4._24WS0033_-_Construction_Drawings.pdf

PDF 26 MB Posted

Attached to
24WS0033 - FREEZER COOLER CONDENSER RETROFIT
Solicitation number
0000034950
Issued by
Los Angeles County, East Los Angeles CDP, Lake Los Angeles CDP, Los Angeles City, California

About this file

This document is a comprehensive set of construction drawings and specifications for a Freezer Cooler Condenser Retrofit project for the California Department of Veterans Affairs at the West Los Angeles Veterans Home. The project involves replacing evaporative coolers and condensing units for freezers and coolers on the lower level and first level servery, including associated refrigerant line replacements, electrical power connections to new equipment, and roofing repairs at pipe penetrations. The project site is located at 11500 Nimitz Avenue, Los Angeles, CA 90049, and involves work in Area D of the facility. The drawings are prepared by HMR Architects and dated June 21, 2024, with electrical engineering by Edge Electrical Consultants and mechanical engineering by Turley & Associates.

The project involves electrical and mechanical retrofit work across multiple levels, with detailed plans for demolition and new installations. The electrical scope includes replacing existing disconnects, modifying panel schedules, and installing new conduits and wiring for the refrigeration equipment. The work is being performed under Office of the State Fire Marshal Permit #24-S-2859 and adheres to 2022 California Building, Electrical, Mechanical, and Fire Codes. The electrical systems will connect to existing panels including EDPD, 1ELDD, and 1ELD, with careful attention to maintaining existing electrical infrastructure while upgrading the refrigeration systems' electrical components. The project appears to be funded through the California Department of Veterans Affairs and is intended to improve the mechanical systems of the Veterans Home.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

RL

KD

/1

/2

:0 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \0

-W

LA

A

C

O V E R S H E E T .D

W G

FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

V2

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

11500 NIMITZ AVE, LOS ANGELES, CA 90049

PROJECT

SITE

VETERANS HOME OF

WEST LOS ANGELES

FREEZER COOLER CONDENSER

RETROFIT

SCOPE OF WORKVICINITY MAP

NOT TO SCALE

CLIENT REPRESENATIVE

INDEX TO DRAWINGS

HMR ARCHITECTS

2130 21st STREET

SACRAMENTO, CA 95818

(916) 736-2724

CONTACT: KIM DEMONGEY

EMAIL: kimd@hmrarchitects.com

ARCHITECTURAL

A0 COVER SHEET

A0.1 REFERENCE CODE ANALYSIS, LEVEL 1

A0.2 REFERENCE CODE ANALYSIS, LEVEL 0

A1.1 PARTIAL FLOOR PLAN - AREA D - LOWER LEVEL

A1.2 PARTIAL FLOOR PLAN - AREA D - LEVEL 1

A2.0 PARTIAL ROOF PLAN - AREA D

COUNT 6 SHEETS

MECHANICAL

M0.1 MECHANICAL LEGEND, SCHEDULE, AND NOTES

M1.1 MECHANICAL DEMOLIION FLOOR PLAN - LOWER LEVEL, AREA D

M1.2 MECHANICAL DEMOLIION FLOOR PLAN - LEVEL 1, AREA D

M2.1 MECHANICAL FLOOR PLAN - LOWER LEVEL, AREA D

M2.2 MECHANICAL FLOOR PLAN - LEVEL 1, AREA D

M3.1 MECHANICAL DEMOLIION ROOFPLAN - AREA D

M3.2 MECHANICAL ROOF PLAN - AREA D

M4.1 MECHANICAL DETAILS

COUNT 8 SHEETS

T-24

T-24 T-24 COMPLIANCE

COUNT 1 SHEETS

ELECTRICAL

E0.1 ABBREVIATIONS, NOTES, MECHANICAL SCHEDULE, & SHEET INDEX

E0.2 ELECTRICAL SPECIFICATIONS

E0.3 ELECTRICAL SPECIFICATIONS

E0.4 ELECTRICAL SPECIFICATIONS

E1.0 PARTIAL DEMOLITION PLAN - AREA D, LOWER LEVEL

E1.1 PARTIAL DEMOLITION PLAN - AREA D, LEVEL 1

E1.2 PARTIAL DEMOLITION ROOF PLAN - AREA D

E2.0 PARTIAL FLOOR PLAN - AREA D, LOWER LEVEL

E2.1 PARTIAL FLOOR PLAN - AREA D, LEVEL 1

E2.2 PARTIAL ROOF PLAN - AREA D

E3.0 PARTIAL ONE-LINE DIAGRAM

E3.1 PANEL SCHEDULES

E4.0 ELECTRICAL DETAILS

E4.1 ELECTRICAL DETAILS

E4.2 ELECTRICAL DETAILS

E4.3 ELECTRICAL DETAILS

E4.4 ELECTRICAL DETAILS

COUNT 17 SHEETS

TOTAL 32 SHEETS

ARCHITECT

ELECTRICAL ENGINEER

DEFERRED APPROVAL

1. REPLACE EVAPORATIVE COOLERS AND CONDENSING UNITS AT FREEZERS AND

COOLERS IN LOWER LEVEL AND FIRST LEVEL SERVERY.

2. REPLACE ASSOCIATED REFRIGERANT LINES.

3. PROVIDE ELECTRICAL POWER TO NEW EQUIPMENT.

4. ROOFING AT PIPE PENETRATIONS.

DEPARTMENT OF VETERANS AFFAIRS

1227 O STREET

SACRAMENTO, CA 95814

(916) 278-6313 CONTACT: DANIELLE De SILVA EMAIL: Danielle.DeSilva@calvet.ca.gov

1. NONE

EDGE ELECTRICAL CONSULTANTS

1807 7th STREET, SUITE 150

SACRAMENTO, CA 95811

(916) 329-8402

CONTACT: WILL KWONG

EMAIL: william@edge-econsulting.com

CALIFORNIA DEPARTMENT OF VETERANS AFFAIRS

A:

& AND

A.B. ANCHOR BOLT

A.C. ASPHALT CONCRETE

A/C AIR CONDITIONING

ACC. ACCESSIBLE

ACOUST. ACOUSTICAL

A.A. AREA DRAIN

ADJ. ADJUSTABLE

A.F.F. ABOVE FINISH FLOOR

AGGR. AGGREGATE

ALUM. ALUMINUM

APPROX. APPROXIMATE

ARCH. ARCHITECT(URAL)

B:

B&B BOARD AND BATTEN

BD. BOARD

BLDG. BUILDING

BLK'G. BLOCKING

BM. BEAM

B.M. BENCH MARK

BTTM. BOTTOM

B.U.R. BUILT UP ROOFING

C:

C.B. CATCH BASIN

C.I. CAST IRON

C.J. CONSTRUCTION JOINT

CLF CHAIN LINK FENCE

CLG. CEILING

CLR. CLEAR

CLKG. CAULKING

CNTR. COUNTER

C.O. CLEAN OUT

COL. COLUMN

CONC. CONCRETE

COND. CONDITION

CONST. CONSTRUCTION

CONT. CONTINUOUS

C.O.T.G. CLEAN OUT TO

GRADE

C.A. CONTROL POINT

CTSK. COUNTERSUNK

D:

DBL. DOUBLE

D.F. DRINKING FOUNTAIN

DEPT. DEPARTMENT

DTL. DETAIL

D.I. DROP INLET

DIAG. DIAGONAL

DIM. DIMENSION

DN. DOWN

DR. DOOR

D.S. DOWN SPOUT

D.S.P. DRY STANDPIPE

DWG. DRAWING

E:

E EAST

(E) EXISTING

EA. EACH

E.D.F. ELECTRIC DRINKING

FOUNTAIN

E.F. EXHAUST FAN

E.J. EXPANSION JOINT

ELEC. ELECTRICAL

ELEV. ELEVATION

EMER. EMERGENCY

ENCL. ENCLOSURE

E.P. ELECTRICAL PANEL

EQ. EQUAL

EQUIP. EQUIPMENT

E.W. EACH WAY

EXPO. EXPOSED

EXP. EXPANSION

EXT. EXTERIOR

F:

