This document is a comprehensive set of construction drawings and specifications for a Freezer Cooler Condenser Retrofit project for the California Department of Veterans Affairs at the West Los Angeles Veterans Home. The project involves replacing evaporative coolers and condensing units for freezers and coolers on the lower level and first level servery, including associated refrigerant line replacements, electrical power connections to new equipment, and roofing repairs at pipe penetrations. The project site is located at 11500 Nimitz Avenue, Los Angeles, CA 90049, and involves work in Area D of the facility. The drawings are prepared by HMR Architects and dated June 21, 2024, with electrical engineering by Edge Electrical Consultants and mechanical engineering by Turley & Associates.
The project involves electrical and mechanical retrofit work across multiple levels, with detailed plans for demolition and new installations. The electrical scope includes replacing existing disconnects, modifying panel schedules, and installing new conduits and wiring for the refrigeration equipment. The work is being performed under Office of the State Fire Marshal Permit #24-S-2859 and adheres to 2022 California Building, Electrical, Mechanical, and Fire Codes. The electrical systems will connect to existing panels including EDPD, 1ELDD, and 1ELD, with careful attention to maintaining existing electrical infrastructure while upgrading the refrigeration systems' electrical components. The project appears to be funded through the California Department of Veterans Affairs and is intended to improve the mechanical systems of the Veterans Home.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
RL
KD
/1
/2
:0 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \0
-W
LA
A
C
O V E R S H E E T .D
W G
FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
V2
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
11500 NIMITZ AVE, LOS ANGELES, CA 90049
PROJECT
SITE
VETERANS HOME OF
WEST LOS ANGELES
FREEZER COOLER CONDENSER
RETROFIT
SCOPE OF WORKVICINITY MAP
NOT TO SCALE
CLIENT REPRESENATIVE
INDEX TO DRAWINGS
HMR ARCHITECTS
2130 21st STREET
SACRAMENTO, CA 95818
(916) 736-2724
CONTACT: KIM DEMONGEY
EMAIL: kimd@hmrarchitects.com
ARCHITECTURAL
A0 COVER SHEET
A0.1 REFERENCE CODE ANALYSIS, LEVEL 1
A0.2 REFERENCE CODE ANALYSIS, LEVEL 0
A1.1 PARTIAL FLOOR PLAN - AREA D - LOWER LEVEL
A1.2 PARTIAL FLOOR PLAN - AREA D - LEVEL 1
A2.0 PARTIAL ROOF PLAN - AREA D
COUNT 6 SHEETS
MECHANICAL
M0.1 MECHANICAL LEGEND, SCHEDULE, AND NOTES
M1.1 MECHANICAL DEMOLIION FLOOR PLAN - LOWER LEVEL, AREA D
M1.2 MECHANICAL DEMOLIION FLOOR PLAN - LEVEL 1, AREA D
M2.1 MECHANICAL FLOOR PLAN - LOWER LEVEL, AREA D
M2.2 MECHANICAL FLOOR PLAN - LEVEL 1, AREA D
M3.1 MECHANICAL DEMOLIION ROOFPLAN - AREA D
M3.2 MECHANICAL ROOF PLAN - AREA D
M4.1 MECHANICAL DETAILS
COUNT 8 SHEETS
T-24
T-24 T-24 COMPLIANCE
COUNT 1 SHEETS
ELECTRICAL
E0.1 ABBREVIATIONS, NOTES, MECHANICAL SCHEDULE, & SHEET INDEX
E0.2 ELECTRICAL SPECIFICATIONS
E0.3 ELECTRICAL SPECIFICATIONS
E0.4 ELECTRICAL SPECIFICATIONS
E1.0 PARTIAL DEMOLITION PLAN - AREA D, LOWER LEVEL
E1.1 PARTIAL DEMOLITION PLAN - AREA D, LEVEL 1
E1.2 PARTIAL DEMOLITION ROOF PLAN - AREA D
E2.0 PARTIAL FLOOR PLAN - AREA D, LOWER LEVEL
E2.1 PARTIAL FLOOR PLAN - AREA D, LEVEL 1
E2.2 PARTIAL ROOF PLAN - AREA D
E3.0 PARTIAL ONE-LINE DIAGRAM
E3.1 PANEL SCHEDULES
E4.0 ELECTRICAL DETAILS
E4.1 ELECTRICAL DETAILS
E4.2 ELECTRICAL DETAILS
E4.3 ELECTRICAL DETAILS
E4.4 ELECTRICAL DETAILS
COUNT 17 SHEETS
TOTAL 32 SHEETS
ARCHITECT
ELECTRICAL ENGINEER
DEFERRED APPROVAL
1. REPLACE EVAPORATIVE COOLERS AND CONDENSING UNITS AT FREEZERS AND
COOLERS IN LOWER LEVEL AND FIRST LEVEL SERVERY.
2. REPLACE ASSOCIATED REFRIGERANT LINES.
3. PROVIDE ELECTRICAL POWER TO NEW EQUIPMENT.
4. ROOFING AT PIPE PENETRATIONS.
DEPARTMENT OF VETERANS AFFAIRS
1227 O STREET
SACRAMENTO, CA 95814
(916) 278-6313 CONTACT: DANIELLE De SILVA EMAIL: Danielle.DeSilva@calvet.ca.gov
1. NONE
EDGE ELECTRICAL CONSULTANTS
1807 7th STREET, SUITE 150
SACRAMENTO, CA 95811
(916) 329-8402
CONTACT: WILL KWONG
EMAIL: william@edge-econsulting.com
CALIFORNIA DEPARTMENT OF VETERANS AFFAIRS
A:
& AND
A.B. ANCHOR BOLT
A.C. ASPHALT CONCRETE
A/C AIR CONDITIONING
ACC. ACCESSIBLE
ACOUST. ACOUSTICAL
A.A. AREA DRAIN
ADJ. ADJUSTABLE
A.F.F. ABOVE FINISH FLOOR
AGGR. AGGREGATE
ALUM. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECT(URAL)
B:
B&B BOARD AND BATTEN
BD. BOARD
BLDG. BUILDING
BLK'G. BLOCKING
BM. BEAM
B.M. BENCH MARK
BTTM. BOTTOM
B.U.R. BUILT UP ROOFING
C:
C.B. CATCH BASIN
C.I. CAST IRON
C.J. CONSTRUCTION JOINT
CLF CHAIN LINK FENCE
CLG. CEILING
CLR. CLEAR
CLKG. CAULKING
CNTR. COUNTER
C.O. CLEAN OUT
COL. COLUMN
CONC. CONCRETE
COND. CONDITION
CONST. CONSTRUCTION
CONT. CONTINUOUS
C.O.T.G. CLEAN OUT TO
GRADE
C.A. CONTROL POINT
CTSK. COUNTERSUNK
D:
DBL. DOUBLE
D.F. DRINKING FOUNTAIN
DEPT. DEPARTMENT
DTL. DETAIL
D.I. DROP INLET
DIAG. DIAGONAL
DIM. DIMENSION
DN. DOWN
DR. DOOR
D.S. DOWN SPOUT
D.S.P. DRY STANDPIPE
DWG. DRAWING
E:
E EAST
