Amendment 0006.pdf

PDF 1 MB Posted

Attached to
Department of State - 3rd Floor Office Build-Out, Detroit, MI
Solicitation number
47PF0021R0002_
Issued by

About this file

This document provides details for a federal solicitation to renovate office space for the Department of State in Detroit, Michigan. The General Services Administration is seeking a contractor to renovate approximately 18,228 square feet on the third floor of the Patrick V. McNamara building to accommodate various functions for the Passport Services including waiting areas, transaction spaces, private offices, open office spaces, conference rooms, and a break room. The scope of work also includes installing a new plenum sound masking system throughout the third floor, renovating the existing men's and women's restrooms, and modifying HVAC, plumbing, electrical, and fire protection systems. The contractor will be responsible for project management, labor, equipment, and all supplies required to complete the renovations, which include new wall construction, furniture partitions and finishes throughout the space.

View the file

Other files

File Type Posted
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001...pdf PDF
RFP 47PF0021R0002.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

����
������������������������ !"#$%&�� �'�$%�!()*�+#&,-.&*/�/���&�

%&(&"0&,�!/�/1&�2#!(&�,&3"-*!/&,� �%�/1&�%&(&"2/�� �� &%3�2%"�%�/��/1&�1�$%�!*,�,!/&�32&(" "&,�.!'�%&3$#/�"*�%&4&(/"�*�� �'�$%�� &%���"��

���5������

�������
������������������������

5������

��
��������������
����
����������������������������

��5������

67889:;<=>?@>A88( ����� �����B�������

?:6@C:6@>8<D8E<F9G9>?>9<@H:<C9D9G?>9<@8<D8G<@>=?G>

I���!.&*,.&*/J.�," "(!/"�*�*$.�&% K���& &(/"0&�,!/& L���%&M$"3"/"�*J2$%(1!3&�%&M$"3"/"�*�*$.�&% ����2%�4&(/�*$.�&%�NOPQRSSTUVRWTXY

Z���!,."*"3/&%&,��'�NOPQ[\]X̂Q\]R_QO\X̀ QaY (�,&

E>?@C?=C8D<=:8bc8d=6e78ffHgcfhi8 2���

���������-3!� !%��L��( %���K�ILK

�j!���!.&*,.&*/�� �3�#"("/!/"�*�*$.�&% j����,!/&,�NkllQOmlnQooY

�p!���.�," "(!/"�*�� �(�*/%!(/J�%,&%�*$.�&%

�p����,!/&,�NkllQOmlnQoqY ff788>r9E89>6:8<@Fs8?;;F96E8><8?:6@C:6@>E8<D8E<F9G9>?>9<@E

5������������

����
�������������������

�������"�����L���/���� �������� ����t�������� ���� ���t��������

�I���!((�$*/"*-�!*,�!22%�2%"!/"�*�,!/!�NOPQ̂XuvÛXwY

������ ��������x��������

��������������x fb788>r9E89>6:8?;;F96E8<@Fs8><8:<C9D9G?>9<@E8<D8G<@>=?G>EH<=C6=E78 9>8:<C9D96E8>r68G<@>=?G>H<=C6=8@y:z6=8?E8C6EG=9z6C89@89>6:8f{7

(1&()��*& !���/1"3�(1!*-&��%,&%�"3�"33$&,�2$%3$!*/�/����NkSXVUP|QRv\][̂U\|Y�/1&�(1!*-&3�3&/� �%/1�"*�"/&.��L�!%&�.!,&�"*�/1&�(�*/%!(/��%,&%��� ������*$.�&%�"*�"/&.��p!�

����/1&�!��0&�*$.�&%&,�(�*/%!(/J�%,&%�"3�.�," "&,�/��%& #&(/�/1&�!,."*"3/%!/"0&�(1!*-&3�N}vV]QR}QV]R_~X}QU_QSR|U_~Q[PPUVX�� QQQQQQRSŜ[ŜUR\U[_QwR\R�QX\V���3&/� �%/1�"*�"/&.��L��2$%3$!*/�/��/1&�!$/1�%"/'�� � !%�LK��pK����

