Amendment 03.pdf

PDF 5 MB Posted

Attached to
Emergency Generator and Fire Pump Replacement Federal contract opportunity
Solicitation number
47PF0022R0090
Issued by
General Services Administration Public Buildings Service Region 5

About this file

This federal contract opportunity notice seeks a contractor to replace the emergency generator and fire pump at the Walter H. Rice Federal Building and U.S. Courthouse in Dayton, Ohio. The scope of work includes replacing the existing diesel generator with a new 500 kW natural gas generator and replacing the existing fire pump. The construction cost estimate ranges from $1 million to $3.375 million. The performance period is 275 calendar days from the on-site notice to proceed. The NAICS code is 236220 with a small business size standard of $39.5 million. A pre-proposal conference will be held on August 29, 2022. Proposals are due by September 30, 2022. The soliciting agency is the General Services Administration Public Buildings Service Region 5.

View the file

Other files for this federal contract opportunity

Other files attached to Emergency Generator and Fire Pump Replacement, newest first.
File Type Posted
Amendment 05.pdf PDF
Amendment 04.pdf PDF
Amendment 02.pdf PDF
2022 08 29 Pre-Poposal Sign-In Sheet.pdf PDF
Updates Description for Bid Adddendum 1.pdf PDF
Bid Addendum 1 - Revised Specs.pdf PDF
Amendment 01.pdf PDF
47PF0022R0090_Rice GEN and FP.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: is required to sign this document and return copies to the issuing office.Contractor is not

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NUMBER 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

R10A. MODIFICATION OF CONTRACT/ORDER NUMBE

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

is not extended.The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

PAGE OF PAGES

CODE6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

R5 AMD Southern Construction Contracting Team 230 S. Dearborn St.

Room 3500 Chicago, IL 60604 USA

R5 AMD Southern Construction Contracting Team 230 S. Dearborn St.

Room 3500 Chicago, IL 60604 USA

47PF0022R0090

1 1

09/21/2022

08/18/2022

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

Amendment 03, Solicitation 47PF0022R0090 Emergency Generator and Fire Pump Replacement Walter H. Rice Federal Building and U.S. Courthouse, 200 West 2nd Street, Dayton, Ohio 45402

Amendment 03 is hereby issued to 1) address all RFI's to date, 2) revise the SF1442 and incorporate a pricing breakdown form, 3) issue bid addendum #2 with drawing updates, 4) incorporate Section 012000 - Allowances, and 5) extend the due date/time to 4:00 PM CDT on 9/30/2022. You must acknowledge receipt of this and all amendments.

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

Responses to All RFI’s

RFP 47PF0022R0090

Emergency Generator and Fire Pump Replacement

Walter H. Rice Federal Building and U.S. Courthouse 200 West 2nd Street, Dayton, Ohio

1) Is the project funded?

Response: Yes; The project is funded.

2) Who is the GSA’s elevator maintenance vendor and contact info? At the pre-bid it was mentioned the vendor listed in the solicitation is not the current vendor.

Response:

The Murphy Elevator Company 800-752-6075 | service@murphyelevator.com

3) Please provide a roof insulation and membrane specification.

Response: The scope of work only entails the existing shed and not the main building roof.

4) Please provide a detail of the existing roof construction.

Response: The scope of work only entails the existing shed and not the main building roof.

5) E-1-2

Note #14 calls for supplying a 150A disconnect switch while the single line diagram (E-2-3 Note #14) calls for supplying a 150A disconnect switch.

Response: The contractor is to supply and install all disconnect switches.

6) E-2-3 Single Line Diagram There are multiple transformer feeds calling for a 4-wire feed. Can the feeds to the transformers be 3-wire?

Response: Yes, the feeds to the transformers can be 3-wire.

Cable schedule calls for #8 conductors for a 100A feed. Should these be #3 conductors?

Response: Yes, use #3 AWG conductors.

Single Line Diagram calls for a 400A feed to ATS-RSB which is rated at 200A.

Response: Revise ATS from 200A to 400A.

7) E-2-4 (Single Line)

Note #2 calls for transformer T-P-PNL to be a 75KVA. Sheet E-1-3 calls for a 45KVA.

Response: New panel P-PNL is a 100A panel. 45KVA transformer is sufficient.

8) The drawings identify 200-square feet of Spray-on Fire Proofing in Room B10 on the north wall near air handling units. The pipe end sealant on insulated piping, pipe wrap on insulated piping throughout;

white sealant on insulated duct work throughout and finish top coat in Jury Room 910C are called out.

In regards to throughout, are all the materials identified to be abated? A quantity for the fire proofing was provided, but nothing else. Is there other ACM to be abated besides the fire proofing?

Response:

Abatement is not required if areas identified in the hazardous materials report as hazardous are not disturbed or affected during construction. Please review the hazardous materials report for a list of these areas.

9) Drawing A-1-01 Partial Demolition Plan First Floor Level, MD-1-1 Generator Demolition Plan –

Basement; FP-0-1 – Hazardous Material Report; and FPD-1-1 and FPD-2-1 Basement Fire Protection Plan all possibly include areas where the fire proofing, pipe insulation and/or end cap materials may need addressed. But nothing is specifically called out. Can you please clarify the scope of the abatement?

Response:

Abatement is not required if areas identified in the hazardous materials report as hazardous are not disturbed or affected during construction. Please review the hazardous materials report for a list of these areas.

10) Drawings E-1-2 and E-2-9 have missing information. On E-1-2 there are arrows with no notes and E-

2-9 has coded notes in which the tail ends of the sentences are cut off. Can you please forward corrected drawings?

Response:

Will adjust columns in coded note list, sheet E-2-9 & replot. Sheet E-1-2, Please verify you are referencing the latest drawing revision: “100% REVISED CONSTRUCTION DOCUMENTS” issued 07/15/2022. All leaders on drawing E-1-2 have accompanying annotations.

11) 3.4 – The alternator shall support 1020 sKVA with a maximum voltage dip of 30% - Could you please bump this value up to 1,720 minimum sKAVA value at 30%?

Response:

The specifications will be revised with a future bid amendment. Please refer to the revised specifications once issued.

Updated Note: There are no changes to the specification section.

12) 3.6 - The alternator shall meet temperature rise standards of UL2200 (120 degrees C). The insulation system material shall be class "H" capable of withstanding 150 degrees C temperature rise. – With a temp rise so high, the generator life will be decreased and run VERY HOT – CAT NG generator will be 105 degrees which will lengthen the life of the generator and run cooler.

Response:

The specifications will be revised with a future bid amendment. Please refer to the revised

13) 5.1 - The UL2200 approved generator package shall incorporate four (4) factory installed circuit breakers. Three of the breaker shall be 80% rated LSI electronic (600, 400 and 200 amp). The fourth breaker will be 800amp thermal magnetic for load banking purposes. The 400amp breaker is for future use. Distributor or field installed breakers are not acceptable. All line side connections are to be factory installed. Output lugs shall be provided for load side connections. – We can’t provide or have space for four breakers inside of the generator. Could we supply the three way breaker provided by Trystar in the attachment? This will suffice the breakers as well as the loadbank and generator docking station as per the intent of the spec.

