AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. AMENDMENT/MODIFICATION NO. 2. EFFECTIVE DATE 3. REQUISITION NO. PAGE
4. ISSUED BY 5. ADMINISTERED BY (If other than Item 4)
6. SUPPLIER NAME AND ADDRESS 7A. AMENDMENT OF SOLICITATION NO.
7B. DATED (SEE ITEM 9)
8A. MODIFICATION OF CONTRACT / ORDER NO.
8B. DATED (SEE ITEM 10)
9. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 6 and 13 and returning is extended. is not extended. Offerors must acknowledge
10. THIS ITEM APPLIES ONLY TO MODIFICATION OF CONTRACT / ORDER IN ITEM 8A. IT MODIFIES THE CONTRACT/ORDER NO. AS SET FORTH IN ITEM 11.
A. THIS CHANGE IS ISSUED PURSUANT TO CLAUSE: (Specify clause by number and name)
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO THE AUTHORITY OF MUTUAL AGREEMENT.
D. OTHER: (Specify type of modification and authority)
E. IMPORTANT: Supplier is not, is required to sign this document and return
1 12 0003 07/12/2021
National Programs Facility Services CMC United States Postal Service 6 Griffin Road North
4BFNPT
Windsor CT 06006-7002
(860) 285-7322
National Programs Facility Services CMC United States Postal Service 6 Griffin Road North
4BFNPT
Windsor CT 06006-7002 x
11. DESCRIPTION OF AMENDMENT/MODIFICATION
number. YOUR OFFER MAY BE REJECTED IF ACKNOWLEDGEMENT OF THIS ADMENDMENT IS NOT RECEIVED AT THE PLACE DESIGNATED AND PRIOR TO THE HOUR AND DATE
SPECIFIED. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or email, provided each letter or email makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or email which includes a reference to the solicitation and amendment x x
4BW-21-A-0005
copies to the issuing office.
07/12/2021
OF
JODI K. GAY
The above numbered Solicitation is amended as set forth in Items 7A and 11. The hour and date specified for receipt of Offers
TELEPHONE
TELEPHONE FAX
FAX
CODE
CODE
CODE
copies of 3 jodi.k.gay@usps.gov
AMENDMENT NO.0003 IS BEING CREATED TO ANSWER QUESTIONS SUBMITTED TO THE POSTAL SERVICE FOR
FURTHER CLARIFICATION AS FOLLOWS:
1. IN PARAGRAPH A. HVAC SYSTEM IT STATES, "THE DETAILS AND PREVENTIVE MAINTENANCE SCHEDULES
FOR EQUIPMENT ASSOCIATED WITH THESE PIECES OF EQUIPMENT ARE NOTED ON THE HVAC STATEMENT OF
WORK."
QUESTION: WHERE IS THE HVAC STATEMENT OF WORK?
RESPONSE: HVAC PM DETAILS AND SCHEDULES ARE BASED ON THE MANUFACTURER'S RECOMMENDATION FOR
EACH PIECE OF EQUIPMENT. ATTACHMENTS A1 THROUGH R1, STARTING ON PAGE 94 OUTLINE WHAT IS
Continued ...
14. UNITED STATES POSTAL SERVICE (CO's Name, Date, Signature)13. SUPPLIER (Name, Date, Signature)
Except as provided herein, all terms and conditions of the document referenced in Item 7A or 8A, as heretofore changed, remain unchanged and in full force and effect.
12. ACCOUNTING DATA A. AWARD PAYMENT TERMS B. NET CHANGE
EMAIL:
TELEPHONE:
EMAIL:
TELEPHONE:
TITLE: TITLE:
X 1
RS21C0
Highlight
RS21C0
Highlight
ITEM NO. DESCRIPTION OF GOODS/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
2 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
CURRENTLY PERFORMED ON ALL EQUIPMENT.
2. COOLING IS PROVIDED BY TWO 500 TON CHILLER
UNITS (TRANE) AND DISTRIBUTED VIA CHILLED WATER
TO 47 AIR HANDLING UNITS WITH DUCTED SUPPLY AND
OPEN PLENUM RETURN.
QUESTION: AHU INSPECTION POINTS TABLE DOES NOT
LINE UP WITH E ITEM A OR TABLE L
MONTHLY/QUARTERLY PM-WHAT IS THE CORRECT NUMBER
OF AIR HANDLING UNITS TO BE MAINTAINED?
RESPONSE: SEE ATTACHMENT NO.0006, A, AIR HANDLER
UNITS.
3. B. "ELECTRICAL POWER SOURCE-GENERAL" IT STATES
"THE BUILDING IS SERVED BY FOUR 800-AMP
PAD-MOUNTED TRANSFORMERS WHICH PROVIDES 480-VOLT
SERVICE TO THE MAIN 3000-AMP SWITCHGEAR LOCATED
ON THE SUBBASEMENT FLOOR." HOWEVER, THERE ARE NO
MAINTENANCE REQUIREMENTS PROVIDED FOR THIS
EQUIPMENT.
QUESTION: IS THE CONTRACTOR RESPONSIBLE FOR
MAINTAINING THE FOUR 800-AMP TRANSFORMERS AND THE
MAIN 3000-AMP SWITCHGEAR?
RESPONSE: CONTRACTOR WILL DO IR TESTING EVERY
OTHER YEAR ON THE FOUR (4) 800-AMP TRANSFORMERS.
