This is a set of electrical construction drawings for Bid Package 3 of an emergency power installation project for the Jordan School District (JSD) in Utah. The project provides emergency power circuits to Information Technology (IT) closets across nine school facilities: Elk Meadows Elementary, Herriman Elementary, Jordan Ridge Elementary, Rosamond Elementary, Rose Creek Elementary, South Jordan Elementary, Southland Elementary, South Hills Middle School, and South Jordan Middle School. The work involves upgrading electrical infrastructure by installing new 4-plex receptacles with red devices (indicating emergency power), modifying existing circuits in electrical panels, installing new 20-ampere and 30-ampere circuit breakers, running conduit and wire from receptacles to breakers, and coordinating with existing electrical systems. The drawings include detailed power plans for each facility at various scales (1/16" = 1'-0" and 1" = 20'-0"), electrical symbols and schedules, standard mounting heights, conduit support methods, equipment specifications, and comprehensive general notes addressing code compliance, voltage drop calculations, coordination with other trades, and demolition requirements.
The drawings specify technical requirements including conductor sizing based on circuit length, NEMA code compliance verification, material specifications for conduit (rigid galvanized conduit, intermediate metallic tubing, and polyvinyl chloride conduit), and load calculations for all equipment. Two of the middle schools require more substantial work: South Hills Middle School requires a new 15-kilovolt-ampere transformer (480V to 208/120V, three-phase), a new panel (EL2), and feeder conductor specifications; South Jordan Middle School requires a new load center (EM2A) extension adjacent to an existing panel with multiple 50-ampere three-phase circuit breakers. The drawings emphasize contractor responsibilities for verifying all existing equipment requirements, conducting voltage drop calculations, maintaining fire-rated penetration integrity, securing required permits and approvals, and coordinating with mechanical contractors to prevent conflicts. The specification references are noted as Section 265100 (16510), and all work must comply with the National Electrical Code (NEC) and applicable Utah codes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EMERGENCY POWER TO IT CLOSETS
FOR THE
JORDAN SCHOOL DISTRICT
BID No. 26KP19
APRIL 2026
ELK MEADOWS ES - 3448 W 9800 S, SOUTH JORDAN
HERRIMAN ES - 13170 S 6000 W, HERRIMAN
JORDAN RIDGE ES - 2636 W 9800 S, SOUTH JORDAN
ROSAMOND ES - 12195 S 2700 W, RIVERTON
ROSE CREEK ES - 12812 S 3600 W, RIVERTON
SOUTH JORDAN ES - 11205 S BLACK CHERRY WY., SOUTH JORDAN
SOUTHLAND ES - 12675 S 2700 W, RIVERTON
SOUTH HILLS MS - 13508 S 4000 W, RIVERTON
SOUTH JORDAN MS - 10245 S 2700 W, SOUTH JORDAN
NUMBER THREE
BID PACKAGE
SYMBOL DESCRIPTION
MOUNTING
HEIGHT NOTES SYMBOL DESCRIPTION
MOUNTING
HEIGHT NOTES
ONE CIRCUIT, HOME RUN TO PANEL
TWO CIRCUIT, HOME RUN TO PANEL
THREE CIRCUIT, HOME RUN TO PANEL
CONDUIT RUN CONCEALED IN WALL OR CEILING
CONDUIT RUN CONCEALED IN FLOOR OR GROUND
CONDUIT UP
CONDUIT DOWN
GENERAL
CONDUIT STUB LOCATION CONDUIT
CAP
CONDUIT/CIRCUIT CONTINUATION
JUNCTION BOX ('F' IN FLOOR) AS NOTED
LIGHT FIXTURE (LETTER DESIGNATES TYPE)X
X X
EQUIPMENT NUMBER
842 ARCHITECTURAL ROOM NUMBER
DEVICE/EQUIPMENT (TEXT DESIGNATES TYPE) SEE SCHEDULEX
DEVICE/EQUIPMENT (TEXT DESIGNATES TYPE) SEE SCHEDULE/LEGENDX
EQUIPMENT PANEL SEE DRAWINGS +72" 6.
CABLE TRAY (BASKET/LADDER) AS NOTED
GROUND BUS BAR +18" 6.
DUPLEX RECEPTACLE 9.
5mA GFCI CIRCUIT BREAKER PROTECTED RECEPTACLE 13.5mA GFCI CIRCUIT BREAKER PROTECTED RECEPTACLE 13.
TOMBSTONE RECEPTACLE
POWER POLE
POWER
UPPER OUTLET
SWITCH CONTROLLEDDUPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
SIMPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
TAMPER-PROOF RECEPTACLE 2. 9.
+18" OR
AS NOTED
DUPLEX RECEPTACLE WITH USB OUTLET 2. 9.
+18" OR
AS NOTED
WEATHERPROOF RECEPTACLE 2. 9.AS NOTED
+24" OR
ISOLATED GROUND RECEPTACLE 2. 9.
+18" OR
AS NOTED
GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
GROUND FAULT INTERRUPTER FOURPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
TVSS PROTECTED RECEPTACLE 2. 9.
+18" OR
AS NOTED
RECEPTACLE SWITCH PACK
ABOVE
CEILING
FLAT PANEL DISPLAY WALL BOX, TVSS RECEPT.,
SPEC. 26 2726
SEE DIAGRAM &
DATA AND OTHER DEVICES, REFER TO DIAGRAMS AS NOTED
CEILING PROJECTION SYSTEM CEILING BOX AND SPEC.