(E) EXISTING
EA. EACH
E.D.F. ELECTRIC DRINKING
FOUNTAIN
E.F. EXHAUST FAN
E.J. EXPANSION JOINT
ELEC. ELECTRICAL
ELEV. ELEVATION
EMER. EMERGENCY
ENCL. ENCLOSURE
E.P. ELECTRICAL PANEL
EQ. EQUAL
EQUIP. EQUIPMENT
E.W. EACH WAY
EXPO. EXPOSED
EXP. EXPANSION
EXT. EXTERIOR
F:
F.A. FIRE ALARM
F.B. FLAT BAR
F.C. FRAMING CLIP
F.D. FLOOR DRAIN
FDN. FOUNDATION
F.F. FINISH FACE
F.E. FIRE EXTINGUISHER
F.L. FLOW LINE
FLR. FLOOR
F.O.C. FACE OF CONCRETE
F.O.F. FACE OF FINISH
F.O.M. FACE OF MASONRY
F.O.W. FACE OF WALL
F.P. FIREPROOF
F.R.P. FIBERGLASS
REINFORCED PANEL
F.O.S. FACE OF STUD
F.S.D. FIRE SMOKE DAMPER
FT. FOOR OR FEET
FTG. FOOTING
F.V. FIELD VERIFY
G:
GA. GAUGE
GALV. GALVANIZED
G.C. GENERAL CONTRACTOR
G.I. GALVANIZED IRON
GLU-LAM GLUE LAMINATER
GND. GROUND
GYP. BD. GYPSUM WALLBOARD
H:
H.B. HOSE BIB
H.C. HOLLOW CORE
HDWD. HARDWOOD
HDBD. HARDBOARD
HDWE. HARDWARE
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
HR. HOUR
HT. HEIGHT
I-J-K-L:
I.D. INSIDE DIAMETER
I.E. INVERT ELEVATION
ISA INTERNATIONAL
SYMBOL
OF ACCESSIBILITY
INSUL. INSULATION
INT. INTERIOR
J.B. JUNCTION BOX
J.H. JOIST HANGER
JT. JOINT
KIT. KITCHEN
LAB. LABORATORY
LAM. LAMINATE
LAV. LAVATORY
LT. LIGHT
L.H. LEFT HAND
M:
MAX. MAXIMUM
M.C. MEDICINE CABINET
MECH. MECHANICAL
MEMB. MEMBRANE
MFR. MANUFACTURER
M.H. MANHOLE
MIN. MINIMUM
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
MTL. METAL
N:
N. NORTH
(N) NEW
N.I.C. NOT IN CONTRACT
NOM. NOMINAL
N.T.S. NOT TO SCALE
O:
OBS. OBSCURE
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.H. OVERHEAD OR
OVERHANG
OPNG. OPENING
OPP. OPPOSITE
O/ OVER
P:
PART. PARTITION
P.B. PANIC BAR
P.L. PROPERTY LINE
P.LAM. PLASTIC LAMINATE
PLAS. PLASTER
PLYWD. PLYWOOD
P.M. PRESSED METAL
P.O.C. POINT OF CONNECTION
PR. PAIR
PROP. PROPERTY
P.S.F. POUNDS PER SQUARE
FOOT
P.S.I. POUNDS PER SQUARE
INCH
P.T. PRESSURE TREATED
Q-R
Q.T. QUARRY TILE
R. RISER
RAD. RADIUS
R.D. ROOF DRAIN
R.E. RIM ELEVATION
REBAR REINFORCING BAR
REF. REFERENCE
REQ'D. REQUIRED
RM. ROOM
R.O. ROUGH OPENING
RWD. REDWOOD
R.W.L. RAIN WATER LEADER
S:
S. SOUTH
S.B. SPLASH BLOCK
S.D. STORM DRAIN
SEC. SECURITY
S.C. SOLID CORE
SCHED. SCHEDULE
SECT. SECTION
SHT. SHEET
SHTG. SHEATHING
SIM. SIMILAR
S.M. SHEET METAL
S.M.S. SHEET METAL SCREW
SPEC'S. SPECIFICATIONS
SQ. SQUARE
S.STL. STAINLESS STEEL
STD. STANDARD
STL. STEEL
STRUCT. STRUCTURAL
S.T.S.M.S. SELF TAPPING SHEET
METAL SCREW
S.S SANITARY SEWER
S/S SERVICE SINK
SUSP. SUSPENDED
SYM. SYMMETRICAL
T:
T.O.C. TOP OF CURB
T&G TOUNGE & GROOVE
T.O.C. TOP OF CONCRETE
T.O.F. TOP OF FRAMING
T.O.S. TOP OF STEEL
TOT. TOTAL
T.O.W. TOP OF WALL
T.P. TOP OF PAVING
TS STRUCTURAL TUBE
TYP. TYPICAL
U:
U.N.O. UNLESS NOTED
OTHERWISE
UNF. UNFINISHED
V:
V.C.T. VINYL COMPOSITION
TILE
V.C.F. VINYL COATED FABRIC
VEN. VENDER
VERT. VERTICAL
V.T.B. VINYL TABK BOARD
V.W.C. VINYL WALL COVERING
W:
W/ WITH
W.C. WATER CLOSET
WD. WOOD
W.H. WATER HEATER
W.M. WATERPROOF
MEMBRANE
W/O WITHOUT
W.R. WATER RESISTANT
WT. WEIGHT
W.W.F. WELDED WIRE FABRIC
A-*
A-*
A-*
1A
X
PL
C
L
CONCRETE
CONCRETE
BLOCK
CERAMIC TILE OR
BRICK
A.C. PAVING
SAND MORTAR
OR PLASTER
AGGREGATE
EARTH
METAL
PLYWOOD
GYPSUM BOARD
GLASS
WOOD FRAMING
(CONT. MEMBER)
WOOD FRAMING
(BLOCKING)
WOOD MEMBER
(FINISHED)
INSULATION
ROOM NUMBER
WINDOW TYPE
DOOR NUMBER
GRID LINE/NUMBER
GRID CENTER
LINE/NUMBER
SHEET WHERE
SECTION IS
DRAWN
SHEET WHERE
DETAIL IS DRAWN
SHEET WHERE ENLARGED
PLAN IS DRAWN
SHEET WHERE
ELEVATION IS DRAWN
DETAIL NUMBER
SECTION NUMBER
LOCATION NUMBER
ELEVATION NUMBER
EQUIPMENT NUMBER
PARTITION TYPE
KEYNOTE
REVISION NUMBER
MATCH LINE
DATUM, WORK OR
CONTROL NUMBER
ANGLE
DIAMETER OR ROUND
PERPENDICULAR
POUND OR NUMBER
CENTERLINE
PLATE OR PROPERTY
LINE
MECH. / PLUMB. ENGINEER
TURLEY & ASSOCIATES
2431 CAPITOL AVENUE
SACRAMENTO, CA 95816
(916) 325-1065
CONTACT: TIM FLAGG
EMAIL: tflagg@turleymech.com
SYMBOLS LEGEND
ABBREVIATIONS LIST
SHEET
NUMBER
DESCRIPTION
A0
COVER SHEET
SITE MAP
WEST LA
VETERANS HOME
NORTH
NOT TO SCALE
NORTH
NOT TO SCALE
PERMIT / APPLICATION NUMBERS:
OFFICE OF THE STATE FIRE MARSHAL # 24-S-2859
CODES USED:
2022 CALIFORNIA ADMINISTRATIVE CODE, CCR, TITLE 24, PART 1
2022 CALIFORNIA BUILDING CODE, VOL. 1 & 2, CCR, TITLE 24, PART 2
2022 CALIFORNIA ELECTRICAL CODE, CCR, TITLE 24, PART 3
2022 CALIFORNIA MECHANICAL CODE, CCR, TITLE 24, PART 4
2022 CALIFORNIA PLUMBING CODE, CCR, TITLE 24, PART 5
2022 CALIFORNIA ENERGY CODE, CCR, TITLE 24, PART 6
2022 CALIFORNIA FIRE CODE, CCR, TITLE 24, PART 9
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE, CCR, TITLE 24, PART 11
2022 CALIFORNIA EXISTING BUILDING CODE, CCR, TITLE 24, PART 10
TITLE 19, CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
JURISDICTION HAVING AUTHORITY: OFFICE OF THE STATE FIRE MARSHAL (OSFM)
THIS PROJECT IS A "TENANT IMPROVEMENT" WITHIN AN EXISTING SPACE, WHICH IS LOCATED ON
THE LOWER & FIRST FLOOR OF AREA D IN THE WEST LA VETERANS
HOME AT 11500 NIMITZ AVENUE, LOS ANGELES, CA 90049. CALVET IS BOTH THE OWNER AND
OCCUPANT OF THIS SPACE.
THIS IS NOT A DEFERRED SUBMITTAL, AND THERE ARE NO DEFERRED SUBMITTALS FOR THIS
PROJECT.