UNDER THE CONTRACT, THE CONTRACTOR IS NOT
RESPONSIBLE FOR THE 3,000-AMP SWITCHGEAR.
4. THIS PARAGRAPH STATES "THE CONTRACTOR SHALL
PROVIDE ADDITIONAL MANAGEMENT SERVICES AS
DIRECTED BY THE CO OR COR THAT ARE REASONABLY
EXPECTED IN THE OPERATION OF A MULTI-TENANT
OFFICE BUILDING, INCLUDING, BUT NOT LIMITED TO,
SCHEDULING ADDITIONAL CUSTODIAL OR SECURITY
SERVICES FOR SPECIAL EVENTS, SCHEDULING
ADDITIONAL DUMPSTER SERVICING WHEN NEEDED, AND
OTHER NON- ROUTINE SERVICES."
QUESTION: WHAT ARE THE NUMBER OF ANNUAL
OCCURRENCES FOR EACH EVENT?
RESPONSE: VARIES. UTILIZE EXISTING HOUSEKEEPING
STAFF FOR VARIED MONTHLY COURT EVENTS. WORK WITH
Continued ...
3 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
ONSITE CONTRACTORS WHEN NEEDED.
SCHEDULE/COORDINATE ADDITIONAL DUMPSTER SERVICING
WHEN NEEDED. MAINTENANCE AND HOUSEKEEPING NEEDS
ARE PLANNED AND COORDINATED WITH EXISTING STAFF.
RESPONSIBLE FOR BADGE SECURITY SYSTEM MAINTENANCE
AND UPKEEP ALONG WITH THE DISTRIBUTION OF
SECURITY BADGES FOR THE FACILITY. ADDITIONAL
SECURITY OFFICER NEEDS COURT PROCEEDINGS AND
SPECIAL EVENTS ARE COORDINATED BY US MARSHAL'S
SERVICE.
5. THIS REQUIREMENT STATES THE CONTRACTOR SHALL
PROVIDE ALL OPERATING PARTS AND SUPPLIES AS WELL
AS ALL CUSTODIAL MACHINERY AND SUPPLIES.
QUESTION: DOES THIS INCLUDE EQUIPMENT AND
SUPPLIES FOR THE CUSTODIAL SERVICES IDENTIFIED IN
THE SOW ON PAGE 84 THAT PERFORMS CUSTODIAL
SERVICE FOR USPS AREAS?
RESPONSE: NO.
6. THIS REQUIREMENT STATES THAT "THERE ARE 42
WATER FOUNTAINS LOCATED THROUGHOUT THE BUILDING
AND THESE ARE CLEANED DAILY BY THE CUSTODIAL
STAFF"
QUESTION: IS THIS PERFORMED BY THE CUSTODIAL
STAFF IDENTIFIED IN THE SOW ON PAGE 84 THAT
PERFORMS CUSTODIAL SERVICES WITHIN THE USPS
AREAS?
RESPONSE: NO.
7. A FILTRINE WATER FOUNTAIN CHILLER IS LOCATED
IN THE MAIN ENGINEERING SPACES AND PREVENTATIVE
MAINTENANCE IS DONE. THREE ICE MACHINES/WATER
DISPENSERS (LOCATED ON 1ST,3RD,4THFLOORS) AND
PREVENTATIVE MAINTENANCE IS DONE ON A MONTHLY
BASIS AND FILTERS ARE CHANGED SEMI-ANNUALLY.
THERE ARE 42 WATER FOUNTAINS LOCATED THROUGHOUT
BUILDING AND THESE ARE CLEANED DAILY BY CUSTODIAL
STAFF AND INSPECTED ON A MONTHLY AND ANNUAL BASIS
BY THE ENGINEERING STAFF."
QUESTION: ARE THERE ANY PREVENTATIVE MAINTENANCE
REQUIREMENTS FOR THE 42 WATER FOUNTAINS LOCATED
4 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
THROUGHOUT THE BUILDING BEYOND THE INSPECTION?
RESPONSE: THESE UNITS ARE INSPECTED AND CLEANED
REGULARLY. ANY NOTED MAINTENANCE ISSUES ARE
REPAIRED. MANUFACTURER MAINTENANCE MANUALS ARE
RETAINED IN-HOUSE.
8. THESE TABLE PROVIDES A COMPREHENSIVE INVENTORY
OF THE VAVS HOWEVER THERE IS NOT A INSPECTION OR
PREVENTATIVE MAINTENANCE REQUIREMENT ASSOCIATED
WITH VAVS.
QUESTION: WHAT IS THE REQUIREMENT FOR MAINTENANCE
OF THE VAVS?
RESPONSE: SUPPLIER WILL CONDUCT REGULAR PM
INSPECTIONS ON ALL EQUIPMENT, CHANGE FILTERS, AND
DO ALL REPAIR WORK. REPAIR IF BROKEN.
9. THIS TABLES A REQUIRES TO "FOLLOW ANY
INSTRUCTIONS LISTED ON WORK ORDER FOR CONDENSER,
EVAPORATOR, FILTER, OPERATION OF UNIT"
QUESTION: WHAT ARE THE INSTRUCTIONS LISTED ON THE
WORK ORDER? WHAT ARE THE SIZES OF THESE UNITS?
RESPONSE: TO BE PROVIDED UNDER AMENDMENT NO.0004.
10. THIS TABLE ONLY INDICATES INSPECTION FOR
THESE AC UNITS.
