This document provides details for a federal solicitation to replace the fire alarm system at the James L. King Federal Justice Building in Miami, Florida. The General Services Administration Southeast Sunbelt Region 4 is seeking proposals for a design-build project to install a new automatic fire alarm system throughout the 315,716 gross square foot building. Proposers must have experience designing and installing fire alarm systems that meet all applicable codes and standards including PBS-P100, NFPA 72, and NFPA 101. The scope of work involves removing the existing system and replacing all initiating devices, notification devices, wiring, tamper switches, flow switches, modules and other components with the exception of the new main fire alarm control panel and remote annunciator recently installed. Proposals are due no later than July 24, 2020. The selected contractor must complete both design and construction within 400 calendar days of the notice to proceed in order to minimize disruption to the occupied facility.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X FIRE SPRINKLER X STANDPIPE X FIRE PUMP
Return completed form to:
(check one) X
(check one) X
(check one) X
Certificate of competency #:
Name, address and phone# of contractor:
Daytime phone number: 754-703-2411
Inspector: Omar Oweis
FPC 17-000109
Name and address of building inspected: JL KING
99 NE 4TH STREET
MIAMI, FL 33132
All standpipe, hoses and system components located at the following address have been inspected and/or tested by a licensed Fire Sprinkler Contractor for proper operation as required by the adopted codes/standards are:
OPERATIONAL NON OPERATIONAL
The fire pump system, components located at the following address have been inspected and/or tested by a licensed Fire Sprinkler Contractor for proper operation as required by the adopted codes/standards are:
OPERATIONAL NON OPERATIONAL
City of Miami Fire Prevention Bureau 444 SW 2nd Ave, 10TH FL Miami, FL 33130
The fire sprinkler system, actuation devices and associated components located at the following address have been inspected and/or tested by a licensed Fire Sprinkler Contractor for proper operation as required by the adopted codes/standards are:
OPERATIONAL NON OPERATIONAL
AMERICAN FIRE SPRINKLER SERVICES, INC.
3371 NW 154th Terrace, Miami, Florida 33054 • Office: (305) 628-0100 • Fax: (305) 628-3556
INSPECTION/TEST CERTIFICATION
Miami, Florida 33054 305-628-0100
Inspector SignatureDate of Inspection Saturday, September 29, 2018
Note: IF THE SYSTEM IS OPERATIONAL: a record shall be maintained and a tag or sticker placed at the base of the system or in the fire pump room, if applicable, showing the date, telephone number and name of the company performing the inspection/test.
Omar Oweis
American Fire Sprinkler Services, Inc.
3371 N.W. 154th Terrace
Type of occupancy / specific use:
Name and address of owner or agent: INSPECTION EXPERTS JASON SAYLOR
9250 RUMSEY ROAD, SUITE #106
COLUMBIA, MD 21045
COMMERCIAL
QUARTERLY SEMI-ANNAUL X ANNUAL
INSPECTOR:
Property: Phone:
Address: Fax:
Owners’ Section: YES NO N/A X X X X X
Inspector's Section:
YES NO N/A
X X X
YES NO N/A
X X X
YES NO N/A
X X
YES NO N/A
X X X
YES NO N/A
X
X X X X X
Date installed X Main Drain Test: YES X NO N/A
If NO explain:
Location of Valve Before Static
0/0/167. Are all gauges up to date?
Pipe Size Residual
PRESSURE
See recommendation
1. Is a stock of sprinklers available?
F. Date sprinkler system installed:
2. Is the system riser or standpipe accessible?
3. Is there a minimum of 18"(457mm) clearance between the top of the storage and the sprinkler deflector?
3. Are all control valves (except OS & Y and gear operated indicating Butterfly valves) open until spring or torsion is felt in the rod then closed 1/4 turn?
