Solar Procurement and Installation for projects identified by the Sustainable Energy Partnership (“SEP”)
Solicitation number
6599
Issued by
Montgomery County, Pennsylvania

About this file

This is an Annual Production Report for solar photovoltaic systems at the Lower Bucks Brownfield site in Levittown, Pennsylvania, prepared by the Pennsylvania Solar Center for the Sustainable Energy Partnership comprising Bucks County, Chester County, Delaware County, and Montgomery County. The document presents detailed engineering analysis and performance projections for two distinct solar system designs proposed for the same project location at 7311 New Falls Rd, Levittown, PA 19055. The first design, the Enphase configuration, features 787 QCells Q.PEAK DUO XL-G11S 585W modules with a 460.40 kW DC nameplate capacity and 336.05 kW AC inverter capacity, utilizing 787 individual Enphase IQ9N-3P-A-US-277 microinverters. The second design, the SolarEdge configuration, uses the same 787 modules with identical DC capacity but incorporates four SolarEdge SE100KUS inverters with 400.00 kW combined AC capacity and 395 SolarEdge S1201 optimizers for module-level power optimization. Both systems utilize fixed-tilt racking at landscape orientation with identical field specifications and identical irradiance metrics.

The Enphase system projects annual energy production of 609.6 MWh with a performance ratio of 84.5%, while the SolarEdge system projects 601.7 MWh with a performance ratio of 83.4%, reflecting the SolarEdge system's higher AC system losses of 4.0% compared to the Enphase system's 0.0% AC system losses. Both designs were analyzed using NREL TMY weather data for the project coordinates (40.15, -74.85) and employ identical bifacial modules with rear irradiance calculations, soiling assumptions, and temperature derating models. The analysis was conducted using Aurora Solar simulation software and accounts for multiple system losses including front shading (2.2%), reflection (3.4%), soiling (2.3%), temperature effects (1.8%), and inverter conversion losses (2.9% for Enphase and 1.5% for SolarEdge). No pricing, contracting terms, timelines, or procurement details are included in this technical performance document.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Lower Bucks Brown�eld Enphase Bucks County, 7311 New Falls Rd, Levittown, PA 19055

Project Name Bucks County

Project

Address

7311 New Falls Rd, Levittown, PA

19055

Prepared By Leo Kowalski leo@pasolarcenter.org

Report

Design Lower Bucks Brownfield Enphase

Module DC

Nameplate

460.40 kW

Inverter AC

Nameplate

336.05 kW

Load Ratio: 1.37

Annual Production 609.6 MWh

Performance Ratio 84.5% kWh/kWp 1,324.2

Weather Dataset TMY, 10km grid (40.15,-74.85), NREL (prospector)

Simulator Version 511b9b6d49-3223cb372b-

73802f8b4b-84e61a7f42

System Metrics Project Location

Monthly Production kW h

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

25k

50k

75k

100k

Sources of System Loss

Front ShadingFront Shading: 2.2%: 2.2%Front Shading: 2.2%

ReflectionReflection: 3.4%: 3.4%Reflection: 3.4%

SoilingSoiling: 2.3%: 2.3%Soiling: 2.3%

IrradianceIrradiance: 0.8%: 0.8%Irradiance: 0.8%TemperatureTemperature: 1.8%: 1.8%Temperature: 1.8%

ElectricalElectrical MismatchMismatch: 0.1%: 0.1% Electrical Mismatch: 0.1%

WiringWiring: 1.3%: 1.3%Wiring: 1.3%

ClippingClipping: 2.1%: 2.1%Clipping: 2.1%

InvertersInverters: 2.9%: 2.9%Inverters: 2.9%

AC SystemAC System: 0.0%: 0.0%AC System: 0.0%

BifacialityBifaciality: 0.1%: 0.1%Bifaciality: 0.1%

Rear MismatchRear Mismatch: 0.0%: 0.0%Rear Mismatch: 0.0%

Annual Production Report produced by Leo Kowalski

© 2026 Aurora Solar 1 / 4 April 20, 2026

Description Output

Delta

Front

Irradiance

(kWh/m )

Annual Global Horizontal

Irradiance 1,464.5

POA Irradiance 1,566.3 6.9%

Shaded Irradiance 1,531.8 -2.2%

Irradiance after Reflection 1,479.7 -3.4%

Irradiance after Soiling 1,445.0 -2.3%

Total Front Collector Irradiance 1,445.0 0.0%

Rear Irradiance

(kWh/m )

Supported only for fixed tilt racking

Surface

Irradiance in

Collector

Plane

Global Incident

Irradiance on

Surface

386.0 -

Surface Reflected

Irradiance after

Albedo

77.2 -80.0%

Conversion from

Surface Area to

Collector Area

110.0

Surface Irradiance in Collector Plane

5.5 -95.0%

Unshaded

Irradiance on

Rear Side

Surface Irradiance in Collector Plane 5.5

Sky Diffuse 1.6

Beam Effective 0.1

Total Unshaded

Irradiance on Rear

Side

7.1

Shaded Irradiance on Rear Side 6.7 -5.0%

Total Rear Collector Irradiance 6.7

Effective Rear Collector

Irradiance

4.7 -30.0%

Total Collector Irradiance 1,449.7

Energy

(kWh)