SEE DIAGRAMABOVE
CEILING
CLOCK OUTLET 2.+90"
PLUGMOLD/SURFACE RACEWAY 2. SEE SPEC.
+46" OR
AS NOTED
DUPLEX RECEPTACLE 2. 9. 11.
+18" OR
AS NOTED
DUPLEX RECEPTACLE EMERGENCY POWER (RED) 2. 9. 11.
+18" OR
AS NOTED
FOURPLEX RECEPTACLE 2. 9. 11.
+18" OR
AS NOTED
FOURPLEX RECEPTACLE EMERGENCY POWER (RED) 2. 9. 11.
+18" OR
AS NOTED
CORD DROP SEE DIAGRAM
DOOR BELL CHIME +90" 2.
FLOOR BOX - SEE SCHEDULE SEE DIAGRAM, SPEC. FLOOR
POKE THRU - SEE SCHEDULE SEE DIAGRAM, SPEC. FLOOR
MOTOR OUTLET
TO SUIT
EQUIP.
PUSHBUTTON 2.+46"
NON-FUSED DISCONNECT SWITCH 5. 6.+60"
FUSED DISCONNECT SWITCH 5. 6.+60"
BREAKER DISCONNECT SWITCH 5. 6.+60"
MANUAL STARTER THERMAL OVERLOAD SWITCH WITH PILOT LIGHT 2.+46"
MAGNETIC STARTER 6. 7.+60"
MAGNETIC STARTER / DISCONNECT COMBINATION +60" 6. 7.
VARIABLE FREQUENCY DRIVE +66" 6.
PANEL BOARD +72" 6.
MAIN DISTRIBUTION PANEL
UTILITY METER +72" 6.
CORD REEL SEE DIAGRAM
CONTROLLED DUPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
CONTROLLED FOURPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
SPECIAL PURPOSE OUTLET 2. 10. W/CAP.+18" OR
AS NOTED
TELECOMMUNICATIONS
WALL PHONE 2.W
+60" OR
AS NOTED
DATA OUTLET , ONE CABLE 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET, TWO CABLES 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET, THREE CABLES 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET , "X" INDICATES QUANTITYX 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET , CEILING AS NOTED
TELEVISION OUTLET
+18" OR
AS NOTED
2. 9. 11.
TELEPHONE TERMINAL BOARD
EQUIPMENT CEILING RACK CEILING
EQUIPMENT 4-POST RACK/CABINET 18. SEE SPEC.AS NOTED
EQUIPMENT 2-POST 18. SEE SPEC.AS NOTED
SPLITTER
ABOVE
CEILING
VIA
ABOVE
CEILING
FIBER BDA
ABOVE
CEILING
ANTENNAXX CEILINGPS = PUBLIC SERVICE
COM = CELLULAR/COMMERCIAL
WIRELESS ACCESS POINT, TWO CABLES 11.
SOLID = WALL, DASHED = CEILING
SYMBOL SCHEDULE
1. SEE FIXTURE SCHEDULE FOR TYPE, MOUNTING AND WATTAGE.
4. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
8. DOUBLE ARROWS INDICATE A DOUBLE FACE UNIT.
3. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
STANDARD MOUNTING HEIGHT UNLESS OTHERWISE NOTED ON PLANS
11. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR,
6. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
5. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE 'HD' 480V.
2. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
10. SUBSCRIPT INDICATES NEMA CONFIGURATION.
* TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN THIS SET OF DRAWINGS.
12. COORDINATE WITH DOOR HARDWARE SUPPLIER.
7. PROVIDE H.O.A. AND S.S. PUSHBUTTONS AS REQUIRED.
13. FOR WATER COOLER LOCATION, SEE DIAGRAM R002. FOR ALL OTHER LOCATIONS
MOUNT AT +16" TO BOTTOM OF THE BOX FROM FINISHED FLOOR, OR AS NOTED.
9. DEVICES NOTED WITH AN "A" ADJACENT TO IT INDICATES TO COORDINATE
14. ARROWS SHOWN ON DEVICE INDICATE THE SENSOR AIMING LOCATION.
15. CAMERA NUMBERS ARE SHOWN INSIDE THE CAMERA SYMBOL. CAMERA TYPES ARE
16. MOUNT ON TRACK OF OVERHEAD DOOR 6" FROM TOP OF DOOR UNLESS OVERHEAD
17. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
SHOWN IN CAMERA TAGS.
DOOR IS ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
DASHED BOX AROUND DEVICE INDICATES INSTALLED IN CEILING.
NOTES:
18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW DENOTES FRONT OF RANK.
19. SPEAKER TO BE MOUNTED IN HORIZONTAL POSITION.
20. MOUNTING HEIGHTS IS TO BOTTOM OF DISPLAY.
WITH MILLWORK SHOP DRAWINGS AND ELEVATIONS FOR HEIGHT.
GENERAL NOTES
1. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL LIGHTING
FIXTURES.
2. VERIFY ALL EQUIPMENT DIMENSIONS AND LOCATIONS BEFORE BEGINNING ROUGH IN. CONSULT ALL
APPLICABLE CONTRACT DRAWINGS AND SHOP DRAWINGS TO INSURE NEC CODE CLEARANCES
REQUIRED AROUND ALL ELECTRICAL EQUIPMENT.
3. CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION
REQUIREMENTS, ETC.) OF ALL EQUIPMENT FURNISHED UNDER ALL DIVISIONS, INCLUDING ALL EXISTING
EQUIPMENT TO BE RE-USED. REVIEW ALL SHOP DRAWINGS AND EXISTING EQUIPMENT BEFORE
BEGINNING ROUGH IN.
4. SEE SECTION 265100 (16510) OF THE SPECIFICATION REQUIRED COORDINATION MEETINGS WITH
MECHANICAL AND CEILING CONTRACTORS.
5. SEE APPLICABLE SHOP DRAWINGS FOR ROUGH IN LOCATION OF ALL EQUIPMENT, WIRING DEVICES, ETC. WHERE APPLICABLE MOUNT ALL WIRING DEVICES ABOVE BACK SPLASH EXCEPT THOSE SERVING
UNDER COUNTER EQUIPMENT.
6. SEE SPECIFICATION FOR ENERGY SAVING LAMP AND BALLAST REQUIREMENTS.
7. FINISHES OF ALL LIGHT FIXTURES SHALL BE AS SELECTED BY ARCHITECT.
8. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COOPERATE WITH THE MECHANICAL CONTRACTOR SUCH THAT NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE OPERATION OF THE ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE INSTALLED IN, ENTER OR PASS THRU ELECTRICAL ROOMS OR
SPACES, OR ABOVE OR BELOW ELECTRICAL EQUIPMENT IN OTHER AREAS.
9. ELECTRICAL BOXES SHALL NOT BE LOCATED IN MASONRY COLUMNS IN BRICK WALLS OR IN GROUTED CELLS ADJACENT TO OPENINGS. COORDINATE LOCATION OF BOXES WITH MASONRY CONTRACTOR.
10. ALL PENETRATIONS OF FIRE RATED FLOORS, WALLS, AND CEILINGS SHALL BE SEALED WITH
APPROVED MATERIAL TO MAINTAIN FIRE RATING OF SURFACE PENETRATED.
11. CONTRACTOR SHALL VERIFY FURNITURE LAYOUT PRIOR TO ANY FLOORBOX OR POKE-THRU
INSTALLATION. COORDINATE EXACT LOCATION OF FLOOR BOX OR POKE-THRU WITH OWNER AND
FURNITURE PROVIDER PRIOR TO ROUGH-IN.
12. PROVIDE ALL EMERGENCY PANELS REFERENCED IN THIS BID SET, EXISTING OR NEW, WITH A RED LABEL WITH THE PANEL NAME. IF AN EXISTING PANEL HAS A LABEL OF ANOTHER COLOR REMOVE THAT
LABEL AND PROVIDE THE NEW.
13. SINCE THE DRAWINGS ARE A SMALL SCALE IT IS IMPOSSIBLE TO LOCATE DEVICES EXACTLY WHERE
THEY ARE DESIRED. VERIFY THE ACTUAL LOCATION OF ALL DEVICES WITH THE OWNERS
REPRESENTATIVE.
14. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS SHALL BE RUN
WITH CONDUCTORS PER TABLE BELOW.
A. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
B. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO KEEP BRANCH CIRCUIT
VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
C. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT STAYS WITHIN 3%
VOLTAGE DROP FOR A 15 AMP LOAD. IF NECESSARY, CONTRACTOR SHALL INCREASE WIRE AND
CONDUIT SIZE TO MEET THE STANDARD AT NO ADDITIONAL COST TO OWNER.
MAXIMUM LENGTH
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
1. COORDINATE ALL NEW ELECTRICAL EQUIPMENT REQUIREMENTS AND MAKE CONNECTION TO EXISTING SYSTEMS. THIS INCLUDES LIGHTING, POWER, SIGNAL, RACEWAY AND OTHER SYSTEMS INCLUDED UNDER DIVISION 26 (16).
2. RELOCATE, REWIRE AND/OR RECONNECT EXISTING ELECTRICAL DEVICES AND/OR EQUIPMENT THAT FOR ANY REASON
OBSTRUCTS CONSTRUCTION.
3. CONCEAL ALL RACEWAY AND WIRING IN EXISTING WALLS, CEILINGS, FLOORS, ETC. EXCEPT WHERE THE USE OF SURFACE
METAL RACEWAYS (E.G. WIRE MOLD) IS INDICATED ON DRAWINGS OR IN SPEC.
4. LEAVE ALL EXISTING EQUIPMENT, IN PORTIONS OF THE BUILDING NOT BEING REMODELED, IN WORKING CONDITION. RESTORE
ALL INTERRUPTED BRANCH CIRCUITS, FEEDERS, ETC. TO WORKING CONDITION.
5. EXISTING RACEWAYS MAY BE REUSED (IN PLACE) WHERE POSSIBLE, AND WHERE IN COMPLIANCE WITH THE SPECIFICATIONS AND THE INTENT OF THE CONTRACT DOCUMENTS. INSURE INTEGRITY OF EXISTING RACEWAY BEFORE REUSE.
