472-26238.RWG Kinross CF & NRT Electrical Upgrades_Plans.pdf
PDF 9 MB Posted
- Solicitation number
- RFQ 171 260000000411 3
- Issued by
- Chippewa County, Michigan
About this file
This electrical engineering plans and specifications document for the State of Michigan Department of Technology, Management and Budget outlines Phase 2 electrical upgrades at the Kinross Correctional Facility and NRT Facility in Kinchloe, Michigan. The project (File Number 472/26238.RWG, Matrix Project Number 260053.00) involves comprehensive medium voltage and low voltage electrical system upgrades including the installation of new pad mount transformers ranging from 75 kVA to 500 kVA, new pad mount switches, underground and overhead conduit systems, branch circuit modifications, and associated electrical infrastructure. The scope encompasses demolition of existing electrical systems, installation of new primary and secondary feeders using 15kV shielded copper wire, modifications to multiple building panels (Tech Building, Maintenance Building, MSI Building, Admin Building, and Warehouse Building), and upgrades to serve a new Training Center. The project is issued for bidding with an issue date of July 27, 2026. Contractors are required to conduct pre-bid site walks to determine the exact extent of work required before submitting proposals.
Key specifications mandate that all electrical work comply with the National Electrical Code and local authority requirements. Conduit installation requirements vary based on height, with minimum raceway sizes of 3/4" trade size and specific strapping and security hardware requirements using Torx T-25 fasteners with center rejection pins. All electrical outages are limited to a maximum of two hours, with portable generators required for extended shutdowns to maintain perimeter detection, video management, and life safety systems; outages must be coordinated minimum two weeks prior with MDOC leadership. The project requires hydrovac excavation and directional boring for underground conduit installation, with GPRS surveys completed prior to any excavation. Arc flash studies, breaker settings, and trip settings are the responsibility of Orion Engineering Company. The document provides detailed electrical symbols, abbreviations, demolition notes indicating transformer removals and retentions, and grounding specifications requiring exothermic welded connections compliant with NEC sections 250.52 through 250.68. Contractors must obtain approval for all shop drawings prior to installation, with work performed without approved drawings undertaken at the contractor's risk.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ENGINEER
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
KINROSS CORRECTIONAL AND NRT FACILITY
ELECTRICAL UPGRADES - PHASE 2
KINCHLOE, MICHIGAN
FILE NUMBER: 472/26238.RWG
FUNDING CODE: 472MTUMAINTPROJ
MATRIX PROJECT NUMBER: 260053.00
PROJECT LOCATION
CODES
N SITE MAP
DRAWING INDEX
SCOPE OF WORK
COVER SHEET
COVER SHEET
file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
X
X
X
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE
DOCK LIGHT FIXTURE
TELEPHONE / DATA OUTLET
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
ELECTRICAL SYMBOLS LEGEND
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER
MAGNETIC STARTER
DISCONNECT SWITCH
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
DESIGNATIONS
(by E.C.)
(by others)
TT
G
WW
PC
CT
TS
T
H
TC
IC
T
1,3
OR
PM
WM
BD
UFD
F S
J
J
D
WH
PP
J
CEILING MOUNTED WIFI
DIGITAL EQUIPMENT METER, AS REQUIRED
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST (E)
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
1. CIRCUITS TO BE EXTENDED SHALL BE PULLED BACK TO THE FIRST PULL/JUNCTION
BOX IN THE CIRCUIT AND RUN NEW WIRE TO THE NEW PANEL.
2. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE MATERIAL TO MAINTAIN
ORIGINAL RATING.
3. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS ARE TO BE
SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL RATING.
4. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
5. CONDUITS AND WIRES SHALL BE INSTALLED STRAIGHT, LEVEL, AND PARALLEL OR
PERPENDICULAR TO THE BUILDING LINES.
6. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO
DETERMINE THE EXACT EXTENT OF THE WORK REQUIRED BEFORE BIDDING THE
PROJECT.