EXISTING BUILDING ANALYSIS OF THE WEST LA VETERANS HOME IS BASED ON DRAWINGS "ISSUED
FOR BID" IN 2006, AS FOLLOWS:
* OCCUPANCY GROUPS (SEE ALSO ACCESSORY USES BELOW)
- I-2 = BUILDING AREAS A (SNF), B (SNF SUPPORT), C (SNF), AND E (RCFE AND
DEMENTIA/ALZHEIMER'S UNITS), WHICH ARE INDICATED IN THE
REFERENCE DRAWINGS AS I-1.1 PER CBC 2001
- B = BUILDING AREA D MEMBER SERVICES, AND BUILDING AREA F UTILITY BUILDING
* CONSTRUCTION TYPES
- I-A = BUILDING AREAS A, B, C, D, AND E
- II-B = BUILDING AREA F
* NUMBER OF STORIES: N/A
* BUILDING AREA: N/A
* PROJECT AREA
LIMITED TO THE KITCHEN ON LOWER LEVEL, LEVEL 1 & ROOF OF BUILDING AREA D
- 1,019 SF FOR BASE DESIGN IN THE LOWER LEVEL ONLY
- 136 SF FOR BASE DESIGN IN THE LEVEL 1
- 117 SF FOR BASE DESING IN THE ROOF LEVEL
* THE EXISTING BUILDING WAS DESIGNED AS SEPARATED WITH ACCESSORY USES.
* SEPARATIONS:
- 2-HOUR RATED SEPARATION WALLS AROUND SHAFTS, STAIRWELLS, AND ELEVATORS
- 1-HOUR RATED SEPARATION WALLS AROUND STORAGE, ELECTRICAL, AND IT ROOMS
- 1-HOUR RATED SEPARATION SMOE BARRIER WALLS BETWEEN BUILDING AREAS A, B, C, D, & E
- 1-HOUR CORRIDOR WALLS
- 1-HOUR OR 2-HOUR RATED EXTERIOR WALLS
- SEE REFERENCE DRAWINGS ON SHEET A0.1 AND A0.2
*ACCESSORY USES: N/A
* AREA TOTALS BY OCCUPANCY TYPE (INCLUDING ACCESSORY USES): N/A
* ALLOWABLE AREA: UNLIMITED
* AREA INCREASE: N/A
* HEIGHT INCREASE: N/A
* FIRE SPRINKLERS: FULLY SPRINKLERED
* FIRE ALARM: EXISTING SYSTEM WITH AUTOMATIC HEAT AND SMOKE DETECTORS AND MANUAL
PULLS STATIONS
* OTHER FIRE PROTECTION SYSTEM: N/A
* SMOKE CONTROL SYSTEM: NO
* OCCUPANT LOAD OF ENTIRE BUILDING: N/A
* OCCUPANT LOAD OF EACH FLOOR: N/A
* YEAR BUILDING WAS CONSTRUCTED: 2010
* HIGH FIRE HAZARD SEVERITY ZONE: NO
* SEISMIC JOINTS AND LOCATIONS: YES, BETWEEN BUILDING AREAS A, B, C, D, AND E
* EMERGENCY RESPONDERS RADIO COVERAGE: FM RADIO NETWORK FOR INTER-BUILDING
COMMUNICATIONS, USING KENWOOD "ADVANCED COMMUNICATIONS SYSTEM", AND CARRIED
BY SECURITY FORCE AT ALL TIMES.
SFM PERMIT #24-S-2859 1
PROJECT CODE DATA
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2859 http://www.hmrarchitects.com
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
RL
KD
/1
/2
:1 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \0
-W
LA
A
C
O V E R S H E E T .D
W G
FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
V2
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
A0.1
REFERENCE CODE ANALYSIS PLAN
LEVEL 1
V1
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
RL
KD
/1
/2
:2 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \0
-W
LA
A
C
O V E R S H E E T .D
W G
FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
V2
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
A0.2
REFERENCE CODE ANALYSIS PLAN
LEVEL 0
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
PARTIAL FLOOR PLAN - AREA D - LOWER LEVEL
FILE: SCALE: 1/8"=1'-0"
FREEZER
D075A
COOLER
D075B
P01 P01
OPEN COVERED WALK
OPEN
AREA
STORAGE
33 37
UU
TT
35 38
WW
DRY
STORAGE
D075C
CARTS
D075D
MECHANICAL
ELECTRICAL
D075F
WAREHOUSE
STORAGE
D075G
LOUNGE
D078
WAREHOUSE
D072
02 CYLINDER
STORAGE
F085
STORAGE
F084
JANITOR
D074
HALL
D075E
STORAGE
D075H
STORAGE
D075J
SERVICE
CORRIDOR
D071
STORAGE
D043B
WORKSTATION
D043
OFFICE
D043A
ELECTRICAL
WAREHOUSE
D042
EMPLOYEE
LAUNDRY
D040
ELECTRICAL
D007
OFFICE
D008
AREA OF WORK
/1
/2
:3 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \W
LA
A F
LO
O R P
LA
N S .D
W G
A1.1
PARTIAL FLOOR PLAN
- AREA D - LOWER LEVEL
KEYNOTES
NORTHNORTH
1D
A1.1
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
RL
KD
/1
/2
:3 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \W
LA
A F
LO
O R P
LA
N S .D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
V2
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
KEYNOTES
1 HOUR RATED CORRIDOR
2 HOUR RATED SEPARATION WALL
AND SHAFT ENCLOSURES
1 HOUR RATED SEPARATION WALL
P01 REMOVE AND REPLACE EVAPORATIVE COOLER.
SEE MECHANICAL AND ELECTRICAL SHEETS
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
PARTIAL FLOOR PLAN - AREA D - LEVEL 1
33 37
UU
TT
35 38
WW
COOLER
D141C
FREEZER
D141B
FOOD
PREPARATION
D141
P01
DINING
D140
SERVERY
D140A
LOUNGE/LOCKERS
D142
PREP.
D141G
HALLWAY
D143 STAFF
TOILET
D142A
POTWASH
D141F
STORAGE
D141E
OFFICE
D141D
STORAGE
D141A
SERVICE
CORRIDOR
D103
ELECTRICAL
D108
STAFF
TOILET
D107
TELECOM
/SIGNAL
D106
SHAFT
D109
ELEV.
STORAGE
D140B
VENDING
D140C
AREA OF WORK
/1
/2
:3 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \W
LA
A F
LO
O R P
LA
N S .D
W G
A1.2
PARTIAL FLOOR PLAN
- AREA D - LEVEL 1
KEYNOTES
NORTHNORTH
1D
A1.1
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
RL
KD
/1
/2
:3 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \W
LA
A F
LO
O R P
LA
N S .D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
V2
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
KEYNOTES
(E) 1 HOUR RATED CORRIDOR
(E) 2 HOUR RATED SEPARATION WALL
AND SHAFT ENCLOSURES
(E) 1 HOUR RATED SEPARATION WALL
(E) 1-HOUR WALL CONSTRUCTION (EXTERIOR
WALL)
P01 REMOVE AND REPLACE EVAPORATIVE COOLER.
SEE MECHANICAL AND ELECTRICAL SHEETS
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
PARTIAL ROOF PLAN - AREA D
R F
R F
33 37
UU
TT
35 38
WW
LEVEL 5 ROOF
(NO WORK)
LOWER LEVEL ROOF
RP2
RP4
RP3
RP4
RP1
RP5
TYP.
RP3
RP4
RP6
LEVEL 2 ROOF
(NO WORK)
RP6
RP7 RP7
AREA OF WORK
PREFORMED FIELD WRAPPED
FLASHING AT ROOF PENETRATION
OR ROOF MOUNTED EQUIPMENT
FILE: SCALE: 1 1/2"=1'-0"
(E) PIPE PENETRATION
SEALANT
S.STL.CLAMP
PREMOLDED
PIPE BOOT
WELDED
SEAM CONT.
(E) PIPE AS OCCURS
BONDING
ADHESIVE
WATER
BLOCK
/4
"C
LR
S.STL.CLAMP
SEALANT
/4
"C
LR
FIELD WRAPPED
FLASHING
MEMBRANE
MEMBRANE
TARGET
WELDED SEAM
CONT.
