PUMP_EXHIBIT_20180919_(1).pdf
PDF 248 KB Posted
- Solicitation number
- 47PH1118R0009
About this file
New Pump Exhibit replacing previous version.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| New_SOW_9-20-18.rtf | RTF text file | |
| SOO_Exhibit_Laredo_(1).docx | DOCX document | |
| 09_Pre-Proposal_Record.pdf | ||
| Laredo_RFI_(1).pdf | ||
| SOW_10-17-18.doc | DOC document | |
| C101_The_Agreement.pdf | ||
| C301_GC_Reps_&_Certs.pdf | ||
| Exhibit_I._SOO_Exhibit.pdf | ||
| Exhibit_D.pdf | ||
| Exhibit_F._Gauge_Exhibit.pdf | ||
| Exhibit_B.pdf | ||
| TX235_01-05-18.pdf | ||
| Exhibit_H._PUMP_EXHIBIT.pdf | ||
| Exhibit_A.pdf | ||
| Exhibit_C.pdf | ||
| Exhibit_G._Lighting_Exhibit.pdf | ||
| 47PH1118R0009__Form.pdf | ||
| Exhibit_E.__Cooling_Tower.pdf | ||
| GSA527-15b.pdf | ||
| TX0311__SOW_08-09-2018.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Submittal Ref. #: 602642.1 rev1
Split coupled vertical in line pump
Model: Series 4300 User-Drive-4x4x8-15 hp Pump (Motor supplier: Armstrong choice)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Tag number: CHWP-1 Pipe orientation: Single
Suction pressure: 0 psigService: CHW
Location: CUP Fluid: Non-Potable Fluid - Water
Quantity: 1 Operating temperature: 45 F
Viscosity: 31 SSUDuty flow per pump: 480 USgpm
Specific gravity: 1.0000Duty head: 65 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 15 hp Inverter motor type: Inverter Duty
Frame number: 254TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1840 rpm
Motor Electrics: 460/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 1 of 10
PUMP EXHIBIT
ShaMarCNolen Highlight
Performance curve
--- Admin Data --- Tag Num: CHWP-1 Service: CHW Location: CUP
--- Motor Data --- Motor Size: 15 hp
--- Design Duty Point --- Flow: 480 usgpm Head: 65 ft Impeller: 8.19 in
--- Performance Data ---
• NPSHR: 13.3 ft
• Eff. @ Design: 78.44 %
• BHP @ Design: 10.04 hp
• Mtr Capability @ Rated Spd: 15.00 hp
• %Mtr Safety: 49.34%
• BEP @ Design Imp.:
79.51 % @ 558.7 usgpm
• %max imp. range: 100.00 %
• Outlet Velocity: 12.1 ft/s
• VFD Setting: 62.4 Hz
Series 4300 User-Drive
4x4x8 @ 1840 rpm
0 0.2 0.4 0.6 0.8 1
Flow ( 1,000 usgpm)
Head
(ft)
8.19 in
6.00 in
System
8.19 in
5 hp
7.5 hp
10 hp
15 hp
64%
53%
Water, spgr= 1.0000
PT87-3-0 (3.28.0.1)
ANSI/HI 14.6.3.4 2B
--- Admin Data --- Tag Num: CHWP-1 Service: CHW Location: CUP
--- Motor Data --- Motor Size: 15 hp
--- Design Duty Point --- Flow: 480 usgpm Head: 65 ft Impeller: 8.19 in
--- Control Data ---
1. Hmax @ 62.4 Hz:
• 480 @ 65, 10.04 hp
2. Control (QPC) @ 57.6 Hz:
• 424 @ 56.4, 7.77 hp
3. Control (QPC) @ 52.9 Hz:
• 364.4 @ 48.5, 5.83 hp
4. Control (QPC) @ 48.1 Hz:
• 299.7 @ 41.2, 4.21 hp
5. Control (QPC) @ 43.4 Hz:
• 225.6 @ 34.6, 2.87 hp
6. Index @ 38.4 Hz:
• 120 @ 28.4, 1.72 hp
7. Hmin: 26 ft 36.2 Hz:
• Setting= 40.00% Hmax
Series 4300 User-Drive
4x4x8 @ 8.19 in
0 0.2 0.4 0.6 0.8 1
Flow ( 1,000 usgpm)
Head
(ft)
63.0 Hz62.4 Hz
38.4 Hz
36.2 Hz
18.0 Hz
System
Avg.Load (QPC)
15 hp
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT87-3-0 (3.28.0.1)
ANSI/HI 14.6.3.4 2B
www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 2 of 10
PUMP EXHIBIT
Dimensional data (not for construction)
Top viewSide view
Weight: 533 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 4 9ANSI-125 8 0.6257.5
Outlet 4 9ANSI-125 8 0.6257.5
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options Bearing Current Handling: AEGIS Shaft Ground
Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-44 (516860-021) www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 3 of 10
PUMP EXHIBIT
Split coupled vertical in line pump
Model: Series 4300 User-Drive-4x4x8-10 hp Pump (Motor supplier: Armstrong choice)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Tag number: CWP-1 Pipe orientation: Single
Suction pressure: 5 psigService: CW
Location: CUP Fluid: Non-Potable Fluid - Water
Quantity: 1 Operating temperature: 85 F
Viscosity: 31 SSUDuty flow per pump: 600 USgpm
Specific gravity: 1.0000Duty head: 40 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 10 hp Inverter motor type: Inverter Duty