F.A. FIRE ALARM

F.B. FLAT BAR

F.C. FRAMING CLIP

F.D. FLOOR DRAIN

FDN. FOUNDATION

F.F. FINISH FACE

F.E. FIRE EXTINGUISHER

F.L. FLOW LINE

FLR. FLOOR

F.O.C. FACE OF CONCRETE

F.O.F. FACE OF FINISH

F.O.M. FACE OF MASONRY

F.O.W. FACE OF WALL

F.P. FIREPROOF

F.R.P. FIBERGLASS

REINFORCED PANEL

F.O.S. FACE OF STUD

F.S.D. FIRE SMOKE DAMPER

FT. FOOR OR FEET

FTG. FOOTING

F.V. FIELD VERIFY

G:

GA. GAUGE

GALV. GALVANIZED

G.C. GENERAL CONTRACTOR

G.I. GALVANIZED IRON

GLU-LAM GLUE LAMINATER

GND. GROUND

GYP. BD. GYPSUM WALLBOARD

H:

H.B. HOSE BIB

H.C. HOLLOW CORE

HDWD. HARDWOOD

HDBD. HARDBOARD

HDWE. HARDWARE

H.M. HOLLOW METAL

HORIZ. HORIZONTAL

HR. HOUR

HT. HEIGHT

I-J-K-L:

I.D. INSIDE DIAMETER

I.E. INVERT ELEVATION

ISA INTERNATIONAL

SYMBOL

OF ACCESSIBILITY

INSUL. INSULATION

INT. INTERIOR

J.B. JUNCTION BOX

J.H. JOIST HANGER

JT. JOINT

KIT. KITCHEN

LAB. LABORATORY

LAM. LAMINATE

LAV. LAVATORY

LT. LIGHT

L.H. LEFT HAND

M:

MAX. MAXIMUM

M.C. MEDICINE CABINET

MECH. MECHANICAL

MEMB. MEMBRANE

MFR. MANUFACTURER

M.H. MANHOLE

MIN. MINIMUM

MISC. MISCELLANEOUS

M.O. MASONRY OPENING

MTL. METAL

N:

N. NORTH

(N) NEW

N.I.C. NOT IN CONTRACT

NOM. NOMINAL

N.T.S. NOT TO SCALE

O:

OBS. OBSCURE

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

O.H. OVERHEAD OR

OVERHANG

OPNG. OPENING

OPP. OPPOSITE

O/ OVER

P:

PART. PARTITION

P.B. PANIC BAR

P.L. PROPERTY LINE

P.LAM. PLASTIC LAMINATE

PLAS. PLASTER

PLYWD. PLYWOOD

P.M. PRESSED METAL

P.O.C. POINT OF CONNECTION

PR. PAIR

PROP. PROPERTY

P.S.F. POUNDS PER SQUARE

FOOT

P.S.I. POUNDS PER SQUARE

INCH

P.T. PRESSURE TREATED

Q-R

Q.T. QUARRY TILE

R. RISER

RAD. RADIUS

R.D. ROOF DRAIN

R.E. RIM ELEVATION

REBAR REINFORCING BAR

REF. REFERENCE

REQ'D. REQUIRED

RM. ROOM

R.O. ROUGH OPENING

RWD. REDWOOD

R.W.L. RAIN WATER LEADER

S:

S. SOUTH

S.B. SPLASH BLOCK

S.D. STORM DRAIN

SEC. SECURITY

S.C. SOLID CORE

SCHED. SCHEDULE

SECT. SECTION

SHT. SHEET

SHTG. SHEATHING

SIM. SIMILAR

S.M. SHEET METAL

S.M.S. SHEET METAL SCREW

SPEC'S. SPECIFICATIONS

SQ. SQUARE

S.STL. STAINLESS STEEL

STD. STANDARD

STL. STEEL

STRUCT. STRUCTURAL

S.T.S.M.S. SELF TAPPING SHEET

METAL SCREW

S.S SANITARY SEWER

S/S SERVICE SINK

SUSP. SUSPENDED

SYM. SYMMETRICAL

T:

T.O.C. TOP OF CURB

T&G TOUNGE & GROOVE

T.O.C. TOP OF CONCRETE

T.O.F. TOP OF FRAMING

T.O.S. TOP OF STEEL

TOT. TOTAL

T.O.W. TOP OF WALL

T.P. TOP OF PAVING

TS STRUCTURAL TUBE

TYP. TYPICAL

U:

U.N.O. UNLESS NOTED

OTHERWISE

UNF. UNFINISHED

V:

V.C.T. VINYL COMPOSITION

TILE

V.C.F. VINYL COATED FABRIC

VEN. VENDER

VERT. VERTICAL

V.T.B. VINYL TABK BOARD

V.W.C. VINYL WALL COVERING

W:

W/ WITH

W.C. WATER CLOSET

WD. WOOD

W.H. WATER HEATER

W.M. WATERPROOF

MEMBRANE

W/O WITHOUT

W.R. WATER RESISTANT

WT. WEIGHT

W.W.F. WELDED WIRE FABRIC

A-*

A-*

A-*

1A

X

PL

C

L

CONCRETE

CONCRETE

BLOCK

CERAMIC TILE OR

BRICK

A.C. PAVING

SAND MORTAR

OR PLASTER

AGGREGATE

EARTH

METAL

PLYWOOD

GYPSUM BOARD

GLASS

WOOD FRAMING

(CONT. MEMBER)

WOOD FRAMING

(BLOCKING)

WOOD MEMBER

(FINISHED)

INSULATION

ROOM NUMBER

WINDOW TYPE

DOOR NUMBER

GRID LINE/NUMBER

GRID CENTER

LINE/NUMBER

SHEET WHERE

SECTION IS

DRAWN

SHEET WHERE

DETAIL IS DRAWN

SHEET WHERE ENLARGED

PLAN IS DRAWN

SHEET WHERE

ELEVATION IS DRAWN

DETAIL NUMBER

SECTION NUMBER

LOCATION NUMBER

ELEVATION NUMBER

EQUIPMENT NUMBER

PARTITION TYPE

KEYNOTE

REVISION NUMBER

MATCH LINE

DATUM, WORK OR

CONTROL NUMBER

ANGLE

DIAMETER OR ROUND

PERPENDICULAR

POUND OR NUMBER

CENTERLINE

PLATE OR PROPERTY

LINE

MECH. / PLUMB. ENGINEER

TURLEY & ASSOCIATES

2431 CAPITOL AVENUE

SACRAMENTO, CA 95816

(916) 325-1065

CONTACT: TIM FLAGG

EMAIL: tflagg@turleymech.com

SYMBOLS LEGEND

ABBREVIATIONS LIST

SHEET

NUMBER

DESCRIPTION

A0

COVER SHEET

SITE MAP

WEST LA

VETERANS HOME

NORTH

NOT TO SCALE

NORTH

NOT TO SCALE

PERMIT / APPLICATION NUMBERS:

OFFICE OF THE STATE FIRE MARSHAL # 24-S-2859

CODES USED:

2022 CALIFORNIA ADMINISTRATIVE CODE, CCR, TITLE 24, PART 1

2022 CALIFORNIA BUILDING CODE, VOL. 1 & 2, CCR, TITLE 24, PART 2

2022 CALIFORNIA ELECTRICAL CODE, CCR, TITLE 24, PART 3

2022 CALIFORNIA MECHANICAL CODE, CCR, TITLE 24, PART 4

2022 CALIFORNIA PLUMBING CODE, CCR, TITLE 24, PART 5

2022 CALIFORNIA ENERGY CODE, CCR, TITLE 24, PART 6

2022 CALIFORNIA FIRE CODE, CCR, TITLE 24, PART 9

2022 CALIFORNIA GREEN BUILDING STANDARDS CODE, CCR, TITLE 24, PART 11

2022 CALIFORNIA EXISTING BUILDING CODE, CCR, TITLE 24, PART 10

TITLE 19, CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS

JURISDICTION HAVING AUTHORITY: OFFICE OF THE STATE FIRE MARSHAL (OSFM)

THIS PROJECT IS A "TENANT IMPROVEMENT" WITHIN AN EXISTING SPACE, WHICH IS LOCATED ON

THE LOWER & FIRST FLOOR OF AREA D IN THE WEST LA VETERANS

HOME AT 11500 NIMITZ AVENUE, LOS ANGELES, CA 90049. CALVET IS BOTH THE OWNER AND

OCCUPANT OF THIS SPACE.