6. REMOVE ALL RACEWAYS, CONDUCTORS, BOXES, DEVICES, EQUIPMENT, ETC. THAT ARE NOT TO BE REUSED.
7. REMOVE EXISTING LIGHT FIXTURES WHICH ARE NOT TO BE REUSED, PLACE IN CARTON, LABEL APPROPRIATELY, AND RETURN
TO OWNER, OR PROPERLY DISPOSE OF FIXTURES THAT THE OWNER CHOOSES NOT TO KEEP.
8. DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
9. DISCONNECT AND RECONNECT ANY/ALL FIXTURES, DEVICES, EQUIPMENT, ETC. REQUIRED FOR PROPER COMPLETION OF THE
WORK.
DEMOLITION NOTES
ABBREV.
# NUMBER
AC ALTERNATING CURRENT
A.F.F. ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING CAPACITY
AM AMPS METER
AMP AMPERE
ANN ANNUNCIATOR
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISH GRADE
C CONDUIT
CAB CABINET
CATB COMMUNITY ANTENNA TELEVISION
CATV CABLE TELEVISION
CKT CIRCUIT
CLG CEILING
CNTR CONTRACTOR
C.O. CONDUIT ONLY
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
C/W COMPLETE WITH
DB DECIBEL
DC DIRECT CURRENT
DWG DRAWING
(E) EXISTING
EC EMPTY CONDUIT
EG EMERGENCY GENERATOR
EMT ELECTRICAL METALLIC TUBING
EX EXPLOSION PROOF
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FT FOOT
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HP HORSE POWER
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IN INCH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MNF MANUFACTURER
MAX MAXIMUM
MB MAIN BUS
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MTG MOUNTING
MTR MOTOR
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT. MANUFAC. ASSOC.
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOC.
N.I.C. NOT IN CONTRACT
NO NORMALLY OPENED
NTS NOT TO SCALE
OS & Y OUTSIDE SCREW & YOKE
PB PUSHBUTTON
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
(R) RELOCATE
RECEP RECEPTACLE
REQ REQUIREMENT
RLA RATED LOAD AMPS
RMS ROOT MEAN SQUARE
SE SERVICE ENTRANCE
SPEC SPECIFICATIONS
SPKR SPEAKER
SS SELECTOR SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UPS UNINTERRUPTED POWER SUPPLY
V VOLT (KV-KILOVOLT)
VA/R VOLT-AMPS/REACTIVE
VM VOLT METER
W WATTS
W/ WITH
WH WATTHOUR METER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFMR SW TRANSFER SWITCH
XP EXPLOSION PROOF
1P SINGLE-PHASE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
Ø PHASE
DESCRIPTION ABBREV. DESCRIPTION
ABBREVIATIONS INDEX
IFC INTERNATIONAL FIRE CADE
E1 SYMBOLS, SCHEDULES AND NOTES
E3.2 ELK MEADOWS ELEMENTARY - POWER PLAN
E3.3 HERRIMAN ELEMENTARY - POWER PLAN
E3.4 JORDAN RIDGE ELEMENTARY - POWER PLAN
E3.5 ROSAMOND ELEMENTARY - POWER PLAN
E3.6 ROSE CREEK ELEMENTARY - POWER PLAN
E3.7 SOUTH JORDAN ELEMENTARY - POWER PLAN
E3.8 SOUTHLAND ELEMENTARY - POWER PLAN
E3.9 SOUTH HILLS MIDDLE SCHOOL - POWER PLAN
E3.10 SOUTH JORDAN MIDDLE SCHOOL - POWER PLAN
INDEX OF ELECTRICAL DRAWINGS
TYPICAL RACEWAY SUPPORT METHODS
NTS
STRUCTURAL UNIT
CONDUIT HANGER
RACEWAY - 3/4" THRU 6"
H003DIAGRAM
NUTS
FLAT WASHER
1/4" STEEL PLATE
NUT
FLAT WASHER
1/4" STEEL PLATE
ALL THREAD ROD
SIZE AS REQUIRED
ALL THREAD - SIZE AS
REQUIRED (3/8" MINIMUM)
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E1
SYMBOLS,
SCHEDULES
AND NOTES
IDF-GYM
MDF-LMC
E1
E2
E3
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.2
ELK MEADOWS
ELEMENTARY
POWER PLAN
EL
K
M
EA
D O
W S
EL
EM
EN
TA
R Y, W
ES
T
S O
U
TH
, S O
U
TH
J O
R D
AN
, U
TA
H
E1 CHANGE OUT THE TWO EXISTING 4-PLEX RECEPTACLES TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND
RECONNECT TO EXISTING CIRCUIT (VERIFY CIRCUIT IN PANELBOARD 'E').
E2 CHANGE OUT THE EXISTING DUPLEX RECEPTACLE TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND
RECONNECT TO EXISTING CIRCUIT (VERIFY CIRCUIT IN PANELBOARD 'E').
E3 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACE IN PANEL 'E'. PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
SHEET KEYNOTES
POWER PLAN
1/16" = 1'-0" 0 8' 16' 32'
MDF-LMC E1
IDF-STO
E3
E2
EXISTING
PANEL 'E'
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.3
HERRIMAN
ELEMENTARY
POWER PLAN
H
ER
R
IM
AN
E
LE
M
EN
TA
R Y, S
O U
TH
W
ES
T, H
ER
R
IM
AN
, U
TA
H
E1 CHANGE OUT THE TWO EXISTING 4-PLEX RECEPTACLES TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND RECONNECT ONE 4-PLEX TO EACH EXISTING CIRCUIT (E-7,9 (VERIFY)). PROVIDE TWO NEW 4-PLEX RECEPTACLES. PROVIDE 20A/1P CIRCUIT BREAKERS AT EXISTING SPACES 33 AND 35 IN PANEL 'E'. PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKERS. VERIFY ALL REQUIREMENTS FOR PANEL
COMPATIBILITY.