(���/1"3�3$22#&.&*/!#�!-%&&.&*/�"3�&*/&%&,�"*/��2$%3$!*/�/��!$/1�%"/'�� �

,����/1&%QNkSXVUP|Q\|SXQ[PQ̀[wUPUVR\U[_QR_wQRv\][̂U\|Y

&t

��������
5�������������������������

������"����j!� ���p!�� �������

����������������
������������������

��(���,!/&�3"-*&, ��!���*!.&�!*,�/"/#&�� �3"-*&%�Nm|SXQ[̂QŜU_\Y

��(���,!/&�3"-*&, ��!���*!.&�!*,�/"/#&�� �(�*/%!(/"*-�� "(&%�Nm|SXQ[̂QŜU_\Y

�L���,&3(%"2/"�*�� �!.&*,.&*/J.�," "(!/"�*���̂~R_U�XwQW|Q���Q}XV\U[_Q]XRwU_~}�QU_VTvwU_~Q}[TUVU\R\U[_�V[_\̂RV\Q}vW�XV\Q̀R\\X̂Q�]X̂XQPXR}UWTX�Y

2!-&������� ����2!-&3

����"33$&,��' (�,&

����*!.&�!*,�!,,%&33�� �(�*/%!(/�%�N�v̀ WX̂�Q}\̂XX\�QV[v_\|�Qk\R\XQR_wQ�O�Q�[wXY ���

������(�*/%!(/�%J� &%�%

NkU~_R\v̂XQ[PQSX̂}[_QRv\][̂U�XwQ\[Q}U~_Y

������$*"/&,�3/!/&3�� �!.&%"(!

NkU~_R\v̂XQ[PQ�[_\̂RV\U_~Q�PPUVX̂Y

�̂X�U[v}QXwU\U[_Qv_v}RWTX

ª«��¬����¤®¢¤¦�¬�¤���̄��¢¢£�«��� �§��̈¢̄�°±�����²�

ª«��¬����¤®¢¤¦�¬�¤���̄��¢¢£�«��� �§��̈¢̄�°±�����²�

²³�́ ��ªµ����ª

²³�́ ��ªµ����ª µ µ� µµ¶ª�¶ª�ª� µ�¶�·¶ª�ª� µ

��������� ���.���0���+����+-

�����1�)2������3��+ ��,-�

)4, )1, )5, )6, 7��� ���!���� ����� ���+����&��� �0����+��&� ��� +������� ��3���� �0�&������������3��+ ��� �� �0����+��&���� +������� ��3���� �0�-

7��� ���$$!����� !� 0�������&������������3�� + ����� !!�.������+ ��� 0���+����.%������ ����� ����0�$ �����-

7��� ���+���� ����������+� �� ������� !���� ���������0����������������� ������������� ���3���������������8�3�������&������������3��� ���������0���������� !!�.������� ��� ������ �������3��+ ��� �+���+���� ��������.����������

7��� ���+���� ��������3�����0� ������� ���������� +�� �!����� ������� ����������������3������������ ����8�3�������&������������3��+ ����� !!�.������� � ��� �������������3��+ ���������������� ���������

7��� ���+���� ��������������0���������� ����0� �������9��+������� ������������ ������+������ ����!��������� ������ ��������� ����&������������3�� + ����� !!�.������� ��� �������������3��+ �������

����������0�������-����� $$!�� .!�&������������ $$��$�� ���������0����������+�����������+��.!��/-

�����<�)� ��� �+�=++������������� ����,-��7��� ����� ����9��� ��&� ++����&� �+���+�� �����'����� �������0�� !������ ��������+��&���!������ �0�+�.%� �������� �$��3�������+���� ����-

* ��+,&� �+�(?&�)@�+���� ������������� ��A��+��� ����������$��+��0�.! �/����������������.��� �+� + �������������0�� !���!���� ����&������ ��&������+��-

�����(4�)=��������0� �+�=$$��$�� �����* � ,-�� B���� $$��$�� ��&���+�� ���������$ ���������� ��+���� ��������� ��� ������+� ��������0� �! ������ �����.%���������0��������������!!�'��0�

)4,=��������0��! ������ ����� ����+���� ������������������������C

���!�+����.D����� �����������������!����� ��!���� ����A����� ���'������� ��.!�-

�����(:;-����������� ����0��������9����0� ������������� ��E����+������!���� ����� ���+�����-������ ����� ����0��������9����0� ������������ !!%� ���#�+�! ��� �����$$!����� !� 0��������-

���2������������ ����� �0��������!��$!�� ��������0�� �! ������ �������� ��� �����.��$! ��+����.!��/�(4&�� ������� �� ������/� �+�����'��+��F����������� ����� �����F-