Response:

The specifications will be revised with a future bid amendment. Please refer to the revised

14) 7.3A – Supplier of the Genset and associated items shall have permanent service facilities in this trade area. These facilities shall comprise a permanent force of factory trained service personnel on 24 hour call, experienced in servicing this type of equipment, providing warranty and routine maintenance service to afford the owner maximum protection. Delegation of this service responsibility for any of the equipment listed herein will not be considered fulfillment of these specifications. Service contracts shall also be available. – Suggestion to have the service company be located less than 25 miles from the Dayton RICE building for immediate response and have a 24x7X365 call availability.

Response:

The specifications will be revised with a future bid amendment. Please refer to the revised

15) 7.4A - The standby electric generating system components, complete genset and instrumentation panel shall be warranted by the manufacturer against defective materials and factory workmanship for a period of ten (10) years. Such defective parts shall be repaired or replaced at the manufacturer's option, free of charge for parts, labor and travel. – Suggestion to detail the coverage to have the “as shipped consist” as well as rental units available if the issue or parts can’t be located to repair the generator – Similar to the Platinum and Platinum Plus warranty which is attached.

Response:

The specifications will be revised with a future bid amendment. Please refer to the revised

16) Who is the fire protection contractor that performed the most recent upgrades to the fire alarm system?

Response:

Madison Services, Inc.

2833 Lincoln Street, Suite #02. Highland, IN 46322

17) General Note 1 on Sheet M-1-2 directs the contractor to receive pricing from Center Point Energy Company for removal of existing meter and installation of new meter. Center Point Energy Company has indicated that only the account holder may request this information. Please provide direction or an allowance value that can be incorporated into pricing submitted.

Response:

Provide a $45,000 allowance.

18) Note 20 on Sheet MD-1-1 directs the contractor to remove existing energy monitoring device and store for re-installation as shown in plans. This device is scheduled for re-installation per note 9 on sheet M- 1-2. Note 10 on Sheet M-1-2 also calls for a new matching energy monitoring device to be installed on new piping. Please provide make/model information on existing device to be reinstalled.

Response: See following photos.

19) Summary 011000 1.5 K notes “Contractor shall coordinate and contract and pay for all O&M personnel to be on-site for training and shutdowns as required to comply with GSA, local fire department, etc.

requirements.” Given the extent of services required is unknown, and hourly rates as well as O&M protocol for providing said services is unavailable, please provide an allowance value for all bidders to carry.

Response:

Refer to the new specification section 012100 Allowances.

20) Section 011400 Work Restrictions section 1.2.C states work in the basement shall occur during Government occupied hours. Section 1.2.D.2 implies that work shall occur during Government unoccupied hours while U.S. Courts are in session. Please reconfirm 1.2.C general working hours;

work in the basement shall occur during Government occupied hours and that other work inside the building but not in the basement shall occur during Government unoccupied hours.

Response:

All work that is noisy shall be done after building occupied hours. All work in the basement may be performed during normal building occupied hours. All work not in the basement shall be done after normal building occupied hours.

21) Please confirm non disruptive work in mechanical areas of the facility, to include the basement, as well as mechanical/electrical closets on various floors, and at the roof/Penthouse level can occur during Government occupied hours.

Response:

All work that is noisy shall be done after building occupied hours. All work in the basement may be performed during normal building occupied hours. All work not in the basement shall be done after normal building occupied hours.

22) Section 013525 Fire Prevention & Protection in Construction, Alteration, and Demolition Projects item 3.1.E 1 notes “Contractor is responsible for costs of shutdowns including assistance by the building O&M service contractor.” Given the extent of services required is unknown, and hourly rates as well as O&M protocol for providing said services is unavailable, please provide an allowance value for all bidders to carry.

Response:

Refer to the new specification section 012100 Allowances.

23) RFI Clarification:

The intent of the work on the shed is to shorten it so that the new generator and pad can fit in front of it with the required clearances and not impact the parking lot. The work involves removing the existing wall/door and a portion of the shed roof via saw cutting. Then, construct a new wall/door to create a shorter storage building under the existing roof.

(See ).

SOLICITATION, OFFER,

AND AWARD

(Construction, Alteration, or Repair) IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.

9. FOR INFORMATION

CALL:

NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid and "bidder".

SOLICITATION

1. SOLICITATION NUMBER

5. REQUISITION/PURCHASE REQUEST NUMBER

CODE

6. PROJECT NUMBER

8. ADDRESS OFFER TO

4. CONTRACT NUMBER

7. ISSUED BY

10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS (Title, identifying number, date)

11. The contractor shall begin performance within

12a. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?

(If "YES", indicate within how many calendar days after award in Item 12b.)

d. Offers providing less than

STANDARD FORM 1442 (REV. 8/2014)

Prescribed by GSA - FAR (48 CFR) 53.236-1(d) calendar days for Government acceptance after the date offers are due will not be considered and will be rejected.

award, YES NO notice to proceed. This performance period is mandatory negotiable.

calendar days and complete it within calendar days after receiving

a. NAME b. TELEPHONE NUMBER (Include area code) (NO COLLECT CALLS)

12b. CALENDAR DAYS

2. TYPE OF SOLICITATION

SEALED BID (IFB)

NEGOTIATED (RFP)

3. DATE ISSUED PAGE OF PAGES

13. ADDITIONAL SOLICITATION REQUIREMENTS:

a. Sealed offers in original and copies to perform the work required are due at the place specified in Item 8 by (hour) Central time (date). If this is a sealed bid solicitation, offers will be publicly opened at that time. Sealed envelopes containing offers shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.

b. An offer guarantee is, is not required.

c. All offers are subject to the (1) work requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.

17. The offeror agrees to perform the work required at the prices specified below in strict accordance with the terms of this solicitation, if this offer is accepted calendar days after the date offers are due. (Insert any number equal to or greater than the minimum requirement by the Government in writing within stated in Item 13d. Failure to insert any number means the offeror accepts the minimum in Item 13d.)

OFFER (Must be fully completed by offeror)

AMOUNTS

18. The offeror agrees to furnish any required performance and payment bonds.

19. ACKNOWLEDGMENT OF AMENDMENTS

(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)

AMENDMENT

NUMBER

DATE.

AWARD (To be completed by Government)

CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE

14. NAME AND ADDRESS OF OFFEROR (Include ZIP Code)

CODE FACILITY CODE

15. TELEPHONE NUMBER (Include area code)

16. REMITTANCE ADDRESS (Include only if different than Item 14.)

20a. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN OFFER (Type or print)

21. ITEMS ACCEPTED:

22. AMOUNT

26. ADMINISTERED BY

30a. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED TO SIGN (Type or print)

31c. DATE

STANDARD FORM 1442 (REV. 8/2014) BACK

31b. UNITED STATES OF AMERICA

BY

31a. NAME OF CONTRACTING OFFICER (Type or print)

29. AWARD (Contractor is not required to sign this document.) Your offer on this solicitation is hereby accepted as to the items listed. This award consummates the contract, which consists of (a) the Government solicitation and your offer, and (b) this contract award. No further contractual document is necessary.