Nameplate 667,304.7

Output at Irradiance Levels 662,275.3 -0.8%

Output at Cell Temperature Derate 650,361.1 -1.8%

Output after Electrical Mismatch 649,924.7 -0.1%

Output after Rear Mismatch 649,714.2 0.0%

Optimal DC Output 641,704.5 -1.3%

Constrained DC Output 628,199.4 -2.1%

Inverter Output 609,823.2 -2.9%

Energy to Grid 609,639.5 0.0%

Temperature Metrics

Avg. Operating Ambient Temp 14.0 °C

Avg. Operating Cell Temp 21.6 °C

Simulation Metrics

Operating Hours 4686

Solved Hours 4686

Annual Production

Description Condition Set 1

Weather Dataset TMY, 10km grid (40.15,-74.85), NREL (prospector)

Solar Angle

Location Meteo Lat/Lng

Transposition

Model Perez Model

Temperature Model Sandia Model

Temperature Model

Parameters

Rack Type a b Temperature Delta

Fixed Tilt -3.56 -0.075 3°C

Flush Mount -2.81 -0.0455 0°C

East-West -3.56 -0.075 3°C

Carport -3.56 -0.075 3°C

Soiling (%) J F M A M J J A S O N D

13 9 4 1 1 1 0 0 1 1 1 7

Albedo J F M A M J J A S O N D

0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20

Rear Mismatch

Loss 10% Rear Shading Factor 5%

Module

Transparency 0%

Irradiation Variance 5%

Cell Temperature

Spread 4° C

Module Binning

Range -2.5% to 2.5%

AC System Derate 0.50%

Module &

Component

Characterizations

Type Component Characterization Bifacial

Module

Q.PEAK DUO XL-G11S 585W

(QCells)

Spec Sheet Characterization, PAN

True

Inverter

IQ9N-3P-A-US-277 (2026)

(Enphase) Default Characterization N/A

Condition Set

Annual Production Report produced by Leo Kowalski

© 2026 Aurora Solar 2 / 4 April 20, 2026 https://app.helioscope.com/library/meteo/5580

Component Name Count

Inverters

IQ9N-3P-A-US-277 (2026)

(Enphase)

787 (336.05 kW)

AC Panels 11 input AC Panel 5

AC Panels 12 input AC Panel 61

AC Home

Runs 10 AWG (Copper)

(234,451.1 ft)

AC Home

Runs 500 MCM (Copper)

66 (84,258.3 ft)

Home Runs 12 AWG (Copper) 1,574

(26,437.3 ft)

Combiners 1 input Combiner 1,574

Strings 10 AWG (Copper) 787 (17,449.5 ft)

Module QCells, Q.PEAK DUO XL-

G11S 585W (585W)

787 (460.40 kW)

Components

Description Combiner Poles String Size Stringing Strategy

Wiring Zone 12 1-1 Along Racking

Wiring Zones

Description Racking Orientation Tilt Azimuth Intrarow

Spacing

Frame

Size Frames Modules Power

Field

Segment 1

Fixed

Tilt

Landscape

(Horizontal)

Module:

10°

Module:

211.83232°

1.6 ft 1x1 787 787

460.40 kW

Field Segments

© 2026 Aurora Solar 3 / 4 April 20, 2026

Detailed Layout2

© 2026 Aurora Solar 4 / 4 April 20, 2026

Lower Bucks Brown�eld String Bucks County, 7311 New Falls Rd, Levittown, PA

19055

Project Name Bucks County

Project

Address

7311 New Falls Rd, Levittown, PA

19055

Prepared By Leo Kowalski leo@pasolarcenter.org

Report

Design Lower Bucks Brownfield String

Module DC

Nameplate

460.40 kW

Inverter AC

Nameplate

400.00 kW

Load Ratio: 1.15

Annual Production 601.7 MWh

Performance Ratio 83.4% kWh/kWp 1,307.0

Weather Dataset TMY, 10km grid (40.15,-74.85), NREL (prospector)

Simulator Version 511b9b6d49-3223cb372b-

73802f8b4b-84e61a7f42

System Metrics Project Location

Monthly Production kW h

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

25k

50k

75k

100k

Sources of System Loss

Front ShadingFront Shading: 2.2%: 2.2%Front Shading: 2.2%

ReflectionReflection: 3.4%: 3.4%Reflection: 3.4%

SoilingSoiling: 2.3%: 2.3%Soiling: 2.3%

IrradianceIrradiance: 0.8%: 0.8%Irradiance: 0.8%TemperatureTemperature: 1.8%: 1.8%Temperature: 1.8%