7. REMOVE ALL EXISTING EXPOSED CONDUIT, WIRE, AND EQUIPMENT NOT TO BE
RE-USED WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
8. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING THE SURFACES
TO MATCH ADJACENT.
9. EXISTING WORK WHICH IS PRESENTLY CONCEALED, WHICH WILL REMAIN CONCEALED,
AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED NOT BE
REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND
THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.
10. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
11. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT VOLTAGES AND LOADS PRIOR TO
INSTALLING SERVICE TO EQUIPMENT.
12. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENTS AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
13. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT RACEWAYS SHALL
BE LIQUID-TITE, MAXIMUM 36" LENGTH AND MUST BE APPROVED BY PSC AND MDOC
PROJECT MANAGER. REFER TO SPECIFICATION 260533 - RACEWAY AND BOXES FOR
ELECTRICAL SYSTEMS.
14. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
14.1. STRAP DISTANCE: 5 FEET.
14.2. STRAP TYPE: 2 HOLE.
14.3. SECURITY HARDWARE:
14.3.1. TORX T-25 WITH CENTER REJECTION PIN.
14.3.2. HEX HEAD CONCRETE SCREWS WITH NO SCREWDRIVER SLOT.
14.3.3. EXPANSION POUND-IN ANCHORS WITH NO SCREWDRIVER SLOT THAT DO
NOT REQUIRE TO BE EXPLOSIVELY DRIVEN.
14.3.4. OR PRE-APPROVED HARDWARE.
14.4. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
14.5. FITTINGS: COMPRESSION.
14.6. BOXES:
14.6.1. SURFACE MOUNTED:
14.6.1.1. BELL BOX: FS TYPE, WITH SQUARE HEAD KO SEAL.
14.6.2. NO KNOCKOUTS, DRILLED AS REQUIRED.
14.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
15. ALL CONDUIT 10 FOOT AND BELOW SHALL MEET THE FOLLOWING REQUIREMENTS:
15.1. STRAP DISTANCE: 3 FEET.
15.2. STRAP TYPE: 2 HOLE.
15.3. SECURITY HARDWARE:
15.3.1. TORX T-25 WITH CENTER REJECTION PIN.
15.3.2. HEX HEAD CONCRETE SCREWS WITH NO SCREWDRIVER SLOT.
15.3.3. EXPANSION POUND-IN ANCHORS WITH NO SCREWDRIVER SLOT THAT DO
NOT REQUIRE TO BE EXPLOSIVELY DRIVEN.
15.3.4. OR PRE-APPROVED HARDWARE.
15.4. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
15.5. FITTINGS: COMPRESSION.
15.6. BOXES:
15.6.1. SURFACE MOUNTED:
15.6.1.1. BELL BOX: FS TYPE, WITH SQUARE HEAD KO SEAL.
15.6.1.2. NO KNOCKOUTS, DRILLED AS REQUIRED.
15.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
16. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE
CEILINGS IS ACCEPTABLE.
16.1. ALL EXPOSED WIRING ABOVE CEILINGS SHALL BE INSTALLED WITH J-HOOKS. DO
NOT CONNECT TO EXISTING CEILING TIE WIRES.
17. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICES CUT INTO WALL.
18. ALL LOCATIONS WHERE THE WALLS CAN NOT BE FISHED SHALL BE SURFACE
MOUNTED CONDUIT FOLLOWING NOTES 12 THROUGH 14 ABOVE.
19. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE
EPC-40-PVC, OR HDPE. ALL EXTERIOR ABOVE GROUND CONDUIT SHALL BE GRC.
20. ALL ELECTRICAL OUTAGES SHALL NOT LAST OVER 2-HOURS. IF A WINDOW OF
GREATER THAN 2-HOURS FOR AN ELECTRICAL SHUT DOWN OR CUT OVER, THEN
PORTABLE GENERATORS SHALL BE USED TO REPLACE ALL PERIMETER DETECTION,
VIDEO MANAGEMENT, LIFE SAFETY, AND ANY OTHER ELECTRICAL SERVICE REQUIRED.