E2 CHANGE OUT THE EXISTING DUPLEX RECEPTACLE TO TWO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND
RECONNECT ONE EXISTING CIRCUIT TO EACH 4-PLEX (E-11,13 (VERIFY)).
E3 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACES 37 AND 39 IN PANEL 'E'. PROVIDE CONDUIT AND WIRE FROM EACH 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
SHEET KEYNOTES
'LC(E)'
'LN(E)'
'P(E)'
'2P(E)'
'3P(E)'
'L(E)'
'E(E)'
'E1(E)'
CLASSROOM
OFFICE
OFFICE
KILN
ASST.
PRINCIPAL'S
OFFICE
CONFERENCE
ROOM
OFFICE
OFFICE
OFFICE
MEDIA CENTER
PSYCHOLOGIST'S
OFFICE
FRONT OFFICE
AREA
RESTROOM
TEACHER
WORK ROOM
RECEPTION
PRINCIPAL'S
OFFICE
'M'
'FACP'
'8P'
'7P1(E)'
EXISTING
PANEL 'E1'
E1 E2
MDF-LMCMDF-LMC
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.4
JORDAN RIDGE
ELEMENTARY
POWER PLAN
JO
R
D
AN
R
ID
G E
EL
EM
EN
TA
R Y, W
ES
T
S O
U
TH
, S O
U
TH
J O
R D
AN
, U
TA
H
POWER PLAN
1/16" = 1'-0" 0 8' 16' 32'
E1 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACES 11 AND 13 IN PANEL 'E1'. PROVIDE CONDUIT AND WIRE FROM EACH 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
E2 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACES 15 AND 17 IN PANEL 'E1'. PROVIDE CONDUIT AND WIRE FROM EACH 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
SHEET KEYNOTES
EXISTING
PANEL 'EM'
E1
E2
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.5
ROSEMOND
ELEMENTARY
POWER PLAN
R O
SA
M
O N
D E
LE
M
EN
TA
R Y, S
O U
TH
W
ES
T, R
IV
ER
TO
N
, U
TA
H
POWER PLAN
1/16" = 1'-0" 0 8' 16' 32'
E1 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACES 20 AND 22 IN PANEL 'EM'. PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
E2 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACE 24 AND 26 IN PANEL 'EM' PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
MDF-LMCE1
IDF-STO
E2
E3
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.6
ROSE CREEK
ELEMENTARY
POWER PLAN
R O
SE
C
R
EE
K
EL
EM
EN
TA
R
Y, S O
U
TH
W
ES
T, R
IV
ER
TO
N , U
TA
H
POWER PLAN
1/16" = 1'-0" 0 8' 16' 32'
E1 CHANGE OUT THE THREE EXISTING 4-PLEX RECEPTACLES TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND RECONNECT ONE EXISTING CIRCUIT TO EACH 4-PLEX (E-7,13, 15 (VERIFY)). PROVIDE A 20A/1P CIRCUIT BREAKER AT SPACE #25. PROVIDE CONDUIT AND WIRE FROM THE NEW 4-PLEX TO THE NEW BREAKER.
E2 CHANGE OUT THE EXISTING DUPLEX RECEPTACLE TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES. PROVIDE A 20A/1P CIRCUIT BREAKERS AT EXISTING SPACES 28 AND 30 IN PANEL 'E'. PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
E3 CHANGE OUT THE EXISTING DUPLEX RECEPTACLE TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES. PROVIDE A 20A/1P CIRCUIT BREAKERS AT EXISTING SPACES 27 AND 29 IN PANEL 'E'. PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
MDF-LMG
IDF-STO
E1
E3 E2
E4
EXISTING PANEL 'E1'
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.7
SOUTH
JORDAN
ELEMENTARY
POWER PLAN
SO
U
TH
J
O R
D
AN
E
LE
M
EN
TA
R
Y, S O
U
TH
B
LA
C K
C H
ER
R
Y W
AY
, S
O U
TH
J
O R
D
AN
, U
TA
H
POWER PLAN
1/16" = 1'-0" 0 8' 16' 32'
E1 CHANGE OUT THE TWO EXISTING 4-PLEX RECEPTACLES TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND
RECONNECT ONE EXISTING CIRCUIT TO EACH 4-PLEX (E1-13,15 (VERIFY)).
E2 CHANGE OUT THE EXISTING DUPLEX RECEPTACLE TO NEW 4-PLEX RECEPTACLE WITH RED DEVICES AND
RECONNECT ONE EXISTING CIRCUIT TO THE 4-PLEX (E1-17 (VERIFY)).
E3 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACE 28 IN PANEL 'E1'. PROVIDE CONDUIT AND WIRE FROM 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
E4 CHANGE OUT THE TWO EXISTING 4-PLEX RECEPTACLES TO NEW 4-PLEX RECEPTACLES WITH RED DEVICES AND
RECONNECT ONE EXISTING CIRCUIT TO EACH 4-PLEX (E1-19,21 (VERIFY)).