ElectricalElectrical MismatchMismatch: 0.3%: 0.3% Electrical Mismatch: 0.3%

OptimizersOptimizers: 1.3%: 1.3%Optimizers: 1.3%

WiringWiring: 0.5%: 0.5%Wiring: 0.5%

InvertersInverters: 1.5%: 1.5%Inverters: 1.5%

AC SystemAC System: 4.0%: 4.0%AC System: 4.0%

© 2026 Aurora Solar 1 / 4 April 20, 2026

Description Output

Delta

Front

Irradiance

(kWh/m )

Annual Global Horizontal

Irradiance 1,464.5

POA Irradiance 1,566.3 6.9%

Shaded Irradiance 1,532.3 -2.2%

Irradiance after Reflection 1,480.1 -3.4%

Irradiance after Soiling 1,445.4 -2.3%

Total Front Collector Irradiance 1,445.3 0.0%

Rear Irradiance

(kWh/m )

Supported only for fixed tilt racking

Surface

Irradiance in

Collector

Plane

Global Incident

Irradiance on

Surface

386.0 -

Surface Reflected

Irradiance after

Albedo

77.2 -80.0%

Conversion from

Surface Area to

Collector Area

110.0

Surface Irradiance in Collector Plane

5.5 -95.0%

Unshaded

Irradiance on

Rear Side

Surface Irradiance in Collector Plane 5.5

Sky Diffuse 1.6

Beam Effective 0.1

Total Unshaded

Irradiance on Rear

Side

7.1

Shaded Irradiance on Rear Side 6.7 -5.0%

Total Rear Collector Irradiance 6.7

Effective Rear Collector

Irradiance

4.7 -30.0%

Total Collector Irradiance 1,450.0

Energy

(kWh)

Nameplate 667,457.3

Output at Irradiance Levels 662,428.2 -0.8%

Output at Cell Temperature Derate 650,508.8 -1.8%

Output after Electrical Mismatch 648,546.3 -0.3%

Output after Rear Mismatch 648,336.6 0.0%

Optimizer Output 640,415.0 -1.3%

Optimal DC Output 637,357.6 -0.5%

Constrained DC Output 636,459.2 -0.1%

Inverter Output 626,907.1 -1.5%

Energy to Grid 601,731.1 -4.0%

Temperature Metrics

Avg. Operating Ambient Temp 14.0 °C

Avg. Operating Cell Temp 21.6 °C

Simulation Metrics

Operating Hours 4686

Solved Hours 4686

Annual Production

Description Condition Set 1

Weather Dataset TMY, 10km grid (40.15,-74.85), NREL (prospector)

Solar Angle

Location Meteo Lat/Lng

Transposition

Model Perez Model

Temperature

Model Sandia Model

Temperature

Model Parameters

Rack Type a b Temperature Delta

Fixed Tilt -3.56 -0.075 3°C

Flush Mount -2.81 -0.0455 0°C

East-West -3.56 -0.075 3°C

Carport -3.56 -0.075 3°C

Soiling (%) J F M A M J J A S O N D

13 9 4 1 1 1 0 0 1 1 1 7

Albedo J F M A M J J A S O N D

0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20

Rear Mismatch

Loss 10% Rear Shading Factor 5%

Module

Transparency 0%

Irradiation

Variance 5%

Cell Temperature

Spread 4° C

Module Binning

Range -2.5% to 2.5%

AC System Derate 0.50%

Module &

Component

Characterizations

Type Component Characterization Bifacial

Module

Q.PEAK DUO XL-G11S

585W (QCells)

Spec Sheet

Characterization, PAN True

Inverter SE100KUS (SolarEdge) Spec Sheet N/A

Buck Boost

Optimizer S1201 (SolarEdge) Mfg Spec Sheet N/A

Condition Set

Annual Production Report produced by Leo Kowalski

© 2026 Aurora Solar 2 / 4 April 20, 2026 https://app.helioscope.com/library/meteo/5580

Component Name Count

Inverters SE100KUS (SolarEdge) 4 (400.00 kW)

AC Panels 4 input AC Panel 1

AC Home

Runs 10 AWG (Copper)

4 (1,468.4 ft)

AC Home

Runs 500 MCM (Copper)

1 (1,482.9 ft)

Strings 10 AWG (Copper) 28 (2,420.2 ft)

Optimizers S1201 (SolarEdge) 395 (474.00 kW)

Module QCells, Q.PEAK DUO XL-

G11S 585W (585W)

787 (460.40 kW)

Components

Description Combiner Poles String Size Stringing Strategy

Wiring Zone - 13-29 Along Racking

Wiring Zones

Description Racking Orientation Tilt Azimuth Intrarow

Spacing

Frame

Size Frames Modules Power

Field

Segment 1

Fixed

Tilt

Landscape

(Horizontal)

Module:

10°

Module:

211.83232°

1.6 ft 1x1 787 787

460.40 kW

Field Segments

© 2026 Aurora Solar 3 / 4 April 20, 2026

Detailed Layout2

© 2026 Aurora Solar 4 / 4 April 20, 2026

File details come from the government source that posted it. Updated .