ALL OUTAGES AND CUT OVERS SHALL BE COORDINATED A MINIMUM OF 2-WEEKS
PRIOR TO WORK, INCLUDING A HOUR BY HOUR SCHEDULE MUST BE SUBMITTED TO
MDOC LEADERSHIP AND THE FACILITY FOR REVIEW.
21. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,
RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.
22. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.
23. CONTRACTOR SHALL NOTIFY PSC OF ANY EXISTING INSTALLATIONS NOT MEETING
THESE STANDARDS PRIOR TO STARTING WORK IN THE AREA.
24. THESE DRAWINGS HAVE BEEN SUBMITTED AND APPROVED BY LOCAL AUTHORITIES
HAVING JURISDICTION. ANY COMMENTS THAT WERE PROVIDED BY THE LOCAL
AUTHORITIES HAVING JURISDICTION HAVE BEEN ADDRESSED, AND THE DRAWINGS
HAVE BEEN MODIFIED ACCORDINGLY. BECAUSE OF THIS, RESPONSIBILITY OF ANY
ISSUES THAT ARISE UPON FINAL INSPECTION SHALL NOT FALL UPON MATRIX
CONSULTING ENGINEERS.
25. ALL EXCAVATION SHALL BE PERFORMED USING HYDROVAC.
26. ALL UNDERGROUND CONDUIT SHALL BE INSTALLED BY DIRECTIONAL BORING.
27. A GPRS SURVEY SHALL BE COMPLETED PRIOR TO ANY EXCAVATION OR DIRECTIONAL
BORING.
GENERAL ELECTRICAL NOTES
VI
AV
B
C
DC
M
B
KP
CR
SS
AS
TS
G GLASS BREAK
TEACHER STATION
ADMINISTRATION STATION
STUDENT STATION
CARD READER
BELL
AUDIO / VIDEO INPUT
VIDEO INPUT
WALL MOUNTED SPEAKER / CLOCK COMBO
WALL MOUNTED SPEAKERS
DUAL FACE CLOCK
CCTV CONTROL PANELCCTV
SECURITY SYSTEM CONTROL PANEL
KEY PAD
BEAM DETECTOR
MOTION DETECTOR
DOOR CONTACT
CAMERA
V
S
C
M
I
SINGLE FACE CLOCK
SOUND and SIGNAL
INTERCOM OUTLET
MICROPHONE OUTLET
TELEVISION OUTLET
CHIME
BUZZER
VOLUME CONTROL
SPEAKER
B
DS ELECTRIC DOOR STRIKE
CP
TS
UNINTERRUPTABLE POWER SUPPLYUPS
1. ORION ENGINEERING COMPANY IS RESPONSIBLE FOR ARC
FLASH STUDY, BREAKER SETTINGS, FUSE SIZES, AND TRIP
SETTINGS. CONTACT KIP JONES: KJONES@ORION-US.COM,
517-740-8885
GENERAL MEDIUM VOLTAGE
ELECTRICAL NOTES
file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
ELECTRICAL
NOTES ABBREV. &
SYMBOLS
ELECTRICAL NOTES,
ABBREVIATIONS, SYMBOLS
AND DETAILS
T
T
T
T
T
T
T
#1
#5
25 KVA
#7
#2#3
#4
#6 #8
#9 #10 #11 #12 #13 #14
#15
#16
#17
#18
#19
#20
#21
#23
#24
#25
#22
#26
#27 #28
#29 #30
2 22 2 2 2 2 2
2 2
#31
#32
WAREHOUSE
EX
METER
EXIST
GENERATOR
#33
EXIST
GENERATOR
K-UNIT
TECH
BUILDING
STEAM
BUILDING
ADMIN
BUILDING
MAINTENANCE
BUILDING
MSI
BUILDING
BUILDING
BUILDING
K-UNIT
GENERATOR
BLDG
EXIST
PNL 'A' EXIST
PNL 'MDP'
EXIST
PNL 'MDP'
EXIST
PNL 'MDP' 12
EXIST
PNL 'MDP'
13 13
13 13 13
75 KVA
75 KVA
75 KVA
150 KVA
150 KVA
45 KVA
225 KVA
75 KVA
150 KVA
225 KVA
EXISTING MEDIUM VOLTAGE OVERHEAD UTILITY LINES TO REMAIN.