(E) SINGLE PLY
ROOFING
(E) INSUL.(E) CONCRETE
ROOF DECK
1/2" GAP MAX.1/2" GAP MAX.
/1
/2
:3 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \W
LA
A .0
R O O F P
LA
N .D
W G
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
RL
KD
/1
/2
:3 P
M
K
IM
D E G O V E R N M
E N T \C
A L V E T \2
C
A L V E T W
LA
F R E E Z E R C O O
LE
R C
O N D E N S E R R
E T R O F
IT
P R O
JE
C T \W
LA
A .0
R O O F P
LA
N .D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
V2
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
A2.0
PARTIAL ROOF PLAN
- AREA D
(E) SINGLE PLY TPO ROOFING TO REMAIN. USE COMPATIBLE MATERIALS FOR
PATCHING.
KEYNOTES
RP1
(E) ROOF DRAIN AND OVERFLOW TO REMAIN
RP2
RP3
(E) HVAC UNIT TO REMAINRP4
RP5
(E) PARAPET TO REMAIN
(E) WALK PADS TO REMAIN
RP6
RP7
1D
A2.0
NORTHNORTH
THRU ROOF PIPE PENETRATION, SEE DETAIL
5D
A2.0
5D
A2.0
REMOVE AND REPLACE CONDENSING UNIT.
SEE MECHANICAL AND ELECTRICAL SHEETS
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
MECHANICAL LEGEND MECHANICAL ABBREVIATIONS
COMPLIANCE NOTES
APPLICABLE CODES
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
T F
LA
G G
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.1
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M0.1
MECHANICAL LEGEND,
SCHEDULES, AND NOTES
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
WW
UU
35 3733
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
LC
O X
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.1
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M1.1
MECHANICAL DEMOLITION
FLOOR PLAN - LOWER LEVEL
AREA D
KEY PLAN
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
TT
UU
3835 37
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
LC
O X
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.2
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M1.2
MECHANICAL DEMOLITION
FLOOR PLAN - LEVEL 1 AREA D
KEY PLAN
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
UU
35 3733
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
LC
O X
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.1
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M2.1
MECHANICAL FLOOR PLAN -
LOWER LEVEL AREA D
KEY PLAN
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
TT
UU
3835 37
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
LC
O X
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.2
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M2.2
MECHANICAL FLOOR PLAN -
LEVEL 1 AREA D
KEY PLAN
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
35 3733
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
T F
LA
G G
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.1
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M3.1
MECHANICAL DEMOLITION ROOF
PLAN - AREA D
KEY PLAN
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
35 3733
JUNE 21, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
T F
LA
G G
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \M
.2
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M3.2
MECHANICAL ROOF PLAN - AREA
D
KEY PLAN
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
T F
LA
G G
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N S E R \M
.1
.D
W
G FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
M4.1
MECHANICAL DETAILS
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
CHECKED BY:
JOB NO.
REVISIONS
DESCRIPTION DATENO.
T&A
T&A
/1
/2
:0 P
M
T F
LA
G G
Z
JO
B F
IL
E S \2
\2
\2
C
A
LV
E T W
E S T L A V
E T E R A N 'S H
O M
E F R E E Z E R C
O O
LE
R C
O N D E N
SE
R \T
.D
W G
FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
1 SFM COMMENTS 09/13/24
& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
24109BP
NS
ZH
T24
TITLE 24
COMPLIANCE
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
NON FUSED DISCONNECT SWITCH.
CONTROL AND/OR EQUIPMENT, PROVIDED UNDER ANOTHER DIVISION,
PROVIDE POWER CONNECTION AS INDICATED.
EQUIPMENT, PROVIDED UNDER ANOTHER DIVISION, PROVIDE POWER-
CONNECTION AS INDICATED.
BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED.
RACEWAY INSTALLED IN CEILING OR WALL. ROUTE EXPOSED IN ALL
UNFINISHED AREAS.
RACEWAY INSTALLED BELOW FINISHED FLOOR, GRADE, OR STRUCTURE
CEILING.
EXISTING CONDUIT RUN TO BE ABANDONED. CONDUIT ABOVE THE FLOOR
AND BELOW THE STRUCTURE ABOVE SHALL BE REMOVED. CONDUCTORS
SHALL BE REMOVED.
X
EXISTING CONDUIT RUN, VERIFY ROUTING ON THE JOB.
REMOVE (E) WIRE, PULL IN NEW WIRES, #12 AWG UNLESS NOTED.
ARROW AT END OF RACEWAY INDICATES HOME RUN TO RESPECTIVE
PANELBOARD OR SWITCHBOARD.
BRANCH CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES A 2 #12 AWG
CIRCUIT WITH 1 #12 AWG GROUND.
STRAIGHT CROSS-LINES IN BRANCH CIRCUIT RACEWAY INDICATE NUMBER
OF #12 AWG WIRES IN A CIRCUIT. SHORT LINES INDICATE UNGROUNDED
CONDUCTORS. LONG LINES INDICATE NEUTRAL CONDUCTORS. WIRES
SHOWN ARE IN ADDITION TO 1 #12 AWG GROUNDING CONDUCTOR.
INDICATES RACEWAY TURNING DOWN.
POWER DISTRIBUTION SYMBOLS
SYMBOL DESCRIPTION
RACEWAY SYMBOLS
SYMBOL DESCRIPTION
ABBREVIATIONS
1PH, 3PH 1 PHASE, 3 PHASE
1P, 2P, 3P 1 POLE, 2 POLE, 3 POLE
3W, 4W 3 WIRE, 4 WIRE
(D) DEMO, DEMOLISH
(E) EXISTING
(ER) EXISTING RELOCATED
(N) NEW
(R) RELOCATE
-A-
A, AMPS AMPERES
AC ALTERNATING CURRENT
AF FRAME RATING IN AMPERES
AFF ABOVE FINISHED FLOOR
AIC AMPERES INTERRUPTING
CAPACITY
AL, ALUM ALUMINUM
ATS AUTO TRANSFER SWITCH
AT TRIP RATING IN AMPERES
AWG AMERICAN WIRE GAUGE
-B-
BTR BUILDING TELECOM ROOM
-C-
C CONDUIT
CB,C/B CIRCUIT BREAKER
CEC CALIFORNIA ELECTRICAL CODE
CT CURRENT TRANSFORMER
CU COPPER
-D-
DC DIRECT CURRENT
-E-
EA EACH
ELEC ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
-F-
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FLA FULL LOAD AMPS
FT FOOT OR FEET
-G-
G, GND GROUND
GA GAUGE
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFI GROUND FAULT INTERRUPTER
-H-
HOA HAND-OFF-AUTO
HP HORSE POWER
-J-
J-BOX JUNCTION BOX
-K-
KVA ONE THOUSAND VOLT-AMPS
KW ONE THOUSAND WATTS
-L-
LCP LIGHTING CONTROL PANEL
LTG LIGHTING
-M-
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVER-CURRENT
PROTECTION
MT EMPTY CONDUIT W/ PULL-LINE
-N-
NC NORMALLY CLOSED
NCTC NURSE CALL TERMINAL CABINET
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER ASSOCIATION
NIES NOT INCLUDED IN ELECTRICAL
SCOPE
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
-O-
OCP OVER-CURRENT PROTECTION
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER
INSTALLED
-P-
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
-R-
RLA RUNNING LOAD AMP
RSC RIGID STEEL CONDUIT
-S-
SPD SURGE PROTECTION DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPST SINGLE POLE SINGLE THROW
SST SOLID STATE TRIP
-T-
TER TELECOM EQUIPMENT ROOM
TR TELECOM ROOM
TM THERMAL MAGNETIC
TTB TERMINAL BACKBOARD
-U-
UG UNDERGROUND
UL UNDERWRITERS LAB.