QUESTION: ARE THERE ANY PREVENTATIVE MAINTENANCE
REQUIREMENTS FOR THESE AC UNITS BEYOND THE
INSPECTION IDENTIFIED IN THE ADDENDUM?
RESPONSE: NO.
11. THE SOW OF WORK IDENTIFIES 10 ELEVATORS
WITHIN THE PAGE BELCHER BUILDING HOWEVER THE ONLY
PM REQUIREMENT APPEARS TO BE CARPET CLEANING FOR
ELEVATOR 1,2,3 IN ADDENDUM M/1 OF 3
QUESTION: ARE THERE ANY OTHER MAINTENANCE OR
INSPECTION REQUIREMENTS FOR THESE ELEVATORS?
RESPONSE: CURRENTLY THERE IS A LOCAL ELEVATOR
VENDOR MAINTENANCE CONTRACT. THE POSTAL SERVICE
5 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
CONDUCTS SEMI-ANNUAL, ANNUAL & 5-YR INSPECTIONS.
THE LOCAL ELEVATOR VENDOR PARTICIPATES IN THE
SEMI-ANNUAL WITH USPS.
12. C. STATES "THE USPS WILL PROVIDE ITS OWN
CUSTODIAL SERVICES IN SPACE USED BY THE USPS AND
THE SUBBASEMENT OF THE PROPERTY."
QUESTION: ARE THERE ANY CUSTODIAL REQUIREMENTS IN
THIS RFP FOR CUSTODIAL SERVICES FOR AND OTHER
COMMON AREAS OR OFFICES?
RESPONSE: THE POSTAL SERVICE IS RESPONSIBLE FOR
HOUSEKEEPING IN POSTAL SERVICE OCCUPIED SPACES.
THE CONTRACTOR IS RESPONSIBLE FOR HOUSEKEEPING
SERVICES IN THE REMAINING AREAS OF THE BUILDING
(COMMON, OFFICES, CHAMBERS, JAIL CELLS), PARKING
LOT AND EXTERIOR PERIMETER GROUNDS.
13. THE CONTRACTOR SHALL PROVIDE ALL PERSONNEL,
EQUIPMENT, TOOLS, SUPERVISION, AND OTHER ITEMS
AND SERVICES NECESSARY TO ENSURE THAT GROUNDS
MAINTENANCE IS PERFORMED AT THE USPS LOCATIONS
SPECIFIED IN THE SOLICITATION IN A MANNER THAT
WILL MAINTAIN HEALTHY GRASS, TREES, SHRUBS, AND
PLANTS AND PRESENT A CLEAN, NEAT, AND
PROFESSIONAL APPEARANCE. THERE DOES NOT APPEAR TO
BE ANY GROUND SPECIFIED IN THIS SOLICITATION.
QUESTION: CAN THE USPS PLEASE SPECIFY THE GROUNDS
THAT WILL REQUIRE MAINTENANCE?
RESPONSE: PLEASE REVIEW THE GROUNDS ON THE
MANDATORY SITE VISIT.
14. PERIOD OF PERFORMANCE
QUESTION: WILL THERE BE A TRANSITION IN PERIOD
BEFORE THE EXPECTED START DATE OF OCTOBER 1, 2021?
RESPONSE: YES. IT IS ANTICIPATED THAT THERE WILL
BE A TRANSITION FROM THE INCUMBENT SUPPLIER TO
THE NEW ONE. THE CONTRACT AWARD DATE AND THE
CONTRACT START DATE MAY VARY.
15. CFR 22.1007
6 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
QUESTION: PLEASE CONFIRM SERVICE CONTRACT ACT AWD
2015-5317, REVISION 13 DATED 01JUN21 IS
APPLICABLE TO THIS SOLICITATION.
RESPONSE: THE POSTAL SERVICE PROVIDES A COPY OF
THE SERVICE CONTRACT ACT WAGES AS PART OF THE
SOLICITATION. IT IS THE RESPONSIBILITY OF THE
OFFEROR TO CONFIRM THE USE AND APPLICATION OF THE
CORRECT SERVICE CONTRACT ACT WAGE DETERMINATION.
16. CFR 22.1007
QUESTION: PLEASE CONFIRM WHICH, IF ANY, OF THE
DAVIS BACON ACTS OK20210028(HEAVY),
OK20210053(BUILDING) AND OK20210017(HIGHWAY) ARE
APPLICABLE TO THIS SOLICITATION.
RESPONSE: RESPONSE: THE POSTAL SERVICE PROVIDES A
COPY OF THE SERVICE CONTRACT ACT WAGES AS PART OF
THE SOLICITATION. IT IS THE RESPONSIBILITY OF
THE OFFEROR TO CONFIRM THE USE AND APPLICATION OF
THE CORRECT SERVICE CONTRACT ACT WAGE
DETERMINATION.
17. PLEASE CLARIFY IF THIS SOLICITATION IS
SUBJECT TO ANY CURRENT EXECUTIVE ORDERS (13706,
$15 MINIMUM, ETC.)
RESPONSE: IT IS THE RESPONSIBILITY OF SUPPLIER TO
CONFIRM WHAT ACTS AND EXECUTIVE ORDERS APPLY TO A
RESULTANT CONTRACT.