THIS IS NOT A DEFERRED SUBMITTAL, AND THERE ARE NO DEFERRED SUBMITTALS FOR THIS

PROJECT.

EXISTING BUILDING ANALYSIS OF THE WEST LA VETERANS HOME IS BASED ON DRAWINGS "ISSUED

FOR BID" IN 2006, AS FOLLOWS:

* OCCUPANCY GROUPS (SEE ALSO ACCESSORY USES BELOW)

- I-2 = BUILDING AREAS A (SNF), B (SNF SUPPORT), C (SNF), AND E (RCFE AND

DEMENTIA/ALZHEIMER'S UNITS), WHICH ARE INDICATED IN THE

REFERENCE DRAWINGS AS I-1.1 PER CBC 2001

- B = BUILDING AREA D MEMBER SERVICES, AND BUILDING AREA F UTILITY BUILDING

* CONSTRUCTION TYPES

- I-A = BUILDING AREAS A, B, C, D, AND E

- II-B = BUILDING AREA F

* NUMBER OF STORIES: N/A

* BUILDING AREA: N/A

* PROJECT AREA

LIMITED TO THE KITCHEN ON LOWER LEVEL, LEVEL 1 & ROOF OF BUILDING AREA D

- 1,019 SF FOR BASE DESIGN IN THE LOWER LEVEL ONLY

- 136 SF FOR BASE DESIGN IN THE LEVEL 1

- 117 SF FOR BASE DESING IN THE ROOF LEVEL

* THE EXISTING BUILDING WAS DESIGNED AS SEPARATED WITH ACCESSORY USES.

* SEPARATIONS:

- 2-HOUR RATED SEPARATION WALLS AROUND SHAFTS, STAIRWELLS, AND ELEVATORS

- 1-HOUR RATED SEPARATION WALLS AROUND STORAGE, ELECTRICAL, AND IT ROOMS

- 1-HOUR RATED SEPARATION SMOE BARRIER WALLS BETWEEN BUILDING AREAS A, B, C, D, & E

- 1-HOUR CORRIDOR WALLS

- 1-HOUR OR 2-HOUR RATED EXTERIOR WALLS

- SEE REFERENCE DRAWINGS ON SHEET A0.1 AND A0.2

*ACCESSORY USES: N/A

* AREA TOTALS BY OCCUPANCY TYPE (INCLUDING ACCESSORY USES): N/A

* ALLOWABLE AREA: UNLIMITED

* AREA INCREASE: N/A

* HEIGHT INCREASE: N/A

* FIRE SPRINKLERS: FULLY SPRINKLERED

* FIRE ALARM: EXISTING SYSTEM WITH AUTOMATIC HEAT AND SMOKE DETECTORS AND MANUAL

PULLS STATIONS

* OTHER FIRE PROTECTION SYSTEM: N/A

* SMOKE CONTROL SYSTEM: NO

* OCCUPANT LOAD OF ENTIRE BUILDING: N/A

* OCCUPANT LOAD OF EACH FLOOR: N/A

* YEAR BUILDING WAS CONSTRUCTED: 2010

* HIGH FIRE HAZARD SEVERITY ZONE: NO

* SEISMIC JOINTS AND LOCATIONS: YES, BETWEEN BUILDING AREAS A, B, C, D, AND E

* EMERGENCY RESPONDERS RADIO COVERAGE: FM RADIO NETWORK FOR INTER-BUILDING

COMMUNICATIONS, USING KENWOOD "ADVANCED COMMUNICATIONS SYSTEM", AND CARRIED

BY SECURITY FORCE AT ALL TIMES.

SFM PERMIT #24-S-2859 1

PROJECT CODE DATA

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2859 http://www.hmrarchitects.com

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

RL

KD

/1

/2

:1 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \0

-W

LA

A

C

O V E R S H E E T .D

W G

FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

V2

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

A0.1

REFERENCE CODE ANALYSIS PLAN

LEVEL 1

V1

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

RL

KD

/1

/2

:2 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \0

-W

LA

A

C

O V E R S H E E T .D

W G

FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

V2

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

A0.2

REFERENCE CODE ANALYSIS PLAN

LEVEL 0

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

PARTIAL FLOOR PLAN - AREA D - LOWER LEVEL

FILE: SCALE: 1/8"=1'-0"

FREEZER

D075A

COOLER

D075B

P01 P01

OPEN COVERED WALK

OPEN

AREA

STORAGE

33 37

UU

TT

35 38

WW

DRY

STORAGE

D075C

CARTS

D075D

MECHANICAL

ELECTRICAL

D075F

WAREHOUSE

STORAGE

D075G

LOUNGE

D078

WAREHOUSE

D072

02 CYLINDER

STORAGE

F085

STORAGE

F084

JANITOR

D074

HALL

D075E

STORAGE

D075H

STORAGE

D075J

SERVICE

CORRIDOR

D071

STORAGE

D043B

WORKSTATION

D043

OFFICE

D043A

ELECTRICAL

WAREHOUSE

D042

EMPLOYEE

LAUNDRY

D040

ELECTRICAL

D007

OFFICE

D008

AREA OF WORK

/1

/2

:3 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \W

LA

A F

LO

O R P

LA

N S .D

W G

A1.1

PARTIAL FLOOR PLAN

- AREA D - LOWER LEVEL

KEYNOTES

NORTHNORTH

1D

A1.1

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

RL

KD

/1

/2

:3 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \W

LA

A F

LO

O R P

LA

N S .D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

V2

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

KEYNOTES

1 HOUR RATED CORRIDOR

2 HOUR RATED SEPARATION WALL

AND SHAFT ENCLOSURES

1 HOUR RATED SEPARATION WALL

P01 REMOVE AND REPLACE EVAPORATIVE COOLER.

SEE MECHANICAL AND ELECTRICAL SHEETS

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

PARTIAL FLOOR PLAN - AREA D - LEVEL 1

33 37

UU

TT

35 38

WW

COOLER

D141C

FREEZER

D141B

FOOD

PREPARATION

D141

P01

DINING

D140

SERVERY

D140A

LOUNGE/LOCKERS

D142

PREP.

D141G

HALLWAY

D143 STAFF

TOILET

D142A

POTWASH

D141F

STORAGE

D141E

OFFICE

D141D

STORAGE

D141A

SERVICE

CORRIDOR

D103

ELECTRICAL

D108

STAFF

TOILET

D107

TELECOM

/SIGNAL

D106

SHAFT

D109

ELEV.

STORAGE

D140B

VENDING

D140C

AREA OF WORK

/1

/2

:3 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \W

LA

A F

LO

O R P

LA

N S .D

W G

A1.2

PARTIAL FLOOR PLAN

- AREA D - LEVEL 1

KEYNOTES

NORTHNORTH

1D

A1.1

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

RL

KD

/1

/2

:3 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \W

LA

A F

LO

O R P

LA

N S .D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

V2

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

KEYNOTES

(E) 1 HOUR RATED CORRIDOR

(E) 2 HOUR RATED SEPARATION WALL

AND SHAFT ENCLOSURES

(E) 1 HOUR RATED SEPARATION WALL

(E) 1-HOUR WALL CONSTRUCTION (EXTERIOR

WALL)

P01 REMOVE AND REPLACE EVAPORATIVE COOLER.

SEE MECHANICAL AND ELECTRICAL SHEETS

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

PARTIAL ROOF PLAN - AREA D

R F

R F

33 37

UU

TT

35 38

WW

LEVEL 5 ROOF

(NO WORK)

LOWER LEVEL ROOF

RP2

RP4

RP3

RP4

RP1

RP5

TYP.

RP3

RP4

RP6

LEVEL 2 ROOF

(NO WORK)

RP6

RP7 RP7

AREA OF WORK

PREFORMED FIELD WRAPPED

FLASHING AT ROOF PENETRATION

OR ROOF MOUNTED EQUIPMENT

FILE: SCALE: 1 1/2"=1'-0"

(E) PIPE PENETRATION

SEALANT

S.STL.CLAMP

PREMOLDED

PIPE BOOT

WELDED

SEAM CONT.

(E) PIPE AS OCCURS

BONDING

ADHESIVE

WATER

BLOCK

/4

"C

LR

S.STL.CLAMP

SEALANT

/4

"C

LR

FIELD WRAPPED

FLASHING

MEMBRANE

MEMBRANE

TARGET

WELDED SEAM

CONT.