�����(1-������/����� $$��$�� ���.�#������+�� ������� �%$�������+���� ����-����������������������$��+��0� �����+-������/�'������������������� ������������0�� �����+�������-��)����7=��51-(?1-, �����(5�)*�����$��������=���+����A@�+���� ����,-

��0 ��G�� ���+�����������+���� ��������+��� ���� $$��$�� ���������������� ���7��� ��)��7,� ���������� +��0����������� $$!�� .!�� ��!���� ������������� ��-��������7�� .!����� ��������&���'�3��&��� !!�����.��������������������

�3�� !!���� !������ ���$�����.%���������0�������� ������!!�'��0����������� )�,���� !������ ���$���������� ��+�.%�C�� )��,���� !������ ���$�����+���� ��+�.%�C�� )���,���� !������ ���$��������� �0�+-

B��������3��0&������� ���0&���� ++��0����+�&� �+�����%���������� ��������� �+� ��������0�

)0, B���������7�1?�������+�������!���� � +������� �����.%���������� ����0���������������� ������ ��+������������3��������������� 8�3�������&���������%���������(5�������� )�,���=������������������!������+������� ����H� �+�

)4, )1, )5, )6, IJKLMKNMOPQNROSTO)�2U-�((A4?(:,OVKWX

)(,=��������0��! ������ ���� ��������� ���������������������C

Description of Amendment

RFP 47PF0021R0002

DOS 3rd Floor Office Build-Out PV McNamara Federal Building 477 Michigan Avenue Detroit, Michigan 48226 Amendment 0006

Amendment 0006 is issued to:

1. Address RFIs received for the DOS 3rd Floor Office Build-Out, PV McNamara Federal Building. The Answers provided in the attached supersede any inconsistent provisions contained in the solicitation.

2. Provide revised specifications.

3. Extend the proposal due date to Tuesday, November 24th at 5:00 PM Eastern

Time.

All other solicitation terms and conditions remain unchanged.

PLEASE NOTE – YOU MUST SIGN THE SF30 INCORPORATING THIS

AMENDMENT IN BOX 15a AND RETURN THE SIGNED FORM ALONG WITH

YOUR PROPOSAL.

g.h. forbes associates 816 E. 4th Street, Royal Oak, MI 48067 www.ghfaa.com 248.542.7866

PVM – DOS 3rd Floor Office Build-Out Passport Services

PCN: RMI12446

G.H. Forbes Associates Architects Amendment #0006 11/19/2020

The following questions were emailed to the project team. Answers are indicated below in red:

1. Sheet M 2 00 calls out 1-1/2" sanitary drain piping. Piping specifications call for all sanitary drain piping to be cast-iron hub and spigot construction. Cast-iron hub and spigot pipe and fittings are not manufactured in 1-1/2" diameter, 2" is the smallest diameter available. We suggest revising the piping specifications or changing the size of the pipes. GSA’s 2018 P100 allows hubless cast iron pipe and fittings with fittings conforming to ASTM A 888 with heavy duty couplings complying with ASTM C1277 and ASTM C1540. Provide 1-1/2” hubless piping, conforming with these requirements. Refer to attached Peter Basso Associates write-up, revised drawing M-701 and specification 22 13 16.

2. Plumbing Plan Note # 14 calls for 3/4" Condensate Drains for AC units. M 6 02 Trap Dimension Table Note B says 1" Minimum for condensate drains. Please clarify intention regarding condensate drain sizes. Provide ¾” condensate piping to all AC units.

END

Mechanical

Electrical

Energy Management

Communication Technologies

Architectural Lighting Design

Commissioning

5145 Livernois, Suite 100 2001 Commonwealth Blvd., Ste. 203

Troy, MI 48098-3276 Ann Arbor, MI 48105

Tel: 248-879-5666 Tel: 734-913-4749

Fax: 248-879-0007 Fax: 734-913-4957 www.PeterBassoAssociates.com

AMENDMENT

Project Name: GHF GSA DOS PVM Third Floor Reno

PBA Project Number: 2019-0072-00

Amendment Number: 0006

Date: November 19th, 2020

Each Bidder’s proposal shall include the work described herein.

Unless otherwise indicated, the work described herein shall comply with, and be equal in all respects to, the original Specifications and the Drawings accompanying same. Include incidental work required to properly complete the work, whether stated herein or not.

