This document provides details for a federal solicitation to replace the fire alarm system at the James L. King Federal Justice Building in Miami, Florida. The General Services Administration Southeast Sunbelt Region 4 is seeking proposals for a design-build project to install a new automatic fire alarm system throughout the 315,716 gross square foot building. Proposers must have experience designing and installing fire alarm systems that meet all applicable codes and standards including PBS-P100, NFPA 72, and NFPA 101. The scope of work involves removing the existing system and replacing all initiating devices, notification devices, wiring, tamper switches, flow switches, modules and other components with the exception of the new main fire alarm control panel and remote annunciator recently installed. Proposals are due no later than July 24, 2020. The selected contractor must complete both design and construction within 400 calendar days of the notice to proceed in order to minimize disruption to the occupied facility.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X FIRE SPRINKLER X STANDPIPE X FIRE PUMP

Return completed form to:

(check one) X

(check one) X

(check one) X

Certificate of competency #:

Name, address and phone# of contractor:

Daytime phone number: 754-703-2411

Inspector: Omar Oweis

FPC 17-000109

Name and address of building inspected: JL KING

99 NE 4TH STREET

MIAMI, FL 33132

All standpipe, hoses and system components located at the following address have been inspected and/or tested by a licensed Fire Sprinkler Contractor for proper operation as required by the adopted codes/standards are:

OPERATIONAL NON OPERATIONAL

The fire pump system, components located at the following address have been inspected and/or tested by a licensed Fire Sprinkler Contractor for proper operation as required by the adopted codes/standards are:

OPERATIONAL NON OPERATIONAL

City of Miami Fire Prevention Bureau 444 SW 2nd Ave, 10TH FL Miami, FL 33130

The fire sprinkler system, actuation devices and associated components located at the following address have been inspected and/or tested by a licensed Fire Sprinkler Contractor for proper operation as required by the adopted codes/standards are:

OPERATIONAL NON OPERATIONAL

AMERICAN FIRE SPRINKLER SERVICES, INC.

3371 NW 154th Terrace, Miami, Florida 33054 • Office: (305) 628-0100 • Fax: (305) 628-3556

INSPECTION/TEST CERTIFICATION

Miami, Florida 33054 305-628-0100

Inspector SignatureDate of Inspection Saturday, September 29, 2018

Note: IF THE SYSTEM IS OPERATIONAL: a record shall be maintained and a tag or sticker placed at the base of the system or in the fire pump room, if applicable, showing the date, telephone number and name of the company performing the inspection/test.

Omar Oweis

American Fire Sprinkler Services, Inc.

3371 N.W. 154th Terrace

Type of occupancy / specific use:

Name and address of owner or agent: INSPECTION EXPERTS JASON SAYLOR

9250 RUMSEY ROAD, SUITE #106

COLUMBIA, MD 21045

COMMERCIAL

QUARTERLY SEMI-ANNAUL X ANNUAL

INSPECTOR:

Property: Phone:

Address: Fax:

Owners’ Section: YES NO N/A X X X X X

Inspector's Section:

YES NO N/A

X X X

YES NO N/A

X X X

YES NO N/A

X X

YES NO N/A

X X X

YES NO N/A

X

X X X X X

Date installed X Main Drain Test: YES X NO N/A

If NO explain:

Location of Valve Before Static

0/0/167. Are all gauges up to date?

Pipe Size Residual

PRESSURE

See recommendation

1. Is a stock of sprinklers available?

F. Date sprinkler system installed:

2. Is the system riser or standpipe accessible?

3. Is there a minimum of 18"(457mm) clearance between the top of the storage and the sprinkler deflector?

3. Are all control valves (except OS & Y and gear operated indicating Butterfly valves) open until spring or torsion is felt in the rod then closed 1/4 turn?

