5-2-CR27021-27131420 Approved Plans.pdf
PDF 6 MB Posted
- Solicitation number
- CR27021
- Issued by
- Utah
About this file
Summary of Approved Construction Plans for HVAC Units Project
This document comprises approved construction plans for a mechanical, plumbing, and electrical project at the Utah State Hospital Support Services facility located at 1300 East Center Street, Provo, Utah. The project, identified as DFCM Project No. 27131420, involves replacement of existing HVAC equipment including rooftop units (RTU-1, RTU-2, RTU-3), exhaust fans (EF-5), evaporative coolers (EC-1, EC-2), and unit heaters (UH-1 through UH-5) with a construction cost estimate of $230,000. The approved plans include comprehensive mechanical, plumbing, and electrical documentation with detailed specifications for equipment schedules, ductwork modifications, gas and water supply extensions, and complete electrical connections. The Division of Facilities Construction and Management (DFCM) approved the plans on September 10, 2026, with project management by Jason Van Ausdal and engineering review by Jacob D. Beck (Mechanical), Jacob D. Beck (Plumbing), and Sang Truong (Electrical). The project is limited to prequalified Stage II contractors currently on the DFCM Prequalified Contractors list.
The mechanical scope includes installation of Trane rooftop units (YSK060, YSK048, YSK072) with heating and cooling capacity ranging from 1,750 to 2,200 CFM, Reznor fuel-fired unit heaters with capacities from 30 to 120 MBH, Markel electric unit heaters rated at 25 kW for hazardous environments, and Arctic Circle evaporative coolers. The plumbing scope encompasses a new AO Smith 100 MBH gas-fired water heater with high-efficiency operation, gas piping extensions with pressure regulators and shut-off valves for all mechanical equipment, and domestic water supply lines with expansion tank provisions. The electrical work includes distribution panels with 208Y/120V and 480Y/277V service, branch circuits for motor starters and disconnects, conduit sizing from 3/4" to 1-1/2", and compliance with NEC standards including ground fault protection and seismic bracing requirements. All equipment is rated for 4,300-foot elevation at the Provo location and requires field verification of existing conditions prior to installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVO, UTAH
C001
JD
COVER SHEET
DFCM Project No. 27131420
CONSTRUCTION DOCUMENTS
Vicinity Map
SHEET INDEX
USH - SUPPORT SERVICES
PROJECT SITE
PROVO, UTAH
NORTH
CONSULTANTS
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)________
1) One Story: ______
c) Total Allowable Area for:
N/A (NON-SEPARATED OCCUPANCIES)
b) Sum of the Ratio Calculations for Mixed Occupancies:
a) 0.25I = 100f F P 30
WstA I 100100 fIA t taA = A + +
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Hours Assembly ListingListing
Element AssemblyHours
Smoke Partitions Fire Partitions
Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers
Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
_____________________________________________________Tabular Area:I:
per Floor (square feet): _________________________________________Actual AreaH:
Number of Stories: ______ Building Height: ___________G:
Required: ______ Provided: _________ Type of Sprinkler System: __________
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: _______ ________ ________ ________ ________
CODE ANALYSIS
N
N N
X X
NO
N/AN/A
NR NR NR NR
NO
YES YES NFPA 13
1 15' - 0"
N/A
3) Deferred Submittals:
a) Seismic Bracing for Mechanical and Electrical. Work related to the deferred
N/A
N/AX
UL
submittals shall not commence until the building official has approved the submittal.
N/A
N/A
B 1300 East Center Street Provo, Utah 84603
HVAC UNITS
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
REVIEWED FOR CODE
COMPLIANCE
LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS
MECHANICAL PLUMBING PLUMBING CONT. LINETYPES LINETYPES CONT.
SYMBOLS
FIRE
M001
JD
MECHANICAL
SYMBOLS AND
ABBREVIATIONS
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
GENERAL NOTES
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
(E) 24/14
(E) 24/14
(E) SUPPLY
GRILLE TO
REMAIN
MD101
JD
LEVEL 1
MECHANICAL DEMO
PLAN
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
KEYED NOTES#
1. DEMOLISH AND REMOVE EXISTING UNIT HEATER, AND ALL
ASSOCIATED ACCESSORIES.
2. DEMOLISH AND REMOVE EXISTING THERMOSTAT. FIELD VERIFY
EXACT LOCATION OF THERMOSTAT PRIOR TO ANY DEMOLITION.
TYPICAL OF ALL.
3. DEMOLISH EXISTING EVAPORATIVE COOLER, FAN, AND ALL
ASSOCIATED ACCESSORIES AS SHOWN X'D. FIELD VERIFY
EXISTING CONDITIONS.
4. DEMOLISH EXISTING ROOFTOP UNIT AND ALL ASSOCIATED
ACCESSORIES. FIELD VERIFY EXISTING CONDITIONS.
5. DEMOLISH EXISTING ROOFTOP EXHAUST FAN AND ALL
ASSOCIATED ACCESSORIES. FIELD VERIFY EXISTING
CONDITIONS.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
T
T
T
UH
UH
UH
UH
UH
T
T
EUH
M501
TYP.
(E) 24/14
(E) 24/14
RTU
RTU
RTU
EF
M501
M501
(TYP)
T
EC
M501
(SIMILAR)
T
EUH
T
EC
42/22
(E) 42/30 GRILLE
M101
JH
LEVEL 1
MECHANICAL PLAN
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
KEYED NOTES#
1. EXTEND COMBUSTION AIR AND FLUE THRU ROOF. PROVIDE
AND INSTALL FLASHING AND SEALANT TO ENSURE WEATHER
TIGHT SEAL.
2. CONNECT NEW DUCTWORK TO EXISTING DUCTWORK BELOW
ROOF. FIELD VERIFY ALL EXISTING CONDITIONS. TYPICAL OF
ALL.
3. UNIT SHALL MAINTAIN EXISTING CONTROLS - INTERLOCK WITH
RTU-3. CONTRACTOR SHALL DISCONNECT AND RECONNECT.
4. EXTEND NEW DUCTWORK TO EXISTING GRILLE. COORDINATE
EXACT GRILLE SIZE WITH EXISTING CONDITIONS.
5. EXTEND EXISTING CONCRETE PAD AS NEEDED TO
ACCOMMODATE NEW EQUIPMENT SIZE.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
M501
JH
MECHANICAL
DETAILS &
SCHEDULES
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
FUEL FIRED UNIT HEATER SCHEDULE
ELECTRICAL
INPUT OUTPUT
MANUFACTURER FLUE AIRFLOW HEATING HEATING MOTOR MOTOR
AND SIZE RATE LOAD LOAD SIZE SPEED
ID MODEL NUMBER LOCATION TYPE (IN) (CFM) (MBH) (BTU/H) (HP) (RPM) FLA MOCP VOLT/PH/HZ NOTES
UH-1 REZNOR UDAS 30 SEE PLANS NATURAL GAS 4 450 30 19.7 1/6 1550 1.9 15 115/1/60 1,2,3
UH-2 REZNOR UDAS 125 SEE PLANS NATURAL GAS 4 1525 120 79.7 1/4 1050 5.1 15 115/1/60 1,2,3
UH-3 REZNOR UDAS 125 SEE PLANS NATURAL GAS 4 1525 120 79.7 1/4 1050 5.1 15 115/1/60 1,2,3
UH-4 REZNOR UDAS 125 SEE PLANS NATURAL GAS 4 1525 120 79.7 1/4 1050 5.1 15 115/1/60 1,2,3
UH-5 REZNOR UDAS 125 SEE PLANS NATURAL GAS 4 1525 120 79.7 1/4 1050 5.1 15 115/1/60 1,2,3
1. GAS HEATING INPUT AT SEA LEVEL, ALL OTHER CAPACITIES AT ELEVATION.
2. SEALED COMBUSTION.
3. UNIT TO COME WITH WALL MOUNTED THERMOSTAT.
ELECTRIC UNIT HEATER SCHEDULE
AIR ELECTRICAL
ENTERING LEAVING
MANUFACTURER AIRFLOW HEATING TEMP. TEMP.