30b. SIGNATURE 30c. DATE

28. NEGOTIATED AGREEMENT (Contractor is required to sign this document and return and deliver all items or perform all work requirements identified on this form and any continuation sheets for the consideration stated in this contract. The rights and obligations of the parties to this contract shall be governed by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certifications, and specifications incorporated by reference in or attached to this contract.

copies to issuing office.) Contractor agrees to furnish

24. SUBMIT INVOICES TO ADDRESS SHOWN IN

(4 copies unless otherwise specified)

23. ACCOUNTING AND APPROPRIATION DATA

ITEM 25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO

27. PAYMENT WILL BE MADE BY

10 U.S.C. 2304(c) ( ) 41 U.S.C. 3304(a) ( )

20b. SIGNATURE 20c. OFFER DATE

CLINS DESCRIPTION PRICE

BASE $

ALLOWANCE 01 $

ALLOWANCE 02 $

TOTAL CONTRACT PRICE (Sum of CLINS 0001, 0002 & 0003) $

Company Name:

Authorized Signature:

Date:

PRICE BREAKDOWN - EMERGENCY GENERATOR AND FIRE PUMP REPLACEMENT

The Contractor, having examined the scope of work, plans, specifications and site conditions of the proposed work, hereby proposes to furnish all materials, labor, supplies and supervision to complete the proposed project per contract documents for the total sum stated.

CONTRACTOR INFORMATION

EMERGENCY GENERATOR AND FIRE PUMP REPLACEMENT PCNEPM52751

WALTER H RICE FEDERAL BUILDING, DAYTON OH BID ADDENDUM #2

ALLOWANCES 012100 - 1

PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICIAL USE ONLY

Do not remove this notice – Properly destroy documents when no longer needed

SECTION 012100 - ALLOWANCES

PART 1 - GENERAL

RELATED DOCUMENTS

A. The Government is providing the references included in this sub-section for information purposes only and is not intended to provide a comprehensive, all-inclusive list of any and all potentially relevant portions of the Contract Documents. Drawings and general provisions of the Contract, including Federal Acquisition Regulations (FAR) and General Services Administration Acquisition Regulations (GSAR) contract clauses, and other Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes administrative and procedural requirements governing allowances.

1. Certain items are described in the Contract Documents as allowance items. The purpose of allowance items is to defer selection of actual products and systems to a later date when direction will be provided to the Contractor. The Contracting Officer will issue Modifications to incorporate allowance items in the Work after actual products and systems have been determined.

B. Types of allowance items may include the following :

1. Lump-sum allowance items.

2. Unit-price allowance items.

3. Quantity allowance items.

1.3 SELECTION AND PURCHASE

A. At the earliest practical date after award of the Contract, advise the contracting officer of the date when final selection and purchase of each product or system described by an allowance item must be completed to avoid delaying the Work. Allowances must be included in all schedule submissions

1.4 ACTION SUBMITTALS

A. Submit proposals for products or systems described by allowance items in the form specified for Change Orders.

1.5 INFORMATIONAL SUBMITTALS

A. Submit copies of invoices or delivery slips to show actual quantities of materials delivered to the site for use in fulfillment of each unit-price and quantity allowance item.

ALLOWANCES 012100 - 2

Do not remove this notice – Properly destroy documents when no longer needed

B. Coordinate and process submittals for allowance items in same manner as for other portions of the Work.

1.6 COORDINATION

A. Coordinate allowance items with other portions of the Work. Furnish templates as required to coordinate installation.

B. Modifications based on an allowance item shall include cost to Contractor of specific products and systems selected by the contracting officer under allowance and shall include taxes, freight, delivery to Project site, Contractor's costs for receiving and handling at Project site, labor, installation, overhead, and profit.

1. If requested by the contracting officer, purchase additional quantities under unit-price or quantity allowances and prepare unused material for storage by Contracting officer. Deliver unused material to Contracting officer's storage space as directed.

1.7 ADJUSTMENT OF ALLOWANCE ITEMS

A. Modifications to an allowance item shall comply with the changes clauses and any other contract modifications procedures found in the Contract Documents.

B. Contracting officer reserves the right to establish the quantity of work-in-place by independent quantity survey, measure, or count.

PART 2 - PRODUCTS (Not Used)

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine products covered by an allowance item promptly on delivery for damage or defects. Return damaged or defective products to manufacturer for replacement.

3.2 PREPARATION

A. Coordinate materials and their installation for each allowance item with related materials and installations to ensure that each allowance item is completely integrated and interfaced with related work.

ALLOWANCES 012100 - 3

Do not remove this notice – Properly destroy documents when no longer needed

3.3 SCHEDULE OF ALLOWANCE ITEMS

A. Allowance Item No. 01: General Note 1 on Sheet M-1-2 directs the contractor to receive pricing from Center Point Energy Company for removal of existing meter and installation of new meter. Lump Sum Allowance (not to exceed): $45,000.00.

B. Allowance Item No. 02: Summary 011000 1.5 K notes “Contractor shall coordinate and contract and pay for all O&M personnel to be on-site for training and shutdowns as required to comply with GSA, local fire department, etc. requirements.” Section 013525 Fire Prevention & Protection in Construction, Alteration, and Demolition Projects item 3.1.E 1 notes “Contractor is responsible for costs of shutdowns including assistance by the building O&M service contractor.” Lump Sum Allowance (not to exceed):

$10,000.00.

END OF SECTION 012100

GSA EMERGENCY GENERATOR AND FIRE PUMP REPLACEMENT

WALTER H RICE FEDERAL BUILDING, DAYTON OH

PCNEPM52751

BID ADDENDUM #2

Updates to documents for BID ADDENDUM #2 submission. 1

Do not remove this notice – Properly destroy documents when no longer needed

UPDATES TO DOCUMENTS FOR BID ADDENDUM #2

September 16, 2022

The following sheets have been updated.

MECHANICAL

1. Drawing MD-1-1

a. Coded notes updated.

2. Drawing M-1-1

a. Coded noted updated.

3. Drawing M-2-1

a. Unchanged

ELECTRICAL

4. Drawing E-0-1

a. Unchanged

5. Drawing ED-1-1

a. Update to basement fire protection demolition plan callouts

b. Update demo note

6. Drawing E-1-1

a. Add note to generator footprint detail

7. Drawing E-1-2

a. Revised coded note 14

8. Drawing E-2-3

a. Revised new transformers to show 3-wire primary

9. Drawing E-2-4

a. Revised new transformers to show 3-wire primary

b. Revised transformer to 45kVA

10. Drawing E-2-9

a. Revised RSB ATS switch from 200A to 400A

FIRE PROTECTION

11. Drawing FP-0-1

a. Unchanged

12. Drawing FPD-1-1

a. Update to basement fire protection demolition plan callouts

b. Update to cross connection detail

i. Update demo plan to reflect removal of inaccurate pipes

ii. Update detail callouts

GSA EMERGENCY GENERATOR AND FIRE PUMP REPLACEMENT

WALTER H RICE FEDERAL BUILDING, DAYTON OH

PCNEPM52751

BID ADDENDUM #2

Updates to documents for BID ADDENDUM #2 submission. 2

Do not remove this notice – Properly destroy documents when no longer needed

13. Drawing FPD-2-1

a. New detail added to sheet

i. Include new pipe demo schematic

ii. Modify basement fire protection demolition plan to reflect demo schematic

b. Update to basement fire protection demolition plan callouts

c. Update to coded notes

14. Drawing FP-1-1

a. Update to basement fire protection plan callouts

b. Add cross connection detail

i. Update demo plan to reflect removal of inaccurate pipes

ii. Update detail callouts

15. Drawing FP-2-1

a. New detail added to sheet

i. Include new pipe demo schematic

ii. Modify basement fire protection plan to reflect demo schematic

b. Update to basement fire protection plan callouts

c. Update to coded notes

16. Drawing FP-3-1

a. Update to fire protection schematic

17. Added specification section 012100 Allowances.

END OF SECTION

MECH.