(E) SINGLE PLY

ROOFING

(E) INSUL.(E) CONCRETE

ROOF DECK

1/2" GAP MAX.1/2" GAP MAX.

/1

/2

:3 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \W

LA

A .0

R O O F P

LA

N .D

W G

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

RL

KD

/1

/2

:3 P

M

K

IM

D E G O V E R N M

E N T \C

A L V E T \2

C

A L V E T W

LA

F R E E Z E R C O O

LE

R C

O N D E N S E R R

E T R O F

IT

P R O

JE

C T \W

LA

A .0

R O O F P

LA

N .D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

V2

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

A2.0

PARTIAL ROOF PLAN

- AREA D

(E) SINGLE PLY TPO ROOFING TO REMAIN. USE COMPATIBLE MATERIALS FOR

PATCHING.

KEYNOTES

RP1

(E) ROOF DRAIN AND OVERFLOW TO REMAIN

RP2

RP3

(E) HVAC UNIT TO REMAINRP4

RP5

(E) PARAPET TO REMAIN

(E) WALK PADS TO REMAIN

RP6

RP7

1D

A2.0

NORTHNORTH

THRU ROOF PIPE PENETRATION, SEE DETAIL

5D

A2.0

5D

A2.0

REMOVE AND REPLACE CONDENSING UNIT.

SEE MECHANICAL AND ELECTRICAL SHEETS

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

MECHANICAL LEGEND MECHANICAL ABBREVIATIONS

COMPLIANCE NOTES

APPLICABLE CODES

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

T F

LA

G G

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.1

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M0.1

MECHANICAL LEGEND,

SCHEDULES, AND NOTES

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

WW

UU

35 3733

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

LC

O X

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.1

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M1.1

MECHANICAL DEMOLITION

FLOOR PLAN - LOWER LEVEL

AREA D

KEY PLAN

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

TT

UU

3835 37

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

LC

O X

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.2

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M1.2

MECHANICAL DEMOLITION

FLOOR PLAN - LEVEL 1 AREA D

KEY PLAN

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

UU

35 3733

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

LC

O X

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.1

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M2.1

MECHANICAL FLOOR PLAN -

LOWER LEVEL AREA D

KEY PLAN

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

TT

UU

3835 37

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

LC

O X

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.2

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M2.2

MECHANICAL FLOOR PLAN -

LEVEL 1 AREA D

KEY PLAN

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

35 3733

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

T F

LA

G G

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.1

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M3.1

MECHANICAL DEMOLITION ROOF

PLAN - AREA D

KEY PLAN

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

35 3733

JUNE 21, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

T F

LA

G G

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \M

.2

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M3.2

MECHANICAL ROOF PLAN - AREA

D

KEY PLAN

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

T F

LA

G G

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N S E R \M

.1

.D

W

G FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

M4.1

MECHANICAL DETAILS

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

CHECKED BY:

JOB NO.

REVISIONS

DESCRIPTION DATENO.

T&A

T&A

/1

/2

:0 P

M

T F

LA

G G

Z

JO

B F

IL

E S \2

\2

\2

C

A

LV

E T W

E S T L A V

E T E R A N 'S H

O M

E F R E E Z E R C

O O

LE

R C

O N D E N

SE

R \T

.D

W G

FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

1 SFM COMMENTS 09/13/24

& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

24109BP

NS

ZH

T24

TITLE 24

COMPLIANCE

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

NON FUSED DISCONNECT SWITCH.

CONTROL AND/OR EQUIPMENT, PROVIDED UNDER ANOTHER DIVISION,

PROVIDE POWER CONNECTION AS INDICATED.

EQUIPMENT, PROVIDED UNDER ANOTHER DIVISION, PROVIDE POWER-

CONNECTION AS INDICATED.

BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED.

RACEWAY INSTALLED IN CEILING OR WALL. ROUTE EXPOSED IN ALL

UNFINISHED AREAS.

RACEWAY INSTALLED BELOW FINISHED FLOOR, GRADE, OR STRUCTURE

CEILING.

EXISTING CONDUIT RUN TO BE ABANDONED. CONDUIT ABOVE THE FLOOR

AND BELOW THE STRUCTURE ABOVE SHALL BE REMOVED. CONDUCTORS

SHALL BE REMOVED.

X

EXISTING CONDUIT RUN, VERIFY ROUTING ON THE JOB.

REMOVE (E) WIRE, PULL IN NEW WIRES, #12 AWG UNLESS NOTED.

ARROW AT END OF RACEWAY INDICATES HOME RUN TO RESPECTIVE

PANELBOARD OR SWITCHBOARD.

BRANCH CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES A 2 #12 AWG

CIRCUIT WITH 1 #12 AWG GROUND.

STRAIGHT CROSS-LINES IN BRANCH CIRCUIT RACEWAY INDICATE NUMBER

OF #12 AWG WIRES IN A CIRCUIT. SHORT LINES INDICATE UNGROUNDED

CONDUCTORS. LONG LINES INDICATE NEUTRAL CONDUCTORS. WIRES

SHOWN ARE IN ADDITION TO 1 #12 AWG GROUNDING CONDUCTOR.

INDICATES RACEWAY TURNING DOWN.

POWER DISTRIBUTION SYMBOLS

SYMBOL DESCRIPTION

RACEWAY SYMBOLS

SYMBOL DESCRIPTION

ABBREVIATIONS

1PH, 3PH 1 PHASE, 3 PHASE

1P, 2P, 3P 1 POLE, 2 POLE, 3 POLE

3W, 4W 3 WIRE, 4 WIRE

(D) DEMO, DEMOLISH

(E) EXISTING

(ER) EXISTING RELOCATED

(N) NEW

(R) RELOCATE

-A-

A, AMPS AMPERES

AC ALTERNATING CURRENT

AF FRAME RATING IN AMPERES

AFF ABOVE FINISHED FLOOR

AIC AMPERES INTERRUPTING

CAPACITY

AL, ALUM ALUMINUM

ATS AUTO TRANSFER SWITCH

AT TRIP RATING IN AMPERES

AWG AMERICAN WIRE GAUGE

-B-

BTR BUILDING TELECOM ROOM

-C-

C CONDUIT

CB,C/B CIRCUIT BREAKER

CEC CALIFORNIA ELECTRICAL CODE

CT CURRENT TRANSFORMER

CU COPPER

-D-

DC DIRECT CURRENT

-E-

EA EACH

ELEC ELECTRICAL

EMT ELECTRICAL METALLIC TUBING

-F-

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FLA FULL LOAD AMPS

FT FOOT OR FEET

-G-

G, GND GROUND

GA GAUGE

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFI GROUND FAULT INTERRUPTER

-H-

HOA HAND-OFF-AUTO

HP HORSE POWER

-J-

J-BOX JUNCTION BOX

-K-

KVA ONE THOUSAND VOLT-AMPS

KW ONE THOUSAND WATTS

-L-

LCP LIGHTING CONTROL PANEL

LTG LIGHTING

-M-

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVER-CURRENT

PROTECTION

MT EMPTY CONDUIT W/ PULL-LINE

-N-

NC NORMALLY CLOSED

NCTC NURSE CALL TERMINAL CABINET

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER ASSOCIATION

NIES NOT INCLUDED IN ELECTRICAL

SCOPE

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

-O-

OCP OVER-CURRENT PROTECTION

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER

INSTALLED

-P-

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE CONDUIT

-R-

RLA RUNNING LOAD AMP

RSC RIGID STEEL CONDUIT

-S-

SPD SURGE PROTECTION DEVICE

SPDT SINGLE POLE DOUBLE THROW

SPST SINGLE POLE SINGLE THROW

SST SOLID STATE TRIP

-T-

TER TELECOM EQUIPMENT ROOM

TR TELECOM ROOM

TM THERMAL MAGNETIC

TTB TERMINAL BACKBOARD

-U-

UG UNDERGROUND

UL UNDERWRITERS LAB.