18. PAGE 93 SECTION F SPECIAL REQUIREMENTS STATES
"THE CONTRACTOR SHALL PROVIDE ADDITIONAL
MANAGEMENT SERVICES AS DIRECTED BY THE CO OR COR
THAT ARE REASONABLY EXPECTED IN THE OPERATION OF
A MULTI-TENANT OFFICE BUILDING, INCLUDING, BUT
NOT LIMITED TO, SCHEDULING ADDITIONAL CUSTODIAL
OR SECURITY SERVICES FOR SPECIAL EVENTS,
SCHEDULING ADDITIONAL DUMPSTER SERVICING WHEN
NEEDED, AND OTHER NON-ROUTINE SERVICES." BUT
FAILS TO PROVIDE ANY SPECIFIC REQUIREMENTS,
WORKLOAD OR ANY OTHER DATA WHICH OFFERORS COULD
REASONABLY RELY UPON IN A FIRM FIXED PRICE
CONTRACT TYPE.
QUESTION: WILL THE USPS CLARIFY THE WORKLOAD
7 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
ASSOCIATED WITH SCHEDULING ADDITIONAL CUSTODIAL
OR SECURITY SERVICES FOR SPECIAL EVENTS,
SCHEDULING ADDITIONAL DUMPSTER SERVICING AND ANY
OTHER NON-ROUTINE SERVICES OR OTHERWISE CHANGE
THE CONTRACT TYPE TO A NEGOTIATED IDIQ OR OTHER
CONTRACT TYPE?
RESPONSE: VARIES. UTILIZE EXISTING HOUSEKEEPING
STAFF FOR VARIED MONTHLY COURT EVENTS. WORK WITH
ONSITE CONTRACTORS WHEN NEEDED.
SCHEDULE/COORDINATE ADDITIONAL DUMPSTER SERVICING
WHEN NEEDED. MAINTENANCE AND HOUSEKEEPING NEEDS
ARE PLANNED AND COORDINATED WITH EXISTING STAFF.
RESPONSIBLE FOR BADGE SECURITY SYSTEM MAINTENANCE
AND UPKEEP ALONG WITH THE DISTRIBUTION OF
SECURITY BADGES FOR THE FACILITY. ADDITIONAL
SECURITY OFFICER NEEDS COURT PROCEEDINGS AND
SPECIAL EVENTS ARE COORDINATED BY US MARSHAL'S
SERVICE. USPS TFM/IFSM CONTRACTS HAVE A SEPARATE
CLIN WITH FUNDING IN THE CONTRACT FOR
OUT-OF-SCOPE WORK.
19. THE USPS MAY BE SALES TAX - EXEMPT IN THE
STATE OF OK.
QUESTION: WILL THE USPS PROVIDE AN OKLAHOMA
CERTIFICATE OF SALES TAX EXEMPTION OR OTHERWISE
CLARIFY WHETHER SALES TAX SHOULD BE INCLUDED IN
OFFERORS PRICES?
RESPONSE: YES. THE POSTAL SERVICE WILL PROVIDE A
TAX EXEMPTION CERTIFICATE AT THE TIME OF CONTRACT
AWARD.
20. IN SECTION 3. ITEMS & PRICES OF THE RFP,
PRICING INFORMATION IS REQUESTED IN PS FORM 8203.
THIS CONFLICTS WITH SECTION 9.D PROPOSAL FORMAT
INSTRUCTIONS/REQUIREMENTS, WHERE IT STATES THAT
COMPLETED PS FORM 8203 IS TO BE INCLUDED IN THE
CONTRACTUAL VOLUME. 9.B_COST/PRICE STATES UNDER
NO CIRCUMSTANCE SHALL COST OR PRICING DATA BE
INCLUDED ELSEWHERE IN THE PROPOSAL. PLEASE
CLARIFY WHICH VOLUME SHOULD INCLUDE PS FORM 8203.
RESPONSE: PLEASE INCLUDE THE SIGNED AND COMPLETED
PS FORM 8203 IN VOLUME 1, COST/PRICE ONLY.
8 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
21. DOES SECTION C PARAGRAPH G OF THE RFP REQUIRE
THE OFFEROR BE RESPONSIBLE FOR THE ACQUISITION
AND MANAGEMENT OF ALL UTILITIES AND SERVICES
ASSOCIATED WITH THIS FACILITY?
RESPONSE: JUST TRASH AND RECYCLING SERVICES.
22. ARE WE TO PROVIDE ALL LAWNCARE SERVICE
EQUIPMENT (LAWN MOWERS, TRACTORS, WEEDWHACKER¿S,
ETC.) TO MAINTAIN THE GROUNDS?
RESPONSE: IF THE SUPPLIER INTENDS TO USE EXISTING
EMPLOYEES TO PERFORM LANDSCAPE SERVICES, THEN THE
SUPPLIER WILL PROVIDE THE NECESSARY EQUIPMENT TO
PERFORM THESE SERVICES. IF THE SUPPLIER
SUBCONTRACTS THIS WORK, IT IS EXPECTED THAT THE
SUPPLIERS SUBCONTRACTOR WILL HAVE THE NECESSARY
EMPLOYEES AND EQUIPMENT TO PERFORM THE REQUIRED
LANDSCAPE SERVICES.
23. ALL PARTS MUST HAVE A BARCODE BE TRACKED TO
THE STORAGE LOCATION AND WHERE AND WHEN IT WAS
USED. IS THIS FOR CONTRACTUAL PARTS OR THE
ENTIRE OPERATION?
RESPONSE: ENTIRE OPERATION.
24. THE USPS WILL PROVIDE ITS OWN CUSTODIAL
SERVICES IN SPACE USED BY THE USPS AND THE
SUB-BASEMENT OF THE PROPERTY. DO WE MANAGE THESE
SERVICES TOO?