AND RATE LOAD CAPACITY DB DB TOTAL CONTROL
ID MODEL NUMBER LOCATION TYPE USAGE (CFM) (BTU/H) (KW) (°F) (°F) AMPS VOLTAGE VOLT/PH/HZ NOTES
EUH-1 MARKEL HLA 20 PAINT ROOM NOTE 1 HEATING 2,450 85,400 25 60 98 31.1 24 460/3/60 1,2,3,4 EUH-2 MARKEL HLA 20 PAINT ROOM NOTE 1 HEATING 2,450 85,400 25 60 98 31.1 24 460/3/60 1,2,3,4
1. HORIZONTAL DISCHARGE, EXOLOSION PROOF UNIT.
2. PROVIDE DISCONNECT SWITCH,
3. MOTOR SHALL BE RATED FOR HAZARDOUS ENVIROMENTS.
4. UNIT TO COME WITH WALL MOUNTED THERMOSTAT FOR STAND-ALONE CONTROLS.
EVAPORATIVE COOLER SCHEDULE
AIR MAKEUP ELECTRICAL, FAN PHYSICAL
ENTERING LEAVING WATER LENGTH
MANUFACTURER AIRFLOW TEMP. TEMP. STATIC INLET MOTOR WIDTH/ PAD
AND RATE DB/WB DB/WB PRESSURE DIA SIZE HEIGHT WEIGHT AREA
ID MODEL NUMBER LOCATION TYPE (CFM) (°F) (°F) (IN. WATER) (IN) (HP) VOLT/PH/HZ (IN) (LBS) (FT²) NOTES
EC-1 ARCTIC CIRCLE ED630G ROOF NOTE 1 3,370 95 63 0.4 1/2 1/2 120/1/60 37 / 37 / 42 250 7.9 1,2,3,4,5,7
EC-2 ARCTIC CIRCLE ES630G GROUND NOTE 6 3,370 95 63 0.4 1/2 1/2 120/1/60 37 / 37 / 42 250 7.9 2,3,4,5,6,7
1. DOWN DISCHARGE. UNIT TO COME WITH ROOF CURB.
2. UNIT CAPACITIES AT SEA LEVEL
3. TWO SPEED MOTOR. UNIT SHALL COME WITH DISCONNECT
4. SINGLE POINT CONNECTION. PROVIDE INTEGRAL TRANSFORMER FOR MOTOR.
5. UNIT TO COME WITH 3.0 GPM PUMP.
6. SIDE DISCHARGE.
7. UNIT TO COME WITH WALL MOUNTED THERMOSTAT CONTROL.
EXHAUST FAN SCHEDULE
AIR FAN ELECTRICAL PHYSICAL CONTROL
MAXIMUM TOTAL FAN
MANUFACTURER AIRFLOW STATIC OUTLET FAN WHEEL STATIC MOTOR MOTOR
AND AIR RATE PRESSURE VELOCITY SPEED DIAMETER EFFICIENCY SIZE BHP WEIGHT
ID MODEL NUMBER LOCATION TYPE TYPE (CFM) (IN. WATER) (FPM) (RPM) (IN) (%) (HP) (HP) VOLT/PH/HZ (LBS) NOTES
EF-5 COOK 120 ACEB ROOF BELT EXHAUST 1085 0.5 1144 1355 12 56% 1/4 0.2 120/1/60 100 A 1,2
1. ALL CAPACITIES AT 4300 FT. ELEVATION.
2. ROOF MOUNTED EXHAUST FAN, COMPLETE WITH 18" PRE-FAB ROOF CURB, GRAVITY BACKDRAFT DAMPER, BIRD SCREEN, INTEGRAL THERMAL OVERLOAD PROTECTION, DISCONNECT.
A. CONTROL: ATC
PACKAGED ROOFTOP UNIT SCHEDULE
SUPPLY FAN HEATING SECTION COOLING SECTION ELECTRICAL PHYSICAL
EXTERNAL INPUT OUTPUT ENTERING/ ENTERING LEAVING
MANUFACTURER AIRFLOW STATIC HEATING HEATING LEAVING COOLING AMBIENT AIR TEMP. AIR TEMP. UNIT UNIT SINGLE DIMENSIONS MAX
AND RATE PRESSURE LOAD LOAD AIR TEMP. LOAD TEMP. DB/WB DB/WB MCA MOP POINT L x W x H WEIGHT ID MODEL NUMBER LOCATION (CFM) (IN. WATER) (MBH) (MBH) (°F) (MBH) (°F) (°F) (°F) SEER2 EER2 REFRIGERANT (A) (A) VOLT/PH/HZ (INCH) (LBS) NOTES
RTU-1 TRANE YSK0 060 ROOF 2,000 1.0 150 99.6 40 / 98 54.0 100 80 / 62 52 / 51 13.4 11 R-454B 29 45 208/3/60 70 / 45 / 47 850 1,2,3,4,5 RTU-2 TRANE YSK 048 ROOF 1,750 1.0 130 86.4 40 / 98 43.3 100 80 / 62 53 / 52 13.4 11 R-454B 27 40 208/3/60 70 / 45 / 47 850 1,2,3,4,5 RTU-3 TRANE YSK 072 ROOF 2,200 1.0 150 99.6 50 / 94 72.5 100 80 / 62 51 / 51 13.4 11 R-454B 38 50 208/3/60 88 / 54 / 51 1200 1,2,3,4,5
1. HEATING INPUT CAPACITY BASED ON SEA LEVEL. ALL OTHER CAPACITIES BASED ON 4300 FEET ELEVATION.
2. PACKAGED ROOFTOP UNIT TO COME WITH SPRING VIBRATION ISOLATION CURB, INTEGRADED OUTSIDE AIR ECONOMIZER AND BAROMETRIC RELIEF.
3. UNIT TO COME WITH STARTER AND DISCONNECT.
4. STANDARD COLOR AND FINISH.
5. UNIT TO COME WITH 7-DAY PROGRAMMABLE THERMOSTAT. CONTRACTOR TO INSTALL ALL NECESSARY CONTROL WIRING FOR FUNCTIONAL THERMOSTAT.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
P401
P401
G (E
G (E)
G (E
G (E
(E)3/4"
(E)3/4"
(E)2"
(E)3/4"
(E)3/4"
(E)2"
(E)3/4"
(E)3/4"
(E)1"
(E)3/4"
PD101
JH
LEVEL 1 PLUMBING
DEMO PLAN
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
KEYED NOTES#
1. DEMOLISH EXISTING GAS SHUT-OFF VALVE AND PRESSURE
REGULATOR LOCATED ON ROOF.
2. DEMOLISH EXISTING GAS SHUT-OFF VALVE AND PRESSURE
REGULATOR.
3. EXISTING MECHANICAL EQUIPMENT TO BE DEMOLISHED. SEE
MECHANICAL DRAWINGS.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
P401
P401
G (E
G (E
G (E
(E)2"
(E)3/4"
(E)3/4"
(E)3/4"
(E)3/4"
(E)2"
(E)3/4"
(E)1"
(E)3/4" 2
(E)3/4"
G (E) 3/4"
D
P101
JD
LEVEL 1 PLUMBING
PLAN
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
KEYED NOTES#
1. GAS SHUT-OFF VALVE AND PRESSURE REGULATOR LOCATED
ON ROOF.
2. MECHANICAL EQUIPMENT. SEE MECHANICAL DRAWINGS.
EXTEND NEW GAS PIPING TO MECHANICAL EQUIPMENT.
PROVIDE NEW PRESSURE REGULATOR WITH VENT LIMITING
DEVICE, GAS SHUT-OFF VALVE AND DIRT LEG AT POINT OF
CONNECTION. SEE GAS PIPE SCHEMATIC FOR PIPE SIZES, GAS
LOAD, ETC.
3. MECHANICAL EQUIPMENT, SEE MECHANICAL DRAWINGS.
EXTEND MAKE-UP WATER LINE TO MECHANICAL EQUIPMENT.
COORDINATE MAKE-UP WATER LINE EXACT POINT OF
CONNECTION WITH SUBMITTED EQUIPMENT.
4. EXTEND 3/4" DRAIN LINE FROM MAKE UP WATER SYSTEM AS
SHOWN. PROVIDE SHUT-OFF VALVE ON VERTICAL RISER 36"
AFF AND HOSE THREAD CONNECTION. COORDINATE EXACT
LOCATION WITH OWNER.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
G (E)
G (E) (E)3/4"
(E)2"
(E)3/4"
WH
1 2
G (E)
G (E)
(E)3/4"DET
P401
JH
PLUMBING
ENLARGED PLANS
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
KEYED NOTES#
1. DEMOLISH AND REMOVE EXISTING WATER HEATER. DEMOLISH
EXISTING DCW, DHW, AND DHWR LINES BACK TO NEAREST
SHUT-OFF VALVE. REPLACE EXISTING SHUT-OFF VALVES WITH
NEW.
2. EXTEND NEW DCW, DHW, DHWR LINES TO NEW WATER HEATER
AND PROVIDE NEW SHUT-OFF VALVES. EXTEND GAS PIPING TO
WATER HEATER, PROVIDE GAS SHUT-OFF VALVE AND
PRESSURE REGULATOR WITH VENT LIMITING DEVICE. SEE
WATER HEATER DETAIL AND GAS PIPE SCHEMATIC.
3. EXISTING MECHANICAL EQUIPMENT TO BE DEMOLISHED. SEE
MECHANICAL DRAWINGS.
