PUMP_EXHIBIT_20180919_(1).pdf

PDF 248 KB Posted

Attached to
Replacement of cooling tower & Pumps at Federal Building/Courhouse, Laredo, TX
Solicitation number
47PH1118R0009
Issued by

About this file

New Pump Exhibit replacing previous version.

View the file

Other files

File Type Posted
New_SOW_9-20-18.rtf RTF text file
SOO_Exhibit_Laredo_(1).docx DOCX document
09_Pre-Proposal_Record.pdf PDF
Laredo_RFI_(1).pdf PDF
SOW_10-17-18.doc DOC document
C101_The_Agreement.pdf PDF
C301_GC_Reps_&_Certs.pdf PDF
Exhibit_I._SOO_Exhibit.pdf PDF
Exhibit_D.pdf PDF
Exhibit_F._Gauge_Exhibit.pdf PDF
Exhibit_B.pdf PDF
TX235_01-05-18.pdf PDF
Exhibit_H._PUMP_EXHIBIT.pdf PDF
Exhibit_A.pdf PDF
Exhibit_C.pdf PDF
Exhibit_G._Lighting_Exhibit.pdf PDF
47PH1118R0009__Form.pdf PDF
Exhibit_E.__Cooling_Tower.pdf PDF
GSA527-15b.pdf PDF
TX0311__SOW_08-09-2018.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Submittal Ref. #: 602642.1 rev1

Split coupled vertical in line pump

Model: Series 4300 User-Drive-4x4x8-15 hp Pump (Motor supplier: Armstrong choice)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Tag number: CHWP-1 Pipe orientation: Single

Suction pressure: 0 psigService: CHW

Location: CUP Fluid: Non-Potable Fluid - Water

Quantity: 1 Operating temperature: 45 F

Viscosity: 31 SSUDuty flow per pump: 480 USgpm

Specific gravity: 1.0000Duty head: 65 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416

Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type: Outside Balanced Rotating face: Resin Bonded Carbon

Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 15 hp Inverter motor type: Inverter Duty

Frame number: 254TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Speed: 1840 rpm

Motor Electrics: 460/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 1 of 10

PUMP EXHIBIT

ShaMarCNolen Highlight

Performance curve

--- Admin Data --- Tag Num: CHWP-1 Service: CHW Location: CUP

--- Motor Data --- Motor Size: 15 hp

--- Design Duty Point --- Flow: 480 usgpm Head: 65 ft Impeller: 8.19 in

--- Performance Data ---

• NPSHR: 13.3 ft

• Eff. @ Design: 78.44 %

• BHP @ Design: 10.04 hp

• Mtr Capability @ Rated Spd: 15.00 hp

• %Mtr Safety: 49.34%

• BEP @ Design Imp.:

79.51 % @ 558.7 usgpm

• %max imp. range: 100.00 %

• Outlet Velocity: 12.1 ft/s

• VFD Setting: 62.4 Hz

Series 4300 User-Drive

4x4x8 @ 1840 rpm

0 0.2 0.4 0.6 0.8 1

Flow ( 1,000 usgpm)

Head

(ft)

8.19 in

6.00 in

System

8.19 in

5 hp

7.5 hp

10 hp

15 hp

64%

53%

Water, spgr= 1.0000

PT87-3-0 (3.28.0.1)

ANSI/HI 14.6.3.4 2B

--- Admin Data --- Tag Num: CHWP-1 Service: CHW Location: CUP

--- Motor Data --- Motor Size: 15 hp

--- Design Duty Point --- Flow: 480 usgpm Head: 65 ft Impeller: 8.19 in

--- Control Data ---

1. Hmax @ 62.4 Hz:

• 480 @ 65, 10.04 hp

2. Control (QPC) @ 57.6 Hz:

• 424 @ 56.4, 7.77 hp

3. Control (QPC) @ 52.9 Hz:

• 364.4 @ 48.5, 5.83 hp

4. Control (QPC) @ 48.1 Hz:

• 299.7 @ 41.2, 4.21 hp

5. Control (QPC) @ 43.4 Hz:

• 225.6 @ 34.6, 2.87 hp

6. Index @ 38.4 Hz:

• 120 @ 28.4, 1.72 hp

7. Hmin: 26 ft 36.2 Hz:

• Setting= 40.00% Hmax

Series 4300 User-Drive

4x4x8 @ 8.19 in

0 0.2 0.4 0.6 0.8 1

Flow ( 1,000 usgpm)

Head

(ft)

63.0 Hz62.4 Hz

38.4 Hz

36.2 Hz

18.0 Hz

System

Avg.Load (QPC)

15 hp

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT87-3-0 (3.28.0.1)

ANSI/HI 14.6.3.4 2B

www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 2 of 10

PUMP EXHIBIT

Dimensional data (not for construction)

Top viewSide view

Weight: 533 lb

• Not to scale

• R = minimum lifting clearance required above motor

• Units of measure : inches [millimeters]

• Coupling guard and flush line (not shown) are supplied

• Tolerance of ± 0.125 inch (± 3 mm) should be used

• For certified dimensions, please contact your Armstrong representative

• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 4 9ANSI-125 8 0.6257.5

Outlet 4 9ANSI-125 8 0.6257.5

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options Bearing Current Handling: AEGIS Shaft Ground

Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-44 (516860-021) www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 3 of 10

