Exhibit_H._PUMP_EXHIBIT.pdf
PDF 210 KB Posted
- Solicitation number
- 47PH1118R0009
About this file
Pump
View the file
Other files
| File | Type | Posted |
|---|---|---|
| PUMP_EXHIBIT_20180919_(1).pdf | ||
| New_SOW_9-20-18.rtf | RTF text file | |
| SOO_Exhibit_Laredo_(1).docx | DOCX document | |
| 09_Pre-Proposal_Record.pdf | ||
| Laredo_RFI_(1).pdf | ||
| SOW_10-17-18.doc | DOC document | |
| C101_The_Agreement.pdf | ||
| C301_GC_Reps_&_Certs.pdf | ||
| Exhibit_I._SOO_Exhibit.pdf | ||
| Exhibit_D.pdf | ||
| Exhibit_F._Gauge_Exhibit.pdf | ||
| Exhibit_B.pdf | ||
| TX235_01-05-18.pdf | ||
| Exhibit_A.pdf | ||
| Exhibit_C.pdf | ||
| Exhibit_G._Lighting_Exhibit.pdf | ||
| 47PH1118R0009__Form.pdf | ||
| Exhibit_E.__Cooling_Tower.pdf | ||
| GSA527-15b.pdf | ||
| TX0311__SOW_08-09-2018.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Submittal Ref. #: 602642.1 rev2
Split coupled vertical in line pump
Model: Series 4300-6x6x8-15 hp Pump (Motor supplier: Armstrong choice)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Tag number: CWP-1 Pipe orientation: Single
Suction pressure: 5 psigService: CW
Location: Fluid: Non-Potable Fluid - Water
Quantity: 1 Operating temperature: 85 F
Viscosity: 31 SSUDuty flow per pump: 825 USgpm
Specific gravity: 1.0000Duty head: 40 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 6 in, Outlet: 6 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 15 hp Inverter motor type: Inverter Duty
Frame number: 254TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1770 rpm
Motor Electrics: 460/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 1 of 10
PUMP EXHIBIT
ShaMarCNolen Highlight
Performance curve
--- Admin Data --- Tag Num: CWP-1 Service: CW Location:
--- Motor Data --- Motor Size: 15 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 825 usgpm Head: 40 ft Impeller: 7.39 in
--- Performance Data ---
• NPSHR: 8.9947 ft
• Eff. @ Design: 78.73 %
• BHP @ Design: 10.58 hp
• Mtr Capability @ Rated Spd: 15 hp
• %Mtr Safety: 41.71%
• BEP @ Design Imp.:
79.22 % @ 896.2 usgpm
• Impeller Max BHP @ Flow:
11.31 hp @ 1205.6 usgpm
• %max imp. range: 52.74 %
• Outlet Velocity: 9.16 ft/s
• VFD Setting: 60.0 Hz
Series 4300
6x6x8 @ 1770 rpm
0 0.4 0.8 1.2 1.6 2
Flow ( 1,000 usgpm)
Head
(ft)
8.19 in
6.50 in
System
7.39 in
7.5 hp
10 hp
15 hp
20 hp
64%
Water, spgr= 1.0000
PT107-1-0 (3.29.0.25)
ANSI/HI 14.6.3.4 2B
--- Admin Data --- Tag Num: CWP-1 Service: CW Location:
--- Motor Data --- Motor Size: 15 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 825 usgpm Head: 40 ft Impeller: 7.39 in
--- System Intersect Data ---
1. System @ 60.0 Hz:
• 825 @ 40, 10.58 hp
2. System @ 51.5 Hz:
• 708.9 @ 29.5, 6.71 hp
3. System @ 43.4 Hz:
• 597 @ 20.9, 4.01 hp
4. System @ 34.9 Hz:
• 480.4 @ 13.6, 2.09 hp
5. System @ 26.4 Hz:
• 363.7 @ 7.7748, 0.91 hp
6. System @ 18.0 Hz:
• 247.6 @ 3.6032, 0.29 hp
Series 4300
6x6x8 @ 7.39 in
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
Flow ( 1,000 usgpm)
Head
(ft)
1858 rpm
1770 rpm
531 rpm
System
1770 rpm
3 hp
5 hp
7.5 hp
10 hp
15 hp
1520 rpm
1280 rpm
1030 rpm
780 rpm
Water, spgr= 1.0000
PT107-1-0 (3.29.0.25)
ANSI/HI 14.6.3.4 2B
www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 2 of 10
PUMP EXHIBIT
Dimensional data (not for construction)
Top viewSide view
Weight: 643 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 6 11ANSI-125 8 0.759.5
Outlet 6 11ANSI-125 8 0.759.5
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
Selected options Pump 50 micron Sediment Filter with Sight Flow Indicator (300 psi) [fif-300] Casing Wear Ring - Bronze CWR Bearing Current Handling: AEGIS Shaft Ground
Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-66 (516860-026) www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 3 of 10
PUMP EXHIBIT
Split coupled vertical in line pump