REMOVE EXISTING OVERHEAD MEDIUM VOLTAGE UTILITY LINES.
REMOVE EXISTING MEDIUM VOLTAGE UNDERGROUND FEEDER.
REMOVE EXISTING PAD MOUNT TRANSFORMER.
EXISTING PAD MOUNT TRANSFORMER TO REMAIN.
REMOVE EXISTING OVERHEAD SECONDARY SERVICE CONDUCTORS.
REMOVE EXISTING BUILDING.
EXISTING MEDIUM VOLTAGE UNDERGROUND FEEDER TO REMAIN.
REMOVE EXISTING UNDERGROUND SECONDARY FEEDERS.
REMOVE EXISTING GENERATOR AND BUILDING. TURN GENERATOR OVER TO
MDOC. GENERATOR AND BUILDING TO REMAIN UNTIL NEW TRAINING
CENTER IS FULLY OPERATIONAL.
REMOVE EXISTING OVERHEAD GENERATOR FEEDER TO EXISTING TEMP
TRAINING BUILDING.
REMOVE EXISTING PANEL 'MDP'. EXISTING BRANCH CIRCUITS TO REMAIN
AND TRANSFERED TO NEW PANEL 'MDP'.
EXISTING MEDIUM VOLTAGE OVERHEAD UTILITY LINES TO REMAIN UNTIL
THE NEW TRAINING CENTER IS FULLY OPERATIONAL.
EXISTING OVERHEAD GENERATOR FEEDER TO EXISTING TEMP TRAINING
BUILDING TO REMAIN UNTIL NEW TRAINING CENTER IS FULLY OPERATIONAL.
DEMOLITION NOTES
file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
N PHASE 2 SITE PLAN - ELECTRICAL DEMOLITION
SCALE: 1" = 100'
25080400 20 160
E-200
JFS
SITE PLAN
ELECTRICAL
DEMOLITION
MVSW #1
MVSW #2
T2
T8
T9
T7
MVSW #9
EXIST
T6
EXIST
T5
NEW
T1
MVSW #8
MVSW
#5
T3
T4
#2#3
#4
EXIST
GENERATOR
K-UNIT
TECH
BUILDING
STEAM
BUILDING
ADMIN
BUILDING
MAINTENANCE
BUILDING
MSI
BUILDING
BUILDING
BUILDING
NEW
TRAINING
CENTER
K-UNIT
GENERATOR
BLDG
EXIST
PNL
EXIST
PNL
EXIST
WAREHOUSE
BUILDING
PNL 'A'
NEW
WAREHOUSE
BUILDING
PNL 'MDP'
NEW
MAINTENANCE
BUILDING
PNL 'MDP'
NEW MSI
BUILDING
PNL 'MDP'
NEW TECH
BUILDING
PNL 'MDP'
EXIST
PNL 'MDP'
MVSW #7
MVSW
#3
MVSW #4
MVSW
#6
MVSW
#10
WAREHOUSE
BUILDING
ELECTRICAL KEY NOTES
REFER TO PANEL SCHEDULES FOR QUANTITY OF BRANCH CIRCUITS TO
RETERMINATE FOR NEW PANEL 'MDP'.