4. DEMOLISH EXISTING GAS SHUT-OFF VALVE AND PRESSURE
REGULATOR.
5. MECHANICAL EQUIPMENT. SEE MECHANICAL DRAWINGS.
EXTEND NEW GAS PIPING TO MECHANICAL EQUIPMENT.
PROVIDE NEW PRESSURE REGULATOR WITH VENT LIMITING
DEVICE, GAS SHUT-OFF VALVE AND DIRT LEG AT POINT OF
CONNECTION. SEE GAS PIPE SCHEMATIC FOR PIPE SIZES, GAS
LOAD, ETC.
6. EXTEND COMBUSTION AIR AND EXHAUST AIR FLUES UP
THROUGH ROOF AND TERMINATE WITH CONCENTRIC FITTING
OR APPROVED MANUFACTURER'S METHOD. INSTALL AND SIZE
PER MANUFACTURER'S REQUIREMENTS. FIELD VERIFY
EXISTING CONDITIONS. ALL ROOF OPENINGS TO BE INSTALLED
PER DFCM STANDARDS, SEE DETAIL.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
P501
JH
PLUMBING DETAILS
& SCHEDULES
09/01/26
260446
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
SU
PP
O
R T
SE
R
VI
C
ES
H
VA
C
U N
IT
S
E as t C en te r S tre et
P ro vo , U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260446
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
09-01-26
EXISTING GAS
METER
WH-1
100 MBH
115 CFH
2 PSI TO 4 OZ. GAS PRESSURE REDUCING VALVE
WITH VENT LIMITING DEVICE.
TYPICAL OF ALL.
UH-1
30 MBH
35 CFH
UH-2
120 MBH
138 CFH
UH-3
120 MBH
138 CFH
RTU-3
150 MBH
173 CFH
RTU-1
150 MBH
173 CFH
RTU-2
130 MBH
150 CFH
UH-5
120 MBH
138 CFH
UH-4
120 MBH
138 CFH
GAS SHUT-OFF VALVE, TYPICAL OF ALL.
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"3/4"
3/4"
3/4"
(E) 3/4" (E) 3/4"
(E) 3/4"(E) 3/4"
(E) 2"
(E) 3/4"
(E) 3/4"
(E) 1"
(E) 1"
(E) 3/4"
(E) 3/4" (E) 3/4"
(E) 3/4"
(E) 3/4"
FLASHING MEMBRANE AND
SEALANT
STAINLESS STEEL
CLAMPING RING
PLUMBING VENT / STACK
ADHERED FIELD FLASHED
MEMBRANE
TYPICAL
HEAT WELDED
FLASHING
NOTE:
IF THE TOP OF THE EXISTING VENT IS
LESS THAN 12" ABOVE THE NEW
FINISHED ROOF SURFACE, THE VENT
MUST BE EXTENDED
TYPICAL
STAINLESS STEEL CLAMPING
RING
SPM MEMBRANE PRE-FABRICATED
BOOT WITH MINIMUM 1" TURN-UP
CONTINUOUS WELD
HEAT WELDED FLASHING
FLASHING MEMBRANE AND
SEALANT
PIPE / CONDUIT
ROOFING MEMBRANE - VARIES
BY PROJECT
ROOF DECK VARIES BY
PROJECT
RIGID INSULATION -
VARIES BY PROJECT
ROOFING MEMBRANE - VARIES
BY PROJECT
ROOF DECK VARIES BY
PROJECT
RIGID INSULATION -
VARIES BY PROJECT
NOTE THAT PITCH POCKETS
ARE NOT AN ACCEPTABLE
METHOD OF WATER-PROOFING
BASE OF PIPES
NOTE THAT WHERE A PIPE IS CAPABLE OF BEING
FLASHED USING A ROOFING MANUFACTURES
PRE-FABRICATED BOOT (SUCH AS SHOWN
ABOVE), THAT OPTION IS REQUIRED AND
SHOULD BE USED OVER A FIELD FLASHED
DETAIL (SUCH AS SHOWN BELOW)
(E) 3/4"
(E) 2"TO EXISTING
EQUIPMENT
(E) 2" (E) 3/4" (E) 3/4"
TO EXISTING
EQUIPMENT
TO EXISTING
EQUIPMENT
WATER HEATER
SHUT OFF COCK (TYP)
GAS SUPPLY
DRIP LEG
AGA RATED TEMP.
AND PRESS. RELIEF
VALVE
DRAIN PAN
FINISHED FLOOR
WH
G
SEISMIC STRP (TYP.)
GAS PRESSURE REGULATOR
SHUT-OFF VALVE (TYP.)
THERMOMETER
REINSTALL TEMPERATURE SENSORS
TO MATCH EXISTING CONDITIONS
DET
1 DOMESTIC EXPANSION TANK
(E) DHWR FROM BUILDING
(E) DCW SUPPLY TO BUIDLING
(E) DHW SUPPLY TO BUIDLING
1-1/2" 1-1/2"
3/4"
GAS FIRED WATER HEATER SCHEDULE
RECOVERY ELECTRICAL
MANUFACTURER INPUT RATE 1ST HR. TANK FLUE HEIGHT/
AND LOAD EFFICIENCY @ 90 F SIZE SIZE DIAMETER
ID MODEL NUMBER LOCATION SERVICE (BTUH) (%) TYPE DELTA T (GAL) (IN) (IN) (KW) V/PH NOTES WH-1 AO SMITH BTX-100 MECHANICAL ROOM DHW 100,000 96 NAT. GAS 129 50 3 67 / 22 -.- 120/1 1,2
1. HIGH EFFICIENCY NATURAL GAS FIRED WATER HEATER.
2. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT. EXTEND DRAIN LINE TO NEAREST FLOOR DRAIN.
EXPANSION TANK SCHEDULE
FLUID PHYSICAL
MANUFACTURER MAX. TANK/ TANK RELIEF DIA./ NPT
AND WORKING ACCEPTANCE SIZE VALVE HEIGHT FITTING
ID MODEL NUMBER LOCATION TYPE FLUID (GAL) (GAL) (PSIG) (IN) (IN) NOTES
DET-1 AMTROL ST-12C MECH. ROOM DIAPHRAM DHW 3.2 6.4 150 12/14 3/4 1,2
1. SEE WATER HEATER DETAIL.
2. PROVIDE WITH ANTI-LEGIONELLA LINER.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/10/2026
EV EV
DO
TV
J
FB PT
J
X##
TC
CR
D
F
M
VFD
XX
POWER SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
S
WALL MOUNTED RECEPTACLE
SWITCHED RECEPTACLE
EMERGENCY RECEPTACLE
GROUND FAULT RECEPTACLE
RECEPTACLE MODIFIERS:
##": HEIGHT AFF O.C.
WP: WEATHERPROOF W/ IN-USE COVER
T: TAMPER-PROOF
U: RECEPTACLE WITH USB OUTLET
G: GROUND FAULT PROTECTED @ BREAKER
H: HOSPITAL GRADE
18"
18"
D Q SP
18"
18"
RECEPTACLE (SPECIFIC HEIGHT)
ISOLATED GROUND RECEPTACLE
7, 25, 30
7, 8
18"
SWITCH MODIFIERS:
K: KEYED
T: TIMER
M: MANUAL STARTER THERMAL
OVERLOAD SWITCH
EMERGENCY POWER OFF PUSH BUTTON
DOOR OPENER PUSH PLATE
ELECTRICAL POWER METER
FUSED DISCONNECT SWITCH
TOMBSTONE RECEPTACLE
CORD REEL, DEVICE VARIES
CORD DROP, DEVICE VARIES
MULTI-OUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
SINGLE / DUAL PORT ELECTRICAL VEHICLE
CHARGER
POWER POLE
NON-FUSED DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC STARTER WITH FUSED DISCONNECT
PUSHBUTTON
VARIABLE FREQUENCY DRIVE
TRANSFORMER:
SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &
REQUIREMENTS.
GENERAL LEGEND
SYMBOL DESCRIPTION NOTES
SOLID ARCHED LINES INDICATE UNSWITCHED
POWER CIRCUITING
DASHED ARCHED LINES INDICATE SWITCHED
POWER CIRCUITING
ONE CIRCUIT, HOME RUN TO PANEL
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
4" CONCRETE
BASE
POWER DISTRIBUTION PANEL 6'-6" TO TOP
FLUSH PANELBOARD 6'-6" TO TOP
SURFACE PANELBOARD 6'-6" TO TOP
TWO CIRCUITS, HOME RUN TO PANEL -
THREE CIRCUITS, HOME RUN TO PANEL -
CONDUIT RUN CONCEALED IN FLOOR OR GROUND -
CONDUIT RUN CONCEALED IN WALL OR CEILING -
CONDUIT UP -
CONDUIT DOWN -
CONDUIT STUB LOCATION CAP CONDUIT
CONDUIT / CIRCUIT CONTINUATION -
GROUND BUS BAR
CABLE TRAY
SOLID BOTTOM
LADDER
BASKET
MOUNTING
AS NOTED
7+18"
EQUIPMENT CEILING RACK
EQUIPMENT CABINET/RACK
EQUIPMENT 2-POST CABINET/RACK
TELEPHONE DEMARCATION BOARD +18"
FLOOR 18,
SEE SPEC.