Model: Series 4300-6x6x10-20 hp Pump (Motor supplier: Armstrong choice)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Tag number: CHWP-1,2 Pipe orientation: Single
Suction pressure: 5 psigService: CHW
Location: Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 85 F
Viscosity: 31 SSUDuty flow per pump: 635 USgpm
Specific gravity: 1.0000Duty head: 70 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 6 in, Outlet: 6 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 20 hp Inverter motor type: Not applicable
Frame number: 256TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1780 rpm
Motor Electrics: 460/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 4 of 10
PUMP EXHIBIT
Performance curve
--- Admin Data --- Tag Num: CHWP-1,2 Service: CHW Location:
--- Motor Data --- Motor Size: 20 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 635 usgpm Head: 70 ft Impeller: 9.34 in
--- Performance Data ---
• NPSHR: 10.9 ft
• Eff. @ Design: 79.20 %
• BHP @ Design: 14.17 hp
• Mtr Capability @ Rated Spd: 20 hp
• %Mtr Safety: 41.12%
• BEP @ Design Imp.:
80.14 % @ 575.4 usgpm
• Impeller Max BHP @ Flow:
15.83 hp @ 890.9 usgpm
• %max imp. range: 61.26 %
• Outlet Velocity: 7.05 ft/s
Series 4300
6x6x10 @ 1780 rpm
0 0.2 0.4 0.6 0.8 1 1.2
Flow ( 1,000 usgpm)
Head
(ft)
10.19 in
8.00 in
System
9.34 in
7.5 hp 10 hp
15 hp
20 hp
25 hp
5 hp
Water, spgr= 1.0000
PT104-2-0 (3.29.0.25)
ANSI/HI 14.6.3.4 2B
Dimensional data (not for construction)
Top viewSide view
Weight: 729 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 5 of 10
PUMP EXHIBIT
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 6 11ANSI-125 8 0.759.5
Outlet 6 11ANSI-125 8 0.759.5
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007
Selected options Bearing Current Handling: Armstrong Choice Shaft Ground
Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-66 (516860-026) www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 6 of 10
PUMP EXHIBIT
Flo-trex valve
Model: FTV-F (2.5 to 12 inch)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Design flowrate
Tag Qty Model Size Config Flange rating Pressure
Drop* Associated pump
CWP-1 1 FTV-6FA 6 in Angle Flanged
ANSI-125 825.0 USgpm 1.6 psi CWP-1 4300-6x6x8-15 hp Pump (Factory Choice Motor)
CHWP-1,2 2 FTV-6FA 6 in Angle Flanged
ANSI-125 635.0 USgpm 1.4 psi CHWP-1,2 4300-6x6x10-20 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
Operating limits (temperature - pressure)
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Maximum pressure: 175 psi
Maximum temperature: 230 F
Dimensional data (not for construction) www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 7 of 10
PUMP EXHIBIT
Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb
Side view Front view
Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 8 of 10
PUMP EXHIBIT
Suction guide
Model: SG (2 to 12 inches)
Project name: GSA Laredo
Location: Representative: Texas Air Systems LLC DFW
Date submitted: 8/31/2017 4:04:39 PM Phone number: 972-652-3080
Engineer: e-mail: michael.cingrani@texasairsystems.com
Contractor: Submitted by: Michael Cingrani
Application design data
Design flowrate
Tag Qty Model System Pump Pressure
Drop* Associated pump
CHWP-1,2 2 SG-66 6 in 6 in 635.0 USgpm 0.5 psi CHWP-1,2 4300-6x6x10-20 hp Pump (Factory Choice Motor)
CWP-1 1 SG-66 6 in 6 in 825.0 USgpm 0.9 psi CWP-1 4300-6x6x8-15 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
SG-66
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-66
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours
Operating limits (temperature - pressure)
SG-66-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 9 of 10
PUMP EXHIBIT
Dimensional data (not for construction)
SG-66 Weight: 141 lb
Side view Top view
Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 8/31/2017, Ref. # 602642.1 rev2 Page 10 of 10
PUMP EXHIBIT