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
SUPPLY
-V-
V VOLTS
VA VOLT-AMPS
VAC VOLTS ALTERNATE CURRENT
-W-
W WATTS
WCR WITHSTAND & CLOSING RATING
WP WEATHERPROOF
-X-
XFMR TRANSFORMER
XFER TRANSFER SWITCH
SHEET INDEX
SHEET DESCRIPTION
ABBREVIATIONS, SYMBOLS, MECHANICAL SCHEDULE & SHEET INDEX
ELECTRICAL SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
PARTIAL DEMOLITION FLOOR PLAN - AREA D - LOWER LEVEL
PARTIAL DEMOLITION FLOOR PLAN - AREA D - LEVEL 1
PARTIAL DEMOLITION ROOF PLAN - AREA D
PARTIAL FLOOR PLAN - AREA D - LOWER LEVEL
PARTIAL FLOOR PLAN - AREA D - LEVEL 1
PARTIAL ROOF PLAN - AREA D
PARTIAL ONE LINE DIAGRAM
PANEL SCHEDULES
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
E0.1
E0.2
E0.3
E0.4
E1.0
E1.1
E1.2
E2.0
E2.1
E2.2
E3.0
E3.1
E4.0
E4.1
E4.2
E4.3
E4.4
FLEX CONDUIT.
NUMBERED NOTE.XX
TRANSFORMER.T
STANDARD ELECTRICAL SYMBOLS
SYMBOL DESCRIPTION
CIRCUIT BREAKER.
2-POLE 1-PHASE MOTOR RATED DISCONNECT SWITCH. AMPERAGE
ADJACENT INDICATES AMPERE RATING OF SWITCH. SWITCH SHALL BE 600V
RATED SWITCH FOR ALL SYSTEMS.
XXA
1-POLE 1-PHASE MOTOR RATED DISCONNECT SWITCH. AMPERAGE
ADJACENT INDICATES AMPERE RATING OF SWITCH. SWITCH SHALL BE
RATED 600V MAXIMUM FOR ALL SYSTEMS.
XXA
FUSED DISCONNECT SWITCH W/ CLASS 'R' DUAL ELEMENT FUSES, SIZED
PER EQUIPMENT NAME PLATE RATING. NUMBER ADJACENT INDICATES
XXA/XP/XXF
AMPERE RATING OF SWITCH / POLES / FUSE RATING. REFER TO PLANS FOR
ACTUAL RATINGS. FUSE SIZE INDICATED ON PLANS IS USED AS THE BASIS
OF DESIGN. FINAL FUSE SIZE INSTALLED SHALL BE CONFIRMED ON THE
FIELD AGAINST EQUIPMENT NAMEPLATE RATING.
GENERAL ELECTRICAL NOTES
1. WHERE PROVIDED, THROUGH-PENETRATION FIRESTOP SYSTEM AND MEMBRANE
PENETRATION DETAILS SHOWN IN THE DETAILS ARE FOR REFERENCE ONLY.
THROUGH- PENETRATIONS AND MEMBRANE PENETRATIONS SHALL BE PROTECTED
BY AN APPROVED PENETRATION FIRESTOP SYSTEM OR MEMBRANE PENETRATION
FIRESTOP SYSTEM INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL
1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) OF
WATER OR AS OTHERWISE PERMITTED BY CBC, SECTION 714. LISTED THROUGH-
PENETRATION FIRESTOP SYSTEMS AND MEMBRANE PENETRATIONS SHALL BE
INSTALLED IN ACCORDANCE WITH THE INSTALLATION DETAILS FOR LISTED SYSTEMS.
LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS, MEMBRANE PENETRATION
PROTECTION AND OTHER PERMITTED MEANS AND METHODS OF PENETRATION
PROTECTION SHALL BE SUBMITTED FOR LOCAL FIRE MARSHAL REVIEW AND
APPROVAL PRIOR TO INSTALLATION.
2. ALL ELECTRICAL EQUIPMENT TO BE INSTALLED OR PERMANENTLY CONNECTED
(HARDWIRED) SHALL BE LISTED, LABELED, OR CERTIFIED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY (NRTL) PER CEC 110.2.
3. ALL EQUIPMENT SHALL BE USED IN ACCORDANCE WITH LISTING PER CEC 110.3B.
MECHANICAL SCHEDULE
DESCRIPTION VOLTAGE/PHASE EQUIPMENT HP FLA KVA REMARKS
EC-C1 208/1 EVAPORATOR COIL 1/15 1.8
EC-C2 208/1 EVAPORATOR COIL 1/15 1.8
EC-F1 208/1 EVAPORATOR COIL 13.7
EC-F2 208/1 EVAPORATOR COIL 13.7
EC-C3 208/1 EVAPORATOR COIL 1/15 1.8
EC-F3 208/1 EVAPORATOR COIL 9.4
CU-1 208/3 CONDENSING UNIT 22.6
CU-2 208/3 CONDENSING UNIT 28.8
CU-3 208/3 CONDENSING UNIT 11.5
CU-4 208/3 CONDENSING UNIT 9.6
JUNCTION BOX, SIZE AND TYPE AS INDICATED OR REQUIRED.J J
INTERRUPTER.
20 AMP 125V 3W DUPLEX CONVENIENCE RECEPTACLE W/ GROUND FAULT
WIRING DEVICE SYMBOLS
SYMBOL DESCRIPTION
DEVICE SUBSCRIPTS DESIGNATE THE FOLLOWING:
= WEATHERPROOFWP
SUBSCRIPTS:
/1
/2
:1 P
M
W
IL
LI
A M
.K W
O N G
D \K
\D
R A W
IN
G S \E
.1
C
O V E R S H E E T .D
W G
FEBRUARY 19, 2024
DRAWN BY:
CHECKED BY:
JOB NO.
RL
KD
/1
/2
:1 P
M
W
IL
LI
A M
.K W
O N G
D \K
\D
R A W
IN
G S \E
.1
C
O V E R S H E E T .D
W G
23052 V1
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING
HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED
WORK OF HMR ARCHITECTS AND MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
WRITTEN CONSENT OF HMR ARCHITECTS
Contact
Project Number
Sacramento | Alameda | Irvine
400 R Street, Ste 333
Sacramento, CA 95811 916.256.2460
K339
WILLIAM
REVISIONS
DESCRIPTION DATENO.
FREEZER COOLER
CONDENSER RETROFIT
11500 NIMITZ AVE.
LOS ANGELES, CA 90049
HMRARCHITECTS
2130 21st Street
Sacramento, CA 95818
T 916 736 2724 www.hmrarchitects.com
1 SFM COMMENTS 09/13/24
E0.1
ABBREVIATIONS,
SYMBOLS, MECHANICAL
SCHEDULE & SHEET INDEX
&[Date]10/11/2024
V2
OSFM PERMIT#24-S-2859
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
11/18/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
SECTION 26 00 00 - ELECTRICAL WORK
PART 1 GENERAL
1.01 CONDITIONS:
A. THE REQUIREMENTS OF GENERAL CONDITIONS AND SPECIAL CONDITIONS APPLY TO
WORK OF THIS SECTION AS IF FULLY REPEATED HEREIN.
1.02 WORK INCLUDED:
A. PROVIDE A COMPLETE WORKING INSTALLATION OF ALL ELECTRICAL AS SHOWN OF
DRAWINGS OR AS SPECIFIED.
B. PROVIDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT NECESSARY FOR THE
COMPLETE IN-PLACE INSTALLATION OF ALL ELECTRICAL AND LOW VOLTAGE ITEMS
COMPLETE AS SHOWN ON DRAWINGS AND AS SPECIFIED.
C. COMPLETE NEW BRANCH CIRCUIT PANELBOARDS, CONDUIT, WIRE, PULL BOXES,
JUNCTION BOXES AND MISCELLANEOUS MATERIALS.
D. ELECTRICAL CONNECTIONS TO EQUIPMENT FURNISHED AND INSTALLED UNDER OTHER
SECTIONS.
E. INCLUDE SEALING AND FIREPROOFING OF CONDUITS, CABLE TRAYS, CABLES ETC.
F. ELECTRICAL COMPONENTS ARE IDENTIFIED AS FOLLOWS:
1. NAMEPLATE FOR EACH CONTROL EQUIPMENT ENCLOSURE.
2. LABEL FOR IDENTIFICATION OF RECEPTACLES, LIGHT SWITCHES, AND CONTROL
DEVICE STATIONS.