EXISTING
PANEL 'EM'
E1
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.8
SOUTHLAND
ELEMENTARY
POWER PLAN
SO
U
TH
LA
N D
E
LE
M
EN
TA
R
Y, S O
U
TH
W
ES
T, R
IV
ER
TO
N , U
TA
H
E1 PROVIDE A 20A/1P CIRCUIT BREAKER AT EXISTING SPACES 13 AND 28 IN PANEL 'EM'. PROVIDE CONDUIT AND WIRE FROM EACH 4-PLEX TO A 20A CIRCUIT BREAKER. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY.
SHEET KEYNOTES
'EM2A'
'AL'
'B1'
'AH''RP1'
'RP2'
'A1'
'MDP'
'LDP'
'T1'
'ME'
'ME1'
'TRANSFER
SWITCH'
'EH'
'T3'
'EL'
'K1'
'K2'
CLASSROOM
A144
CLASSROOM
A145 CLASSROOM
A158 CLASSROOM
A159
CORRIDOR
A101
CLASSROOM
A155
CLASSROOM
A156
CLASSROOM
A142
CLASSROOM
A143
CORRIDOR
A169
VEST.
A170
CLASSROOM
A138
CLASSROOM
A139
CORRIDOR
A157
TEACH PREP
A150
TEACH PREP
A151 JAN
A152
GIRLS
A153
PRACT STOR
A162
BAND
A160
CHORAL
A161
PRACT
A164
BAND STORAGE
A128
BOYS
A154
CLASSROOM
A138
CLASSROOM
A136
CLASSROOM
A137
CLASSROOM
A148
CLASSROOM
A149
CLASSROOM
A146
CLASSROOM
A147
CORRIDOR
A165
VEST.
A166
VEST.
A130B
TEACH PREP
A135
TEACH PREP
A134 BOYS
A167 GIRLS
A168
CHASE
A168A
CHASE
A167A
VEST.
A100
VICE PRINCIPAL
A129
RESTROOM
A130
COUNSELING
A119
ATTENDANCE
A124
SICK ROOM
A125
RESTROOM
A122
RESTROOM
A126
COUNSELOR
A115
COUNSELOR
A118
COPY/ MAIL
A103
STORAGE
A104PSYCHOLOGIST
A117
COUNSELOR
A114
COUNSELOR
A113
OFFICE
A106
SRO
A105
STORAGE
A110 PRINCIPAL
A109
CONFERENCE
A107
MAIN OFFICE
A102
HALL
A112
STORAGE
B103
B B102
E B104
B.
B105
CORRIDOR
B111
AUDITORIUM
B109
CORRIDOR
B112
STOR
B107
CORRIDOR
B106
STAIR
B108
ENTRY
B101
CORRIDOR
D121CORRIDOR
C138
J C132
JAN OFFICE
C133 STO
C134
STO
C135
JAN
C129
OFFICE
C128
LAV
C128A
LAV
C109A
OFFICE
C109
TOILET
C127
TOILET
C108
CHASE
C127A
JAN
C111
GIRLS
LOCKERS
C110
BOYS LOCKERS
C130
CLASSROOM
C104
RESOURCE
CLASSROOM
C105
RESTROOM/SHOWER
C105B
STORAGE
C105A
CORRIDOR
C121
CLASSROOM
C101
STO
C107
STORAGE
C102
ELECTRICAL
C103
J.
C106
GIRLS
C139
BOYS
C140
STO
D113
CAFETERIA
D157
GYMNASIUM
C136
CORRIDOR
D121
VEST.
D100
BREAK
D137
KITCHEN
D130
SERV
D143
SERV
D142
FOOD COURT
D141
TEACH LOUNGE
D104
BOYS
D106
GIRLS
D107
HALL
D167
BOYS
D153
GIRLS
D152
STOR
D124
FRZZ
D131
REFR
D132
OFFICE
D133
LAUNDRY
D134
DRY STOR.
D135
MECHANICL
ROOM
D125
FAN ROOM
D127
ELECTRICAL
ROOM
D126
STORAGE
ROOM
D128
FILE ROOM
D122
OFFICE
D123
CLASSROOM
D101
CORRIDOR
D161
ART
E139
ART
E140
VEST.
E100
ART STOR/ KILN
E142
ART STOR/ KILN
E141
VEST
E130
CORRIDOR
E108
CORRIDOR
E101
TLC LAB 2000
E102
A/V E105
CLASSROOM
E138
CLASSROOM
E137
OFF/STO
E103
OFF/STO
E106
LECTURE
E104
SMART LAB
E107
CLASSROOM
E135
CLASSROOM
E136
CORRIDOR
E131
TEACH PREP
E132
TEACH PREP
E133
BOYS
E134
CHASE
E143
CLASSROOM
E128
CLASSROOM
E127
J.
E113
GIRLS
E114
LAB
E117
CLASSROOM
E126
CLASSROOM
E125
CLASSROOM
E123
CLASSROOM
E122
CLASSROOM
E119
CLASSROOM
E118
CORRIDOR
E121
MEDIA CENTER
F146
CLASSROOM
F148
CORRIDOR
F101
OFFICE
F151
BOYS
F154
GIRLS
F155
JAN
F156
MEDIA WORK
F152
PERIOD
F153
ELEC ROOM
F141
TEACH PREP
F142
AV STOR
F143
CAREER
F144
CONF
F145
VEST.