B13

DN

STORAGE

SHED

MECH.

B11

R M

G 3PSI

G

H

P

EX 3"

EX 2"

EX 2"

V

V

V

G HP

CODED NOTES

1. REMOVE DIESEL FUEL STORAGE TANK AND CONCRETE PAD LOCATED AT

GROUND LEVEL IN PARKING LOT.

2. REMOVE 1" DIESEL FUEL PIPING FROM STORAGE TANK TO DAY TANK LOCATED

IN BASEMENT.

3. REMOVE DIESEL FUEL DAY TANK

4. REMOVE 1" DIESEL FUEL PIPING FROM DAY TANK TO GENERATOR

5. REMOVE DOMESTIC WATER BACKFLOW PREVENTER

6. REMOVE DOMESTIC WATER PIPING FROM SUPPLY PIPING IN CORRIDOR AND

FROM BACKFLOW PREVENTER TO GENERATOR HEAT EXCHANGER.

7. CAP REMAINING DOMESTIC WATER SUPPLY PIPING IN CORRIDOR

8. REMOVE GENERATOR EXHAUST PIPE MUFFLER

9. REMOVE 8" GENERATOR EXHAUST PIPING

10. CAP REMAINING EXHAUST PIPING AT STAIRWELL WALL AND ABOVE ROOF.

ABANDON PIPING INSIDE STORAGE BUILDING CHASE IN PLACE.

11. EXISTING GAS PRESSURE REGULATOR VENT PIPING TO REMAIN

12. EXISTING 3PSI GAS PIPING TO BUILDING TO REMAIN

13. EXISTING GAS METER TO BE REMOVED BY GAS COMPANY

14. EXISTING GAS REGULATOR TO BE REMOVED BY GAS COMPANY

15. EXISTING HIGH PRESSURE GAS SERVICE PIPING TO BE REMOVED BY GAS

COMPANY

16. EXISTING 3 PSI GAS PIPING TO BE REMOVED BY CONTRACTOR

17. EXISTING REGULATOR VENT PIPING TO BE REMOVED BY CONTRACTOR

18. EXISTING RELIEF VENT PIPING TO BE REMOVED BY CONTRACTOR

19. REMOVE EXISTING VENT PIPING EXTENDING ABOVE GRADE.

20. REMOVE EXISTING ENERGY MONITORING DEVICE AND STORE FOR

RE-INSTALLATION AS SHOWN IN PLANS. (INTECK MODEL #100G DLS

DATALOGGING ERT MODULE)

HARDLINES DESIGN

METRO CD ENGINEERING

24 X 36

45402-1443OHDAYTON

200 W SECOND STREET

RICE FEDERAL BUILDING

A. ADEJOBI

GENERATOR AND FIRE PUMP REPLACEMENT

ISSUED FOR

BID ADDENDUM 2

09/16/2022

CDN

M

MECHANICAL DEMOLITION PLANS

MD-1-1

SCALE: 1/8" = 1'-0"

GENERATOR DEMOLITION PLAN-BASEMENT (WEST)

M1

N

SYMBOL LEGEND

* ALL SYMBOLS MAY NOT BE USED

PIPE UP

PIPE DOWN

OBJECTS TO BE REMOVED

EXISTING OBJECTS TO REMAIN

PIPE TEE BRANCH UP

PIPE TEE BRANCH DOWN

SHUTOFF VALVE

OS&Y VALVE

NATURAL GAS REGULATOR

NEW WORK TO BE PROVIDED

NATURAL GAS PIPING, HIGH PRESSURE

NATURAL GAS PIPING, PRESSURE INDICATED

NATURAL GAS VENT PIPING

CONNECT TO EXISTING

SCALE: NONE

EXISTING NATURAL GAS METER ASSEMBLY

M2

EXISTING OWNER DEVICE

TO BE REMOVED

REGULATOR

METER

VENT PIPING

SCALE: 1/8" = 1'-0"

GAS METER DEMOLITION PLAN-BASEMENT (EAST)

M1

N

G HP

G 3PSI

V

GENERAL NOTES

1. THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST FOR CENTER POINT

ENERGY COMPANY TO REMOVE THE EXISTING NATURAL GAS METER AND

ASSOCIATED PIPING; AND TO PROVIDE AND INSTALL THE REPLACEMENT DUAL

NATURAL GAS METER MANIFOLD.

2. THE CONTRACTOR SHALL COORDINATE PHASING OF DEMOLITION AND

CONSTRUCTION WORK WITH THE GSA AND CENTER POINT ENERGY COMPANY

TO MINIMIZE DISRUPTION OF NATURAL GAS SERVICE TO THE BUILDING AND

OPERATIONAL READINESS OF THE EMERGENCY GENERATOR

HIGH PRESSURE

SERVICE PIPING

3PSI BUILDING

SUPPLY PIPING

MICHAEL

CHOW

E-64993

S

T

A

T

E

OF

O

H

I

O

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

AL

E

N

G

I

N

E

E

R

AutoCAD SHX Text L

AutoCAD SHX Text K

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

FOR OFFICIAL USE ONLY

AutoCAD SHX Text

UNITED STATES GOVERNMENT

AutoCAD SHX Text

PROPERTY OF THE

AutoCAD SHX Text

GREAT LAKES REGION 5

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

DISCIPLINE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PCN NO.

AutoCAD SHX Text

GSA PM

AutoCAD SHX Text

PROJ. DESC.

AutoCAD SHX Text

BLDG NO.

AutoCAD SHX Text

CITY/ST./ZIP

AutoCAD SHX Text

STREET

AutoCAD SHX Text

BLDG NAME

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FLOOR NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

SHEET DESIGNATOR

AutoCAD SHX Text SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

AutoCAD SHX Text

SHEET SIZE

AutoCAD SHX Text

SUB A/E

AutoCAD SHX Text

PRIME A/E

AutoCAD SHX Text

CONS. CONTR.

AutoCAD SHX Text

A/E CON. NO.

AutoCAD SHX Text

CONTRACTORS

AutoCAD SHX Text

CONSTR. CON.

AutoCAD SHX Text

A/E TASK NO.

AutoCAD SHX Text

CONS. WORK

AutoCAD SHX Text

CONTRACTOR INFO

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

230 S. DEARBORN, CHICAGO IL

AutoCAD SHX Text

OH0195ZZ

AutoCAD SHX Text

EPM52751

AutoCAD SHX Text

AutoCAD SHX Text

BSMT

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

AutoCAD SHX Text

REVISION

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

LIMITED OFFICIAL USE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text

B12

MECH.

B34

MECH.

B13

STAIR

ST4-B1

MECH.

B11

LOCKERS

B18A

ELEC.

B14

2 3

2"

EX 3"

G

P S

I

G

P S

I

SEE SHEET M1-2

FOR CONTINUATION

STAIR

EXISTING

SHED

EX. MAN

HOLE

EXISTING

GUARD

BOOTH

EXISTING

BUILDING

EXISTING

PARKING LOT

PARKING

#34

GENERATOR

G

2"

3"

HARDLINES DESIGN

METRO CD ENGINEERING

24 X 36

45402-1443OHDAYTON

200 W SECOND STREET

RICE FEDERAL BUILDING

A. ADEJOBI

GENERATOR AND FIRE PUMP REPLACEMENT

ISSUED FOR

BID ADDENDUM 2

09/16/2022

CDN

M

MECHANICAL PLANS WEST

M-1-1

Scale: 1/8" = 1'-0"

BASEMENT MECHANICAL PLAN WEST

M-1-1

N

CODED NOTES

1. NEW NATURAL GAS PIPING THRU WALL ABOVE DOOR AT APPROX. ELEVATION

OF 9'-0 A.F.F.