1. Does the system have a hydraulic plate?
A. General
4. Are all quick response sprinklers in service for less than 20 years?
5. Are all sprinklers free of paint, corrosion or physical damage?
6. Are all piping free of corrosion, mechanical damage and not leaking?
1. Fire department connections identification sign(s) in place?
B. Control valves
1. Are all system control valves accessible in open or closed position locked, sealed or equipped with tamper switch ?
2. Are all valves identified by a sign?
2. Fire department connections visible, and accessible?
C. Alarm
1. Did the water flow alarm pass the test?
2. Is there a copy of NFPA available?
3. Sprinklers less than 50 years old
2. Did the supervisory signal pass the test?
D. Fire department connections
3. Fire department connections plugs or caps in place, couplings and swivels not damaged and rotate smoothly?
E. Sprinklers
E. Was the system free of actuations of devices or alarms since last inspection?
JL KING
99 NE 4TH STREET
MIAMI, FL 33132
A. Is building occupied?
E-Mail: sprinklerheads@bellsouth.net • Website: www.americanfiresprinklers.com
INSPECTION TEST & MAINTENANCE OF WET FIRE SPRINKLER SYSTEM
B. Has the classification of hazard of contents remained the same since last inspection?
C. All fire protection system in service?
D. Has the system remained in service without modification since last inspection?
INSPECTION DATE: Omar Oweis
754-703-2411 N/A
9/29/2018
QUARTERLY SEMI-ANNAUL X ANNUAL
Property: Phone:
Address: Fax:
YES NO N/A
X X X X X X X X
X X X X X X X X
X X X X
X X
X X X X X X X X X X
X X
24. Roof manifold valves good condition
25. Caps or plugs on FDC
26. FDC swivel rotation is nonbinding
32. Piping appears to be leak tight
34. Does building require a 5 year PRV inspection
27. FDC manifold valves good condition
28. FDC location plainly visible
29. FDC identification plate in place
30. Piping free of physical damage
31. Piping (exterior) is free of corrosion
33. Main drain at supply
21. Roof manifold equipped with hose valves
16. System free of visible water leaks
17. Hose valve outlets equipped with reducing hose adapter
22. Roof manifold hose valve caps in place
23. Roof manifold swivel rotation is nonbinding
10. Tamper switches appear operational
11. Alarm devices appear operational
18. Inspection of cabinet per NFPA 1962
19. Inspection of hose per NFPA 1962
20. Inspection of hose nozzle NFPA 1962
4. Backflow assembly valves sealed open
6. Backflow assembly operating OK
7. Valve area clear of obstructions
8. Valve area accessible
9. Roof manifold control valve closed
99 NE 4TH STREET N/A
MIAMI, FL 33132
Note: IF THE SYSTEM IS OPERATIONAL: a record shall be maintained and a tag or sticker placed at the base of the system or in the fire pump room, if applicable, showing the date, telephone number and name of the company performing the inspection/test
E-Mail: sprinklerheads@bellsouth.net • Website: www.americanfiresprinklers.com
A. General
1. System in service on inspection
2. System equipped with flow switch
3. Control valves open
INSPECTION TEST & MAINTENANCE OF WET STANDPIPE SYSTEM
12. Exterior fittings free of water leakage
13. Hose valve free of physical damage
14. Hose valve outlets with cap
15. Hose valve outlet thread in good condition
Inspector’s Section:
5. Backflow assembly valves locked/tamper open
754-703-2411
INSPECTION DATE: 9/29/2018 Omar Oweis
JL KING
Property: Phone:
Address: Fax:
QUARTERLY SEMI-ANNAUL X ANNUAL
Horizontal X
Electric X
Test Header X
Vertical Roof Manifold X
Desiel
PUMP MANUF. DRIVER MANUF.
TYPE DRIVER MODEL #
PUMP SERIAL NO. DRIVER SERIAL#
100 440/480 RATED CAPACITY GPM1000
DRIVER
VOLTAGE
110 PSI
TDH (TOTAL
DISHCARGE HEAD) FRAME/RPM/HP 365T 3525 100
95 PSI ROTATION
CUT IN 175 PSI RATED SPEED/HP 3555 87 BHP
CUT OUT 185 PSI IMP DIAMETER INCH
OSY SIZE 8” INCH
TS MANUF. BFV SIZE 8” INCH
TS MODEL #. BFV SIZE 8” INCH
TS SERIAL # BFV SIZE 8” INCH
PUMP VOLTAGE / HP BFV SIZE 8” INCH
JOCKEY PUMP JOCKEY PUMP CONTROLLER
PUMP MANUF.
PUMP MODEL NO.
PUMP SERIAL NO.