3. WIRE MARKER FOR EACH CONDUCTOR AT PANEL BOARDS' GUTTERS, PULL BOXES,
OUTLET AND JUNCTION BOXES, AND EACH LOAD CONNECTION.
4. PERMANENT INK FELT TIP MARKER ON COVER INDICATING PANEL AND CIRCUIT FOR
JUNCTION BOXES LOCATED ABOVE SUSPENDED CEILINGS AND BELOW CEILINGS IN
NON-PUBLIC AREAS.
1.03 CODES AND STANDARDS
A. WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH CALIFORNIA OCCUPATIONAL
SAFETY HEALTH ACT (CAL-OSHA), CALIFORNIA ELECTRICAL CODE (CEC), STATE FIRE
MARSHAL, TITLE 8, SAFETY ORDERS OF DIVISION OF INDUSTRIAL SAFETY (ESO), THE
NATIONAL FIRE PROTECTION ASSOCIATION, CALIFORNIA BUILDING CODE (CBC);
CALIFORNIA CODE OF REGULATIONS - TITLE 24 AND OTHER APPLICABLE LAWS OR
REGULATIONS. NOTHING IN THE DRAWINGS OR SPECIFICATIONS SHALL BE CONSTRUED
TO PERMIT WORK NOT CONFORMING TO THESE CODES.
B. WHEN CONTRACT DOCUMENTS DIFFER FROM GOVERNING CODES, FURNISH, AND INSTALL
LARGER SIZE OR HIGHER STANDARDS CALLED FOR WITHOUT EXTRA CHARGE.
1.04 QUALITY ASSURANCE:
A. REQUIREMENTS OF REGULATORY AGENCIES:
1. NOTHING IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO PERMIT WORK
NOT CONFORMING TO APPLICABLE CODES, LAWS, ORDINANCES, RULES, OR
REGULATIONS.
2. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS AND IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CONTRACTORS ASSOCIATION (NECA) STANDARD OF INSTALLATION.
3. EQUIPMENT TO BE INSTALLED OR PERMANENTLY CONNECTED (HARDWIRED) SHALL
BE LISTED, LABELED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY (NRTL).
1.05 PERMITS, FEES, AND INSPECTIONS
A. CONTRACTOR SHALL OBTAIN ALL PERMITS AND ARRANGE FOR OWNER TO PAY REQUIRED
FEES TO ANY GOVERNMENTAL AGENCY OR UTILITY COMPANY HAVING JURISDICTION
OVER THE WORK OF THIS SECTION. INSPECTIONS REQUIRED BY ANY LOCAL ORDINANCES
OR UTILITY COMPANIES DURING CONSTRUCTION SHALL BE ARRANGED BY THE
CONTRACTOR.
B. ALL WORK AND MATERIALS COVERED BY THESE SPECIFICATIONS AND ACCOMPANYING
DRAWINGS SHALL ALWAYS BE SUBJECT TO INSPECTION BY THE ARCHITECT OR HIS
REPRESENTATIVE. ANY MATERIAL NOT IN ACCORDANCE WITH THE PLANS AND
SPECIFICATIONS, OR NOT INSTALLED IN A NEAT AND WORKMANLIKE MANNER, SHALL,
UPON ORDER FROM THE ARCHITECT, BE REMOVED FROM THE PREMISES OR CORRECTIVE
ACTION TAKEN WITHIN THREE (3) DAYS; AND IF MATERIAL IN QUESTION HAS BEEN
INSTALLED, THE ENTIRE EXPENSE FOR REMOVING AND REINSTALLING SHALL BE BORNE
BY THE CONTRACTOR.
C. ON COMPLETION OF THE WORK, SATISFACTORY EVIDENCE SHALL BE FURNISHED TO THE
ARCHITECT TO SHOW THAT ALL WORK HAS BEEN INSTALLED IN ACCORDANCE WITH THE
CODES.
D. THE CONTRACTOR SHALL COOPERATE WITH THE ARCHITECT AND SHALL PROVIDE
ASSISTANCE AT ALL TIMES FOR THE INSPECTION OF THE ELECTRICAL WORK PERFORMED
UNDER THIS CONTRACT. CONTRACTOR SHALL REMOVE COVERS, OPERATE MACHINERY,
OR PERFORM ANY REASONABLE WORK WHICH, IN THE OPINION OF THE ENGINEER, WILL
BE NECESSARY TO DETERMINE THE QUALITY AND ADEQUACY OF THE WORK.
1.06 SPECIFICATIONS AND CONTRACT DRAWINGS
A. ACCURACY OF DATA GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACT AS COULD BE
SECURED, BUT THEIR EXTREME ACCURACY IS NOT GUARANTEED. THE DRAWINGS AND
SPECIFICATIONS ARE FOR THE ASSISTANCE AND GUIDANCE OF THE CONTRACTOR AND
EXACT LOCATIONS, DISTANCES, LEVELS, ETC., WILL BE GOVERNED BY THE
CONSTRUCTION AND THE CONTRACTOR SHALL ACCEPT SAME WITH THIS
UNDERSTANDING.
B. LAYOUTS OF EQUIPMENT, ACCESSORIES AND WIRING SYSTEMS ARE DIAGRAMMATIC (NOT
PICTORIAL AND NOT EXACT) BUT SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE.
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND OTHER DRAWINGS SHALL BE
EXAMINED NOTING ALL CONDITIONS THAT MAY AFFECT THIS WORK. WHERE
CONNECTIONS TO EQUIPMENT PROVIDED BY OTHER DIVISIONS ARE SHOWN ON
ELECTRICAL DRAWINGS, REFER TO DRAWINGS OF RESPECTIVE DIVISION FOR EXACT
LOCATIONS AND ELECTRICAL REQUIREMENTS OF EQUIPMENT.
C. REPORT CONFLICTING CONDITIONS TO THE ARCHITECT FOR ADJUSTMENT BEFORE
PROCEEDING WITH WORK. SHOULD CONTRACTOR PROCEED WITH WORK WITHOUT
REPORTING CONFLICT(S), HE DOES SO ON HIS OWN RESPONSIBILITY, AND SHALL ALTER
WORK IF DIRECTED BY THE ARCHITECT, AT HIS OWN EXPENSE.
D. RIGHT IS RESERVED TO MAKE MINOR CHANGES IN LOCATIONS OF EQUIPMENT AND
WIRING SYSTEMS SHOWN, PROVIDING CHANGE IS ORDERED BEFORE CONDUIT RUNS
AND/OR WORK DIRECTLY CONNECTED TO SAME IS INSTALLED AND NO EXTRA MATERIALS
ARE REQUIRED.
E. DRAWINGS AND SPECIFICATIONS MAY BE SUPERSEDED BY LATER DETAIL SPECIFICATION
AND DETAIL DRAWINGS PREPARED BY THE ARCHITECT, AND THE CONTRACTOR SHALL
CONFORM TO THEM AND TO SUCH REASONABLE CHANGES IN THE CONTRACT DRAWINGS
AS MAY BE CALLED FOR BY THESE REVISED DRAWINGS WITHOUT EXTRA COST TO THE
OWNER.
F. CONTRACTOR MAY REQUEST ADDITIONAL DETAIL(S), AND SUCH SHALL BE CONFORMED
TO, WITHOUT ADDITIONAL COST. CONTRACTOR MAY OFFER ALTERNATE DETAIL(S), BUT
SUCH DETAIL(S) SHALL BE APPROVED BY ARCHITECT AND AUTHORITY HAVING
JURISDICTION
1.07 SUBMITTALS:
A. SUBMISSION REQUIREMENTS
1. CONTRACTOR IS RESPONSIBLE FOR THE SCHEDULING OF SUBMITTALS TO AVOID
DETRIMENTAL IMPACT TO THE CONSTRUCTION SCHEDULE AND TO SUPPORT THE
TIMELY SEQUENCE OF THE WORK. ALLOW A MINIMUM OF 15-WORKING DAYS FOR
SUBMITTAL REVIEW BY THE ENGINEER. COMPLEX SUBMITTALS OR SUBMITTALS
WHICH ARE NOT PROVIDED AS COMPLETE PACKAGES MAY TAKE LONGER THAN
15-WORKING DAYS FOR REVIEW. CONTRACTOR SHOULD ALLOW TIME FOR POTENTIAL
REJECTION AND RE-SUBMITTAL OF SUBMITTALS WHICH ARE BEING OFFERED AS
SUBSTITUTION TO THE SPECIFIED PRODUCTS.