1. Does the system have a hydraulic plate?

A. General

4. Are all quick response sprinklers in service for less than 20 years?

5. Are all sprinklers free of paint, corrosion or physical damage?

6. Are all piping free of corrosion, mechanical damage and not leaking?

1. Fire department connections identification sign(s) in place?

B. Control valves

1. Are all system control valves accessible in open or closed position locked, sealed or equipped with tamper switch ?

2. Are all valves identified by a sign?

2. Fire department connections visible, and accessible?

C. Alarm

1. Did the water flow alarm pass the test?

2. Is there a copy of NFPA available?

3. Sprinklers less than 50 years old

2. Did the supervisory signal pass the test?

D. Fire department connections

3. Fire department connections plugs or caps in place, couplings and swivels not damaged and rotate smoothly?

E. Sprinklers

E. Was the system free of actuations of devices or alarms since last inspection?

JL KING

99 NE 4TH STREET

MIAMI, FL 33132

A. Is building occupied?

E-Mail: sprinklerheads@bellsouth.net • Website: www.americanfiresprinklers.com

INSPECTION TEST & MAINTENANCE OF WET FIRE SPRINKLER SYSTEM

B. Has the classification of hazard of contents remained the same since last inspection?

C. All fire protection system in service?

D. Has the system remained in service without modification since last inspection?

INSPECTION DATE: Omar Oweis

754-703-2411 N/A

9/29/2018

QUARTERLY SEMI-ANNAUL X ANNUAL

Property: Phone:

Address: Fax:

YES NO N/A

X X X X X X X X

X X X X X X X X

X X X X

X X

X X X X X X X X X X

X X

24. Roof manifold valves good condition

25. Caps or plugs on FDC

26. FDC swivel rotation is nonbinding

32. Piping appears to be leak tight

34. Does building require a 5 year PRV inspection

27. FDC manifold valves good condition

28. FDC location plainly visible

29. FDC identification plate in place

30. Piping free of physical damage

31. Piping (exterior) is free of corrosion

33. Main drain at supply

21. Roof manifold equipped with hose valves

16. System free of visible water leaks

17. Hose valve outlets equipped with reducing hose adapter

22. Roof manifold hose valve caps in place

23. Roof manifold swivel rotation is nonbinding

10. Tamper switches appear operational

11. Alarm devices appear operational

18. Inspection of cabinet per NFPA 1962

19. Inspection of hose per NFPA 1962

20. Inspection of hose nozzle NFPA 1962

4. Backflow assembly valves sealed open

6. Backflow assembly operating OK

7. Valve area clear of obstructions

8. Valve area accessible

9. Roof manifold control valve closed

99 NE 4TH STREET N/A

MIAMI, FL 33132

Note: IF THE SYSTEM IS OPERATIONAL: a record shall be maintained and a tag or sticker placed at the base of the system or in the fire pump room, if applicable, showing the date, telephone number and name of the company performing the inspection/test

E-Mail: sprinklerheads@bellsouth.net • Website: www.americanfiresprinklers.com

A. General

1. System in service on inspection

2. System equipped with flow switch

3. Control valves open

INSPECTION TEST & MAINTENANCE OF WET STANDPIPE SYSTEM

12. Exterior fittings free of water leakage

13. Hose valve free of physical damage

14. Hose valve outlets with cap

15. Hose valve outlet thread in good condition

Inspector’s Section:

5. Backflow assembly valves locked/tamper open

754-703-2411

INSPECTION DATE: 9/29/2018 Omar Oweis

JL KING

Property: Phone:

Address: Fax:

QUARTERLY SEMI-ANNAUL X ANNUAL

Horizontal X

Electric X

Test Header X

Vertical Roof Manifold X

Desiel

PUMP MANUF. DRIVER MANUF.

TYPE DRIVER MODEL #

PUMP SERIAL NO. DRIVER SERIAL#

100 440/480 RATED CAPACITY GPM1000

DRIVER

VOLTAGE

110 PSI

TDH (TOTAL

DISHCARGE HEAD) FRAME/RPM/HP 365T 3525 100

95 PSI ROTATION

CUT IN 175 PSI RATED SPEED/HP 3555 87 BHP

CUT OUT 185 PSI IMP DIAMETER INCH

OSY SIZE 8” INCH

TS MANUF. BFV SIZE 8” INCH

TS MODEL #. BFV SIZE 8” INCH

TS SERIAL # BFV SIZE 8” INCH

PUMP VOLTAGE / HP BFV SIZE 8” INCH

JOCKEY PUMP JOCKEY PUMP CONTROLLER

PUMP MANUF.

PUMP MODEL NO.

PUMP SERIAL NO.