RESPONSE: NO.
25. CONTRACTOR SHALL PROVIDE ALL OPERATING PARTS
AND SUPPLIES AS WELL AS ALL CUSTODIAL MACHINERY
AND SUPPLIES. STORAGE IS AVAILABLE ON SITE; THE
CONTRACTOR IS RESPONSIBLE FOR STORAGE OF
SUPPLIES. DO THE PARTS AND SUPPLIES APPLY TO
SECTION C ABOVE?
RESPONSE: NO.
26. THERE ARE 42 WATER FOUNTAINS LOCATED
THROUGHOUT THE BUILDING AND THESE ARE CLEANED
DAILY BY THE CUSTODIAL STAFF AND INSPECTED ON A
MONTHLY AND ANNUAL BASIS BY THE ENGINEERING
9 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
STAFF. ONLY THE FOUNTAINS OUTSIDE OF SPACE USED
BY THE USPS AND THE SUBBASEMENT OF THE PROPERTY?
RESPONSE: ENGINEERING STAFF INSPECTS/REPAIRS ALL
FOUNTAINS ON THE PROPERTY (POSTAL OCCUPIED AND
NON-POSTAL OCCUPIED). OUR HOUSEKEEPING CLEANS
NON-POSTAL OCCUPIED FOUNTAINS ONLY. POSTAL
HOUSEKEEPING CLEANS FOUNTAINS IN POSTAL-OCCUPIED
SPACE.
27. SINKS, TOILETS AND URINALS ARE CLEANED DAILY
BY CUSTODIAL STAFF AND ATTENDED TO IF THERE IS A
MALFUNCTION BY THE ENGINEERING STAFF. ONLY THE
SINKS, TOILETS AND URINALS OUTSIDE OF SPACE USED
BY THE USPS AND THE SUBBASEMENT OF THE PROPERTY?
RESPONSE: ENGINEERING STAFF INSPECTS/REPAIRS ALL
SINKS, TOILETS & URINALS ON THE PROPERTY (POSTAL
OCCUPIED AND NON-POSTAL OCCUPIED). OUR
HOUSEKEEPING CLEANS NON-POSTAL OCCUPIED SINKS,
TOILETS & URINALS. POSTAL HOUSEKEEPING CLEANS
SINKS, TOILETS & URINALS IN POSTAL-OCCUPIED SPACE.
28. ALL PARTS MUST HAVE A BARCODE BE TRACKED TO
THE STORAGE LOCATION AND WHERE AND WHEN IT WAS
USED, THROUGH THE WORK ORDER SYSTEM IS THE
RESPONSIBILITY OF CONTRACTOR?
QUESTION: IS THE WORK ORDER SYSTEM THE SAME AS
MICRO MAIN REFERENCED IN SECTION C ABOVE?
RESPONSE: NO DIFFERENT APPLICATIONS.
29. THE REFERENCED PARAGRAPHS STATE 1) "ALL
INFORMATION RELATING TO COST OR PRICING DATA MUST
BE INCLUDED IN VOLUME I." 2) D. ANY PROPOSAL
CONTAINING OPTIONS THAT IS MATERIALLY UNBALANCED
AS TO PRICES FOR BASE AND OPTION QUANTITIES MAY
BE DISREGARDED AS UNACCEPTABLE. AN UNBALANCED
PROPOSAL IS ONE THAT IS BASED ON PRICES
SIGNIFICANTLY LESS THAN COST FOR SOME WORK AND
PRICES THAT ARE SIGNIFICANTLY OVERSTATED FOR
OTHER WORK. THESE (AND OTHER) PARAGRAPHS DO NOT
SEEM TO DESCRIBE IN DETAIL THE REQUIREMENTS FOR A
PRICE PROPOSAL OTHER THAN OFFERORS ARE TO FILL
OUT FORM PS FORM 8203 - (MAY 2020). THIS CAN
ALLOW AMBIGUOUS STATEMENTS FROM OFFERORS TO BE
10 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
MADE WHICH, WHEN NOT PROPERLY SUPPORTED, MAY LEAD
TO POOR PERFORMANCE FOR THE CLIENT, POOR
FINANCIAL PERFORMANCE BY THE OFFEROR AND EVEN
BANKRUPTCY IN SOME CASES.
QUESTION: PLEASE CLARIFY IF THERE ARE ANY
REQUIREMENTS IN THE COST VOLUME 1 OTHER THAN TO
PROVIDE A COMPLETED FORM PS FORM 8203 - (MAY
2020) AND IF SO, WHAT THE SPECIFIC REQUIREMENTS
ARE, AND LEVEL OF DETAIL REQUIRED.
RESPONSE: THE DETAILS IN COST VOLUME 1 SHOULD BE
SUFFICIENT ENOUGH AS TO SHOW HOW THE OFFEROR
CALCULATED THE THREE (3) YEAR BASE, AND THE TWO -
2-YEAR OPTIONS TO RENEW. ALL INFORMATION
RELATING TO COST OR PRICING DATA MUST BE INCLUDED
IN VOLUME 1. PRICE EVALUATIONS WILL BE BASED ON
THE TOTAL COST TO THE POSTAL SERVICE FOR THE
THREE (3) YEAR BASE PERIOD AND THE TWO - 2-YEAR
OPTIONS TO RENEW.