WALL / FLOOR 18,
SEE SPEC.
CEILING
EXISTING --
DEMO --
TEMPORARY --
NEW --
CONDUIT
OHP: OVERHEAD POWER SERVICE
UGP: UNDERGROUND POWER
SERVICE
UGF: UNDERGROUND FIBER
SERVICE
TEL: TELEPHONE SERVICE
POWER DISTRIBUTION EQUIPMENT SYMBOLS
CONTROLLED RECEPTACLE 7, 8+18" OR AS
NOTED
SPD PROTECTED RECEPTACLE 7+18" OR AS
NOTED
TIME CLOCK +48"
NOT IN CONTRACT --
MAGNETIC STARTER WITH BREAKER DISCONNECT
CEILING MOUNTED RECEPTACLE CEILING
TV BACKBOX FLAT PANEL
HEIGHT +12"
NOTES:
1. HATCHED FILL INDICATES SWITCHBOARD OR POWER
DISTRIBUTION PANEL.
2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH & DEPTH).
4. DOOR INDICATES FRONT OF RECESSED PANEL.
'H P
1A
'L P
1A
'M D
P
'SB1'
POWER TAGS LEGEND
GENERAL LEGEND
SYMBOL DESCRIPTION NOTESMOUNTING
KEYNOTE
ROOM NAME & NUMBER
DIAGRAM TAG
MATCH LINE TAG
ROOM NAME & NUMBER W/ ZONE I.D.
JUNCTION BOX
x
S: SIMPLEX D: DUPLEX
Q: FOURPLEX SP: SPECIAL PURPOSE
FLOOR BOX / POKE-THRU
- SEE SCHEDULE FOR TYPE INFORMATION
EQUIPMENT SYSTEM PANELS
ACS: ACCESS CONTROL PANEL
ATS: AUTOMATIC TRANSFER SWITCH
IDS: INTRUSION DETECTION PANEL
PSP: POWER SUPPLY PANEL
RP#: LIGHTING PANEL
DAS: DISTRIBUTED ANTENNA SYSTEM
ERCCS: FIRST RESPONDERS RADIO SYSTEM
CATV: CABLE TV CONTENT EQUIPMENT
7, 8, 13
CEILING
CEILING
+46"OR AS
NOTED
7, REFER TO
SPEC
+46" 7
+46" 7
9, 10
9, 10, 11
+72" TO TOP
+60" TO TOP
18, SEE SPEC.
7, 22
Space
Space
XX
DEVICES WITH A CHEVRON INDICATE TO
COORDINATE WITH MILLWORK PRIOR TO ROUGH-IN.
ELEVATION TAG. HATCHED AREA INDICATES
WHICH WALL, NUMBER INDICATES VIEW, AND
CENTER NUMBER INDICATES WHICH SHEET.
REVISION CLOUD DELTA. SHOWN WITH CLOUD
AND INDICATES A CHANGE PER THE TITLE BLOCK.
TAG FOR MECHANICAL, KITCHEN, AND SHOP
DEVICES. REFER TO SCHEDULES FOR INFO.
9, 10, 11
9, 10, 11
+46" 7
9, 10
+46" 7
+60" TO TOP
+60" TO TOP
+60" TO TOP
+60" TO TOP
+60" TO TOP 9, 10, 11
+60" TO TOP
FLOOR
AS NOTED 20
25, 30
+46" 7
COUNTER TOP
MATCH LINE
SEE -/---
32" OR AS
INDICATED
L I C
E N
S E D
P
ROFESS IONA
L
E N
G I N
E E
R
14275529
S
T A
T E O F U
TA
H
SANG TRUONG
No.
Project #: 260447 Electrical PM: Sang Truong
DFCM APPROVAL STAMP
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
A
B
C
D
E
1 2 3 4 5 6
09/04/2026
260446
ST
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:
Resolut Group, 2025
Original drawings remain the property of the Engineer and as such the Engineer retains total ownership and control. The design represented by these drawings are sold to the client for a one time use, unless otherwise agreed upon in writing by the
Engineer.
C
U S
H
S U
P P
O R
T S
E R
V
IC
E S
H V
A C
U N
IT
S
E a s t
C e n te r S tr e e t
P ro v o
U ta h
LA
ELECTRICAL TITLE
SHEET
EG001
ELECTRICAL ABBREVIATIONS INDEX
ABBREV. DESCRIPTION
A AMPS
AC ALTERNATING CURRENT
ACLG ABOVE CEILING
ADC ANALOG-TO-DIGITAL
CONVERTER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFF / A.F.F. ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AM AMPS METER
AMP AMPERE
AMPL AMPLIFIER
ANN ANNUNCIATOR
AOE AUDIO-OVER-ETHERNET
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIOVISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BC BARE COPPER
BD BOARD
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
BPM BEATS-PER-MINUTE
C, CND CONDUIT
C.O. CONDUIT ONLY
C/W COMPLETE WITH
CAB CABINET
CAT CATEGORY CABLE
CAT# CATALOG
CATB COMMUNITY ANTENNA
TELEVISION
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CF CREST FACTOR
CKT CIRCUIT
CLG CEILING
CMPR COMPRESSOR
CNTR CONTRACTOR
CO CONDUIT ONLY
CODEC CODER-DECORDER
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONV CONVECTOR
CP CIRCULATING PUMP
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
CV CONSTANT VOLTAGE
DAC DIGITAL-TO-ANALOG
CONVERTER
DB DECIBEL
DBFS DB REF. FULL SCALE
DBM DB REF. 0.001 WATT
DBU DB REF. 0.775 V
DBV DB REF. 1 V
DC DIRECT CURRENT
DCP DOMESTIC CIRCULATING PUMP
DED DEDICATED
DEPT DEPARTMENT
DET DETAIL
DFA DROP FROM ABOVE
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DR DYNAMIC RANGE
DS DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
E EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EG EMERGENCY GENERATOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY/EGRESS BATTERY
EMI ELECTRO-MAGNETIC
INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EN EXISTING TO BE REPLACED
WITH NEW
ENT ELEC. NON-METAL. TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
ER EXISTING TO BE RELOCATED
ES SOURCE VOLTAGE
EWC ELECTRIC WATER COOLER
EX EXISTING TO BE REMOVED AND
OFFERED UP TO THE OWNER
FOR FIRST RIGHTS OF REFUSAL.
PROPERLY AND LEGALLY
DISPOSE OF MATERIAL IF
REFUSED
FA FIRE ALARM
FABP FIRE ALARM BOOSTER PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FCU FAN COIL UNIT
FIR FINITE IMPULSE RESPONSE
FILTER
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FMC FLEXIBLE METAL CONDUIT
FU FUSE
FUDS FUSE SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
ABBREV. DESCRIPTION
GEC GRND. ELEC. COND. AT SES
GEN GENERATOR
GFCI GROUND FAULT CURRENT
INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRC GALVANIZED RIGID CONDUIT
GYP BD GYPSUM BOARD
HOA HAND-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSE POWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING & AIR
CONDITIONING
HZ HERTZ
I/W INTERLOCK WITH
IC INTERRUPTING CAPACITY
IFC INTERNATIONAL FIRE CODE
IG ISOLATED GROUND
IIR INFINITE IMPULSE RESPONSE
FILTER
IMC INTERMEDIATE METALLIC
CONDUIT
INCAND INCANDESCENT
IR INFRARED
IT TOTAL CURRENT
J-BOX JUNCTION BOX
KCMIL 1000 CIRCULAR MILS (MCM)
KHZ THOUSANDS OF HZ
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
KWH KILOWATT HOUR
LCS C-WEIGHTED SLOW SOUND
LEVEL
LEQ EQUIVALENT SOUND LEVEL
LFMC LIQUID-TIGHT FLEX.
METAL. COND.
LFNC LIQUID-TIGHT FLEX. NON-METAL.
COND.
