Exhibit_H._PUMP_EXHIBIT.pdf

PDF 210 KB Posted

Attached to
Replacement of cooling tower & Pumps at Federal Building/Courhouse, Laredo, TX
Solicitation number
47PH1118R0009
Issued by

About this file

Pump

View the file

Other files

File Type Posted
PUMP_EXHIBIT_20180919_(1).pdf PDF
New_SOW_9-20-18.rtf RTF text file
SOO_Exhibit_Laredo_(1).docx DOCX document
09_Pre-Proposal_Record.pdf PDF
Laredo_RFI_(1).pdf PDF
SOW_10-17-18.doc DOC document
C101_The_Agreement.pdf PDF
C301_GC_Reps_&_Certs.pdf PDF
Exhibit_I._SOO_Exhibit.pdf PDF
Exhibit_D.pdf PDF
Exhibit_F._Gauge_Exhibit.pdf PDF
Exhibit_B.pdf PDF
TX235_01-05-18.pdf PDF
Exhibit_A.pdf PDF
Exhibit_C.pdf PDF
Exhibit_G._Lighting_Exhibit.pdf PDF
47PH1118R0009__Form.pdf PDF
Exhibit_E.__Cooling_Tower.pdf PDF
GSA527-15b.pdf PDF
TX0311__SOW_08-09-2018.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Submittal Ref. #: 602642.1 rev2

Split coupled vertical in line pump

Model: Series 4300-6x6x8-15 hp Pump (Motor supplier: Armstrong choice)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Tag number: CWP-1 Pipe orientation: Single

Suction pressure: 5 psigService: CW

Location: Fluid: Non-Potable Fluid - Water

Quantity: 1 Operating temperature: 85 F

Viscosity: 31 SSUDuty flow per pump: 825 USgpm

Specific gravity: 1.0000Duty head: 40 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416

Connections: Inlet: 6 in, Outlet: 6 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type Outside Balanced Rotating face: Resin Bonded Carbon

Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 15 hp Inverter motor type: Inverter Duty

Frame number: 254TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Speed: 1770 rpm

Motor Electrics: 460/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 1 of 10

PUMP EXHIBIT

ShaMarCNolen Highlight

Performance curve

--- Admin Data --- Tag Num: CWP-1 Service: CW Location:

--- Motor Data --- Motor Size: 15 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 825 usgpm Head: 40 ft Impeller: 7.39 in

--- Performance Data ---

• NPSHR: 8.9947 ft

• Eff. @ Design: 78.73 %

• BHP @ Design: 10.58 hp

• Mtr Capability @ Rated Spd: 15 hp

• %Mtr Safety: 41.71%

• BEP @ Design Imp.:

79.22 % @ 896.2 usgpm

• Impeller Max BHP @ Flow:

11.31 hp @ 1205.6 usgpm

• %max imp. range: 52.74 %

• Outlet Velocity: 9.16 ft/s

• VFD Setting: 60.0 Hz

Series 4300

6x6x8 @ 1770 rpm

0 0.4 0.8 1.2 1.6 2

Flow ( 1,000 usgpm)

Head

(ft)

8.19 in

6.50 in

System

7.39 in

7.5 hp

10 hp

15 hp

20 hp

64%

Water, spgr= 1.0000

PT107-1-0 (3.29.0.25)

ANSI/HI 14.6.3.4 2B

--- Admin Data --- Tag Num: CWP-1 Service: CW Location:

--- Motor Data --- Motor Size: 15 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 825 usgpm Head: 40 ft Impeller: 7.39 in

--- System Intersect Data ---

1. System @ 60.0 Hz:

• 825 @ 40, 10.58 hp

2. System @ 51.5 Hz:

• 708.9 @ 29.5, 6.71 hp

3. System @ 43.4 Hz:

• 597 @ 20.9, 4.01 hp

4. System @ 34.9 Hz:

• 480.4 @ 13.6, 2.09 hp

5. System @ 26.4 Hz:

• 363.7 @ 7.7748, 0.91 hp

6. System @ 18.0 Hz:

• 247.6 @ 3.6032, 0.29 hp

Series 4300

6x6x8 @ 7.39 in

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

Flow ( 1,000 usgpm)

Head

(ft)

1858 rpm

1770 rpm

531 rpm

System

1770 rpm

3 hp

5 hp

7.5 hp

10 hp

15 hp

1520 rpm

1280 rpm

1030 rpm

780 rpm

Water, spgr= 1.0000

PT107-1-0 (3.29.0.25)

ANSI/HI 14.6.3.4 2B

www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 2 of 10

PUMP EXHIBIT

Dimensional data (not for construction)

Top viewSide view

Weight: 643 lb

• Not to scale

• R = minimum lifting clearance required above motor

• Units of measure : inches [millimeters]