file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
N PHASE 2 SITE PLAN - POWER
SCALE: 1" = 100'
25080400 20 160
E-201
JFS
SITE PLAN
MEDIUM VOLTAGE
POWER - NEW
150A
LOOP
SWITCH
#1
150A
LOOP
SWITCH
#2
200A
INCOMING
LINE
12.47kV 208/120V
150 KVA
TECH BUILDING
NEW PAD MOUNT
TRANSFORMER
400A
12.47kV 208/120V
75 kVA
BUILDING 240 AND 243
NEW PAD MOUNT
TRANSFORMER
200A
SCALE: NONE
MEDIUM VOLTAGE
RISER DIAGRAM - NEW
12.47kV 208/120V
75 KVA
ADMIN BUILDING
EXISTING PAD MOUNT TRANSFORMER
12.47kV 208/120V
150 kVA
K-UNIT
EXISTING PAD MOUNT TRANSFORMER
12.47kV 208/120V
75 kVA
MSI BUILDING
EXISTING PAD MOUNT TRANSFORMER
M
UTILITY CO.
#2#3 #4 #7
#6
#5
#8
#9 #10 #11 #12 #13 #14
#15
#16 #17 #18
#19
#20
#21
#22
#24
#23
#25 #26 #27 #28 #29 #30
12.47kV 208/120V
225 KVA
POWERHOUSE
EXISTING PAD MOUNT TRANSFORMER
SCALE: NONE
MEDIUM VOLTAGE
RISER DIAGRAM - DEMOLITION
1 1
2 2 2 2 2 2 2 2
2 2
2 2 2 2
#31
#32
12.47kV 480/277V
500 KVA
NEW TRAINING BUILDING
NEW PAD MOUNT
TRANSFORMER
EXIST
(4) #3/0
2" CND
M
UTILITY CO.
EXISTING MEDIUM VOLTAGE OVERHEAD UTILITY LINES TO REMAIN.
REMOVE EXISTING OVERHEAD MEDIUM VOLTAGE UTILITY LINES.
REMOVE EXISTING MEDIUM VOLTAGE UNDERGROUND FEEDER.
REMOVE EXISTING PAD MOUNT TRANSFORMER.
EXISTING PAD MOUNT TRANSFORMER TO REMAIN.
REMOVE EXISTING OVERHEAD SECONDARY SERVICE CONDUCTORS.
REMOVE EXISTING BUILDING.
EXISTING MEDIUM VOLTAGE UNDERGROUND FEEDER TO REMAIN.
REMOVE EXISTING UNDERGROUND SECONDARY FEEDER.
REMOVE EXISTING TRANSFORMER MOUNTED UTILITY KWH METER.
EXISTING UNDERGROUND MEDIUM VOLTAGE FEEDER TO REMAIN.
EXISTING UNDERGROUND LOW VOLTAGE FEEDER TO REMAIN.
REMOVE EXISTING PANEL 'MDP'. EXISTING BRANCH CIRCUITS TO REMAIN
AND TRANSFERED TO NEW PANEL 'MDP'.
EXISTING PANEL TO REMAIN.
DEMOLITION NOTES
EXIST
(4) #500 KCMIL
4" CND
(2) SETS OF
(4) 350KCMIL
3" CND
TO BE INSTALLED AS PART OF NORTHERN
REGION TRAINING AND PROFESSIONAL
DEVELOPMENT CENTER PROJECT.