F140
CORRIDOR
F141
CLASSROOM
F107
FOODS
F106
STOR
F105STOR
F103
PANTRY
F104
SEWING
F102
SCIENCE
F113
SCIENCE
F112
SCIENCE
F114
SCIENCE
F115
SCIENCE
F116
CORRIDOR
F121
CORRIDOR
F131
CLASSROOM
F123
CLASSROOM
F122
CLASSROOM
F125
CLASSROOM
F124
TEACH PREP
F137
TEACH PREP
F128
GIRLS
F127
JAN
F126
CLASSROOM
F133
CLASSROOM
F136
CLASSROOM
F135
CLASSROOM
F134
VEST.
F130
'B4'
'D8' 'D2'
'D1'
'DXDP'
'T2'
'DX' 'D3'
'D5'
'D6'
'D7'
'RP3'
VICE PRINCIPAL
A127GROUP ROOM
A121
EL2-8EL2-4
IDF-222f
EL-9
IDF-215c
EL2-8EL2-6
IDF-116b
EXISTING PANEL 'EH'
NEW TRANSFORMER 'TX-EL2'
NEW PANEL 'EL2'
EL2-12EL2-10
IDF-607
EL2-13EL2-11
IDF-306
EL2-5
MDF
EL2-1
EL2-7EL2-3
EL2-6EL2-2
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.9
SOUTH HILLS
MIDDLE
SCHOOL
POWER PLAN
SO
U
TH
H
IL
LS
M
ID
D
LE
S C
H O
O L, S
O U
TH
W
ES
T, R
IV
ER
TO
N
, U
TA
H
POWER PLAN
1" = 20'-0" 0 10' 20' 40'
E1 PROVIDE A 30A/3P CIRCUIT BREAKER IN THE EXISTING PANEL 'EH'. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY IN 'EH'. REFER TO ONE-LINE DIAGRAM FOR FEEDER SIZING. COORDINATE WITH OWNER FOR
ACCESS TO MOUNTING SPACE FOR NEW TRANSFORMER AND PANEL 'EL2'.
SHEET KEYNOTES
NEW TRANSFORMER 'TX-EM3'
480V-208/120 VOLT
3 PHASE, 4 WIRE,
15 KVA
(3) #10 THWN AND
(1) #10 GRND.
IN 1" CONDUIT
(4) #4 THWN AND
(1) #8 GRND.
IN 1-1/4" CONDUIT
WOODWORKING
E108
WOODWORKING
E102
WOOD STOR
E111
SUPPLY
E110
TEACH PREP
E109
PAINT
E103
PAINT
E104
PROJ STOR
E105
PROJ STOR
E106
VEST
E100
METAL WORK
E107
HALL
E141
JAN
E113
GIRLS
E114
TEACH PREP
E139
SUPPLY
E140
METAL STOR
E117
CLASSROOM
E138
CLASSROOM
E137
CLASSROOM
E136
CLASSROOM
E135
CORRIDOR
E101
BOYS
E134
CHASE
E143
TEACH PREP
E133
TEACH PREP
E132
VEST
E130
CORRIDOR
E131
CLASSROOM
E127
CLASSROOM
E128
CLASSROOM
E118
CLASSROOM
E119
CLASSROOM
E122
CLASSROOM
E123
CLASSROOM
E125
CLASSROOM
E126
CORRIDOR
E121
VEST
E120
SEWING
F102
PANTRY
F104
STO
F105STO
F103
FOODS
F106
CLASSROOM
D133
CORRIDOR
F101
TEACH WORK
F149
CLASSROOM
F148
MEDIA CENTER
F146
CONF
F145
VEST
F140
CAREERS
F144
AV. STOR
F143
TEACH PREP
F142
DARK RM
F157
CORRIDOR
F141
PERIOD ST
F153
MEDIA WORK
F152
OFFICE
F151
BOYS
F154
GIRLS
F155
J.