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER

SUPPLY

-V-

V VOLTS

VA VOLT-AMPS

VAC VOLTS ALTERNATE CURRENT

-W-

W WATTS

WCR WITHSTAND & CLOSING RATING

WP WEATHERPROOF

-X-

XFMR TRANSFORMER

XFER TRANSFER SWITCH

SHEET INDEX

SHEET DESCRIPTION

ABBREVIATIONS, SYMBOLS, MECHANICAL SCHEDULE & SHEET INDEX

ELECTRICAL SPECIFICATIONS

ELECTRICAL SPECIFICATIONS

ELECTRICAL SPECIFICATIONS

PARTIAL DEMOLITION FLOOR PLAN - AREA D - LOWER LEVEL

PARTIAL DEMOLITION FLOOR PLAN - AREA D - LEVEL 1

PARTIAL DEMOLITION ROOF PLAN - AREA D

PARTIAL FLOOR PLAN - AREA D - LOWER LEVEL

PARTIAL FLOOR PLAN - AREA D - LEVEL 1

PARTIAL ROOF PLAN - AREA D

PARTIAL ONE LINE DIAGRAM

PANEL SCHEDULES

ELECTRICAL DETAILS

ELECTRICAL DETAILS

ELECTRICAL DETAILS

ELECTRICAL DETAILS

ELECTRICAL DETAILS

E0.1

E0.2

E0.3

E0.4

E1.0

E1.1

E1.2

E2.0

E2.1

E2.2

E3.0

E3.1

E4.0

E4.1

E4.2

E4.3

E4.4

FLEX CONDUIT.

NUMBERED NOTE.XX

TRANSFORMER.T

STANDARD ELECTRICAL SYMBOLS

SYMBOL DESCRIPTION

CIRCUIT BREAKER.

2-POLE 1-PHASE MOTOR RATED DISCONNECT SWITCH. AMPERAGE

ADJACENT INDICATES AMPERE RATING OF SWITCH. SWITCH SHALL BE 600V

RATED SWITCH FOR ALL SYSTEMS.

XXA

1-POLE 1-PHASE MOTOR RATED DISCONNECT SWITCH. AMPERAGE

ADJACENT INDICATES AMPERE RATING OF SWITCH. SWITCH SHALL BE

RATED 600V MAXIMUM FOR ALL SYSTEMS.

XXA

FUSED DISCONNECT SWITCH W/ CLASS 'R' DUAL ELEMENT FUSES, SIZED

PER EQUIPMENT NAME PLATE RATING. NUMBER ADJACENT INDICATES

XXA/XP/XXF

AMPERE RATING OF SWITCH / POLES / FUSE RATING. REFER TO PLANS FOR

ACTUAL RATINGS. FUSE SIZE INDICATED ON PLANS IS USED AS THE BASIS

OF DESIGN. FINAL FUSE SIZE INSTALLED SHALL BE CONFIRMED ON THE

FIELD AGAINST EQUIPMENT NAMEPLATE RATING.

GENERAL ELECTRICAL NOTES

1. WHERE PROVIDED, THROUGH-PENETRATION FIRESTOP SYSTEM AND MEMBRANE

PENETRATION DETAILS SHOWN IN THE DETAILS ARE FOR REFERENCE ONLY.

THROUGH- PENETRATIONS AND MEMBRANE PENETRATIONS SHALL BE PROTECTED

BY AN APPROVED PENETRATION FIRESTOP SYSTEM OR MEMBRANE PENETRATION

FIRESTOP SYSTEM INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL

1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) OF

WATER OR AS OTHERWISE PERMITTED BY CBC, SECTION 714. LISTED THROUGH-

PENETRATION FIRESTOP SYSTEMS AND MEMBRANE PENETRATIONS SHALL BE

INSTALLED IN ACCORDANCE WITH THE INSTALLATION DETAILS FOR LISTED SYSTEMS.

LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS, MEMBRANE PENETRATION

PROTECTION AND OTHER PERMITTED MEANS AND METHODS OF PENETRATION

PROTECTION SHALL BE SUBMITTED FOR LOCAL FIRE MARSHAL REVIEW AND

APPROVAL PRIOR TO INSTALLATION.

2. ALL ELECTRICAL EQUIPMENT TO BE INSTALLED OR PERMANENTLY CONNECTED

(HARDWIRED) SHALL BE LISTED, LABELED, OR CERTIFIED BY A NATIONALLY

RECOGNIZED TESTING LABORATORY (NRTL) PER CEC 110.2.

3. ALL EQUIPMENT SHALL BE USED IN ACCORDANCE WITH LISTING PER CEC 110.3B.

MECHANICAL SCHEDULE

DESCRIPTION VOLTAGE/PHASE EQUIPMENT HP FLA KVA REMARKS

EC-C1 208/1 EVAPORATOR COIL 1/15 1.8

EC-C2 208/1 EVAPORATOR COIL 1/15 1.8

EC-F1 208/1 EVAPORATOR COIL 13.7

EC-F2 208/1 EVAPORATOR COIL 13.7

EC-C3 208/1 EVAPORATOR COIL 1/15 1.8

EC-F3 208/1 EVAPORATOR COIL 9.4

CU-1 208/3 CONDENSING UNIT 22.6

CU-2 208/3 CONDENSING UNIT 28.8

CU-3 208/3 CONDENSING UNIT 11.5

CU-4 208/3 CONDENSING UNIT 9.6

JUNCTION BOX, SIZE AND TYPE AS INDICATED OR REQUIRED.J J

INTERRUPTER.

20 AMP 125V 3W DUPLEX CONVENIENCE RECEPTACLE W/ GROUND FAULT

WIRING DEVICE SYMBOLS

SYMBOL DESCRIPTION

DEVICE SUBSCRIPTS DESIGNATE THE FOLLOWING:

= WEATHERPROOFWP

SUBSCRIPTS:

/1

/2

:1 P

M

W

IL

LI

A M

.K W

O N G

D \K

\D

R A W

IN

G S \E

.1

C

O V E R S H E E T .D

W G

FEBRUARY 19, 2024

DRAWN BY:

CHECKED BY:

JOB NO.

RL

KD

/1

/2

:1 P

M

W

IL

LI

A M

.K W

O N G

D \K

\D

R A W

IN

G S \E

.1

C

O V E R S H E E T .D

W G

23052 V1

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING

HEREIN CONSTITUTE ORIGINAL & UNPUBLISHED

WORK OF HMR ARCHITECTS AND MAY NOT BE

DUPLICATED, USED OR DISCLOSED WITHOUT

WRITTEN CONSENT OF HMR ARCHITECTS

Contact

Project Number

Sacramento | Alameda | Irvine

400 R Street, Ste 333

Sacramento, CA 95811 916.256.2460

K339

WILLIAM

REVISIONS

DESCRIPTION DATENO.

FREEZER COOLER

CONDENSER RETROFIT

11500 NIMITZ AVE.

LOS ANGELES, CA 90049

HMRARCHITECTS

2130 21st Street

Sacramento, CA 95818

T 916 736 2724 www.hmrarchitects.com

1 SFM COMMENTS 09/13/24

E0.1

ABBREVIATIONS,

SYMBOLS, MECHANICAL

SCHEDULE & SHEET INDEX

&[Date]10/11/2024

V2

OSFM PERMIT#24-S-2859

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

11/18/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

SECTION 26 00 00 - ELECTRICAL WORK

PART 1 GENERAL

1.01 CONDITIONS:

A. THE REQUIREMENTS OF GENERAL CONDITIONS AND SPECIAL CONDITIONS APPLY TO

WORK OF THIS SECTION AS IF FULLY REPEATED HEREIN.

1.02 WORK INCLUDED:

A. PROVIDE A COMPLETE WORKING INSTALLATION OF ALL ELECTRICAL AS SHOWN OF

DRAWINGS OR AS SPECIFIED.

B. PROVIDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT NECESSARY FOR THE

COMPLETE IN-PLACE INSTALLATION OF ALL ELECTRICAL AND LOW VOLTAGE ITEMS

COMPLETE AS SHOWN ON DRAWINGS AND AS SPECIFIED.

C. COMPLETE NEW BRANCH CIRCUIT PANELBOARDS, CONDUIT, WIRE, PULL BOXES,

JUNCTION BOXES AND MISCELLANEOUS MATERIALS.

D. ELECTRICAL CONNECTIONS TO EQUIPMENT FURNISHED AND INSTALLED UNDER OTHER

SECTIONS.