2. EXISTING PROPELLER WALL FAN TO REMAIN

3. EXISTING DE-ACTIVATED VENTILATION AIR INLET SHUTTER TO REMAIN

4. EXISTING VENTILATION TUNNELS BELOW GRADE TO AREA WELL

5. EXISTING EXHAUST HOOD TO REMAIN

6. NEW NATURAL GAS PIPING UP TO GENERATOR AT GROUND LEVEL.

7. NATURAL GAS PIPING UP FROM AREA WELL AT BASEMENT LEVEL. ROUTE

THRU STORAGE SHED WALL AT APPROX. 7'-0" A.F.F.

8. SUPPORT NATURAL GAS PIPING FROM CONCRETE PARKING LOT WALL.

9. PROVIDE PIPE SUPPORT STAND FOR NATURAL GAS PIPING AT ELBOW WHERE

PIPING TURNS HORIZONTAL.

10. PROVIDE PRESSURE REGULATOR: 6000 CFH, 2 PSIG INLET, 10 IN. WC. OUTLET.

INCREASE PIPE SIZE TO 3" DOWNSTREAM OF REGULATOR.

11. EXISTING 3" NATURAL GAS PIPING TO HEATING AND WATER HEATING

EQUIPMENT

GENERAL NOTES

1. THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST FOR CENTER POINT

ENERGY COMPANY TO REMOVE THE EXISTING NATURAL GAS METER AND

ASSOCIATED PIPING; AND TO PROVIDE AND INSTALL THE REPLACEMENT DUAL

NATURAL GAS METER MANIFOLD.

2. THE CONTRACTOR SHALL COORDINATE PHASING OF DEMOLITION AND

CONSTRUCTION WORK WITH THE GSA AND CENTER POINT ENERGY COMPANY

TO MINIMIZE DISRUPTION OF NATURAL GAS SERVICE TO THE BUILDING AND

OPERATIONAL READINESS OF THE EMERGENCY GENERATOR

SYMBOL LEGEND

* ALL SYMBOLS MAY NOT BE USED

PIPE UP

PIPE DOWN

OBJECTS TO BE REMOVED

EXISTING OBJECTS TO REMAIN

PIPE TEE BRANCH UP

PIPE TEE BRANCH DOWN

SHUTOFF VALVE

OS&Y VALVE

NATURAL GAS REGULATOR

NEW WORK TO BE PROVIDED

NATURAL GAS PIPING, HIGH PRESSURE

NATURAL GAS PIPING, PRESSURE INDICATED

NATURAL GAS VENT PIPING

CONNECT TO EXISTING

G HP

G 3PSI

V

Scale: 1/8" = 1'-0"

GRADE LEVEL MECHANICAL PLAN WEST

M-1-1

N

MICHAEL

CHOW

E-64993

S

T

A

T

E

OF

O

H

I

O

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

AL

E

N

G

I

N

E

E

R

AutoCAD SHX Text

UP

AutoCAD SHX Text

UNEXCAVATED

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FOR OFFICIAL USE ONLY

AutoCAD SHX Text

UNITED STATES GOVERNMENT

AutoCAD SHX Text

PROPERTY OF THE

AutoCAD SHX Text

GREAT LAKES REGION 5

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

DISCIPLINE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PCN NO.

AutoCAD SHX Text

GSA PM

AutoCAD SHX Text

PROJ. DESC.

AutoCAD SHX Text

BLDG NO.

AutoCAD SHX Text

CITY/ST./ZIP

AutoCAD SHX Text

STREET

AutoCAD SHX Text

BLDG NAME

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FLOOR NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

SHEET DESIGNATOR

AutoCAD SHX Text SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

AutoCAD SHX Text

SHEET SIZE

AutoCAD SHX Text

SUB A/E

AutoCAD SHX Text

PRIME A/E

AutoCAD SHX Text

CONS. CONTR.

AutoCAD SHX Text

A/E CON. NO.

AutoCAD SHX Text

CONTRACTORS

AutoCAD SHX Text

CONSTR. CON.

AutoCAD SHX Text

A/E TASK NO.

AutoCAD SHX Text

CONS. WORK

AutoCAD SHX Text

CONTRACTOR INFO

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

230 S. DEARBORN, CHICAGO IL

AutoCAD SHX Text

OH0195ZZ

AutoCAD SHX Text

EPM52751

AutoCAD SHX Text

AutoCAD SHX Text

BSMT

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

AutoCAD SHX Text

REVISION

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

LIMITED OFFICIAL USE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8'

16'

TELE.

B09

MECH.

BMA

VERT. PEN.

VP1-B1

STORAGE

B4

EX 3"

G

P

S I

G

P

S I

2"

3"

SEE SHEET M1-1

FOR CONTINUATION

SIDEWALK

GRAVEL AREA

AREA WELL

WILKINSON ST.

G 3PSI

G 3PSI

2"

3"

PARKING LOT

HARDLINES DESIGN

METRO CD ENGINEERING

24 X 36

45402-1443OHDAYTON

200 W SECOND STREET

RICE FEDERAL BUILDING

A. ADEJOBI

GENERATOR AND FIRE PUMP REPLACEMENT

ISSUED FOR

BID ADDENDUM 2

09/16/2022

Scale: 1/8" = 1'-0"

BASEMENT MECHANICAL PLAN EAST

M-1-2

N

CDN

M

MECHANICAL PLANS EAST

M-1-2

CODED NOTES

1. EXISTING NATURAL GAS PIPING TO BUILDING TO REMAIN

2. NEW NATURAL GAS PIPING ROUTED THRU BASEMENT TO NEW GENERATOR

3. NEW GAS PIPING FROM GAS METER ALONG EXISTING WALL, DROPS DOWN

UNDERGROUND INTO BUILDING THROUGH BASEMENT WALL.

4. NATURAL GAS REGULATOR BY GAS COMPANY

5. BUILDING GAS METER BY GAS COMPANY

6. GENERATOR GAS METER BY GAS COMPANY

7. CONNECT NEW 3" GAS PIPE INTO EXISTING PIPE.

8. NEW NATURAL GAS PIPING THRU WALL ABOVE DOOR AT APPROX. ELEVATION

OF 9'-0 A.F.F.

9. RE-INSTALL ENERGY MONITORING DEVICE REMOVED DURING DEMOLITION.

SEE SHEET MD-1-1 (INTECK MODEL #100G DLS DATALOGGING ERT MODULE)

10. INSTALL NEW ENERGY MONITORING DEVICE, MATCH EXISTING, MAKE ALL

FINAL CONNECTIONS. (INTECK MODEL #100G DLS DATALOGGING ERT

MODULE)

11.

12. NEW FENCE, SEE ARCHITECTURAL PLANS FOR DETAILS.

13. NEW BOLLARDS, SEE ARCHITECTURAL PLANS FOR DETAILS.

GENERAL NOTES

1. THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST FOR CENTER POINT

ENERGY COMPANY TO REMOVE THE EXISTING NATURAL GAS METER AND

ASSOCIATED PIPING; AND TO PROVIDE AND INSTALL THE REPLACEMENT DUAL

NATURAL GAS METER MANIFOLD.