30. THE PWS SAYS WE ARE TO CLEAN ALL AREAS NOT
OCCUPIED BY THE USPS. HOWEVER, IT DOES NOT
SPECIFY WHERE THESE AREAS ARE. IN ORDER TO
ESTIMATE OUR STAFFING FOR CLEANING WE WILL NEED
THE SQUARE FOOTAGE OF AREAS WE ARE TO CLEAN
BROKEN DOWN BY FLOOR TYPE (HARD FLOORS OR
CARPET). CAN THE GOVERNMENT PLEASE PROVIDE THIS
INFORMATION?
RESPONSE: SEE ATTACHMENT NO.0007 - PAGE BELCHER
FEDERAL SUILDING CUSTODIAL SERVICES-SQUARE
FOOTAGE.
31. PLEASE PROVIDE THE NUMBER OF RESTROOMS TO BE
CLEANED TO INCLUDE THE NUMBER OF FIXTURES
(TOILETS, SINKS AND URINALS). THIS INFORMATION
CANNOT BE FOUND IN THE PWS.
RESPONSE: SEE ATTACHMENT NO.0008 - RESTROOM AND
RESTROOM FIXTURES COUNT DATED 07/21/21.
32. THE PWS STATES WE ARE TO DO TRASH REMOVAL.
HOWEVER, NO PICKUP SCHEDULE HAS BEEN PROVIDED.
PLEASE PROVIDE THE PICKUP SCHEDULE ALONG WITH THE
NUMBER AND SIZE OF DUMPSTERS.
11 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
RESPONSE: PAPER RECYCLING (ENTIRE BUILDING
INCLUDING USPS): CARDBOARD COMPACTOR USPS OWNS
THE COMPACTING UNIT, A LOCAL VENDOR SERVICES 40
YD CONTAINER. EMPTIED APPROXIMATELY EVERY 6 WEEKS.
FIVE, 96-GAL PAPER RECYCLE TOTES ON 2M, 3RD & 4TH
FLOOR FOR COURT USE (EMPTIED WEEKLY)
BOTTLES/CANS RECYCLING (ENTIRE BUILDING INCLUDING
USPS): FOUR - GAYLORD BINS (48 X 40 X 36") W
CASTERS, EMPTIED 1-2 TIME/YEAR.
TRASH (ENTIRE BUILDING INCLUDING USPS): TRASH
COMPACTOR 40 YD EMPTIED APPROXIMATELY EVERY 5-6
WEEKS. OPEN TOPS RANGE FROM 20-40 YD, AS NEEDED.
E-WASTE: ON AN AS-NEEDED BASIS ONLY.
COURTS IT DEPT TAKE CARE OF THEIR OWN EWASTE.
33. THE PWS STATES WE ARE TO DO WINDOW WASHING.
PLEASE PROVIDE THE NUMBER OF EXTERIOR WINDOWS SO
OUR WINDOW WASHING SUBCONTRACTOR CAN ESTIMATE THE
EXTERIOR WINDOW WASHING.
RESPONSE: WINDOW COUNT AVAILABLE AT THE TIME OF
SITE VISIT.
INTERIOR GLASS: UPPER FLOORS EXISTING
HOUSEKEEPING STAFF CLEAN INTERIOR GLASS ON UPPER
FLOORS 1X/YEAR AND/OR SPECIAL TENANT REQUESTS.
1ST FLOOR POSTAL BOX LOBBY INTERIOR GLASS USPS
HOUSEKEEPING. 4TH STREET MAIN ENTRANCE DOORS &
SLIDERS INTERIOR GLASS LOCAL VENDOR. MAIN LOBBY
INTERIOR BULLETPROOF GLASS THROUGHOUT THE SECURED
CHECKPOINT HOUSEKEEPING USES A SPECIAL CLEANER
FOR BULLETPROOF GLASS, CLEAN AS NEEDED.
EXTERIOR GLASS: DENVER AVENUE, USPS 15-MINUTE
PARKING EXTERIOR GLASS, LOCAL VENDOR. ALONG 4TH
STREET EXTERIOR GLASS, LOCAL VENDOR. 4TH STREET
SECURED MAIN ENTRANCE DOORS BOTH EXTERIOR &
INTERIOR GLASS, LOCAL VENDOR.
34. THE PWS DOES NOT SPECIFY WHAT TYPE OF
LANDSCAPING IS TO BE PROVIDED. PLEASE PROVIDE
THE NUMBER AND SIZE OF PLANT BEDS AND LAWN
SURFACES.
RESPONSE: THE BUILDING IS 408' X 203". 4TH
STREET/SOUTH SIDE OF THE BUILDING (408') HAS 5-6
12 12 CONTINUATION SHEET
PAGE OFREQUISITION NO.
CONTRACT/ORDER NO.
EFFECTIVE DATE
AWARD/ MASTER CONTRACT NO SOLICITATION NO.
ISSUE DATE
SOLICITATION
07/12/2021 07/12/2021
4BW-21-A-0005
FLOWER BEDS, LAWN (15-20,W X 408' W, YAUPON
HOLLIES AND A COUPLE OF LARGE OAK TREES. DENVER
AVENUE 15-MINUTE POSTAL PARKING/EAST SIDE (203')
HALF OF THE WIDTH OF THIS SIDE OF THE BUILDING IS
LAWN AND YAUPON HOLLIES.
THE REMAINING AREAS AROUND THE PERIMETER OF THE
BUILDING ARE PARKING LOT.