Specifications Issued: 221316

Drawings Issued: M 7 01

Mechanical Specification Items:

MS-1 Refer to Section 221316 Sanitary Waste and Vent Piping

1. Added section 2.3 Hubless Cast-Iron Soil Pipe and Fittings.

2. Added section 3.3-D.

Mechanical Drawing Items:

MD-1 Refer to Sheet M 7 01

1. Added Hubless Cast-Iron piping to Plumbing Piping & Valve Application Schedule.

End of Addendum.

\\pba.local\projects\2019\2019-0072-00\Bidding\Addendum Writeups\Amendment 0006\Amendment 0006 Write Up.docx

3RD FLOOR OFFICE BUILD-OUT PBS-REG-5

PV McNAMARA BUILDING - DETROIT, MI PCN: RMI 12446

SANITARY WASTE AND VENT PIPING 22 13 16 - 1

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

SECTION 22 13 16 - SANITARY WASTE AND VENT PIPING

GENERAL

1.1 RELATED DOCUMENTS

1.2 DEFINITIONS

1.3 SYSTEMS DESCRIPTIONS

1.4 SUBMITTALS

1.5 QUALITY ASSURANCE

1.6 PROJECT CONDITIONS

PRODUCTS

2.1 MANUFACTURERS

2.2 HUB-AND-SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS

2.3 HUBLESS CAST-IRON SOIL PIPE AND FITTINGS

2.4 SPECIALTY PIPE FITTINGS

2.5 ENCASEMENT FOR UNDERGROUND METAL PIPING

EXECUTION

3.1 EXCAVATION

3.2 PIPING SYSTEM INSTALLATION

3.3 JOINT CONSTRUCTION

3.4 SPECIALTY PIPE FITTING INSTALLATION

3.5 VALVE INSTALLATION

3.6 HANGER AND SUPPORT INSTALLATION

3.7 CONNECTIONS

3.8 IDENTIFICATION

3.9 FIELD QUALITY CONTROL

3.10 CLEANING

GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

B. Related Sections include the following:

1. Division 20 Section “Mechanical General Requirements”.

2. Division 20 Section “Basic Mechanical Materials and Methods”.

3. Division 22 Section “Drainage Piping Specialties”.

4. Division 22 Section “Sanitary Waste and Vent Piping” for piping outside building.

SANITARY WASTE AND VENT PIPING 22 13 16 - 2

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

1.2 DEFINITIONS

A. ABS: Acrylonitrile-butadiene-styrene plastic.

B. EPDM: Ethylene-propylene-diene terpolymer rubber.

C. LLDPE: Linear, low-density polyethylene plastic.

D. NBR: Acrylonitrile-butadiene rubber.

E. PE: Polyethylene plastic.

F. PVC: Polyvinyl chloride plastic.

G. TPE: Thermoplastic elastomer.

1.3 SYSTEMS DESCRIPTIONS

A. Sanitary waste and vent piping system materials are scheduled on the Drawing.

1.4 SUBMITTALS

A. Product Data: For pipe, tube, fittings, and couplings.

B. Field quality-control inspection and test reports.

1.5 QUALITY ASSURANCE

A. Piping materials shall bear label, stamp, or other markings of specified testing agency.

B. Cast-iron soil pipe shall be marked with the collective trademark of Cast Iron Soil Pipe Institute (CISPI).

C. Comply with NSF 14, "Plastics Piping Systems Components and Related Materials," for plastic piping components. Include marking with "NSF-dwv" for plastic drain, waste, and vent piping; "NSF-drain" for plastic drain piping; "NSF-tubular" for plastic continuous waste piping; and "NSF-sewer" for plastic sewer piping.

1.6 PROJECT CONDITIONS

A. Interruption of Existing Sanitary Waste Service: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary service according to requirements indicated:

SANITARY WASTE AND VENT PIPING 22 13 16 - 3

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

1. Notify Owner no fewer than two days in advance of proposed interruption of sanitary waste service.

2. Do not proceed with interruption of sanitary waste service without Owner's written permission.

PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified.

2.2 HUB-AND-SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS

A. Pipe and Fittings: ASTM A 74, Service class.

B. Gaskets: ASTM C 564, rubber.

2.3 HUBLESS CAST-IRON SOIL PIPE AND FITTINGS

A. Pipe and Fittings: ASTM A 888 or CISPI 301.

B. Heavy-Duty, Hubless-Piping Couplings:

1. Manufacturers:

a. ANACO-Husky; McWane Plumbing Group; SD 4000.

b. Ferguson Enterprises, Inc.; ProFlo (Private labeled IDEAL-TRIDON).

c. IDEAL-TRIDON; Heavy-Duty “HD” No-Hub Couplings.

d. Norma Group; Clamp-All Products; HI-TORQ 125.