2. THE CONTRACTOR SHALL COORDINATE PHASING OF DEMOLITION AND

CONSTRUCTION WORK WITH THE GSA AND CENTER POINT ENERGY COMPANY

TO MINIMIZE DISRUPTION OF NATURAL GAS SERVICE TO THE BUILDING AND

OPERATIONAL READINESS OF THE EMERGENCY GENERATOR

SCALE: NONE

REPLACEMENT NATURAL GAS METER ASSEMBLY

M-1-2

PLUG VALVE

REGULATOR

RELIEF VALVE

RELIEF VENT

UP TO 8'-0"

ABOVE GRADE

PLUG VALVE

PLUG VALVE

PLUG VALVE

BUILDING

METER

GENERATOR

METER

CONNECT TO

EXISTING BUILDING

SUPPLY PIPING IN

BASEMENT

EXISTING GRADE

ROUTE THRU

BUILDING BASEMENT

TO GENERATOR

ENTIRE METER MANIFOLD ASSEMBLY

PROVIDED AND INSTALLED BY THE

NATURAL GAS COMPANY

2"

3"

Scale: 1/4" = 1'-0"

GROUND LEVEL MECHANICAL PLAN EAST

M-1-2

N

KEY PLAN

MICHAEL

CHOW

E-64993

S

T

A

T

E

OF

O

H

I

O

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

A L

E

N

G

I

N

E

E

R

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text

FOR OFFICIAL USE ONLY

AutoCAD SHX Text

UNITED STATES GOVERNMENT

AutoCAD SHX Text

PROPERTY OF THE

AutoCAD SHX Text

GREAT LAKES REGION 5

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

DISCIPLINE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PCN NO.

AutoCAD SHX Text

GSA PM

AutoCAD SHX Text

PROJ. DESC.

AutoCAD SHX Text

BLDG NO.

AutoCAD SHX Text

CITY/ST./ZIP

AutoCAD SHX Text

STREET

AutoCAD SHX Text

BLDG NAME

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FLOOR NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

SHEET DESIGNATOR

AutoCAD SHX Text SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

AutoCAD SHX Text

SHEET SIZE

AutoCAD SHX Text

SUB A/E

AutoCAD SHX Text

PRIME A/E

AutoCAD SHX Text

CONS. CONTR.

AutoCAD SHX Text

A/E CON. NO.

AutoCAD SHX Text

CONTRACTORS

AutoCAD SHX Text

CONSTR. CON.

AutoCAD SHX Text

A/E TASK NO.

AutoCAD SHX Text

CONS. WORK

AutoCAD SHX Text

CONTRACTOR INFO

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

230 S. DEARBORN, CHICAGO IL

AutoCAD SHX Text

OH0195ZZ

AutoCAD SHX Text

EPM52751

AutoCAD SHX Text

AutoCAD SHX Text

BSMT

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

AutoCAD SHX Text

REVISION

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

LIMITED OFFICIAL USE ONLY

AutoCAD SHX Text

PLUG VALVE TYP OF 4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

AREAWAY

STAIR

ST4-B1

EX.ATS

41'-9 1/2"

5'-9"

EXIST

EXIST

EXIST.

PIPING

EXIST.

MECH.

REMOVE EXISTING GENERATOR,

BATTERY, CONCRETE PAD AND

ALL EXISTING COMPONENTS

AFTER INSTALLATION AND

TESTING OF NEW GENERATOR

AND COMPONENTS

XFMR

EXISTING PULL

BOXES

TO REMAIN

EXISTING PANEL BH

120/208V,3Ø,4W

EXISTING

PANEL 8A

277/480V,3Ø,4W

EXISTING 3,000A

SWITCHBOARD

277/480V,3Ø,4W

EXISTING 500A

EMERGENCY

277/480V,3Ø,4W

SECTION

EXISTING

BUCKET

TOOL

EXISTING

METER

EXISTING

EQUIPMENT

EXISTING

TRANSFORMER

REMOVE EXISTING ATS, CONCRETE

PAD AND ALL EXISTING COMPONENTS

AFTER INSTALLATION AND TESTING OF

NEW GENERATOR AND COMPONENTS.

CONTRACTOR SHALL COORDINATE,

SECURE AND PAY FOR ALL COSTS

INCLUDING PERMITS REQUIRED TO

REMOVE THE EXISTING GENERATOR

AND OTHER EQUIPMENT. THIS

INCLUDES ANY CRANE RENTALS,

PERMITTING REQUIREMENTS, O&M

COSTS, ROAD TRAFFIC SHUTDOWNS,

ETC. PATCH AND PAINT CONCRETE TO

MATCH EXISTING

REMOVE EXISTING GENERATOR

REMOTE TESTING COMPONENTS

AFTER INSTALLATION AND

TESTING OF NEW GENERATOR

AND COMPONENTS

EXISTING PANEL BC

120/208V,3Ø,4W

EXISTING

MECHANICAL

ROOM

B13

EXISTING WALL FAN AND CONTROL

DISCONNECT SWITCH TO REMAIN

E X

I S

T I N

G

V F

D S

EXISTING INLET SHUTTER TO

REMAIN

EXISTING PROPELLER

WALL FAN TO REMAIN

EXISTING

POWER

LOGIC

EXISTING

EMG PANEL

BXD AND

DISCONNECT

#2#1

FIRE PUMP

SEWAGE PUMPS

FIRE PUMP CONTROL

PANEL AND

AUTOMATIC

TRANSFER SWITCH.

DEMO CONDUIT AND CONDUCTOR

FROM (E)FIRE-PUMP & (E)JOCKEY

PUMP AND CONTROLS, BACK TO

(E)EMERGENCY SWITCHBOARD

JOCKEY PUMP

DEMO CONDUIT AND

CONDUCTOR BETWEEN

GENERATOR (E)ATS

SWITCHES AND MAIN

SWITCHBOARD

(E)SEWAGE PUMPS 1& 2

& STORM PUMP, DEMO

CONDUCTOR AND

CONDUIT BACK TO

(E)PANEL BXA

DEMO CONDUIT AND CONDUCTOR

BETWEEN (E)MCC-SECTION J AND

(E)EMERGENCY SWITCHBOARD

HARDLINES DESIGN

METRO CD ENGINEERING

24 X 36

45402-1443OHDAYTON

200 W SECOND STREET

RICE FEDERAL BUILDING

A. ADEJOBI

GENERATOR AND FIRE PUMP REPLACEMENT

ISSUED FOR

BID ADDENDUM 2

09/16/2022

MICHAEL

CHOW

E-64993

S

T

A

T

E

OF

O

H

I

O

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

AL

E

N

G

I

N

E

E

R

RLK

E

ELECTRICAL BASEMENT DEMO PLAN

ED-1-1

SCALE: 1/4" = 1'-0"

ELECTRICAL BASEMENT DEMOLITION PLAN

ED-1

N

AutoCAD SHX Text L

AutoCAD SHX Text H

AutoCAD SHX Text J

AutoCAD SHX Text K

AutoCAD SHX Text M

AutoCAD SHX Text

UP

AutoCAD SHX Text

UNEXCAVATED

AutoCAD SHX Text

FOR OFFICIAL USE ONLY

AutoCAD SHX Text

UNITED STATES GOVERNMENT

AutoCAD SHX Text

PROPERTY OF THE

AutoCAD SHX Text

GREAT LAKES REGION 5

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

DISCIPLINE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PCN NO.