DTMB FILE NO. 472/23280.SDW
TO BLDG #240
EXIST MAIN PANEL
TO BLDG #243
EXIST MAIN PANELNEW
(4) #4/0
(1) #6 GND,
(1) 2" CND
TO UNIT K
EXISTING TAPS
EXISTING
PANEL
NEW
WH 'MDP'
208/120 3 Ø, 4W
400A MCB
PANEL
EXIST
WH SERVICE #2
208/120 3 Ø, 4W
200A MCB
NEW
(4) #3/0
(1) #6 GND,
(1) 2" CND
600A
NEW
(4) #500 KCMIL
(1) #3 GND,
(1) 4" CND
NEW
(4) #500 KCMIL
(1) #3 GND,
(1) 4" CND
#33
PANEL
NEW
PANEL 'MDP'
208/120 3 Ø, 4W
400A MCB
PANEL
NEW
MAINT 'MDP'
208/120 3 Ø, 4W
400A MCB
PANEL
NEW
TECH 'MDP'
208/120 3 Ø, 4W
400A MCB
NEW
(4) #500 KCMIL
(1) #3 GND,
(1) 4" CND
PANEL
EXIST
MSI 'MDP'
208/120 3 Ø, 4W
MLO
PANEL
EXIST
MAINT 'MDP'
208/120 3 Ø, 4W
MLO
PANEL
EXIST
WH 'MDP'
208/120 3 Ø, 4W
200A MLO
PANEL
EXIST
WH SERVICE #2
208/120 3 Ø, 4W
200A MLO
PANEL
EXIST
TECH 'MDP'
208/120 3 Ø, 4W
MLO
12.47KV 3PH 3W
M
UTILITY CO.
EXIST
EXIST
POLE
#3
EXIST
EXIST
POLE
#2
EXIST
EXIST
POLE
#4
EXIST
SPARE
FUSED
SWITCH
NEW
(4) #500 KCMIL
(1) #3 GND,
(1) 4" CND
MVSW #4
NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
T3
MVSW #5
T4
200A
MVSW #3MVSW #2
MVSW #10 MVSW #9 MVSW #8 MVSW #7 MVSW #6
T2 T1
T9 T8 T7 T6 T5
12.47kV 208/120V
150 KVA
K-UNIT
NEW PAD MOUNT
TRANSFORMER
400A
12.47kV 208/120V
150 KVA
WAREHOUSE BUILDING
NEW PAD MOUNT
TRANSFORMER
400A
12.47kV 208/120V
150 KVA
MSI BUILDING
NEW PAD MOUNT
TRANSFORMER
400A
12.47kV 208/120V
150 KVA
MAINT BUILDING
NEW PAD MOUNT
TRANSFORMER
400A
12.47kV 208/120V
75 KVA
ADMIN BUILDING
EXIST PAD MOUNT
TRANSFORMER
12.47kV 208/120V
225 KVA
POWERHOUSE
EXISTING PAD MOUNT
TRANSFORMER
MVSW #1
EXIST
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
15kV PAD MOUNT
SWITCH
600A
400A200A
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
NEW
(3) #1/0 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND NEW
(3) #2 15KV 133% SHIELDED
MV-105 COPPER WIRE.
(1) #6 GND,
(1) 4" CND
25 KVA
225 KVA
150 KVA
75 KVA
150 KVA
45 KVA
75 KVA
20A SPARE
15kV PAD MOUNT
SWITCH
600A
20A SPARE
15kV PAD MOUNT
SWITCH
600A
20A SPARE
15kV PAD MOUNT
SWITCH
600A
10A SPARE
15kV PAD MOUNT
SWITCH
600A
15A SPARE
15kV PAD MOUNT
SWITCH
600A
60A SPARE
15kV PAD MOUNT
SWITCH
600A
20A SPARE
15kV PAD MOUNT
SWITCH
600A
10A SPARE
15kV PAD MOUNT
SWITCH
600A
20A SPARE
15kV PAD MOUNT
SWITCH
600A
T5
T6 file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
ELECTRICAL
DETAILS
MEDIUM VOLTAGE
RISER DIAGRAM
DEMOLITION AND NEW
MAIN SERVICE
DISCONNECT
UTILITY
TRANSFORMER
N G
MAIN BONDING
JUMPERGROUNDING ELECTRODE
CONDUCTOR
NEUTRAL
CONDUCTOR
TYPICAL PAD MOUNT TRANSFORMER
SERVICE GROUNDING DETAIL
SCALE: N.T.S.
NOTES:
1. ALL GROUNDING CONDUCTOR CONNECTIONS TO MAIN BUILDING
GROUND BUS SHALL BE EXOTHERMIC WELDED.