LOC LOCATE OR LOCATION
LP, SPL SOUND PRESSURE LEVEL
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LU LOUDNESS UNIT METERING
LUFS LOUDNESS UNIT FULL SCALE
LV LOW VOLTAGE
M/C MOMENTARY CONTACT
MAC MEDIA ACCESS CONTROL
MAG.S MAGNETIC STARTER
MAX MAXIMUM
MB MAIN BUS
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MEP MECHANICAL, ELECTRICAL, AND
PLUMBING
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MNF MANUFACTURER
MOA MULTI-OUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MSS MOTOR STARTER SWITCH
MTG MOUNTING
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
N NEW
N.I.C. NOT IN CONTRACT
N/A NOT APPLICABLE
N1 NEMA 1
N3R NEMA 3R
NAC NOTIFICATION APPLIANCE
CIRCUIT PANEL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT.
MANUFAC. ASSOC.
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NFPA NATIONAL FIRE PROTECTION
ASSOC.
NL NIGHT LIGHT, BYPASS LOCAL
SWITCHING
NO NORMALLY OPENED
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
OC ON CENTER
OH OVERHEAD
OL OVERLOADS
OS & Y OUTSIDE SCREW & YOKE
OSI OPEN SYSTEM INTEGRATION
PA PASCAL
PB PUSHBUTTON
PBB PRIMARY BONDING BUSBAR
PC PLUMBING CONTRACTOR
PCM PULSE CODE MODULATION
PDU POWER DISTRIBUTION UNIT
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PIV POST INDICATING VALVE
PLEN PLENUM
PNL PANEL
POC POINT OF CONNECTION
POE POWER OVER ETHERNET
POS POINT OF SALE
PP POWER POLE
PPM PEAK PROGRAM METER
PR PAIR
PRI PRIMARY
PROJ PROJECTION
ABBREV. DESCRIPTION
PRV POWER ROOF VENTILATOR
PSI POUNDS-PER-SQUARE-INCH
PT POTENTIAL TRANSFORMER
PTP POINT TO POINT
PTZ PAN, TILT, AND ZOOM
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
QUAN QUANTITY
R RESISTANCE
RECEP, RECPT RECEPTACLE
REQ,REQD REQUIRED
REX REQUEST TO EXIT
RF RADIO FREQUENCY
RFM ROOF MOUNTED
RL LOAD RESISTANCE
RLA RATED LOAD AMPS
RM ROOM
RMC RIGID METALLIC CONDUIT
RMP ROCKY MOUNTAIN POWER
RMS ROOT MEAN SQUARE
RNC RIGID NON-METALLIC COND.
RPM ROTATIONS-PER-MINUTE
RS SOURCE RESISTANCE
RT TOTAL RESISTANCE
RTU ROOF TOP UNIT
RX RECEIVER
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SBB SECONDARY BONDING BUSBAR
SBG SUPPLEMENTARY BONDING
GRID
SBJ SYSTEM BONDING JUMPER
SC SURFACE CONDUIT
SCA SHORT CIRCUIT AMPERES
SDI SERIAL DIGITAL INTERFACE
SE SERVICE ENTRANCE
SEC SECONDARY
SES SMOKE EVACUATION SYSTEM
SHT SHEET
SIM SIMILAR
SLD SINGLE-LINE DIAGRAM
SNR SIGNAL-TO-NOISE RATIO
SP SPARE
SPDIF SONY PHILLIPS DIGITAL
INTERFACE
SPEC SPECIFICATIONS
SPKR LOUDSPEAKER
SPL SOUND PRESSURE LEVEL
SPP SINGLE-POINT POWER
SR SURFACE RACEWAY
SS SELECTOR SWITCH
SSW SELECTOR SWITCH
STA STATION
STD STANDARD
STP SHIELDED TWISTED PAIR
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
TBB TELECOMMUNICATIONS
BONDING BACKBONE
TBC TELECOMMUNICATIONS
BONDING CONDUCTOR
TC TEMP. CONTROL CONTR.
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
TX TRANSMITTER
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTED POWER
SUPPLY
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UTP UNSHIELDED TWISTED PAIR
UV ULTRAVIOLET
V VOLT (KV-KILOVOLT)
VA VOLT/AMPS
VA/R, VAR VOLT-AMPS/REACTIVE
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DC CURRENT
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VI VOLUME INDICATOR
VIF VERIFY IN FIELD
VM VOLT METER
VOL VOLUME
VU VOLUME UNIT
W WATTS
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WH WATTHOUR METER
WP WEATHERPROOF/NEMA 3R
XFMR TRANSFORMER
XFMR SW SW TRANSFER SWITCH
XFR TRANSFER
XL X-CONNECTOR LOCKING
XLR X-CONNECTOR LOCKING
RUBBERIZED
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
1P ONE-POLE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∠ ANGLE
& AND
@ AT
° DEGREE
▲ DELTA
', FT FOOT, FEET
", IN INCH, INCHES
# NUMBER
Ω, OHM UNIT OF ELECTRICAL
RESISTANCE
Ø, PH PHASE
℄, CTR CENTER LINE, CENTER
P PLATE
SYMBOL LEGEND GENERAL NOTES
1. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE
& DETAILS.
2. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.
3. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.
4. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
5. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
6. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
7. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
8. NOT USED.
9. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR
480 VOLT.
10. SIZE TO THE EQUIPMENT BEING CONTROLLED.
11. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.
12. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
13. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
14. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.
15. COORDINATE WITH DOOR HARDWARE SUPPLIER.
16. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS
A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
17. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
19. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.
20. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
21. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.
22. ROUGH-IN TO BE HORIZONTAL.
23. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE
REQUIRED.
24. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.
25. SUBSCRIPT INDICATES NEMA CONFIGURATION.
26. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.
27. USE WITH POWER PACK.
28. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
29. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.
30. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE
INDICATES INSTALLED IN CEILING.
31. WALL DEVICES NOTED WITH A CHEVRON INDICATE THE PROPOSED INSTALLATION HEIGHT.
COORDINATE WITH MILLWORK SHOP DRAWINGS & ELEVATIONS FOR HEIGHT.
ELECTRICAL SHEET INDEX
SHEET NUMBER SHEET NAME
EG001 ELECTRICAL TITLE SHEET
EG002 ELECTRICAL DETAILS & SCHEDULES
EG003 ELECTRICAL ONE-LINE DIAGRAM
ED101 LEVEL 1 ELECTRICAL DEMOLITION PLAN
ED102 ROOF ELECTRICAL DEMOLITION PLAN
EP101 LEVEL 1 ELECTRICAL POWER PLAN
EP102 ROOF ELECTRICAL POWER PLAN
ELECTRICAL GENERAL NOTES
1. GENERAL SCOPE & COMPLIANCE
A. INSTALL COMPLETE, OPERABLE ELECTRICAL SYSTEMS AS SHOWN AND SPECIFIED. BID
SHALL INCLUDE ALL WORK, MATERIALS, AND COORDINATION NECESSARY FOR A FULLY
FUNCTIONAL INSTALLATION.
B. ALL WORK SHALL COMPLY WITH THE NEC, NFPA 72, IBC/IFC, APPLICABLE LOCAL AND
STATE CODES, AHJ REQUIREMENTS, AND INDUSTRY STANDARDS.
C. ALL EQUIPMENT SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY (E.G., UL, ETL) FOR ITS INTENDED USE.
D. ALL EQUIPMENT PROVIDED SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY (NRTL).
E. FINAL INSTALLATION SHALL BE FREE OF DEFECTS AND APPROVED BY THE AHJ, OWNER,
ARCHITECT, AND ENGINEER.
F. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS SHALL BE
CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND BID WITH THIS INTENT.
G. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL APPLICABLE CONTRACT
DOCUMENTS, INCLUDING ARCHITECTURAL, MECHANICAL, STRUCTURAL, AND OTHER
TRADE DRAWINGS, TO COORDINATE LOCATIONS, DIMENSIONS, AND REQUIREMENTS. NO
ADDITIONAL COSTS WILL BE ALLOWED FOR FAILURE TO COORDINATE.
H. CONTRACTOR SHALL VERIFY ALL EQUIPMENT DIMENSIONS, ELECTRICAL LOADS
(VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC.), AND ROUGH-IN LOCATIONS
BEFORE INSTALLATION. VERIFY NEC CODE CLEARANCES AROUND ALL ELECTRICAL
EQUIPMENT.
I. ALL WORK SHALL CONFORM TO LOCAL AND STATE CODES, THE LATEST EDITION OF THE
NEC, AND ALL APPLICABLE INDUSTRY STANDARDS.
J. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND REPRESENT
THE GENERAL SCOPE OF WORK. RACEWAY ROUTING, UNLESS SPECIFICALLY SHOWN,
SHALL BE FIELD-DETERMINED IN COORDINATION WITH OTHER TRADES.
K. COORDINATE WITH ALL APPLICABLE SPECIFICATIONS, INCLUDING SECTION 265100
(16510) FOR REQUIRED COORDINATION MEETINGS WITH MECHANICAL AND CEILING
CONTRACTORS.