AutoCAD SHX Text

GSA PM

AutoCAD SHX Text

PROJ. DESC.

AutoCAD SHX Text

BLDG NO.

AutoCAD SHX Text

CITY/ST./ZIP

AutoCAD SHX Text

STREET

AutoCAD SHX Text

BLDG NAME

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FLOOR NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

SHEET DESIGNATOR

AutoCAD SHX Text SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

AutoCAD SHX Text

SHEET SIZE

AutoCAD SHX Text

SUB A/E

AutoCAD SHX Text

PRIME A/E

AutoCAD SHX Text

CONS. CONTR.

AutoCAD SHX Text

A/E CON. NO.

AutoCAD SHX Text

CONTRACTORS

AutoCAD SHX Text

CONSTR. CON.

AutoCAD SHX Text

A/E TASK NO.

AutoCAD SHX Text

CONS. WORK

AutoCAD SHX Text

CONTRACTOR INFO

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

230 S. DEARBORN, CHICAGO IL

AutoCAD SHX Text

OH0195ZZ

AutoCAD SHX Text

EPM52751

AutoCAD SHX Text

AutoCAD SHX Text

BSMT

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

AutoCAD SHX Text

REVISION

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

LIMITED OFFICIAL USE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

DN

EXISTING

SHED

EXISTING

GUARD

BOOTH

EXISTING

BUILDING

EXISTING

BUILDING

LOWER

ENTRY

11'-0"

MOVE SHED WALL IN 11'-0"

"A"

"A"

EXISTING

ASPHALT

PARKING #32

NO EXISTING PARKING SPACES WILL BE

REMOVED

GOVERNMENT

TO MOVE

EXISTING

RECYCLING BIN

FROM PARKING

SPOT #32 TO

PARKING SPOT

#34

NEW CONCRETE

GUARD POST .

SEE TYP. BOLLARD

DETAIL THIS SHEET

PARKING #33

PARKING #34

EX. MAN

HOLE

EXISTING DIESEL TANK AND CONCRETE PAD TO BE

DEMOLISHED AND REMOVED IN ITS ENTIRETY

NEW CONCRETE GUARD POST - TYP. OF 3

SEE TYP. BOLLARD DETAIL THIS SHEET

USE BLACK ASPHALT SEALANT TO PAINT OVER EXISTING

PARKING STRIP AS PARKING SPOT #34 WOULD NO

LONGER BE USED

CONTRACTOR TO ENSURE THERE ARE NO CONFLICTS

WITH MANHOLE

NEW SHED WALL AND

6'-4" DOOR ROUGH OPENING

RELOCATE (2) EXISTING

FEEDER CONDUITS FOR

GUARD BOOTH AS

NECESSARY TO AVOID ANY

CONFLICTS

NEW FREE-STANDING

800A

GENERATOR QUICK

CONNECTION BOX

EXISTING DUMPSTER

TO REMAIN

EXISTING SPRINKLER

CONNECTION AND

PROTECTIVE

CONCRETE GUARD

POST

ELECTRICAL CONTRACTOR SHALL RELOCATE EXISTING

SHED LIGHT FIXTURE. EXTEND EXISTING CONDUIT AND

WIRING AS REQUIRED. VERIFY EXACT REQUIREMENTS IN

FIELD PRIOR TO BID AND INCLUDE ALL COSTS IN BID.

ELECTRICAL CONTRACTOR SHALL RELOCATE EXISTING

SHED RECEPTACLE. EXTEND EXISTING CONDUIT AND

WIRING AS REQUIRED. VERIFY EXACT REQUIREMENTS IN

FIELD PRIOR TO BID AND INCLUDE ALL COSTS IN BID.

ELECTRICAL CONTRACTOR SHALL RELOCATE EXISTING

SHED LIGHT SWITCH. EXTEND EXISTING CONDUIT AND

WIRING AS REQUIRED. VERIFY EXACT REQUIREMENTS IN

FIELD PRIOR TO BID AND INCLUDE ALL COSTS IN BID.

MAXIMUM ALLOWABLE

GENERATOR FOOTPRINT. TO

MAINTAIN CORRECT

CLEARANCES, GENERATOR

MUST FIT WITHIN REGION

SHOWN

CONCRETE HOUSE-KEEPING

PAD

3' REQUIRED EQUIPMENT

CLEARANCE

17'-3"

5'-11"

EXISTING GATE

AND POURED

WALL TO

REMAIN

EXISTING

GRADE/

ASPHALT

EXISTING

WALL TO

REMAIN

EXISTING

BUILDING

3'-0"

CLEARANCE

AROUND NEW

GENERATOR

NEW MIN. 7"

CONCRETE PAD

W/ RE-BAR.

EXTEND 18"

AROUND ALL

SIDES OF NEW

GENERATOR

OUTLINE OF NEW SHED WALL

AND 6'-4" DOOR ROUGH OPENING

BEYOND NEW GENERATOR AND

EXISTING DOORS TO REMAIN

NEW

FREE-STANDING

800A

CAMLOCK QUICK

CONNECTION

CABINET ON 4"

CONCRETE

HOUSEKEEPING

PAD

NEW CONCRETE

GUARD POST -

TYP. OF 3. SEE TYP.

BOLLARD DETAIL

THIS SHEET

SYMBOLS / LEGEND

EQUIPMENT

CLEARANCES

CONCRETE

HOUSEKEEPING

EQUIPMENT PAD

EQUIPMENT

FOOTPRINT

HARDLINES DESIGN

METRO CD ENGINEERING

24 X 36

45402-1443OHDAYTON

200 W SECOND STREET

RICE FEDERAL BUILDING

A. ADEJOBI

GENERATOR AND FIRE PUMP REPLACEMENT

ISSUED FOR

BID ADDENDUM 2

09/16/2022

MICHAEL

CHOW

E-64993

S

T

A

T

E

OF

O

H

I

O

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

AL

E

N

G

I

N

E

E

R

RLK

E

ELECTRICAL GROUND LEVEL PLAN

E-1-1

SCALE: 1/4" = 1'-0"

ELECTRICAL GROUND LEVEL PLAN

E-1-1

N

SCALE: 1/4" = 1'-0"

ELECTRICAL GROUND LEVEL ELEVATION "A"

E-1-1

SCALE: N.T.S.

TYP. CONCRETE BOLLARD DETAIL

E-1-1

CONCRETE CAP

2"

2'-0"

1'-0"

18" DIA.

3'-0"

3'-0"

6"Ø STANDARD GALVANIZED STEEL

PIPE FILLED W/ CONCRETE (APPLY

TWO COATS YELLOW PAINT) MIN. 0.185"

WALL THICKNESS OR 1/8" THICK HIGH

DENSITY POLYETHYLENE (HDPE)

BOLLARD COVER COLOR YELLOW

SLOPE CONCRETE BASE

EXISTING FINISHED SERVICE

AS PER PLANS

CONCRETE FOOTING

AutoCAD SHX Text

FOR OFFICIAL USE ONLY

AutoCAD SHX Text

UNITED STATES GOVERNMENT

AutoCAD SHX Text

PROPERTY OF THE

AutoCAD SHX Text

GREAT LAKES REGION 5

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

DISCIPLINE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PCN NO.