35. CAN THE SOLICITATION BE EXTENDED?
RESPONSE: YES. THE SOLICITATION CLOSE DATE HAS
BEEN EXTENDED TO MONDAY, AUGUST 30, 2021, 5:00PM
E.T.
ATTACHMENTS: 3, 5 PAGES TOTAL.
************ NOTICE TO OFFERORS *************
PLEASE COMPLETE HIGHLIGHTED BOXES 6 AND 13.
ONCE COMPLETED, PLEASE SCAN AND E-MAIL OR FAX
BACK THIS COMPLETED AMENDMENT NO.0003 TO
650.357.6746, OR E-MAIL AT paul.a.digrassi@usps.gov.
Period of Performance: 10/01/2021 to 09/30/2024
Equipment Floor Manufacturer Model
Number Serial Number HP Cooling
Tonnage
Heating
Tonnage AHU 048 Basement Carrier ----- N493660 1 ----- -----
AHU 049 A Basement sub Trane 21 K-73071 7.5 10 20
AHU 049 B Basement sub Trane 6 K- 73091 0.5 10 20
AHU 049 E Basement sub Trane T-14 K-73045 3
AHU 073 A 1M Trane 6 K-73108 1 6.9 20
AHU 074 A 1M Trane 41 K-73072 15 26.3 20
AHU 074 E 1M Trane T-24 K-73046 7.5 ----- -----
AHU 075 A 1M Trane 41 K-73073 10 10 20
AHU 075 B 1M Trane L-6 K-73110 2 10 20
AHU 075 E 1M Trane T-24 K-73047 5 ----- -----
AHU 076 A 1M Trane 21 K-73074 7.5 10 20
AHU 076 B 1M Trane 3 K-73111 1 10 20
AHU 076 E 1M Trane T-17 K-73048 3 ----- -----
AHU 077 A 1M Trane 41 K-73075 15 10 20
AHU 077 B 1M Trane 8 K-73112 1 10 20
AHU 077 E 1M Trane T-24 K-73049 7.5 ----- -----
AHU 078 A 1M Trane 31 K-73076 10 10 20
AHU 078 B 1M Trane 6 K-73113 0.5 10 20
AHU 078 E 1M Trane T-21 K-73050 5 ----- -----
AHU 079 A 1M Trane L-3 K-73114 1 5.6 20
AHU 080 A 1M Trane 31 K-73077 15 13 20
AHU 080 B 1M Trane 6 K-73115 0.5 10 20
AHU 080 E 1M Trane 21 K-73051 5 ----- -----
AHU 085 A 2M Trane 41 K-73080 15 11.7 20
AHU 085 B 2M Trane 8 K-73094 1 10 20
AHU 085 E 2M Trane T-24 K-73053 7.5 ----- -----
AHU 086 A 2M Trane 41 K-73081 15 10 20
AHU 086 B 2M Trane L-8 K-73095 1.5 1 20
AHU 086 E 2M Trane T-24 K-73054 7.5 ----- -----
AHU 087 A 2M East Trane 31 K-73082 10 10.5 20
AHU 087 B 2M Trane 6 K73096 1 10 20
AHU 087 E 2M Trane T-21 K73055 5 ----- -----
AHU 088 A 2M York
XT1-075X120-
KAQA046A ACRMXT0152 40 ----- -----
AHU 089 A 2M York
XT1-072X126-
KAQA046A ACRMXT0153 40 ----- -----
AHU 093 A 3 Trane 50 K-73085 15 10 20
AHU 093 B 3 Trane 8 K-73116 1.5 10 20
AHU 093 E 3 Trane T-24 K73057 7.5 ----- -----
AHU 094 A 3 Trane 41 K-73086 15 11 20
AHU 094 B 3 Trane 8 K-73117 1.5 10 20
AHU 094 E 3 Trane T-24 K73058 7.5 ----- -----
AHU 095 A 3 Trane 50 K-73087 20 10 20
AHU 095 B 3 Trane 8 K-73118 1.5 10 20
Air Handler Units
AHamm Typewritten Text A
AHamm Typewritten Text A/1 of 2
AHamm Typewritten Text
AHamm Typewritten Text
AHU 095 E 3 Trane T-35 K73070 10 ----- -----
AHU 100 A Penthouse Trane 35 K-73088 10 10 20
AHU 100 B Penthouse Trane T-14 K73099 5 10 20
AHU 100 E Penthouse Trane T-17 K73059 3 ----- -----
AHU 101 A Penthouse Trane L-31 K-73089 10 10 20
AHU 101 B Penthouse Trane 14 K-73100 2 10 20
AHU 101 E Penthouse Trane T-14 K73060 3 ----- -----
AHU 102 A Penthouse Trane 50 K-73090 20 12 20
AHU 102 B Penthouse Trane 14 K-73101 5 10 20
AHU 102 E Penthouse Trane T-24 K73061 5 ----- -----
AHU 103 A Penthouse Trane L-17 K73119 5 10 20
AHU 103 B Penthouse Trane 6 K-73102 1 10 20
AHU 103 E Penthouse Trane T-10 K73062 2 ----- -----
AHU 104 A Penthouse Trane L-12 K-73120 5 10 20
AHU 104 B Penthouse Trane 3 K-73103 1 10 20
AHU 104 E Penthouse Trane T-8 K73063 1 ----- -----
AHU 105 A Penthouse Trane 12 K-73121 5 10 20
AHU 105 B Penthouse Trane 3 K-73104 1 10 20
AHU 105 E Penthouse Trane T-8 K730064 1 ----- -----
AHU 106 A Penthouse Trane 41 K-73131 30 10 20
AHU 106 B Penthouse Trane 6 K-73105 1.5 10 20
AHU 106 E Penthouse Trane T-24 K73065 7.5 ----- -----
AHU 107 A Penthouse Trane 50 K-73132 40 10 20
AHU 107 B Penthouse Trane 10 K73106 2 10 20