PUMP VOLTAGE / HP

CUT IN 165 PSI

CUT OUT 175 PSI

FTA500L-BF02B

14453

208-230/460 440/480 2VOLTAGE / / HP2

OWNER SECTION

YES NO

CONTROLLER MANUF.

XIS FIRE PUMP IN SERVICE?

Firetrol

X

CONTROLLER FIRE PUMP DRIVER

Firetrol Centrical peerless Lincoln

IS THE FIRE PUMP BEING TESTED EVERY WEEK? X

HAS THE FIRE PUMP REMAINED IN SERVICE SINCE LAST INSPECTION?

CONTROLLER MODEL NO. FTAJ1250AA100B Horizontal split case 5AEF11G

E-Mail: sprinklerheads@bellsouth.net • Website: www.americanfiresprinklers.com

INSPECTION TEST & MAINTENANCE OF FIRE PUMP SYSTEM

INSPECTION DATE: 9/29/2018 Omar Oweis

5M1140

CONTROLLER SERIAL NO. - HP 144925 476033 41921001542

CONTROLLER HP / VOLTAGE 460

NET PRESSURE 100%

LEFT NET PRESSURE 150%

115 PSI

______________ PSI

8.60”

TYPE:

TYPE:

TYPE:

TYPE:

TRANSFER SWITCH

460 TYPE:

CONTROLLER MODEL NO.

CONTROLLER SERIAL NO. HP

GRUNDFOS

#2-80

CONTROLLER MANUF.

Hubbell

CAT# 25017EFP

212045-1-1

N/A

JL KING 754-703-2411

99 NE 4TH STREET N/A

MIAMI, FL 33132

Property: Phone:

Address: Fax:

YES NO N/A

X X X X

X X X X X X X X X X

X

X

X

X X X X X

PSI /

discharge 185 psi 130 Net psi X

NOTES

12. Jockey pump operational?

N/A

8. Fire Pump controller indicating power on?

9. Transfer switch-indicating power on?

10. Circuit breaker & isolation switch on?

11. Circuit breaker & isolation switch exercised?

3. Pump house or room adequately lighted?

4. Pump monitored by fire alarm panel?

5. Ventilating louvers free to operate?

6. Suction/discharge & bypass control valves are in open position?

7. All piping is free of leaks?

99 NE 4TH STREET

MIAMI, FL 33132

INSPECTION ITEMS:

1. Pump in service on inspection?

2. Pump house or room dry, clean and at least 40 degrees Fahrenheit?

INSPECTION DATE: 9/29/2018 Omar Oweis

JL KING 754-703-2411

20. Packing boxes, bearings and pump casing free from over-heating

21. Shaft and play acceptable?

22. Pump coupling alignment acceptable?

23. Churn (no flow) suction

17. Pressure relief valve operating with proper pressure downstream while pump is running and free of damage?

13. Jockey Pump controller on and set on auto?

14. Fire pump & Jockey pump have separate pressure sensing lines?

18. Pump packing glands showing slight discharge, bolts and nuts free of corrosion? (Adjust if necessary)

19. Pump free of unusual noises or vibrations?

15. Fire pump & Jockey pump pressure sensing lines ½” diameter, located between discharge control valve and discharge check valve with proper test valves?

16. Pump circulation relief valve flowing water, while pump churns, free of damage and pipe adequate drainage?

Phone:

Fax:

TEST DRIVER PRESSURE PRESSURE NET NOZZLE TOTAL

SPEED DISCHARG

E SUCTION SIZE FLOW

RPM PSI PSI PSI INCHES 1 2 3 4 5

Churn 3577 185 55 130 100% 10 10 10

347 347 347 150% 22 18 10

515 465 347

A 100 200 300 400 500 600 700 800 900 1000 1100 1200 B 200 400 600 800 1000 1200 1400 1600 1800 2000 2100 2200 C 400 800 1200 2000 2200 2400 2800 3200 3600 4000 4500 5000

TOTAL FLOW Scale Used: B

FLOWS PITOT / FLOW

1¾"ROOF

3553 155 45 110 1¾"

DI

SC

HA

RG

E

3548 135 40 95

99 NE 4TH STREET N/A

MIAMI, FL 33132

INSPECTION DATE: 9/29/2018 Omar Oweis

JL KING 754-703-2411