2. CONTRACTOR SHALL REVIEW SUBMITTALS FOR COMPLETENESS, COORDINATION AND
CONFLICTS BETWEEN SUBCONTRACTORS AND OTHER WORK IN THE CONTRACT
DOCUMENTS. SUBMITTALS MADE BY CONTRACTOR WHICH ARE NOT THOROUGHLY
REVIEWED BY THE CONTRACTOR WILL BE RETURNED. SUBMITTALS WHICH VARY
SIGNIFICANTLY FROM THE CONTRACT DOCUMENTS AND ARE NOT SO IDENTIFIED
PRIOR TO SUBMISSION, WILL BE RETURNED TO THE CONTRACTOR WITHOUT REVIEW.
3. MAKE SUBMISSIONS WITHIN FOLLOWING NUMBER OF DAYS FROM ISSUANCE OF
NOTICE TO PROCEED OR START LETTER
a. ITEMS NEEDED IN INITIAL STAGES OF WORK OR REQUIRING LONG LEAD-TIME FOR
ORDERING: 15 CALENDAR DAYS.
b. ALL OTHER ITEMS: 21 CALENDAR DAYS.
4. BEFORE SUBMITTING A SHOP DRAWING OR ANY RELATED MATERIAL, CONTRACTOR
SHALL: REVIEW EACH SUCH SUBMISSION FOR CONFORMANCE WITH THE MEANS,
METHODS, TECHNIQUES, SEQUENCES, AND OPERATIONS OF CONSTRUCTION, AND
SAFETY PRECAUTIONS AND PROGRAMS INCIDENTAL THERETO, ALL OF WHICH ARE
THE SOLE RESPONSIBILITY OF THE CONTRACTOR; APPROVE EACH SUCH SUBMISSION
BEFORE SUBMITTING IT; AND STAMP EACH SUCH SUBMISSION BEFORE SUBMITTING IT.
ENGINEER SHALL ASSUME THAT NO SHOP DRAWING OR RELATED SUBMITTAL
COMPRISES A VARIATION UNLESS THE CONTRACTOR ADVISES THE ENGINEER
OTHERWISE VIA A WRITTEN INSTRUMENT WHICH IS ACKNOWLEDGED BY THE
ENGINEER IN WRITING.
5. ENGINEER WILL CHECK SUBMITTALS FOR CONFORMANCE WITH DESIGN CONCEPTS
OF PROJECT. APPROVAL COVERS ONLY SUCH CONFORMANCE. EFFORT WILL BE MADE
BY ENGINEER TO DISCOVER ANY ERRORS, BUT RESPONSIBILITY FOR ACCURACY AND
CORRECTNESS OF ALL SUBMITTALS SHALL BE WITH THE CONTRACTOR.
6. APPROVAL OF SUBMITTALS WILL BE ON A GENERAL BASIS ONLY AND SHALL NOT
RELIEVE THE CONTRACTOR FROM THEIR RESPONSIBILITY FOR PROPER FITTING AND
CONSTRUCTION OF THE WORK, NOR FROM FURNISHING MATERIALS AND LABOR
REQUIRED BY THE CONTRACT WHICH MAY NOT BE INDICATED ON THE SUBMITTALS
WHEN APPROVED.
7. NO PORTION OF THE WORK REQUIRING SUBMITTALS SHALL BE COMMENCED UNTIL
THE SUBMITTAL FOR THAT PORTION OF THE WORK HAS BEEN APPROVED BY
ENGINEER. ALL SUCH PORTIONS OF WORK SHALL BE IN ACCORDANCE WITH THE
APPROVED SUBMITTAL. ANY WORK PERFORMED WITHOUT APPROVED SUBMITTALS
WILL BE DONE SO AT THE CONTRACTOR'S OWN RISK. WORK FOUND NOT TO BE IN
COMPLIANCE WITH THE APPROVED SUBMITTALS SHALL BE REMOVED AND
CORRECTED AT THE CONTRACTOR'S OWN EXPENSE.
8. NUMBER OF COPIES REQUIRED - CONTRACTOR SHALL SUBMIT FOLLOWING NUMBER
OF COPIES:
a. SHOP DRAWINGS: 1-ELECTRONIC COPY IN PDF FORMAT.
b. PRODUCT DATA/MATERIAL LISTS: 1-ELECTRONIC COPY IN PDF FORMAT.
c. SAMPLES: AS SPECIFICALLY INDICATED IN PERTINENT SPECIFICATION SECTION.
d. SUBSTITUTION REQUEST: 1-COPY IN PDF FORMAT
9. SUBMITTALS SHALL INCLUDE (WHERE APPLICABLE):
a. DATE AND REVISION DATES.
b. PROJECT TITLE AND NUMBER.
c. THE NAMES OF ARCHITECT, ENGINEER, CONTRACTOR, SUBCONTRACTOR AND
SUPPLIER OR MANUFACTURER.
d. IDENTIFICATION OF PRODUCT OR MATERIAL.
e. RELATION TO ADJACENT STRUCTURE OR MATERIAL.
f. FIELD DIMENSIONS CLEARLY IDENTIFIED AS SUCH.
g. SPECIFICATION SECTION NUMBER.
h. A BLANK SPACE FOR ENGINEER'S STAMP.
i. CONTRACTOR'S STAMP ON EACH, INITIALED OR SIGNED, CERTIFYING THAT
SUBMITTAL WAS REVIEWED, FIELD MEASUREMENTS HAVE BEEN VERIFIED AND
SUBMITTAL IS IN COMPLIANCE WITH THE APPLICABLE SPECIFICATION SECTION
AND THE OVERALL CONTRACT DOCUMENTS.
10. INCOMPLETE, INACCURATE, OR NON-COMPLYING SUBMITTALS REQUIRING REVISIONS,
RE-SUBMITTAL, AND ADDITIONAL REVIEW TIME, SHALL NOT BE CONSIDERED AS A
BASIS FOR CONTRACT TIME EXTENSION.
B. REQUIRED SUBMITTALS
1. VARIOUS SPECIFICATION SECTIONS MAY STATE ADDITIONAL INFORMATION TO BE
SUBMITTED.
2. SUBMITTALS ARE REQUIRED FOR ALL MATERIALS EVEN THOUGH THE SUBMITTED
MATERIAL MAY BE EXACTLY AS SPECIFIED IN THE PROJECT MANUAL.
3. ELECTRICAL MATERIALS SUBMITTAL:
a. SUBMIT PRODUCT DATA ONLY FOR MATERIALS THAT ARE BEING SUBSTITUTED.
PRODUCT DATA IS NOT REQUIRED FOR MATERIALS THAT ARE BEING PROVIDED
AS SPECIFIED.
b. ELECTRICAL MATERIALS INCLUDE RACEWAY, BOXES, SUPPORTS, FINISH
MATERIAL, ETC.
4. ELECTRICAL EQUIPMENT SUBMITTAL:
a. SUBMIT PRODUCT DATA FOR ALL EQUIPMENT.
b. ELECTRICAL EQUIPMENT INCLUDES PANELBOARDS, SWITCHBOARDS, TRANSFORMERS, UNDERGROUND PULL BOXES, FLOOR BOXES, LIGHT FIXTURES, ETC.
5. LOW VOLTAGE AND CONTROL SYSTEMS SUBMITTALS:
a. PROVIDE PRODUCT DATA FOR EACH ITEM IN THE SYSTEM.
b. PROVIDE SHOP DRAWINGS FOR EACH SYSTEM.
c. LOW VOLTAGE AND CONTROL SYSTEMS INCLUDE LIGHTING CONTROLS, SOUND
COMMUNICATIONS, FIRE ALARM, ETC.
C. PRODUCT DATA
1. MANUFACTURER'S STANDARD SCHEMATIC DRAWINGS:
a. MODIFY DRAWINGS TO DELETE INFORMATION WHICH IS NOT APPLICABLE TO THE
PROJECT.
b. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION
WHICH IS APPLICABLE TO THE PROJECT.
2. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES,
PERFORMANCE CHARTS, ILLUSTRATIONS, AND OTHER STANDARD DESCRIPTIVE DATA.
a. CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS, OR
MODELS. MARK OUT OR REMOVE ALL EXTRANEOUS INFORMATION.
b. SHOW DIMENSIONS AND CLEARANCES REQUIRED.
c. SHOW PERFORMANCE CHARACTERISTICS AND CAPACITIES.
d. SHOW WIRING DIAGRAMS AND CONTROLS.
1.08 SYSTEM DESCRIPTION:
A. RACEWAY AND BOXES LOCATED AS INDICATED ON DRAWINGS, AND AT OTHER LOCATIONS
REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND
COMPLIANCE WITH REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN
APPROXIMATE LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE
WIRING SYSTEM.
B. CONDUCTOR SIZES ARE BASED ON COPPER UNLESS INDICATED AS ALUMINUM OR "AL".
C. WHEN ALUMINUM CONDUCTOR IS SUBSTITUTED FOR COPPER CONDUCTOR, SIZE TO
MATCH CIRCUIT REQUIREMENTS, TERMINATIONS, CONDUCTOR AMPACITY AND VOLTAGE
DROP. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING MAXIMUM NUMBER OF
ALUMINUM CONDUCTORS FOR SUBSTITUTED COPPER CONDUCTORS IN SPECIFIED
CONDUIT.
D. ALL WIRING SHALL BE INSTALLED IN RACEWAY.
E. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE GALVANIZED RIGID STEEL CONDUIT.
PROVIDE CAST METAL OUTLET, PULL, AND JUNCTION BOXES.
F. WET AND DAMP LOCATIONS: GALVANIZED RIGID STEEL CONDUIT. PROVIDE CAST METAL
OUTLET, JUNCTION, AND PULL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN
FINISHED AREAS.
G. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE
SHEET-METAL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES WHERE SHOWN ON DRAWINGS.
PROVIDE J-HOOKS WHEN SHOWN ON PLANS.
H. EXPOSED INTERIOR DRY LOCATIONS: USE RIGID STEEL CONDUIT OR INTERMEDIATE
METAL CONDUIT BELOW EIGHT FEET OR WHERE SUBJECT TO DAMAGE. USE RIGID STEEL
CONDUIT, INTERMEDIATE METAL CONDUIT, OR ELECTRICAL METALLIC TUBING ABOVE
EIGHT FEET OR IN ELECTRICAL, MECHANICAL OR TELECOMMUNICATION ROOMS. USE
SHEET-METAL OR CAST METAL BOXES. USE FLUSH MOUNTING OUTLET BOX IN FINISHED
AREAS. PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES.
I. PRODUCT REQUIREMENTS: PROVIDE PRODUCTS AS FOLLOWS:
1. STRANDED CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS.
2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS.
3. CONDUCTOR NOT SMALLER THAN 12 AWG FOR POWER AND LIGHTING CIRCUITS.
4. CONDUCTOR NOT SMALLER THAN 12 AWG FOR LINE VOLTAGE CONTROL CIRCUITS
(120-VOLT).
5. CONDUCTOR NOT SMALLER THAN 16 AWG FOR CONTROL CIRCUITS.
6. INCREASE WIRE SIZE IN BRANCH CIRCUITS TO LIMIT VOLTAGE DROP TO A MAXIMUM
OF 3 PERCENT.
7. 10 AWG CONDUCTORS FOR 20 AMPERE OR LARGER AS DESIGNATED ON PLANS FOR
120-VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 75 FEET.
J. CONDUCTOR AND CABLE APPLICATIONS:
1. DO NOT USE CONDUCTORS AND CABLES FOR APPLICATIONS OTHER THAN AS
PERMITTED BY NFPA 70 AND PRODUCT LISTING.
2. PROVIDE SINGLE CONDUCTOR BUILDING WIRE INSTALLED IN SUITABLE RACEWAY
UNLESS OTHERWISE INDICATED, PERMITTED, OR REQUIRED.
3. ARMORED CABLE IS NOT PERMITTED.
4. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE
THHN/THWN-2 INSULATION, IN RACEWAY.
5. EXPOSED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN-2
INSULATION, IN RACEWAY.
6. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN/THWN-2
INSULATION, IN RACEWAY.
7. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN-2
INSULATION, IN RACEWAY.
8. EXTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE XHHW-2 INSULATION, IN
RACEWAY.
9. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE, TYPE XHHW-2 INSULATION, IN
RACEWAY.
K. WIRING DEVICE APPLICATIONS:
1. PROVIDE WIRING DEVICES SUITABLE FOR INTENDED USE AND WITH RATINGS
ADEQUATE FOR LOAD SERVED.
1.09 DEMOLITION:
A. REMOVAL OF EXISTING ELECTRICAL EQUIPMENT, WIRING, AND CONDUIT IN AREAS TO BE
REMODELED; REMOVAL OF DESIGNATED CONSTRUCTION; DISMANTLING, CUTTING AND
ALTERATIONS FOR COMPLETION OF THE WORK.
1. PROTECT ITEMS TO REMAIN.
2. RELOCATE EXISTING EQUIPMENT TO ACCOMMODATE CONSTRUCTION.
3. CONDUCT DEMOLITION TO MINIMIZE INTERFERENCE WITH ADJACENT AND OCCUPIED
BUILDING AREAS.
4. COORDINATE DEMOLITION WORK WITH OWNER'S REPRESENTATIVE AND ALL OTHER
DISCIPLINES.
5. COORDINATE AND SEQUENCE DEMOLITION SO AS NOT TO CAUSE SHUTDOWN OF
OPERATION OF SURROUNDING AREAS.
6. SHUT-DOWN PERIODS:
a. ARRANGE TIMING OF SHUT-DOWN PERIODS OF IN-SERVICE PANELS WITH
OWNER'S REPRESENTATIVE. DO NOT SHUT DOWN ANY UTILITY WITHOUT PRIOR
WRITTEN APPROVAL AND SUBMITTING A “METHOD OF PROCEDURE” FOR REVIEW
b. KEEP SHUT-DOWN PERIOD TO MINIMUM OR USE INTERMITTENT PERIOD AS
DIRECTED BY OWNER'S REPRESENTATIVE.
c. MAINTAIN LIFE-SAFETY SYSTEMS IN FULL OPERATION IN OCCUPIED FACILITIES OR
PROVIDE NOTICE MINIMUM 72 HOURS IN ADVANCE AND FIRE WATCH.
7. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER.
1.10 DRAWINGS AND COORDINATION WITH OTHER WORK:
A. DRAWINGS:
1. FOR PURPOSES OF CLARITY AND LEGIBILITY, DRAWINGS ARE ESSENTIALLY
DIAGRAMMATIC TO THE EXTENT THAT MANY OFFSETS, BENDS, SPECIAL FITTINGS,
AND THE EXACT LOCATIONS OF ITEMS ARE NOT SHOWN, UNLESS SPECIFICALLY
DIMENSIONED.
2. EXACT ROUTING OF WIRING AND LOCATIONS OF OUTLETS, PANELS, AND OTHER
ITEMS, SHALL BE GOVERNED BY STRUCTURAL CONDITIONS, AND MATERIALS AND
EQUIPMENT ALREADY IN PLACE. USE DATA IN THE CONTRACT DOCUMENTS. IN
ADDITION, THE ARCHITECT RESERVES THE RIGHT, AT NO INCREASE IN CONTRACT
SUM, TO MAKE ANY REASONABLE CHANGE IN LOCATIONS OF EXPOSED ELECTRICAL
ITEMS, TO GROUP THEM INTO ORDERLY RELATIONSHIP AND/OR INCREASE THEIR
UTILITY. VERIFY THE ARCHITECT'S REQUIREMENTS IN THIS REGARD PRIOR TO
ROUGHING-IN.
3. DIMENSIONS, LOCATIONS OF DOORS, PARTITIONS AND SIMILAR PHYSICAL…