PUMP EXHIBIT

Split coupled vertical in line pump

Model: Series 4300 User-Drive-4x4x8-10 hp Pump (Motor supplier: Armstrong choice)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Tag number: CWP-1 Pipe orientation: Single

Suction pressure: 5 psigService: CW

Location: CUP Fluid: Non-Potable Fluid - Water

Quantity: 1 Operating temperature: 85 F

Viscosity: 31 SSUDuty flow per pump: 600 USgpm

Specific gravity: 1.0000Duty head: 40 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416

Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type: Outside Balanced Rotating face: Resin Bonded Carbon

Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 10 hp Inverter motor type: Inverter Duty

Frame number: 215TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Speed: 1727 rpm

Motor Electrics: 460/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 4 of 10

PUMP EXHIBIT

Performance curve

--- Admin Data --- Tag Num: CWP-1 Service: CW Location: CUP

--- Motor Data --- Motor Size: 10 hp

--- Design Duty Point --- Flow: 600 usgpm Head: 40 ft Impeller: 7.85 in

--- Performance Data ---

• NPSHR: 11.7 ft

• Eff. @ Design: 74.31 %

• BHP @ Design: 8.16 hp

• Mtr Capability @ Rated Spd: 9.76 hp

• %Mtr Safety: 19.62%

• BEP @ Design Imp.:

78.84 % @ 478.5 usgpm

• %max imp. range: 84.77 %

• Outlet Velocity: 15.12 ft/s

• VFD Setting: 58.5 Hz

Series 4300 User-Drive

4x4x8 @ 1727 rpm

0 0.2 0.4 0.6 0.8 1

Flow ( 1,000 usgpm)

Head

(ft)

8.19 in

6.00 in

System

7.85 in

5 hp

7.5 hp

10 hp

15 hp

64%

53%

Water, spgr= 1.0000

PT87-3-0 (3.28.0.1)

ANSI/HI 14.6.3.4.1

--- Admin Data --- Tag Num: CWP-1 Service: CW Location: CUP

--- Motor Data --- Motor Size: 10 hp

--- Design Duty Point --- Flow: 600 usgpm Head: 40 ft Impeller: 7.85 in

--- Control Data ---

1. Set Point @ 58.5 Hz:

• 600 @ 40, 8.16 hp

2. Control (CPC) @ 56.6 Hz:

• 543.3 @ 40, 7.16 hp

3. Control (CPC) @ 54.2 Hz:

• 465.4 @ 40, 5.98 hp

4. Control (CPC) @ 52.2 Hz:

• 388.9 @ 40, 5.01 hp

5. Control (CPC) @ 50.2 Hz:

• 296 @ 40, 4.05 hp

6. Index @ 48.0 Hz:

• 150 @ 40, 2.96 hp

7. Hmin: 40 ft 47.1 Hz:

• Setting= 100.00% Hmax

Series 4300 User-Drive

4x4x8 @ 7.85 in

0 0.2 0.4 0.6 0.8 1

Flow ( 1,000 usgpm)

Head

(ft)

63.0 Hz

58.5 Hz

48.0 Hz

47.1 Hz

18.0 Hz

System

Avg.Load (CPC)

10 hp

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT87-3-0 (3.28.0.1)

ANSI/HI 14.6.3.4.1

1 2 3 4 5 6 www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 5 of 10

PUMP EXHIBIT

Top viewSide view

Weight: 443 lb

• Not to scale

• R = minimum lifting clearance required above motor

• Units of measure : inches [millimeters]

• Coupling guard and flush line (not shown) are supplied

• Tolerance of ± 0.125 inch (± 3 mm) should be used

• For certified dimensions, please contact your Armstrong representative

• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 4 9ANSI-125 8 0.6257.5

Outlet 4 9ANSI-125 8 0.6257.5

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options Casing Wear Ring - Bronze CWR Bearing Current Handling: AEGIS Shaft Ground

Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-44 (516860-021) www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 6 of 10

PUMP EXHIBIT

Flo-trex valve

Model: FTV-F (2.5 to 12 inch)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Design flowrate

Tag Qty Model Size Config Flange rating Pressure

Drop* Associated pump

CHWP-1 1 FTV-4FA 4 in Angle Flanged

ANSI-125 480.0 USgpm 3.0 psi CHWP-1 4300 User-Drive-4x4x8-15 hp Pump (Factory Choice Motor)

CWP-1 1 FTV-6FA 6 in Angle Flanged

ANSI-125 600.0 USgpm 1.3 psi CWP-1 4300 User-Drive-4x4x8-10 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

Operating limits (temperature - pressure)

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi

Maximum temperature: 230 F

Dimensional data (not for construction) www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 7 of 10

PUMP EXHIBIT

Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb

Side view Front view

Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb

Side view Front view

Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 8 of 10

PUMP EXHIBIT

Suction guide

Model: SG (2 to 12 inches)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Design flowrate

Tag Qty Model System Pump Pressure

Drop* Associated pump

CWP-1 1 SG-44 4 in 4 in 600.0 USgpm 2.1 psi CWP-1 4300 User-Drive-4x4x8-10 hp Pump (Factory Choice Motor)

CHWP-1 1 SG-44 4 in 4 in 480.0 USgpm 1.2 psi CHWP-1 4300 User-Drive-4x4x8-15 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

SG-44

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-44

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

SG-44-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 9 of 10

PUMP EXHIBIT

SG-44 Weight: 72 lb

Side view Top view

Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 10 of 10