E. INCLUDE SEALING AND FIREPROOFING OF CONDUITS, CABLE TRAYS, CABLES ETC.

F. ELECTRICAL COMPONENTS ARE IDENTIFIED AS FOLLOWS:

1. NAMEPLATE FOR EACH CONTROL EQUIPMENT ENCLOSURE.

2. LABEL FOR IDENTIFICATION OF RECEPTACLES, LIGHT SWITCHES, AND CONTROL

DEVICE STATIONS.

3. WIRE MARKER FOR EACH CONDUCTOR AT PANEL BOARDS' GUTTERS, PULL BOXES,

OUTLET AND JUNCTION BOXES, AND EACH LOAD CONNECTION.

4. PERMANENT INK FELT TIP MARKER ON COVER INDICATING PANEL AND CIRCUIT FOR

JUNCTION BOXES LOCATED ABOVE SUSPENDED CEILINGS AND BELOW CEILINGS IN

NON-PUBLIC AREAS.

1.03 CODES AND STANDARDS

A. WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH CALIFORNIA OCCUPATIONAL

SAFETY HEALTH ACT (CAL-OSHA), CALIFORNIA ELECTRICAL CODE (CEC), STATE FIRE

MARSHAL, TITLE 8, SAFETY ORDERS OF DIVISION OF INDUSTRIAL SAFETY (ESO), THE

NATIONAL FIRE PROTECTION ASSOCIATION, CALIFORNIA BUILDING CODE (CBC);

CALIFORNIA CODE OF REGULATIONS - TITLE 24 AND OTHER APPLICABLE LAWS OR

REGULATIONS. NOTHING IN THE DRAWINGS OR SPECIFICATIONS SHALL BE CONSTRUED

TO PERMIT WORK NOT CONFORMING TO THESE CODES.

B. WHEN CONTRACT DOCUMENTS DIFFER FROM GOVERNING CODES, FURNISH, AND INSTALL

LARGER SIZE OR HIGHER STANDARDS CALLED FOR WITHOUT EXTRA CHARGE.

1.04 QUALITY ASSURANCE:

A. REQUIREMENTS OF REGULATORY AGENCIES:

1. NOTHING IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO PERMIT WORK

NOT CONFORMING TO APPLICABLE CODES, LAWS, ORDINANCES, RULES, OR

REGULATIONS.

2. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS AND IN ACCORDANCE WITH THE NATIONAL

ELECTRICAL CONTRACTORS ASSOCIATION (NECA) STANDARD OF INSTALLATION.

3. EQUIPMENT TO BE INSTALLED OR PERMANENTLY CONNECTED (HARDWIRED) SHALL

BE LISTED, LABELED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING

LABORATORY (NRTL).

1.05 PERMITS, FEES, AND INSPECTIONS

A. CONTRACTOR SHALL OBTAIN ALL PERMITS AND ARRANGE FOR OWNER TO PAY REQUIRED

FEES TO ANY GOVERNMENTAL AGENCY OR UTILITY COMPANY HAVING JURISDICTION

OVER THE WORK OF THIS SECTION. INSPECTIONS REQUIRED BY ANY LOCAL ORDINANCES

OR UTILITY COMPANIES DURING CONSTRUCTION SHALL BE ARRANGED BY THE

CONTRACTOR.

B. ALL WORK AND MATERIALS COVERED BY THESE SPECIFICATIONS AND ACCOMPANYING

DRAWINGS SHALL ALWAYS BE SUBJECT TO INSPECTION BY THE ARCHITECT OR HIS

REPRESENTATIVE. ANY MATERIAL NOT IN ACCORDANCE WITH THE PLANS AND

SPECIFICATIONS, OR NOT INSTALLED IN A NEAT AND WORKMANLIKE MANNER, SHALL,

UPON ORDER FROM THE ARCHITECT, BE REMOVED FROM THE PREMISES OR CORRECTIVE

ACTION TAKEN WITHIN THREE (3) DAYS; AND IF MATERIAL IN QUESTION HAS BEEN

INSTALLED, THE ENTIRE EXPENSE FOR REMOVING AND REINSTALLING SHALL BE BORNE

BY THE CONTRACTOR.

C. ON COMPLETION OF THE WORK, SATISFACTORY EVIDENCE SHALL BE FURNISHED TO THE

ARCHITECT TO SHOW THAT ALL WORK HAS BEEN INSTALLED IN ACCORDANCE WITH THE

CODES.

D. THE CONTRACTOR SHALL COOPERATE WITH THE ARCHITECT AND SHALL PROVIDE

ASSISTANCE AT ALL TIMES FOR THE INSPECTION OF THE ELECTRICAL WORK PERFORMED

UNDER THIS CONTRACT. CONTRACTOR SHALL REMOVE COVERS, OPERATE MACHINERY,

OR PERFORM ANY REASONABLE WORK WHICH, IN THE OPINION OF THE ENGINEER, WILL

BE NECESSARY TO DETERMINE THE QUALITY AND ADEQUACY OF THE WORK.

1.06 SPECIFICATIONS AND CONTRACT DRAWINGS

A. ACCURACY OF DATA GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACT AS COULD BE

SECURED, BUT THEIR EXTREME ACCURACY IS NOT GUARANTEED. THE DRAWINGS AND

SPECIFICATIONS ARE FOR THE ASSISTANCE AND GUIDANCE OF THE CONTRACTOR AND

EXACT LOCATIONS, DISTANCES, LEVELS, ETC., WILL BE GOVERNED BY THE

CONSTRUCTION AND THE CONTRACTOR SHALL ACCEPT SAME WITH THIS

UNDERSTANDING.

B. LAYOUTS OF EQUIPMENT, ACCESSORIES AND WIRING SYSTEMS ARE DIAGRAMMATIC (NOT

PICTORIAL AND NOT EXACT) BUT SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE.

ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND OTHER DRAWINGS SHALL BE

EXAMINED NOTING ALL CONDITIONS THAT MAY AFFECT THIS WORK. WHERE

CONNECTIONS TO EQUIPMENT PROVIDED BY OTHER DIVISIONS ARE SHOWN ON

ELECTRICAL DRAWINGS, REFER TO DRAWINGS OF RESPECTIVE DIVISION FOR EXACT

LOCATIONS AND ELECTRICAL REQUIREMENTS OF EQUIPMENT.

C. REPORT CONFLICTING CONDITIONS TO THE ARCHITECT FOR ADJUSTMENT BEFORE

PROCEEDING WITH WORK. SHOULD CONTRACTOR PROCEED WITH WORK WITHOUT

REPORTING CONFLICT(S), HE DOES SO ON HIS OWN RESPONSIBILITY, AND SHALL ALTER

WORK IF DIRECTED BY THE ARCHITECT, AT HIS OWN EXPENSE.

D. RIGHT IS RESERVED TO MAKE MINOR CHANGES IN LOCATIONS OF EQUIPMENT AND

WIRING SYSTEMS SHOWN, PROVIDING CHANGE IS ORDERED BEFORE CONDUIT RUNS

AND/OR WORK DIRECTLY CONNECTED TO SAME IS INSTALLED AND NO EXTRA MATERIALS

ARE REQUIRED.

E. DRAWINGS AND SPECIFICATIONS MAY BE SUPERSEDED BY LATER DETAIL SPECIFICATION

AND DETAIL DRAWINGS PREPARED BY THE ARCHITECT, AND THE CONTRACTOR SHALL

CONFORM TO THEM AND TO SUCH REASONABLE CHANGES IN THE CONTRACT DRAWINGS

AS MAY BE CALLED FOR BY THESE REVISED DRAWINGS WITHOUT EXTRA COST TO THE

OWNER.

F. CONTRACTOR MAY REQUEST ADDITIONAL DETAIL(S), AND SUCH SHALL BE CONFORMED

TO, WITHOUT ADDITIONAL COST. CONTRACTOR MAY OFFER ALTERNATE DETAIL(S), BUT

SUCH DETAIL(S) SHALL BE APPROVED BY ARCHITECT AND AUTHORITY HAVING

JURISDICTION

1.07 SUBMITTALS:

A. SUBMISSION REQUIREMENTS

1. CONTRACTOR IS RESPONSIBLE FOR THE SCHEDULING OF SUBMITTALS TO AVOID

DETRIMENTAL IMPACT TO THE CONSTRUCTION SCHEDULE AND TO SUPPORT THE

TIMELY SEQUENCE OF THE WORK. ALLOW A MINIMUM OF 15-WORKING DAYS FOR

SUBMITTAL REVIEW BY THE ENGINEER. COMPLEX SUBMITTALS OR SUBMITTALS

WHICH ARE NOT PROVIDED AS COMPLETE PACKAGES MAY TAKE LONGER THAN

15-WORKING DAYS FOR REVIEW. CONTRACTOR SHOULD ALLOW TIME FOR POTENTIAL

REJECTION AND RE-SUBMITTAL OF SUBMITTALS WHICH ARE BEING OFFERED AS

SUBSTITUTION TO THE SPECIFIED PRODUCTS.

