Laredo_RFI_(1).pdf

PDF 95 KB Posted

Attached to
Replacement of cooling tower & Pumps at Federal Building/Courhouse, Laredo, TX
Solicitation number
47PH1118R0009
Issued by

About this file

Contractor questions with Government responses.

View the file

Other files

File Type Posted
PUMP_EXHIBIT_20180919_(1).pdf PDF
New_SOW_9-20-18.rtf RTF text file
SOO_Exhibit_Laredo_(1).docx DOCX document
09_Pre-Proposal_Record.pdf PDF
SOW_10-17-18.doc DOC document
C101_The_Agreement.pdf PDF
C301_GC_Reps_&_Certs.pdf PDF
Exhibit_I._SOO_Exhibit.pdf PDF
Exhibit_D.pdf PDF
Exhibit_F._Gauge_Exhibit.pdf PDF
Exhibit_B.pdf PDF
TX235_01-05-18.pdf PDF
Exhibit_H._PUMP_EXHIBIT.pdf PDF
Exhibit_A.pdf PDF
Exhibit_C.pdf PDF
Exhibit_G._Lighting_Exhibit.pdf PDF
47PH1118R0009__Form.pdf PDF
Exhibit_E.__Cooling_Tower.pdf PDF
GSA527-15b.pdf PDF
TX0311__SOW_08-09-2018.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

47PH1118R0009 - Laredo Cooling Tower

During the site visit, it was stated via phone that the magnitude of this project is between $500,000 - $1,000,000. On the Fedbizopps, it says $250,000 - $500,000. Which is the correct magnitude for this solicitation? The magnitude is $250,000-$500,000. Refer to the FBO solicitation.

Who is the current provider for the existing DDC/BAS system for this facility? David Morris Performance Controls Group, LLC.

24044 Cinco Village Center Blvd. Suite 100 Katy, TX 77494 o 713.559.6999 f 281.547.6001 c 281.900.9808 dmorris@performancecontrolsgroup.com David.morris@gsa.gov

Where are the cooling tower VFD's to be installed? Indoor/Outdoor? NEMA rating?

Inside the chiller mechanical room. Indoor NEMA 1

Who is the current provider for the central plant chemical treatment & maintenance?

WTS is the current sub.

In reference to the Fan Coil units:

Are these to be single wall or double wall construction? Double Wall. Please provide specifications. Specifications are in the solicitation.

This is calling for a 24/7 Time Clock.

Would it be acceptable to substitute for a 7 day programmable thermostat? Yes Insulate supply air duct?Yes Internal or external? External Insulation type, density, thickness/r-value? Duct Board 1.5 Inch! Density 70Kg/m3! Minimum R 4 r value

During the walk-thru it was noticed that the condenser water lines to the cooling tower were insulated? Is it required the new piping be Insulated? No

Would it be acceptable to use Aquatherm SDR-17.6 PP-R resin (Fusiolen) for piping sizes 2.5"> and type-L copper/pro-press for 2"<? No! Copper tubing will be permitted for the cooling tower makeup water line. Steel pipe will be required for condenser water lines and chilled water lines.

https://www.fbo.gov/index?s=opportunity&mode=form&id=5f1102820ea990fcc4f179361e52d9be&tab=core&_cview=0 https://maps.google.com/?q=24044+Cinco+Village+Center+Blvd.+Suite+100+Katy,+TX+77494&entry=gmail&source=g https://maps.google.com/?q=24044+Cinco+Village+Center+Blvd.+Suite+100+Katy,+TX+77494&entry=gmail&source=g

47PH1118R0009 - Laredo Cooling Tower https://www.fbo.gov/index?s=opportunity&mode=form&id=5f1102820ea990fcc4f179361e52d9be&tab=core&_cview=0