2. DRAWINGS & COORDINATION
A. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SHOWING GENERAL SCOPE AND INTENT
ONLY. EXACT ROUTING, BENDS, PULL BOXES, AND OTHER INSTALLATION DETAILS ARE
THE CONTRACTOR’S RESPONSIBILITY.
B. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE/DEVICE
LOCATIONS, MECHANICAL PLANS FOR COORDINATED PENETRATIONS, AND SHOP
DRAWINGS FOR EQUIPMENT DIMENSIONS.
C. COORDINATE WITH ALL OTHER TRADES BEFORE ROUGH-IN TO AVOID CONFLICTS WITH
DUCTWORK, PIPING, STRUCTURE, AND EQUIPMENT.
D. ARCHITECTURAL AND MECHANICAL PLANS ARE PART OF THE ELECTRICAL DOCUMENTS
WHERE THEY PERTAIN TO ELECTRICAL WORK.
E. NO ADDITIONAL COST WILL BE ALLOWED FOR FIELD CONFLICTS OR EQUIPMENT
DIMENSION VARIATIONS DUE TO FAILURE TO COORDINATE.
3. PRE-BID & PRE-INSTALLATION REQUIREMENTS
A. VISIT THE SITE, REVIEW ALL CONTRACT DOCUMENTS, AND VERIFY EXISTING
CONDITIONS BEFORE BIDDING.
B. NOTIFY THE ENGINEER IN WRITING OF ERRORS, OMISSIONS, OR CONFLICTS PRIOR TO
BID. CHANGES WILL BE ISSUED VIA PRE-BID ADDENDUM.
C. VERIFY ALL ELECTRICAL LOADS, VOLTAGES, PHASES, AND CONNECTION
REQUIREMENTS FOR NEW AND EXISTING EQUIPMENT TO BE REUSED.
D. OBTAIN AND REVIEW WIRING DIAGRAMS FROM EQUIPMENT SUPPLIERS BEFORE ROUGH-
IN.
4. CLEARANCES & CODE-REQUIRED SPACE
A. MAINTAIN NEC-REQUIRED WORKING CLEARANCES AROUND ALL ELECTRICAL
EQUIPMENT.
B. IF CLEARANCE ISSUES ARE FOUND, NOTIFY THE DESIGNER IMMEDIATELY. IF
DISCOVERED AFTER INSTALLATION, RELOCATE AT THE CONTRACTOR’S EXPENSE
UNLESS OTHERWISE DIRECTED.
C. DO NOT ALLOW FOREIGN PIPING, DUCTWORK, OR UNRELATED EQUIPMENT IN
ELECTRICAL ROOMS OR ABOVE/BELOW ELECTRICAL EQUIPMENT.
5. MATERIALS & INSTALLATION STANDARDS
A. MINIMUM CONDUIT SIZE: 3/4".
a. INTERIOR: EMT WITH SET-SCREW FITTINGS.
b. EXTERIOR: EMT WITH COMPRESSION GLAND TYPE FITTINGS.
c. UNDERGROUND: PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN
CORROSION-RESISTANT MATERIAL WHERE IN DIRECT SOIL CONTACT.
B. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS IN ALL
CONDUITS; CONDUIT SHALL NOT BE USED AS A GROUNDING CONDUCTOR.
C. COPPER CONDUCTORS, 600V RATED, THHN/THWN-2: #10 AWG AND SMALLER SOLID.
#8 AWG AND LARGER STRANDED. INCREASE CONDUCTOR SIZE TO #10 FOR 20A RUNS
OVER 125 FEET.
D. FLEXIBLE/SEALTITE CONDUIT LIMITED TO 6 FEET FOR FIXTURE AND MOTOR
CONNECTIONS AS NOTED OR VIBRATION-PRONE EQUIPMENT.
E. ALL EMPTY CONDUITS/RACEWAYS SHALL HAVE NYLON BUSHINGS AND 200 LB-RATED
PULL STRINGS.
F. SECURE CONDUIT AND BOXES TO STRUCTURE PER INDUSTRY STANDARDS. EXPOSED
CONDUIT SHALL BE PLUMB, LEVEL, PARALLEL TO BUILDING LINES, AND PAINTED TO
MATCH ADJACENT FINISHES IF VISIBLE.
G. CONDUITS/RACEWAYS SHALL BE CONCEALED WHERE PRACTICABLE. EXPOSED
CONDUIT/RACEWAY SHALL BE PAINTED TO MATCH ADJACENT SURFACES.
H. WIRING DEVICES SHALL BE WHITE WITH STAINLESS STEEL COVER PLATES UNLESS
OTHERWISE NOTED.
I. CONDUCTORS SHALL BE COPPER.
J. CAP AND LABEL ALL EMPTY CONDUIT TO REMAIN.
1. DEVICE & EQUIPMENT PLACEMENT
A. MOUNT WIRING DEVICES ABOVE BACKSPLASHES UNLESS SERVING UNDER-COUNTER
EQUIPMENT.
B. INSTALL SWITCHES, RECEPTACLES, AND CONTROLS AT ADA-COMPLIANT HEIGHTS.
C. OFFSET DEVICES ON OPPOSITE SIDES OF A WALL AT LEAST 12" TO REDUCE SOUND
TRANSMISSION.
D. COORDINATE FURNITURE LAYOUTS FOR FLOOR BOX AND POKE-THRU LOCATIONS
BEFORE ROUGH-IN.
E. LABEL ALL RECEPTACLE AND SWITCH FACEPLATES WITH CIRCUIT ID (XX-XX FORMAT).
F. PROVIDE TAMPER-RESISTANT RECEPTACLES AT ALL CODE-REQUIRED AND CHILD-
ACCESSIBLE LOCATIONS.
G. PROVIDE GFCI PROTECTION PER NEC, IN BATHROOMS, KITCHENS, OUTDOORS, WITHIN 6
FEET OF SINKS, AND WHERE REQUIRED FOR DIAGNOSTIC EQUIPMENT, TOOLS, OR
LIGHTING.
H. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS
SHALL BE RUN WITH CONDUCTORS PER TABLE BELOW.
a. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
b. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO
KEEP BRANCH CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
c. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT
STAYS WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF
NECESSARY,CONTRACTOR SHALL INCREASE WIRE AND CONDUIT SIZE TO MEET
THE STANDARD AT NO ADDITIONAL COST TO OWNER.
I. MAINTAIN ELECTRICAL CONTINUITY TO REMAINING EQUIPMENT WHEN REMOVING
EXISTING EQUIPMENT.
J. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE
SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.
K. EXTERIOR OUTLETS SHALL HAVE CAST COVERS WITH FLIP-TYPE LIDS UNLESS
OTHERWISE NOTED. ALL WP OUTLET HOODS SHALL BE EXTRA-DUTY, WHILE-IN-USE
TYPE, AND LOW-PROFILE WHERE PRACTICAL.
2. SPECIAL SYSTEMS
A. PROVIDE ADDRESSABLE FIRE ALARM SYSTEM PER NFPA 72, IBC/IFC, AND LOCAL CODES.
INCLUDE MONITORING OF SPRINKLER/TAMPER SWITCHES, AHU DUCT DETECTORS (>2000
CFM), PULL STATIONS AT EXITS, AND HEAT/SMOKE DETECTION AS SHOWN. SUBMIT
SHOP DRAWINGS FOR APPROVAL BEFORE INSTALLATION.
B. PROVIDE STRUCTURED CABLING FROM TELECOM/DATA/CATV OUTLETS TO THE MAIN
RACK/BOARD, WITH LABELING AT BOTH ENDS. INSTALL IN CONDUIT UNLESS ABOVE
ACCESSIBLE CEILINGS. USE PLENUM-RATED CABLE IN PLENUM SPACES.
C. PROVIDE HEAVY-DUTY FUSED DISCONNECTS.
D. SUBMIT SCALED LAYOUTS OF ELECTRICAL ROOMS (1/4" = 1') BASED ON FINAL
EQUIPMENT SUBMITTALS.
E. OBTAIN ALL WIRING DIAGRAMS FOR EQUIPMENT FROM SUPPLIERS BEFORE ROUGH-IN.
F. COORDINATE WITH EQUIPMENT SUPPLIERS FOR EXACT EQUIPMENT LOCATIONS AND
ELECTRICAL CONNECTIONS PRIOR TO ROUGH-IN.
G. THE ELECTRICAL CONTRACTOR SHALL MAKE FINAL EQUIPMENT CONNECTIONS UNLESS
OTHERWISE DIRECTED.
3. PENETRATIONS & SEALING
A. SEAL ALL PENETRATIONS OF FIRE-RATED FLOORS, WALLS, AND CEILINGS WITH
APPROVED FIRESTOP SYSTEMS TO MAINTAIN RATING.