2. Standards: ASTM C 1277 and ASTM C 1540, or ASTM C 1277 and FM 1680 Class I.

3. Description: Stainless-steel shield with stainless-steel bands and tightening devices; and ASTM C 564, rubber sleeve with integral, center pipe stop.

SANITARY WASTE AND VENT PIPING 22 13 16 - 4

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

2.4 SPECIALTY PIPE FITTINGS

A. Flexible, Nonpressure Pipe Couplings: Comply with ASTM C 1173, elastomeric, sleeve-type, reducing or transition pattern. Include shear ring, ends of same sizes as piping to be joined, and corrosion-resistant-metal tension band and tightening mechanism on each end.

1. Manufacturers:

a. Dallas Specialty & Mfg. Co.

b. Fernco, Inc.

c. Logan Clay Products Company (The).

d. Mission Rubber Co.

e. NDS, Inc.

f. Plastic Oddities, Inc.

2. Sleeve Materials:

a. For Cast-Iron Soil Pipes: ASTM C 564, rubber.

b. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 5926, PVC.

c. For Dissimilar Pipes: ASTM D 5926, PVC or other material compatible with pipe materials being joined.

2.5 ENCASEMENT FOR UNDERGROUND METAL PIPING

A. Description: ASTM A 674 or AWWA C105, high-density, crosslaminated PE film of 0.004-inch or LLDPE film of 0.008-inch minimum thickness.

B. Form: Sheet or tube.

C. Color: Black or natural.

EXECUTION

3.1 EXCAVATION

A. Comply with requirements in Division 31 Section “Earth Moving” for excavating, trenching, and backfilling.

3.2 PIPING SYSTEM INSTALLATION

A. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and

SANITARY WASTE AND VENT PIPING 22 13 16 - 5

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on coordination drawings.

B. Sanitary sewer piping outside the building is specified in Division 22 Section "Sanitary Sewerage."

C. Basic piping installation requirements are specified in Division 20 Section "Basic Mechanical Materials and Methods."

D. Install cleanouts at grade and extend to where building sanitary drains connect to building sanitary sewers.

E. Install cleanout fitting with closure plug inside the building in sanitary force-main piping.

F. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

G. Make changes in direction for soil and waste drainage and vent piping using appropriate branches, bends, and long-sweep bends. Sanitary tees and short-sweep 1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical. Use long-turn, double Y-branch and 1/8-bend fittings if 2 fixtures are installed back to back or side by side with common drain pipe. Straight tees, elbows, and crosses may be used on vent lines. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited.

H. Install soil and waste drainage and vent piping at the following minimum slopes, unless otherwise indicated:

1. Building Sanitary Drain: 1/8-inch per foot downward in direction of flow, unless otherwise noted.

2. Horizontal Sanitary Drainage Piping: 1/8-inch per foot downward in direction of flow, unless otherwise noted.

3. Vent Piping: 1/8-inch per foot down toward vertical fixture vent or toward vent stack.

I. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is without membrane waterproofing.

J. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction.

SANITARY WASTE AND VENT PIPING 22 13 16 - 6

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

3.3 JOINT CONSTRUCTION

A. Basic piping joint construction requirements are specified in Division 20 Section "Basic Mechanical Materials and Methods."

B. Join hub-and-spigot, cast-iron soil piping with gasket joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook" for compression joints.

C. Join hub-and-spigot, cast-iron soil piping with calked joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook" for lead and oakum calked joints.

D. Join hubless cast-iron soil piping according to CISPI 310 and CISPI's "Cast Iron Soil Pipe and Fittings Handbook" for hubless-coupling joints.