Frame number: 215TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1727 rpm
Motor Electrics: 460/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 4 of 10
PUMP EXHIBIT
Performance curve
--- Admin Data --- Tag Num: CWP-1 Service: CW Location: CUP
--- Motor Data --- Motor Size: 10 hp
--- Design Duty Point --- Flow: 600 usgpm Head: 40 ft Impeller: 7.85 in
--- Performance Data ---
• NPSHR: 11.7 ft
• Eff. @ Design: 74.31 %
• BHP @ Design: 8.16 hp
• Mtr Capability @ Rated Spd: 9.76 hp
• %Mtr Safety: 19.62%
• BEP @ Design Imp.:
78.84 % @ 478.5 usgpm
• %max imp. range: 84.77 %
• Outlet Velocity: 15.12 ft/s
• VFD Setting: 58.5 Hz
Series 4300 User-Drive
4x4x8 @ 1727 rpm
0 0.2 0.4 0.6 0.8 1
Flow ( 1,000 usgpm)
Head
(ft)
8.19 in
6.00 in
System
7.85 in
5 hp
7.5 hp
10 hp
15 hp
64%
53%
Water, spgr= 1.0000
PT87-3-0 (3.28.0.1)
ANSI/HI 14.6.3.4.1
--- Admin Data --- Tag Num: CWP-1 Service: CW Location: CUP
--- Motor Data --- Motor Size: 10 hp
--- Design Duty Point --- Flow: 600 usgpm Head: 40 ft Impeller: 7.85 in
--- Control Data ---
1. Set Point @ 58.5 Hz:
• 600 @ 40, 8.16 hp
2. Control (CPC) @ 56.6 Hz:
• 543.3 @ 40, 7.16 hp
3. Control (CPC) @ 54.2 Hz:
• 465.4 @ 40, 5.98 hp
4. Control (CPC) @ 52.2 Hz:
• 388.9 @ 40, 5.01 hp
5. Control (CPC) @ 50.2 Hz:
• 296 @ 40, 4.05 hp
6. Index @ 48.0 Hz:
• 150 @ 40, 2.96 hp
7. Hmin: 40 ft 47.1 Hz:
• Setting= 100.00% Hmax
Series 4300 User-Drive
4x4x8 @ 7.85 in
0 0.2 0.4 0.6 0.8 1
Flow ( 1,000 usgpm)
Head
(ft)
63.0 Hz
58.5 Hz
48.0 Hz
47.1 Hz
18.0 Hz
System
Avg.Load (CPC)
10 hp
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT87-3-0 (3.28.0.1)
ANSI/HI 14.6.3.4.1
1 2 3 4 5 6 www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 5 of 10
PUMP EXHIBIT
Top viewSide view
Weight: 443 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 4 9ANSI-125 8 0.6257.5
Outlet 4 9ANSI-125 8 0.6257.5
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options Casing Wear Ring - Bronze CWR Bearing Current Handling: AEGIS Shaft Ground
Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-44 (516860-021) www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 6 of 10
PUMP EXHIBIT
Flo-trex valve
Model: FTV-F (2.5 to 12 inch)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Design flowrate
Tag Qty Model Size Config Flange rating Pressure
Drop* Associated pump
CHWP-1 1 FTV-4FA 4 in Angle Flanged
ANSI-125 480.0 USgpm 3.0 psi CHWP-1 4300 User-Drive-4x4x8-15 hp Pump (Factory Choice Motor)
CWP-1 1 FTV-6FA 6 in Angle Flanged
ANSI-125 600.0 USgpm 1.3 psi CWP-1 4300 User-Drive-4x4x8-10 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
Operating limits (temperature - pressure)
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Maximum pressure: 175 psi
Maximum temperature: 230 F
Dimensional data (not for construction) www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 7 of 10
PUMP EXHIBIT
Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb
Side view Front view
Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb
Side view Front view
Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 8 of 10
PUMP EXHIBIT
Suction guide
Model: SG (2 to 12 inches)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 3/17/2017 12:15:08 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Design flowrate
Tag Qty Model System Pump Pressure
Drop* Associated pump
CWP-1 1 SG-44 4 in 4 in 600.0 USgpm 2.1 psi CWP-1 4300 User-Drive-4x4x8-10 hp Pump (Factory Choice Motor)
CHWP-1 1 SG-44 4 in 4 in 480.0 USgpm 1.2 psi CHWP-1 4300 User-Drive-4x4x8-15 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
SG-44
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-44
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours
Operating limits (temperature - pressure)
SG-44-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 9 of 10
PUMP EXHIBIT
SG-44 Weight: 72 lb
Side view Top view
Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 3/20/2017, Ref. # 602642.1 rev1 Page 10 of 10
PUMP EXHIBIT
| Submittals |
| Submittals |
| Submittals |
| Submittals |
| Suction Guide |
File details come from the government source that posted it.