B. ROOF PENETRATIONS FOR CONDUIT SHALL USE SEALED ROOF JACKS COMPATIBLE
WITH THE ROOF WARRANTY.
C. UNDERGROUND/UNDERFLOOR CONDUITS SHALL BE AT LEAST 24" BELOW GRADE/SLAB
UNLESS NOTED OTHERWISE.
D. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE
SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.
4. TESTING, CLEANING, & TURNOVER
A. TEST AND VERIFY PROPER OPERATION OF ALL ELECTRICAL SYSTEMS AT COMPLETION.
B. CLEAN ALL FIXTURES, DEVICES, AND EQUIPMENT; REMOVE LABELS, DIRT, PAINT,
GREASE, AND DEBRIS BEFORE FINAL ACCEPTANCE.
C. PROVIDE ALL O&M MANUALS AND AS-BUILT DRAWINGS WITH WIRING DIAGRAMS INSIDE
EQUIPMENT AND IN THE PROJECT CLOSEOUT DOCUMENTS.
MAXIMUM LENGTH
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
ELECTRICAL GENERAL PROVISIONS
DESCRIPTION OF WORK: EXTENT OF ELECTRICAL WORK IS INDICATED ON DRAWINGS. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SUPERVISION AND SERVICE NECESSARY FOR A COMPLETE ELECTRICAL SYSTEM. WORK
INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOWING ITEMS:
• ELECTRICAL CONNECTIONS FOR EQUIPMENT
• CONDUCTORS AND CABLES
• GROUNDING
• SUPPORTING DEVICES
• CONDUIT RACEWAYS
• ELECTRICAL BOXES AND FITTINGS
• RACEWAYS SYSTEMS
• ELECTRICAL SEISMIC CONTROL
• ELECTRICAL IDENTIFICATION
• SWITCHGEAR AND SWITCHBOARDS
• PANELBOARDS
• SERVICE ENTRANCE
• WIRING DEVICES
• OVERCURRENT PROTECTIVE DEVICES
• MOTOR AND CIRCUIT DISCONNECTS
• MOTOR STARTERS
• VARIABLE FREQUENCY DRIVES
• EMERGENCY ELECTRICAL SYSTEMS
• DEMOLITION
INTERPRETATION OF DRAWINGS AND SPECIFICATIONS: BEFORE BIDDING, CONTRACTOR SHALL FAMILIARIZE
THEMSELVES WITH THE DRAWINGS, SPECIFICATIONS AND PROJECT SITE.
VISIT THE SITE DURING THE BIDDING PERIOD TO DETERMINE EXISTING CONDITIONS AFFECTING ELECTRICAL AND
OTHER WORK, ALL COSTS ARISING FROM SITE CONDITIONS AND/OR PREPARATION SHALL BE INCLUDED IN THE
BASE BID. NO ADDITIONAL CHARGES WILL BE ALLOWED DUE TO INADEQUATE SITE INSPECTION.
QUALITY ASSURANCE: PERFORM WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC). COMPLY
WITH REQUIREMENTS FOR STATE AND LOCAL ORDINANCES. OBTAIN ALL PERMITS, INSPECTIONS, ETC FOR
AUTHORITY HAVING JURISDICTION (AHJ). EMPLOY ONLY QUALIFIED CRAFTSMEN WITH AT LEAST THREE (3) YEARS
OF EXPERIENCE. WORKMANSHIP SHALL BE NEAT, HAVE A GOOD MECHANICAL APPEARANCE AND CONFORM TO
BEST ELECTRICAL STATE CONTRACTING LICENSE. PROVIDE EQUIPMENT AND MATERIALS THAT ARE
UNDERWRITERS LABORATORIES INC. (UL) LISTED AND LABELED.
SUBMITTALS: AFTER THE CONTRACT IS AWARDED BUT PRIOR TO MANUFACTURE OR INSTALLATION OF ANY
EQUIPMENT, PREPARE COMPLETE SHOP DRAWINGS.
1. PROVIDE SUBMITTALS IN PORTABLE DOCUMENT FORMAT (PDF).
2. DOCUMENTS MUST BE ELECTRONICALLY BOOKMARKED AND KEYWORD SEARCHABLE USING
(HTTP://ADOBE.COM/ACROBAT) ADOBE ACROBAT OR BLUEBEAM REVU
(HTTP://BLUEBEAM.COM) FOR EACH RELEVANT SECTION. (I.E. INCLUDE ELECTRONIC BOOKMARKS
SEPARATION “LIGHT FIXTURES” FROM “PANELBOARDS”.)
3. ELECTRONICALLY HIGHLIGHT ALL OPTIONS FOR LIGHT FIXTURES, ELECTRICAL EQUIPMENT, ETC.
MANUAL HIGHLIGHTING AND SCANNING OF THE DOCUMENTS IS NOT ACCEPTABLE AND WILL NOT BE
REVIEWED.
4. PROVIDE ONLY COMPLETED CUTSHEETS FOR ALL FIXTURE AND EQUIPMENT TYPES. BLANK
CUTSHEETS SUBMITTED WITH A SCHEDULE ARE NOT ACCEPTABLE AND WILL NOT BE REVIEWED.
5. A MAXIMUM OF ONE SUBMITTAL PER SPECIFICATION SECTION IS ALLOWED, IT IS NOT ACCEPTABLE TO
PROVIDE PRODUCT BY PRODUCT SUBMITTAL. SINGLE PRODUCT SUBMITTALS WILL NOT BE REVIEWED.
A. ELECTRICAL CONNECTIONS FOR EQUIPMENT
B. CONDUCTORS AND CABLES
C. GROUNDING
D. SUPPORTING DEVICES
E. CONDUIT RACEWAYS
F. ELECTRICAL BOXES AND FITTINGS
G. RACEWAYS SYSTEMS
H. ELECTRICAL SEISMIC CONTROL
I. ELECTRICAL IDENTIFICATION
J. SWITCHGEAR AND SWITCHBOARDS
K. PANELBOARDS
L. SERVICE ENTRANCE
M. WIRING DEVICES
N. OVERCURRENT PROTECTIVE DEVICES
O. MOTOR AND CIRCUIT DISCONNECTS
P. MOTOR STARTERS
6. PRODUCTS: PRODUCTS ARE SPECIFIED BY MANUFACTURE NAME, DESCRIPTION AND/OR CATALOG
NUMBER. PROVIDE PRODUCTS OF MANUFACTURERS SPECIFIED. SUBSTITUTIONS WILL BE CONSIDERED
IF A DUPLICATE WRITTEN APPLICATION IS SUBMITTED. NO MATERIAL MAY BE SUBSTITUTED AFTER THE
BID OPENING. PROVIDE BLOCK OUTS, SLEEVES, ETC. REQUIRED FOR INSTALLATION OF WORK
SPECIFIED.
7. RECORD DRAWINGS: MAINTAIN ON A DAILY BASIS, A COMPLETE SET OF RECORD DRAWINGS, REFLECTING AN ACCURATE DIMENSIONAL RECORD OF ALL BURIED OR CONCEALED WORK. MARK
RECORD DRAWINGS TO SHOW THE PRECISE LOCATION OF CONCEALED WORK AND EQUIPMENT,
INCLUDING CONCEALED OR EMBEDDED CONDUIT AND JUNCTION BOXES AND ALL CHANGES AND
DEVIATIONS IN THE WORK FROM THAT SHOWN ON THE CONTRACT DOCUMENTS.
8. OPERATION AND MAINTENANCE MANUALS: PROVIDE OPERATION AND MAINTENANCE DATA BOOKS FOR
ALL EQUIPMENT AND MATERIALS FURNISHED UNDER THIS DIVISION.
9. GUARANTEE: ENSURE THAT ELECTRICAL SYSTEMS INSTALLED UNDER THIS CONTRACT IS IN PROPER
WORKING ORDER AND IN COMPLIANCE WITH DRAWINGS, SPECIFICATIONS, AND/OR AUTHORIZED
CHANGES, WITHOUT ADDITIONAL CHARGE, REPLACE ANY WORK OR MATERIALS WHICH DEVELOP
DEFECTS, EXCEPT FROM ORDINARY WEAR AND TEAR, WITHIN ONE YEAR FROM THE DATE OF
SUBSTANTIAL COMPLETION.
10. FIRE PROTECTION SEALS: SEAL ALL PENETRATIONS FOR WORK OF THIS SECTION THROUGH FIRE
RATED FLOORS, WALLS, CEILINGS TO PREVENT THE SPREAD OF SMOKE, FIRE, TOXIC GAS, OR WATER
THROUGH THE PENETRATION EITHER BEFORE, DURING OR AFTER FIRE.