2. NEC, SECTIONS 250.52, 250.53, 250.64, 250.66, AND 250.68 - GROUNDING
ELECTRODES, GROUNDING ELECTRODE CONDUCTORS, AND BONDING
JUMPERS SHALL COMPLY WITH THE CODE. PROVIDE A GROUNDING
DETAIL IF USED FOR GENERATOR. IF NOT BEING USED PROVIDE THE
CORRECT SIGNAGE PER 701.7(B).
3. PROVIDE GROUND ENHANCING MATERIAL (GEM) FOR ALL GROUND
RODS. INSTALL GEM IN ACCORDANCE WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS
GROUND ROD SPACING
10'-0" MIN (TYPICAL)
#2/0 BARE STRANDED COPPER WIRE,
BURIED 24" MIN BELOW GRADE
(TYPICAL)
3/4" X 10'-0" LONG COPPERWELD
GROUND ROD BURIED
24" MIN. BELOW GRADE
(TYPICAL)
NEW CONCRETE PAD FOR LOW PROFILE
MEDIUM VOLTAGE PAD MOUNT SWITCH DETAIL
SCALE: N.T.S.
EARTH
NEW CONCRETE PAD WITH
8" ABOVE GRADE
NEW LOW PROFILE PAD MOUNT SWITCH
SLAB GRADE
EXPANSION JOINT
8" 4"
NEW CONCRETE PAD WITH
12" ABOVE GRADE
SWITCH COMPARTMENT DIVIDER
(TYP.)
CONDUIT/CABLE STUB INTO BASE
(TYP)
CONDUIT/CABLE STUB INTO BASE
(TYP)
18"
MIN.
18"
MIN.
18"
MIN.
18"
MIN.
NEW CONCRETE PAD FOR MEDIUM VOLTAGE
PAD MOUNT TRANSFORMER DETAIL
SCALE: N.T.S.
EARTH
NEW PAD MOUNT TRANSFORMER
SLAB GRADE
EXPANSION JOINT
4"
NEW CONCRETE PAD WITH
12" ABOVE GRADE
MEDIUM VOLTAGE/LOW VOLTAGE
COMPARTMENT DIVIDER
(TYP.)
OPENING THRU CONCRETE BASE FOR
CONDUIT/CABLE ENTRY. COORDINATE EXACT SIZE AND
LOCATION WITH MANUFACTURER'S RECOMMENDATIONS.
(TYP.)
CONDUIT/CABLE STUB INTO BASE
(TYP)
CONDUIT/CABLE STUB INTO BASE
(TYP)
18"
MIN.
18"
MIN.
18"
MIN.
OPENING THRU CONCRETE BASE FOR
CONDUIT/CABLE ENTRY. COORDINATE EXACT SIZE AND
LOCATION WITH MANUFACTURER'S RECOMMENDATIONS.
(TYP.)
OPENING THRU CONCRETE BASE FOR
CONDUIT/CABLE ENTRY. COORDINATE EXACT SIZE AND
LOCATION WITH MANUFACTURER'S RECOMMENDATIONS.
(TYP.)
OPENING THRU CONCRETE BASE FOR
CONDUIT/CABLE ENTRY. COORDINATE EXACT SIZE AND
LOCATION WITH MANUFACTURER'S RECOMMENDATIONS.
(TYP.)
MEDIUM
VOLTAGE
COMPARTMENT
LOW VOLTAGE
COMPARTMENT
NEW 12" SUBBASE
NEW CONCRETE PAD WITH
8" ABOVE GRADE
8"
NEW 12" SUBBASE
file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
ELECTRICAL
DETAILS
ELECTRICAL DETAILS
file no.
checked by drawn by consultant issue date contract order no.
472MTUMAINTPROJ
consultant job no.
260053.00
472/26238.RWG
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
07/27/2026
M A
T R
I X
ISSUED FOR BIDDING
ELECTRICAL
DETAILS
ELECTRICAL PANEL
SCHEDULES