PUMP VOLTAGE / HP
CUT IN 165 PSI
CUT OUT 175 PSI
FTA500L-BF02B
14453
208-230/460 440/480 2VOLTAGE / / HP2
OWNER SECTION
YES NO
CONTROLLER MANUF.
XIS FIRE PUMP IN SERVICE?
Firetrol
X
CONTROLLER FIRE PUMP DRIVER
Firetrol Centrical peerless Lincoln
IS THE FIRE PUMP BEING TESTED EVERY WEEK? X
HAS THE FIRE PUMP REMAINED IN SERVICE SINCE LAST INSPECTION?
CONTROLLER MODEL NO. FTAJ1250AA100B Horizontal split case 5AEF11G
E-Mail: sprinklerheads@bellsouth.net • Website: www.americanfiresprinklers.com
INSPECTION TEST & MAINTENANCE OF FIRE PUMP SYSTEM
INSPECTION DATE: 9/29/2018 Omar Oweis
5M1140
CONTROLLER SERIAL NO. - HP 144925 476033 41921001542
CONTROLLER HP / VOLTAGE 460
NET PRESSURE 100%
LEFT NET PRESSURE 150%
115 PSI
______________ PSI
8.60”
TYPE:
TYPE:
TYPE:
TYPE:
TRANSFER SWITCH
460 TYPE:
CONTROLLER MODEL NO.
CONTROLLER SERIAL NO. HP
GRUNDFOS
#2-80
CONTROLLER MANUF.
Hubbell
CAT# 25017EFP
212045-1-1
N/A
JL KING 754-703-2411
99 NE 4TH STREET N/A
MIAMI, FL 33132
Property: Phone:
Address: Fax:
YES NO N/A
X X X X
X X X X X X X X X X
X
X
X
X X X X X
PSI /
discharge 185 psi 130 Net psi X
NOTES
12. Jockey pump operational?
N/A
8. Fire Pump controller indicating power on?
9. Transfer switch-indicating power on?
10. Circuit breaker & isolation switch on?
11. Circuit breaker & isolation switch exercised?
3. Pump house or room adequately lighted?
4. Pump monitored by fire alarm panel?
5. Ventilating louvers free to operate?
6. Suction/discharge & bypass control valves are in open position?
7. All piping is free of leaks?
99 NE 4TH STREET
MIAMI, FL 33132
INSPECTION ITEMS:
1. Pump in service on inspection?
2. Pump house or room dry, clean and at least 40 degrees Fahrenheit?
INSPECTION DATE: 9/29/2018 Omar Oweis
JL KING 754-703-2411
20. Packing boxes, bearings and pump casing free from over-heating
21. Shaft and play acceptable?
22. Pump coupling alignment acceptable?
23. Churn (no flow) suction
17. Pressure relief valve operating with proper pressure downstream while pump is running and free of damage?
13. Jockey Pump controller on and set on auto?
14. Fire pump & Jockey pump have separate pressure sensing lines?
18. Pump packing glands showing slight discharge, bolts and nuts free of corrosion? (Adjust if necessary)
19. Pump free of unusual noises or vibrations?
15. Fire pump & Jockey pump pressure sensing lines ½” diameter, located between discharge control valve and discharge check valve with proper test valves?
16. Pump circulation relief valve flowing water, while pump churns, free of damage and pipe adequate drainage?
Phone:
Fax:
TEST DRIVER PRESSURE PRESSURE NET NOZZLE TOTAL
SPEED DISCHARG
E SUCTION SIZE FLOW
RPM PSI PSI PSI INCHES 1 2 3 4 5
Churn 3577 185 55 130 100% 10 10 10
347 347 347 150% 22 18 10
515 465 347
A 100 200 300 400 500 600 700 800 900 1000 1100 1200 B 200 400 600 800 1000 1200 1400 1600 1800 2000 2100 2200 C 400 800 1200 2000 2200 2400 2800 3200 3600 4000 4500 5000
TOTAL FLOW Scale Used: B
FLOWS PITOT / FLOW
1¾"ROOF
3553 155 45 110 1¾"
DI
SC
HA
RG
E
3548 135 40 95
99 NE 4TH STREET N/A
MIAMI, FL 33132
INSPECTION DATE: 9/29/2018 Omar Oweis
JL KING 754-703-2411