AHU 107 E Penthouse Trane T-24 K73066 7.5 ----- -----
AHU 108 A Penthouse Trane 21 K-73133 20 10 20
AHU 108 B Penthouse Trane 6 K-73107 0.75 10 20
AHU 108 E Penthouse Trane T-14 K73067 3 ----- -----
Equipment Floor Parent Manufacturer Model Number Serial Number Type
AC40 1M 1805 Trane 4TTR4060B1000AA 7075XXDD2F 410A
AC41-A 1M 1805 Trane 4TTR5024E1000A 12256PTM5F 410A
AC42 1M 1805 Trane 4TTR4024A1000AA 7045P7G2F 410A
AC43-Portable 4th 4472 MovinCool Classic Plus 14 3000452140 R-22
AC45 Roof 4331 Dayton AC060X1321 W0A6775763 R-22
AC46-A Roof 4331 Dayton ACO60X1031A WKMM043566 R-22
AC47 Basement 0635 Lennox HS6-813V-3L 5479H01394
AC48-Portable Basement 0900 Dayton 2NRX2C G0311110014 410A
Equipment Floor Parent Manufacturer Model Number Serial Number
0645A/C Basement 0645 Frigidaire FAC105 4CE67
0164 Parking Lot 0163 Frederick
Window Units
Split A/C Units
AHamm Typewritten Text
AHamm Typewritten Text A/2 of 2
AHamm Typewritten Text
AHamm Typewritten Text
AHamm Typewritten Text A
AHamm Typewritten Text
Page Belcher Federal Building Jul-21 Custodial Services - Square Footage
Area Waxed Flooring Housekeeping
Basement Basement Corridors 2,131 2,131
Basement Lobbies 567 567
Basement Restrooms 304
US Marshal Service 627
Snack Bar
Basement Total 2,698 3,629
1st Floor Sallyport and Mags 3,624
South Lobby Entrance 1,400 1,400
Postal Window Service
P.O. Boxes
East Lobby Entrance
1st Floor Total 1,400 5,024
2nd Floor 2nd Floor Grand Jury 1,830
US Attorney 1,930
US Marshal Service 25,965
2nd Floor Corridors 3,555 3,555
2nd Floor Lobbies 564 564
2nd Floor Total 4,119 33,844
2M Floor 2M Corridors
2M Lobbies
3rd Floor 3rd Floor Courts 16,810
3rd Floor Corridors 4,372 5,138
3rd Floor Lobbies 761 761
Probation 15,849
3rd Floor Restrooms 1,773
US Marshal Service 851
Janitorial 547
Ice Room 164
3rd Floor Total 5,133 41,893
4th Floor Courts 53,726
US Marshal Service 5,455
10th Circuit 4,883
4th Floor Corridors 8,072 8,072
4th Floor Lobbies 814 814
4th Floor Restrooms 1,360
Janitorial 352
Building 957
4th Floor Total 8,886 75,619
Penthouse Corridors 2,436
Corridors Total 2,436
Total SF 22,236 162,445
C:\Users\RS21C0\AppData\Local\Microsoft\Windows\INetCache\Content.Outlook\2UQDHKX6\Custodial Services Square
Footage by Floor 07-2021.xls
Restroom and Restroom Fixtures Count 07/21/21
4th Floor
38 Restrooms
48 toilets
48 sinks
4 urinals
1 shower
0 fitness center
2 mop sink
2 jail cell (8'x10') w toilet/sink combo
3rdFloor
1 fitness center (1155 sf rubber flooring, equipment)
MRR (363 sf) WRR (342 sf)
2 toilets 2 toilets
4 sinks 2 sinks
2 showers 2 showers
Remainder of 3rd Floor
19 restrooms
28 toilets
28 sinks
3 urinals
1 shower
1 mop sink
2 jail cells (10'x10') w toilet/sink combo
2M ( Postal Housekeeping cleans these restrooms , we maintenance)
3 Restrooms
7 toilets
5 sinks
1 urinals
1 mop sink
2nd Floor
1 fitness center (2427 sf rubber flooring, equipment)
MRR (481 sf) WRR (280 sf)
1 toilet 1 toilet
2 sinks 2 sinks
3 showers 2 showers
2 urinals
Remainder of 2nd Floor
11 restrooms
2 restrooms not in service, not cleaned
11 toilets
13 sinks
2 urinals
2 shower
1 mop sink
7 jail cells (10'x10') w toilet/sink combo
1 Prisoner processing area w shower & sink
1M Floor (Postal Housekeeping cleans these restrooms, we maintenance)
4 restrooms
2 restrooms not in service, not cleaned
10 toilets
6 sinks
3 urinals
1 mop sink
1st Floor ( Postal Housekeeping cleans these restrooms , we maintenance)
4 restrooms
1 restrooms not in service, not cleaned
3 toilets
4 sinks
1 urinals
1 mop sink
Subasement
6 restrooms
8 toilets
8 sinks
2 urinals
1 shower
2 emergency showers
1 mop sink
1 washer for housekeeping
1 Dryer for housekeeping