
23 21 11 4 1 0 1 1 1 1 5 16
Albedo J F M A M J J A S O N D
0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20
Rear Mismatch
Loss 10% Rear Shading Factor 5%
Module
Transparency 0%
Irradiation Variance 5%
Cell Temperature
Spread 4° C
Module Binning
Range -2.5% to 2.5%
AC System Derate 0.50%
Module &
Component
Characterizations
Type Component Characterization Bifacial
Module
Q.PEAK DUO XL-G11S 585W
(QCells)
Spec Sheet Characterization, PAN
True
Inverter
CPS SCA 36KTL-DO (US)
(Chint) Manufacturer N/A
Condition Set
Annual Production Report produced by Pennsylvania Solar Center
CPS SCA 36KTL-DO (US)
(Chint)
35 (1.26 MW)
Strings 10 AWG (Copper)
(42,382.7 ft)
Module QCells, Q.PEAK DUO XL-
G11S 585W (585W)
3,043 (1.78
MW)
Components
Description Combiner Poles String Size Stringing Strategy
Emergency Ops S - 13-16 Along Racking
Archives - 13-16 Along Racking
Garage - 13-16 Along Racking
Coroners - 13-16 Along Racking
Emergnecy Ops N - 13-16 Along Racking
Wiring Zones
Description Racking Orientation Tilt Azimuth Intrarow
Spacing
Frame
Size Frames Modules Power
Field
Segment 5 Fixed Tilt
Portrait
(Vertical)
Module:
25° Module: 180° 12.0 ft 2x1 385 770
450.45 kW
Field
Segment 7 Fixed Tilt
Portrait
(Vertical)
Module:
25° Module: 180° 12.0 ft 2x1 208 416
243.36 kW
Field
Segment 8 Fixed Tilt
Portrait
(Vertical)
Module:
25° Module: 180° 12.0 ft 2x1 546 1,092
638.82 kW
Field
Segment 4
Flush
Mount
Landscape
(Horizontal) 10° 325.20993° 0.0 ft 1x1 307 307
179.60 kW
Field
Segment 5 Fixed Tilt
Portrait
(Vertical)
Module:
25°
Module:
165.68896°
12.0 ft 2x1 229 458
267.93 kW
Field Segments