2. CONTRACTOR SHALL REVIEW SUBMITTALS FOR COMPLETENESS, COORDINATION AND

CONFLICTS BETWEEN SUBCONTRACTORS AND OTHER WORK IN THE CONTRACT

DOCUMENTS. SUBMITTALS MADE BY CONTRACTOR WHICH ARE NOT THOROUGHLY

REVIEWED BY THE CONTRACTOR WILL BE RETURNED. SUBMITTALS WHICH VARY

SIGNIFICANTLY FROM THE CONTRACT DOCUMENTS AND ARE NOT SO IDENTIFIED

PRIOR TO SUBMISSION, WILL BE RETURNED TO THE CONTRACTOR WITHOUT REVIEW.

3. MAKE SUBMISSIONS WITHIN FOLLOWING NUMBER OF DAYS FROM ISSUANCE OF

NOTICE TO PROCEED OR START LETTER

a. ITEMS NEEDED IN INITIAL STAGES OF WORK OR REQUIRING LONG LEAD-TIME FOR

ORDERING: 15 CALENDAR DAYS.

b. ALL OTHER ITEMS: 21 CALENDAR DAYS.

4. BEFORE SUBMITTING A SHOP DRAWING OR ANY RELATED MATERIAL, CONTRACTOR

SHALL: REVIEW EACH SUCH SUBMISSION FOR CONFORMANCE WITH THE MEANS,

METHODS, TECHNIQUES, SEQUENCES, AND OPERATIONS OF CONSTRUCTION, AND

SAFETY PRECAUTIONS AND PROGRAMS INCIDENTAL THERETO, ALL OF WHICH ARE

THE SOLE RESPONSIBILITY OF THE CONTRACTOR; APPROVE EACH SUCH SUBMISSION

BEFORE SUBMITTING IT; AND STAMP EACH SUCH SUBMISSION BEFORE SUBMITTING IT.

ENGINEER SHALL ASSUME THAT NO SHOP DRAWING OR RELATED SUBMITTAL

COMPRISES A VARIATION UNLESS THE CONTRACTOR ADVISES THE ENGINEER

OTHERWISE VIA A WRITTEN INSTRUMENT WHICH IS ACKNOWLEDGED BY THE

ENGINEER IN WRITING.

5. ENGINEER WILL CHECK SUBMITTALS FOR CONFORMANCE WITH DESIGN CONCEPTS

OF PROJECT. APPROVAL COVERS ONLY SUCH CONFORMANCE. EFFORT WILL BE MADE

BY ENGINEER TO DISCOVER ANY ERRORS, BUT RESPONSIBILITY FOR ACCURACY AND

CORRECTNESS OF ALL SUBMITTALS SHALL BE WITH THE CONTRACTOR.

6. APPROVAL OF SUBMITTALS WILL BE ON A GENERAL BASIS ONLY AND SHALL NOT

RELIEVE THE CONTRACTOR FROM THEIR RESPONSIBILITY FOR PROPER FITTING AND

CONSTRUCTION OF THE WORK, NOR FROM FURNISHING MATERIALS AND LABOR

REQUIRED BY THE CONTRACT WHICH MAY NOT BE INDICATED ON THE SUBMITTALS

WHEN APPROVED.

7. NO PORTION OF THE WORK REQUIRING SUBMITTALS SHALL BE COMMENCED UNTIL

THE SUBMITTAL FOR THAT PORTION OF THE WORK HAS BEEN APPROVED BY

ENGINEER. ALL SUCH PORTIONS OF WORK SHALL BE IN ACCORDANCE WITH THE

APPROVED SUBMITTAL. ANY WORK PERFORMED WITHOUT APPROVED SUBMITTALS

WILL BE DONE SO AT THE CONTRACTOR'S OWN RISK. WORK FOUND NOT TO BE IN

COMPLIANCE WITH THE APPROVED SUBMITTALS SHALL BE REMOVED AND

CORRECTED AT THE CONTRACTOR'S OWN EXPENSE.

8. NUMBER OF COPIES REQUIRED - CONTRACTOR SHALL SUBMIT FOLLOWING NUMBER

OF COPIES:

a. SHOP DRAWINGS: 1-ELECTRONIC COPY IN PDF FORMAT.

b. PRODUCT DATA/MATERIAL LISTS: 1-ELECTRONIC COPY IN PDF FORMAT.

c. SAMPLES: AS SPECIFICALLY INDICATED IN PERTINENT SPECIFICATION SECTION.

d. SUBSTITUTION REQUEST: 1-COPY IN PDF FORMAT

9. SUBMITTALS SHALL INCLUDE (WHERE APPLICABLE):

a. DATE AND REVISION DATES.

b. PROJECT TITLE AND NUMBER.

c. THE NAMES OF ARCHITECT, ENGINEER, CONTRACTOR, SUBCONTRACTOR AND

SUPPLIER OR MANUFACTURER.

d. IDENTIFICATION OF PRODUCT OR MATERIAL.

e. RELATION TO ADJACENT STRUCTURE OR MATERIAL.

f. FIELD DIMENSIONS CLEARLY IDENTIFIED AS SUCH.

g. SPECIFICATION SECTION NUMBER.

h. A BLANK SPACE FOR ENGINEER'S STAMP.

i. CONTRACTOR'S STAMP ON EACH, INITIALED OR SIGNED, CERTIFYING THAT

SUBMITTAL WAS REVIEWED, FIELD MEASUREMENTS HAVE BEEN VERIFIED AND

SUBMITTAL IS IN COMPLIANCE WITH THE APPLICABLE SPECIFICATION SECTION

AND THE OVERALL CONTRACT DOCUMENTS.

10. INCOMPLETE, INACCURATE, OR NON-COMPLYING SUBMITTALS REQUIRING REVISIONS,

RE-SUBMITTAL, AND ADDITIONAL REVIEW TIME, SHALL NOT BE CONSIDERED AS A

BASIS FOR CONTRACT TIME EXTENSION.

B. REQUIRED SUBMITTALS

1. VARIOUS SPECIFICATION SECTIONS MAY STATE ADDITIONAL INFORMATION TO BE

SUBMITTED.

2. SUBMITTALS ARE REQUIRED FOR ALL MATERIALS EVEN THOUGH THE SUBMITTED

MATERIAL MAY BE EXACTLY AS SPECIFIED IN THE PROJECT MANUAL.

3. ELECTRICAL MATERIALS SUBMITTAL:

a. SUBMIT PRODUCT DATA ONLY FOR MATERIALS THAT ARE BEING SUBSTITUTED.

PRODUCT DATA IS NOT REQUIRED FOR MATERIALS THAT ARE BEING PROVIDED

AS SPECIFIED.

b. ELECTRICAL MATERIALS INCLUDE RACEWAY, BOXES, SUPPORTS, FINISH

MATERIAL, ETC.

4. ELECTRICAL EQUIPMENT SUBMITTAL:

a. SUBMIT PRODUCT DATA FOR ALL EQUIPMENT.

b. ELECTRICAL EQUIPMENT INCLUDES PANELBOARDS, SWITCHBOARDS, TRANSFORMERS, UNDERGROUND PULL BOXES, FLOOR BOXES, LIGHT FIXTURES, ETC.

5. LOW VOLTAGE AND CONTROL SYSTEMS SUBMITTALS:

a. PROVIDE PRODUCT DATA FOR EACH ITEM IN THE SYSTEM.

b. PROVIDE SHOP DRAWINGS FOR EACH SYSTEM.

c. LOW VOLTAGE AND CONTROL SYSTEMS INCLUDE LIGHTING CONTROLS, SOUND

COMMUNICATIONS, FIRE ALARM, ETC.