AutoCAD SHX Text

GSA PM

AutoCAD SHX Text

PROJ. DESC.

AutoCAD SHX Text

BLDG NO.

AutoCAD SHX Text

CITY/ST./ZIP

AutoCAD SHX Text

STREET

AutoCAD SHX Text

BLDG NAME

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FLOOR NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

SHEET DESIGNATOR

AutoCAD SHX Text SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

AutoCAD SHX Text

SHEET SIZE

AutoCAD SHX Text

SUB A/E

AutoCAD SHX Text

PRIME A/E

AutoCAD SHX Text

CONS. CONTR.

AutoCAD SHX Text

A/E CON. NO.

AutoCAD SHX Text

CONTRACTORS

AutoCAD SHX Text

CONSTR. CON.

AutoCAD SHX Text

A/E TASK NO.

AutoCAD SHX Text

CONS. WORK

AutoCAD SHX Text

CONTRACTOR INFO

AutoCAD SHX Text

GENERAL SERVICES ADMINISTRATION

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

230 S. DEARBORN, CHICAGO IL

AutoCAD SHX Text

OH0195ZZ

AutoCAD SHX Text

EPM52751

AutoCAD SHX Text

AutoCAD SHX Text

BSMT

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

AutoCAD SHX Text

REVISION

AutoCAD SHX Text 09/16/2022

AutoCAD SHX Text

LIMITED OFFICIAL USE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

SCALE: 1/8"=1'-0"

FREE-STANDING TRANSFER SWITCHES

NEW 600A AUTOMATIC TRANSFER SWITCH -

LIFE SAFETY ATS-LS

UNIT HEIGHT 90"

NEW 4" CONCRETE HOUSEKEEPING PAD -

EXTEND 4" ALL SIDES

42" SIDE CLEARANCE FOR EXISTING FAN

DISCONNECT

37"

8"

40"

30"

8"

1'-8" 2'-5 5/16"

10'-11"

3'-1 5/16"

NEW 600A

MANUAL TRANSFER SWITCH - MTS

UNIT HEIGHT 84"

2'-5"

40" FRONT CLEARANCE FOR DOORS

37" SIDE CLEARANCE FOR LOUVER

NEW 200A AUTOMATIC

TRANSFER SWITCH - REQUIRED STAND-BY

ATS-RSB. UNIT HEIGHT 78.1"

SYMBOLS / LEGEND

EQUIPMENT

CLEARANCES

CONCRETE

HOUSEKEEPING

EQUIPMENT PAD

EQUIPMENT

FOOTPRINT

STAIR

ST4-B1

5'-9"

EXIST

EXIST.

MECH.

NEW 200A AUTOMATIC TRANSFER

SWITCH - REQUIRED STAND-BY ATS-RSB

5'-9"

EXISTING PANEL 8A 277/480V,3Ø,4W

EXISTING 3,000A SWITCHBOARD

277/480V,3Ø,4W

EXISTING EQUIP.

EXISTING TRANSFORMER

EXISTING PANEL BXD 277/480V,3Ø,4W

EXISTING PANEL BXA 277/480V,3Ø,4W

EXISTING ELECTRICAL EQUIPMENT

EXISTING DISCONNECT SWITCH

EXISTING TRANSFORMER T-3 HMT

TWO EXISTING TRANSFORMERS STACKED

EXISTING PANEL BXB 120/208V,3Ø,4W

EXISTING PANEL BC

120/208V,3Ø,4W

EXISTING ELECTRICAL EQUIPMENT

EXISTING ELECTRICAL EQUIPMENT

41'-9 1/2"

EXIST

APPROX. LOCATION IN PARKING LOT

NEW FREE-STANDING 800A

GENERATOR QUICK CONNECTION BOX

NEW

EQUIPMENT

ROOM

B13

NEW 600A MANUAL

TRANSFER SWITCH - MTS

NEW 600A AUTOMATIC

TRANSFER SWITCH -

LIFE SAFETY ATS-LS

RAE

NEW GENERATOR EMERGENCY

STOP BUTTON UNDER EXISTING FAN.

COORDINATE LOCATION IN FIELD

NEW GEN SET REMOTE ANNUNCIATOR UNDER EXISTING FAN

COORDINATE LOCATION IN FIELD

X F

M R

NEW 250A FUSED (DOUBLE LUGS) DISCONNECT SWITCH TO (E)

PNL BXC BASEMENT & (N) PNL RSB-1 IN PENTHOUSE

NEW PANEL RSBDP 200A, 277/480V, 3PH, 4W

NEW 75KVA TRANSFORMER T-RSB

NEW PANEL EMLSDPB 600A, 277/480V, 3P/4W

CONNECT TO NEW 500KW

GENERAC GENERATOR IN

PARKING LOT

EXISTING LOUVER INSTALLED

FLUSH IN WALL. PART OF

TRANSFER SWITCH IS IN FRONT OF

LOUVER BUT TRANSFER SWITCH

SITS 4 INCHES IN FRONT OF WALL.

MAINTAIN 42" WORKING CLEARANCE

FOR EXISTING FAN DISCONNECT

E X

I S

T I N

G

V F

D S

TO NEW REQUIRED STANDBY

PANEL RSB-1 IN PENTHOUSE

MECH RM P1

DEMO CONDUIT AND CONDUCTOR TO

EXISTING TRANSFORMER T-3 HMT

DEMO CONDUIT AND

CONDUCTOR TO EXISTING

PENTHOUSE PANEL PX

CONDUIT

ETR

TO EXISTING

TRANSFORMER

T-X DISCONNECT

ON 1ST FLOOR

FEEDING PANEL

1XB

T-3

HMT

EXISTING POWER LOGIC

EXISTING METER

EXISTING PULL BOXES TO

REMAIN

NEW 277/480V 3P/4W

400A PANEL BA-1

EXISTING BUCKET TOOL

EXIST.

PIPING

EXISTING PANEL BH

120/208V,3Ø,4W

EXISTING 600A EMERGENCY

SECTION 277/480V,3Ø,4W

NEW 120/208V 3P 4W 100A

PANEL BXB-1

NEW 45KVA TRANSFORMER

& 100A 480V 3P/4W FUSED

DISCONNECT T-BXB-1

(E)PANEL BXC

RE-FEED PANEL FROM

RSBDP

E X

I S

T I N

G

M

C C

BD

BDBB

#2#1

EXISTING PANEL BXD

DISC SW

P-2 NEW JOCKEY PUMP

P-1

NEW

FIRE

PUMP

SEWAGE

PUMPS

NEW JOCKEY PUMP CONTROL PANEL.

RELOCATED EXISTING SPRINKLER HEAD CABINETS APPROXIMATE

LOCATION. VERIFY LOCATION WITH EXISTING AND NEW CONDITIONS.

NEW WALL MOUNTED GRUNDFOS-PEERLESS "FIRE CONNECT" FIRE

PUMP MONITORING SYSTEM.

NEW FIRE PUMP CONTROL PANEL AND

AUTOMATIC TRANSFER SWITCH.

DEMO CONDUIT & CONDUCTOR

TO STORM PUMP SP-2, SEWAGE

EJECTOR PUMPS 1 & 2

PROVIDE CONDUCTOR AND CONDUIT

FOR…