F156
CORRIDOR
F111
SCIENCE
F112
SCIENCE
F115
SCIENCE PREP
F114
SCIENCE
F116
CORRIDOR
F121
CLASSROOM
F122
CLASSROOM
F123
CLASSROOM
F124
CLASSROOM
F125
TEACH PREP
F137
TEACH PREP
F128
JAN
F126
GIRLS
F127
CLASSROOM
F133
CLASSROOM
F136
CLASSROOM
F135
CLASSROOM
F134
VEST
F130
CORRIDOR
F131
PRACT-STOR
A164
CHORAL
A161
BAND
A160
PRACT-STOR
A162
CORRIDOR
A101
CLASSROOM
A155
CLASSROOM
A159
CLASSROOM
A158
CLASSROOM
A156
CORRIDOR
A157
CLASSROOM
A145
CLASSROOM
A144
CLASSROOM
A143
CLASSROOM
A142
PRACTICE
ROOM
A163
STORAGE
A128BOYS
A154
STORAGE
A120
GROUP ROOM
A121
FLEX SPACE
A127
CAMERA
A129
RESTROOM
A130
JAN
A152GIRLS
A153
TEACH PREP
A151
TEACH PREP
A150
CORRIDOR
A169VEST
A170
CLASSROOM
A138
CLASSROOM
A139
CLASSROOM
A136
CLASSROOM
A137
VEST
A180
CORRIDOR
A165 VEST
A166
CLASSROOM
A147
CLASSROOM
A146
CLASSROOM
A149CLASSROOM
A148
VEST
A100
TEACHER PREP
A135 TEACHER PREP
A134
BOYS
A167 GIRLS
A168
PIPE CHASE
A132
PIPE CHASE
A131
COUNSELING
A119
RESTROOM
A122
SICK ROOM
A125
RESTROOM
A126
ATTENDANCE
A124
COUNSELOR
A115 COUNSELOR
A118
HALL
A116
PSYCHOLOGIST
A117
COUNSELOR
A114
STORAGE
A104
COPY / MAIL
A103
SRO
A105
OFFICE
A106COUNSELOR
A113
HALL
A112
PRINCIPAL
A110 VICE PRINCIPAL
A109
VICE PRINCIPAL
A108
CONFERENCE
A107
ENTRY
B101
CORRIDOR
B113
MECH
B102
STOR
B103
Unoccupied Unoccupied
AUDITORIUM
B109
MECH
B104
CLASSROOM
C101
ELECTRICAL
C103
STORAGE
C102
STO
C107
JAN
C106
CORRIDOR
C139
WOMEN'S
C164
CHASE
C164A
CHASE
C165A
MEN'S
C165
GIRLS LOCKER
ROOM
C110
CORRIDOR
C121
CLASSROOM
C104
STO
C126
TOILET
C108 OFFICE
C109
JAN
C111
LAV
C109A
LAV
C128A
TOILET
C127
CHASE
C127A
OFFICE
C128
JAN
D144
BOYS LOCKER
ROOM
C130
CLASSROOM
C105
JAN
C132
JAN OFF
C133
STO
C134
STO
C135
CORRIDOR
C138
CLASSROOM
D101
ART #2
D102
TEACH LOUNGE
D104
CORRIDOR
D121
MEN
D106
CHASE
D103
WOMEN
D107
HALL
D167
CORRIDOR
D161 CHASE
D124
STOR ROOM
D123
OPEN
D128
ART STOR &
KILN RM
D131
REFRIG
D133
FREEZ
D132
KITCHEN
D141
OFF
D134
LOCK
D135
LAUN
D143
CAN
D142
EQUIP ROOM
D127
RUBBISH STO
D126
VEST
D120
TEACH PREP
D125
DRY FOOD STO
D138
JAN
D137
RECEIVING
D136
VEST
D100
CAFETERIA
D157
VEST
C129
STOR
C131
GYMNASIUM
C136
CORRIDOR
B111
VEST
B110
STAIR
C140
'EM2'
'EM'
'EM2A'
'AH'
'RP1'
'A1'
'B3'
'XFMR
SW'
'FACP'
'B2'
EM2A-1
EM2A-3
IDF-218d
EXISTING PANEL 'EM2'
NEW PANEL 'EM2A' E1
EM2A-2
IDF-KIT MOUNTED
ABOVE THE TOP
CABINET
E2
EM2A-5
MDF
EM2A-7
EM2A-4
IDF-812
IDF-110
EM2A-6
E3
IDF-306c
EM2A-9 EM2A-11
JO
R
D
AN
S C
H O
O L
D
IS
TR
IC
T
EM
ER
G
EN
C
Y
PO
W
ER
T O
IT
C
LO
SE
TS
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
BI
D
P
AC
KA
G
E #3
E3.10
SOUTH
JORDAN
MIDDLE
SCHOOL
POWER PLAN
SO
U
TH
J
O R
D
AN
M
ID
D
LE
S C
H O
O L, S
O U
TH
W
ES
T, S
O U
TH
J
O R
D
AN
, U
TA
H
POWER PLAN
1" = 20'-0" 0 10' 20' 40'
E1 PROVIDE A LOAD CENTER 'EM2A' (EXTENSION TO PANEL 'EM2') ADJACENT TO PANEL 'EM2'. PROVIDE A 50A/3P CIRCUIT BREAKER AT SPACES 27, 29, 31. VERIFY ALL REQUIREMENTS FOR PANEL COMPATIBILITY IN 'EM2'
E2 PROVIDE THE NEW DUPLEX IN THE JUNCTION BOX SUPPLIED INSIDE THE IDF CABINET.
E3 CHANGE OUT THE EXISTING 4-PLEX RECEPTACLE TO A NEW 4-PLEX RECEPTACLE WITH RED DEVICES AND
RECONNECT TO EXISTING CIRCUIT (EM2-25 (VERIFY)).
SHEET KEYNOTES
(4) #6 THWN AND (1) #8 GND
IN 1" CONDUIT
| Sheets and Views |
| 24349-A CVR-Layout1 |
| 24349-A E1-Layout1 |
| 24349-D E32-Layout1 |
| 24349-D E33-Layout1 |
| 24349-D E34-Layout1 |
| 24349-D E35-Layout1 |
| 24349-D E36-Layout1 |
| 24349-D E37-Layout1 |
| 24349-D E38-Layout1 |
| 24349-D E39-Layout1 |
| 24349-D E310-Layout1 |