3.4 SPECIALTY PIPE FITTING INSTALLATION

A. Transition Couplings:

1. Install transition couplings at joints of piping with small differences in OD's.

2. In Drainage Piping: Shielded, nonpressure transition couplings.

3. In Aboveground Force Main Piping: Fitting-type transition couplings.

3.5 VALVE INSTALLATION

A. General valve installation requirements are specified in Division 20 Section "Valves."

3.6 HANGER AND SUPPORT INSTALLATION

A. Pipe hangers and supports are specified in Division 20 Section "Hangers and Supports." Install the following:

1. Vertical Piping: MSS Type 8 or Type 42, clamps.

2. Install individual, straight, horizontal piping runs according to the following:

a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers.

b. Longer Than 100 Feet: MSS Type 43, adjustable roller hangers.

c. Longer Than 100 Feet, if Indicated: MSS Type 49, spring cushion rolls.

3. Multiple, Straight, Horizontal Piping Runs 100 Feet or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze.

4. Base of Vertical Piping: MSS Type 52, spring hangers.

B. Install supports according to Division 20 Section "Hangers and Supports."

SANITARY WASTE AND VENT PIPING 22 13 16 - 7

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

C. Support vertical piping and tubing at base and at each floor.

D. Rod diameter may be reduced 1 size for double-rod hangers, with 3/8-inch minimum rods.

E. Install hangers for cast-iron soil piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/2 and NPS 2: 60 inches with 3/8-inch rod.

2. NPS 3: 60 inches with 1/2-inch rod.

3. NPS 4 and NPS 5: 60 inches with 5/8-inch rod.

4. NPS 6 and NPS 8: 60 inches with 3/4-inch rod.

5. NPS 10 and NPS 12: 60 inches with 7/8-inch rod.

F. Install supports for vertical cast-iron soil piping every 15 feet.

G. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions.

3.7 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect soil and waste piping to exterior sanitary sewerage piping. Use transition fitting to join dissimilar piping materials.

C. Connect drainage and vent piping to the following:

1. Plumbing Fixtures: Connect drainage piping in sizes indicated, but not smaller than required by plumbing code.

2. Plumbing Fixtures and Equipment: Connect atmospheric vent piping in sizes indicated, but not smaller than required by authorities having jurisdiction.

3. Plumbing Specialties: Connect drainage and vent piping in sizes indicated, but not smaller than required by plumbing code.

4. Equipment: Connect drainage piping as indicated. Provide shutoff valve, if indicated, and union for each connection. Use flanges instead of unions for connections NPS 2-1/2 and larger.

3.8 IDENTIFICATION

A. Identify exposed sanitary waste and vent piping. Comply with requirements for identification specified in Division 20 Section "Mechanical Identification."

SANITARY WASTE AND VENT PIPING 22 13 16 - 8

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

3.9 FIELD QUALITY CONTROL

A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction.

1. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures.

2. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements.

B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection.

C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.

D. Test sanitary drainage and vent piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows:

1. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit separate report for each test, complete with diagram of portion of piping tested.

2. Leave uncovered and unconcealed new, altered, extended, or replaced drainage and vent piping until it has been tested and approved. Expose work that was covered or concealed before it was tested.

3. Roughing-in Plumbing Test Procedure: Test drainage and vent piping, except outside leaders, on completion of roughing-in. Close openings in piping system and fill with water to point of overflow, but not less than 10-foot head of water.

From 15 minutes before inspection starts to completion of inspection, water level must not drop. Inspect joints for leaks.

4. Finished Plumbing Test Procedure: After plumbing fixtures have been set and traps filled with water, test connections and prove they are gastight and watertight. Plug vent-stack openings on roof and building drains where they leave building. Introduce air into piping system equal to pressure of 1-inch wg. Use U-tube or manometer inserted in trap of water closet to measure this pressure. Air pressure must remain constant without introducing additional air throughout period of inspection. Inspect plumbing fixture connections for gas and water leaks.

5. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained.

6. Prepare reports for tests and required corrective action.

E. Test force-main piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows:

SANITARY WASTE AND VENT PIPING 22 13 16 - 9

FOR OFFICIAL USE ONLY

Do not remove this notice Properly destroy documents when no longer needed

1. Leave uncovered and unconcealed new, altered, extended, or replaced force-main piping until it has been tested and approved. Expose work that was covered or concealed before it was tested.

2. Cap and subject piping to static-water pressure of 150 psig, without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for four hours. Leaks and loss in test pressure constitute defects that must be repaired.

3. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained.

4. Prepare reports for tests and required corrective action.

3.10 CLEANING

A. Clean interior of piping. Remove dirt and debris as work progresses.

B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work.

C. Place plugs in ends of uncompleted piping at end of day and when work stops.

END OF SECTION 22 13 16