C. PRODUCT DATA

1. MANUFACTURER'S STANDARD SCHEMATIC DRAWINGS:

a. MODIFY DRAWINGS TO DELETE INFORMATION WHICH IS NOT APPLICABLE TO THE

PROJECT.

b. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION

WHICH IS APPLICABLE TO THE PROJECT.

2. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES,

PERFORMANCE CHARTS, ILLUSTRATIONS, AND OTHER STANDARD DESCRIPTIVE DATA.

a. CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS, OR

MODELS. MARK OUT OR REMOVE ALL EXTRANEOUS INFORMATION.

b. SHOW DIMENSIONS AND CLEARANCES REQUIRED.

c. SHOW PERFORMANCE CHARACTERISTICS AND CAPACITIES.

d. SHOW WIRING DIAGRAMS AND CONTROLS.

1.08 SYSTEM DESCRIPTION:

A. RACEWAY AND BOXES LOCATED AS INDICATED ON DRAWINGS, AND AT OTHER LOCATIONS

REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND

COMPLIANCE WITH REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN

APPROXIMATE LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE

WIRING SYSTEM.

B. CONDUCTOR SIZES ARE BASED ON COPPER UNLESS INDICATED AS ALUMINUM OR "AL".

C. WHEN ALUMINUM CONDUCTOR IS SUBSTITUTED FOR COPPER CONDUCTOR, SIZE TO

MATCH CIRCUIT REQUIREMENTS, TERMINATIONS, CONDUCTOR AMPACITY AND VOLTAGE

DROP. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING MAXIMUM NUMBER OF

ALUMINUM CONDUCTORS FOR SUBSTITUTED COPPER CONDUCTORS IN SPECIFIED

CONDUIT.

D. ALL WIRING SHALL BE INSTALLED IN RACEWAY.

E. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE GALVANIZED RIGID STEEL CONDUIT.

PROVIDE CAST METAL OUTLET, PULL, AND JUNCTION BOXES.

F. WET AND DAMP LOCATIONS: GALVANIZED RIGID STEEL CONDUIT. PROVIDE CAST METAL

OUTLET, JUNCTION, AND PULL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN

FINISHED AREAS.

G. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE

SHEET-METAL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.

PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES WHERE SHOWN ON DRAWINGS.

PROVIDE J-HOOKS WHEN SHOWN ON PLANS.

H. EXPOSED INTERIOR DRY LOCATIONS: USE RIGID STEEL CONDUIT OR INTERMEDIATE

METAL CONDUIT BELOW EIGHT FEET OR WHERE SUBJECT TO DAMAGE. USE RIGID STEEL

CONDUIT, INTERMEDIATE METAL CONDUIT, OR ELECTRICAL METALLIC TUBING ABOVE

EIGHT FEET OR IN ELECTRICAL, MECHANICAL OR TELECOMMUNICATION ROOMS. USE

SHEET-METAL OR CAST METAL BOXES. USE FLUSH MOUNTING OUTLET BOX IN FINISHED

AREAS. PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES.

I. PRODUCT REQUIREMENTS: PROVIDE PRODUCTS AS FOLLOWS:

1. STRANDED CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS.

2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS.

3. CONDUCTOR NOT SMALLER THAN 12 AWG FOR POWER AND LIGHTING CIRCUITS.

4. CONDUCTOR NOT SMALLER THAN 12 AWG FOR LINE VOLTAGE CONTROL CIRCUITS

(120-VOLT).

5. CONDUCTOR NOT SMALLER THAN 16 AWG FOR CONTROL CIRCUITS.

6. INCREASE WIRE SIZE IN BRANCH CIRCUITS TO LIMIT VOLTAGE DROP TO A MAXIMUM

OF 3 PERCENT.

7. 10 AWG CONDUCTORS FOR 20 AMPERE OR LARGER AS DESIGNATED ON PLANS FOR

120-VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 75 FEET.

J. CONDUCTOR AND CABLE APPLICATIONS:

1. DO NOT USE CONDUCTORS AND CABLES FOR APPLICATIONS OTHER THAN AS

PERMITTED BY NFPA 70 AND PRODUCT LISTING.

2. PROVIDE SINGLE CONDUCTOR BUILDING WIRE INSTALLED IN SUITABLE RACEWAY

UNLESS OTHERWISE INDICATED, PERMITTED, OR REQUIRED.

3. ARMORED CABLE IS NOT PERMITTED.

4. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE

THHN/THWN-2 INSULATION, IN RACEWAY.

5. EXPOSED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN-2

INSULATION, IN RACEWAY.

6. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN/THWN-2

INSULATION, IN RACEWAY.

7. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN-2

INSULATION, IN RACEWAY.

8. EXTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE XHHW-2 INSULATION, IN

RACEWAY.

9. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE, TYPE XHHW-2 INSULATION, IN

RACEWAY.

K. WIRING DEVICE APPLICATIONS:

1. PROVIDE WIRING DEVICES SUITABLE FOR INTENDED USE AND WITH RATINGS

ADEQUATE FOR LOAD SERVED.

1.09 DEMOLITION:

A. REMOVAL OF EXISTING ELECTRICAL EQUIPMENT, WIRING, AND CONDUIT IN AREAS TO BE

REMODELED; REMOVAL OF DESIGNATED CONSTRUCTION; DISMANTLING, CUTTING AND

ALTERATIONS FOR COMPLETION OF THE WORK.

1. PROTECT ITEMS TO REMAIN.

2. RELOCATE EXISTING EQUIPMENT TO ACCOMMODATE CONSTRUCTION.

3. CONDUCT DEMOLITION TO MINIMIZE INTERFERENCE WITH ADJACENT AND OCCUPIED

BUILDING AREAS.

4. COORDINATE DEMOLITION WORK WITH OWNER'S REPRESENTATIVE AND ALL OTHER

DISCIPLINES.

5. COORDINATE AND SEQUENCE DEMOLITION SO AS NOT TO CAUSE SHUTDOWN OF

OPERATION OF SURROUNDING AREAS.

6. SHUT-DOWN PERIODS:

a. ARRANGE TIMING OF SHUT-DOWN PERIODS OF IN-SERVICE PANELS WITH

OWNER'S REPRESENTATIVE. DO NOT SHUT DOWN ANY UTILITY WITHOUT PRIOR

WRITTEN APPROVAL AND SUBMITTING A “METHOD OF PROCEDURE” FOR REVIEW

b. KEEP SHUT-DOWN PERIOD TO MINIMUM OR USE INTERMITTENT PERIOD AS

DIRECTED BY OWNER'S REPRESENTATIVE.

c. MAINTAIN LIFE-SAFETY SYSTEMS IN FULL OPERATION IN OCCUPIED FACILITIES OR

PROVIDE NOTICE MINIMUM 72 HOURS IN ADVANCE AND FIRE WATCH.

7. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER.

1.10 DRAWINGS AND COORDINATION WITH OTHER WORK:

A. DRAWINGS:

1. FOR PURPOSES OF CLARITY AND LEGIBILITY, DRAWINGS ARE ESSENTIALLY

DIAGRAMMATIC TO THE EXTENT THAT MANY OFFSETS, BENDS, SPECIAL FITTINGS,

AND THE EXACT LOCATIONS OF ITEMS ARE NOT SHOWN, UNLESS SPECIFICALLY

DIMENSIONED.

2. EXACT ROUTING OF WIRING AND LOCATIONS OF OUTLETS, PANELS, AND OTHER

ITEMS, SHALL BE GOVERNED BY STRUCTURAL CONDITIONS, AND MATERIALS AND

EQUIPMENT ALREADY IN PLACE. USE DATA IN THE CONTRACT DOCUMENTS. IN

ADDITION, THE ARCHITECT RESERVES THE RIGHT, AT NO INCREASE IN CONTRACT

SUM, TO MAKE ANY REASONABLE CHANGE IN LOCATIONS OF EXPOSED ELECTRICAL

ITEMS, TO GROUP THEM INTO ORDERLY RELATIONSHIP AND/OR INCREASE THEIR

UTILITY. VERIFY THE ARCHITECT'S REQUIREMENTS IN THIS REGARD PRIOR TO

ROUGHING-IN.

3. DIMENSIONS, LOCATIONS OF DOORS, PARTITIONS AND SIMILAR PHYSICAL…

This is the start of the file's text. The full file is on GovTribe.