• Coupling guard and flush line (not shown) are supplied

• Tolerance of ± 0.125 inch (± 3 mm) should be used

• For certified dimensions, please contact your Armstrong representative

• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 6 11ANSI-125 8 0.759.5

Outlet 6 11ANSI-125 8 0.759.5

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

Selected options Pump 50 micron Sediment Filter with Sight Flow Indicator (300 psi) [fif-300] Casing Wear Ring - Bronze CWR Bearing Current Handling: AEGIS Shaft Ground

Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-66 (516860-026) www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 3 of 10

PUMP EXHIBIT

Split coupled vertical in line pump

Model: Series 4300-6x6x10-20 hp Pump (Motor supplier: Armstrong choice)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Tag number: CHWP-1,2 Pipe orientation: Single

Suction pressure: 5 psigService: CHW

Location: Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 85 F

Viscosity: 31 SSUDuty flow per pump: 635 USgpm

Specific gravity: 1.0000Duty head: 70 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416

Connections: Inlet: 6 in, Outlet: 6 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type Outside Balanced Rotating face: Resin Bonded Carbon

Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 20 hp Inverter motor type: Not applicable

Frame number: 256TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Speed: 1780 rpm

Motor Electrics: 460/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 4 of 10

PUMP EXHIBIT

Performance curve

--- Admin Data --- Tag Num: CHWP-1,2 Service: CHW Location:

--- Motor Data --- Motor Size: 20 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 635 usgpm Head: 70 ft Impeller: 9.34 in

--- Performance Data ---

• NPSHR: 10.9 ft

• Eff. @ Design: 79.20 %

• BHP @ Design: 14.17 hp

• Mtr Capability @ Rated Spd: 20 hp

• %Mtr Safety: 41.12%

• BEP @ Design Imp.:

80.14 % @ 575.4 usgpm

• Impeller Max BHP @ Flow:

15.83 hp @ 890.9 usgpm

• %max imp. range: 61.26 %

• Outlet Velocity: 7.05 ft/s

Series 4300

6x6x10 @ 1780 rpm

0 0.2 0.4 0.6 0.8 1 1.2

Flow ( 1,000 usgpm)

Head

(ft)

10.19 in

8.00 in

System

9.34 in

7.5 hp 10 hp

15 hp

20 hp

25 hp

5 hp

Water, spgr= 1.0000

PT104-2-0 (3.29.0.25)

ANSI/HI 14.6.3.4 2B

Dimensional data (not for construction)

Top viewSide view

Weight: 729 lb

• Not to scale

• R = minimum lifting clearance required above motor

• Units of measure : inches [millimeters]

• Coupling guard and flush line (not shown) are supplied

• Tolerance of ± 0.125 inch (± 3 mm) should be used

• For certified dimensions, please contact your Armstrong representative

• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 5 of 10

PUMP EXHIBIT

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 6 11ANSI-125 8 0.759.5

Outlet 6 11ANSI-125 8 0.759.5

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007

Selected options Bearing Current Handling: Armstrong Choice Shaft Ground

Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-66 (516860-026) www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 6 of 10

PUMP EXHIBIT

Flo-trex valve

Model: FTV-F (2.5 to 12 inch)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Design flowrate

Tag Qty Model Size Config Flange rating Pressure

Drop* Associated pump

CWP-1 1 FTV-6FA 6 in Angle Flanged

ANSI-125 825.0 USgpm 1.6 psi CWP-1 4300-6x6x8-15 hp Pump (Factory Choice Motor)

CHWP-1,2 2 FTV-6FA 6 in Angle Flanged

ANSI-125 635.0 USgpm 1.4 psi CHWP-1,2 4300-6x6x10-20 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

Operating limits (temperature - pressure)

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi

Maximum temperature: 230 F

Dimensional data (not for construction) www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 7 of 10

PUMP EXHIBIT

Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb

Side view Front view

Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 8 of 10

PUMP EXHIBIT

Suction guide

Model: SG (2 to 12 inches)

Project name: GSA Laredo

Location: Representative: Texas Air Systems LLC DFW

Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080

Engineer: e-mail: michael.cingrani@texasairsystems.com

Contractor: Submitted by: Michael Cingrani

Application design data

Design flowrate

Tag Qty Model System Pump Pressure

Drop* Associated pump

CHWP-1,2 2 SG-66 6 in 6 in 635.0 USgpm 0.5 psi CHWP-1,2 4300-6x6x10-20 hp Pump (Factory Choice Motor)

CWP-1 1 SG-66 6 in 6 in 825.0 USgpm 0.9 psi CWP-1 4300-6x6x8-15 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

SG-66

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-66

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

SG-66-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 9 of 10

PUMP EXHIBIT

Dimensional data (not for construction)

SG-66 Weight: 141 lb

Side view Top view

Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 10 of 10

PUMP EXHIBIT

Submittals
Submittals
Submittals
Submittals
Suction Guide