11. POWER OUTAGES: ALL POWER OUTAGES REQUIRED FOR EXECUTION OF THIS WORK SHALL OCCUR
DURING NON-STANDARD WORKING HOURS AND AT THE CONVENIENCE OF THE OWNER. INCLUDE ALL
COSTS FOR OVERTIME WORK IN BID.
12. EXCAVATING FOR ELECTRICAL WORK: LOCATE AND PROTECT EXISTING UTILITIES AND OTHER
UNDERGROUND WORK. PERFORM EXCAVATION IN A MANNER WHICH PROTECTS WALLS, FOOTINGS AND
OTHER STRUCTURAL MEMBERS.
13. CONCRETE BASES: PROVIDE 4” CONCRETE BASES FOR ELECTRICAL EQUIPMENT.
14. ROOF PENETRATIONS: PROVIDE ROOF JACK, SIZED TO FIT TIGHTLY TO RACEWAY FOR WEATHERTIGHT
SEAL.
ELECTRICAL CONNECTIONS FOR EQUIPMENT
1. VERIFY EXACT LOAD AND LOCATION OF ALL EQUIPMENT BEFORE ROUGH-IN FOR EACH ELECTRICAL
CONNECTION. PROVIDE COMPLETE ASSEMBLY OF MATERIAL, INCLUDING BUT NOT NECESSARILY
LIMITED TO, RACEWAYS, CONDUCTORS, CORDS, CORD CAPS, PLUGS, WIRING DEVICES, PRESSURE
CONNECTORS, TERMINALS (LUGS), ELECTRICAL INSULATION TAPE, HEAT-SHRINKABLE INSULATION
TUBING, CABLE TIES, SOLDERLESS WIRE NUTS, AND OTHER ITEMS AND ACCESSORIES AS NEEDED TO
COMPLETE SPLICES, TERMINATIONS, AND CONNECTIONS AS REQUIRED. FOR PERMANENTLY
INSTALLED FIXED EQUIPMENT, PROVIDE FLEXIBLE SEAL-TITE CONNECTIONS. FOR MOVABLE AND/OR
PORTABLE EQUIPMENT, PROVIDE WIRE DEVICE, CORD CAP, AND MULTI-CONDUCTOR CORD.
CONDUCTORS AND CABLES
1. PROVIDE FACTORY FABRICATED CONDUCTORS FOR SIZES, RATINGS, MATERIAL, AND TYPES
INDICATED FOR EACH SERVICE. PROVIDE COPPER CONDUCTORS, WITH THHN/THWN INSULATION. SIZE
ALL CONDUCTORS IN ACCORDANCE WITH NEC: MINIMUM SIZE TO BE #12 AWG. PROVIDE STRANDED
CONDUCTORS FOR #8 AWG AND LARGER.
2. THE FOLLOWING COLOR SCHEME SHALL BE USED:
3. MC CABLE:
A. MC CABLE IS ACCEPTABLE FOR ALL BRANCH CIRCUITS INSTALLED IN GYPSUM WALLBOARD
WALLS FROM THE HOME RUN DEVICE BOX TO THE LAST DEVICE BOX ON THE BRANCH CIRCUIT
AND ALL BOXES IN BETWEEN, FROM THE HOME RUN DEVICE BOX TO THE BRANCH PANEL, THE
CIRCUIT SHALL BE INSTALLED IN AN APPROVED RACEWAY. MC CABLE IS ACCEPTABLE FOR ALL
LIGHT FIXTURE WHIPS NOT LONGER THAN SIX FEET IN LENGTH. LOCATED IN REMOVABLE GRID
CEILINGS. MC CABLE IS UNACCEPTABLE TO BE INSTALLED FROM LIGHT FIXTURE TO LIGHT
FIXTURE. ALL MC CABLE SHALL BE PROVIDED WITH ANTI SHORT FITTINGS.
B. THE USE OF MC-PCS CABLE IS ACCEPTABLE FOR LIGHT FIXTURE WHIPS UTILIZING 0-10V
CONTROL SCHEMES, NOT LONGER THAN 72” IN LENGTH, LOCATED ABOVE REMOVABLE GRID
CEILINGS. ALL MC CABLE SHALL BE PROVIDED WITH ANTI-SHORT FITTINGS.
a. ACCEPTABLE MANUFACTURERS
• AFC – MC LUMINARY CABLE
• ENCORE – MC-LED LIGHTING CABLE
• SOUTHWIRE – MC-PCS DUO
GROUNDING
• PROVIDE GROUNDING AND BONDING OF ALL ELECTRICAL AND COMMUNICATION APPARATUS,
MACHINERY, APPLIANCES, BUILDING COMPONENTS, AND ITEMS REQUIRED BY THE NEC TO PROVIDE A
PERMANENT, CONTINUOUS LOW IMPEDANCE, GROUNDING SYSTEM. PROVIDE AN NEC
BONDING/GROUNDING CONDUCTOR IN ALL RACEWAYS USE FOR POWER DISTRIBUTION.
SUPPORTING DEVICES
• PROVIDE SUPPORTS, ANCHORS, SLEEVES AND SEALS AS REQUIRED FOR A COMPLETE RACEWAY
SUPPORT SYSTEM, INCLUDING BUT NOT LIMITED TO: CLEVIS HANGERS, RISER CLAMPS, C-CLAMPS, BEAM CLAMPS, ONE- AND TWO-HOLE CONDUIT STRAPS, OFFSET CONDUIT CLAMPS, EXPANSION
ANCHORS, TOGGLE BOLTS, THREADED RODS, U-CHANNEL STRUT SYSTEM, AND ALL OTHER
ASSOCIATED ACCESSORIES. INSTALL IN ACCORDANCE WITH MANUFACTURER’S WRITTEN
INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE SUPPORTING DEVICES
COMPLY WITH REQUIREMENTS. PROVIDE RIGID ATTACHMENT OF ALL FLOOR MOUNTED EQUIPMENT TO
THE FLOOR SLAB OR STRUCTURAL SYSTEM.
CONDUIT RACEWAYS
1. PROVIDE METAL CONDUIT, TUBING, AND FITTINGS OF TYPES, GRADES, SIZES, AND WEIGHTS (WALL
THICKNESS) AS REQUIRED; WITH MINIMUM TRADE SIZE OF 3/4”. INSTALL ELECTRICAL RACEWAY
SYSTEMS IN ACCORDANCE WITH MANUFACTURER’S WRITTEN INSTRUCTIONS AND APPLICABLE
REQUIREMENTS OF NEC AND NECA “STANDARD OF INSTALLATION” IN ACCORDANCE WITH THE
FOLLOWING:
A. FEEDERS: INSTALL FEEDERS RATED 100 AMPS AND GREATER, IN ELECTRICAL METALLIC CONDUIT
(EMT); WHERE BURIED BELOW GRADE, INSTALL IN CONCRETE ENCASED N0N-METALIC CONDUIT
OR DUCT (SCHEDULE 40 PVC).
B. BRANCH CIRCUITS, AND INDIVIDUAL EQUIPMENT CIRCUITS RATED LESS THAT 100 AMPS; INSTALL
IN ELECTRICAL METALLIC TUBING (EMT). WHERE LOCATED IN POURED WALLS, BELOW CONCRETE
SLAB-ON-GRADE, OR IN EARTH FILL, INSTALL IN NON-METALLIC PLASTIC DUCT (SCHEDULE 40
PVC). ENCASE NON-METALLIC PLASTIC DUCT 1-1/4” AND LARGER IN CONCRETE.
C. PROVIDE RIGID METAL CONDUIT (RMC) FOR ALL BENDS IN BURIED CONDUIT GREATER THAN 30
DEGREES. PROVIDE PROTECTIVE COATING FOR RIGID METAL CONDUIT BENDS.
D. INSTALL FLEXIBLE CONDUIT FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER
ELECTRICAL EQUIPMENT WHERE SUBJECT TO MOVEMENT AND VIBRATIONS.
E. PROVIDE “OZ” EXPANSION FITTINGS ON ALL CONDUITS CROSSING BUILDING EXPANSION JOINTS, BOTH IN SLAB AND SUSPENDED.
F. DUCT BANKS” PROVIDE DUCT BANK CONSTRUCTION AS INDICATED USING 3000 PSI CONCRETE
WITH RED MARKER DYE. INSTALL #4 REINFORCING BAR IN EACH CORNER OF DUCT BANK.
PROVIDE MINIMUM OF 4” CONCRETE COVER ON ALL SIDES OF EXTERIOR CONDUITS.
ELECTRICAL BOXES AND FITTINGS
1. PROVIDE ONE PIECE GALVANIZED FLAT ROLLED SHEET STEEL INTERIOR OUTLET WIRING BOXES, CORROSION-RESISTANT CAST-METAL WEATHERPROOF…
This is the start of the file's text. The full file is on GovTribe.